项目名称
PROJECT Gibe III Hydro Electric Project
文件名称
TITLE Calculation Report of Generator Netural Grounding
4、Bus capacitance:0.006975 uF
6、GCB capacitance:0.26 uf
C0=0.933075+0.006975+0.0092+0.26=1.20925
XC0=106/314×1.20925 =2633.6Ω
The capacitive reactance-to-ground (xcg) seen at the neutral is equal to the parallel combination
of the capacitive reactance-to-ground of all three phases, which is one-third of 2633.6 Ω and
XCG=XC0/3=2633.6/3=877.9Ω
2、A 15000 v/400 v distribution transformer is used to ground the generator neutral. Therefore, the
secondary resistor must be calculated so that the effective neutral resistance is equal to or less
than rn(= 877.9 ω), as shown in equation:Transformer ratio
N=15/(0.4)=37.5
2
Secondary resistance RSEC=RN/N =877.9/37.52=0.624Ω
3、The exact value of resistance is not critical. Equipment capacitive tolerances and the resistance
change due to temperature rise cause this calculation to be only an estimate. The conservative
approach for lower transient overvoltage is with a greater i2r loss or higher generator fault current.
Reducing the ohmic value of the secondary resistor to reduce transient overvoltage may tend to
increase damage resulting from ground faults. A slightly smaller resistor could be selected based
upon operational practice of the resistor and the rated transformer capacity (KVA). the maximum
-1-
ISEC MAX=VSEC MAX/RSEC= (VGEN(L-L)/ 3 )×(1/N)×(1/RSEC)
=(15000/ 3 )×(1/37.5)×(1/0.624)
= 370A
2
4、Resistor power PR=I R=3702×0.624=85.43KW
5)Insulation level:BIL,(peak)105 kV
Industrial frequency withstand voltage,(virtual value,1min)45 kV
6)Voltage tap:±2.5%
7) Insulation grade: H
2、Resistor:
3、Isolator:
1) Model: Gn19-15/400
2) Type:single phase、50hz、indoor
3) Rated voltage(kv): 15
4、Current transformer:
-2-
1) Type: primary LMZ- 0.5, 15/1A
6、Measurement:1600×1200×1900 mm3
7、Level of protection:IP20
-3-