DS™ Thermal Management System
System Design Catalog
35 to 105 kW (10 to 30 ton) Capacity, Upflow and Downflow,
50 and 60 Hz, Air-cooled, Water/Glycol-cooled,
GLYCOOL™ Economizer Coil,
Dual-Cool DX with Secondary Chilled-water Coil
The information contained in this document is subject to change
without notice and may not be suitable for all applications. While
every precaution has been taken to ensure the accuracy and
completeness of this document, Vertiv assumes no responsibility
and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods,
tools, and materials to be used in performing procedures not
specifically described in this document.
The products covered by this instruction manual are manufactured
and/or sold by Vertiv This document is the property of Vertiv and
contains confidential and proprietary information owned by Vertiv.
Any copying, use or disclosure of it without the written permission
of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered
trademarks of the respective companies. Any questions regarding
usage of trademark names should be directed to the original
manufacturer.
D S 0 3 5 A U A 1 E I * * * *
Digit 8 = Voltage
A = 460 V - 3 ph - 60 Hz
B = 575 V - 3 ph - 60 Hz
C = 208 V - 3 ph - 60 Hz
D = 230 V - 3 ph - 60 Hz
2 = 380 V - 3 ph - 60 Hz
Digit 11 = Humidifier
0 = No humidifier
I = Infrared Humidifier
Air-cooled—Unit piping is spun closed from the factory and contains a nitrogen holding charge. Each installation requires
1
refrigerant piping to a condenser.
Glycol-cooled—Units are factory-charged and tested. Field-supplied and field-installed piping is required from the unit to the
2
drycooler and pump package.
GLYCOOL-Integrated Fluid Economizer—Units are factory-charged and tested. Field-supplied and field-installed piping is
required from the unit to the drycooler and pump package. An additional Liebert® Economizer coil is included for use when
3
fluid temperatures are sufficiently low (below room temperature). Economizer cooling is provided by circulating cold glycol
through this second coil, reducing or eliminating compressor operation.
Water-cooled—Units are factory-charged and tested. Field-supplied and field-installed water piping is required from the unit
4
to the cooling tower.
DUAL-COOL—System has all of the features of a compressorized system, but adds a second cooling coil that is connected
5 to a source of chilled water. Cooling is provided by circulating chilled water, when available, through this second coil and
reducing compressor operation.
Figure 1.3 Downflow blower configurations, bottom and under-floor supply with EC fans
NOTE: In upflow units with EC fans in the plenum, supply air exits the front or rear only. Figure 1.4
above represents the possible options.
Figure 1.5 Upflow blower configurations, front-return with forward-curved blowers
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
270.3 352.5
Total kBTUH (kW) — — — —
(79.2) (103.3)
269.2 337.5
Sensible kBTUH (kW) — — — —
(78.9) (98.9)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
Total kBTUH (kW) 137.1 (40.2) 155.3 (45.5) 216.8 (63.5) 258.6 (75.8) 277.6 (81.3) 353.7 (103.6)
Sensible kBTUH (kW) 136.4 (40) 154.7 (45.3) 215.7 (63.2) 255.6 (74.9) 275.1 (80.6) 338.3 (99.1)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
Total kBTUH (kW) 130.4 (38.2) 148.1 (43.4) 206.5 (60.5) 248 (72.7) 265.8 (77.9) 308.2 (90.3)
Sensible kBTUH (kW) 110.8 (32.5) 126.3 (37) 177.6 (52) 209.4 (61.4) 224.9 (65.9) 274.3 (80.4)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
Total kBTUH (kW) 124.7 (36.5) 141.9 (41.6) 197.4 (57.8) 68.9 (238.4) 255.5 (74.9) 327.8 (96)
Sensible kBTUH (kW) 110.8 (32.5) 126.3 (37) 177.6 (52) 209.4 (61.4) 224.9 (65.9) 274.3 (80.4)
2 System Data 11
Table 2.1 Application data—Air-cooled, under-floor discharge with EC fans (continued)
Model Size 035 042 053 070 077 105
Standard Fan Motor, hp (kW) 3.75 (2.8) 3.75 (2.8) 4.15 (3.1) 4.15 (3.1) 4.15 (3.1) 3.6 (2.7)
Number of Fans 1 1 2 2 2 3
1. Application data is rated and factory-certified per ASHRAE 127-2012 with a 5% tolerance.
2. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
3. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors
only
Table 2.2 Application data—Air-cooled with forward-curved blowers, Upflow models only
Model Size 035 042 053 070 077 105
Net APPLICATION DATA kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
Net APPLICATION DATA kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll or Digital Scroll Compressors with Forward-Curved Blowers Scroll Compressors Only
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
Total kBTUH (kW) 135.5 (39.7) 149.2 (43.7) 212.1 (62.1) 252.6 (74.0) 270.1 (79.1) 346.9 (101.6)
Sensible kBTUH (kW) 116.0 (34.0) 148.9 (43.6) 209.3 (61.3) 246.6 (72.3) 265.6 (77.8) 330.4 (96.8)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
Total kBTUH (kW) 130.8 (38.3) 141.9 (41.6) 202.5 (59.3) 243 (71.2) 259 (75.9) 333.5 (97.7)
Sensible kBTUH (kW) 123.2 (36.1) 136.1 (39.9) 191.6 (56.1) 225 (65.9) 242.6 (71.1) 300.4 (88.0)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
Total kBTUH (kW) 125.4 (36.7) 135.7 (39.8) 194.2 (56.9) 233.9 (68.5) 249.3 (73) 321.1 (94.1)
Sensible kBTUH (kW) 109.4 (32.1) 120.6 (35.3) 170.4 (49.9) 200.1 (58.6) 215.2 (63.1) 266.6 (78.1)
Standard Fan Motor, hp (kw) 3 (2.2) 5 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10 (7.5)
Optional Fan Motor, hp (kW) 5 (3.7) 7.5 (5.6) 5 (3.7) 7.5 (5.6) 10 (7.5) 15 (11.2)
Number of Fans 1 1 2 2 2 3
1. APPLICATION DATA is rated and factory-certified per ASHRAE 127-2012 with a 5% tolerance.
2. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
3. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors
only
Face Area, sq. ft. (m2) 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0)
Rows of Coil 3 3 3 3 3 3
REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular; capacity does not include fan motor heat
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (optional selection)
Capacity, kBTUH (kW) 51.2 (15.0) 51.2 (15.0) 85.3 (25.0) 85.3 (25.0) 85.3 (25.0) 102.4 (30.0)
2 System Data 13
Table 2.3 Physical data—Air-cooled systems (continued)
Model Size 035 042 053 070 077 105
HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb./hr. (kg/h) 11.0 (5.0) 11.0 (5.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0)
FILTER SECTION
Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (Filter types cannot be mixed, must be all
MERV 8 or all MERV 11.)
Downflow Models
Quantity 3 3 4 4 4 4
2 @ 25x20 2 @ 25x20
Nominal Size, inches 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20
1 @ 25x16 1 @ 25x16
Upflow Models
(Front and Rear return) Filters located in separate filter box on rear return; located on lower unit panel on front return.
Quantity 4 4 6 6 6 8
PIPING CONNECTION SIZES - Air-cooled Liebert® DS Indoor Unit (Not External Line Sizes)
Liquid Line, O.D. Copper (2/unit) 1/2 1/2 5/8 5/8 5/8 5/8
Hot Gas Line, O.D. Copper (2/unit) 5/8 5/8 7/8 7/8 7/8 1-1/8
Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4
Number of Fans 2 2 2 2 2 2
DUAL-COOL UNITS DATA, Water (0% Glycol), Net Application Data, kBTUH (kW)
CAUTION: CuNi coil option must be specified when Econ-O-Coil is applied to open water tower.
75°F DB, 61.1°F WB, (23.9°C DB, 16.2°C WB) 45% RH, 45°F EWT, 55°F LWT Based on Forward-Curved Blowers
Total Capacity, kBTUH (kW) 101.6 (29.8) 109.8 (32.2) 170.4 (49.9) 188.8 (55.3) 196.8 (57.7) 258.8 (75.8)
Sensible Capacity, kBTUH (kW) 98.2 (28.8) 107.8 (31.6) 157.1 (46) 176.4 (51.7) 185.4 (54.3) 249.1 (73)
Flow Rate GPM (I/m) @ 10°F Rise 22.4 (84.8) 25.5 (96.5) 36.4 (138) 41.7 (158) 46 (174) 59.4 (225)
Pressure Drop, ft. (kPa), valve, coil 8.3 (24.81) 10.50 (31.39) 10.40 (31.09) 13.3 (39.8) 15.9 (47.6) 15.9 (47.5)
Fluid Volumes
Econ-O-Coil Fluid Volume, gal (l) 5 (19.0) 5 (19.0) 8 (30.4) 8 (30.4) 8 (30.4) 10 (38.0)
Application data is rated per ASHRAE 127-2012 with a 5% tolerance
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
Total kBTUH (kW) 143.3 (42) 162.1 (47.5) 224.1 (66.3) 275.6 (80.8) — —
Sensible kBTUH (kW) 142.1 (41.6) 161 (47.2) 215.6 (64.3) 262.6 (77) — —
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
Total kBTUH (kW) 136.7 (40.1) 154.8 (45.4) 216.1 (63.3) 264.6 (77.5) — —
Sensible kBTUH (kW) 129.4 (37.9) 147 (43.1) 200.1 (58.6) 238.9 (70) — —
2 System Data 15
Table 2.4 Application data—Water-cooled with EC fans (continued)
Model Size: 35 42 053 070 077 105
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
Total kBTUH (kW) 131 (38.4) 148.4 (43.5) 206.5 (60.5) 253.5 (74.3) — —
Sensible kBTUH (kW) 115.2 (33.8) 130.9 (38.4) 178.9 (52.2) 212.7 (62.3) — —
Number of Fans 1 1 2 2 — —
1. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
2. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
3. Digital scroll not available on 077 and 105 models. Units available with semi-hermetic only.
Net Application Data, kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
348.9
Total kBTUH (kW) — — — — 289.9 (85.0)
(102.2)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
139.7 269.6
Total kBTUH (kW) 156.3 (45.8) 219.6 (64.9) — —
(40.9) (64.9)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
133.2
Total kBTUH (kW) 148.8 (43.6) 212.1 (32.2) 259.1 (75.9) — —
(39.0)
125.8
Sensible kBTUH (kW) 141.6 (41.5) 192.6 (56.4) 229.3 (67.2) — —
(36.9)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
202.9
Total kBTUH (kW) 127.5 (37.4) 142.3 (41.7) 248.5 (72.8) — —
(59.5)
203.9
Sensible kBTUH (kW) 111.7 (32.7) 125.5 (36.8) 171.5 (50.3) — —
(59.8)
Standard Air Volume f3/m (m3/h) 0.2-in. 5,200 6,200 7,500 9,000 10,400 13,700
External Static (8,835 (10,034) (12,734) (15,291) (17,670) (23,276)
Standard Fan Motor, hp (kW) 3 (2.2) 5 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10 (7.5)
Optional Fan Motor, hp (kW) 5 (3.7) 7.5 (5.6) 5 (3.7) 7.5 (5.6) 10 (7.5) 15 (11.2)
Number of Fans 1 1 2 2 2 3
1. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
2. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
3. Digital scroll not available on 077 and 105 models. Units available with semi-hermetic only.
Face Area, sq. ft. (sq. m) 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0)
Rows of Coil 3 3 3 3 3 3
REHEAT SECTION
Electric Reheat - Three-stage, Stainless Steel Fin Tubular, capacity does not include fan motor heat
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (optional selection)
Capacity, kBTUH (kW) 51.2 (15.0) 51.2 (15.0) 85.3 (25.0) 85.3 (25.0) 85.3 (25.0) 102.4 (30.0)
2 System Data 17
Table 2.6 Physical data—Water-cooled units (continued)
Model Size 035 042 053 070 077 105
HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb./hr. (kg/h) 11.0 (5.0) 11.0 (5.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0)
FILTER SECTION
Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (Filter types cannot be mixed, must be all
MERV 8 or all MERV 11.)
Downflow Models
Quantity 3 3 4 4 4 4
2 @ 25x20 2 @ 25x20
Nominal Size, inches 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20
1 @ 25x16 1 @ 25x16
Upflow Models (Front and Rear Return)—Filters located in separate filter box on rear return, located on lower unit panel on front
return
Quantity 4 4 6 6 6 8
WATER COOLED SYSTEM - Digital Scroll Compressors, based on 75°F/45% room conditions
Condenser Flow Requirements - Maximum design water pressure 150psi (1034kPa), 350psi (2413kPa) available as option; with EC
Fans
THR, kBTUH (kw) 169.8 (49.8) 194.5 (57) 258.5 (75.8) 325.3 (95.3) — —
83°F (28.3°C) EWT, GPM (l/m) 28.5 (107.9) 32.5 (123) 44 (166) 55.5 (210.1) — —
Water Supply, O.D. Copper 1-5/8” (41) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54)
Water Return, O.D. Copper 1-5/8” (41) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54)
Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4
Hot Water Reheat, O.D. Copper 5/8 5/8 5/8 5/8 5/8 5/8
DUAL-COOL UNITS APPLICATION DATA, Water (0% Glycol), Net Application Data kBTUH (kW)
CAUTION: CuNi coil option must be specified when Econ-O-Coil is applied to open water tower.
75°F DB, 62.57 WB (23.9°C DB, 16.9°C WB) 45% RH, 45°F EWT, 55°F LWT; with EC Fans
Total Capacity, kBTUH (kW) 101.6 (29.8) 109.8 (32.2) 170.4 (49.9) 198.1 (58) 196.8 (57.7) 280.1 (82.1)
Sensible Capacity, kBTUH (kW) 98.2 (28.8) 107.8 (31.6) 157.1 (46) 181.4 (53.2) 185.4 (54.3) 63.7 (4)
Flow Rate GPM (I/m) @ 10°F Rise 22.4 (1.4) 25.5 (1.6) 36.4 (2.3) 47.2 (3.0) 46.1 (2.9) 54.9 (3.5)
Pressure Drop, ft. (kPa), valve, coil 8.3 (24.81) 10.50 (31.39) 10.40 (31.09) 17.2 (51.41) 15.9 (47.6) 18 (53.80)
FLUID VOLUMES
Econ-O-Coil Fluid Volume, gal (l) 5 (19.0) 5 (19.0) 8 (30.4) 8 (30.4) 8 (30.4) 10 (38.0)
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor,
Semi-Hermetic Compressors (4 Step Cooling) with EC Fans
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
2 System Data 19
Table 2.7 Application data—Glycol-cooled units with EC fans (continued)
Model Size 035 042 053 070 077 105
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
203.6
Total kBTUH (kW) 128 (37.5) 145.2 (42.5) 244.5 (71.6) — —
(59.7)
203
Sensible kBTUH (kW) 128 (37.5) 145.2 (42.5) 242.2 (71.0) — —
(59.5)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
193.4
Total kBTUH (kW) 120.6 (35.3) 136.8 (40.1) 233.1 (68.3) — —
(56.7)
Sensible kBTUH (kW) 119.6 (35.1) 135.9 (39.8) 187 (54.8) 221.1 (65.1) — —
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
184.1
Total kBTUH (kW) 114.7 (33.6) 130.2 (38.2) 223.2 (65.4) — —
(54.0)
167.2
Sensible kBTUH (kW) 107.1 (31.4) 121.8 (35.7) 198.4 (58.1) — —
(49.0)
Standard Air Volume f3/m (m3/h) 5,200 6200 8,000 9,600 11,000 13.700
0.2" External Static (8,835) (10534) (13,592) (16,310) (18,689) (23,276)
Number of Fans 1 1 2 2 2 3
1. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
2. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
3. Digital scroll not available on 077 and 105 models; units available with semi-hermetic only.
4. 40% ethylene glycol
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors
Semi-Hermetic Compressors (4 Step Cooling) with Forward-Curved Blowers
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
300.0
Total kBTUH (kW) — — — — — 246.6 (72.3)
(87.9)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
206.2
Sensible kBTUH (kW) — — — — — 262.2 (76.8)
(60.4)
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
Total kBTUH (kW) 106.5 (31.2) 124.5 (36.5) 139.4 (40.8) 199.3 (58.4) 239 (70.1) — —
Sensible kBTUH (kW) 106.5 (31.2) 124.5 (36.5) 139.4 (40.8) 197.1 (57.8) 234.3 (68.7) — —
2 System Data 21
Table 2.8 Application data—Glycol-cooled units with forward-curved blowers (continued)
Model Size 028 035 042 053 070 077 105
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
Total kBTUH (kW) 100.8 (29.6) 117 (34.3) 130.8 (38.3) 189.8 (55.6) 228.3 (66.9) — —
Sensible kBTUH (kW) 100.4 (29.4) 116.1 (34) 130.2 (38.1) 180.5 (52.9) 213.5 (62.6) — —
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
Total kBTUH (kW) 95.4 (28) 111.2 (32.6) 124 (36.4) 181.1 (53.1) 218.8 (53.1) — —
Sensible kBTUH (kW) 89.8 (26.3) 103.5 (30.3) 116.3 (34.1) 161 (47.2) 190.1 (55.7) — —
Standard Air Volume f3 /m 4,400 5,200 6,300 7,500 9,000 10,400 13,700
(m3 /h)
0.2" External Static (7,476) (8,835) (10,704) (12,743) (15,291) (17,670) (23,276)
Standard Fan Motor hp (kW) 2 (1.5) 3 (2.2) 5 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10 (7.5)
Optional Fan Motor hp (kW) 3 (2.2) 5 (3.7) 7.5 (5.6) 5 (3.7) 7.5 (5.6) 10 (7.5) 15 (11.2)
Number of Fans 1 1 1 2 2 2 3
1. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
2. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
3. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors
only
4. 40% ethylene glycol
Face Area, sq. ft. (sq. m) 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0)
Rows of Coil 3 3 3 3 3 3
REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular, Capacity Does Not Include Fan Motor Heat
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (Optional Selection)
Capacity, kBTUH (kW) 51.2 (15.0) 51.2 (15.0) 85.3 (25.0) 85.3 (25.0) 85.3 (25.0) 102.4 (30.0)
HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb/hr (kg/h) 11.0 (5.0) 11.0 (5.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0)
FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11
(Filter types cannot be mixed, must be all MERV 8 or all MERV 11)
Downflow Models
Quantity 3 3 4 4 4 4
2 @ 25x20 2 @ 25x20
Nominal Size, inches 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20
1 @ 25x16 1 @ 25x16
Quantity 4 4 6 6 6 8
OUTDOOR DRYCOOLERS - STANDARD 95°F AMBIENT SELECTION; SEE Drycooler Match-up Selections on page 59 FOR OTHER
SELECTIONS
Number of Fans 2 2 3 3 3 4
GLYCOL-COOLED SYSTEM -Semi-Hermetic Compressors, based on 75°F/45% room conditions with EC fans
70 96
104°F (40°C) EGT, GPM (l/m) — — — —
(265) (363)
31.3 50.6
Pressure Drop, ft. of water (kPa), — — — —
(93.6) (151.3)
GLYCOL-COOLED SYSTEM - Digital Scroll Compressors, based on 75°F/45% room conditions with EC Fans
THR, kBTUH (kW) 162.4 (47.6) 486.8 (54.7) 248 (72.7) 311.1 (91.2) — —
104°F (40°C) EGT, GPM (l/m) 33.5 (127) 39 (148) 52 (163.5) 64 (242) — —
Pressure Drop,
14.0 (41.9) 18.6 (55.6) 17.9 (53.5) 26.6 (79.5) — —
ft. of water (kPa)
2 System Data 23
Table 2.9 Physical data—Glycol-cooled units (continued)
Model Size 035 042 053 070 077 105
Glycol Supply, O.D. Copper 1-5/8” 2-1/8” 2-1/8” 2-1/8” 2-1/8” 2-1/8”
Glycol Return, O.D. Copper 1-5/8” 2-1/8” 2-1/8” 2-1/8” 2-1/8” 2-1/8”
Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4
Hot Water Reheat, O.D. Copper 5/8 5/8 5/8 5/8 5/8 5/8
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor,
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
Total kBTUH (kW) 127.1 (37.2) 143.5 (42.1) 201.6 (59.1) 241.9 (70.9) — —
Sensible kBTUH (kW) 127.1 (37.2) 143.5 (42.1) 201.1 (58.9) 239.6 (70.2) — —
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
Total kBTUH (kW) 119.6 (35.1) 135.1 (39.6) 191.4 (56.1) 230.6 (67.6) — —
Sensible kBTUH (kW) 118.6 (34.8) 134.0 (39.3) 185.1 (54.2) 219.5 (64.3) — —
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
Total kBTUH (kW) 113.7 (33.3) 128.5 (37.6) 182.3 (53.4) 220.7 (64.7) — —
Sensible kBTUH (kW) 106.1 (31.1) 120.1 (35.2) 165.5 (48.5) 195.8 (57.4) — —
Standard Air Volume f3/m (m3/h) 5,200 6200 8,000 9,600 10,400 13,500
0.2" External Static (8,835) (10,534) (13,592) (16,310) (17670) (22937)
Number of fans 1 1 2 2 2 3
1. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
2. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
3. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors
only.
4. 40% ethylene glycol.
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
2 System Data 25
Table 2.11 Application Data—GLYCOOL™ units with forward-curved blowers (continued)
Model Size 035 042 053 070 077 105
Net Application Data kBTUH (kW), Standard Air Volume and Evaporator Fan Motor
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
197.4
Total kBTUH (kW) 123.5 (36.2) 137.8 (40.4) 236.6 (69.3) — —
(57.9)
195.3
Sensible kBTUH (kW) 123.5 (36.2) 137.8 (40.4) 231.8 (67.9) — —
(57.2)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
187.9
Total kBTUH (kW) 116.1 (34) 129.3 (37.9) 225.9 (66.2) — —
(55.1)
178.8
Sensible kBTUH (kW) 115.1 (33.7) 128.6 (37.7) 211.1 (61.9) — —
(52.4)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
179.1
Total kBTUH (kW) 110.2 (32.3) 122.5 (35.9) 216.4 (63.4) — —
(52.5)
159.2
Sensible kBTUH (kW) 102.5 (30) 114.7 (33.6) 187.6 (55) — —
(46.7)
Standard Air Volume f3/m (m3/h) 5,200 6,300 7,500 9,000 10,400 13,700
0.2" External Static (8,835) (10,704) (12,743) (15,291) (17,670) (23,276)
Standard Fan Motor hp (kW) 3 (2.2) 5 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10 (7.5)
Optional Fan Motor hp (kW) 5 (3.7) 7.5 (5.6) 5 (3.7) 7.5 (5.6) 10 (7.5) 15 (11.2)
Number of Fans 1 1 2 2 2 3
1. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
2. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
3. Digital scroll not available on 077 and 105 models; units available with semi-hermetic
4. 40% ethylene glycol
Face Area, sq. ft. (sq. m) 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0)
Rows of Coil 3 3 3 3 3 3
REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular, Capacity Does Not Include Fan Motor Heat
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (Optional Selection)
Capacity, kBTUH (kW) 51.2 (15.0) 51.2 (15.0) 85.3 (25.0) 85.3 (25.0) 85.3 (25.0) 102.4 (30.0)
HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb/hr (kg/h) 11.0 (5.0) 11.0 (5.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0)
FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11
(filter types cannot be mixed, must be all MERV 8 or all MERV 11)
Downflow Models
Quantity 3 3 4 4 4 4
2 @ 25x20 2 @ 25x20
Nominal Size, inches 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20
1 @ 25x16 1 @ 25x16
Upflow Models (Front & Rear Return) Filters located in separate filter box on rear return, located on lower unit panel on front return
Quantity 4 4 6 6 6 8
OUTDOOR DRYCOOLERS - Standard 95°F Ambient Selection; See Drycooler Match-up Selections on page 59 for other selections
Number of Fans 2 2 3 3 3 4
GLYCOOL SYSTEM - Semi-Hermetic Compressors, Based on 75°F/45% Room Conditions with EC Fans
49.6
Pressure Drop, ft. of water (kPa), — — — — 32.2 (96.25)
(148.30)
2 System Data 27
Table 2.12 Physical data—GLYCOOL™ units (continued)
Model Size 035 042 053 070 077 105
GLYCOOL SYSTEM - Digital Scroll Compressors, Based on 75°F/45% Room Conditions with EC Fans
THR, kBTUH (kW) 162.4 (47.6) 186.8 (54.7) 248 (72.7) 311.1 (91.2) — —
104°F (40°C) EGT, GPM (l/m) 33.5 (127) 39 (148) 51 (193) 64 (242) — —
Pressure Drop, ft. of water (kPa) 14.0 (41.85) 18.6 (55.60) 17.2 (51.41) 26.6 (79.51) — —
Glycol Supply, O.D. Copper 1-5/8” (41) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54)
Glycol Return, O.D. Copper 1-5/8” (41) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54) 2-1/8” (54)
Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4
Hot Water Reheat, O.D. Copper 5/8 5/8 5/8 5/8 5/8 5/8
ECON-O-COIL APPLICATION DATA (GLYCOOL Units), 40% Ethylene Glycol, Net Application Data, kBTUH (kW)
75°F DB, 62.57°FWB (23.9°C, 16.9°C) 45% RH, 45°F EGT Room Conditions with EC Fans
Total capacity, kBTUH (kW) 93.9 (27.5) 103.9 (30.4) 156.8 (45.9) 182.3 (53.4) 182.3 (57.2) 243.3 (71.3)
Sensible Capacity 93.9 (27.5) 103.9 (30.4) 152.6 (44.7) 176.9 (51.8) 176.9 (51.8) 238.2 (69.8)
Flow rate, GPM (l/m) 33.5 (127) 39 (148) 51 (193) 64 (242) 72 (273) 89 (337)
33.8
Pressure Drop, ft. of water (kPa) 25.7 (76.82) 38.9 (116.27) 59.1 (176.65) 73.5 (219.70) 75.2 (224.78)
(101.03)
FLUID VOLUMES
Unit Volume w/Econ-O-Coil, gal (l) 9 (34.2) 9 (34.2) 14 (53.2) 14 (53.2) 14 (53.2) 17 (64.6)
Model Volts 208 230 460 575 208 230 460 575 208 230 460 575
FLA 70.7 68.2 33.4 25.5 63.1 60.9 29.5 25.2 63.1 60.9 29.5 25.2
DS035 WSA 86.3 83.2 40.8 31.9 68.3 66.1 32 27.1 69 67 32.7 27.1
OPD 90 90 45 30 80 80 40 30 80 80 40 30
FLA 78.2 75.9 37.7 33 78.1 75.9 37.7 33 78.1 75.9 37.7 33
DS042 WSA 95.7 92.5 46 36 85.2 83 41.2 35.8 85.2 83 41.2 35.8
FLA 119.9 116 57.1 43.5 109.2 104.8 52.4 42 109.2 104.8 52.4 42
DS053 WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 117.2 112.8 56.5 45
FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 127.8 123.4 58 46.4
DS070 WSA 156.9 152 72.9 55.5 138.2 133.8 62.8 50 138.2 133.8 62.8 50
DS077 WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 151 146.6 66.2 54
FLA 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1
DS105 WSA 198.8 198.2 97.4 76.4 186.5 182.1 91.6 75.4 186.5 182.1 91.6 75.4
OPD 225 225 110 100 225 225 110 100 225 225 110 100
1. Reduced reheat for 035, and 042 models is 10 kW.
2. Reduced reheat for 053, 070, and 077 models is 15 kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
Model Volts 208 230 460 575 208 230 460 575 208 230 460 575
FLA 70.7 68.2 33.4 25.5 49.8 49.8 23.7 17.8 56.9 55.3 26.9 20.4
DS035 WSA 86.3 83.2 40.8 31.1 55 55 26.2 19.7 69 67 32.7 24.8
OPD 90 90 45 30 70 70 35 25 80 80 35 25
FLA 78.2 75.7 37.5 29.4 64.8 64.8 31.9 25.6 64.8 64.8 31.9 25.6
DS042 WSA 95.7 92.5 46 36 71.9 71.9 35.4 28.4 78.4 76.4 37.8 29.6
FLA 119.9 116 57.1 43.5 82.6 82.6 40.8 30.4 92.1 89.6 44.1 33.5
DS053 WSA 145.3 140.4 69.4 52.8 90.6 90.62 44.9 33.4 110.52 107.4 53.1 40.3
FLA 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 101.4 101.2 46.9 35.7
DS070 WSA 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 122.15 119.02 56.6 43
FLA 134.9 131 61.4 47.5 112.6 112.6 49.4 38.4 112.6 112.6 49.4 38.4
DS077 WSA 164.0 159.2 74.8 57.8 124.37 124.4 54.6 42.4 129.27 126.15 58.5 45.3
FLA 164 163.5 79.8 62.6 144.9 144.9 72.1 57.5 144.9 144.9 72.1 57.5
DS105 WSA 198.8 198.2 97.4 76.4 159.9 159.9 80 63.8 169.3 165.5 81.3 63.9
OPD 225 225 110 90 200 200 110 80 200 200 110 80
1. Reduced reheat for 035, and 042 models is 10 kW.
2. Reduced reheat for 053, 070, and 077 models is 15 kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
Table 3.3 Electrical data by Reheat Options with Humidifier—Air-cooled systems with forward-curved
blowers (Standard-kilowatt Electric Reheat)
Reheat Options: Electric, Std. kW None
Motor
Model Volts 208 230 460 575 208 230 460 575
hp
035 3.0 WSA 88.5 84.4 41.9 33.0 70.5 67.3 33.1 28.0
OPD 90 90 45 35 90 80 40 35
035 5.0 WSA 94.6 90.0 44.7 35.8 76.6 72.9 35.9 30.2
Motor
Model Volts 208 230 460 575 208 230 460 575
hp
042 5.0 WSA 104 99.3 49.9 39.1 93.5 89.8 45.1 38.9
042 7.5 WSA 111.5 106.1 53.3 42.0 101.0 96.6 48.5 41.8
053 3.0 WSA 137.5 131.6 66.2 50.8 109.4 104.0 53.3 42.5
053 5.0 WSA 143.6 137.2 69.0 53.5 115.5 109.6 56.1 44.7
070 5.0 WSA 155.2 148.8 72.5 55.2 136.5 130.6 62.4 49.7
070 7.5 WSA 162.7 155.6 75.9 58.1 144.0 137.4 65.8 52.6
077 7.5 WSA 169.8 162.8 77.8 60.4 156.8 150.2 69.2 56.6
077 10.0 WSA 176.4 168.8 80.8 62.4 163.4 156.2 72.2 58.6
105 10.0 WSA 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9
105 15.0 WSA 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9
Motor
Model Volts 208 230 460 575 208 230 460 575
hp
035 3.0 WSA 88.5 84.4 41.9 32.0 57.2 56.2 27.3 20.6
OPD 90 90 45 35 70 70 35 25
035 5.0 WSA 94.6 90.0 44.7 34.2 63.3 61.8 30.1 22.8
042 5.0 WSA 104.0 99.3 49.9 39.1 80.2 78.7 39.3 31.5
042 7.5 WSA 111.5 106.1 53.3 42.0 87.7 85.5 42.7 34.4
053 3.0 WSA 137.5 131.6 66.2 50.3 82.8 81.8 41.7 30.9
053 5.0 WSA 143.6 137.2 69.0 52.5 88.9 87.4 44.5 33.1
070 5.0 WSA 155.2 148.8 72.5 55.2 109.9 108.4 50.8 38.1
070 7.5 WSA 162.7 155.6 75.9 58.1 117.4 115.2 54.2 41.0
077 7.5 WSA 169.8 162.8 77.8 60.4 130.2 128.0 57.6 45.0
077 10.0 WSA 176.4 168.8 80.8 62.4 136.8 134.0 60.6 47.0
Motor
Model Volts 208 230 460 575 208 230 460 575
hp
105 15.0 WSA 220.1 215.3 109.1 85.9 181.2 177.0 91.7 73.3
Model Motor, hp Volts 208 230 460 575 208 230 460 575
035 3.0 WSA 71.2 68.2 33.8 28.0 71.2 68.2 33.8 25.7
OPD 90 80 40 35 80 80 40 30
035 5.0 WSA 77.3 73.8 36.6 30.2 77.3 73.8 36.6 27.9
OPD 90 90 45 35 90 80 40 30
042 5.0 WSA 93.5 89.8 45.1 38.9 86.7 83.2 41.7 32.7
042 7.5 WSA 101.0 96.6 48.5 41.8 94.2 90.0 45.1 35.6
053 3.0 WSA 109.4 104.0 53.3 42.5 102.7 98.6 49.9 37.8
053 5.0 WSA 115.5 109.6 56.1 44.7 108.8 104.2 52.7 40.0
070 5.0 WSA 136.5 130.6 62.4 49.7 120.5 115.8 56.2 42.7
Model Motor, hp Volts 208 230 460 575 208 230 460 575
070 7.5 WSA 144.0 137.4 65.8 52.6 128.0 122.6 59.6 45.6
077 7.5 WSA 156.8 150.2 69.2 56.6 135.1 129.8 61.5 47.9
077 10.0 WSA 163.4 156.2 72.2 58.6 141.7 135.8 64.5 49.9
105 10.0 WSA 192.4 185.2 96.3 78.9 175.2 168.6 86.0 67.4
105 15.0 WSA 207.8 199.2 103.3 84.9 190.6 182.6 93.0 73.4
Model Number Volts 208 230 460 575 208 230 460 575 208 230 460 575
FLA 70.7 68.2 33.4 25.5 63.1 60.9 29.5 25.2 63.1 60.9 29.5 25.2
035 WSA 86.3 83.2 40.8 31.9 68.3 66.1 32 27.1 69 67 32.7 27.1
OPD 90 90 45 30 80 80 40 30 80 80 40 30
FLA 78.2 75.9 37.7 33 78.1 75.9 37.7 33 78.1 75.9 37.7 33
042 WSA 95.7 92.5 46 36 85.2 83 41.2 35.8 85.2 83 41.2 35.8
FLA 119.9 116 57.1 43.5 109.2 104.8 52.4 42 109.2 104.8 52.4 42
053 WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 117.2 112.8 56.5 45
FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 127.8 123.4 58 46.4
070 WSA 156.9 152 72.9 55.5 138.2 133.8 62.8 50 138.2 133.8 62.8 50
077 WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 151 146.6 66.2 54
FLA 164 163.5 82.5 64.7 158.6 154.2 75.7 62.2 158.6 154.2 75.7 62.2
105 WSA 198.8 198.2 100.1 78.5 173.6 169.2 83.6 68.5 173.6 169.2 84 68.5
OPD 225 225 110 90 225 225 110 90 225 225 110 90
1. Reduced reheat for 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
6. Steam canister humidifiers not available on models with EC fans.
Model# Volts 208 230 460 575 208 230 460 575 208 230 460 575
FLA 70.7 68.2 33.4 25.5 49.8 49.8 23.7 17.8 56.9 55.3 26.9 20.4
035 WSA 86.3 83.2 40.8 31.1 55 55 26.2 19.7 69 67 32.7 24.8
OPD 90 90 45 30 70 70 35 25 80 80 35 25
FLA 78.2 75.7 37.5 29.4 64.8 64.8 31.9 25.6 64.8 64.8 31.9 25.6
042 WSA 95.7 92.5 46 36 71.9 71.9 35.4 28.4 78.4 76.4 37.8 29.6
FLA 119.9 116 57.1 43.5 82.6 82.6 40.8 30.4 92.1 89.6 44.1 33.5
053 WSA 145.3 140.4 69.4 52.8 90.6 90.62 44.9 33.4 110.5 107.4 53.1 40.3
FLA 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 101.4 101.2 46.9 35.7
070 WSA 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 122.2 119.02 56.6 43
FLA 134.9 131 61.4 47.5 112.6 112.6 49.4 38.4 112.6 112.6 49.4 38.4
077 WSA 164.0 159.2 74.8 57.8 124.4 124.4 54.6 42.4 129.3 126.15 58.5 45.3
FLA 164 163.5 82.5 64.7 132 132 64.1 50.6 140.4 137.4 69.6 54.7
105 WSA 198.8 198.2 100.1 78.5 147 147 72 56.9 169.3 165.5 84 66
OPD 225 225 110 90 200 200 100 80 200 200 100 80
1. Reduced reheat for 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
6. Steam canister humidifiers not available on models with EC fans.
Model Motor hp Volts 208 230 460 575 208 230 460 575
035 3.0 WSA 88.5 84.4 41.9 33.0 70.5 67.3 33.1 28.0
OPD 90 90 45 35 90 80 40 35
035 5.0 WSA 94.6 90.0 44.7 35.8 76.6 72.9 35.9 30.2
042 5.0 WSA 104 99.3 49.9 39.1 93.5 89.8 45.1 38.9
042 7.5 WSA 111.5 106.1 53.3 42.0 101.0 96.6 48.5 41.8
053 3.0 WSA 137.5 131.6 66.2 50.8 109.4 104.0 53.3 42.5
053 5.0 WSA 143.6 137.2 69.0 53.5 115.5 109.6 56.1 44.7
070 5.0 WSA 155.2 148.8 72.5 55.2 136.5 130.6 62.4 49.7
070 7.5 WSA 162.7 155.6 75.9 58.1 144.0 137.4 65.8 52.6
077 7.5 WSA 169.8 162.8 77.8 60.4 156.8 150.2 69.2 56.6
077 10.0 WSA 176.4 168.8 80.8 62.4 163.4 156.2 72.2 58.6
Model Motor hp Volts 208 230 460 575 208 230 460 575
105 15.0 WSA 220.1 215.3 109.1 85.9 194.9 186.3 92.6 79.5
Model Motor hp Volts 208 230 460 575 208 230 460 575
035 3.0 WSA 88.5 84.4 41.9 32.0 57.2 56.2 27.3 20.6
OPD 90 90 45 35 70 70 35 25
035 5.0 WSA 94.6 90.0 44.7 34.2 63.3 61.8 30.1 22.8
042 5.0 WSA 104.0 99.3 49.9 39.1 80.2 78.7 39.3 31.5
042 7.5 WSA 111.5 106.1 53.3 42.0 87.7 85.5 42.7 34.4
053 3.0 WSA 137.5 131.6 66.2 50.3 82.8 81.8 41.7 30.9
053 5.0 WSA 143.6 137.2 69.0 52.5 88.9 87.4 44.5 33.1
Model Motor hp Volts 208 230 460 575 208 230 460 575
070 5.0 WSA 155.2 148.8 72.5 55.2 109.9 108.4 50.8 38.1
070 7.5 WSA 162.7 155.6 75.9 58.1 117.4 115.2 54.2 41.0
077 7.5 WSA 169.8 162.8 77.8 60.4 130.2 128.0 57.6 45.0
077 10.0 WSA 176.4 168.8 80.8 62.4 136.8 134.0 60.6 47.0
105 10.0 WSA 204.7 201.3 102.1 79.9 152.9 150.1 74 58.3
105 15.0 WSA 220.1 215.3 109.1 85.9 168.3 164.1 81 64.3
Model Motor, hp Volts 208 230 460 575 208 230 460 575
035 3.0 WSA 71.2 68.2 33.8 28.0 71.2 68.2 33.8 25.7
OPD 90 80 40 35 80 80 40 30
035 5.0 WSA 77.3 73.8 36.6 30.2 77.3 73.8 36.6 27.9
OPD 90 90 45 35 90 80 40 30
042 5.0 WSA 93.5 89.8 45.1 38.9 86.7 83.2 41.7 32.7
042 7.5 WSA 101.0 96.6 48.5 41.8 94.2 90.0 45.1 35.6
053 3.0 WSA 109.4 104.0 53.3 42.5 102.7 98.6 49.9 37.8
053 5.0 WSA 115.5 109.6 56.1 44.7 108.8 104.2 52.7 40.0
070 5.0 WSA 136.5 130.6 62.4 49.7 120.5 115.8 56.2 42.7
070 7.5 WSA 144.0 137.4 65.8 52.6 128.0 122.6 59.6 45.6
077 7.5 WSA 156.8 150.2 69.2 56.6 135.1 129.8 61.5 47.9
077 10.0 WSA 163.4 156.2 72.2 58.6 141.7 135.8 64.5 49.9
Model Motor, hp Volts 208 230 460 575 208 230 460 575
Unit-to-Unit Networking
4 Planning Guidelines 43
Table 4.2 Liebert DS downflow unit weights and shipping weights—Approximate (continued)
Downflow Downflow Shipping Weights, lb (kg)
Standard Scroll* Dual Cool Air 2200 (998) 2350 (1066) 2540 (1153)
GLYCOOL/Dual Cool
2930 (1332) 3092 (1403) 3292 (1494)
Water
Standard Scroll* Dual Cool Air 3015 (1368) 3463 (1571) 3683 (1671)
GLYCOOL/Dual Cool
3505 (1590) 3953 (1794) 4173 (1893)
Water
Forward-
Model EC Fan Unit Weight, Curved Domestic, lb Export, lb
Compressor Type Cooling Type
Number lb (kg) Unit Weight, lb (kg) (kg)
(kg)
Dual Cool Air 1520 (689) 1670 (758) 1808 (821) 1978 (898)
VS035-042 Scroll or Digital-scroll Water/Glycol 1680 (762) 1830 (830) 1968 (893) 2138 (970)
2410
Air-cooled 1900 (862) 2070 (939) 2220 (1007)
(1094)
Dual Cool Air 2080 (943) 2250 (1021) 2400 (1089) 2590 (1175)
VS053 Scroll or Digital-scroll 2732
Water/Glycol 2200 (998) 2370 (1075) 2532 (1149)
(1240)
GLYCOOL/Dual Cool
2380 (1080) 2550 (1157) 2712 (1231) 2912 (1321)
Water
Forward-
Model EC Fan Unit Weight, Curved Domestic, lb Export, lb
Compressor Type Cooling Type
Number lb (kg) Unit Weight, lb (kg) (kg)
(kg)
Dual Cool Air 2080 (943) 2250 (1021) 2400 (1089) 2590 (1175)
GLYCOOL/Dual Cool
2380 (1080) 2550 (1157) 2712 (1231) 2912 (1321)
Water
2862
Air-cooled 2330 (1057) 2500 (1134) 2662 (1208)
(1299)
VS077
3042
Dual Cool Air 2510 (1139) 2680 (1216) 2842 (1290)
Semi-hermetic (1380)
GLYCOOL/Dual Cool
2810 (1275) 2980 (1352) 3142 (1426) 3342 (1516)
Water
3403
Air-cooled 2760 (1252) 3000 (1361) 3183 (1444)
VS105 (1544)
Dual Cool Air 3090 (1402) 3330 (1510) 3513 (1594) 3733 (1694)
Semi-hermetic
Water/Glycol 3130 (1420) 3370 (1529) 3553 (1612) 3773 (1712)
GLYCOOL/Dual Cool
3460 (1569) 3700 (1678) 3883 (1762) 4103 (1862)
Water
4 Planning Guidelines 45
4.2 Planning Dimensions
The unit, floor stand, and plenum dimensions are described in the submittal documents included in the
Submittal Drawings on page 81.
The following table lists the relevant documents by number and title.
Downflow Units
DPN003643 Cabinet Dimensional Data, 35 to 105 kW (10 to 30 ton), all blower types
Upflow Units
Floor Stands
DPN003240 Floorstand Dimensional Data, Downflow Models, 35 to 42 kW (10 to 12 ton), EC fans
Floorstand Dimensional Data, Downflow and Upflow Models, 35 to 42 kW (10 to 12 ton),
DPN003134
Forward-curved Blowers
Floorstand Dimensional Data, Downflow and Upflow Models, 105 kW (30 ton), Forward-
DPN003149
curved Blowers
Blower outlet and Deck Dimensions, Upflow Models, 35 to 42 kW (10 to 12 ton), Forward-
DPN001120
curved blowers
Blower outlet and Deck Dimensions, Upflow Models, 53 to 77 kW (15 to 22 ton), Forward-
DPN001191
curved blowers
Blower outlet and Deck Dimensions, Upflow Models, 105 kW (30 ton), Forward-curved
DPN001192
blowers
Rear-return Filter Box Dimensions, Upflow Models, 35 to 105 kW (10 to 30 ton), All
DPN001196
compressor types, Forward-curved blowers.
Rear-return Filter Box Dimensions, Upflow Models, 35 to 105 kW (10 to 30 ton), All
DPN003974
compressor types, EC fans.
Plenums
Plenum Dimensional Data, Upflow Models, 35 to 105 kW (10 to 30 ton), Forward-curved
DPN003164
blowers
DPN003458 Plenum Dimensional Data, Upflow Models, 35 to 42 kW (10 to 12 ton), EC fans
DPN003453 Plenum Dimensional Data, Upflow Models, 53 to 77 kW (15 to 22 ton), EC fans
Air-cooled Units
DPN003730 Air Cooled Models with Liebert® MC Condenser with and without Lee-Temp
Water/Glycol-cooled Units
GLYCOOL™ Units
Econ-O-Coil™ Option
5 Piping 47
Table 5.2 Piping Connection Drawings (continued)
Document Number Title
Table 6.2 85°F/33RH return air conditions for Hot Aisle/Cold Aisle applications
Outdoor Design Ambient Temperature
Model
95°F (35°C) 100°F (38°C) 105°F (41°C) 110°F (43°C) 115°F (46°C) 120°F (49°C)
Table 6.3 75°F/45RH return air conditions Quiet-Line™ for lower sound levels1
Outdoor Design Ambient Temperature
Model
95°F (35°C) 100°F (38°C) 105°F (41°C) 110°F (43°C) 115°F (46°C)
6 Heat Rejection—Liebert MC™ Condensers 49
Table 6.3 75°F/45RH return air conditions Quiet-Line™ for lower sound levels1 (continued)
Outdoor Design Ambient Temperature
Model
95°F (35°C) 100°F (38°C) 105°F (41°C) 110°F (43°C) 115°F (46°C)
MCS 56 53 73 69 73 76 74 67 61 81
80 52 70 76 79 81 79 72 65 85
MCM
160 55 73 79 82 84 82 75 68 89
110 65 74 78 83 85 83 76 69 89
MCL
220 68 77 81 86 88 86 79 72 92
Table 6.5 Electrical data, three-phase, 60Hz condenser, Premium EC-fan Control
Model Voltage FLA WSA OPD
1. FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device.
Maximum Overcurrent
15 15 15 15
Protection Device, Amps
1. The Liebert® Lee-Temp receiver requires a separate power feed for heaters.
2. The condenser is not designed to supply power to the receiver heater pads.
3. The Liebert Lee-Temp system allows system startup and positive head pressure control in outdoor temperature as low
as -30°F (-34°C).
