33.

051/1

DSU: Pressure transducer


How energy efficiency is improved
Simplest conversion of pressures into proportional standard signal.
Areas of application
For measuring pressures in liquids, gases and vapours. Non-wearing measurement procedure by
means of contact-free inductive signal conversion.
Features
• Pressure range: 0 to 25 bar
• Standard signal 0(2) to 10 V or 0(4) to 20 mA.
• Up to 110 °C and up to 40 bar maximum sensor values
• 24 V~/=, ± 20% supply voltage
Technical description P
• Light-alloy housing with transparent cover made of impact-resistant thermoplastic
• Ambient temperature: -20 to +70 °C
• IP65
Y05043
• Standard housing-mounted plug with cable connector for cables from 6 to 10 mm in diameter
• Pressure connection G½"A
• Extensive range of accessories 10 V Output signal 20 mA

Type Measuring range Max. sensor values Weight


bar bar °C kg
Brass pressure sensor for non-aggressive media
DSU 101 F001 0...1,0 1.5 70 0,6
DSU 103 F001 0...2,5 4 70 0,6 2 4
DSU 106 F001 0...6,0 10 70 0,6
0 0
DSU 110 F001 0...10 16 70 0,6 0 Measuring range 100 %
DSU 116 F001 0...16 25 70 0,6 B05044

DSU 125 F001 0...25 40 70 0,6


Stainless-steel pressure sensor for aggressive media
DSU 201 F001 0...1,0 1.5 110 0,6
DSU 203 F001 0...2,5 4 110 0,6
DSU 206 F001 0...6,0 10 110 0,6
DSU 210 F001 0...10 16 110 0,6
DSU 216 F001 0...16 25 110 0,6
DSU 225 F001 0...25 40 110 0,6

Power supply 24 V ~/= ± 20%, 50...60 Hz Perm. ambient temp. –20...70 °C


Power consumption approx. 1 VA Degree of protection IP 65 (EN 60529)
Output signal 1) 0...10 V, load > 500 Ω Protection class III (EN 61140)
switchable to 2...10 V, load > 500 Ω
Linearity approx. 1% Wiring diagram A05045
Hysteresis approx. 1% Dimension drawing M05046
Temperature coefficient ~0.03%/K Fitting instructions MV 505364
Permissible vacuum loading –1,0 bar
Type 101; 103; 106 –0,7 bar
Type 201; 203; 206 –0,7 bar

Accessories
0035465 000 Brass throttle screw for damping pressure surges
0214120 000 Stainless-steel throttle screw for damping pressure surges
0192700 000* 1 m of copper capillary tubing for damping pressure surges
0114467 000* 1 m of stainless-steel capillary tubing for damping pressure surges
0192222 000* Cap nut with solder connector
0311572 000* Brass screw fitting for copper tubing of Ø 6 mm
0259239 000* Brass reduction piece G½ onto 7½ " 20 UNF-2A for copper tubing of Ø 6 mm
0259983 000* Fixing bracket for rail mounting: C-rail EN-50022-C20 and C30
0296936 000* Fixing bracket for rail: top-hat rail EN 60715, 35 × 7,5 or 35 × 15
0259984 000* Bracket for 3-point fixing
0292018 001* Damping screw for damping pressure surges in low-viscosity media
*) Dimension drawing or wiring diagram are available under the same number

1) At a load of < 500 Ω, the transducer switches automatically to 0...20 mA (or 4...20 mA).
Factory setting is 0...10 V. Output is protected against short circuits and over-voltage up to 24 V~.

Sauter Components 7133051003 04


33.051/2 DSU

Operation
The pressure in the sensor acts on a bourdon tube, thereby producing a force on the conversion
spring. The resultant movement is converted into a standard electrical signal by an inductive distance
sensor. The output signal rises in proportion to the pressure.
Additional details
Materials which come into contact with the medium are:
brass, stainless steel and the seal's nitrile rubber (on the brass pressure sensor);
stainless steel (on the stainless-steel sensor) material no. 1.4104 and 1.4541.
To protect the DSU with a fuse, a fuse of at least 250 mA/250 V should be used.
Additional technical data
Complies with:-
EMC directive 2004/108/EC EN 61000-6-1/ EN 61000-6-2
EN 61000-6-3/ EN 61000-6-4
Covered by Art. 3.3. of the PED without safety function

Wiring diagram

Auto U/I

0/2...10 V
0/4...20 mA
1 2 3

24 V~/=
A05045b
xi

Dimension drawing

45
80 50 25
3

61
67

a
10

Pg11

Ø4,5 67
s
6 28
G1/2A
Type a s
DSU 101...103 131 36
DSU 106...125 146 27
DSU 201...210 131 36
DSU 216...225 109 22
M05046

Sauter Components 7133051003 04


DSU 33.051/3

Accessories
114467 192222 311572
192700 G1/2 G1/2 25,5

s27 8
s22

Ø6

G1/2
42,5

Ø26
1000

NW 1.0 (192700)
NW 1.5 (114467) s27
M00777

Ø 12
M00317a
R1/2 M00316a

259239 259983 296936


80 25
G1/2 5 4,5
67
4,5
38

30

32
40
18
13
s27
25

4,5
7/16"
20-UNF-2A M00653
12
M00315

0,
5
13
18 M00166

259984 292018
20
1,5
M4

4,5
Ø1,58
Ø0,38

4,5 7,5 s5
M3×6
11
25

37

25
10

M04566

9 3,5
58
M00654

Printed in Switzerland
Right of amendment reserved
N.B.: A comma between cardinal
numbers denotes a decimal point
© Fr. Sauter AG, CH-4016 Basle
Sauter Components 7133051003 04