Professional Documents
Culture Documents
8 Air Conditioning Unit
8 Air Conditioning Unit
Replacing
Op nbr
Removing
1. Poke out and remove the lock strip, see [Invalid linktarget] .
Figure 1
Removing lock strip
Installing
5. Install the lock strip with the aid of tool 14 211 207, see [Invalid linktarget] .
CAUTION
Turn the hook on the tool in the direction the strip is being installed.
Figure 2
Installing lock strip
Service Information
Adjusting possibilities
Figure 1
Operator seat, mechanically sprung
1. Back-rest inclination
2. Seat inclination
3. Seat height
4. Longitudinal adjustment
5. Lumbar support
6. Height limiter with locking function;
Figure 2
Seat with air suspension
1. Back-rest inclination
2. Seat inclination
3. Seat height
4. Longitudinal adjustment
5. Lumbar support
6. Height limiter with locking function;
Removing
2. Loosen and remove the four hexagon socket head bolts (M6) retaining the seat to the attaching bracket.
4. Lay the seat on its back and pull to extend the scissors-like linkage.
5. Remove the air hose, the nipple and the nut which locks the air spring.
6. Remove the attaching bolt (hex socket 6 mm) and take out the air spring. See [Invalid linktarget] .
Figure 1
Installing
8. Install the nut and the nipple. Lock with locking fluid medium.
11. Install the seat and tighten down with the four hexagon socket head bolts.
1. Slacken both hexagon socket head bolts for the back-rest on the left side of the seat.
2. Install a washer (part No. 14214375-9) on the front hexagon socket head bolt.
Figure 1
4. Hold the washer with a 22 mm open end spanner or an adjustable spanner and tighten down the front hexagon
socket head bolt.
6. If further adjustment is required, install a washer on the right side of the seat as well.
Service Information
Maintenance advice
Make sure that the functions of the seat are not blocked by objects on the floor.
Check that the parts of the seat belt are not damaged. In case of damage, replace the whole seat belt kit.
If the air-suspended seat does not retain its set position, check that the air system is not leaking.
Check for play at the slide rails. Max. 1 mm (0.04 in) longitudinally and max. 1 mm (0.04 in) sideways. If the play
exceeds these values, replace the slide rails. Lubricate the slide rails.
Check that oil does not leak out of the shock absorber. Replace in case of a leak.
Check the seat attachment against the floor. Check that none of the bolts are loose.
WARNING
If protective bellows is missing, there is risk of pinching in the lever system.
Service Information
Figure 1
Operator seat, height adjustment
1. Spacer sleeve
Service Information
Safety instructions
WARNING
Only use refrigerant containers approved for this purpose when filling / emptying refrigerant.
Never fill a refrigerant container to more than 60 % of its gross weight classification. There must be sufficient space
left for the gas to cope with the increase in pressure because of the change in volume arising during temperature
changes, for example caused by exposure to sunlight.
Never expose a refrigerant container to temperatures above 50 °C (122 °F). Even a correctly filled container may be
at risk of exploding at temperatures above 50 °C (122 °F).
Always carry out service work in well ventilated areas. R134a vapours are heavier than air and may therefore
accumulate in low lying areas, such as an inspection pit.
Service Information
Removing
2. Remove the attaching plate together with the fan unit, see [Invalid linktarget] .
Figure 1
Attaching plate with fan unit
Figure 2
Fan unit
1. Fan housings
2. Engine
3. Fan wheels
Installing
9. Install the attaching plate together with the fan unit in the machine.
Removing
3. Pinch the hoses on either side of the valve with two pairs of pliers, see [Invalid linktarget] .
Figure 1
Installing
5. Install the new valve and connect the hoses. Remove the pliers.
Figure 2
1. Clip
2. Lever
6. Install the control wire.
Adjusting: Heat control valve lever (2) must be right up against the stop lug when the temperature control arm is
approximately 2.5 mm (0.1 in) away from its end position. If necessary loosen clip (1) and adjust the position of the
control arm, see [Invalid linktarget] and [Invalid linktarget] .
Figure 3
Check
7. Set the temperature control to the minimum position, see [Invalid linktarget] . Start and run the engine until warm.
Feel the hoses to the heating unit, [Invalid linktarget] . They must not be warm. Turn off the engine.
Figure 4
WARNING
If the machine is equipped with AC, take care not to damage any connections to the evaporator.
2. Remove the attaching plate together with the fan unit, see [Invalid linktarget] .
Figure 1
Attaching plate with fan unit
3. Pinch the heater radiator hoses (1), [Invalid linktarget] , with two pairs of pliers. Disconnect the hoses from the
heater radiator.
Figure 2
1. Close the door and all windows. Start and run the engine until it has reached normal working temperature.
2. Turn the fan switch (4) to position 3 (maximum speed). Set recirculation control (3) to the recirculation position and
heating control (2) to minimum position, see [Invalid linktarget] and [Invalid linktarget] . Start the air conditioning.
Figure 1
Air conditioning, serial No. –2900
1. Measuring point
2. Heating control
3. Recirculation position
4. Switches
3. Run the engine at approx. 1 800 rpm. Measure the temperature at the front right air nozzle on the instrument
panel. Keep measuring for approximately 5 minutes. See [Invalid linktarget] and [Invalid linktarget] .
Figure 2
Air conditioning, serial No. 2901–, US 60001–
1. Measuring point
2. Heating control
3. Recirculation position
4. Switches
4. At some time during the testing the temperature should drop to around +4 – +9 °C (+39 – +48 °F) at a normal
ambient temperature of 20°C (68 °F) and normal air humidity.
Service Information
Figure 1
Air conditioning, principle diagram
1. Expansion valve
2. Evaporator
3. Thermostat
4. Compressor
5. Capacitor
6. Receiver drier (no sight glass) (lubricating oil PAG-type) Part No. 1161425
A. Fluid
B. Gas
C. Gas
D. Fluid
The service points (connections) in the form of quick-action couplings are positioned on the receiver drier (high
pressure) and behind a plate at the lower, front, right edge of the cab (low pressure).
There is no sight glass, which means that weighing scales must be used in order to fill the correct amount of R134a.
NOTE!
In order to fill and empty R134a systems, special equipment is required, e.g. FRS-10GS.
Equipment intended for a R12 system must not be used for a R134a system, with the exception of the vacuum pump.
The refrigerants R12 and R134a must not be mixed. Otherwise there is a risk of compressor breakdown.
Service Information
Figure 1
Figure 2
Weighing scales 9812444
Vacuum pumping
1. Connect yellow hose (Y2) with vacuum gauge between vacuum pump and outlet No. 6 on the filling and recycling
station, see [Invalid linktarget] .
Figure 1
Vacuum pumping
2. Connect yellow hose (Y1) to the receiver drier on the machine and open the valve, see [Invalid linktarget] .
4. Open the breather valve on the vacuum pump and vacuum-pump for 5–10 minutes. Close the valve and vacuum-
pump for approximately a further 50 minutes.
CAUTION
The air conditioning should be vacuum-pumped to make sure that all moisture is removed from the system. As it
takes approx. 50 minutes to vacuum-pump, the time could be used for filling lubricating oil (PAG type), see [Invalid
linktarget] . Open the valve and allow the measured amount of oil to be sucked into the system. See ”Refrigerant
R134a, emptying”, point 15, see [Invalid linktarget] .
Figure 2
Filling lubricating oil
1. 9812447 Nipple
2. Oil hose 9998237
6. Test for leakage while there is a partial vacuum in the system. The partial vacuum in the system must not change
more than 0.01 MPa (0.1 bar) (1.5 psi) (during a period of approximately 10 minutes. If the partial vacuum changes
more, it is an indication that there is a leak in the system. Rectify any leaks.
Filling
7. Connect red hose to the receiver drier and yellow hose to the container, see [Invalid linktarget] .
Figure 3
Filling refrigerant
8. Place the container upside down on the weighing scales.
12. Fill the system with approximately 200 gram (7 oz) of refrigerant.
Turn off the filling and recycling station and close the valve on the container.
Wipe off any oil and blow with compressed air in the "sniffing holes" on the couplings.
Leakage check
13. Test for leakage using a leak detector and rectify any leaks, see [Invalid linktarget] .
In case of a major leak, pump out the system and rectify, see [Invalid linktarget] .
Figure 4
Leakage check
14. Open the container valve and start the filling and recycling station.
Fill according to the air conditioning specifications, total weight 2.0 +0.1 kg (4.4 +0.2 lb).
15. Close the valve on the container and turn off the filling and recycling station.
Checking pressure
16. Start the engine (and run it at approx. 1800 rpm) and start the air conditioning. Check that the low-pressure gauge
on the filling and recycling station shows 1–3 bar (14.5–44 psi) and that the high-pressure gauge shows 8–14 bar
(116–203 psi) at an ambient temperature of approximately 20 °C (68 °F).
Stop the engine.
17. Disconnect the filling and recycling station from the machine.
18. Test the function of the air conditioning according to [Invalid linktarget] .
Service Information
Refrigerant, emptying
Op nbr 87402
1. Make the service connections for the AC system accessible on the machine.
2. Connect the yellow hose to the receiver drier on the machine, see [Invalid linktarget] .
Figure 1
Connecting hose to receiver drier
3. Connect the blue hose to the low-pressure outlet under the cab, see [Invalid linktarget] .
Connect the red hose to the container for R134a, see [Invalid linktarget] .
Figure 2
Connecting hose at low-pressure outlet
4. Place the container on a weighing scales and set the weighing scales to zero, if the amount of refrigerant is to be
checked. See [Invalid linktarget] . Press button 7 on the weighing scales to set it to zero.
Figure 3
Emptying
1. Valve
CAUTION
Note that the valves are to be screwed clockwise.
7. Press button 5 to switch on voltage to the weighing scale socket 1. The lamp 230 VAC lights up, see [Invalid
linktarget] .
Figure 4
Switching on voltage
Figure 5
Filling and recycling station
9 Low-pressure gauge
12 Switch, start / stop
9. When low-pressure gauge (9), see [Invalid linktarget] , shows 0 pressure or a partial vacuum, the system has been
emptied.
CAUTION
The valves are to be screwed counter-clockwise.
13. Disconnect the hoses from the three connections on the machine and reconnect them to the respective "blind"
plugs (connections) on the filling and recycling station.
14. The refrigerant circuit can now be opened without releasing any refrigerant.
WARNING
The filling and recycling station contains pressurised oil.
15. Carefully open valve (2), see [Invalid linktarget] , on the oil separator on the station. Screw the valve inward. Drain
off any lubricating oil (PAG type) into a graduated measuring glass. Close the valve on the oil separator when all oil
has run out.
CAUTION
Top up the air conditioning with the same amount of oil as was drained off. If no lubricating oil (PAG type) runs out,
there is no need to fill any oil in the air conditioning.
Figure 6
Draining AC compressor oil
Service Information
Figure 1
A. Radio aerial
B. Telephone aerial
C. Two-way radio
Never use communication equipment, e.g. a mobile telephone, which is not correctly installed in the cab, while the machine
is running. Its signals may interfere with important electronics in the electrical system of the machine. The communication
equipment must be connected to the electrical system of the machine and connected to an external, permanent aerial
according to the instructions of the manufacturer.
All installation of electronic additional equipment must therefore be carried out according to the manufacturer"s instructions
and by competent personnel.
CAUTION
Only CE marked equipment may be installed. Leads to/from radio transmitter / telephone must not be routed close to leads
for the gear-shifting electronics. Supply and return leads should be laid together.
Voltage supply to the above optional equipment is taken from connector CRC (14 V) in the overhead panel and in the
instrument panel from a loose lead in the cable harness routed from the ceiling to connector CP (24 V).
Figure 2
D Radio
E Cable harness in right post
F Loose lead in cable harness from ceiling to connector CP.
Cable red marked +12V.
G Voltage converter
H Connector CRC
I Telephone / two-way radio
Thank you for your purchase.
Have a nice day.
file:///C|/Users/app/Documents/yeqiwen-END.txt[2014/6/26 14:43:09]