You are on page 1of 31

www.CRAworld.

com

Final Report

Acoustic Assessment Report


Dufferin Organics Processing Facility
Dufferin Waste Management Facility
Toronto, Ontario

Prepared for: City of Toronto

Conestoga-Rovers & Associates


651 Colby Drive
Waterloo, Ontario N2V 1C2

April ϵ, 2014 • 081337 • Report No. 16


City of Toronto Acoustic Assessment Report

Table of Contents
Page

Section 1.0 Introduction ............................................................................................... 1

Section 2.0 Noise Source Summary............................................................................... 2

Section 3.0 Point-of-Reception Summary ..................................................................... 2

Section 4.0 Sound Level Data ....................................................................................... 3


4.1 Short-Term Steady State Sound Level Measurements .................................... 3

Section 5.0 Assessment Criteria .................................................................................... 4

Section 6.0 Impact Assessment .................................................................................... 4


6.1 Steady-State Sound Levels ............................................................................... 4

Section 7.0 Conclusions ................................................................................................ 6

List of Figures
(Following Text)

Figure 1 Site & Noise Source Location Plan


Figure 2 Point-Of-Reception Location Plan

List of Tables
(Following Text)

Table 1 Noise Source Summary


Table 2 Point-Of-Reception Noise Impact – Unattenuated Sound Levels
Table 3 Acoustic Assessment Summary – Steady State Sound Levels

081337 (16)
April 2014
City of Toronto Acoustic Assessment Report

List of Appendices

Appendix A Zoning Map


Appendix B Summary of Insignificant Noise Sources
Appendix C Noise Specification and Worst-Case Simultaneous Operations Summary
Appendix D CADNA/A Sample Calculation for POR1

081337 (16)
April 2014
City of Toronto Acoustic Assessment Report

Section 1.0 Introduction

Conestoga-Rovers & Associates (CRA) was retained to prepare an Acoustic Assessment Report (AAR) for
the City of Toronto (City) Dufferin Organics Processing Facility (DOPF) located at the Dufferin Waste
Management Facility (DWMF) facility (Site) located at 35 Vanley Crescent in Toronto, Ontario. The AAR
has been prepared as an Application for an Amendment to the Ministry of the Environment (MOE)
Environmental Compliance Approval (ECA) No. 5459-8CSRVT dated March 11, 2011. The AAR is being
amended as follows:

• The removal of the existing two HVAC units (Point Sources S5 and S6)
• The addition of 8 new Air Heating Units (AHU) (Point Sources S7-S14)
• The removal of the existing three truck routes (Line Sources T1-T3)
• The addition of one new truck route (Line Source T4)

The City operates the DOPF to process source-separated organic (SSO) material at the Site. The DOPF
will operate 24 hours per day, 7 days per week.

The AAR presented herein provides an evaluation of the potential worst-case environmental noise
impacts from DOPF noise emissions generated during normal operations on the sensitive receptors
located nearest to the DOPF. The AAR was prepared consistent with the following MOE guidance:

• NPC-233, "Information to be Submitted for Approval of Stationary Sources of Sound, October 1995"
• "Appendix A – Supporting Information for an Acoustic Assessment Report or Vibration Assessment
Report Required by a Basic Comprehensive C of A" as specified in the MOE guidance entitled "Basic
Comprehensive Certificates of Approval (Air) – User Guide, April 2004"
• NPC-300, "Environmental Noise Guideline – Stationary and Transportation Sources – Approval and
Planning"
• NPC-103, "Procedures, August 1978"

The Site plan, as provided in Figure 1, is owned by the City and is zoned as G (Greenbelt Zone) and M3
(Industrial Zone 3). The site is zoned Industrial M3 under the Corporation of the Township of North York
Zoning By-law 7625 (as amended). Under North York Zoning By-law 7625, all waste management
activities are considered to be Essential Services and are therefore compliant with the zoning by-law.

The recent City of Toronto Zoning By-law 569-2013, which came into force on May 9, 2013, supersedes
the North York Zoning By-law 7625; but only where this new City Zoning By-law applies. The new City
Zoning By-law does not apply to the Site, as illustrated in Appendix A. The provisions of the North York
Zoning By-law were not repealed by the new City Zoning By-law and thus remain in-force for the Site.

081337 (16)
April 2014 1
City of Toronto Acoustic Assessment Report

The DWMF is located in an Acoustical Class 2 area defined by NPC-300 as an area with an acoustical
environment that has qualities representative of both Class 1 and Class 3 areas:

• Sound levels characteristic of Class 1 during daytime hours


• Low evening and night background sound level defined by natural environment and infrequent
human activity during nighttime hours

The topography surrounding the DOPF is essentially flat.

Section 2.0 Noise Source Summary

This AAR focused on the sound emissions from the noise sources identified at the DOPF with the
potential to adversely impact the sensitive receptors. The Noise Source Summary is provided in Table 1
and the noise source locations are identified on Figure 1. CRA evaluated the following significant noise
sources identified by the Cadna modelling ID number:

• Biofilter Exhaust Stack – Point Source (S1)


• Truck Route – Line Source (T4)

There are no sources of impulse or vibration at the DOPF.

The other noise sources at the DOPF have not been included since they are considered insignificant
contributors to the overall DOPF noise level at the sensitive receptors. A summary of insignificant noise
sources is provided in Table B.1 of Appendix B.

Section 3.0 Point-of-Reception Summary

The identification of appropriate sensitive point(s)-of-reception is necessary to conduct the assessment


for the DOPF. A "point-of-reception" is any point on the premises of a person where sound, originating
from other than those premises, is received. The point-of-reception may be located on permanent or
seasonal residences, hotels/motels, nursing/retirement homes, rental residences, hospitals,
campgrounds, parks, schools, cemeteries, or places of worship.

The objective of this AAR is to determine the predictable worst-case 1-hour equivalent sound level
(1-hour Leq) at the worst-case point(s)-of-reception. The worst-case point(s)-of-reception is (are)
defined as the sensitive receptor(s) with the greatest potential exposure to the DOPF noise sources due
to proximity and direct line-of-sight exposure.

