You are on page 1of 2

Amps X 1000 Bus1 (Nom. kV=11, Plot Ref.

kV=11)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

Relay2 - P - 51
500 500
OC2
Relay2 - P - 50
ABB
300 OC2 300
REF 615
ABB CT Ratio 800:1
REF 615 Group 1
CT Ratio 800:1 IEC Normal Inverse
100 Group 1 Pickup = 2 (0.05 - 5 xCT Sec)
100
Inst = 11.55 (1 - 40 xCT Sec) Time Dial = 2.5
Time Delay = 0.15 s 3x = 15.8 s, 5x = 10.7 s, 8x = 8.24 s
50 50

30 Relay2 - P - 51 30

OC1
ABB
REF 615
10 CT Ratio 800:1 10
Group 1
IEC Normal Inverse
5 5
Seconds

Pickup = 1.43 (0.05 - 5 xCT Sec)


Time Dial = 2.05
3 3
3x = 12.9 s, 5x = 8.77 s, 8x = 6.76 s

1 Relay2 - P - 50 1
OC1
ABB
.5 .5
REF 615
CT Ratio 800:1
.3 .3
Group 1
Inst = 7.68 (1 - 40 xCT Sec)
Time Delay = 0.1 s
BHEL_MTR1-100%
.1 ±
.1

R
.05 .05
Relay2
.03 .03

.01 .01
.5BHEL_MTR1
1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
10000 kW
Amps X 1000 Bus1 (Nom. kV=11, Plot Ref. kV=11) ETAP Star 19.0.1C

Project: Rev: Base


Engineer: Fault: Phase