MAJOR SIM REFERENCE PRODUCT AREA DETAILS


8.00 0 183062,1-1478283501 LD PC DRIVERS VersaMax Current Fault Table was sometimes autocleared. Discrete non-intelligent Versamax modules such as MDL750
autocleared the faults when the field power was restored and the modules were back in the OK state.
8.00 0 184330,1-2575586383 LD PC DRIVERS Mistake in "Installing the device driver for a PCI device (card)" help topic. The topic said that this procedure applied to Windows
XP only, but it applies also to Windows 7. The restriction "Windows XP only" has been removed from the topic.

8.00 0 183964,183769,1- LD PC LOGIC ASCII driver timeouts occurred in Windows 7 x64 whereas they did not in Windows XP.
1802003291,1-1682685497
This was caused by timing differences in the operating system COM interfaces. Solution: Tweak the Timeout values for MSGRX
and/or MSGTX CFBs. For more information: On the Help menu, click Search. In the Search window that appears, search for
"Tips on setting MSGTX and MSGRX timeouts" (USE THE QUOTATION MARKS).
8.00 0 183749,1-1637788534,1- LD PC WEBVIEW Web views did not support the STEP data type in SFCs.
1628709051
8.00 0 184239,183152,1- LD PLC CBLOCKS Logic download did not work if C block had BOOL and User-defined Data Type input parameters
2567841047,1-1495446697
8.00 0 184430,1-2738316168 LD PLC DATA MONITORING Logic Developer became unresponsive when closing a project while online to a Controller and Data Monitor was running with
live variable data
8.00 0 184180,1-2521785578 LD PLC DOWNLOAD Unexpected Error (VersaProDocument) terminated a download
8.00 0 184300,1-1675854491 LD PLC DOWNLOAD Fault, "Unable to deliver configuration to module", logged against IC695PMM335. This occurred when the PMM335 module had
its Number of Axes parameter set to 0.
8.00 0 184247,1-2572986101 LD PLC EDITORS Unwanted CALL instruction added in FBD editor during validation
8.00 0 184287,1-2595633731 LD PLC EDITORS Adding or editing members of a block resulted in errors on pre-existing members. Wire elements of an FBD block were
corrupted when duplicating a parameter of that FBD block.
8.00 0 184223,1-2553188581 LD PLC EGD EGD report did not generate
8.00 0 184155,1-2500347460 LD PLC FUNCTION BLOCKS Search for reference address was not finding the occurrences in FBD blocks
8.00 0 184031,1-1721529541 LD PLC GENERAL Opening a project after disabling the telephony service caused Logic Developer to stop responding
8.00 0 184291,1-2595788243 LD PLC GENERAL Logic Developer stopped responding after opening a project. This occurred after opening a project, importing a Toolchest
drawer, and clicking any Logic Developer project node in the Navigator.
8.00 0 184192,1-2528725931 LD PLC IMPORT Logic Developer stopped responding when trying to import a block that calls a non-existing C block
8.00 0 184230,1-2483502448 LD PLC IMPORT Logic Developer closed abruptly when importing a CC90 project
8.00 0 184447 LD PLC IMPORT VersaSafe block import error not properly described in Feedback Zone message
8.00 0 183951,1-1736028971 LD PLC LOGIC Uploading logic from Controller corrupted parameterized block parameters. I/O address of a variable aliased to a variable
used in a parameterized block was incremented after an upload from the Controller.
8.00 0 184037,1-1559708981 LD PLC LOGIC User-defined Data Type (UDT) I/O variable used as an input element to a block caused unexpected results
Solution: I/O variables of a UDT are not supported as input elements of a block of logic. Error 12707 occurs at validation.

8.00 0 184151,1-2495047132 LD PLC LOGIC Unable to use indirect address on Q output of move_to_flat instruction. Fixed for both MOVE_TO_FLAT (in LD, FBD, and ST) and
MOVE_FROM_FLAT (supported only in LD).
8.00 0 184166,1-2518946179 LD PLC LOGIC After setting a member variable's data type to MC_JerkUnits and closing and re-opening the Parameters dialog box, the data
type of this UDFB member variable was set to None.
8.00 0 184266,1-2594831334 LD PLC LOGIC In the ST language, the IN operand of ARRAY_SIZE, ARRAY_SIZE_DIM1, and ARRAY_SIZE_DIM2 did not support BYTE arrays in
non-discrete memory
8.00 0 184281,1-2595634031 LD PLC LOGIC After importing one island, an ST block was created. When instantiating the safety logic block, about 42,000 instance variable
elements were created for one island's inputs, outputs, and members. Configuring more than 5 islands caused the variable
count to exceed the highly recommended maximum of 250,000 variables supported per project, which prevented a download
to the Controller.

Validation Error 12708 appears with instructions on how to upgrade the existing VersaSafe project.
8.00 0 184361,1-2649947631 LD PLC LOGIC User-defined Data Types linked to the same fxClass in the Toolchest contained different element names
8.00 0 183266,1-1536085574 LD PLC ONLINE Descriptions on array elements of UDFB member variables were displayed incorrectly in the LD editor. This occurred when a
User-Defined Function Block (UDFB) had an array as an input variable, the array head had a description, and each element
had a description. When online monitoring an element of that array in an instance variable of that UDFB, the LD editor did not
display the element's description; it displayed the array head's description.
8.00 0 184027,1-1808881431 LD PLC ONLINE Incorrect instance variable indication when function block parameter was negated. This occurred in LD, FBD, and ST function
block instance variables when a function block parameter was negated.
8.00 0 184483,1-2751814081 LD PLC PROFINET Moving PROFINET module in module list added incorrect, unnecessary references in Feedback Zone
8.00 0 184431,1-2727262127 LD PLC REDUNDANCY Restoring a CPU redundancy project and going online sometimes caused Config to become Not Equal in the status bar

8.00 0 184028,1-1848481762 LD PLC REPORTING Saving fault table produced invalid XML file. This occurred when a fault table with XML entity references was saved and
opened.
8.00 0 184205,1-2533650821 LD PLC UDT Slow to open User-defined Data Type (UDT) editor for UDT containing over 1600 parent elements
8.00 0 184326,184226,1- LD PLC UPLOAD Variable count was increasing on target upload operation
2646259281,1-2534824949,1-
2698014111
8.00 0 183836,1-1528167481 LD PLC UTILITIES Set Temporary IP Utility caused IP Address to be cached in the ARP table after Windows 7 or Windows XP reboot. Solution: The
Set Temporary IP Utility dialog box now has a Clear Cache button. Clicking it clears the cached IP address.

8.00 0 184248,1-2572986145 LD PLC VALIDATION Validation produced annoying message boxes that required to click OK. The errors now appear in the Feedback Zone and do
not require clicking OK. The Symbolic processing error is now Error 12721, which specifies the affected block of logic and the
affected parameter.
8.00 0 183343,1-1547184991 LD PLC VARIABLES When a UDT was configured as a parameter of an LD block and any UDT member was used in the LD editor of the same block,
a change in the UDT element name was not reflected in the LD editor until after the project was closed and reopened.

8.00 0 183346,1-1547196681 LD PLC VARIABLES Publish column in the Variable report showed an "x" mark although the variable was published
8.00 0 183631,1-1603594851 LD PLC VARIABLES Changing User-defined Data Type array size after validation caused element descriptions to be lost
8.00 0 184131,1-1669905311 LD PLC VARIABLES Unable to delete variables in a project that had duplicate reference addresses. This occurred when the variables were mapped
to system variable reference addresses in %S or %SA memory.
8.00 0 183206,1-1536038373 PME PROPERTY INSPECTOR Color property drop-down boxes partially hid elliptical custom color buttons
8.00 0 184268,1-2565698471 VIEW DRIVERS When configuring the "Custom Macro value" addresses for the View OPC - GE Focas Ethernet driver, the address always
became invalid. On Windows 7, that configuration sometimes caused the software to close abruptly.
8.00 0 183137,1-1526726211 VIEW GRAPHICAL PANEL After converting a QuickPanel target to a QuickPanel View/Control target, the image resolution of a bitmap image object set in
the View Developer Panel editor was not retained in View Runtime
8.00 0 184231,1-2549819775 VIEW RUNTIME QuickPanel View/Control (QPV/C) security settings were not saved when rebooting QPV/C unit
8.00 0 184518,1-2752249388 VIEW RUNTIME View Runtime stopped responding when another View Runtime connected to it through View Networking
8.00 0 184402,1-2568825495 VIEW SCRIPTING Tags with periods in the tagname were not working in View VB Script editor
8.00 0 184254,1-2577118671 VIEW VARIABLES Proxy variables not getting added on dragging Logic Developer variables to View target
8.00 0 183405,1-1559823551 VIEW WEBVIEW Screen did not always automatically refresh when navigating from one panel to another in web views
8.00 1 184688,184644,1- LD PLC EDITORS Variable description was not visible in LD editor
2906639206,1-2866719161,1-
2871716366,1-2885232628

8.00 1 184404,1-2632639431 LD PLC EGD Saving project with Series 90-30 target showed Error 12245 in Messages tab of Feedback Zone
8.00 1 184620,1-2808459171 LD PLC EGD EGD variables were deleted when building EGD exchanges
8.00 1 184610,1-2731406439 LD PLC FUNCTION BLOCKS Validation Error 9682 unexpectedly occurred while accessing read-only UDFB member
8.00 1 184616,1-2806303801 LD PLC PROFINET Could not configure a third-party S7-300 PROFINET device when using its GSDML 2.25 file. The 192-byte area for mapping the
module data to PACSystems RX3i memory was not displayed.
8.00 1 184598,1-2803302082 LD PLC REPORTING Hardware Configuration report did not list any modules when PROFINET I/O modules are configured
8.00 1 184639,1-2867733104 LD PLC REPORTING Hardware Configuration report listed an unknown part number, IC200RAC001
8.00 1 184621,1-2843053001 LD PLC RVTs Entering "1p" in the Address cell at the right end of a row in a Reference View Table (RVT) caused the software to close abruptly

8.00 1 184478,1-2745079151 LD PLC UDT Variable index on UDT array in UDFB block caused validation Error 9618
8.00 1 184380,1-2468145271,1- LD PLC VALIDATION No error displayed for invalid TSL parameter value in Network Settings dialog box of PBM300
2680909070
8.00 1 184625,1-2849606076 LD PLC VALIDATION Unexpected validation errors regarding CPU memory areas when using the French Language Pack

© 2017, General Electric Company https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 12/11/2017


Fixed Issues Page 2 of 9

8.00 1 TFS15182-1,TFS15182-1 PME PROPERTY INSPECTOR (32-bit Windows 7.) Opening the property column display in very specific scenario displayed no columns
The issue occurred after the following sequence of operations:
1. Creating a project and, in the Project Template field, selecting Empty Project.
2. Adding a target.
3. On the Variables tab of the Navigator, clicking the leftmost icon to open the property column display.
8.00 1 184653,1-2891922047,1- VIEW GRAPHICAL PANEL Undo operation in Graphical Panel was not working
2883041381
8.00 1 184659,1-2856974970 VIEW GRAPHICAL PANEL Change to View panel was not reflecting in Runtime
8.00 1 184617,1-2825603343 VIEW VALIDATION Validation did not issue errors when GOTO buttons pointed to deleted panels
8.00 2 184692,1-2919593431 LD PLC CONVERSION Target conversion from PACSystems RXi to PACSystems RX3i produced errors. This occurred when the references of used
system variables were not displayed in the Feedback Zone across the target conversion.
8.00 2 184237,1-2555748671 LD PLC DEVICENET Series 90-30 target configured with a DeviceNet slave was losing config equality on project reopen
8.00 2 184796,1-3068128418 LD PLC DEVICENET Series 90-30 HWC upload with DNS downloaded from older version caused software to close abruptly
8.00 2 184391,1-2707112120,1- LD PLC DOWNLOAD The software closed abruptly after consecutive downloads.
2609960771
8.00 2 184638,1-2854529821 LD PLC EGD Word-for-Word change caused HWC to become Not Equal (HWC became Not Equal while building EGD exchanges.)

