Liebert PDX motors. More efficient than centrifugal
1.0 Challenger Compact blowers even when operating at 100%
3000 System
Direct Expansion System Chilled
0.5 Water System fan speed
yy Liebert PDX: 11kW, 18kW, 23kW, 29kW yy0.0
Liebert PCW Downflow: 11kW, 17kW,
18kW with
yyUnique, floor-level air discharge
18kW with
capacities (3, 5, 6.5, 8 Tons, 29kWfixed
capacities
capacity (3,
EC5, 8 Tons
fans configuration reduces mix between
respectively) respectively)
fans
hot and cold air, improving efficiency
3.0 20
2.5 16
2.0 14
SCOP
Liebert Liebert
SCOP
1.5 12 PCW
Liebert PDX
1.0 Challenger Compact Compact
8.0
3000 System Liebert System
0.5 4.0 Challenger
0.0 3000
0.0
18kW with 18kW with 17kW with fixed 17kW with
fixed capacity EC fans capacity fans EC fans
fans
DX SYSTEM 25% more efficient than the CHILLED WATER SYSTEM- Two times the
20 efficiency of the industry-standard Liebert
industry-standard Liebert Challenger 3000
16 Challenger 3000
SCOP (Sensible
14 Coefficient of Performance)=Net Sensible Cooling Capacity/Total System Energy Consumption SCOP (Sensible Coefficient of
Performance)=Net Sensible Cooling Capacity/Total System Energy Consumption
SCOP
Liebert
2
12 PCW
Compact
8.0
Greater Protection Direct Expansion Air-Cooled System
yySelf-optimizing features and advanced PX011 PX018 PX023 PX029
controls fine-tune system operations Net Capacity Data - Std. Airflow - Upflow kBtuh (kW) kBtuh (kW) kBtuh (kW) kBtuh (kW)
for fewer adverse events and longer 75°F DB, 52°F DP (44.6% RH)
equipment life providing availability Total 37.1 (10.9) 63 (18.5) 81.2 (23.8) 101 (29.6)
approaching 100%
Sensible 33.4 (9.8) 59.4 (17.4) 74 (21.7) 89.2 (26.1)
yyLiebert® iCOM™ unit control provides Fan Data
access to system status, operations Std. Airflow, CFM (CMH) 1800 (3060) 2800 (4757) 3500 (5946) 4300 (7305)
and event log and maintenance history Std. Fan Motor, HP (kW) 1.3 (1) 4.15 (3.1) 4.15 (3.1) 4.15 (3.1)
External Static Pressure, in. WG (Pa) 0.8 (199) 0.8 (199) 1 (249) 1 (249)
yyAdvanced freeze and pressure
routines to prevent icing on coils and
locked out compressors
Chilled Water System
Lower Capital, Installation and
PW011 PW017 PW029
Maintenance Costs
Net Capacity Data - Std. Airflow - Upflow kBtuh (kW) kBtuh (kW) kBtuh (kW)
yyLiebert iCOM controls provide faster 75°F DB, 52°F DP (44.6% RH), 45°F EWT, 55°F LWT
installation, easy event identification Total 38.6 (11.3) 53.8 (15.8) 87.4 (25.6)
and self-optimization for mantaining Sensible 36.9 (10.8) 52.8 (15.5) 82.2 (24.1)
optimal performance without manual Flow Rate, GPM (l/m) 8.1 (30.7) 11.9 (45) 19.4 (73)
intervention
Unit Pressure Drop, ft. of water (kPa) 4.3 (12.8) 8.4 (25.1) 13.1 (39.3)
yyNo fan belts to maintain and replace Fan Data (3.1kW EC Blower)
Std. Airflow, CFM (CMH) 1800 (3060) 3500 (5946) 4300 (7305)
yyEasy access at front and side for faster
Std. Fan Motor, HP (kW) 1.3 (1) 4.15 (3.1) 4.15 (3.1)
servicing
External Static Pressure, in. WG (Pa) 0.8 (199) 0.8 (199) 1 (249)
2.55
2.45
Liebert
2.35 PDX
SCOP
Compact
2.25 System
18kW with
2.15 2016 DOE EC fans
Standard
2.05
3