L o a d resistances and deformation values of components and kits used in this software are resulting from ETAs which are summarized in
"ETA_Modular_support_system_V1.2_en, English".
Th e d e sign methodology of kits and the deflection values of channels with discret loading conditions have been determined in accordance with EAD 280016-00-0602.
W h e n p l a s tic hinges occur a rope shape following a kinematic chain approach is derived to get a new equilibrium under large deformations.
Th e c a l culations determine the final z-ordinate of the lowest point of the system in deformed state after loading under fire conditions. It is the responsibility of the design
e n gineer to assess whether or not other building components, such as fire rated ceiling, could be negatively impacted.
The design must be checked for plausibility before assembly and installation.
The construction overall displacement was not checked against available space due to the respective option was disabled. Make sure the parameter is controlled separately by
the responsible engineer, if needed.
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan
Hilti Aktiengesellschaft | Feldkircherstrasse 100 | Postfach 333 | 9494 Schaan
Phone: | Fax: | E-Mail: Hilti PROFIS Installation 2.26.0
Cu. no./ Company: / Page: 2 of 11
Contact: Project: 21-120-CT Fire Rated
Address: , Subproject: CT 750mm_Fire
Phone Mobile/Office: / Hilti TB/VB:
E-Mail: Date: 7/6/2021
Calculation factors:
Design basis: EAD 280016-00-0602
Load combination design basis: Eurocode 1990
L1 Dead load
L2 Live load
Load combinations:
ULS
LC1-ULS-Fire = 1.00 * L1 + 1.00 * L2
The space evaluation can be of utmost importance in Fire Safety Design. It must be assured that the aggregate
deflection of all components do not negatively impact any other building component, especially fire-rated ceilings
positioned directly below the modular support system.
Please note that the calculations provided do not consider the deflection of any attached components such as pipes, air
ducts or cables trays between the modular support system. This must be checked in addition and added to values
provided in this report.
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan
Hilti Aktiengesellschaft | Feldkircherstrasse 100 | Postfach 333 | 9494 Schaan
Phone: | Fax: | E-Mail: Hilti PROFIS Installation 2.26.0
Cu. no./ Company: / Page: 3 of 11
Contact: Project: 21-120-CT Fire Rated
Address: , Subproject: CT 750mm_Fire
Phone Mobile/Office: / Hilti TB/VB:
E-Mail: Date: 7/6/2021
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan
Hilti Aktiengesellschaft | Feldkircherstrasse 100 | Postfach 333 | 9494 Schaan
Phone: | Fax: | E-Mail: Hilti PROFIS Installation 2.26.0
Cu. no./ Company: / Page: 4 of 11
Contact: Project: 21-120-CT Fire Rated
Address: , Subproject: CT 750mm_Fire
Phone Mobile/Office: / Hilti TB/VB:
E-Mail: Date: 7/6/2021
Parts List:
lblU3DField
Channels
Pos Qty Description Item Weight [kg] Length [m] Beam No.
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan
Hilti Aktiengesellschaft | Feldkircherstrasse 100 | Postfach 333 | 9494 Schaan
Phone: | Fax: | E-Mail: Hilti PROFIS Installation 2.26.0
Cu. no./ Company: / Page: 5 of 11
Contact: Project: 21-120-CT Fire Rated
Address: , Subproject: CT 750mm_Fire
Phone Mobile/Office: / Hilti TB/VB:
E-Mail: Date: 7/6/2021
Pos Qty Description Item Weight [kg] Length [m] Beam No.