081337 (16)
April 2014 2
City of Toronto Acoustic Assessment Report

The worst-case sensitive point(s)-of-reception (POR) are:

• POR1 – nearest façade of a single-storey daycare on Loadstar Road approximately 220 metres (m)
east of the site (1.5 m above grade [AG])
• POR2 – nearest façade of a two-storey residence on Stanstead Drive approximately 445 m east of
the site (4.5 m AG)

The location of the worst-case PORs, are identified on Figure 2.

All POR locations within 500 m of the DOPF were considered; however, the noise impact at only the
worst-case and most exposed PORs are presented herein.

Section 4.0 Sound Level Data

4.1 Short-Term Steady State Sound Level Measurements

Short-term sound level measurements were taken using a Larson Davis LXT System. The Larson-Davis
LXT System includes a Type 1 Precision Sound Level Meter (SLM), Model LXT (Serial Number 0001181); a
pre-amplifier, Model PRMXT1 (Serial Number 0229); and a 1/2-inch free field condenser microphone
Model 377M05 (Serial Number 100881). The SLM was calibrated and checked at 114 decibels (dBA)
before and after each measurement period using a Larson-Davis CAL200 Acoustic Calibrator (Serial
Number 4730).

The sound descriptor used in the evaluation for the DOPF noise sources is the 1-hour Leq, which is a
time weighted energy average of the source. The Leq sound measurements consisted of short-term
readings taken over an observation time of 15-second intervals with the detector in slow response using
A-weighting, such that the sound levels are reported in units of dBA. All measurements were recorded
and stored in the SLM. In accordance with NPC-103 "Procedures, August 1978" (NPC-103), at least three
measurements were taken for each of the Facility noise sources.

Sound level measurements were taken at a reference distance depending on the height of the source(s)
being measured and proximity to other noise sources. The location and reference distance were
selected to ensure that the reference measurement was a valid representation of the dominant
source(s) being measured. The measurement location was selected in order to measure the sound
emitted in the direction of the worst-case exposure in line with the nearby sensitive receptors wherever
possible and/or to minimize the influence of other noise sources and directivity issues.

081337 (16)
April 2014 3
City of Toronto Acoustic Assessment Report

Sound level measurements were conducted in September 20, 2010, and December 6, 2012, during
normal operating conditions. Meteorological conditions consisted of low winds (less than 15 km/hr),
low humidity and no precipitation.

The noise measurement data is provided in Appendix C and summarized in Table C.1.

Section 5.0 Assessment Criteria

Assessment criteria may be determined for a POR based on the MOE's minimum exclusionary sound
level limits, as presented in NPC-300, in comparison to the background sound levels experienced in the
area. The "background sound level" is defined as the sound level present in the environment that is
produced by noise sources other than those from the DOPF, and would include traffic sound levels and
sound from neighboring industrial/commercial activity. The higher of the two assessment criteria is
selected for purpose of assessment.

The DOPF is located in an Acoustic Class 2 Area. Class 2 Areas have the following minimum sound level
limits expressed as a 1-hour Leq that can be applied to assess the sound levels emitted by the Facility
noise sources:

Time of Day Minimum Sound Level

Façade Point-of-Reception
7:00 a.m. to 11:00 p.m. 50 dBA
11:00 p.m. to 7:00 a.m. 45 dBA

Outdoor Points-of-Reception
7:00 a.m. to 7:00 p.m. 50 dBA
7:00 p.m. to 11:00 p.m. 45 dBA

The applicable noise criteria at the points-of-reception are based on the higher of the background sound
level and the MOE's minimum sound level limits. CRA has selected the MOE minimum limits to be
conservative.

Section 6.0 Impact Assessment

6.1 Steady-State Sound Levels

The worst-case assessment of steady-state noise sources at the selected points-of-reception was based
on measured sound levels and manufacturer's data. Cadna A Acoustical Modelling Software (Cadna A),

081337 (16)
April 2014 4
City of Toronto Acoustic Assessment Report

version 4.4, was used to model the potential impacts of the significant noise sources. Cadna A calculates
sound level emissions based on the ISO 9613-2 standard "Acoustics – Attenuation of Sound during
Propagation Outdoors". Cadna A output files for POR1 is provided in Appendix D.

The worst-case cumulative Facility-wide unattenuated sound levels estimated at the receptor(s)
included attenuation affects as applicable for all significant noise sources. Off-site buildings were input
as intervening structures. The heights of the buildings that were used in the model are presented on
Figure 1.

Cadna A modelling assumptions used in this AAR included:

• Noise Sources: All sources were modelled using the 1/1 octave band data from source
measurements, manufacturer's sound level data or MOE approved reference materials. Moving
point-line sources are based on the input sound level data and the physical dimensions of the travel
path for the mobile sources.
• Noise Source Elevation: The heights of the sources are summarized in Table C.1 of Appendix C.
• Reflection Order: A maximum reflection order of 1.0 was used to evaluate indirect noise impact
from one reflecting surface.
• Ground Absorption: The model was set up with a conservative ground absorption factor of 0.25 and
the areas of grass/soft ground were input with ground absorption of 1.0.
• Receptor elevation: POR receptor heights were modelled appropriately to represent the worst-case
elevation as detailed in Section 3.0.
• Time-weighted Adjustment: Time-weighted adjustments for sources that do not operate
continuously are summarized in Table C.1
• Tonality: No sources were observed to be tonal.
• Building Surfaces: The buildings are modelled as reflective surfaces.

On-site truck traffic, identified as Sources T4 was modelled as moving-point line sources. Truck activity
is summarized in Table C.1.

The sound power level estimation for the Biofilter is provided in Table C.2.

The unattenuated day and nighttime sound levels estimated at the worst-case PORs are summarized in
Table 2.

A noise abatement action plan is not required for this Facility.

081337 (16)
April 2014 5
City of Toronto Acoustic Assessment Report

Section 7.0 Conclusions

The unattenuated steady-state and impulse sound levels estimated at the PORs are below the MOE's
minimum exclusionary daytime and nighttime sound level limits, as summarized in Table 3.

