Metasys 10 Integration with CCURE + victor

Integration Highlights
 Metasys/ CCURE – Overview
o Security Panel online/offline CCURE Access Control and victor Video Management Systems are now fully
status integrated w ith Metasys through a VND Integration driver installed on the NAE85
o Door statuses/Access softw are or NAE55 hardw are. This driver enables the NxE to speak to the CCURE
o Input status for contact 9000 and victor server over w eb services.
switches
o Outputs for other door locks
such as Active and Inactive.

 Metasys/victor
o Audio Alert Status
o Camera Alert Status Failure
o Camera Storage Status
o Video Recorder Alert Status
o Video Recorder Protection
o Video Recorder Storage Status

 Video Analytics Features


o Motion detection
o Motion in a certain direction
o Object entered or exited the Component Requirements
frame of view To integrate CCURE / victor systems, the follow ing requirements are needed:
o Perimeter protection  CCURE 9000 installed on a server - Version 2.70
o Object lingering in view  victor installed on a unified installation or on a separate server- Version 5.2
o Crowd or queue formation  NAE85 installed on its ow n server or NAE55 – Version 10.0 or later
o Face detected  CCURE and victor w eb service license active on the server
o License plate recognition  Ethernet connection betw een CCURE 9000, victor and NAE.
o Video lost or dark frame System Requirements
detection Supported OS Windows Server Windows Server Windows Server
o Light change 2016 (64-bit) 2012 R2 with 2012 (64-bit)
o Spot or area temperature Update 1 (64-bit)
alarms (using IR capable
cameras) Supported Hardware 2 GB RAM 160 GB hard disk
o User alarms from the Victor minimum space minimum
system
o Video streaming

© 2018 Johnson Controls. All Rights Reserved. Revision Information


Ty co and the product names listed above are marks and/or registered marks. Unauthorized use is strictly prohibited.
Product offerings and specifications are subject to change without notice. Actual products may vary from photos.
Not all products include all features. Availability varies by region; contact your sales representative.
Access Control Features
The CCURE integration into Metasys w ill provide visibility of access control panel and door status and activity as w ell as other types of
inputs associated w ith access control including:
 Security Panel online/offline status
 Door statuses such as Normal, Door Forced, Held Open, Locked, Unlocked, Momentary Unlocked, Open Closed, Badge
Access Granted, Badge Access Denied.
 Door Access Granted
 Input status for contact sw itches, etc. such as Active, Inactive, Armed, and Disarmed.
 Outputs for other door locks such as Active and Inactive.

Video Status Features


 Audio Alert Status include Normal, Audio Recording Failure, and Audio Loss
 Camera Alert Status include Normal, Video Loss, Video Pipeline Failure, Video Stream Failure, Video Recording Failure, Dark
Frame Detection
 Camera Storage Status include Normal and Max Retention
 Recorder Archive Storage Status include Normal and Degraded
 Video Recorder Alert Status include Normal, Overheat, Reboot, Alarm Recovery Completed, Sensor Alarm
 Video Recorder Protection Status include None, Monitor, Failover, Primary Active, Primary Not Active
 Video Recorder Storage Status include Normal, Disk Full, Raid Degradation, Volume Missing, No Volumes, Volume Corrupt,
Volume Failed, New Volume, Volume Re-added, Unhealthy Disk, and Disk Temperature

Video Analytics Features (Events only into Metasys)


 Motion detected in general or in a specific area of the camera view , or motion detected in the foreground or background.
 Motion in a certain direction
 Object entered or exited the frame of view
 Perimeter protection
 Object lingering in view
 Crow d or queue formation
 Face detected
 License plate recognition
 Video lost or dark frame detection
 Light change
 Spot or area temperature alarms (using IR capable cameras)
 User alarms from the Victor system
 Video streaming failures

© 2018 Johnson Controls. All Rights Reserved. Revision Information


Ty co and the product names listed above are marks and/or registered marks. Unauthorized use is strictly prohibited.
Product offerings and specifications are subject to change without notice. Actual products may vary from photos.
Not all products include all features. Availability varies by region; contact your sales representative.