Structure connections
Connections
Accessories
Beam No. 2
lblHorizontalEndToEnd3 lblVerticalEndToEnd3
lblHorizontalAxial3 lblVerticalAxial3
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan
Hilti Aktiengesellschaft | Feldkircherstrasse 100 | Postfach 333 | 9494 Schaan
Phone: | Fax: | E-Mail: Hilti PROFIS Installation 2.26.0
Cu. no./ Company: / Page: 6 of 11
Contact: Project: 21-120-CT Fire Rated
Address: , Subproject: CT 750mm_Fire
Phone Mobile/Office: / Hilti TB/VB:
E-Mail: Date: 7/6/2021
Static model:
imgStaticModel
Nodes
Node Position [m]
Hinged axis Base plate Building material
No. X Y Z
Beams
Beam Length Rotation A Iy Iz E
Channel
No. [m] [º] [mm²] [cm^4] [cm^4] [N/mm²]
1 AM10x1000 4.8 1.0000 0 52.30 0.02 0.02 210,000
2 MQ-41 3m 0.8500 180 264.92 5.78 7.68 210,000
3 AM10x1000 4.8 1.0000 0 52.30 0.02 0.02 210,000
A = Cross section area, Iy Iz = Moment of inertia, E = Modulus of elasticity (data used for calculation of cold state)
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan
Hilti Aktiengesellschaft | Feldkircherstrasse 100 | Postfach 333 | 9494 Schaan
Phone: | Fax: | E-Mail: Hilti PROFIS Installation 2.26.0
Cu. no./ Company: / Page: 7 of 11
Contact: Project: 21-120-CT Fire Rated
Address: , Subproject: CT 750mm_Fire
Phone Mobile/Office: / Hilti TB/VB:
E-Mail: Date: 7/6/2021
Fire Rating
fp_θ [MPa] fy_θ [MPa] Ea_θ [MPa] εp_θ εy_θ εt_θ a b c
[min]
120 6.04 9.664 7134.75 0.000846561 0.02 0.15 0.01916055 3.72548891 0.10148891
Distributed loads
Load Beam Position Width Forces [kN/m]
Load type
No. No. [m] [m] X Y Z
1 Dead load 2 0.0500 0.7500 0.0000 0.0000 1.1333
Load description
No. Type Description Size [m] Spacing [m]
1 Custom load
object
Calculation summary
imgSummary
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan
Hilti Aktiengesellschaft | Feldkircherstrasse 100 | Postfach 333 | 9494 Schaan
Phone: | Fax: | E-Mail: Hilti PROFIS Installation 2.26.0
Cu. no./ Company: / Page: 8 of 11
Contact: Project: 21-120-CT Fire Rated
Address: , Subproject: CT 750mm_Fire
Phone Mobile/Office: / Hilti TB/VB:
E-Mail: Date: 7/6/2021
Supports
Support loading definition
Bending theory
Kinematic Chain
Node 1
Node 4
Note: The values refer to the resistance of the support inclusive of all elements
Support Verification
1 HKD M10x40 (C_R) 0.4370 0.1317 0.0000 0.0000 0.0000 0.0000 30.43
4 HKD M10x40 (C_R) 0.4370 -0.1317 0.0000 0.0000 0.0000 0.0000 30.43
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan
Hilti Aktiengesellschaft | Feldkircherstrasse 100 | Postfach 333 | 9494 Schaan
Phone: | Fax: | E-Mail: Hilti PROFIS Installation 2.26.0
Cu. no./ Company: / Page: 9 of 11
Contact: Project: 21-120-CT Fire Rated
Address: , Subproject: CT 750mm_Fire
Phone Mobile/Office: / Hilti TB/VB:
E-Mail: Date: 7/6/2021
Connections
Connection loading definition
Bending theory
Kinematic Chain
Node 2
Node 3
Connection Verification
2 MQZ-L11 (C_D) 0.4564 0.0000 0.0000 0.0000 0.0000 0.0000 67.22 Kinematic Chain
3 MQZ-L11 (C_D) 0.4564 0.0000 0.0000 0.0000 0.0000 0.0000 67.22 Kinematic Chain
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan
Hilti Aktiengesellschaft | Feldkircherstrasse 100 | Postfach 333 | 9494 Schaan
Phone: | Fax: | E-Mail: Hilti PROFIS Installation 2.26.0
Cu. no./ Company: / Page: 10 of 11
Contact: Project: 21-120-CT Fire Rated
Address: , Subproject: CT 750mm_Fire
Phone Mobile/Office: / Hilti TB/VB:
E-Mail: Date: 7/6/2021
Suspension rods
Suspension rod loading definition
Bending theory
Kinematic Chain
Beam 3
Beam 1
3 AM10x1000 4.8 0.4564 0.0000 0.0000 0.0000 0.0000 0.0000 96.90 Kinematic Chain
1 AM10x1000 4.8 0.4564 0.0000 0.0000 0.0000 0.0000 0.0000 96.90 Kinematic Chain
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan
Hilti Aktiengesellschaft | Feldkircherstrasse 100 | Postfach 333 | 9494 Schaan
Phone: | Fax: | E-Mail: Hilti PROFIS Installation 2.26.0
Cu. no./ Company: / Page: 11 of 11
Contact: Project: 21-120-CT Fire Rated
Address: , Subproject: CT 750mm_Fire
Phone Mobile/Office: / Hilti TB/VB:
E-Mail: Date: 7/6/2021
Beams
Support loading definition
Bending theory
Kinematic Chain
Beam Details
Max Moment and stress are valid for bending theory only.
Deflection Verification
Beam End Beam Pipe Ring T-rod Pipe Ring Total Deflection Z-Ceiling Z-Available
Position [m] Status
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
Max. Beam
0.0 391.3 N/A 0.0 391.3 1,412.0
Deflection
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan
Hilti Aktiengesellschaft | Feldkircherstrasse 100 | Postfach 333 | 9494 Schaan
Phone: | Fax: | E-Mail: Hilti PROFIS Installation 2.26.0
Cu. no./ Company: / Page: 12 of 11
Contact: Project: 21-120-CT Fire Rated
Address: , Subproject: CT 750mm_Fire
Phone Mobile/Office: / Hilti TB/VB:
E-Mail: Date: 7/6/2021
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must
arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti
on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current
and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be
liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by
you.
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan