Sls - Uls
Sls - Uls
net/publication/301398451
CITATIONS READS
0 4,157
3 authors, including:
Some of the authors of this publication are also working on these related projects:
Studies on Steel Building Components and Connections under Environmental and Cyclic Loads View project
All content following this page was uploaded by Rama Raju Kunadharaju on 24 May 2016.
Abstract
Consideration of site specific lateral loading due to wind or earthquake loads along with vertical
gravity loads is important for finding the behaviour of tall buildings. The design criteria for tall
buildings are strength, serviceability and human comfort. In the present study, the analysis and design
of a 3B+G+40 storey residential building for earthquake and wind loads is carried out considering
the member forces due to dead load, live Load, wind load and earthquake load combinations with
the partial safety factors for limit state of collapse as per Indian standard codes of practice. The
members are designed for the most critical member forces. In present study, an alternative simplified
method of considering load combinations for finding the member forces and choosing the most
critical member forces for design is suggested. The final design of members is found to be more
economical and satisfy the recommendations of most of the international codes of practice.
Keywords: Tall buildings; seismic loads; wind loads; response spectrum method; gust factor
method.
Introduction
In general, for design of tall buildings both wind as well as earthquake loads need to be considered.
The important factors need to be considered in seismic resistant design of structures are, the
characteristics of the structure (type, height and base dimensions of the structure, damping of the
structure, importance of the structure and ductility of the structure) and the location of the structure
(earthquake zone in which the structure is located - gives characteristics of the earthquake ground
motion represented by amplitude of ground motion i.e., Peak Ground Acceleration (PGA) and the
site soil conditions). As per IS 875(Part 3):1987, when wind interacts with a building, both positive
and negative pressures occur simultaneously, and the building must have sufficient strength to resist
the applied loads from these pressures to prevent wind induced building failure. The magnitude of
the wind pressure is a function of exposed basic wind speed, topography, building height, internal
pressure, and building shape.
In the present study, a simplified method for designing a 3B+G+40 multi-stored residential
building against earthquake and wind loads is proposed. The building is on soft soil and assumed to
be located at Mumbai. The member forces are calculated with load combinations for limit state of
collapse and limit state of serviceability given in Table 18 of IS 456: 2000 and the members are
669
2014
c ICCMS Organisers. Published by Research Publishing. All rights reserved.
ISBN:978-981-09-1139-3 || doi:10.3850/978-981-09-1139-3 154
designed for the most critical member forces among them. The building is subjected to self-weight,
dead load, and live load as per IS 875(Part 1, Part 2):1987. Safety of the structure is checked with
respect to the limits prescribed for base shear, roof displacement, inter-storey drifts and accelerations
in codes of practice and other references in literature on effects of earthquake and wind loads on
buildings. A new method of design with less number of load combinations of dead load (DL), live
load (LL), earthquake load (EL) and wind load (WL) with partial safety factors for earthquake and
wind loads equal to 1.0 as suggested by most of the international codes (Table 1) is proposed. This
method requires less design effort, and it can be used for non-orthogonal buildings (building not
oriented along the orthogonal horizontal direction) and helps in arriving at more economical sections
in designs as compared to method given in IS 456:2000. Eurocode 2-2004 also suggests same
procedure for earthquake loads, but it does not require to be multiplied any factor for responses. But
for wind loads it prescribes a partial safety factor of 1.5.
The building has been provided with wall type RCC columns as shown in Figure 1. The
dimensions of columns suggested in INSDAG report, 2007 with rectangular, L, T and Star sections
are given in Table 3 and shown in Figure 1. In the analysis, the L and T shaped columns with D and B
Modeling of loads
The basic loads considered in this study are dead load (DL), live loads (LL), earthquake loads
(EL) and wind loads (WL). The summary of DL and LL considered for the building is given in Table
4. In load combinations involving Imposed Loads (LL), IS 1893 (Part I):2002 recommends for loads
up to and including 3 kN/m2, 25% of the imposed load to be considered for seismic weight calculations.
The earthquake loads are assigned in X and Y directions as ELx and ELy respectively as per IS
1893(Part 1): 2002.
Table 3 Column schedule
Column C1 C2 C3 C4 C5
B
Base to 5th floor 0.5×1.25 1.25×0.5 B B
26.7
4.95 3.80 4.60 4.60 3.80 4.95
B1 B2 B2 B1
10
C3 C3 C2 C3 C3
B1
B1
B2
4.4
B2
B2
B2
B2
C2 C2 C2 C2 C2 C2 C2
9
B2 B2 B2 B2 B2 B2
C1 C1
B2
4.435
B2
B1
8 B1
B1 B1 B1 B1
C3 B2 C1 C1 B2 C3
7
B1
B1
B2
B1
B2
4.57
B2 C4 C5 C5 C4 B2 C1
6
30.485
C1 B1 B1 B1
B2
3.375
B1
B2
6.79
C1 B1 B1 B1 C1
5
B2 C4 C5 C5 C4 B2
4.57
B2
B2
B1
B1
B1
C1 C1 C3
4
B2 B1 B2
C3 B1 B1 B1
B1
4.435
B2
B1
B2
3
C1 C1
2.25
B2 B2 B2 B2 B2 B2 C2
2
C2 C2 C2 C2 C2 C2
B2
B2
B1
B2
B2
B2
B1
4.4
C3 C3 C2 C3 C3
1
B1 B2 B2 B1
1 2 3 4 5 6 7 8 9
Note:All Dimensions are in 'm' B1 B2 Shear wall
Figure 1 Plan of the Building
As per Clause 7.8.2 of IS 1893(Part 1): 2002, for buildings having height greater than 90m,
dynamic analysis with time history or response spectrum method need to be performed to obtain the
design seismic force, and its distribution to along the height of the building and to the various lateral
resisting elements. Since the building taken for study is having a height of 148.9m (more than 90 m
Table 5 Natural frequency, periods and Mass participation factor for different modes
Mode 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Frequency (Hz) 0.24 0.25 0.28 0.76 0.76 0.83 1.36 1.37 1.40 1.97 2.01 2.02 2.61 2.64 2.74 3.32 3.38 3.45 3.52 3.56
Period (s) 4.2 4.0 3.6 1.3 1.3 1.2 0.7 0.7 0.7 0.5 0.5 0.5 0.4 0.4 0.4 0.3 0.3 0.3 0.3 0.3
Mass X 0.0 73.0 73.0 73.0 87.0 87.0 91.1 91.1 91.1 92.8 92.8 92.8 94.2 94.2 94.2 94.9 94.9 94.9 94.9 94.9
Participation
Factor (%) Y 71.4 71.4 71.4 85.6 85.6 85.6 85.6 90.2 90.2 90.2 90.2 92.2 92.2 92.2 93.9 93.9 93.9 93.9 94.6 94.6
ܸ௭ ൌ ܸ ݇ଵ ݇ଶ ݇ଷ (1)
Where, Vb is basic wind speed in m/s, k1 is probability factor (risk coefficient), k2is terrain roughness
and height factor and k3 is topography factor as per Clause 5.3.3.The lateral force along wind load
on a structure on a strip area (Ae) at any height, z is found by equation,
where, Cf is force coefficient for building, calculated from Clause 6.3.2.1(Figure 4), Ae is effective
frontal area considered for the structure at height z, Pz is design pressure at height z due to hourly
mean wind obtained as ͲǤܸ௭ଶ (N/m2), G is gust factor (peak load / mean load) as per Clause 8.3. The
data considered for the gust factor method are wind speed, Vb=44m/s, force coefficient, Cf=1.38,
K1=1.07, K2 is varying with height as per Terrain Category I, K3=1, Life of the structure 100yrs,
Gust factor, G=1.787. For analysis, the lateral force Fz is considered in kN/m2, and the wind
intensities at various heights are given as input to the STAAD.Pro software as given in Table 6. From
the analysis, the base shear due to wind load for wind speed Zone III in X- and Y- direction are found
to be 13648.03 and 12072.3kN respectively.
Table 7 Degree of human discomfort and the acceleration levels (Simiu and Scanlan, 1996)
Degree of discomfort Imperceptible Perceptible Annoying Very annoying Intolerable
Acceleration (%g) <0.5 0.5 to 1.5 1.5 to 5 5 to 15 >15
Load Combinations
The variations in loads due to unforeseen increases in loads, the types of limit states are taken
into account to define the design load. The design load is given by design load = γf × characteristic
load Section 36.4 of IS 456: 2000, where γf is partial safety for the loads given in Table 18 of IS 456:
2000. After the computational model is developed and the loads are assigned, the model needs to be
analyzed for the individual load cases. The internal forces in the members (e.g., bending moment,
shear force and axial force) for earthquake and wind load cases are combined as per Table18 of IS
456: 2000, IS 1893(Part 1): 2002, Section 6.3. The building is found to be insensitive to torsional
and vertical loads. Because the building is oriented in orthogonal direction, as per clause 6.3.2.1, the
internal forces in the members (e.g., bending moment, shear force and axial force) in the building are
found from 25, DL, LL, EL and WL combinations with the partial safety factors for limit state of
collapse given in Table 8. The members are designed for the most critical member forces among
them. The analysis and design for these load combinations are given in Appendix A.