081337 (16)
April 2014 6
0 20 40 60m

LANDSCAPING LEGEND
SHED
PROPERTY BOUNDARY
HT = 3m S1 SIGNIFICANT NOISE SOURCE

S14 TRUCK ROUTE


No. 75
FIBRE TRANSFER AREAS OF GROUND ABSORPTION
BUILDING S2A S12
S1 S11
HT = 7.3m
S2B
S13

HT = 8.9m T4
No. 700
BIOFILTER, EQUIPMENT ORGANICS PROCESSING
& STACK FACILITY
(HT = 8m) DIGESTER
#2 HT = 7.3m
S4 S9 S7
S10
S3 S8
DIGESTER
#1

VANLEY CRES.
LITY
500 ACI
No. ERY F
COV
AL RE
ERI
MAT

WEIGH SCALES
TE
GA

300
No. FER
NS
BU TRA DING
L
ILD BUI
IN
G

ADMINISTRATION
BUILDING

figure 1
STORAGE PAD SITE AND NOISE LOCATION PLAN
ACOUSTIC ASSESSMENT REPORT
DUFFERIN ORGANICS PROCESSING FACILITY

81337-D.1(016)GN-WA001 APR 8/2014


622700 622800 622900 623000 623100 623200 623300 623400 623500 623600
4846800

4846800
POR2
4846700

4846700
POR1
4846600

4846600
4846500

4846500
4846400

4846400
4846300

4846300
622700 622800 622900 623000 623100 623200 623300 623400 623500 623600

Point Source ACOUSTIC ASSESSMENT REPORT


Line Source DUFFERIN WASTE MANAGEMENT FACILITY - TORONTO, ONTARIO
Building
Ground Absorption FIGURE 2
Receiver POINT-OF-RECEPTION LOCATION PLAN
TABLE 1 Page 1 of 1

NOISE SOURCE SUMMARY


CITY OF TORONTO, DUFFERIN ORGANICS PROCESSING FACILITY
TORONTO, ONTARIO

Unattenuated
Cadna A Sound Power Source Sound Noise Control
ID Source Description Source Type Level (1) Location (2) Characteristics (3) Measures (4)
(dBA)

S1 Biofilter Exhaust Stack Point 99.8 O S U


S2a Biofilter Fan #1 Point 90.7 O S U
S2b Biofilter Fan #2 Point 90.6 O S U
S3 Flare Point 79.6 O S U
S4 Flare Compressor Point 85.4 O S U
S7 AHU 1 Point 71.3 O S U
S8 AHU 2 Point 71.3 O S U
S9 AHU 3 Point 71.3 O S U
S10 AHU 4 Point 71.3 O S U
S11 AHU 6 Point 71.3 O S U
S12 AHU 7 Point 71.3 O S U
S13 AHU 5 Point 71.3 O S U
S14 AHU 8 Point 71.3 O S U
T4 Truck Route Moving Point - Line 109.9 O S U

Notes:
(1) Sound Power Level (PWL) in dBA calculated from sound pressure level and reference distance and includes + 5 dBA tonal penalty if applicable.
Resulting PWL based on dimensions of vertical area source or travel path and equipment movements for moving point line/area sources.
(2) Source Location:
O - located/installed outside of building
I - located/installed inside of building
(3) Sound Characteristics:
S - Steady
Q - Quasi Steady Impulsive
I - Impulsive
B - Buzzing
T - Tonal
C - Cyclic
TW - Time Weighted
(4) Noise Control Measures:
S - silencer, acoustic louvre, muffler
A - acoustic lining, plenum
B - barrier, berm, screening
L - lagging
E - acoustic enclosure
O - other
U - uncontrolled
AC - administrative control
CRA 081337-16 T1-T3
TABLE 2 Page 1 of 1

POINT-OF-RECEPTION NOISE IMPACT - UNATTENUATED SOUND LEVELS


CITY OF TORONTO, DUFFERIN ORGANICS PROCESSING FACILITY
TORONTO, ONTARIO

Lodestar Road Daycare Stanstead Drive Residence Facade


POR1 POR2
Cadna A Distance to Distance to
ID Source Description Receptor Sound Level (1) Receptor Sound Level (1)
(m) (Leq) (m) (Leq)
S1 Biofilter Exhaust Stack 307 35.4 dBA 520 32.3 dBA
T4 Truck Route 270 42.9 dBA 520 38.4 dBA
Total Facility Sound Level (1-hour Leq): 43.6 dBA 39.4 dBA

Notes:
(1) Sound Level at the Receptor was calculated using Cadna A Acoustical Modelling Software.

CRA 081337-16 T1-T3


TABLE 3 Page 1 of 1

ACOUSTIC ASSESSMENT SUMMARY - STEADY STATE SOUND LEVELS


CITY OF TORONTO, DUFFERIN ORGANICS PROCESSING FACILITY
TORONTO, ONTARIO

Unattenuated
Point-of- Sound Level at Verified by Compliance with
Reception Point-of-Reception Point-of-Reception Acoustic Performance Performance
ID Description Predicted Audit Limit (1) Limit
(Leq) (Yes/No) (Leq) (Yes/No)
POR1 Lodestar Road Daycare 43.6 (dBA) No 50.0 (dBA) (2) Yes
POR2 Stanstead Drive Residence Facade 39.4 (dBA) No 45.0 (dBA) Yes

Note:
(1) Minimum MOE sound level limits defined in NPC-300.
(2) Limited to Daytime Use.

CRA 081337-16 T1-T3


City of Toronto Acoustic Assessment Report

Appendix A
Zoning Map

081337 (16)
April 2014
0 25 50 75m

OPEN SPACE NATURAL

UTILITY AND TRANSPORTATION

SITE COMMERCIAL
COMMERCIAL RESIDENTIAL
COMMERCIAL RESIDENTIAL
EMPLOYMENT
EMPLOYMENT INDUSTRIAL
INSTITUTIONAL

SOURCE: CITY OF TORONTO ZONING BY-LAW 569-2013.


figure A.1
LAND USE ZONING DESIGNATION PLAN
DUFFERIN ORGANICS PROCESSING FACILITY

81337-D.1(016)GN-WA002 APR 4/2014


City of Toronto Acoustic Assessment Report

Appendix B
Summary of Insignificant Noise Sources

081337 (16)
April 2014
Page 1 of 1
TABLE B.1

INSIGNIFICANT NOISE SOURCE SUMMARY


CITY OF TORONTO, DUFFERIN ORGANICS PROCESSING FACILITY
TORONTO, ONTARIO

ECA
Source
ID Source Description Comments

S5 Condensate Pump Source Estimated to be < 20 dBA at worst-case POR.


H-1 & H-2 Boilers Source Estimated to be < 20 dBA at worst-case POR.
H-3, H-4, H-5, H-8, & H-10 Comfort Heating Equipment Source Estimated to be < 20 dBA at worst-case POR.
NA Digesters Source Estimated to be < 20 dBA at worst-case POR.
S2a-b Biofilter Fans #1 & #2 Source Modelled to be < 20 dBA at worst-case POR.
S3 Flare Source Modelled to be < 20 dBA at worst-case POR.
S4 Flare Compressor Source Modelled to be < 20 dBA at worst-case POR.
S7-S14 AHUs Source Modelled to be < 20 dBA at worst-case POR.

CRA 081337-16 APPB-TB.1


City of Toronto Acoustic Assessment Report

Appendix C
Noise Specification and Worst-Case Simultaneous Operations Summary

081337 (16)
April 2014
Page 1 of 1

TABLE C.1

ACOUSTIC ASSESSMENT SUMMARY - STEADY STATE SOUND LEVELS


CITY OF TORONTO, DUFFERIN ORGANICS PROCESSING FACILITY
TORONTO, ONTARIO

Unadjusted Sound Pressure


Total Sound Tonal Penalty Reference Height Equipment Movements
Cadna Noise Source Description Data Quality 1/1 Octave Band Data Power Level Assessment Distance Absolute Above Roof Day Night Speed
ID 31.5 63 125 250 500 1K 2K 4K 8K (dBA) dB(A) (m) (m) (m) (#/Hour) (#/Hour) (km/h) Reference/Comments
S1 Biofilter Exhaust Stack PWL (dB) 0.0 97.7 101.3 102.3 95.3 94.3 91.3 86.3 82.3 106.5 NO 0 0.00 40.00 - N/A N/A N/A Manufactuerer's specifications and engineering estimate, refer to Table C.2
A-weighted correction -39.4 -26.2 -16.1 -8.6 -3.2 0.0 1.2 1.0 -1.1
PWL (dBA) -39.4 71.5 85.2 93.7 92.1 94.3 92.5 87.3 81.2 99.8
S2a Biofilter Fan #1 SPL Data (dB) 74.3 72.7 71.8 73.3 72.4 68.3 68.4 68.6 71.7 NO 0 1.40 1.00 - N/A N/A N/A Manufactuerer's specifications
PWL (dB) 88.2 86.6 85.7 87.2 86.3 82.2 82.3 82.5 85.6 95.2
A-weighted correction -39.4 -26.2 -16.1 -8.6 -3.2 0.0 1.2 1.0 -1.1
PWL (dBA) 48.8 60.4 69.6 78.6 83.1 82.2 83.5 83.5 84.5 90.7
S2b Biofilter Fan #2 SPL Data (dB) 72.7 75.9 70.7 71.9 68.4 67.4 66.0 64.8 75.2 NO 0 1.40 1.20 - N/A N/A N/A Manufacturer's specifications
PWL (dB) 86.6 89.8 84.6 85.8 82.3 81.3 79.9 78.7 89.1 95.3
A-weighted correction -39.4 -26.2 -16.1 -8.6 -3.2 0.0 1.2 1.0 -1.1
PWL (dBA) 47.2 63.6 68.5 77.2 79.1 81.3 81.1 79.7 88.0 90.5
S3 Flare SPL Data (dB) 78.0 77.2 75.4 68.6 67.4 65.0 57.0 55.5 49.2 NO 0 0.90 7.50 - N/A N/A N/A Source Measurement - Sept. 20, 2010
PWL (dB) 88.1 87.3 85.5 78.7 77.5 75.1 67.1 65.6 59.3 92.3
A-weighted correction -39.4 -26.2 -16.1 -8.6 -3.2 0.0 1.2 1.0 -1.1
PWL (dBA) 48.7 61.1 69.4 70.1 74.3 75.1 68.3 66.6 58.2 79.6
S4 Flare Compressor SPL Data (dB) 67.8 68.9 70.9 68.8 64.4 63.4 63.1 71.5 64.1 NO 0 1.00 1.40 - N/A N/A N/A Source Measurement - Sept. 20, 2010
PWL (dB) 78.8 79.9 81.9 79.8 75.4 74.4 74.1 82.5 75.1 88.6
A-weighted correction -39.4 -26.2 -16.1 -8.6 -3.2 0.0 1.2 1.0 -1.1
PWL (dBA) 39.4 53.7 65.8 71.2 72.2 74.4 75.3 83.5 74.0 85.4
S7 AHU1 PWL (dB) 0.0 44.1 56.4 67.6 65.4 67.6 64.4 60.7 54.6 72.9 NO 0 0.00 4.30 1.50 N/A N/A N/A Representative of sources S8-14
A-weighted correction -39.4 -26.2 -16.1 -8.6 -3.2 0.0 1.2 1.0 -1.1 Manufacturer's specifications
PWL (dBA) -39.4 17.9 40.3 59.0 62.2 67.6 65.6 61.7 53.5 71.3
T4 Truck Route SPL Data (dB) 0.0 86.0 81.0 74.0 76.0 73.0 72.0 69.0 60 NO 0 10.00 2.00 - 8 8 15 Referenced from UK Department for Environment, Food and Rural Affairs
PWL (dB) 31.0 117.0 112.0 105.0 107.0 104.0 103.0 100.0 91.0 119.0 15 (Defra) Noise Database for Construction Noise document
A-weighted correction -39.4 -26.2 -16.1 -8.6 -3.2 0.0 1.2 1.0 -1.1 15 Transport Truck Route - 26ton 235kw
PWL (dBA) -8.4 90.8 95.9 96.4 103.8 104.0 104.2 101.0 89.9 109.9 DEFRA Table 1(c) #16