8.00 2 184629,1-2830675121 LD PLC LOGIC References tab in Feedback Zone did not display variable references after upload. This occurred with variables used in LD logic
until an operation like Search or opening a block was performed.
8.00 2 184732,1-2951495009 LD PLC LOGIC Software closed abruptly while opening logic block when online and logic equal. This occurred when opening logic that had
references to an array variable with a variable index.
8.00 2 184753,1-3012833741 LD PLC LOGIC References tab in Feedback Zone did not display variable references after importing LD or FBD block
8.00 2 184511,1-2753868631,1- LD PLC UDT The number of UDT variables was not counted correctly
2772326381
8.00 2 184718,1-2960297837 LD PLC UDT Adding a variable to any other page in the UDT editor caused an internal error to occur and the software to close abruptly.

8.00 2 184656,1-2841992530 LD PLC UPLOAD Invalid variable name after uploading Series 90-30 logic then closing and reopening project
8.00 2 184327,1-2606856171 LD PLC VARIABLES Function block count sometimes increased after downloads, uploads, and validation
8.00 2 184383,1-2638517936 VIEW ALARMS Navigating between panels caused the Operator column in the Alarm window to lose its contents. This occurred both on
QuickPanel View/Control units and in simulation mode.
8.00 2 184711,1-2927835705 VIEW DRIVERS OPC integrated driver runtime had a 2-hour demo timeout even when View was licensed
8.00 2 184417,1-2726999951 VIEW WEBVIEW Rotation animation was not working correctly in web views for line object
8.00 3 184680,1-2891922001 LD PLC VALIDATION Error 12560: Duplicate Cam Profile Variable Reference. These false errors appeared on first target validate after Word-for-
Word operation.
8.00 3 184847,1-3134689081 LD PLC VALIDATION Error 8019: Ladder element does not have valid associated variable. These false errors appeared when locally scoped
variables had local alias.
8.00 3 184761 PCM AUDIT TRAILS Opening the Audit Trial Report Manager generated the message "Unrecognized database format '...\AUDIT.MDB'
This fix affects only users whose Audit database is set up to use the Microsoft Access type (.mdb).

For the fix to work properly after installing this SIM, do as follows:
1. Move your Microsoft Access database to a different location.
2. Restart the Proficy Change Management Server.
Result: a new Microsoft Access Database will be recreated with the correct database format.

To view the old Microsoft Access Database, you need to use outside software -- not the Audit Trail Report Manager.
8.00 3 184739 PCM GENERAL Change Management Client API 8.0 did not function properly with Cimplicity 9.0
8.00 3 184752 PCM SERVER Configuring Access DB for Audit DB generated "ERROR - Audit DB Path contains Invalid Character!" on 64-bit O/S
8.00 3 184816,1-3106487954 PME HELP One EMEA and one APO phone numbers were incorrect on the Contact Us help page
8.00 3 184749,184763,184787,18484 PME TOOLCHEST Drawing objects could not be merged properly into the Toolchest
9,1-2969829902,1-
2960297761,1-3060343391,1-
3139040821,1-3178474155,1-
3189664301

8.00 3 184789,1-3051101647 VIEW COLLECTORS View Data Collector and Historian 5.0: Unsolicited Collection Interval did not work
8.00 4 184622,1-2790737911 PCM GENERAL User licenses leaked when scheduled PrePAC compares ran continuously
8.00 4 184819,1-3090979851,1- PME LICENSING Unable to transfer software license in some cases
3131130731,1-3131401810,1-
3202259285,1-2899030697

8.00 7 184954,1-3500998497 LD PC RUNTIME PID instruction was not suppored in QP+


8.00 8 184979,1-3626203515 LD PC RETENTIVE DATA Retentive data was limited to 27000 bytes on a QuickPanel+
8.00 8 184943,184945,1- LD PLC FUNCTION BLOCKS Logic Execution Problem with UDFB call
3341036311,1-3363928358
8.00 8 184973,1-3548527273 LD PLC FUNCTION BLOCKS Adding to structure did not update existing variables
8.00 8 184939,1-3473023698 VIEW ALARMS Secondary alarms in the mirror not being displayed
8.00 9 185036,1-3825316691,1- VIEW RUNTIME GE SRTP driver Communication with PLC failed for string and LREAL with suffix tag in QuickPanel+
3723191331
8.00 9 185055,1-3790299334 VIEW RUNTIME The assignment to a :HIGH or :LOWLIMIT of an indirect variable, the value of that variable can not be written to
8.00 10 185044,1-3845856312,1- VIEW DOWNLOAD QP+ target download to local media aborted abruptly with error 2394 when HMI Publish property was turned on in target
4092868551 properties.
8.00 10 KEP54305,1-3909015621 VIEW RUNTIME Upgraded to new ProficyViewIntegratedOPCDriver install(5.12.162.0) to address failed reads issue with GE Ethernet View OPC
Driver
8.00 11 185100,00192843 LD PC FUNCTION BLOCKS ME crash on attempt to open UDFB FBD logic block
8.00 11 184972,00189048&00193825 LD PC RMS QuickPanel+ download error, unable to perform Run Mode Store to Controller

8.50 0 184637,1-2841343199 LD PLC EQUALITY Compare report and other display issues when using "LM90" colors
8.50 0 184813,1-3095980561 LD PLC HELP Error 8053 description was not updated with IC695CRU320
8.50 0 DE990 LD PLC HELP Math instruction overflows help not properly documented, In the F1 help of every LD math instruction, the overflow help was
not sufficiently detailed. In each case, it was replaced with a link to a detailed explanation.
8.50 0 184883,1-3190029707 LD PLC VALIDATION The software closed abruptly when validating a Logic Developer target. This occurred when a BOOL operand like a NOCON
was assigned to a UDFB instance operand like INPUT_REF.
Solution: Validation now catches such logic as an error, which prevents downloading.
8.50 0 184876,1-3073293747 PCM SERVER Multiple instances of Machine Edition on a single machine used multiple PCM user licenses
8.50 0 184759,1-3022592171 VIEW GRAPHICAL OBJECTS Button text did not change if the setlanguage script function was used
8.50 0 184619,1-2813425211 VIEW SCRIPTING When a VBScript was running periodically, it appeared to cause a constant memory increase in the View Runtime
8.50 0 184640,1-2803597626 VIEW VALIDATION This occurred on QuickPanel+ and QuickPanel View/Control units. An out-of-range value entered on such units was ignored on
the units but passed to PLCs. Now it is not passed to PLCs.
8.50 0 184658,1-2872567463 VIEW WEBVIEW Web View showing incorrect values and not responding to user actions
8.50 1 184979,1-3626203515 LD PC RETENTIVE DATA Retentive data was limited to 27000 bytes on a QuickPanel+
8.50 1 184943,184945,1- LD PLC FUNCTION BLOCKS Logic Execution Problem with UDFB call
3341036311,1-3363928358
8.50 1 184973,1-3548527273 LD PLC FUNCTION BLOCKS Adding to structure did not update existing variables
8.50 1 184992 LD PLC IEC 61850 Missing OPERChk UDT variable in IEC61850 protocol variable (e.g. S10_sr350_GEDevice. XCBR1_Pos.Oper_ctlVal_CO.OPERChk)

8.50 1 DE1335 LD PLC LOGIC EGD Memory leak and prepare variable for validate crash.
8.50 1 DE1342 LD PLC LOGIC Fixed a problem with WFW changes when working with older projects.
8.50 1 DE1346 LD PLC LOGIC PME thread count increases each time it attempts to connect to a controller
8.50 1 184967 PCM SCHEDULER Scheduled Compare for iFix project failed for exception
8.50 1 184939,1-3473023698 VIEW ALARMS Secondary alarms in the mirror not being displayed
8.50 2 DE1349 LD PLC HWC Corrects a crash that was occurring intermittently on random LD-PLC projects during a validate/download
8.50 2 DE1374 LD PLC HWC Corrects an issue where the IO Endian Conversion binary for a Profinet IO module was incorrect when IO reference where
grouped and data types were mixed
8.50 2 DE1382,1-3775053131 LD PLC TARGETS Fixes issue with adding a new 90-70 target to an existing project

© 2017, General Electric Company https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 12/11/2017


Fixed Issues Page 3 of 9

8.50 2 184387,1-2698819851 LD PLC VALIDATION After editing linked UDT and undo checkout results in validation error 12579
8.50 2 184603,1-2803597884 LD PLC VALIDATION Project Validation increases memory usage of PME from ~500,000 to 610,000k
8.50 2 184762,1-2997745651 LD PLC VALIDATION After adding new TON function block variable to ST block and updating toolchest link, linked ST blocks are not updated with
new variable
8.50 2 184764,1-3027464361 VIEW ALARMS Bit Alarms Refresh in editor keeps refreshing locking up the software
8.50 3 185020,1-3754975091 LD PLC FUNCTION BLOCKS No Validation error on configuring block parameter bool array of smaller dimension than required on a PSB operand
8.50 3 185011,1-3713741349 LD PLC HWC 9030 to RX3i target convert allowed configuring ETM module in expansion rack
8.50 3 184988,1-3655980713 LD PLC LOGIC Updating PPS blocks from toolchest takes 6-8 minutes to complete, even though Feedback zone says done
8.50 3 185084,1-3987993039 LD PLC LOGIC Logic paste into ladder editor was not working. Was popping 'cannot create variables in monitor mode' error for variables

8.50 3 185025,185026,1- LD PLC UPLOAD 9070 - Logic NE after RMS and PME crash after logic only upload
3781849121,1-3781915731
8.50 3 184986,1-3654653111 LD PLC VALIDATION Updating PPS blocks to the current version and validate results in dangling Errors
8.50 3 184989,1-3663487980 LD PLC VALIDATION Imported code from good project results in errors "too complex/stack overflow
8.50 3 184822,1-3097664971 LD PLC VARIABLES When importing an exported block of logic, variables were missing
8.50 3 185008,1-3097664971 LD PLC VARIABLES PME crashed when trying to change UDT element name
8.50 3 185076 PCM GENERAL Error message "The Options: Preferences registry information is invalid" showed up at startup of PME
8.50 3 185010 PCM SERVER In the Server Configuration leaving the Audit Database Type field blank and hitting OK caused the utility to stop working

8.50 3 185028 PCM UTILITIES Change Management screen saver displayed a wrong product version number
8.50 3 184963,1-3508695273 VIEW DRIVERS Unable to change AB Remote I/O Driver Baud Rate property on QuickPanel target
8.50 3 185055,1-3790299334 VIEW RUNTIME The assignment to a :HIGH or :LOWLIMIT of an indirect variable, the value of that variable can not be written to
8.50 3 185061,1-3876469821 VIEW RUNTIME QuickPanel+ was not configurable without installing Logic Developer PC component
8.50 4 DE1405,1-3885569958 LD PLC LOGIC Controller halt during online edit session
8.50 4 185034,1-3814544457 LD PLC ONLINE EDIT Word-For-Word took more time to complete (~30 seconds versus <5 seconds in earlier version)
8.50 4 185005,1-3664992946 PCM 3rd PARTY Adding large RSLogix 5000 project failed for timeout at project exporting
8.50 4 185021,1-3767567521 PCM SECURITY Unchecked-out read-only ME project allowed user to add power lines to ladder logic and send the changes to the PLC

8.50 4 185044,1-3845856312,1- VIEW DOWNLOAD QP+ target download to local media aborted abruptly with error 2394 when HMI Publish property was turned on in target
4092868551 properties.
8.50 4 185036,1-3825316691,1- VIEW RUNTIME GE SRTP driver Communication with PLC failed for string and LREAL with suffix tag in QuickPanel+
3723191331
8.50 4 KEP54305,1-3909015621 VIEW RUNTIME Upgraded to new ProficyViewIntegratedOPCDriver install(5.12.162.0) to address failed reads issue with GE Ethernet View OPC
Driver
8.50 5 185100,00192843 LD PC FUNCTION BLOCKS ME crash on attempt to open UDFB FBD logic block
8.50 5 184972,00189048&00193825 LD PC RMS QuickPanel+ download error, unable to perform Run Mode Store to Controller

8.50 5 184958,00193825,00189009,0 LD PLC DATA MONITORING IOComp evaluation copy pop-up dialog on using Data Logging Window
0194892
8.50 5 185128,00205338 VIEW DRIVERS QuickPanel+ CTC Serial Driver was corrupting negative value
8.50 5 185129,00204523 VIEW DRIVERS Unable to read %M bits using the GE SRTP driver on QuickPanel+
8.50 6 DE1751,00193610 LD PLC EGD Rx7i EGD stops after RMS download
8.50 6 DE1754,00223232 LD PLC EGD A problem has been reported with PME 8.5 and Rx3i PLC's when EGD exchanges are set to produce in backup
8.50 6 185115,00189273 VIEW DRIVERS Improved "DH+ and DF1" drivers to correctly read and write the ND type double integer registers. When the ND type address is
used the drivers use two consecutive register contents to form a 32 bit integer value.
8.50 7 DE1792 LD PLC LOGIC Generating C Structure is adding extra padding
8.50 7 DE1793 LD PLC LOGIC UDT element offset calculations are not always correct when using nested structures
8.50 8 DE1883,00189040 LD PC DRIVERS QuickPanel+ Control Stopped working on network disruption
8.50 8 DE1872,00189057,00189061 LD PC EDITORS PC/QP/QP+ Control variable online value in ST logic editor was appearing question marks

8.50 8 DE1886,00237971,00189027 LD PLC HWC Unnecessary Warning 8434 coming on multiple Validate

8.50 8 DE1868,00189157,00205371,0 VIEW GRAPHICAL PANEL QuickPanel+ redraw issue when using Indexed Image Display
0240307,00240999
8.50 8 DE1867,00192744 VIEW TARGET VIEWER Remote Target Viewer was disconnecting after certain period of time, introduced 5 Retries
8.50 9 185142,00239910 PCM 3rd PARTY RSLogix 5000 project compare failed for a script error "Type mismatch: 'psRSLogix5000Fix'"
8.50 9 185143 PCM 3rd PARTY An exception occurred during scheduled compare for a RSLogix 5/500/5000 project if the compare was configured to create a
new version on miscompare and there were miscompares found.
8.50 9 185137 PCM AUDIT TRAILS PCM operations on CIMPLICITY v9.0 projects didn't get logged into the PCM audit database
8.50 9 DE1953,00189013 VIEW ALARMS Alarm header was not showing Chinese characters properly.
8.50 10 185067,00179549 PCM AUDIT TRAILS Audit trail did not log Machine Edition downloads
8.50 11 185155,00257880 PCM SCHEDULER Scheduled PAC compare failed to generate comparison report upon miscompares and caused the Machine Edition to crash at
upload
8.50 11 185153,00259014,00179203 PCM SERVER Adding a large CIMPLICITY/iFIX project failed for exception

8.50 12 185167,00291079 PCM SECURITY Read-only ME project allowed user to draw power lines using the CTRL+ARROW keys
8.50 12 185166,00292231,00302183 PCM SERVER Canceling the previous operation on ME project always failed when the server was using SVN as backend

8.50 13 00324448 LD PC LOGIC TON in LD PC (QP+) don't seem to function properly.


8.50 13 185172,00323298 PCM GENERAL A Machine Edition project could be checked into the PCM Server while it was actively open in another instance of Machine
Edition
8.50 13 185169,00304366 PCM SERVER Server stopped responding or Operations failed when multiple clients performed operations concurrently
8.50 14 00335382 LD PLC HWC Fixed Versamax Profibus DP issue - GSD Module crash after selection
8.50 14 00330703 LD PLC LOGIC Fixed issue when validating projects with specific logic topologies
8.50 15 00343621 LD PLC HWC Fixed issue where the incorrect configuration was being generated for a Profibus slave module under a BEM003 Profibus
Master and the Slave module had more than 4 data area.
8.50 16 00350257 LD PLC UDFB Fixed issue where monitoring a UDFB instances with variable description turned on would cause memory usage to constantly
increase and would also cause an increase in CPU usage.
8.50 16 00364900 PCM GENERAL The project popup menu items were not always enabled or disabled according to the current status of the project
8.50 16 00364055 PCM SECURITY User with the Logic Changes permission was not able to edit Structured Text files in a ME project
8.50 16 00341471 PCM SECURITY Read-only ME project allowed user to force the values in the Reference View Tables
8.50 17 00304465 VIEW RUNTIME Strange behaviour on Momentary button.
8.50 17 00391870 VIEW RUNTIME Runtime error on QPView Windows CE 4.10.
8.50 17 00435233 VIEW RUNTIME unable to find runtime when trying to start QP view project.
8.50 17 00345759 LD PC PC CONTROL FxControl.exe will not run.
8.60 0 DE1405,1-3885569958 LD PLC DOWNLOAD RMS FDelete list with an entry for a file and an entry for the directory containing the file would cause controller stop/halt

8.60 0 185078,00189744 LD PLC EGD PPS 2.50 SIM2 - new member variable not added to EGD exchange during 1st validate/build
8.60 0 DE1721 LD PLC EGD EGD Bind and Build is not incrementing the signature in the config server when called from validate or validate & build.

8.60 0 DE1770,00189177 LD PLC EGD The parameters dialog box was not checking lengths of a DINT Member Variable
8.60 0 DE1354,1-3059766364,1- LD PLC FUNCTION BLOCKS UDT Count is set incorrectly and being saved (Close/open does not fix)
3654652604
8.60 0 DE1412 LD PLC FUNCTION BLOCKS Using a member of a UDFB that is a UDT type on the ANY UDT type parameter of a C block will generate a type mismatch
error.
8.60 0 DE1749,00222122 LD PLC HELP Help says IC693CPU370 supports Set Temporary IP, but that CPU has no Ethernet port
8.60 0 DE1312 LD PLC HWC Can't copy module using Copy and Paste operation
8.60 0 DE1701,00192644,00188950 LD PLC HWC Operations relating to 9030 or 9070 editor tabs on a third monitor could crash PME. Issue can happen when opening or
closing one of these editors, or dragging PME with these editors open
8.60 0 DE1843,00202358 LD PLC HWC Unexpected error 9671 on project reopen when RX7i HWC Module Interrupt was configured on logic block scheduling property

8.60 0 DE1874,00238817 LD PLC HWC RX3i HSB mirror wizard showing invalid profinet messages on mirroring when PNC, PNS are already present in the secondary
HWC
8.60 0 DE1844,00238148 LD PLC IMPORT Misleading message on LM90, VersaPro project import

© 2017, General Electric Company https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 12/11/2017


Fixed Issues Page 4 of 9

8.60 0 DE1826 LD PLC LOGIC Nested function blocks in a redundant system could sometimes cause one of the controllers to fail to start.
8.60 0 184834,1-3130261496 LD PLC ONLINE EDIT ME reporting an error during online editing and, at some point, shuts down
8.60 0 DE1890 LD PLC PNSR Controller Name and IP address collision messages were incorrect when PNC in primary had non-default Name or IP address

8.60 0 DE1374 LD PLC PROFINET PROFINET Group IO Reference setting incorrectly changes endian of some data
8.60 0 185121,00204768 LD PLC REDUNDANCY ME crash when adding Rx3i Redundant Mirror
8.60 0 DE1057 LD PLC REDUNDANCY Switching between primary and secondary controller show status of the target as NE Until validating
8.60 0 184835,1-3134043540 LD PLC VALIDATION ME crash on validate target using a specific logic topology
8.60 0 184843,1-3113656671 LD PLC VALIDATION Replace UDT with same name UDT with elements moved in position, followed by "Clean Build Folders" resulted in unexpected
validation error
8.60 0 DE1353,1-2894462941 LD PLC VALIDATION Modified Tag Count wording to ensure everyone knows the counts are approximate
8.60 0 DE1729,00208542 LD PLC VALIDATION After importing a particular logic topology via XML, PME is crashing during the validate
8.60 0 DE1750,00221282 LD PLC VALIDATION RX3i ST logic, 1156 lines of code deleted during target validate
8.60 0 DE1747,00194203 LD PLC VARIABLES Machine Edition save impossible after structure duplication
8.60 0 DE1755,00222088 LD PLC VARIABLES When duplicating a Control Module Variable (instance), the duplicate gets all of its members set to 1
8.60 0 US8755,00222345 LD PLC VARIABLES Cut, copy and Paste of LD or FBD logic using variable array elements was not copying array element descriptions to a different
target
8.60 0 US8773,00189005 LD PLC VARIABLES Bit-referenced elements of a duplicated array were not getting next reference address assigned
8.60 0 US8782,00224771 LD PLC VARIABLES Unable to edit ladder logic after cancelling export drawer action in toolchest
8.60 0 DE1302 PME INSTALL ME crash when CIMPLICITY 8.2 SIM 24 is installed.
8.60 0 DE1746,00194139 PME SETTINGS ME crash when changing general settings where multiple instances of ME are running.
8.60 0 DE1852,00239080 VIEW DRIVERS Fanuc CNC driver and device were not showing Alarm and Event properties to configure
8.60 0 DE1875,00225244 VIEW DRIVERS Boolean addresses (such B3:0/0 or N7:0/15) can now be added as data type ‘Double’ without failing validation (AB DF1)

8.60 0 184933 VIEW RUNTIME GE SRTP driver Communication failed in Factory refreshed panel, when updated with backed up runtime files in QuickPanel+

8.60 0 184959 VIEW RUNTIME Historian Trend Tool was not working in Historian mode (when connected to Historian data source) for QuickPanel+
8.60 0 185128,00206838 VIEW SCRIPTING For specific project PME was closing abruptly on attempt to insert variable in View or VB script
8.60 0 US8781,00225238 VIEW SECURITY Error 6014 help page does not mention about the available option to convert this error into a warning
8.60 0 DE1853,00209093 VIEW WEBVIEW When viewing a project in a webview,the alarm object did not refresh properly when in an overlapped panel. Only the grey
background color is displayed until an alarm is generated in the alarm window.
8.60 1 DE2042,00189133 LD PLC DOWNLOAD Fixed crash during stop mode download to CRU320.
8.60 1 DE2050,00259124 LD PLC DOWNLOAD Download updated program to controller when in run-mode will produce an error.
8.60 1 DE1934,00245234 LD PLC EGD Fixed duplicate exchanges getting created on Validate/Build.
8.60 1 DE2001,002222196 LD PLC EGD EGD Configuration Server Produced Exchange changes are not always detected.
8.60 1 DE1931,00246681 LD PLC FUNCTION BLOCKS ME crash when editing parameters of a UDFB.
8.60 1 DE1973,00238816 LD PLC FUNCTION BLOCKS UDFB Elements were not retaining transfer list settings on a CSV variable Import.
8.60 1 DE2022,00257945,00256887 LD PLC LOGIC PID Tuning crashes ME.

8.60 1 DE2059,00262623 LD PLC LOGIC Option check boxes missing on replace instruction dialog.
8.60 1 DE1971,00251194 LD PLC TOOLCHEST PME 8.6 missing contacts in tool chest LD drawer.
8.60 1 DE1826,00194561 LD PLC UDT Adding a Nested UDT variable to the transfer list fails a redundant start.
8.60 1 DE2063,00193826 LD PLC UPLOAD Fixed corruption of variables on upload of project from 90-30 PLC.
8.60 1 DE1892,00194174 LD PLC VALIDATION Validation error on a variable of type DL_SamplingRate in ST.
8.60 1 DE1932,00240770 LD PLC VALIDATION Unknown Validation Exception with CAM Block.
8.60 1 DE2023,00257021 LD PLC VALIDATION Validate is crashing VersaMax with addition of IL blocks.
8.60 1 DE2043,00260474 PME GENERAL ME crash when changing general settings where multiple instances of ME are running.
8.60 1 DE2039,00188987 PME UTILITIES Corrected issues for non-English operating systems on Set Temp IP Tool
8.60 1 DE2019,00193797 VIEW ALARMS Driver diagnostics dialog box did not show all characters for few lines of text
8.60 1 00193797 VIEW DRIVERS PME 8.50 , win7 64bit. Driver diagnostics popup box doesn't show all characters
8.60 1 DE2024,00256132 VIEW GRAPHICAL OBJECTS Toolchest linked graphical object was not resizing for source update in toolchest
8.60 1 DE2025,00188988 VIEW SCRIPTING Variable drag to VBScript editor was not dropping in correct format (Lengthy text was getting added)
8.60 1 00246806 VIEW WEBVIEW Web View of HMI (QuickPanel *), doesn't have digital signature required by Java 1.8.20 (and soon 1.7.?)
8.60 2 DE2217 LD PLC DOWNLOAD Unable to set the Sweep Setting in Sweep Tab of the Show Status dialog
8.60 2 DE2307 LD PLC DOWNLOAD Unable to set the Date/Time in Date Tab of the Show Status dialog
8.60 2 DE2041,00193907 LD PLC EGD Unable to get EGD Consumed Exchange to work properly.
8.60 2 DE2092,00263621 LD PLC HWC 90-30 CPU372 conversion to RX3i was missing Ethernet module.
8.60 2 DE2093,00267971 LD PLC HWC Conversion of RX3i 12 slot to 16 slot resulted in two LRE001's.
8.60 2 DE2226 LD PLC HWC HWC Import fails when the import involves a catalog version upgrade for a CPE305 or CPE310.
8.60 2 DE2234,00272485 LD PLC HWC Profinet IO variables missing after updating PNC.
8.60 2 DE2235,00276067 LD PLC HWC RX3i PNC001 catalog upgrade was losing PNC IP Address.
8.60 2 DE2233,00276026 LD PLC LOGIC Can't import C block from Toolchest or paste from a second instance.
8.60 2 DE2286 LD PLC UDT Generate C Structure for UDT was adding filler byte when not needed.
8.60 2 DE2347 LD PLC UDT Special characters in description of XML export will cause Toolchest import to fail.
8.60 2 DE2044,00250066 LD PLC VALIDATION Validation may randomly crash on multi-core PC.
8.60 2 DE2094 LD PLC VALIDATION Validation may randomly result in 0, 1, or 2 errors.
8.60 2 DE2060,00189718 VIEW DOWNLOAD Incorrect error message when QP View model download does not match the connected physical model
8.60 2 00205331 VIEW DRIVERS When using a shared variables between a rx3i and a QP, the REAL variables from the PLC projects are not displayed properly
on a QP runtime.
8.60 2 00215164 VIEW LANGUAGE View Runtme does not display a carriage return properly when running on a QP+ when using the language grids.
8.60 2 DE2066,00189103 VIEW LANGUAGE Message animation problem if source language is equal to destination language
8.60 2 00261286 VIEW VARIABLES #BatteryStatus variables not working properly in QP+ targets.
8.60 2 00280246 VIEW VARIABLES After a shared project is added to the variables tab and add shared variables chosen, PME disappears.
8.60 2 DE2062,00192742 VIEW WEBVIEW Numeric Data Entry (NDE) object on WebView misinterpreted user input value
8.60 3 DE2524,00271443 LD PLC EDITORS The REAL array variable could not be detected in ST block
8.60 3 DE2308,00276255 LD PLC EGD EGD configServer issue - Consumed exchange is missing data ranges
8.60 3 DE2430,00281792 LD PLC EGD Produced Exchanges no longer export
8.60 3 DE2261,00255393 LD PLC HWC RX3i PMM335 fault message (loss of module) during download.
8.60 3 DE2400 LD PLC HWC CPE330 identified incorrectly in error message when trying to store a different CPU in the configuration.
8.60 3 DE2454 LD PLC HWC Validation of DUAL HWC causes PME to crash.
8.60 3 DE2510,00285756 LD PLC LOGIC 9030 - NE_REAL Instruction Not Operating Properly.
8.60 3 DE2522 LD PLC UDT UDT elements used as public member of UDFB are writeable outside the UDFB
8.60 3 DE2532 LD PLC UDT Fixed a problem with offsets shown in the UDT editor when nesting arrays of structures
8.60 3 00289179 VIEW CONVERSION The 'convert to' option from an old legacy QP to a QP VIew/Control does not work in Machine Edition V8.6 SIM 1/SIM 2.
(Solution: User required to use ADMIN Mode for this operation)
8.60 3 00289687 VIEW Download CME - Problems downloading the 7" demo application to a QP+ Firmware 20. (Solution: User required to use ADMIN Mode for
this operation)
8.60 3 00275665 VIEW DRIVERS Negative values on QP+ via Modbus TCP/IP.
8.60 3 00282990 VIEW DRIVERS 7" QP+ - PME 8.50 SIM 10 Ethernet I/O Driver communication problem (I/O Dropped occasionally).
8.60 3 00275369,00274205,00276249 VIEW GRAPHICAL OBJECTS Choosing Animations tab on graphical objects was leading PME to crash.
,00276402,00283266
8.60 3 00274666 VIEW GRAPHICAL PANEL PME 8.6 SIM 1 - PME crashed on download of project
8.60 4 DE2539,00291013 LD PLC HWC PME not generating Hardware configuration report.
8.60 4 00310581 LD PLC INSTALL LD PLC component-only installation.
8.60 4 DE1996,00238186 LD PLC LOGIC PME freezes during WFW changes.
8.60 4 DE2606 LD PLC LOGIC Error 9683 being logged against UDT elements when a write should be allowed.
8.60 4 DE2630,00295522 LD PLC LOGIC PME would not allow RMS after upload from a project stored with PME 8.00.
8.60 4 00288827 VIEW CONTROLLERS & IO Controller will not be automatically started after battery replacement, #Command script needs to be used to start it.

8.60 4 00268572,00286499 VIEW LOGGING Logging appears to be generating SDMemoryX folders when the SDcard is unplugged.
8.60 4 00301177 VIEW ONLINE Scan time going to a higher value periodically.
8.60 4 00220722 VIEW RUNTIME ME Windows PC View Runtime Crashing.
8.60 4 00269211 VIEW RUNTIME Quickpanel Locks up after script run and view runtime minimizes.
8.60 4 00303405 VIEW RUNTIME Issue with ME 8.6 after a PC crash.
8.60 4 00244712 VIEW TARGETS QuickPanel Plus in Landscape Mode.

© 2017, General Electric Company https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 12/11/2017


Fixed Issues Page 5 of 9

8.60 5 00289078,00289094,00296367 LD PC LOGIC PME 8.6 Crashes when adding PID block to Quickpanel+ Control Ladder block.
,00307852,00316677
8.60 5 DE2735,00299618 LD PLC EGD Fixed issue with EGD Exchanges not showing up in consumed selections
8.60 5 DE2741,00303096 LD PLC EGD Fixed issue with Consumed exchanges issuing error 8687
8.60 5 DE2673,00301453 LD PLC LOGIC Certain legacy projects were failing to import due to the names on blocks or support files.
8.60 5 00308518 VIEW RUNTIME ME 8.6 SIM3, QP+ 10” Build 11 - Enhanced Security setup, enter /confirm password. (Solution: User required to use ADMIN Mode
for this operation)
8.60 5 00311412 VIEW RUNTIME QP+ ViewScript Operator "BAND" does not work with negative Values.
8.60 5 00317137 VIEW RUNTIME V8.5 SIM 8; QP+ 12" Alarming does not work when highest bit of DINT is true - In simulation it does work.
8.60 6 N/A PME LICENSING Modified Licensing to include VersaMax PLC to the Lite Developer Suite
8.60 6 00320883,00292085 VIEW RUNTIME View Runtime shutdown unexpectedly when View Native DF1 Driver is configured.
8.60 7 185170,00267410 PCM AUDIT TRAILS Audit Trail Report Manager did not open properly
8.60 7 00320003 VIEW DOWNLOAD Download to local media was failing in QP+ targets when Enable Networking was set to True.
8.60 7 00318006 VIEW GRAPHICAL PANEL Windows x64 View Runtime on PC, cannot restrict taskbar access (thin line visible/ accessible)
8.60 8 DE3031 LD PLC UDT Fixed issue with filler bytes not showing offset in C structure like other elements
8.60 8 185143 PCM 3RD PARTY COMPONENTS An exception occurred during scheduled compare for a RSLogix 5/500/5000 project if the compare was configured to create a
new version on miscompare and there were miscompares found.
8.60 8 185067,00179549 PCM AUDIT TRAILS Audit trail did not log Machine Edition downloads
8.60 8 185137 PCM AUDIT TRAILS PCM operations on CIMPLICITY v9.0 projects didn't get logged into the PCM audit database
8.60 8 185176 PCM GENERAL Make Latest operation caused Machine Edition to terminate unexpectedly
8.60 8 185172,00323298 PCM GENERAL A Machine Edition project could be checked into the PCM Server while it was actively open in another instance of Machine
Edition
8.60 8 185155,00257880 PCM SCHEDULER Scheduled PAC compare failed to generate comparison report upon miscompares and caused the Machine Edition to crash at
upload
8.60 8 185167,00291079 PCM SECURITY Read-only ME project allowed user to draw power lines using the CTRL+ARROW keys
8.60 8 185174 PCM SERVER Cimplicity 9.0 Project was not added to the PCM server properly
8.60 8 185169,00304366 PCM SERVER Server stopped responding or operations failed when multiple clients performed operations concurrently
8.60 8 185166,00292231, 00302183 PCM SERVER Canceling the previous operation on ME project always failed when the server was using SVN as backend
8.60 8 185153,00259014, 00179203 PCM SERVER Adding a large CIMPLICITY/iFIX project failed for exception
8.60 9 DE3050,00335382 LD PLC HWC Fixed VersaMax Profibus DP issue - GSD Module crash after selection
8.60 9 DE1999,00208350 LD PLC LOGIC logic going not equal during test and edit
8.60 9 00333846,00334490,00329983 VIEW RUNTIME Script Command SendEmail no longer operating in QP+ environment.
8.60 11 00353563 LD PC LOGIC LD-PC control - crash when open PID block.
8.60 11 DE3122,00348202 LD PLC EGD EGD config error on 90-30
8.60 11 DE3117,00339138 LD PLC HWC Fixed issue where uploading into a new target from a controller that was downloaded using Moderate compression would fail.

8.60 11 DE3114,00343621 LD PLC HWC Fixed issue where the incorrect configuration was being generated for a Profibus slave module under a BEM003 Profibus
Master and the Slave module had more than 4 data area.
8.60 11 DE3149,00350294 LD PLC IMPORT Fixed issue where importing the latest GSDML files for the PNS001 and CEP001 on a 32-bit OS would result in a "out of memory
error".
8.60 11 DE3208,00360032 LD PLC LOGIC Fixed issue not being able to import VS1 and VS2 files from VersaSafe.
8.60 11 DE3203,00324912 LD PLC LOGIC Fixed issue where using a variable indexed array of BOOL on a PSB input would cause the PLC to crash.
8.60 11 DE3154,00350257 LD PLC UDFB Fixed issue where monitoring a UDFB instances with variable description turned on would cause memory usage to constantly
increase and would also cause an increase in CPU usage.
8.60 11 DE3124,00348982 LD PLC UPLOAD Upload from 90-70 failing on DECL file.
8.60 11 185178,00332993 PCM GENERAL A Machine Edition project got locked out after an Undo Checkout of the project failed with a crash
8.60 11 185180,00346403 PCM TOOLCHEST The toolchest drawers in the server location didn't show up
8.60 11 DE3059,00335275 PPS FUNCTION BLOCKS The Formula for the ADV_PID and PID blocks has been reverted to its previous version without scaling factor added.
8.60 11 00333539,00346412 VIEW RUNTIME Memory Leak on QP+ view runtime.
8.60 11 00284942 VIEW RUNTIME Web view was not getting updated with values though runtime was working fine.
8.60 11 00340172 VIEW RUNTIME Touch Animation-Open URL will not work in QP+.
8.60 12 00371823 LD PC LOGIC PME crashes when inserting a customer PC function block into ladder editor.
8.60 12 DE3271,00368751 LD PLC HWC Fixed issue when opening older 5.70 projects.
8.60 12 DE3225,00365198 LD PLC HWC Fixed GSDML issue regarding missing Device Type names.
8.60 12 DE3218,00359998 LD PLC LOGIC Fixed issue for VersaSafe startup error: warning unable to check safety logic for block
8.60 12 DE3265,00367966 LD PLC LOGIC Fixed issue when hovering over a member variable.
8.60 12 DE3209 LD PLC LOGIC Updated PACSystems C Toolkit URL for VersaSafe blocks.
8.60 12 185182,00364055 PCM SECURITY User with the Logic Changes permission was not able to edit Structured Text files in a ME project
8.60 12 185181,00341471 PCM SECURITY Read-only ME project allowed user to force the values in the Reference View Table
8.60 12 00369819 VIEW Editor PME crashes when converting to QP V/C from legacy TCP QP.
8.60 12 00368386 VIEW MESSAGE GRIDS Message Grid is fill with weird character
8.60 12 00368335 VIEW MESSAGE GRIDS text in indexed message grids is garbled.
8.60 12 00369312 VIEW MESSAGE GRIDS Triggered Message Grids have corrupted messages.
8.60 12 00370749 VIEW MESSAGE GRIDS corrupt text on panels for QP after upgrading to 8.6 SIM11 from SIM 10.
8.60 13 DE3361 LD PLC EGD Invalid Network ID selection was shown on CPE330 for EGD produced exchanges.
8.60 13 DE3357,00377387 LD PLC HWC Fixed issue that caused a project corruption when upgrading a redundant CPE330 to a new catalog version. Also added some
code that repairs projects already corrupted by this issue. These repaired projects will require manual review of the Redundant
Transfer List settings.
8.60 13 DE3358 LD PLC HWC HWC export was mising GSDMLs from embedded PNCs.
8.60 13 DE3314,00374007 LD PLC LOGIC PME crashes during project validation with >150 of ST logic errors.
8.60 13 DE3220,00362169 LD PLC LOGIC Upload VersaMax project including IC200BEM003 fails.
8.60 13 DE3338,00377381,00376109 LD PLC LOGIC Can no longer configure submodule I/O on Profinet submodules.
8.60 13 185183,00364900 PCM GENERAL The project popup menu items were not always enabled or disabled according to the current status of the project
8.60 13 00299620, 00303770, 00334344,VIEW
00339723 OBJECTS Toolchest and its link object resize issues.
8.60 13 00316263 VIEW RUNTIME QPV & QP+ ChangeImage bug using negative height bmp file.
8.60 14 DE3477,00392699 GENERAL UTILITIES Corrected issues with the Updater utility.
8.60 14 DE3475 LD PLC EGD Fixed CPE330 issue with EGD exchanges possibly having an empty Adapter property.
8.60 14 DE3426/DE3476,00388107 LD PLC EGD Fixed a CPE330 NetworkID issue when using redundancy.
8.60 14 DE3421,00379019 LD PLC LOGIC Fixed an issue with moving a number into a variable.
8.60 14 DE3427,00385694 LD PLC LOGIC Fixed CPE330 issues with using Variable Mode.
8.60 14 185186,00377682 PCM GENERAL Label item for undo checkout of a ME project showed up in the project's History Report when the server was using VSS as
backend. Special Instructions: This fix will prevent the issue from occurring in the future. However, the existing label items
containing the label string '_FUndoCheckout' have to be manually changed to '_FUndoCheckin' in the server VSS DB in order
for them to stop showing up in the History Report.
8.60 14 185187,00378887 PCM PLANT LAYOUT The pages of a factory layout were randomly listed in the Navigator and in the InfoViewer
8.60 14 00312808 VIEW EDITORS Opening a project with 10 targets is taking more time.
8.60 14 00342078,00367696 ,00385667 VIEW TRAPISERVER QP+ even with security enabled vnc server still allow access .
8.60 15 DE3625,00393994 LD PLC HWC Importing configuration for IEC61850 doesn't always clean up previous configuration properly.
8.60 15 DE3404,00367313 LD PLC LOGIC Memory Leak when monitoring alias variables
8.60 15 DE3738,00411575 LD PLC LOGIC Flicker issue with linked LD logic
8.60 15 185188,00386830 PCM LOCAL MANAGER Machine Edition crashed when logging on to the Local Change Management
8.60 15 00358586,00382204,00389450 VIEW RUNTIME SendEmail function not working
,00367513,00369063,0038942
7
8.60 15 DE3832,00423540 LD PLC HWC CPE330 Variable Mode Crash
8.60 15 DE3362,00360824 LD PLC HWC Redundancy Tab in Online Status is not there for CPE330
8.60 15 DE3563,00399426 LD PLC LOGIC ARRAY_SIZE always gives value of 1 for PSB input parameter.
8.60 15 DE3343,00375833 LD PLC HWC Opening a RX3i NIU project can cause variable terminals on ETM001 to be deleted.
8.60 15 DE3795,00410232 LD PLC LOGIC PME crashes when validate the Rx3i project
8.60 15 DE3803,00410539 LD PLC UPLOAD Upload issue from Rx3i with a PMM335
8.60 15 DE3842,00418243 LD PLC DATA WATCH Opening project generates random Data Watch error
8.60 15 DE3851,00406099 LD PLC LOGIC Issue with extra filler bytes at end of structure when generating "C" structure for a UDT.
8.60 16 DE4065,00436787 LD PLC LOGIC Crash on Edit Block properties after Import of Control Modules.
8.60 16 DE4121,00437917 LD PLC LOGIC Fixes 8512 unknown validation exception that randomly occurred.
9.00 0 DE2952,00286516 LD PLC COMMUNICATIONS Crash if a download to an Rx3i is done after changing the IP Address in the ETM.

© 2017, General Electric Company https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 12/11/2017


Fixed Issues Page 6 of 9

9.00 0 DE1988,00194077 LD PLC DATA MONITORING Array-type variables are not refreshed in Data Watch Auto tab when scrolled down.
9.00 0 DE2040,00189713 LD PLC DOWNLOAD RX3i Download Error 8097 Ethernet CPE305.
9.00 0 DE2225,00275548 LD PLC HELP IC695PNC001 - catalogue version help file not available.
9.00 0 DE2236,00276300 LD PLC HELP Request to edit the SVC_REQ 24 help.
9.00 0 DE1987,00189200 LD PLC HWC Name and description of Profibus Slave modules disappear after close and open.
9.00 0 DE1990,00189207 LD PLC HWC MASTER HARDWARE CHECKSUM NOT EQUAL on Target Upload Verify Equality with DeviceNet.
9.00 0 DE2786,00318079 LD PLC HWC RX3i CPU Type showing incorrectly.
9.00 0 DE2805,00290111 LD PLC HWC RX3i redundancy system - config going not equal.
9.00 0 DE2009,00226069 LD PLC IMPORT Variables exported from PME to CSV then contents copied from CSV file to Variables in navigator causes changes in ref
addresses.
9.00 0 DE2383,00283464 LD PLC IMPORT Unable to Import String Functions From Toolchest Drawer.
9.00 0 DE1983,00242093 LD PLC LOGIC _Main block is missing logic after upload to empty project.
9.00 0 DE1992,00194174 LD PLC LOGIC Validation error on a variable of type DL_SamplingRate in ST.
9.00 0 DE1999,00208350 LD PLC LOGIC Logic going not equal during test edit.
9.00 0 DE2036,00260513 LD PLC LOGIC Validation Error is not linking anywhere which makes it very difficult to find the problem.
9.00 0 DE2538,00291986 LD PLC LOGIC Linked LD block is flickering.
9.00 0 DE2219,00273328 LD PLC UPLOAD Linked logic loses Toolchest link after upload in PACSystems.
9.00 0 DE2381,00281063 LD PLC UPLOAD 9030 Config (DNM200) is NOT EQUAL on upload/verify/validate.
9.00 0 DE2384,00279269 LD PLC UPLOAD Logic Not equal on upload.
9.00 0 DE1986,00194560 LD PLC VARIABLES Attempt to open project gives tag database error.
9.00 0 DE1997,00222345 LD PLC VARIABLES Cut/copy and Paste of Array does not copy array element descriptions.
9.00 0 DE2014,00189056 LD PLC VARIABLES The duplicate address could not be found.
9.00 0 DE2003,00250513 PME GENERAL When moving PME storage directory the utilities XML files starts tossing error messages.
9.00 0 DE2051,00259124 PME HELP Hyperlink in Feedback zone goes no where, even though help indicates it should.
9.00 0 DE2232,00276311 PME INTERFACE No scroll bar in Toolchest window.
9.00 0 DE2619,00296845 PME INTERFACE Control I/O tab appears for no reason after PME is rebooted the first time.
9.00 0 DE2664,00276292 PME PROPERTY INSPECTOR Misaligned Rows in Variable Table View - Unable to select tags.
9.00 1 DE3154,00350257 LD PLC FUNCTION BLOCKS Fixed issue where monitoring a UDFB instances with variable description turned on would cause memory usage to constantly
increase and would also cause an increase in CPU usage.
9.00 1 DE3050,00335382 LD PLC HWC Fixed Versamax Profibus DP issue - GSD Module crash after selection
9.00 1 DE3114,00343621 LD PLC HWC Fixed issue where the incorrect configuration was being generated for a Profibus slave module under a BEM003 Profibus
Master and the Slave module had more than 4 data area.
9.00 1 DE3117,00339138 LD PLC HWC Fixed issue where uploading into a new target from a controller that was downloaded using either Moderate or High
compression would fail.
9.00 1 DE3149,00350294 LD PLC IMPORT Fixed issue where importing the latest GSDML files for the PNS001 and CEP001 on a 32-bit OS would result in a "out of memory
error".
9.00 1 DE3124,00348982 LD PLC UPLOAD Fixed issue where uploading from a 9070 Controller that contained a large number of blocks(>200) would fail.
9.00 1 185176 PCM GENERAL Make Latest operation caused Machine Edition to terminate unexpectedly
9.00 1 DE3077 PME LICENSING Fixed issue where a project could not be saved when the project was opened with an unlicensed PME and license was
subsequently added.
9.00 1 DE3136,00350320 PME REPORTING Fixed issue where the Page Setup Print Options(paper, orientation and margins) were missing.
9.00 1 DE3111,00315909 PME SETTINGS Fixed issue where Custom Colors in the Options Tab are not saved.
9.00 1 DE3065,0034987 PME UTILITIES Fixed issue where launching of utilities via the Ribbon Bar are offset by 1.
9.00 1 DE3911,00335275 PPS PPS BLOCKS The Formula for the ADV_PID and PID blocks has been reverted to it's previous version without scaling factor added
9.00 2 00353563 LD PC LOGIC LD-PC control - crash when open PID block.
9.00 2 DE3226,00364996 LD PLC EGD Fixed crash that occurrs after installing SIM1 when editing/adding produced EGD exchanges for 9070 or 9030 controllers.

9.00 2 DE3199,00355827 LD PLC LOGIC FBD F11/F12 toggle functions not working.
9.00 2 DE3203,00324912 LD PLC LOGIC CPE305 Crash when Array with Variable Index Used as Input to Parametrized LD Block.
9.00 2 DE3208,00360032 LD PLC LOGIC Unable to Add VersaSafe Logic Blocks.
9.00 2 185178,00332993 PCM GENERAL A Machine Edition project got locked out after an Undo Checkout of the project failed with a crash
9.00 2 185180,00346403 PCM Toolchest The toolchest drawers in the server location didn't show up
9.00 2 DE3175,00352218 PME INTERFACE Find in target command disappears from the quick access toolbar
9.00 2 00284942 VIEW RUNTIME Web view was not getting updated with values though runtime was working fine.
9.00 2 00333539,00346412 VIEW RUNTIME Memory Leak on QP+ view runtime.
9.00 2 00361547 VIEW RUNTIME Send Email functionality through scripts was failing in QP+.
9.00 3 DE3265,00367966 LD PC LOGIC Fixed issue when hovering over a member variable.
9.00 3 DE3225,00365198 LD PLC HWC Fixed GSDML issue regarding missing Device Type names.
9.00 3 DE3271,00368751 LD PLC HWC Fixed issue when opening older 5.70 projects.
9.00 3 DE3209 LD PLC LOGIC Updated PACSystems C Toolkit URL for VersaSafe blocks.
9.00 3 DE3218,00359998 LD PLC LOGIC Fixed issue for VersaSafe startup error: warning unable to check safety logic for block.
9.00 3 DE3279,00371051 LD PLC LOGIC Improved security for locked blocks.
9.00 3 DE3314,00374007 LD PLC LOGIC Fixed crash when Validation issues too many errors.
9.00 3 185181,00341471 PCM SECURITY Read-only ME project allowed user to force the values in the Reference View Tables
9.00 3 185182,00364055 PCM SECURITY User with the Logic Changes permission was not able to edit Structured Text files in a ME project
9.00 4 DE3088,00372817 LD PLC EDITORS Fixed crash when opening multiple LD block editors.
9.00 4 DE3361 LD PLC EGD Invalid Network ID selection was shown on CPE330 for EGD produced exchanges.
9.00 4 DE3357,00377387 LD PLC HWC Fixed issue that caused a project corruption when upgrading a redundant CPE330 to a new catalog version. Also added some
code that repairs projects already corrupted by this issue. These repaired projects will require manual review of the Redundant
Transfer List settings.
9.00 4 DE3358 LD PLC HWC HWC export was mising GSDMLs from embedded PNCs.
9.00 4 DE3320,00362169 LD PLC LOGIC Upload Versamax project including IC200BEM003 or empty carrier fails.
9.00 4 DE3338,00377381,00376109 LD PLC LOGIC Can no longer configure submodule I/O on Profinet submodules.

9.00 4 185183,00364900 PCM GENERAL The project popup menu items were not always enabled or disabled according to the current status of the project
9.00 5 DE3426,00388107 LD PLC EGD Fixed use of CPE330 EGD NetworkID with redundancy.
9.00 5 DE3405 LD PLC HWC Added ability to Change GSDML for the CPE330.
9.00 5 DE3363,00376325 LD PLC VARIABLES Fixed Feedback Zone References tab.
9.00 5 DE3421,00379019 LD PLC VARIABLES Fixed issues moving values into variables.
9.00 5 185186,00377682 PCM GENERAL Label item for undo checkout of a ME project showed up in the project's History Report when the server was using VSS as
backend.

This fix will prevent the issue from occurring in the future. However, the existing label items containing the label string
'_FUndoCheckout' have to be manually changed to '_FUndoCheckin' in the server VSS DB in order for them to stop showing up
in the History Report.
9.00 5 185187,00378887 PCM PLANT LAYOUT The pages of a factory layout were randomly listed in the Navigator and in the InfoViewer
9.00 6 DE3442,00388066 LD PLC EGD Smart Build does not catch an EGD error on second validation.
9.00 6 DE3362,00360824 LD PLC HWC Redundancy Tab in Online Status is not there for CPE330
9.00 6 DE3427,00385694 LD PLC HWC Embedded PNC Variable mode target property could not be enabled and IO Variables on embedded PNC devices were
incorrect.
9.00 6 DE3443,00382185 LD PLC LOGIC Unable to download Cam Files
9.00 6 DE3429 PME PME Local Change Management option is missing on PME 9.0
9.00 6 DE3477,00392699 PME PME Apply Machine Edition Updates on Startup does not work, but works in older version 8.50
9.00 6 DE3049,00384202 PME PROJECT DeviceNet Communications Module was preventing opening of project
9.00 6 00312808 VIEW EDITORS Opening a project with 10 targets is taking more time.
9.00 6 00342078,00367696,00385667 VIEW SECURITY QP+ even with security enabled vnc server still allow access .

9.00 7 DE3381,00380354 LD PLC HELP CPE330 missing F1 help in InfoViewer.


9.00 7 DE3343,00375833 LD PLC HWC Opening a RX3i NIU project can cause variable terminals on ETM001 to be deleted.
9.00 7 DE3424,00385613 LD PLC HWC Converting a 90-30 target to RX3i did not always convert DeviceNet devices properly.
9.00 7 DE3563,00399426 LD PLC LOGIC ARRAY_SIZE always gives value of 1 for PSB input parameter.
9.00 7 185188,00386830 PCM LOCAL MANAGER Machine Edition crashed when logging on to the Local Change Management
9.00 7 DE3544,00392435 PME PROJECT Closing a shared project would sometimes cause PME to crash.
9.00 7 DE3541,00393282 PME TOOLCHEST Previews were not appearing in the Companion Help window.
9.00 7 DE3540,00392869 PME VARIABLES In some cases, it was possible to delete variables that were in use.

© 2017, General Electric Company https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 12/11/2017


Fixed Issues Page 7 of 9

9.00 7 DE3543,00397071 PME VARIABLES Performance can degrade when selecting variables.
9.00 7 00316263 VIEW RUNTIME QPV & QP+ ChangeImage bug using negative height bmp file.
9.00 7 00358586,00382204,00389450 VIEW RUNTIME QP+ View closes when email is sent.
,00367513,00369063,0038942
7
9.00 8 DE3842,00418243 LD PLC DATA WATCH Opening project generates random Data Watch error
9.00 8 DE3547,00392832 LD PLC EGD EGD Configuration Server does not update correctly.
9.00 8 DE3832,00423540 LD PLC HWC CPE330 Variable Mode Crash
9.00 8 DE3625,00393994 LD PLC HWC Importing configuration for IEC61850 doesn't always clean up previous configuration properly.
9.00 8 DE3795,00410232 LD PLC LOGIC PME crashes when validate the Rx3i project
9.00 8 DE3636,00408245 LD PLC LOGIC PME Rejects Valid Ladder Logic Rung
9.00 8 DE3408,00408245 LD PLC LOGIC Project with a DSM module configured shows all logic elements as not equal after Verify
9.00 8 DE3404,00367313 LD PLC LOGIC Memory Leak when monitoring alias variables
9.00 8 DE3803,00410539 LD PLC UPLOAD Upload issue from Rx3i with a PMM335
9.00 8 185190,00408038 PCM GENERAL Layout of tool windows was reset after PME close and re-open
9.00 8 185189,00405892 PCM SECURITY Unauthorized users were allowed to create or add projects to local computer and server
9.00 9 DE3888,00428995 LD-PLC CBLOCKS PME exists abnormally when validating target with C block
9.00 9 DE3911,00430824 LD-PLC CONTROL MODULES Redundant CPU330 is not showing Transfer List columns on control modules
9.00 9 DE3851,00406099 LD-PLC UDT PACsystems C Toolkit mislocating UDT data
9.00 9 DE3914,00432783 LD-PLC HWC Adding a data area to IC693DNM200 crashes
9.00 9 DE3917,00432034 LD-PLC VERSASAFE Adding new VersaSafe Logic Blocks does not generate the correct functions
9.00 9 DE3927 LD-PLC GSDML Embedded Profinet ports did not support update GSDML
9.00 9 00358586 , 00304465 VIEW RUNTIME Stuck button! v8.5 sim 12
9.00 9 00388366 VIEW RUNTIME Logging to Historian on a QP+
9.00 9 00369819 VIEW EDITOR PME crashes when converting to QP V/C from legacy TCP QP
9.00 9 00299620 , 00303770 VIEW EDITOR Image objects not keeping size after closing and opening of project
,00334344 ,00339723
9.00 9 00340172 VIEW RUNTIME Touch Animation-Open URL will not work in QP+.
9.00 9 DE3932,00425410 LD PLC LOGIC Unable to RMS a project upgraded from PME 8.50
9.00 10 00288828 LDPC RUNTIME QP+ 7 and 12 - PC Control - Positive Transition Contact will pass power flow when attempting a RMS (Run Mode Store)

9.00 10 00311809 VIEW WEBVIEW WebVIEW when QP is in portrait


9.00 10 00419810 VIEW RUNTIME Email wont send
9.00 10 00439839 VIEW RUNTIME ChangeBitmap Problem with bmp that have negative image height
9.00 10 DE4002,00442312,00443246 LD PLC HWC Software Crashes when trying to edit IC200ALG620 module carrier field

9.00 10 DE3953,00422519 PME VARIABLES Infinite refresh loop seen in status bar on certain variables
9.00 10 DE3958,00437548 LD PLC LOGIC Downloading logic with PACMotions Instructions cause the IC695CPE400 to halt
9.00 10 DE4033,00450633 LD PLC IMPORT Import of FBD Block Corruption
9.00 10 DE4010,00445056 LD PLC IMPORT Import of Block using Global Variables fails
9.00 10 00361102 VIEW EDITOR QP+ Enhanced security doesn`t work
9.00 11 TT185193 PCM GENERAL History Report doesn't function with IE 11 in use
9.00 11 TT185194 PCM GENERAL Unable to get the Checked Out Projects Report with IE 11 in use
9.00 11 TT185195 PCM GENERAL Clicking a iFIX or CIMPLICITY project node in the Navigator window brings up a script error when IE 11 is in use
9.00 11 TT185196 PCM GENERAL Comparison Report shows up with compare results missing when IE 11 is in use
9.00 11 TT185197 PCM GENERAL Download to PC Device operation of RSLogix 5/500/5000 project fails with a script error
9.00 11 00398653,TT185198 PCM GENERAL PME crashes when trying to set the Communication Type property for a LM9030/9070 project
9.00 11 TT185200 PCM PLANT LAYOUT The pages of the sample layout 'GenericLayout' show up blank in the InfoViewer when IE 11 is in use
9.00 11 DE4065,00436787 LD PLC LOGIC Crash on Edit Block properties after Import of Control Modules.
9.00 11 DE4121,00437917 LD PLC LOGIC Fixes 8512 unknown validation exception that randomly occurred.
9.00 11 TT185201 PCM GENERAL Various PCM operations on custom projects fail when the Debug property of the custom project type is set to 1
9.00 11 00392922 , 00395469 VIEW RUNTIME Alarms Buffering Enhancement
9.00 11 US 19411 VIEW RUNTIME A new option provided in the data entry Keyboard and keypad of the Runtime object to increase its size
9.00 11 00384629 VIEW RUNTIME View Script Bug - AppExec numStartMode does not work in QP+
9.00 11 00354563 VIEW RUNTIME QuickPanel + n/a QP View update via CFcard deleted user
9.00 11 DE4107 LD PLC IMPORT Import of of PSB and UDFB blocks fail
9.00 11 TT185203,00407902 PCM 3RD PARTY COMPONENTS PME crashes when adding GE Fanuc CNC project
9.00 12 DE4169 LD PLC ST SIZE_OF reports incorrect size in ST
9.00 12 DE4275, 00485849 LD PLC IMPORT Software will not validate and crashes
9.00 12 DE4274, 00485846 LD PLC GENERAL Crash with "Catastrophic Failure" error
9.00 12 DE4206, 00473136 LD PLC IMPORT Block Export and Import
9.00 12 DE4276, 00485851 LD PLC GENERAL Program File Corrupted
9.50 0 DE3088,00372817 LD PLC EDITORS Fixed crash when opening multiple LD block editors.
9.50 0 DE3226,00364996 LD PLC EGD Fixed crash that occurrs after installing SIM1 when editing/adding produced EGD exchanges for 9070 or 9030 controllers.

9.50 0 DE3361 LD PLC EGD Invalid Network ID selection was shown on CPE330 for EGD produced exchanges.
9.50 0 DE3426,00388107 LD PLC EGD Fixed use of CPE330 EGD NetworkID with redundancy.
9.50 0 DE3442,00388066 LD PLC EGD Smart Build does not catch an EGD error on second validation.
9.50 0 DE3547,00392832 LD PLC EGD EGD Configuration Server does not update correctly.
9.50 0 DE3122,00348202 LD PLC EGD Crash when configuring an EGD produced exchange for a 90-30 target with a CPU364
9.50 0 DE3693 LD PLC EGD Embedded Ports are not interacting with the EGD config server properly
9.50 0 DE2805,00290111 LD PLC EQUALITY RX3i redundancy system - config going not equal
9.50 0 DE3194 LD PLC FBD FBD Preview from Toolchest no longer works
9.50 0 DE3154,00350257 LD PLC FUNCTION BLOCKS Fixed issue where monitoring a UDFB instances with variable description turned on would cause memory usage to constantly
increase and would also cause an increase in CPU usage.
9.50 0 DE3381,00380354 LD PLC HELP CPE330 missing F1 help in InfoViewer.
9.50 0 DE3105,00343087 LD PLC HELP Assigning a %I to a coil generate validation error when help says it's allowed for 9030
9.50 0 DE3180,00354602 LD PLC HELP Updated PACSystems RX3i Serial Communications Modules Companion help file
9.50 0 DE3184,00346312 LD PLC HELP Bad Gateway IP leads to misleading error - 0.0 Mismatch of Communications Interface
9.50 0 DE3727,00416239 LD PLC HELP Help is wrong for command line launch
9.50 0 DE3050,00335382 LD PLC HWC Fixed Versamax Profibus DP issue - GSD Module crash after selection
9.50 0 DE3114,00343621 LD PLC HWC Fixed issue where the incorrect configuration was being generated for a Profibus slave module under a BEM003 Profibus
Master and the Slave module had more than 4 data area.
9.50 0 DE3117,00339138 LD PLC HWC Fixed issue where uploading into a new target from a controller that was downloaded using either Moderate or High
compression would fail.
9.50 0 DE3225,00365198 LD PLC HWC Fixed GSDML issue regarding missing Device Type names.
9.50 0 DE3271,00368751 LD PLC HWC Fixed issue when opening older 5.70 projects.
9.50 0 DE3343,00375833 LD PLC HWC Opening a RX3i NIU project can cause variable terminals on ETM001 to be deleted.
9.50 0 DE3357,00377387 LD PLC HWC Fixed issue that caused a project corruption when upgrading a redundant CPE330 to a new catalog version. Also added some
code that repairs projects already corrupted by this issue. These repaired projects will require manual review of the Redundant
Transfer List settings.
9.50 0 DE3358 LD PLC HWC HWC export was mising GSDMLs from embedded PNCs.
9.50 0 DE3362,00360824 LD PLC HWC Redundancy Tab in Online Status is not there for CPE330
9.50 0 DE3405 LD PLC HWC Added ability to Change GSDML for the CPE330.
9.50 0 DE3424,00385613 LD PLC HWC Converting a 90-30 target to RX3i did not always convert DeviceNet devices properly.
9.50 0 DE3427,00385694 LD PLC HWC Embedded PNC Variable mode target property could not be enabled and IO Variables on embedded PNC devices were
incorrect.
9.50 0 DE3625,00393994 LD PLC HWC Importing configuration for IEC61850 doesn't always clean up previous configuration properly.
9.50 0 DE3832,00423540 LD PLC HWC CPE330 Variable Mode Crash
9.50 0 DE3112,00339410 LD PLC HWC Versamax IO carrier popup selection box is empty
9.50 0 DE3425 LD PLC HWC Cannot copy/paste Profinet IO device from PNC to Embedded one on CPE330
9.50 0 DE3227 LD PLC HWC Number Media Redundancy Managers >1 not detecting embedded Profinet on CPE330
9.50 0 DE3258 LD PLC HWC PME CPE330 Overlapping Subnet Detection Issue
9.50 0 DE3261 LD PLC HWC PME crashes when IO device added to Embedded Profinet

© 2017, General Electric Company https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 12/11/2017


Fixed Issues Page 8 of 9

9.50 0 DE3420 LD PLC HWC Redundancy mode should be disabled for Embeded PNC devices when redundancy switched to True on CPE330

9.50 0 DE3149,00350294 LD PLC IMPORT Fixed issue where importing the latest GSDML files for the PNS001 and CEP001 on a 32-bit OS would result in a "out of memory
error".
9.50 0 DE3056 LD PLC IMPORT Importing Redundany HWC with Catalog upgrades has bad results when selecting 'No'
9.50 0 DE3216,00362907 LD PLC INSTALL PME9.0 with 8.60 remnants (left over sims) results in unexpected behaviors (MasterList)
9.50 0 DE3199,00355827 LD PLC LOGIC FBD F11/F12 toggle functions not working.
9.50 0 DE3203,00324912 LD PLC LOGIC CPE305 Crash when Array with Variable Index Used as Input to Parametrized LD Block.
9.50 0 DE3208,00360032 LD PLC LOGIC Unable to Add VersaSafe Logic Blocks.
9.50 0 DE3209 LD PLC LOGIC Updated PACSystems C Toolkit URL for VersaSafe blocks.
9.50 0 DE3218,00359998 LD PLC LOGIC Fixed issue for VersaSafe startup error: warning unable to check safety logic for block.
9.50 0 DE3279,00371051 LD PLC LOGIC Improved security for locked blocks.
9.50 0 DE3314,00374007 LD PLC LOGIC Fixed crash when Validation issues too many errors.
9.50 0 DE3320,00362169 LD PLC LOGIC Upload Versamax project including IC200BEM003 or empty carrier fails.
9.50 0 DE3338,00377381,00376109 LD PLC LOGIC Can no longer configure submodule I/O on Profinet submodules.

9.50 0 DE3404,00367313 LD PLC LOGIC Memory Leak when monitoring alias variables
9.50 0 DE3408,00408245 LD PLC LOGIC Project with a DSM module configured shows all logic elements as not equal after Verify
9.50 0 DE3443,00382185 LD PLC LOGIC Unable to download Cam Files
9.50 0 DE3563,00399426 LD PLC LOGIC ARRAY_SIZE always gives value of 1 for PSB input parameter.
9.50 0 DE3636,00408245 LD PLC LOGIC PME Rejects Valid Ladder Logic Rung
9.50 0 DE3795,00410232 LD PLC LOGIC PME crashes when validate the Rx3i project
9.50 0 DE3318,00373375 LD PLC LOGIC Unable to add VersaSafe Logic to the PME
9.50 0 DE3835 LD PLC OPTIONS Sync Process System Data property is missing from Controller General options
9.50 0 DE3092 LD PLC REPORTING Redundant 9070 material report is showing HWC from one configuration only
9.50 0 DE3702 LD PLC ST In ST - Compare Length is using the head of the array and not the entire array
9.50 0 DE3851,00406099 LD PLC UDT PACsystems C Toolkit mislocating UDT data
9.50 0 DE3624 LD PLC UDT The length of a UDT string member is not importing Properly when imported as part of a UDFB
9.50 0 DE3124,00348982 LD PLC UPLOAD Fixed issue where uploading from a 9070 Controller that contained a large number of blocks(>200) would fail.

9.50 0 DE3803,00410539 LD PLC UPLOAD Upload issue from Rx3i with a PMM335
9.50 0 DE3174,00354075 LD PLC VALIDATION Upon import getting a HSDR .ext error on import. PME then crashes when Processing SEQUENC .exp
9.50 0 DE3407 LD PLC VALIDATION PNS modules disappear from Profinet on Primary HWC after second mirroring.
9.50 0 DE3406 LD PLC VALIDATION Validation does not remove PNC submodules from Secondary HWC.
9.50 0 DE3363,00376325 LD PLC VARIABLES Fixed Feedback Zone References tab.
9.50 0 DE3421,00379019 LD PLC VARIABLES Fixed issues moving values into variables.
9.50 0 185176 PCM GENERAL Make Latest operation caused Machine Edition to terminate unexpectedly
9.50 0 185178,00332993 PCM GENERAL A Machine Edition project got locked out after an Undo Checkout of the project failed with a crash
9.50 0 185183,00364900 PCM GENERAL The project popup menu items were not always enabled or disabled according to the current status of the project

9.50 0 185186,00377682 PCM GENERAL Label item for undo checkout of a ME project showed up in the project's History Report when the server was using VSS as
backend.

This fix will prevent the issue from occurring in the future. However, the existing label items containing the label string
'_FUndoCheckout' have to be manually changed to '_FUndoCheckin' in the server VSS DB in order for them to stop showing up
in the History Report.
9.50 0 185190,00408038 PCM GENERAL Layout of tool windows was reset after PME close and re-open
9.50 0 DE3428,185188,00386830 PCM LOCAL MANAGER Machine Edition crashed when logging on to the Local Change Management
9.50 0 185187,00378887 PCM PLANT LAYOUT The pages of a factory layout were randomly listed in the Navigator and in the InfoViewer
9.50 0 185181,00341471 PCM SECURITY Read-only ME project allowed user to force the values in the Reference View Tables
9.50 0 185182,00364055 PCM SECURITY User with the Logic Changes permission was not able to edit Structured Text files in a ME project
9.50 0 185189,00405892 PCM SECURITY Unauthorized users were allowed to create or add projects to local computer and server
9.50 0 185180,00346403 PCM Toolchest The toolchest drawers in the server location didn't show up
9.50 0 DE3673 PME CONVERT Project with max Lans allows CPU310 to be replaced with CPE330.
9.50 0 DE3175,00352218 PME INTERFACE Find in target command disappears from the quick access toolbar
9.50 0 DE3077 PME LICENSING Fixed issue where a project could not be saved when the project was opened with an unlicensed PME and license was
subsequently added.
9.50 0 DE3429 PME PME Local Change Management option is missing on PME 9.0
9.50 0 DE3477,00392699 PME PME Apply Machine Edition Updates on Startup does not work, but works in older version 8.50
9.50 0 DE3049,00384202 PME PROJECT DeviceNet Communications Module was preventing opening of project
9.50 0 DE3544,00392435 PME PROJECT Closing a shared project would sometimes cause PME to crash.
9.50 0 DE3121 PME PROJECT DW Lists initialize error during openning empty project after download of a large project
9.50 0 DE3033 PME PROJECT Pressing the 'X' to close PME while opening or saving a large project may lead to a crash
9.50 0 DE3249 PME PROJECT Project will not open if another project is already open
9.50 0 DE3136,00350320 PME REPORTING Fixed issue where the Page Setup Print Options(paper, orientation and margins) were missing.
9.50 0 DE3111,00315909 PME SETTINGS Fixed issue where Custom Colors in the Options Tab are not saved.
9.50 0 DE3541,00393282 PME TOOLCHEST Previews were not appearing in the Companion Help window.
9.50 0 DE3065,00349787 PME UTILITIES Fixed issue where launching of utilities via the Ribbon Bar are offset by 1.
9.50 0 DE3540,00392869 PME VARIABLES In some cases, it was possible to delete variables that were in use.
9.50 0 DE3543,00397071 PME VARIABLES Performance can degrade when selecting variables.
9.50 0 DE3059,00335275 PPS PPS BLOCKS The Formula for the ADV_PID and PID blocks has been reverted to it's previous version without scaling factor added

9.50 0 00312808 VIEW EDITORS Opening a project with 10 targets is taking more time.
9.50 0 00284942 VIEW RUNTIME Web view was not getting updated with values though runtime was working fine.
9.50 0 00316263 VIEW RUNTIME QPV & QP+ ChangeImage bug using negative height bmp file.
9.50 0 00361547 VIEW RUNTIME Send Email functionality through scripts was failing in QP+.
9.50 0 00333539,00346412 VIEW RUNTIME Memory Leak on QP+ view runtime.
9.50 0 00358586,00382204,00389450 VIEW RUNTIME QP+ View closes when email is sent.
,00367513,00369063,0038942
7
9.50 0 00342078,00367696,00385667 VIEW SECURITY QP+ even with security enabled vnc server still allow access .

