w w w . t ra n sfo r m e r s - m a g a z i n e . co m 87
FLUIDS
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 89
FLUIDS
Table 3. Meaning of the identifying letter codes in the ordering designation of mineral oil according to IEC 60296
Example 1. For order for inhibited high grade recycled oil for transformers: TRAI.
Example 2. For order for uninhibited unused oil for transformers: TVBU.
Example 3. For order for inhibited high-grade unused oil for switchgear: SVAI.
Example 4. For order for trace inhibited recycled oil for switchgear: SRBT.
Transformer 0 1,800 − 10
Transformer − 20 1,800 − 30
Transformer − 30 1,800 − 40
a
for low ambient temperature applications; in other cases, the value shall be discussed between the user and manufacturer
All mineral insulating oils are physically ties are summarised in Chapter 7 of IEC 12. Conclusion
miscible with each other and are consid- 60296 (Ed. 5). Such general properties are,
ered to result, after homogenisation, in a e.g., electrostatic charging tendency (ECT), With the items listed above, IEC 60296
single homogeneous phase and without gassing tendency, thermal properties, aro- (Ed. 5) gives better answers to the indus-
precipitation of insoluble substances, or matic content, lubricating properties, par- try and also addresses environmental and
formation of turbidity. The mixture, how- ticle content, etc. In case limit values are sustainability requirements.
ever, can show different properties from necessary for the correct functioning of
the original oils, for example, density, a certain type of equipment, these values
viscosity, total sulphur content, oxidation must be clarified and negotiated between
Bibliography
stability, or stray gassing. customer and manufacturer. [1] IEC 60296, Ed. 4.0, Fluids for electro-
technical applications – unused miner-
Mineral insulating oils of the same class al insulating oils for transformers and
and type, the same group, same LCSET, 11. Transformer oil equivalents switchgear, Ed. 4.0, 2012
and containing the same types of additives (informative, new, Annex D of
are considered to be compatible with each IEC 60296) [2] TOR-WG D1.70, Functional prop-
other in mixtures up to 10 % with no need erties of modern insulating liquids
for additional testing. For all known oil parameters there are for transformers and similar electri-
standards for measuring as well as in the cal equipment, https://www.cigre.org/
If oils of a different class, type, group, ASTM and in the IEC world. Some of userfiles/files/News/2018/TOR_WG_
LCSET, or type of additives are mixed, the them deliver the same values, and some of D1_70_Functional_properties_of_mod-
resulting mixture shall be classified and them do not. It is sometimes difficult for a ern_insulating_liquids_for_transform-
tested according to Table 1 and Table 2. user to carry out an evaluation and com- ers_and_similar_electrical_equipment.
parison between results achieved with dif- pdf, current 4 September 2020
ferent standards.
10. General properties [3] IEC 60076-7, Power Transformers.
Of course, there are further mineral oil Annex D is the first attempt to provide Part 7: Loading Guide for mineral oil
properties, which can be of importance, but guidance on standard measuring procedure immersed power transformers, Ed. 2.0,
no general limit values exist. These proper- equivalents, based on equivalency of results. 2018
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 91