6 Heat Rejection—Liebert MC™ Condensers 51
6.4 Liebert MC Shipping Dimensions and Weights
For Liebert® MC condenser shipping dimensions and weights, please consult the "Liebert® MC Condenser
Installer/User Guide," available at https://www.vertivco.com/en-us/support/.
6.4.1 Condenser and Options Net Weights
Total unit weight is the sum of the condenser weight with the selected legs plus the weight of any option.
DPN002425 Dual-circuit piping, 2-fan and 4-fan units without Liebert® Lee-Temp™
6 Heat Rejection—Liebert MC™ Condensers 53
6.7 Liebert MC Electrical Field Connections
Condenser-rated voltage should be verified with available power supply before installation. Refer to the
unit’s electrical schematic and serial tag for specific electrical requirements. Line voltage electrical service
is required for all condensers at the location of the condenser. The voltage supply to the condenser may
not be the same voltage supply as required by the indoor unit. Consider using UPS equipment on both
data center cooling units and Liebert MC condensers to maintain uninterrupted cooling capability. Refer
to the unit’s serial tag for specific condenser electrical requirements. A unit disconnect is standard.
However, a site disconnect may be required per local code to isolate the unit for maintenance. Route the
supply power to the site disconnect switch and then to the unit. Route the conduit to the knockout
provided in the bottom right end of the electrical control enclosure. Connect the earth ground wire lead
to the marked earth ground connection terminal provided near the factory-installed disconnect switch..
NOTE: Liebert Lee-Temp™ kits require a separate line voltage electrical supply for the heated receivers.
See Air-cooled Electrical Data on page 29, for power requirements.
The electrical connections are described in the submittal documents included in the Submittal Drawings
on page 81.
The following table lists the relevant documents by number and title.
Power-supply wiring
Low-voltage wiring
1. See 7.2 above for separate power feed needed for Lee-Temp receiver heaters.
2. HP = horsepower, FLA= full-load amps, WSA = wire-size amps, OPD = maximum overload-protective device
Source: DPN004123, Rev. 0
Table 7.5 Separate electrical supply requirements for Liebert® Lee-Temp™ receivers, 60Hz, 1 ph
Voltage 120 120 208/230 208/230
OPD 15 15 15 15
Only one independent input power supply is needed per piggyback unit; connect to Terminals 90 & 91.
Piggyback Condensers
DPN000695 Dimensional and Weight Data, 72-in. and 97-in. frame models
Floor Stands
DPN000696 Connection Locations and Refrigerant Planning Values, 72-in. and 97-in. frame models
95°F (35°C) 100°F (38°C) 105°F (41°C) 95°F (35°C) 100°F (38°C) 105°F (41°C)
NOTE: Drycooler recommendations based on one drycooler per indoor unit, 40% propylene glycol,
75°F/45% RH unit return air conditions. Consult factory for match-up needs using multiple indoor
units, different return-air conditions or alternate glycol temperatures.
DSO (Fan Cycling Control) - A thermostatic control cycles the fan on a single-fan drycooler in response to
leaving fluid temperatures. Two or more thermostats are employed on drycoolers with two or more fans to
cycle fans or groups of fans in response to leaving fluid temperatures.
Pump Controls - Available on all Fan Speed and Fan Cycling Control drycoolers. Controls for pump(s) up
to 7.5 hp are built into the same integral electric panel as the drycooler fan controls. Pump fuses, overload
heaters and flow switch (dual pump control models) are included with the Liebert® pump packages or
must be field-supplied for field-supplied pumps.
Remote Pump-control Panel option - Consult your local sales representative. Provides controls for primary
and standby pump for multiple-drycooler systems.
Table 8.2 Drycooler internal volume, CFM, connections size, dry weight and fluid volume
Total heat Glycol Pressure No. of Internal Inlet/Outlet
Model Air Dry No. of
rejection, flow rate, drop, ft internal No. fluid connection
number flow weight, inlets/
kBtuh (kW) GPM H2O circuits of fans volume, size,
*D** (CFM) lb (kg) outlets
@25F ITD (lpm) (kPa) (Std.) gal. (L) OD Cu in.
Standard Models
540
174 173 (50.8) 40 (152) 10.5 (31) 16 2 13300 6.9 (26.2) 1/1 2-1/8
(245)
580
197 197 (57.7) 40 (152) 13.9 (42) 16 2 12645 9 (34) 1/1 2-1/8
(263)
620
225 231 (67.7) 65 (246) 10.9 (33) 26 2 12200 11.1 (42.1) 1/1 2-1/8
(281)
735 10.0
260 260 (76.3) 60 (227) 10.1 (30) 24 3 19900 1/1 2-1/8
(333) (37.8)
795 13.1
310 311 (91.0) 80 (303) 9.8 (29) 32 3 19000 1/1 2-1/8
(361) (50.0)
855 19.4
350 353 (103) 80 (303) 14.6 (44) 32 3 17400 1/1 2-1/8
(388) (73.3)
940 13.1
352 328 (96.2) 60 (227) 12.9 (39) 24 4 1/1 2-1/8
24800 (426) (49.6)
1020 17.4
419 394 (115) 80 (303) 12.7 (38) 32 4 23650 1/1 2-1/8
(463) (65.9)
1050 22.0
466 441 (129) 100 (379) 12.7 (38) 40 4 1/1 2-5/8
22800 (476) (83.3)
1100 26.3
491 469 (137) 120 (455) 12.8 (38) 48 4 21700 1/1 2-5/8
(499) (99.6)
1830 33.0
650 652 (191) 130 (493) 15.2 (45) 52 6 2/2 2-1/8
36500 (831) (124.9)
795 13.1
173 185 (54.2) 80 (303) 9.7 (29) 32 3 8520 1/1 2-1/8
(361) (50.0)
940 13.1
205 219 (64.2) 60 (227) 12.9 (39) 24 4 11680 1/1 2-1/8
(426) (50.0)
1020 17.4
248 248 (72.8) 80 (303) 12.5 (37) 32 4 11360 1/1 2-1/8
(463) (65.9)
Standard Models
Values are calculated per UL 1995. OPD values may be adjusted higher than calculations to compensate for maximum anticipated
application temperatures.
Model #: 139, 174, 197, 225 260, 310, 350 419, 466, 491 620, 650 880
Pum FL WS OP FL WS OP FL WS OP FL WS OP FL WS OP
Ph
p hp A A D A A D A A D A A D A A D
208/230/60
0.75 3 10.5 11.4 15 14.0 14.9 20 17.5 18.4 25 24.5 25.4 30 31.5 32.4 40
1.5 3 13.6 15.3 20 17.1 18.8 25 20.6 22.3 25 27.6 29.3 35 34.6 36.3 40
2.0 3 14.5 16.4 20 18.0 19.9 25 21.5 23.4 30 28.5 30.4 35 35.5 37.4 45
3.0 3 17.6 20.3 30 21.1 23.8 30 24.6 27.3 35 31.6 34.3 40 38.6 41.3 50
5.0 3 23.7 27.9 40 27.2 31.4 45 30.7 34.9 50 37.7 41.9 50 44.7 48.9 60
7.5 * 3 31.2 37.3 60 34.7 40.8 60 38.2 44.3 60 45.2 51.3 70 52.2 58.3 80
10.0 * 3 37.8 45.5 70 41.3 49.0 70 44.8 52.5 80 51.8 59.5 90 58.8 66.5 90
15 * 3 53.2 64.8 110 56.7 68.3 110 60.2 71.8 110 37.2 78.8 110 74.2 85.8 125
460/60
0.75 3 5.0 5.4 15 6.7 7.1 15 8.4 8.8 15 11.8 12.2 15 15.2 15.6 20
1.5 3 6.4 7.2 15 8.1 8.9 15 9.8 10.6 15 13.2 14.0 20 16.6 17.4 20
2.0 3 6.8 7.7 15 8.5 9.4 15 10.2 11.1 15 13.6 14.5 20 17.0 17.9 20
3.0 3 8.2 9.4 15 9.9 11.1 15 11.6 12.8 15 15.0 16.2 20 18.4 19.6 25
5.0 3 11.0 12.9 20 12.7 14.6 20 14.4 16.3 20 17.8 19.7 25 21.2 23.1 30
7.5 3 14.4 17.2 25 16.1 18.9 25 17.8 20.6 30 21.2 24.0 30 24.6 27.4 35
10.0 3 17.4 20.9 30 19.1 22.6 35 20.8 24.3 35 24.2 27.7 40 27.6 31.1 45
15 * 3 24.4 29.7 50 26.1 31.4 50 27.8 33.1 50 31.2 36.5 50 34.6 39.9 60
575/60
0.75 3 4.1 4.5 15 5.5 5.9 15 6.9 7.3 15 9.7 10.1 15 12.5 12.9 15
1.5 3 5.2 5.8 15 6.6 7.2 15 8.0 8.6 15 10.8 11.4 15 13.6 14.2 20
2.0 3 5.5 6.2 15 6.9 7.6 15 8.3 9.0 15 11.1 11.8 15 13.9 14.6 20
3.0 3 6.7 7.7 15 8.1 9.1 15 9.5 10.5 15 12.3 13.3 15 15.1 16.1 20
5.0 3 8.9 10.4 15 10.3 11.8 15 11.7 13.2 15 14.5 16.0 20 17.3 18.8 20
7.5 3 11.8 14.1 20 13.2 15.5 20 14.6 16.9 25 17.4 19.7 25 20.2 22.5 30
10.0 3 13.8 16.6 25 15.2 18.0 25 16.6 19.4 30 19.4 22.2 30 22.2 25.0 35
15 3 19.8 24.1 40 21.2 25.5 40 22.6 26.9 40 25.4 29.7 45 28.2 32.5 45
Values are calculated per UL 1995. Pump FLA values used are based on NEC tables for motor horsepower. OPD values may be
adjusted higher than calculations to compensate for maximum anticipated application temperatures.
* May require electrical component(s) with higher capacity in the drycooler. Consult factory representatives for assistance before
ordering.
Pump
Ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
hp
208/230/3/60
15 * 3 51.6 63.2 100 53.4 65.0 110 57.0 68.6 110 60.6 72.2 110
460/3/60
575/3/60
DPN000721 Cabinet and Anchor dimensions for 6- to 8-fan standard and Quiet-Line drycoolers
DPN000275 Connection locations for 1-fan, 2-fan, 3-fan, and 4-fan units
DPN003822 Typical arrangement for multiple drycoolers and multiple indoor thermal-management units
NOTE: Higher-capacity pumps are available. Please contact your local sales rep for more information.
NOTE: Drycooler recommendations based on one drycooler per indoor unit and are sized using
approximately 120°F (49°C) EGT and 110°F (43°C) LGT. Consult your sales rep for match-up needs
using multiple indoor or alternative glycol temperatures.
For pump capacities, see Figure 8.1 on page 65.
Model No. of Fans CFM (m3/hr) Ext. Static Pressure - in. (Pa)
1. Values are without filter box. External Static Pressure = filter pressure drop + other static drops.
PD-333 models with filter section will be factory supplied with 15HP motor. ESP higher than 0.50" (125Pa) will reduce airflow.
Blower
Model Voltage Pump
Motor hp Total Unit Pump Only Total Unit Total Unit
Only
FLA WSA OPD hp FLA FLA WSA OPD hp FLA WSA OPD
PD- 230 7.5 22.0 27.5 45 3 9.6 31.6 37.1 50 5 37.2 42.7 60
223 460 7.5 11.0 13.8 20 3 4.8 15.8 18.6 25 5 18.6 21.4 30
PD- 230 7.5 22.0 27.5 45 5 9.6 37.2 42.7 30 3 31.6 37.1 50
290 460 7.5 11.0 13.8 20 5 4.8 18.6 21.4 25 3 15.8 18.6 25
ph = phase; FLA = Full Load Amps; WSA = Wire Size Amp; OPD = Maximum Overcurrent Protection Device
Source: DPN004124 Rev. 0
Piggyback Drycoolers
DPN000710 Dimensional and Weight Data, 72-in. and 97-in. frame models
Floor Stands
71
This page intentionally left blank
WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment
damage, injury or death. Read all of the following instructions and verify that all lifting and
moving equipment is rated for the weight of the unit before attempting to move, lift, remove
packaging from or prepare the unit for installation.
CAUTION: Risk of contact with sharp edges and exposed fasteners. Can cause injury. Wear
appropriate, OSHA-approved personal protective equipment (PPE) when installing the
component.
CAUTION: Risk of handling heavy unit and component parts. Can cause injury and equipment
damage. Use OSHA-recommended safe lifting techniques and/or lifting equipment rated for the
weight of the unit.
73
NOTICE
Risk of improper disassembly. Can cause equipment damage.
Disassembling this unit requires substantial work, including reclaiming refrigerant and
charging the unit, cutting and brazing refrigerant lines, cutting and brazing water lines,
disconnecting and reconnecting electrical lines and moving heavy, bulky equipment. One
member of the crew disassembling the unit must be qualified in wiring, brazing and
refrigeration.
Improperly disassembling or reassembling the DS may affect warranty.
The disassembly dimensions and details are described in the submittal documents included in the
Submittal Drawings on page 81.
The following table lists the relevant documents by number and title.
Downflow Units
Upflow Units
75
21. Un-sweat or cut all copper water pipes that interconnect unit sections.
22. Immediately cap and seal all piping that has been cut, including the suction and liquid lines, as
well as the fluid piping on GLYCOOL and dual-cool units.
B.3 Remove the Compressor Assembly
1. Secure the compressor wire harness to the compressor assembly.
2. Remove the 10 thread-cutting bolts holding the compressor section assembly to the filter and
electric box assembly and the blower and coil assembly.
There are five bolts in the front, four in the back and one on the top at the middle of the unit.
a. Begin removing bolts at the bottom of the unit and progress toward the top. Use this
method for the front and back bolts.
b. Stabilize the compressor section before removing the top, middle bolt.
NOTICE
Risk of oil loss or displacement. Can cause compressor damage.
The compressor section is top-heavy and has a small base. It must remain upright. Do not lay
the compressor section on its side during or after removing it from the unit. Do not remove
shipping blocks from Semi-hermetic compressors until the unit is fully reassembled and ready
for installation.
NOTE: We recommend using piano jacks when moving this section.
Remove the Filter and Electric Box Assembly
1. Using a stepladder to reach the top of the unit, remove the filter support plate; it is attached to
the filter and electric box assembly with two screws, one on each end.
2. Remove tags from the Schrader fittings on top of the coil headers. Retain the tags for
replacement during reassembly.
3. Remove 16 screws, (8) on each side, from the evaporator top cover plate to coil assembly. Coil
top blocker will remain with top section for rigidity.
4. Remove coil access plates from the left side of the unit.
5. Remove the four thread-cutting bolts securing the filter and electric box assembly to the
blower and coil assembly. There are two on the left and two on the right.
6. Separate the unit sections with caution.
NOTICE
Risk of improper handling.
•The filter and electric box section should be moved forward and set on the floor.
•Make sure to lift the coil plate over the Schrader fittings on the headers. We recommend
using four people to remove this section. Special care is required when moving this
section because the legs are not designed to withstand strong shocks.
• The blower and coil assembly must remain upright. The coil is not secured to the blower
and coil assembly.
• Secure the coil to the bottom section with straps or a similar method before moving the
section.
7. Move each section of the unit to the installation location.
B.4 Reassembly—Downflow Units
1. Replace the top section.
Make sure to clear the Schrader valves on the coil header.
2. Reconnect the filter and electric box assembly to the blower and coil assembly using thread-
cutting bolts.
Torque the bolts to 225 in-lb. (25 Nm)
3. Reattach the evaporator top cover plate; there are eight screws on each side.
77
B.6 Disassembly—Upflow Units
1. Remove the unit from its skid.
2. Remove all panels except top front accent.
3. Remove all filters on front return units. This allows easier access to items located in the filter
and coil assembly.
4. All wires are hot stamped and all circuit board connectors are lettered for easy replacement.
Cable ties will need to be cut and replaced as necessary. Reference unit wiring schematic on
dead-front panel for details.
5. Label the (3) quick connect plugs from the compressor compartment, and disconnect them.
6. Disconnect compressor wire harness, including crankcase heater wires, if applicable, from
contactor in electric box. Pull conduit and wires into compressor compartment.
7. Reheat (optional component): Disconnect reheat wire harness from bottom of contactor in
electric box. Unplug low-voltage quick connect for reheat safety wires. Pull conduit and wires
into filter and coil assembly section of unit.
8. Humidifier (optional component):
a. Disconnect the humidifier wire harness from the bottom of the contactor in the electric
box.
For infrared humidifiers: Remove the quick-connect plugs from these low-voltage
connections: 35-5 and 35-6 (safety under pan), 35-3 and 35-4 (humidifier make-up valve)
and 8-5 and 8-7 (high water alarm).
b. Disconnect 35-3 and 35-4 from the control board.
c. Pull the conduit and wires into the unit’s filter and coil assembly section.
9. Condensate pump (optional component): Disconnect condensate pump high-voltage wire
harness. Remove low volt wires from terminal strip #24 and #55. Pull conduit and wires into
filter and coil assembly section of unit.
10. GLYCOOL/Dual-Cool (optional component): On units with actuator, unplug valve actuator
harness at actuator and pull wire harness into electric box. Disconnect glycol sensor from
control board and pull into filter and coil assembly section of unit.
11. Smoke detector (optional component): For units with smoke detector, remove cover on smoke
detector. Remove plug connector from smoke detector and pull into electric box. Remove wires
from terminal strip #91, 92, 93 and route the wires to the smoke detector box. Remove the
sensing tube from the bottom of the plastic elbow.
12. Filter Clog Switch: Disconnect both tubes from the filter clog switch. Pull both of the tubes into
the electric box.
13. Close the electric box cover and the accent panel.
14. Remove the pull bar that supports the accent panel from left end of unit, otherwise it will fall
out when the compressor section is removed.
15. Evacuate and recover all refrigerant from the unit.
Air-cooled units contain an inert-gas holding charge. Water, glycol and GLYCOOL units are
factory charged with refrigerant. Refer to the ASHRAE Refrigeration Handbook for general,
good-practice refrigeration piping.
NOTICE
Risk of compressor oil contamination with moisture. Can cause equipment damage.
We recommend front-seating the compressor service valves. Front-seating the valves keeps
the inert gas or refrigerant charge in the compressor and prevents moisture from
contaminating the compressor oil. This is particularly important with units using R-407C
refrigerant.
16. Cut and pull back insulation from piping.
79
3. Reattach the compressor section. Insert all compressor thread-cutting bolts before tightening
them all down.
4. Reinstall the pull bar to support the accent panel.
5. Reinstall the low-voltage plugs in the compressor section.
6. Rewire the compressor, reheat, humidifier, condensate pump and smoke detector, if applicable.
7. Reattach the sensing tube to the blower inlet.
8. Reattach the plug connection at the actuator and reroute the sensor back through electric
box and onto control board, on GLYCOOL and dual-cool units.
9. Piping must be reassembled in accordance with local codes.
10. Move the insulation and plastic bushings away from the brazing area.
11. Wrap the piping with wet cloths. Use copper fittings where required.
12. Refer to the ASHRAE Refrigeration Handbook for general, good-practice refrigeration piping.
13. Open service valves on compressor.
14. Reinsert plastic bushings.
15. Charge the unit with refrigerant; see the unit’s nameplate for the proper charge.
16. Replace the galvanized panels on the left side of the coil.
17. Replace the filters.
18. Replace the panels.
B.9 Reassembly Checklist—Upflow Unit
1. Thread-cutting bolts reconnected at a torque specification of 225 in-lb. (25 Nm).
2. High-voltage wires connected to proper contactors:
a. compressor
b. reheat, if applicable
c. humidifier, if applicable
d. condensate pump, if applicable
3. Low-voltage wires connected:
a. actuator
b. terminal strip
c. plug connections
d. smoke detector, if applicable
4. Coil access plates on left side replaced
5. Motor access plate on right side replaced
6. Water lines brazed
7. Suction and liquid refrigerant lines brazed
8. Unit recharged
9. Filters replaced
10. Panels replaced
11. Piping systems pressure-checked for leaks
Component Location
DPN003643 Cabinet Dimensional Data, 35 to 105 kW (10 to 30 ton), all blower types
DPN003240 Floorstand Dimensional Data, Downflow Models, 35 to 42 kW (10 to 12 ton), EC fans
Floorstand Dimensional Data, Downflow and Upflow Models, 105 kW (30 ton), Forward-
DPN003149
curved Blowers
Blower outlet and Deck Dimensions, Upflow Models, 35 to 42 kW (10 to 12 ton), Forward-
DPN001120
curved blowers
Blower outlet and Deck Dimensions, Upflow Models, 53 to 77 kW (15 to 22 ton), Forward-
DPN001191
curved blowers
Blower outlet and Deck Dimensions, Upflow Models, 105 kW (30 ton), Forward-curved
DPN001192
blowers
Rear-return Filter Box Dimensions, Upflow Models, 35 to 105 kW (10 to 30 ton), All
DPN001196
compressor types, Forward-curved blowers.
Rear-return Filter Box Dimensions, Upflow Models, 35 to 105 kW (10 to 30 ton), All
DPN003974
compressor types, EC fans.
Plenum Dimensional Data, Upflow Models, 35 to 105 kW (10 to 30 ton), Forward-curved
DPN003164
blowers
DPN003458 Plenum Dimensional Data, Upflow Models, 35 to 42 kW (10 to 12 ton), EC fans
DPN003453 Plenum Dimensional Data, Upflow Models, 53 to 77 kW (15 to 22 ton), EC fans
81
Table C.1 Submittal-drawings Contents (continued)
Document Number Title
Electrical Connections
Unit-to-Unit Networking
DPN000695 Dimensional and Weight Data, 72-in. and 97-in. frame models
DPN000710 Dimensional and Weight Data, 72-in. and 97-in. frame models
DPN000696 Connection Locations and Refrigerant Planning Values, 72-in. and 97-in. frame models
83
Table C.1 Submittal-drawings Contents (continued)
Document Number Title
DPN002425 Dual-circuit piping, 2-fan and 4-fan units without Liebert® Lee-Temp™
Cabinet and Anchor dimensions for 6- to 8-fan standard and Quiet-Line drycoolers
DPN003822 Typical arrangement for multiple drycoolers and multiple indoor thermal-management units
Outlet Connection
(lower header)
4 3/4"
121mm
Disconnect B
Switch 4 1/4"
108mm
B 1" 1 3/4"
43 3/16" 25mm 44mm
C D 1097mm 1 3/4"
44mm
A 1 7/8"
48mm 4 1/4"
37 11/16" 41 1/4" 108mm
O1/2" (13mm)
Anchor Bolts (Typ.)
957mm 1046mm O 9/16"
14mm
Typ. 1"
25mm
1 7/8"
48mm
4 legs furnished for 1, 2, 3, & 4 fan models
6 legs furnished for 4 fan models
Unit Anchor Plan DETAIL A
A B C D CFM (I/s) CFM (I/s) Internal Volume Dry Wt.
Liebert Model No. of fans
in. (mm) in. (mm) in. (mm) in. (mm) 60Hz (See note 1) 50Hz (See note 1) Gal. (Liters) Lbs. (kg)
*D**033 7200 (3398) 6000 (2932) 1.2 (4.6) 355 (161)
*D**069 6866 (3240) 5722 (2700) 2.4 (9.2) 375 (170)
*D**092 1 51-1/2 (1308) 44 (1118) 42 (1067 6633 (3130) 5527 (2609) 3.7 (13.9) 395 (179)
*D**109 6322 (2984) 5268 (2486) 4.9 (18.6) 415 (188)
*D**112 6088 (2873) 5074 (2394) 5.8 (22) 435 (197)
*D**139 13732 (6481) 11443 (5401) 4.8 (18.2) 500 (227)
N/A
*D**174 13265 (6261) 11054 (5217) 6.9 (26.2) 540 (245)
2 91-1/2 (2324) 84 (2134) 82 (2083)
*D**197 12645 (5968) 10535 (4973) 9 (34) 580 (263)
*D**225 12177 (5748) 10147 (4789) 11.1 (42.1) 620 (281)
*D**260 19898 (9392) 16582 (7827) 10 (37.8) 735 (333)
*D**310 3 131-1/2 (3340) 124 (3150) 122 (3099) 18965 (8951) 15804 (7459) 13.1 (49.6) 795 (361)
*D**350 17398 (8212) 14499 (6843) 19.4 (73.3) 855 (388)
*D**352 24800 (11705) 20667 (9755) 13.1 (49.6) 940 (426)
*D**419 23650 (11163) 19708 (9302) 17.4 (65.9) 1020 (463)
4 171-1/2 (4356) 164 (4166) 82 (2083) 80 (2032)
*D**466 22770 (10747) 18975 (8956) 22 (83.3) 1050 (476)
*D**491 21700 (10242) 18083 (8535) 26.3 (99.6) 1100 (499)
Notes:
1. All Drycooler fan motors are 3/4H.P.
Form No.: DPN001040_REV4
2. A miniimum clearance of 36" (914mm) is recommended on all sides for proper operation and component access.
DPN000274 REV : 4
Page :1 /1 REV DATE : 3/17
LIEBERT DRYCOOLER
PIPING CONNECTIONS
INLET CONNECTION
(UPPER HEADER)
OUTLET CONNECTION
(LOWER HEADER)
DPN000275 REV : 6
Page :1 /1 REV DATE : 7/17
LIEBERT DRYCOOLER
ELECTRICAL FIELD CONNECTIONS
FLUID TEMPERATURE CONTROL
Notes:
1. Refer to specification sheet for full load amp and wire
size amp ratings.
Factory installed
disconnect switch
(optional)
19"
3 483mm
2 7/8"
73mm
15 7/8"
403mm
6 3/8" 1 3/4"
162mm 44mm
8 3/4"
222mm
12 1/4"
311mm
30" SINGLE PACKAGE 0.75 - 7.5 HP
762mm
17"
432mm
3/4"
19mm
NOTE: C
ANGLES LOCATED INSIDE, BOTTOM A
OF PUMP PACKAGE. VIEW USED FOR
MOUNTING REFERENCE.
B
PUMP PACKAGE MOUNTING ANGLES
DPN000278 REV : 2
Page :1 /1 REV DATE : 3/17
LIEBERT DRYCOOLER
CABINET ANCHOR DIMENSIONAL & GENERAL DATA
43 1/8"
1-4 FAN QUIET-LINE MODELS 1095mm
TOP OF
FAN GUARD
43 9/16"
1107mm
Outlet Connection
(lower header)
4 3/4"
121mm
Disconnect B 4 1/4"
Switch 108mm
1 3/4"
44mm
B 1"
43 3/16" 25mm
C D 1097mm 1 3/4"
44mm
A 1 7/8" 4 1/4"
37 11/16" 41 1/4" 48mm 108mm
O1/2" (13mm) 957mm 1046mm
Anchor Bolts (Typ.) Typ. O 9/16"
14mm
Typ. 1"
1 7/8" 25mm
4 legs furnished for 1, 2, 3, & 4 fan models Unit Anchor Plan 48mm
6 legs furnished for 4 fan models
DETAIL A
A B C D CFM (I/s) CFM (I/s) Internal Volume Dry Wt.
Quiet-Line Model No. of fans
in. (mm) in. (mm) in. (mm) in. (mm)60Hz (See note 1) 50Hz (See note 1) Gal. (Liters) Lbs. (kg)
*D**040 3110 (5285) 2592 (4404) 2.4 (9.1) 375 (170)
*D**057 1 51-1/2 (1308) 44 (1118) 42 (1067 2990 (5081) 2492 (4234) 3.7 (14) 395 (179)
*D**060 2840 (4826 2367 (4021) 4.9 (18.5) 415 (188)
*D**080 6220 (10569) 5183 (8808) 4.8 (18.2) 500 (227)
*D**111 2 91-1/2 (2324) 84 (2134) 82 (2083) N/A 5980 (10161) 4983 (8468) 6.9 (26.1) 540 (245)
*D**121 5680 (9651) 4733 (8043) 9 (34.1) 580 (263)
*D**158 8970 (15242) 7475 (12702) 10 (37.9) 735 (333)
*D**173 3 131-1/2 (3340) 124 (3150) 122 (3099) 8520 (14477) 7100 (12064) 13.1 (49.6) 795 (361)
*D**178 7440 (12462) 6200 (10535) 19.4 (73.4) 855 (388)
*D**205 11680 (19847) 9733 (16539) 13.1 (49.6) 940 (426)
4 171-1/2 (4356) 164 (4166) 82 (2083) 80 (2032)
*D**248 11360 (19303) 9467 (16086) 17.4 (65.9) 1020 (463)
Notes:
1. All Drycooler fan motors are 1/4H.P.
Form No.: DPN001040_REV4
2. A miniimum clearance of 36" (914mm) is recommended on all sides for proper operation and component access.
DPN000280 REV : 4
Page :1 /1 REV DATE : 7/17
LIEBERT DRYCOOLER
PIPING CONNECTIONS & DIMENSIONAL DATA
DUAL PUMP PACKAGE
DUAL PACKAGE 0.75 - 5 HP
1 3" (76.2mm) DIA. PUMP SUCTION CONNECTION K.O.'S
2
1
2 3" (76.2mm) DIA. PUMP DISCHARGE
32 1/4" CONNECTION K.O.'S
2 819mm 3
1 3 7/8" (22.2mm) DIA. ELECTRICAL K.O.'S
8 3/4"
222mm 1 3/4" 2 7/8"
12 1/4" 44mm 73mm
311mm
30"
23 3/4" 762mm
603mm
27 1/4"
PUMP PACKAGE MOUNTING ANGLES
692mm
32" 6
813mm
33 3/16"
843mm 16 3/8"
29 3/16" 416mm
741mm Mounting Hole Dimensional Data in. (mm)
Pump Package A B C
41"
1041mm 6 1/2" Dual (0.75-5HP) 30-1/4 (768) 2-1/2 (64) 22-1/2 (572)
165mm Dual (7.5HP) 39-5/16 (999) 1-3/4 (45) 26-7/8 (683)
Form No.: DPN001040_REV4
DPN000328 REV : 2
Page :1 /1 REV DATE : 3/17
LIEBERT DRYCOOLER
ELECTRICAL & PIPING CONNECTION DATA
PUMP PACKAGE
GLYCOL PUMP DATA
ELECTRICAL DATA 60Hz PIPING CONNECTIONS NPT FEMALE IN.