9.50 0 DE3888,00428995 LD PLC CBLOCKS PME exists abnormally when validating target with C block
9.50 0 DE3911,00430824 LD PLC CONTROL MODULES Redundant CPU330 is not showing Transfer List columns on control modules
9.50 0 DE3914,00432783 LD PLC HWC Adding a data area to IC693DNM200 crashes
9.50 0 DE3917,00432034 LD PLC VERSASAFE Adding new VersaSafe Logic Blocks does not generate the correct functions
9.50 1 DE3927 LD PLC GSDML Embedded Profinet ports did not support update GSDML
9.50 1 DE3932,00425410 LD PLC LOGIC Unable to RMS a project upgraded from PME 8.50
9.50 1 DE3958,00437548 LD PLC LOGIC Downloading logic with PACMotions Instructions cause the IC695CPE400 to halt
9.50 1 DE3953,00422519 PME VARIABLES Infinite refresh loop seen in status bar on certain variables
9.50 1 DE3989 LD PLC HWC Materials List status column was blank
9.50 2 US20079 LD PLC HWC Add RSTi-EP Family to Lite License
9.50 2 US20077 LD PLC VALIDATION Added Validation Error for unsupported Interrupts in CPE400 and CPE100
9.50 2 US20057 LD PLC HWC Enforced documented memory limitations for CPE100
9.50 2 00288828 LDPC RUNTIME QP+ 7 and 12 - PC Control - Positive Transition Contact will pass power flow when attempting a RMS (Run Mode Store)

9.50 2 00311809 VIEW WEBVIEW WebVIEW when QP is in portrait


9.50 2 00419810 VIEW RUNTIME Email wont send
9.50 2 00439839 VIEW RUNTIME ChangeBitmap Problem with bmp that have negative image height
9.50 2 DE4002,00442312,00443246 LD PLC HWC Software Crashes when trying to edit IC200ALG620 module carrier field

9.50 2 DE4028 LD PLC PROFINET PROFINET Explorer feature doesn't populate data on target EPSCPE100
9.50 2 00448300 LDPC CONTROL RUNTIME PME v9.5 - Win 10 x32 or x64 try to download a QP+ with View and PC in Simulator 
9.50 2 DE4033,00450633 LD PLC IMPORT Import of FBD Block Corruption
9.50 2 DE4010,00445056 LD PLC IMPORT Import of Block using Global Variables fails

© 2017, General Electric Company https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 12/11/2017


Fixed Issues Page 9 of 9

9.50 3 DE4029 LD PLC VARIABLES PME Hangs when the Value Resolution of Relocated Variable dialog is displayed during a download.
9.50 3 DE4030,00449750 LD PLC CONVERT Fix issue with converting DeviceNet from 90-30 to RX3i
9.50 3 TT185193 PCM GENERAL History Report doesn't function with IE 11 in use
9.50 3 TT185194 PCM GENERAL Unable to get the Checked Out Projects Report with IE 11 in use
9.50 3 TT185195 PCM GENERAL Clicking a iFIX or CIMPLICITY project node in the Navigator window brings up a script error when IE 11 is in use

9.50 3 TT185196 PCM GENERAL Comparison Report shows up with compare results missing when IE 11 is in use
9.50 3 TT185197 PCM GENERAL Download to PC Device operation of RSLogix 5/500/5000 project fails with a script error
9.50 3 00398653,TT185198 PCM GENERAL PME crashes when trying to set the Communication Type property for a LM9030/9070 project
9.50 3 TT185200 PCM PLANT LAYOUT The pages of the sample layout 'GenericLayout' show up blank in the InfoViewer when IE 11 is in use
9.50 3 00392922 , 00395469 VIEW RUNTIME Alarms Buffering Enhancement
9.50 3 US 19411 VIEW RUNTIME A new option provided in the data entry Keyboard and keypad of the Runtime object to increase its size

9.50 3 00447429 VIEW RUNTIME TrendX crashes when trying to view the log
9.50 3 DE4107 LD PLC IMPORT Import of of PSB and UDFB blocks fail
9.50 3 00384629 VIEW RUNTIME View Script Bug - AppExec numStartMode does not work in QP+
9.50 4 DE4065,00436787 LD PLC LOGIC Crash on Edit Block properties after Import of Control Modules.
9.50 4 DE4121,00437917 LD PLC LOGIC Fixes 8512 unknown validation exception that randomly occurred.
9.50 4 TT185201 PCM GENERAL Various PCM operations on custom projects fail when the Debug property of the custom project type is set to 1

9.50 4 US21053 LD PLC HWC Enable Profinet MRP Support for the EPSCPE100
9.50 4 TT185202 PCM GENERAL Custom property in the Inspector doesn't display its new value automatically after its custom edit dialog is closed

9.50 4 00354563 VIEW RUNTIME QuickPanel + n/a QP View update via CFcard deleted user
9.50 4 00388366 VIEW RUNTIME Logging to Historian on a QP+
9.50 4 00361102 VIEW EDITOR QP+ Enhanced security doesn`t work
9.50 4 TT185203,00407902 PCM 3RD PARTY COMPONENTS PME crashes when adding GE Fanuc CNC project
9.50 4 DE4098 LD PLC IMPORT Import Control Module from file does not bring in CM ID
9.50 4 DE3949, 00436787 LD PLC IMPORT Crash on Edit Block properties after Import of Control Modules
9.50 4 DE4088, 00459037 LD PLC IMPORT Possibly Different Tags mapped to same memory symbolic memory area?
9.50 4 00395033 VIEW RUNTIME SetDisplayBrightness to turn on the backlight
9.50 4 DE4169 LD PLC LOGIC SIZE_OF in ST could return wrong size in specific case
9.50 4 DE4064 LD PLC IMPORT Upload 9.6 project to 9.0 or 9.5 version should not be allowed
9.50 5 00474434 VIEW RUNTIME Error with License in PME
9.50 5 00474557 VIEW RUNTIME pme950 sim3 - Server Busy error in Machine Edition
9.50 6 DE4227, 00478381 PME DOWNLOAD Config NE status on download, verify config says equal
9.50 6 DE4206, 00473136 LD PLC IMPORT Block Export and Import
9.50 6 DE4201, 00462930 PME LOGIC Mystery Xfer Behaviour
9.50 6 DE4185, 00463701 LD PLC ST Trying to move one array to another array in structure text getting error "8028 variable is too small for parameter"

9.50 6 DE4264 PME HWC Crash when adding variable to VersaMax PNS IO Terminal
9.50 6 00362116 LD PC RUNTIME LD PC Drivers - Ethernet IOFaults - IC200EBI001
9.50 6 00470913 VIEW RUNTIME Runtime Crash when trying to execute SQL command dbFileSQL
9.50 6 00482659 VIEW RUNTIME Problem with dbSQL SELECT
9.50 6 00491664 VIEW RUNTIME Unable to download to Older Quickpanels
9.50 6 00431572 LD PC RUNTIME Outputs dropping out, QP+ IC200EBI001 with ME 9.0 Sim 6
9.50 6 00436999 VIEW COMMUNICATIONS PME 9.50 - Target Viewer Crashed on connect to a target
9.50 6 00441401 VIEW RUNTIME PME 9.5 - Windows 10 -locking up when downloading to a Win target
9.50 6 00448660 LD PC RUNTIME QP+ 7" - Control Ethernet Driver COM Drop with VersaMax EBI001
9.50 6 00464078 VIEW RUNTIME Quickpanel QPICxxxxxxxx - trying to download to old quickpanel and is getting error 8272 binary file exceeds allowable size.
9.50 6 00474605 VIEW RUNTIME PME 9.50 SIM 3 - Out of Memory Error on TCP QP Download
9.50 6 00474665 VIEW RUNTIME Proficy Machine Edition 9.5- Error:Unable to convert database type to match string tag
9.50 6 00477368 VIEW IMPORT PME 9.5 - import QuickPanel Jr crashes
9.50 6 00480039 VIEW RUNTIME out of memory error when attempting download to qpj-3xxxx
9.50 6 00480352 VIEW RUNTIME PME 9.5 sim4 problem supporting an older Quickpanel 7.4
9.50 6 00480514 VIEW COMMUNICATIONS Target Viewer does not work at Windows 10 build 1703
9.50 6 00484360 VIEW COMMUNICATIONS pme v9.50 - unable to connect to old quickpanel
9.50 6 00485201 VIEW RUNTIME PME 9.50 - TCP QP CQPICTDE0000-A project download PME crash with OUT OF Memory Error
9.50 6 00492016 VIEW EDITOR DH485 driver on QP+
9.50 6 00493051 VIEW RUNTIME PME 9.50 TCP QP - Out of Memory Error on TCP QP download
9.50 6 00497688 view COMMUNICATIONS PME 9.50 - Target Viewer Crashed on connect to a target
9.50 6 DE4266 LD PLC HWC Recoverable Local Memory Error Setting Missing from CPE400 HWC Faults Tab
9.50 6 DE4274, 00485846 LD PLC LOGIC Crash with "Catastrophic Failure" error
9.50 6 DE4275, 00485849 LD PLC LOGIC Software will not validate and crashes
9.50 6 DE4233, 00478148 LD PLC LOGIC Crashes PME: will not show rung 69
9.50 6 DE4272, 00475691 LD PLC LOGIC PME can crash when viewing reference addresses in LD editor
9.50 6 DE4279 LD PLC HWC PME Store fails with embedded PNC and PROFINET Device with HSB Redundancy enabled
9.50 6 DE4253, 00481936 LD PLC HWC Addition of ETM will change all EGD to new adapter
9.50 6 DE4214, 00474626 LD PLC HWC Unable to assign IO variables to ALG630 in versamax PNS
9.50 6 DE4276, 00485851 LD PLC LOGIC Program File Corrupted
9.50 6 DE4245 LD PLC GENERAL CPE400/CPE330 Redundancy REQUIRES Background Window Timer (ms) = 5ms
9.50 6 DE4205, 00472992 LD PLC HWC Unhandled exception when editing profinet device
9.50 6 DE4255, 00440013 LD PLC GENERAL Multi-Instance connection issue with 2 or more PLCs