CRA 081337-16 APPC-TC.1-TC.2


Page 1 of 1
TABLE C.2

BIOLFILTER STACK (S1) SOUND POWER LEVEL ESTIMATION


CITY OF TORONTO, DUFFERIN ORGANICS PROCESSING FACILITY
TORONTO, ONTARIO

63 125 250 500 1k 2k 4k 8k


Biofilter fan 1 (PWL dB) 108 109 106 99 98 95 90 86
Biofilter fan 2 (PWL dB) 108 109 106 99 98 95 90 86

total 111 112 109 102 101 98 93 89

Duct attenuation (dB per 0.3 m) 0.1 0.08 0.05 0.05 0.05 0.05 0.05 0.05
Total duct attenuation 13.3 10.7 6.7 6.7 6.7 6.7 6.7 6.7

Attenuated Stack (PWL dB) 97.7 101.3 102.3 95.3 94.3 91.3 86.3 82.3

Stack height (total duct length) 40 m round, straight metal

Notes:
(1) Duct attenutation provided from Hoover & Keith "Noise Control for Buildings and Manufacturing Plants" Table 9-3
for round, striaght metal ducting.
(2) It has been conservatively assumed that the sound from both fans is being emitted at the top of the stack after
ducting losses as calculated above.

CRA 081337-16 APPC-TC.1-TC.2


City of Toronto Acoustic Assessment Report

Appendix D
CADNA/A Sample Calculation for POR1

081337 (16)
April 2014
Configuration
Parameter Value
General
Country (user defined)
Max. Error (dB) 0.00
Max. Search Radius (m) 2000.00
Min. Dist Src to Rcvr 0.00
Partition
Raster Factor 0.50
Max. Length of Section (m) 1000.00
Min. Length of Section (m) 1.00
Min. Length of Section (%) 0.00
Proj. Line Sources On
Proj. Area Sources On
Ref. Time
Reference Time Day (min) 60.00
Reference Time Night (min) 60.00
Daytime Penalty (dB) 0.00
Recr. Time Penalty (dB) 6.00
Night-time Penalty (dB) 10.00
DTM
Standard Height (m) 0.00
Model of Terrain Triangulation
Reflection
max. Order of Reflection 1
Search Radius Src 100.00
Search Radius Rcvr 100.00
Max. Distance Source - Rcvr 1000.00 1000.00
Min. Distance Rvcr - Reflector 1.00 1.00
Min. Distance Source - Reflector 0.50
Industrial (ISO 9613)
Lateral Diffraction some Obj
Obst. within Area Src do not shield On
Screening Excl. Ground Att. over Barrier
Dz with limit (20/25)
Barrier Coefficients C1,2,3 3.0 20.0 0.0
Temperature (°C) 10
rel. Humidity (%) 70
Ground Absorption G 0.25
Wind Speed for Dir. (m/s) 3.0
Roads (???)
Railways (???)
Aircraft (???)
Strictly acc. to AzB
Receiver
Name: Lodestar Road Daycare
ID: POR1
X: 623320.25
Y: 4846641.45
Z: 1.50

Point Source, ISO 9613, Name: ''Biofilter Exhaust Stack'', ID: ''S1''
Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623013.05 4846640.08 40.00 0 0 99.8 99.8 0.0 -2.1 60.8 1.1 0.3 0.0 0.0 0.0 -0.0 -0.0 35.4 35.4

Point Source, ISO 9613, Name: ''Biofilter Fan #1'', ID: ''S2a''
Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623014.07 4846641.10 1.00 0 0 90.7 90.7 0.0 0.0 60.7 3.6 0.6 0.0 0.0 14.8 -0.0 -0.0 11.1 11.1

Point Source, ISO 9613, Name: ''Biofilter Fan #2'', ID: ''S2b''
Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623012.02 4846638.49 1.20 0 0 90.6 90.6 0.0 0.0 60.8 5.7 -0.9 0.0 0.0 19.3 -0.0 -0.0 5.7 5.7

Point Source, ISO 9613, Name: ''Flare'', ID: ''S3''


Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 622980.11 4846572.63 7.50 0 0 79.6 79.6 0.0 0.0 61.8 1.2 -0.9 0.0 0.0 4.6 -0.0 -0.0 12.9 12.9

Point Source, ISO 9613, Name: ''Flare Compressor'', ID: ''S4''


Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 622994.67 4846579.01 1.40 0 0 85.4 85.4 0.0 0.0 61.4 6.0 -0.7 0.0 0.0 12.9 -0.0 -0.0 5.7 5.7

Point Source, ISO 9613, Name: ''AHU 1'', ID: ''S7''


Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623082.37 4846587.89 4.55 0 0 71.3 71.3 0.0 0.0 58.7 1.6 -1.3 0.0 0.0 0.0 -0.0 -0.0 12.3 12.3
2 623082.37 4846587.89 4.55 1 0 71.1 71.1 0.0 0.0 59.4 1.9 -1.1 0.0 0.0 0.0 -0.0 1.0 9.9 9.9
3 623082.37 4846587.89 4.55 1 0 71.3 71.3 0.0 0.0 59.4 1.8 -0.3 0.0 0.0 8.3 -0.0 1.0 1.1 1.1

Point Source, ISO 9613, Name: ''AHU 2'', ID: ''S8''


Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623053.94 4846578.97 8.82 0 0 71.3 71.3 0.0 0.0 59.7 1.8 -1.0 0.0 0.0 0.0 -0.0 -0.0 10.8 10.8

Point Source, ISO 9613, Name: ''AHU 3'', ID: ''S9''


Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623053.71 4846579.20 8.82 0 0 71.3 71.3 0.0 0.0 59.8 1.8 -1.0 0.0 0.0 0.0 -0.0 -0.0 10.8 10.8

Point Source, ISO 9613, Name: ''AHU 4'', ID: ''S10''


Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623053.41 4846579.50 8.82 0 0 71.3 71.3 0.0 0.0 59.8 1.8 -1.0 0.0 0.0 0.0 -0.0 -0.0 10.8 10.8

Point Source, ISO 9613, Name: ''AHU 6'', ID: ''S11''


Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623079.58 4846646.34 8.82 0 0 71.3 71.3 0.0 0.0 58.6 1.6 -0.3 0.0 0.0 0.0 -0.0 -0.0 11.3 11.3
2 623079.58 4846646.34 8.82 1 0 71.3 71.3 0.0 0.0 59.2 1.7 -0.6 0.0 0.0 0.0 -0.0 1.0 10.0 10.0

Point Source, ISO 9613, Name: ''AHU 7'', ID: ''S12''


Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623080.11 4846647.12 8.82 0 0 71.3 71.3 0.0 0.0 58.6 1.6 -0.3 0.0 0.0 0.0 -0.0 -0.0 11.3 11.3
Point Source, ISO 9613, Name: ''AHU 7'', ID: ''S12''
Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
2 623080.11 4846647.12 8.82 1 0 71.3 71.3 0.0 0.0 59.2 1.7 -0.6 0.0 0.0 0.0 -0.0 1.0 10.0 10.0

Point Source, ISO 9613, Name: ''AHU 5'', ID: ''S13''


Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623048.94 4846634.58 8.82 0 0 71.3 71.3 0.0 0.0 59.7 1.8 -0.6 0.0 0.0 0.0 -0.0 -0.0 10.5 10.5

Point Source, ISO 9613, Name: ''AHU 8'', ID: ''S14''


Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623038.88 4846665.82 4.55 0 0 71.3 71.3 0.0 0.0 60.0 1.8 0.2 0.0 0.0 2.1 -0.0 -0.0 7.1 7.1

Line Source, ISO 9613, Name: ''Truck Route '', ID: ''T4''
Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
1 623032.33 4846546.14 2.00 0 0 95.7 95.7 0.0 0.0 60.6 1.9 -2.0 0.0 0.0 6.6 -0.0 -0.0 28.6 28.6
2 623099.57 4846566.35 2.00 0 0 95.7 95.7 0.0 0.0 58.3 1.5 -1.3 0.0 0.0 7.9 -0.0 -0.0 29.3 29.3
3 623133.88 4846584.16 2.00 0 0 89.1 89.1 0.0 0.0 56.8 1.3 -0.2 0.0 0.0 7.9 -0.0 -0.0 23.3 23.3
4 623134.88 4846595.48 2.00 0 0 85.8 85.8 0.0 0.0 56.6 1.3 -0.3 0.0 0.0 3.7 -0.0 -0.0 24.4 24.4
5 623137.81 4846628.62 2.00 0 0 94.9 94.9 0.0 0.0 56.2 1.3 0.4 0.0 0.0 0.0 -0.0 -0.0 37.0 37.0
6 623071.23 4846691.18 2.00 0 0 95.9 95.9 0.0 0.0 59.1 1.6 0.9 0.0 0.0 0.0 -0.0 -0.0 34.3 34.3
7 623122.49 4846666.91 2.00 0 0 93.2 93.2 0.0 0.0 57.0 1.4 1.3 0.0 0.0 0.0 -0.0 -0.0 33.6 33.6
8 623003.31 4846685.38 2.00 0 0 91.1 91.1 0.0 0.0 61.1 1.9 -0.2 0.0 0.0 0.0 -0.0 -0.0 28.3 28.3
9 622998.78 4846671.64 2.00 0 0 83.6 83.6 0.0 0.0 61.2 2.0 -0.1 0.0 0.0 2.1 -0.0 -0.0 18.5 18.5
10 622997.32 4846667.21 2.00 0 0 84.2 84.2 0.0 0.0 61.2 2.0 0.3 0.0 0.0 5.8 -0.0 -0.0 14.9 14.9
11 622992.52 4846652.62 2.00 0 0 91.3 91.3 0.0 0.0 61.3 2.0 -0.3 0.0 0.0 7.4 -0.0 -0.0 20.9 20.9
12 622986.97 4846635.77 2.00 0 0 87.1 87.1 0.0 0.0 61.5 2.0 -1.5 0.0 0.0 14.5 -0.0 -0.0 10.7 10.7
13 622981.00 4846617.64 2.00 0 0 91.7 91.7 0.0 0.0 61.6 2.0 -1.6 0.0 0.0 14.7 -0.0 -0.0 15.0 15.0
14 622975.27 4846600.24 2.00 0 0 86.3 86.3 0.0 0.0 61.8 2.0 -1.2 0.0 0.0 10.7 -0.0 -0.0 12.9 12.9
15 622843.73 4846477.85 2.00 0 0 97.5 97.5 0.0 0.0 65.0 2.7 -2.4 0.0 0.0 4.9 -0.0 -0.0 27.2 27.2
16 622835.96 4846482.18 2.00 0 0 96.6 96.6 0.0 0.0 65.1 2.7 -2.3 0.0 0.0 4.8 -0.0 -0.0 26.3 26.3
17 622796.46 4846502.38 2.00 0 0 80.6 80.6 0.0 0.0 65.7 2.8 -2.1 0.0 0.0 5.1 -0.0 -0.0 9.2 9.2
18 622974.98 4846571.75 2.00 0 0 82.6 82.6 0.0 0.0 61.9 2.1 -1.7 0.0 0.0 9.9 -0.0 -0.0 10.4 10.4
19 622975.74 4846568.53 2.00 0 0 82.2 82.2 0.0 0.0 61.9 2.1 -1.7 0.0 0.0 10.1 -0.0 -0.0 9.7 9.7
20 622977.35 4846561.62 2.00 0 0 87.6 87.6 0.0 0.0 61.9 2.1 -1.7 0.0 0.0 9.9 -0.0 -0.0 15.4 15.4
21 622979.27 4846553.42 2.00 0 0 84.8 84.8 0.0 0.0 61.9 2.1 -1.6 0.0 0.0 11.0 -0.0 -0.0 11.4 11.4
22 622980.58 4846547.84 2.00 0 0 84.7 84.7 0.0 0.0 61.9 2.1 -1.9 0.0 0.0 12.8 -0.0 -0.0 9.8 9.8
23 622981.74 4846543.29 2.00 0 0 82.9 82.9 0.0 0.0 61.9 2.1 -2.0 0.0 0.0 12.8 -0.0 -0.0 8.0 8.0
24 622985.35 4846530.63 2.00 0 0 90.7 90.7 0.0 0.0 61.9 2.1 -2.1 0.0 0.0 5.9 -0.0 -0.0 22.9 22.9
25 623029.47 4846705.80 2.00 0 0 89.5 89.5 0.0 0.0 60.5 1.8 0.2 0.0 0.0 0.0 -0.0 -0.0 27.0 27.0
26 622957.10 4846454.33 2.00 0 0 91.9 91.9 0.0 0.0 63.2 2.3 -2.4 0.0 0.0 6.9 -0.0 -0.0 22.0 22.0
27 622974.10 4846591.86 2.00 0 0 86.7 86.7 0.0 0.0 61.9 2.1 -1.1 0.0 0.0 8.9 -0.0 -0.0 15.0 15.0
28 622974.36 4846582.26 2.00 0 0 87.3 87.3 0.0 0.0 61.9 2.1 -1.4 0.0 0.0 9.1 -0.0 -0.0 15.6 15.6
29 622974.54 4846575.29 2.00 0 0 82.9 82.9 0.0 0.0 61.9 2.1 -1.6 0.0 0.0 9.6 -0.0 -0.0 11.0 11.0
30 622989.36 4846510.41 2.00 0 0 90.7 90.7 0.0 0.0 62.0 2.1 -2.2 0.0 0.0 6.5 -0.0 -0.0 22.3 22.3
31 623014.09 4846700.98 2.00 0 0 89.2 89.2 0.0 0.0 60.9 1.9 -0.2 0.0 0.0 0.0 -0.0 -0.0 26.6 26.6
32 622987.86 4846509.81 2.00 0 0 90.2 90.2 0.0 0.0 62.1 2.1 -2.2 0.0 0.0 6.5 -0.0 -0.0 21.8 21.8
33 622984.84 4846489.61 2.00 0 0 90.3 90.3 0.0 0.0 62.3 2.1 -2.2 0.0 0.0 6.3 -0.0 -0.0 21.8 21.8
34 622905.24 4846449.21 2.00 0 0 92.1 92.1 0.0 0.0 64.2 2.5 -2.4 0.0 0.0 5.6 -0.0 -0.0 22.2 22.2
35 622975.19 4846472.12 2.00 0 0 90.6 90.6 0.0 0.0 62.7 2.2 -2.3 0.0 0.0 6.6 -0.0 -0.0 21.4 21.4
36 622984.24 4846490.51 2.00 0 0 90.1 90.1 0.0 0.0 62.3 2.1 -2.2 0.0 0.0 6.3 -0.0 -0.0 21.6 21.6
37 622905.24 4846448.90 2.00 0 0 91.9 91.9 0.0 0.0 64.2 2.5 -2.4 0.0 0.0 5.6 -0.0 -0.0 22.0 22.0
38 622994.49 4846528.81 2.00 0 0 89.4 89.4 0.0 0.0 61.8 2.0 -2.1 0.0 0.0 6.1 -0.0 -0.0 21.6 21.6
39 622975.49 4846471.52 2.00 0 0 90.3 90.3 0.0 0.0 62.7 2.2 -2.3 0.0 0.0 6.7 -0.0 -0.0 21.1 21.1
40 622932.38 4846444.68 2.00 0 0 91.2 91.2 0.0 0.0 63.8 2.4 -2.4 0.0 0.0 6.5 -0.0 -0.0 21.1 21.1
41 622930.87 4846444.08 2.00 0 0 90.9 90.9 0.0 0.0 63.8 2.4 -2.4 0.0 0.0 6.4 -0.0 -0.0 20.7 20.7
42 622950.47 4846448.60 2.00 0 0 89.7 89.7 0.0 0.0 63.4 2.3 -2.4 0.0 0.0 6.9 -0.0 -0.0 19.5 19.5
43 622964.04 4846457.95 2.00 0 0 89.1 89.1 0.0 0.0 63.1 2.3 -2.4 0.0 0.0 7.0 -0.0 -0.0 19.2 19.2
44 622882.63 4846458.55 2.00 0 0 89.8 89.8 0.0 0.0 64.5 2.6 -2.4 0.0 0.0 5.5 -0.0 -0.0 19.6 19.6
45 623046.63 4846550.44 2.00 1 0 73.0 73.0 0.0 0.0 60.4 10.0 -3.0 0.0 0.0 5.4 -0.0 1.0 -0.8 -0.8
46 623051.77 4846551.98 2.00 1 0 77.6 77.6 0.0 0.0 60.2 9.8 -2.9 0.0 0.0 5.3 -0.0 1.0 4.2 4.2
47 623056.39 4846553.37 2.00 1 0 70.8 70.8 0.0 0.0 60.1 9.7 -2.9 0.0 0.0 0.0 -0.0 1.0 2.9 2.9
48 623083.59 4846561.54 2.00 1 0 86.9 86.9 0.0 0.0 60.3 2.7 -2.3 0.0 0.0 5.3 -0.0 1.0 19.9 19.9
Line Source, ISO 9613, Name: ''Truck Route '', ID: ''T4''
Nr. X Y Z Refl. Freq. LxT LxN K0 Dc Adiv Aatm Agr Afol Ahous Abar Cmet RL LrT LrN
(m) (m) (m) (Hz) dB(A) dB(A) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) dB(A) dB(A)
49 623104.42 4846567.80 2.00 1 0 87.3 87.3 0.0 0.0 60.1 2.7 -2.1 0.0 0.0 0.0 -0.0 1.0 25.5 25.5
50 623117.30 4846571.67 2.00 1 0 86.0 86.0 0.0 0.0 60.1 2.7 -1.7 0.0 0.0 0.0 -0.0 1.0 24.0 24.0
51 623059.91 4846554.43 2.00 1 0 78.7 78.7 0.0 0.0 60.2 2.0 -1.9 0.0 0.0 5.0 -0.0 1.0 12.4 12.4
52 623063.47 4846555.50 2.00 1 0 84.4 84.4 0.0 0.0 60.2 2.0 -1.8 0.0 0.0 6.6 -0.0 1.0 16.4 16.4
53 623067.83 4846556.81 2.00 1 0 81.8 81.8 0.0 0.0 60.1 2.0 -2.0 0.0 0.0 4.9 -0.0 1.0 15.8 15.8
54 623070.84 4846557.71 2.00 1 0 81.6 81.6 0.0 0.0 60.1 2.0 -1.9 0.0 0.0 5.3 -0.0 1.0 15.1 15.1
55 623076.52 4846559.42 2.00 1 0 86.2 86.2 0.0 0.0 60.1 2.0 -1.8 0.0 0.0 5.2 -0.0 1.0 19.8 19.8
56 623048.81 4846551.10 2.00 1 0 84.6 84.6 0.0 0.0 60.4 1.9 -1.6 0.0 0.0 7.5 -0.0 1.0 15.4 15.4
57 623052.92 4846552.33 2.00 1 0 81.3 81.3 0.0 0.0 60.3 1.9 -1.5 0.0 0.0 7.5 -0.0 1.0 12.0 12.0
58 623055.96 4846553.24 2.00 1 0 82.5 82.5 0.0 0.0 60.3 1.9 -1.7 0.0 0.0 4.8 -0.0 1.0 16.2 16.2
59 623033.18 4846546.40 2.00 1 0 76.2 76.2 0.0 0.0 62.1 3.2 -2.5 0.0 0.0 12.5 -0.0 1.0 -0.0 -0.0
60 623083.12 4846561.40 2.00 1 0 88.4 88.4 0.0 0.0 60.3 2.0 -1.0 0.0 0.0 9.5 -0.0 1.0 16.5 16.5
61 623093.21 4846564.44 2.00 1 0 84.9 84.9 0.0 0.0 60.2 2.0 -1.3 0.0 0.0 0.0 -0.0 1.0 23.0 23.0
62 623135.45 4846601.89 2.00 1 0 63.7 63.7 0.0 0.0 56.6 22.2 -2.5 0.0 0.0 19.2 -0.0 1.0 -32.8 -32.8
63 623135.91 4846607.11 2.00 1 0 64.9 64.9 0.0 0.0 56.5 22.1 -2.4 0.0 0.0 16.9 -0.0 1.0 -29.2 -29.2
64 623140.33 4846657.06 2.00 1 0 60.6 60.6 0.0 0.0 61.2 37.9 -2.6 0.0 0.0 0.0 -0.0 1.0 -36.8 -36.8
65 623088.67 4846683.05 2.00 1 0 90.8 90.8 0.0 0.0 59.1 1.8 -0.3 0.0 0.0 0.0 -0.0 1.0 29.2 29.2
66 623043.99 4846703.87 2.00 1 0 86.7 86.7 0.0 0.0 61.5 3.0 -2.3 0.0 0.0 11.5 -0.0 1.0 12.0 12.0
67 623104.52 4846675.66 2.00 1 0 56.4 56.4 0.0 0.0 61.7 11.5 -1.8 0.0 0.0 0.0 -0.0 1.0 -16.0 -16.0
68 623078.73 4846687.68 2.00 1 0 86.9 86.9 0.0 0.0 60.5 2.0 -1.1 0.0 0.0 16.4 -0.0 1.0 8.1 8.1
69 623070.12 4846691.69 2.00 1 0 86.1 86.1 0.0 0.0 60.6 2.1 -1.0 0.0 0.0 14.3 -0.0 1.0 9.0 9.0
70 623138.33 4846659.19 2.00 1 0 63.9 63.9 0.0 0.0 61.2 37.9 -2.6 0.0 0.0 0.0 -0.0 1.0 -33.7 -33.7
71 623108.45 4846673.75 2.00 1 0 78.0 78.0 0.0 0.0 61.8 11.7 -1.8 0.0 0.0 0.0 -0.0 1.0 5.4 5.4
72 623036.21 4846706.52 2.00 1 0 80.7 80.7 0.0 0.0 61.6 3.0 -2.3 0.0 0.0 10.8 -0.0 1.0 6.5 6.5
73 623024.41 4846705.26 2.00 1 0 83.7 83.7 0.0 0.0 62.2 3.2 -2.5 0.0 0.0 11.1 -0.0 1.0 8.7 8.7
74 622974.29 4846584.72 2.00 1 0 68.6 68.6 0.0 0.0 61.9 41.2 -3.3 0.0 0.0 23.7 -0.0 1.0 -55.8 -55.8
75 623019.55 4846704.06 2.00 1 0 80.7 80.7 0.0 0.0 62.2 3.2 -2.5 0.0 0.0 11.9 -0.0 1.0 4.8 4.8
76 623017.44 4846702.87 2.00 1 0 77.1 77.1 0.0 0.0 62.2 3.2 -2.5 0.0 0.0 12.0 -0.0 1.0 1.2 1.2
77 623012.23 4846699.93 2.00 1 0 85.6 85.6 0.0 0.0 62.1 3.2 -2.5 0.0 0.0 11.3 -0.0 1.0 10.5 10.5
78 623007.65 4846697.33 2.00 1 0 62.9 62.9 0.0 0.0 62.1 3.2 -2.4 0.0 0.0 11.3 -0.0 1.0 -12.3 -12.3

You might also like