HP FLA (FULL LOAD AMPS)
PHASE SUCTION DISCHARGE
208V 230V 460V 575V
1 7.6 6.9 N/A N/A
3/4
3.5 3.2 1.6 1.3
1-1/4 3/4
1-1/2 6.6 6.0 3.0 2.4
2 7.5 6.8 3.4 2.7
3
3 10.6 9.6 4.8 3.9 1
1-1/2
5 16.7 15.2 7.6 6.1 1-1/4
7.5 24.2 22 11 9 3 3
ELECTRICAL DATA 50Hz PIPING CONNECTIONS NPT FEMALE IN.
HP FLA (FULL LOAD AMPS)
PHASE SUCTION DISCHARGE
380V / 415V
1 1.64 / 1.63
1-1/2 2.4 / 2.25 1-1/4 3/4
2 3 3.00 / 2.88
3 4.7 / 4.38 1-1/4
1-1/2
5 7.9 / 7.47 1
Form No.: DPN001040_REV4
DPN000329 REV : 3
Page :1 /1 REV DATE : 5/17
LIEBERT PIGGYBACK CONDENSER
DIMENSIONAL DATA
72" & 97" FRAME MODELS
1 1/8"
(29mm) E D
H B
K J Overall
Overall
R
K
OPTIONAL FAN
DISCHARGE
S
DISCONNECT
H SWTICH
(OPTIONAL) 72"
J
1829mm
35 1/8" R
(892mm) FAN
DISCHARGE
34"
5" 864mm
(127mm) Typ.
G
34" Front View 1"
CONDENSER COIL INLET 864mm 25mm
AND DUCT 10"
CONNECTION Rear View Typ.
(254mm) C A
Unit Base Unit Base
1-1/4" NPT-Female UNIT DIMENSIONAL DATA
Drain Outlet connection Shaded areas indicate a
C recommended clearance
T be provided for component
access.
F
FLOOR
LEVEL
A FAN DISCHARGE DATA
REAR DISCHARGE
Unit Shipping Weight lbs. (kg) OPTIONAL TOP DISCHARGE
Liebert Model No. Domestic Pkg Ex port Pkg
FLOOR CUTOUT DIMENSIONS
PB-350A
PB-550A 1180 (535) 1330 (603)
PB-675A
PB-925A
PB-1100A 1630 (739) 1780 (807)
PB-1350A
Note:
1. A 1" (25mm) flange is provided on coil inlet opening and fan discharge opening for duct connections.
DPN000695 REV : 5
Page :1 /1 REV DATE : 3/17
LIEBERT PIGGYBACK CONDENSER
PRIMARY CONNECTION LOCATIONS &
REFRIGERANT PLANNING VALUES
72" & 97" FRAME MODELS Optional Ducting
Optional Ducting
1 13/16" A
46mm
Typ. All Sizes
C B
2 Typ.
Typ. 1
5 1/2" 1 B C
F 140mm
3 1/4" 2 D
83mm 3"
76mm
G 1 1/2"
38mm
3 8" 3" 4
203mm 76mm
Drain Outlet Location
1-1/4" NPT-Female 3" 4
6" 76mm
152mm
3" 3" E
76mm 76mm
3 4
9 11/16"
All Models 2 4 246mm
4
12 5/8"
321mm
7 7/8"
PB-1350A Rear View 1 4 200mm 4 1/2" 4
114mm
Liebert Dimensional Data in. (mm)
Model No. A B C D E F G
PB-350A Approx imate
Connection Sizes O.D. Cu
PB-550A Liebert Model Refrigeration
2 per unit
PB-675A 10-1/8 (267) 28-3/4 (730) 27-1/4 (692) 2-1/2 (64) 15-1/2 (394) 36 (914) No. Charge per ciruit
6 (152) Liquid Line Hot Gas Line R-407C lbs.
PB-925A
PB-1100A PB-350A 24
5/8"
PB-1350A 11-1/4 (286) 24 (610) 26-1/2 (673) 7 (178) 16-1/2 (419) 48-1/2 (1232) PB-550A 30
1/2"
PB-675A 35
Notes: 7/8"
PB-925A 33
1. Multiple K.O. of O1-3/8" (35mm), O1-3/4" (45mm), and O2-1/2" (64mm) for Main Power Supply (Typ.) PB-1100A
5/8" 1-1/8" 69
2. 7/8" (22mm) K.O. for Lee-Temp Power Supply (Typ.) PB-1350A
3. Cover Plate for access of Liquid Line and Hot Gas Line.
Form No.: DPN001040_REV4
DPN000696 REV : 4
Page :1 /1 REV DATE : 3/17
LIEBERT PIGGYBACK CONDENSER
ELECTRICAL FIELD CONNECTIONS
72" & 97" FRAME MODELS
Factory installed unit disconnect switch (optional)
Three phase electric service
not by Liebert
Single Phase for Lee-Temp heaters
electric service not by Liebert
1. Refer to specification sheet for full load amp and wire size amp ratings.
DPN000697 REV : 2
Page :1 /1 REV DATE : 3/17
LIEBERT PIGGYBACK DRYCOOLER
DIMENSIONAL DATA
1 1/8"
(29mm) E
72" & 97" FRAME MODELS
H
K J D
R B Ove
Dimerall
Overanllsions nsions
K Dime
OPTIONAL FAN
DISCHARGE
S DISCONNECT
H SWTICH
J
35 1/8" R 72"
(892mm) FAN (1829mm)
DISCHARGE
5" 34"
(127mm) 864mm Typ. 36"
914mm
G
CONDENSER COIL INLET
AND DUCT 1"
CONNECTION Rear View 10"
(254mm)
34"
864mm (25.4mm)
Typ. A Typ.
1-1/4" NPT-Female C Unit
Drain Outlet connection Unit Base
C Base
15 7/16"
UNIT DIMENSIONAL DATA Front View
(392mm) Shaded areas indicate recommended
FLOOR clearance for component access
LEVEL
A F
REAR OF
FLOOR CUTOUT DIMENSIONS CABINET
Unit Shipping Weight lbs. (kg)
Liebert Model No. Domestic Pkg Ex port Pkg
PD-102
PD-133 1230 (558) 1380 (626)
PD-150
PD-223
PD-290 1680 (726) 1830 (830)
PD-333
Note:
1. A 1" (25.4mm) flange is provided oncoil inlet opening and fan discharge opening for duct connections.
DPN000710 REV : 5
Page :1 /1 REV DATE : 3/17
LIEBERT PIGGYBACK DRYCOOLER
PRIMARY CONNECTION LOCATIONS
72" & 97" FRAME MODELS
See Note 2
D
See Note 1
E
A
See A
Note 3 4 E
C
B
1 13/16" B
4 46mm
3" 4
D 76mm
1"
25mm 4
Panel
3"
76mm 4
3" Model PD-333
76mm 4
Rear View
C
See Note 3 4
DPN000711 REV : 3
Page :1 /1 REV DATE : 3/17
LIEBERT PIGGYBACK DRYCOOLER
ELECTRICAL FIELD CONNECTIONS
Factory installed unit disconnect switch.
DPN000712 REV : 2
Page :1 /1 REV DATE : 3/17
LIEBERT DRYCOOLER
CABINET & ANCHOR DIMENSIONAL DATA
6 & 8 FAN HEAT REJECTION QUIET-LINE MODELS
Recommended rigging and
spreader bars required for
installation. Rigging and bars
not supplied by Liebert
87 1/8"
E 2213mm
43 1/8"
1095mm
TOP OF
FAN GUARD
37 7/8"
962mm
18"
457mm
Optional disconnect Center leg Location of holes and support for rigging
switch handle provided on O1-1/2" (38mm) Typ. (4) places
8 fan models
D
only
86 3/4" C
2203mm
1 7/8"
48mm
C
A B 1"
25mm
O 9/16"
14mm
Notes: Typ. 4 1/4"
1. 4 legs furnished for 6 fan models 108mm
6 legs furnished for 8 fan models 1"
2. A clearance of 36" (914mm) is 25mm
81 5/16" 84 3/4" 1 3/4"
2065mm O 1/2" 2154mm recommended on all sides for 44mm
Typ. 13mm proper operation and component access.
Anchor Bolts (Typ.) 1 3/4"
44mm
1 7/8" 4 1/4"
48mm 108mm
DPN000721 REV : 2
Page :1 /1 REV DATE : 3/17
LIEBERT PIGGYBACK
FLOORSTAND DIMENSIONAL DATA
CONDENSER & DRYCOOLER
1"
(25.4mm)
31"
(787mm) 31"
(787mm)
C
B
A
Notes:
Form No.: DPN001040_REV4
1. Leveling feet are provided with u1-1/2" (38mm) adjustment from nominal height.
DPN000727 REV : 2
Page :1 /1 REV DATE : 3/17
LIEBERT DS
OPTIONAL PIPING SCHEMATIC
ECON-O-COIL MODELS
RETURN RETURN
SUPPLY SUPPLY
ECON-O-COIL ECON-O-COIL
FACTORY PIPING
FIELD PIPING
1 SUPPLIED WITH 10 FEET EXTRA THERMISTOR WIRE FOR INSTALLATION ON FIELD SUPPLY LINE.
DPN000805 REV : 3
Page :1 /1 REV DATE : 1/17
LIEBERT DS
PIPING SCHEMATIC
WATER/GLYCOL 77kW - 105kW SEMI-HERMETIC COMPRESSOR MODELS
Optional Dual Pump System shown
EXPANSION
LIEBERT TANK 2
CUSTOMER HEAT REJECTION GLYCOL
HEAT REJECTION PUMPS 1
Check Valves
(on Dual Pump
DRYCOOLER Pressure Systems only)
1 Port
COOLING TOWER (Glycol)
AND PUMP SYSTEM Aquastat Gate Valves 1
BY OTHERS Sensing
Bulbs
RETURN SUPPLY
Muffler COMPRESSOR
External
Service Equalizer 2-Way
Check Valve 4 Valve Regulating
Valve
DISCHARGE
NOTE: SCHEMATIC REPRESENTATION SHOWN. THIS SCHEMATIC DOES NOT IMPLY OR system high points
DEFINE ELEVATIONS AND COMPONENT LOCATION, UNLESS SPECIFICALLY NOTED. 4. This check valve is present on 77kW models only.
DPN000895 REV : 11
Page :1 /1 REV DATE : 6/18
LIEBERT DS
PIPING SCHEMATIC
WATER/GLYCOL SCROLL COMPRESSOR MODELS
Optional Dual Pump System shown
EXPANSION
LIEBERT TANK 2
CUSTOMER HEAT REJECTION GLYCOL
HEAT REJECTION PUMPS 1
Check Valves
(on Dual Pump
DRYCOOLER Pressure Systems only)
1 Port
COOLING (Glycol) Gate Valves
TOWER Aquastat
AND PUMP Sensing 1
SYSTEM Bulbs
BY OTHERS
Hose Air Vents Pressure Port 1
1 Bib Shut-Off Valve 1 (typical) 3
RETURN SUPPLY
LIEBERT DS UNIT
(and associated piping) RETURN
SUPPLY
Service
Valve
Service External 2-Way
Check COMPRESSOR Valve Regulating
Valve Equalizer
Valve
DISCHARGE
RETURN SUPPLY
Muffler COMPRESSOR
Service External
Valve Equalizer
Check Valve 4
DISCHARGE
3-Way
PARADENSER® Regulating
CONDENSER Valve
RETURN SUPPLY
LIEBERT DS UNIT
(and associated piping) ECON-O-COIL RETURN SUPPLY
Shut-Off Valve 1
3-Way 1 Shut-Off Valve
LIQUID Chilled Glycol Hose Hose
Sensing Bulb Valve 1 Bib Bib 1
EVAPORATOR Thermistor
Service COIL
Valve SUCTION
Check External
Service
Valve COMPRESSOR Valve Equalizer
DISCHARGE
3-Way
PARADENSER® Regulating
CONDENSER Valve
NOTE: SCHEMATIC REPRESENTATION SHOWN. THIS SCHEMATIC DOES NOT IMPLY OR DEFINE
ELEVATIONS AND COMPONENT LOCATION, UNLESS SPECIFICALLY NOTED. 3 Locate at tops of all risers and any intermediate
system high points
DPN000898 REV : 6
Page :1 /1 REV DATE : 1/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW AIR COOLED 35-42kW (10-12 TONS) SCROLL OR DIGITAL SCROLL
COMPRESSOR MODELS W/ FORWARD CURVED BLOWERS
ECR 5
2 R1 ECS 5
X O
1
G2 BLOWER
HUM OUTLET
G1 CPD 3
35" LV1
889mm L2 R2 2 Y
L1 LV2
E1 E2 LV3
2 R3 FRONT OF UNIT
73"
6 G2 1854mm
Top View
6 G1
17 1/8" L2
434mm L1
3 7/8" 9 7/8" CGD 4
98mm 251mm
14 1/4"
362mm
CGD 4 Front View
Left Side View (Left Front Panel Not Shown)
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field routed alternatives for refrigerant gas & liquid line connection points.
3. Forward Curved Blower Shown. See submittal page DPN001120 for blower outlet and deck dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit.
drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only.
6. When piping out of the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
LV2 ELECTRICAL CONN. (LOW VOLT) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 ELECTRICAL CONN. (LOW VOLT) 31-15/16 (811)
DPN001119 REV : 6
Page :1 /1 REV DATE : 5/17
LIEBERT DS
BLOWER OUTLET & DECK DIMENSIONAL DATA
UPFLOW 35-42kW (10-12 TONS) W/ FORWARD CURVED BLOWERS
86" 1
2186mm
B E C
Blower Outlet
35"
889mm
Ref.
76"
1930mm
Unit
Height
Front of Unit
Notes:
DPN001120 REV : 6
Page :1 /1 REV DATE : 7/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW WATER/GLYCOL/GLYCOOL™ 35-42kW (10-12 TONS) SCROLL &
DIGITAL SCROLL COMPRESSOR MODELS W/ FORWARD CURVED BLOWER
1
2 W1, W2 5 X O
ECR BLOWER
ECS
HUM OUTLET
CPD
3
35"
889mm
LV1 Y
2 7/8" LV2
( 73mm )
LV3
E1 E2
Top View 86"
FRONT OF UNIT
2184.4mm
W3 2
WS WS
WR WR
3 7/8"
( 98mm )
CGD 4
3. Forward Curved Blower shown. See submittal page DPN001120 for blower outlet and deck dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only (four-pipe system).
POINT DESCRIPTION X in. (mm) Y in. (mm) CONNECTION SIZE / OPENING
35kW (10 TON) 42kW (12 TON)
W1 WATER/GLYCOL/GLYCOOL™ ACCESS (BOTTOM) 2
79-15/16 (2030) 9 (229) 3-1/2" (89mm) X 8" (203mm)
W2 WATER/GLYCOL/GLYCOOL™ ACCESS (TOP) 2
W3 WATER/GLYCOL/GLYCOOL™ ACCESS (SIDE) 2 6" (152mm) x 17-3/16" (437mm)
WS WATER/GLYCOL/GLYCOOL™ SUPPLY N/A N/A
WR WATER/GLYCOL/GLYCOOL™ RETURN
1-5/8" O.D. Cu 2-1/8" O.D. Cu
ECS ECON-O-COIL SUPPLY 5 7-5/16 (186)
56 (1422)
ECR ECON-O-COIL RETURN 5 4-1/2 (114)
CGD CONDENSATE GRAVITY DRAIN 4 N/A N/A 3/4" NPT FEMALE
CPD CONDENSATE PUMP DISCHARGE (OPT) 11-1/8 (283) 1/2" O.D. Cu
56-1/4 (1429)
HUM HUMIDIFIER SUPPLY LINE 9-1/8 (232) 1/4" O.D. Cu
E1 52-3/8 (1330)
ELECTRICAL CONN. (HIGH VOLT) 30 (762) 2-1/2"
E2 46-7/8 (1191)
LV1 29-1/16 (738)
Form No.: DPN001040_REV4
LV2 ELECTRICAL CONN. (LOW VOLT) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 31-15/16 (811)
DPN001179 REV : 9
Page :1 /1 REV DATE : 5/17
LIEBERT DS
BLOWER OUTLET & DECK DIMENSIONAL DATA
UPFLOW 53-77kW (15-22 TONS) W/ FORWARD CURVED BLOWERS
1
109"
2767mm
Blower Outlets B E C
Typ.
A
Typ.
34 7/8"
887mm
DPN001191 REV : 8
Page :1 /1 REV DATE : 1/17
LIEBERT DS
BLOWER OUTLET & DECK DIMENSIONAL DATA
UPFLOW 105kW (30 TONS) W/ FORWARD CURVED BLOWERS
132"
3354mm
G
Blower Outlets
F
B E C
Typ.
A
Typ.
35"
889mm
Ref.
76"
1930mm
Front of unit Unit
Height
DPN001192 REV : 3
Page :1 /1 REV DATE : 1/17
LIEBERT DS
REAR RETURN FILTER BOX DIMENSIONAL DATA
UPFLOW 35-105kW (10-30 TONS) ALL COMPRESSOR MODELS
W/ FORWARD CURVED BLOWERS
FILTER FILTER
ACCESS ACCESS
DOOR DOOR
7 7/8"
202mm
76"
1930mm
40"
1016mm
38 1/4"
971mm
Duct Size
3 1/2"
89mm
D Duct Size
A B C
Notes:
1. Filters can be accessed from either side.
2. 25" (635mm) minimum clearance provided on one side for filter access.
3. Filter boxes are shipped flat and must be field assembled.
105kW, All Models 2-1/4 (57) 100-1/4 (2546) 29-1/2 (749) 97-1/8 (2467) 8
DPN001196 REV : 6
Page :1 /1 REV DATE : 5/18
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW AIR COOLED 77kW (22 TONS)
SEMI-HERMETIC COMPRESSOR MODELS W/ FORWARD CURVED BLOWERS
ECR
2 R1 ECS 5 X O
1
BLOWER BLOWER
HUM OUTLET OUTLET
35" CPD
889mm 3 3
L1L2 G1G2
R2 2 LV1
LV2
LV3 Y
E1 E2
Top View 109"
FRONT OF UNIT
2769mm
2 R3
20" L1 L2 G1G2 7
509mm
CGD 4
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field routed alternatives for refrigerant gas & liquid line connection points.
3. Forward Curved Blowers shown. See submittal page DPN001191 for blower outlet and deck dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
6. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
POINT DESCRIPTION X in. (mm) Y in. (mm) CONNECTION SIZE / OPENING
R1 REFRIGERANT ACCESS (TOP) 2 83-3/4 (2127) 1-7/8 (48) 22-1/2"(572mm) X 15-3/16" (386mm)
R2 REFRIGERANT ACCESS (BOTTOM) 2 86 (2184) 13-7/8 (352) 16-7/16" (418mm) X 4" (102mm)
R3 REFRIGERANT ACCESS (SIDE) 2 N/A N/A 6" (152mm) X 17-3/16" (437mm)
L1 LIQUID LINE SYSTEM 1 97 (2464)
16-3/4 (425) 5/8" O.D. Cu
L2 LIQUID LINE SYSTEM 2 93-5/16 (2370)
G1 HOT GAS DISCHARGE 1 6 90-5/8 (2302)
16-5/8 (422) 1-1/8" O.D. Cu
G2 HOT GAS DISCHARGE 2 6 88 (2235)
CGD CONDENSATE GRAVITY DRAIN 4 N/A N/A 3/4" NPT FEMALE
CPD CONDENSATE PUMP DISCHARGE (OPT) 11-7/8 (302) 1/2" O.D. Cu
79-5/16 (2015)
HUM HUMIDIFIER SUPPLY LINE 9-7/8 (251) 1/4" O.D. Cu
ECS ECON-O-COIL SUPPLY 5 7-7/8 (200)
78-5/8 (1997) 2-1/8" O.D. Cu
ECR ECON-O-COIL RETURN 5 4-5/8 (117)
E1 75-3/8 (1915)
ELECTRICAL CONN. (HIGH VOLT) 30 (762) 2-1/2"
E2 69-7/8 (1775)
LV1 29-1/16 (738)
LV2 ELECTRICAL CONN. (LOW VOLT) 19-1/2 (495) 30-1/2 (775) 7/8"
Form No.: DPN001040_REV4
DPN001212 REV : 6
Page :1 /1 REV DATE : 5/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW AIR COOLED 53-77kW 15-22 TONS
SCROLL OR DIGITAL SCROLL COMPRESSORS
2 R1 ECR 5
ECS 5
X O
1
2 R2 BLOWER BLOWER
G2 OUTLET OUTLET
G1 3 3
35"
889mm LV1
HUM LV2 Y
L2 CPD
L1 L1 LV3
E1 E2
12 7/8" Top View Front of Unit
325mm 98"
2 R3 2489mm
17 1/8"
4 433mm
CGD
9 7/8"
3 7/8"
98mm
251mm G2 6 Front View
5 CGD
14 1/4"
362mm L2
(Left Panel Not Shown)
G1 6
Left Side View L1
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field routed alternatives for refrigerant gas and liquid line connection points.
3. Forward Curved Blowers shown. See submittal page DPN001191 for blower outlet and deck dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit.
Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only.
6. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running the lines to the top.
7. Digital Scroll Compressor not available on DS077 models.
POINT DESCRIPTION X in. (mm) Y in. (mm) CONNECTION SIZE / OPENING
R1 REFRIGERANT ACCESS (TOP) 2 83-5/8 (2124) 2 (51) 12"(305mm) X 4" (102mm)
R2 REFRIGERANT ACCESS (BOTTOM) 2 82-3/4 (2102) 14-3/4 (375) 12-3/16" (310mm) X 4" (102mm)
R3 REFRIGERANT ACCESS (SIDE) 2 N/A N/A 6" (152mm) X 17-3/16" (437mm)
53kW (15TONS) / 70 & 77kW (20 & 22TONS)
L1 LIQUID LINE SYSTEM 1 94-11/16 (2405)
16-3/4 (425) 1/2" O.D. Cu 5/8" O.D. Cu
L2 LIQUID LINE SYSTEM 2 91-7/8 (2334)
G1 HOT GAS DISCHARGE 1 6 88-3/4 (2254)
16-3/8 (416) 7/8" O.D. Cu 1-1/8" O.D. Cu
G2 HOT GAS DISCHARGE 2 6 85-9/16"(2173)
CGD CONDENSATE GRAVITY DRAIN 4 N/A N/A 3/4" NPT FEMALE
CPD CONDENSATE PUMP DISCHARGE (OPT) 11-7/8 (302) 1/2" O.D. Cu
79-5/16 (2015)
HUM HUMIDIFIER SUPPLY LINE 9-7/8 (251) 1/4" O.D. Cu
ECS ECON-O-COIL SUPPLY 5 7-7/8 (200)
78-5/8 (1997) 2-1/8" O.D. Cu
ECR ECON-O-COIL RETURN 5 4-5/8 (117)
E1 75-3/8 (1915)
ELECTRICAL CONN. (HIGH VOLT) 30 (762) 2-1/2"
E2 69-7/8 (1775)
LV1 29-1/16 (738)
Form No.: DPN001040_REV4
LV2 ELECTRICAL CONN. (LOW VOLT) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 31-15/16 (811)
DPN001213 REV : 4
Page :1 /1 REV DATE : 4/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW WATER/GLYCOL/GLYCOOL™ 53-77kW (15-22 TONS)
ALL COMPRESSOR MODELS W/ FORWARD CURVED BLOWERS 1
ECR
W1, W2 2 ECS 5 X O
BLOWER BLOWER
OUTLET OUTLET
35" 3 3
889mm
HUM
2 7/8" CPD
73mm LV1
LV2 Y
LV3
E1 E2
109" Front of unit
2769mm
2 W3 Top View
WS
3 7/8" WS WR
98mm
WR
CGD 4
9 7/8"
251mm CGD 4
Front View
14 1/4"
362mm (Left Panel Not Shown)
Left Side View
Notes:
1. Drawing not to scale. All dimensions are from rear corner if unit including panels, and have a tolerance of ± 1/2" (13mm).
3. Forward Curved Blowers shown. See submittal page DPN001191 for blower outlet and deck dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only (four-pipe system).
6. Digital Scroll compressors not available on 77kW models.
7. Semi-Hermetic Compressor only available on 77kW models.
LV2 ELECTRICAL CONN. (LOW VOLT) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 ELECTRICAL CONN. (LOW VOLT) 31-15/16 (811)
DPN001214 REV : 5
Page :1 /1 REV DATE : 5/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW AIR COOLED 105kW (30 TONS) ALL COMPRESSOR MODELS
2 R1 ECR 1
2 R2 ECS 5 X O
9 7/8"
CGD 4
Front View
251mm
14 1/4" (Left Panel Not Shown)
362mm
Notes: Left Side View
1 . Drawing not to scale. All dimensions from rear corner of unit including panel, and have a tolerance of u 1/2" (13mm).
2. Field routed alternatives for refrigerant gas and liquid line connection points.
3. Forward Curved Blowers shown. See submittal page DPN001192 for blower outlet and deck dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only.
6. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
7. Digital Scroll compressors not available on DS105 models.
POINT DESCRIPTION X in. (mm) Y in. (mm) CONNECTION SIZE / OPENING
R1 REFRIGERANT ACCESS (TOP) 2 106-7/8 (2715) 1-7/8 (48) 22-1/2"(572mm) X 15-3/16" (386mm)
R2 REFRIGERANT ACCESS (BOTTOM) 2 109-1/8 (2772) 13-7/8 (352) 16-7/16" (418mm) X 4" (102mm)
R3 REFRIGERANT ACCESS (SIDE) 2 N/A N/A 6" (152mm) X 17-3/16" (437mm)
L1 LIQUID LINE SYSTEM 1 121-3/4 (3092)
16-3/4 (425) 5/8" O.D. Cu
L2 LIQUID LINE SYSTEM 2 118-1/8 (3000)
G1 HOT GAS DISCHARGE 1 6 118-1/4 (3004)
14-1/4 (362) 1-1/8" O.D. Cu
G2 HOT GAS DISCHARGE 2 6 115-5/8 (2937)
CGD CONDENSATE GRAVITY DRAIN 4 N/A N/A 3/4" NPT FEMALE
CPD CONDENSATE PUMP DISCHARGE (OPT) 102-3/8 (2600) 13-5/8 (346) 1/2" O.D. Cu
HUM HUMIDIFIER SUPPLY LINE 13-1/8 (333) 1/4" O.D. Cu
ECS ECON-O-COIL SUPPLY 5 101-1/8 (2569) 10-1/4 (260)
2-5/8" O.D. Cu
ECR ECON-O-COIL RETURN 5 5-1/4 (133)
E1 98-1/2 (2502)
ELECTRICAL CONN. (HIGH VOLT) 30 (762) 2-1/2"
E2 93 (2362)
LV1 41-1/8 (1045)
LV2 38-7/8 (987)
ELECTRICAL CONN. (LOW VOLT) 30-3/8 (772) 7/8"
Form No.: DPN001040_REV4
DPN001257 REV : 4
Page :1 /1 REV DATE : 1/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW WATER/GLYCOL/GLYCOOL™ 105kW (30 TONS)
ALL COMPRESSOR MODELS
ECR
1
W1, W2 2 ECS 5 X O
WS
WR
3 7/8" WS
98mm WR
CGD 4
9 7/8" Front View
251mm CGD 4
14 1/4"
362mm (Left Panel Not Shown)
Left Side View
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
3. Forward Curved Blowers shown. See submittal page DPN001192 for blower outlet and deck dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only (four-pipe systems).
DPN001258 REV : 3
Page :1 /1 REV DATE : 1/17
LIEBERT DS
PIPING SCHEMATIC
WATER/GLYCOL DIGITAL SCROLL COMPRESSOR MODELS
Optional Dual Pump System shown
EXPANSION
LIEBERT TANK 2
GLYCOL
HEAT REJECTION PUMPS
CUSTOMER 1
HEAT REJECTION Check Valves
(on Dual Pump
DRYCOOLER Pressure Systems only)
(Glycol) 1 Port
COOLING TOWER Gate Valves 1
AND PUMP SYSTEM Aquastat
BY OTHERS Sensing
Bulbs
RETURN SUPPLY
LIEBERT DS UNIT
(and associated piping) RETURN
SUPPLY
Optional 3-Way
Motorized Ball
LIQUID 1 Shut-Off Valve Shut-Off Valve 1
Valve
28-42kW Digital Solenoid Valve Sensing Bulb 1 Hose
EVAPORATOR Bib Hose
53-70kW Digital COIL 1
Bib
Solenoid Valve SUCTION
Service
Valve
Check Service 2-Way
External
Valve COMPRESSOR Valve Motorized
Equalizer From
Ball Valve
iCOM
DISCHARGE Control
PARADENSER®
CONDENSER
RETURN SUPPLY
Service
Valve
Service External
Check 3-Way
Valve Equalizer
Valve COMPRESSOR Motorized
Ball Valve From
iCOM
DISCHARGE Control
PARADENSER®
CONDENSER
OPTIONAL FACTORY PIPING 1 Components are not supplied by Liebert but are
FACTORY PIPING required for proper operation and maintenance
FIELD PIPING
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE 2 Field installed at highest point in system on
return line to pumps
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE 3 Locate at tops of all risers and any intermediate
Form No.: DPN001040_REV4
NOTE: SCHEMATIC REPRESENTATION SHOWN. THIS SCHEMATIC DOES NOT IMPLY OR DEFINE ELEVATIONS system high points
AND COMPONENT LOCATION, UNLESS SPECIFICALLY NOTED.
DPN001432 REV : 3
Page :1 /1 REV DATE : 4/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
DOWNFLOW WATER/GLYCOL/GLYCOOL™ 105kW (30 TONS)
ALL COMPRESSOR MODELS
A A
1
X O
W
WS
WR Y
EC FANS 35"
OUTLET 889mm
3 3
ECS ECR 2
CD LV1
LV2
LV3
E1 E2 HUM Front of Unit
Section A-A
132"
3353mm
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
3. Supplied on Dual Cooling systems only (four-pipe system).
DPN002153 REV : 3
Page :1 /1 REV DATE : 1/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
DOWNFLOW AIR COOLED 105kW (30 TONS) ALL COMPRESSOR MODELS
A A
X 1
O
4 G2
4 G1 R Y
EC FANS 35"
889mm
L1 L2 OUTLET
3 3
ECS ECR 2
LV1
CD LV2
LV3
HUM Front of Unit
E1 E2 Section A-A
132"
3353mm
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
3. Supplied on Dual Cooling systems only.
4. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
DPN002154 REV : 3
Page :1 /1 REV DATE : 1/17
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL
FAN 2
FAN 1
8
10
SH
12
13
70
71
9 230
NOTICE !