Unlike most of the international codes (Table 1), the partial safety factors given in IS 456:2000
are more than 1.0 for earthquake and wind loads. For more precise calculation of ELs, it is more
appropriate to take site specific response spectra obtained at the location of the building from
probabilistic seismic hazard analysis (PSHA) than using partial safety factor more than 1. The
numbers of EL combinations need to be taken for non-orthogonal buildings are twenty five (National
Disaster Management Authority, 2011). There is no specific method for taking WL for non-
orthogonal buildings in IS 875(Part3):1987. The present method requires more number of load cases
(more design effort) and it is highly conservative in design of buildings.
A methodology of combining the maximum value of each action effect on the structure due to
the two horizontal components of seismic action estimated by the ‘square root of the sum of the
The percentage of longitudinal and shear reinforcement required by the method given in IS
456:2000 and newly proposed method for beam at 5th floor is given in Table 11. The percentage of
reduction in longitudinal and shear reinforcement in 5th floor by new method over the method
described in IS 456:2000 is found to be 55.39%. Design moments in beams and columns, obtained
by the proposed method, satisfies the condition of strong column and weak beam requirement of
Clause 7.2. The final dimensions of beam sections are satisfying the requirement for earthquake-
induced effects mentioned in Clause 6 of Doc No. CED 39 (7941) WC.
Reinforcement details
The typical reinforcement joint details of the columns, C1 (11th to Roof) and beam, B2 joint detailing
is shown in Figure 2. The reinforcement details beam B2:L2,0, L9,0 are shown in Figure 3 and the
reinforcement details of columns, C1 (Base to 5th), C2 (11th to Roof), C34,9 (L-section), C46,8 (T-
section) and C55,6 (Star section) are shown in Figure 4. For the proposed methodology reinforcement
detailing would be same. Since, the load combination with earthquake is governing, the ductile
detailing as per IS 13920:1993 or recent Doc No. CED39 (7941) WC need to be followed. The
ductile detailing condition of relative strength of beam and column should be checked at each beam
column joint as per Clause 7.2 of Doc No. CED39 (7941) WC. The condition states that, at each
beam-column joint of a moment- resisting frame, the sum of nominal design strength of columns
meeting at that joint (with nominal strength calculated for the factored axial load in the direction of
the lateral force under consideration so as to give least column nominal design strength) along each
principal plane shall be at least 1.4 times the sum of nominal design strength of beams meeting at
that joint in the same plane,݅Ǥ ݁ǡ ߑܯ ͳǤͶߑܯ ǡ ܹ݄݁݁ݎǡ ߑܯ ൌ ܯ ܯ and ߑܯ ൌ ܯ௧ ܯ Ǥ
As an example, for joint number 678 with column C1 (11th to Roof) and beam B2, the sum of nominal
design strength of columns (ߑܯ ൌ250) is approximately equal to sum of nominal design strength
of beams (ͳǤͶߑܯ =252). i.e., ߑܯ ؆ ͳǤͶߑܯ ǤSimilar way all the joints need to be checked. If it is
not satisfied, the sections need to be revised.
In this paper, the analysis and design of a 3B+G+40-storey RCC high rise building subjected to wind
and seismic loads is carried out as per IS codes of practice. The structural model and its loading
conditions are taken from the INSDAG report, INS/PUB/104 (2007). The building is modeled as 3D
space frame using STAAD.Pro software. Base shear is found with seismic coefficient method (ṼB)
and response spectrum method (VB) as per IS 1893(Part1):2002. The analysis of the building due to
wind load is carried out using Gust factor method given in IS 875(Part3):1987. Safety of the structure
is checked against allowable limits prescribed for inter-storey drifts, base shear, accelerations and
roof displacements in codes of practice and, other references in literature on effects of earthquake
and wind loads on buildings. Member forces were found for 25 load combinations with the partial
safety factors for collapse given in IS 456: 2000, and the members were designed for the most critical
forces among them. Unlike most of the international codes (Table 1), the partial safety factors given
in IS 456:2000 are more than 1.0 for earthquake and wind loads. For more precise calculation of ELs,
it is more appropriate to take site specific response spectra obtained at the location of the building
from probabilistic seismic hazard analysis (PSHA) than using partial safety factor more than 1. The
numbers of EL combinations need to be taken for non-orthogonal buildings are 25. There is no
specific method for taking WL for non-orthogonal buildings in IS 875(Part3):1987. The present
method requires more number of load cases (more design effort) and it is highly conservative in
lo=1.0
lo=1.0 0.15
hc=3.5 0.25
lo=1.0
lo=1.0
1.0
ߑܯ ൌ ܯ ܯ ൌ ͳǤͺͳ ͳ͵Ǥ͵Ͷ ൌ ͳͺͲǤͳͷǢ ߑܯ ؆ ͳǤͶߑܯ =1.4×180.15=252.21
ܽ݊݀ߑܯ ൌ ܯ௧ ܯ ൌ ͳͳͻǤͳ ͳ͵Ͳ ൌ ʹͷͲ; ߑܯ ؆ ͳǤͶߑܯ
Figure 2 C1 (11th to Roof) and beam B2 joint detailing
Acknowledgment
This paper is being published with the kind permission of Director, CSIR-Structural Engineering
Research Centre, Chennai-600113, India. The authors thank staff of Vibration Control Group, CSIR-
SERC for their help in various stages of this study.
1.18
1.18
1.48
A' B' C'
0.495
0.495 4.95
a) Longitudinal reinforcement
0.3
2#-25Ø 2#-25Ø
2#-32Ø
0.7 2#-32Ø
2#-32Ø
2#-25Ø
0.5 0.3
1.25 1.00
36#32Ø 14#32Ø
a) C1 (Base to 5th) b) C2 (11th to Roof)
0.3 2 0.3
0.075 0.3
0.3
2# 32Ø
0.3 2# 25Ø
0.04
2.00
2# 32Ø 2# 32Ø
0.3
0.3
0.025
2.00 0.3
42 #32Ø 54#32Ø 32#32Ø & 24#25Ø
c) C34,9 (L-section) d) C4 6,8(T-section) e) C55,6 (Star section)
Note: All units are in ‘m’
Figure 4 Column reinforcement details of Rectangular, L, T and Star sections
References
Building subjected to Wind and Earthquake Loads”, The Eighth Asia-Pacific Conference on Wind
Engineering, December 10-14, 2013, Chennai, India.
IS 456: 2000, “Plain and reinforced concrete - Code of practice”, Bureau of Indian standards, New
Delhi, 2000.
IS 875 (Part 1, Part 2, Part 3 ):1987, “Code of practice for design loads (other than earthquake) for
buildings and structures”.
IS 1893 (Part 1):2002, “Criteria for earthquake resistant design of structures”, Bureau of Indian
standards, New Delhi, 2002.
IS13920: 1993, “Ductile detailing of reinforced concrete structures subjected to seismic forces - Code
of practice”, Bureau of Indian standards, New Delhi, 1993.
Islam, M. S., Ellingwood, B., Corotis, R. B., "Dynamic Response of Tall Buildings to Stochastic
Wind Load," Journal of Structural Engineering, ASCE, Volume 116, No. 11, November 1990.
Jain S. K, Murty C.V.R., “Proposed Draft Provisions and Commentary on Indian Seismic Code IS
1893 (Part I)” , IITK-GSDMA-EQ05-V4.0, IITK-GSDMA-EQ15-V3.0.
National Disaster Management Authority, (2011), “Development of Probabilistic seicmic hazard
map of india” Technical report, ISBN 978-93-80440-12-5.
Rama Raju K, Shereef M I, Nagesh R Iyer, Gopalakrishnan S, “Analysis and Design of RC Tall
Building subjected to Wind and Earthquake Loads”, The Eighth Asia-Pacific Conference on
Wind Engineering, December 10-14, 2013, Chennai, India.
Simu, E and Miyata, T. (2006), “Design of buildings and bridges for wind a practical guide for
ASCE-7 standard users and designers of special structures, John Wiley & Sons.
Simiu, E, Scanlan R. H., Wind effects on structures: fundamentals and applications to design, New
York: John Wiley, 1996.
Sinha, S.N., Handbook of reinforced concrete design, 1996, Tata McGraw-Hill Publishing Company
limited, New Delhi 110 008.
SP 16, Design Aids for reinforced concrete IS 456, 1978.