THIS HOLE FOR FIELD
SUPPLIED EXTRA LOW
VOLTAGE CONTROL WIRING
4) SPD field connection terminals – High voltage surge protective device (SPD) terminals. SPD is an optional device.
DPN002169 REV : 10
Page :1 /3 REV DATE : 2/17
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL
5) CANbus terminal connections – Field terminals for CANbus cable connection.
• 5A is the CANbus connectors.
o TB49-1 is the input terminal for CANbus high.
o TB49-3 is the input terminal for CANbus low.
o TB50-1 is output terminal for CANbus high.
o TB50-3 is the output terminal for CANbus low.
o Each CANbus cable shield is connected to terminal “SH”, item 9.
• 5B is the “END OF LINE” jumper.
• 5C is the CANbus “DEVICE ADDRESS DIP SWITCH”. CANbus cable not by Liebert. See Note 2. (below)
6) Remote unit shutdown – Replace existing jumper between terminals TB38-1 and TB38-2 with field supplied normally closed
switch having a minimum 75VA 24VAC rating. Use field supplied Class 1 wiring. (This is an optional feature that may be owner specified.)
7) Alarm terminal connections –
a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common, TB74-2 is normally open, and TB74-3 is
normally closed. 1 Amp 24VAC is the maximum load. Use Class 1 field supplied wiring.
b. Shutdown Alarm Relay indicates when condenser loses power, or when a critical alarm has occurred that shuts down the
condenser unit. TB74-4 is common, TB74-5 is normally open, and TB74-6 is normally closed. 1 Amp 24VAC is the maximum load.
Use Class 1 field supplied wiring.
8) Indoor unit interlock and SPD alarm terminals –
a. On any call for compressor operation, normally open contact is closed across terminals 70 and 71 for Circuit 1, and normally open
contact is closed across terminals 70 and 230 for Circuit 2 from indoor room unit.
b. During SPD alarm, normally open contact is closed across terminals 12 & 13. SPD is an optional device.
9) CANbus shield terminal – Terminal for field shield connection of the CANbus field supplied cables. The shield of CANbus field supplied
cables must not be connected to ground at the condenser.
10) Primary low voltage entrance – One 7/8” (22.2mm) diameter knockout that is free for customer low voltage wiring.
11) SPD entrance – One 7/8” (22.2mm) diameter knockout hole located at the bottom of the enclosure. High voltage surge protective device
(SPD) is optional.
NOTES:
1. Refer to specification sheet for unit voltage rating, full load amp, and wire size amp ratings.
2. The CANbus wiring is field supplied and must be:
- Braided shield or foil shield with drain wire
- Shield must be wired to ground at indoor unit
- 22-18AWG stranded tinned copper
- Twisted pair (minimum 4 twists per foot)
- Low Capacitance (15pF/FT or less)
- Must be rated to meet local codes and conditions
- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER
3. Do not run in same conduit, raceway, or chase as high voltage wiring.
4. For CANbus network lengths greater than 450FT (137M) call Factory.
Form No.: DPN001040_REV4
DPN002169 REV : 10
Page :2 /3 REV DATE : 2/17
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL
5. All wiring must be sized and selected for insulation case per NEC and other local codes.
6. Do not bend cables to less than four times the diameter of the cable.
7. Do not deform cables when securing in bundles or when hanging them.
8. Avoid running the cables by devices that may introduce noise, such as machines, fluorescent lights, and electronics.
9. Avoid stretching cables.
10. The electrically commutated (EC) motors included in the Liebert MC Condenser are suitable for connection to power supplies with a
solidly grounded neutral or high resistance to ground or corner ground.
a. Acceptable power supplies for 208 to 575V nominal units:
• 208V wye with solidly grounded neutral and 120V line to ground;
• 380V wye with solidly grounded neutral and 220V line to ground;
• 480V wye with solidly grounded neutral and 277V line to ground;
• 575V wye with solidly grounded neutral and 332V line to ground (uses step-down transformer);
• Wye with high resistance (or impedance) ground;
• Delta with corner ground
b. Unacceptable power supplies for 208V to 575V nominal units:
• Delta without ground or with floating ground;
• Delta with grounded center tap.
Form No.: DPN001040_REV4
DPN002169 REV : 10
Page :3 /3 REV DATE : 2/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
DOWNFLOW AIR COOLED 77kW (22 TONS)
SEMI-HERMETIC COMPRESSOR MODELS
A A
X
O
1
4
R
EC FANS Y
35" OUTLET
889mm
L1 L2 G1 G2
LV1
3 3 LV2
ECS ECR 2
CD LV3
E1 E2 HUM
Section A-A Front of Unit
109"
2769mm
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
3. Supplied on Dual Cooling systems only.
4. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
DPN002179 REV : 4
Page :1 /1 REV DATE : 5/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
DOWNFLOW AIR COOLED 53-77kW
SCROLL OR DIGITAL SCROLL COMPRESSOR MODELS W/ EC FANS
A A
X
O 1
R
Y
L1 L2 G1 G2
35"
889mm EC Fan EC Fan
Outlet Outlet
4 LV1
3 3
ECS ECR 2 LV2
CD LV3
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
3. Supplied on Dual Cooling systems only.
Form No.: DPN001040_REV4
4. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
5. Digital Scroll compressor not available on DS077 models.
DPN002182 REV : 7
Page :1 /1 REV DATE : 1/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
DOWNFLOW WATER/GLYCOL/GLYCOOL™ 53-77kW (15-22 TONS)
ALL COMPRESSOR MODELS
A A
X 1
O
Y
WS EC FANS
35" WR OUTLET
889mm
3 3
ECS ECR 2 LV1
CD LV2
LV3
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
3. Supplied on Dual Cooling systems only (four-pipe system).
4. Digital Scroll compressors not available on 77kW models.
5. Semi-Hermetic Compressor available only on 77kW models.
DPN002183 REV : 4
Page :1 /1 REV DATE : 5/17
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL WITH LEE-TEMP
Electrical Connections for Lee-Temp Receiver
FAN2
Lee-Temp receiver tank (1 per circuit).
NOTE: Heater pad voltage available for FAN1
3) Primary high voltage entrance – Two 7/8” (22.2mm) diameter knockouts located at the bottom of the enclosure.
4) SPD field connection terminals – High voltage surge protective device (SPD) terminals. SPD is an optional device.
DPN002374 REV : 9
Page :1 /3 REV DATE : 2/17
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL WITH LEE-TEMP
5) CANbus terminal connections – Field terminals for CANbus cable connection.
• 5A is the CANbus connectors.
o TB49-1 is the input terminal for CANbus high.
o TB49-3 is the input terminal for CANbus low.
o TB50-1 is output terminal for CANbus high.
o TB50-3 is the output terminal for CANbus low.
o Each CANbus cable shield is connected to terminal “SH”, item 9.
• 5B is the “END OF LINE” jumper.
• 5C is the CANbus “DEVICE ADDRESS DIP SWITCH”. CANbus cable not by Liebert. See Note 2 (below).
6) Remote unit shutdown – Replace exiting jumper between terminals TB38-1 and TB38-2 with field supplied normally closed switch having
a minimum 75VA 24VAC rating. Use field supplied Class 1 wiring. (This is an optional feature that may be owner specified.)
7) Alarm terminal connections –
a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common, TB74-2 is normally open, and TB74-3 is
normally closed. 1 Amp 24VAC is the maximum load. Use Class 1 field supplied wiring.
b. Shutdown Alarm Relay indicates when condenser loses power, or when a critical alarm has occurred that shuts down the
condenser unit. TB74-4 is common, TB74-5 is normally open, and TB74-6 is normally closed. 1 Amp 24VAC is the maximum load.
Use Class 1 field supplied wiring.
8) Indoor unit interlock and SPD alarm terminals –
a. On any call for compressor operation, normally open contact is closed across terminals 70 & 71 for Circuit 1, and normally open
contact is closed across terminals 70 & 230 for Circuit 2 from indoor room unit.
b. During SPD alarm, normally open contact is closed across terminals 12 & 13. SPD is an optional device.
9) CANbus shield terminal – Terminal for field connection of the CANbus field supplied cables. Shield of CANbus field supplied cables must
not be connected to ground.
10) Primary low voltage entrance – One 7/8” (22.2mm) diameter knockout that is free for customer low voltage wiring.
11) SPD entrance – One 7/8” (22.2mm) diameter knockout hole located at the bottom of the enclosure. High voltage surge protective device
(SPD) is optional.
NOTES:
1. Refer to specification sheet for unit voltage rating, full load amp, and wire size amp ratings.
2. The CANbus wiring is field supplied and must be:
- Braided shield or foil shield with drain wire
- Shield must be wired to ground at indoor unit
- 22-18AWG stranded tinned copper
- Twisted pair (minimum 4 twists per foot)
- Low Capacitance (15pF/FT or less)
- Must be rated to meet local codes and conditions
- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER
3. Do not run in same conduit, raceway, or chase as high voltage wiring.
4. For CANbus network lengths greater than 450FT (137M) call Factory.
Form No.: DPN001040_REV4
DPN002374 REV : 9
Page :2 /3 REV DATE : 2/17
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL WITH LEE-TEMP
5. All wiring must be sized and selected for insulation case per NEC and other local codes.
6. Do not bend cables to less than four times the diameter of the cable.
7. Do not deform cables when securing in bundles or when hanging them.
8. Avoid running the cables by devices that may introduce noise, such as machines, fluorescent lights, and electronics.
9. Avoid stretching cables.
10. The electrically commutated (EC) motors included in the Liebert MC Condenser are suitable for connection to power supplies with a
solidly grounded neutral or high resistance to ground or corner ground.
A. Acceptable power supplies for 208 to 575V nominal units:
• 208V wye with solidly grounded neutral and 120V line to ground;
• 380V wye with solidly grounded neutral and 220V line to ground;
• 480V wye with solidly grounded neutral and 277V line to ground;
• 575V wye with solidly grounded neutral and 332V line to ground (uses step-down transformer);
• Wye with high resistance (or impedance) ground;
• Delta with corner ground
B. Unacceptable power supplies for 208V to 575V nominal units:
• Delta without ground or with floating ground;
• Delta with grounded center tap.
Form No.: DPN001040_REV4
DPN002374 REV : 9
Page :3 /3 REV DATE : 2/17
LIEBERT MC CONDENSER
PIPING DIMENSIONAL DATA
DUAL CIRCUIT 2 FAN & 4 FAN UNITS
COVER *
VERTICAL
INVERTED TRAPS
ARE FACTORY PROVIDED
INSIDE CONDENSER
FIELD PIPING
LEAVING LIQUID
LINE
HORIZONTAL
ENTERING HOT
GAS LINE
DETAIL A
CIRCUIT #1 CIRCUIT #2
C VIEW
B VIEW COVER*
POSITION ELBOW TO
DIRECT RELIEF VALVE B VIEW FASTEN HOT GAS LINE TO CABINET
USING FLAT SURFACE CLAMPS WITH
DOWNWARD ISOLATORS(FIELD SUPPLIED)
LEAVING SEE DETAIL A-A
LIQUID LINE
LIQUID LINE HOT GAS LINE
FROM CONDENSER TO CONDENSER
GENERAL ARRANGEMENT
DPN002426 REV : 7
Page :1 /1 REV DATE : 12/16
LIEBERT DRYCOOLER
PIPING CONNECTIONS
6 & 8 FAN QUIET-LINE MODELS
INLET CONNECTIONS
OUTLET CONNECTIONS
DPN002430 REV : 2
Page :1 /1 REV DATE : 3/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW AIR COOLED 35-42kW (10-12 TONS)
SCROLL OR DIGITAL SCROLL COMPRESSOR MODELS W/ EC FANS
ECR
2 R1 ECS 5
X O
1
HUM
2 R2
L1L2 CPD
3
35" G1G2 EC Fan Outlet
889mm Y
LV1
E1 E2 LV2
LV3
2 R3 Top View 73"
FRONT OF UNIT
1854mm
9 7/8"
14 1/4" 251mm 4 CGD 6 Front View
362mm (Left Panel Not Shown)
Notes: Left Side View
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field routed alternatives for refrigerant gas & liquid line connection points.
3. EC fan shown. See submittal page DPN003458 for EC fan outlet & plenum dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only.
6. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
DPN002740 REV : 3
Page :1 /1 REV DATE : 5/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW WATER/GLYCOL/GLYCOOL™ 35-42kW (10-12 TONS)
SCROLL & DIGITAL SCROLL COMPRESSOR MODELS
ECR
W/ EC FANS
2 W1, W2 ECS 5
X O
1
HUM
35" 3
889mm CPD Y
EC Fan Outlet
2 7/8"
73mm LV1
LV2
E1 E2 LV3
WS
WS WR
3 7/8"
98mm WR
CGD 4
9 7/8"
251mm
CGD 4 Front View
14 1/4" (Left Panel Not Shown)
362mm
Notes:
Left Side View
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ±1/2" (13mm).
3. EC fan shown. See submittal page DPN003458 for EC fan outlet and plenum dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only (four-pipe systems).
DPN002741 REV : 4
Page :1 /1 REV DATE : 5/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW AIR COOLED 77kW (22 TONS)
SEMI-HERMETIC COMPRESSOR MODELS
ECR
W/ EC FANS
2 R1 ECS 5 X O 1
2 R2 HUM
35"
889mm 3
L1L2G1G2 CPD Y
EC Fan Outlet
LV1
E1
E2 LV2
LV3
Top View Front of Unit
109"
2 R3 2769mm
6
3 7/8" G1 G2
98mm 20" L1L2
509mm
CGD 4
9 7/8"
251mm CGD 4 Front View
14 1/4" (Left Panel Not Shown)
362mm
Notes:
Left Side View
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ±1/2" (13mm).
2. Field routed alternatives for refrigerant gas & liquid line connection points.
3. EC fans shown. See submittal page DPN003453 for EC fan outlet and plenum dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only.
6. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
DPN002742 REV : 3
Page :1 /1 REV DATE : 5/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW AIR COOLED 53-77kW (15-22 TONS)
SCROLL OR DIGITAL SCROLL COMPRESSOR MODELS
2 R1 ECR 5
ECS 5 X O
1
2 R2 HUM
CPD 3
35" EC Fan Outlet
889mm Y
G1G2
L1 L2 LV1
E1
E2 LV2
2. Field routed alternatives for refrigerant gas and liquid line connection points.
3. EC fans shown. See submittal page DPN003453 for EC fan outlet and plenum dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only.
6. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
7. Digital Scroll compressor not available on DS077 models.
POINT DESCRIPTION X in. (mm) Y in. (mm) CONNECTION SIZE / OPENING
R1 2 REFRIGERANT ACCESS (TOP) 83-5/8 (2124) 2 (51) 12"(305mm) X 4" (102mm)
R2 2 REFRIGERANT ACCESS (BOTTOM) 82-3/4 (2102) 14-3/4 (375) 12-3/16" (310mm) X 4" (102mm)
R3 2 REFRIGERANT ACCESS (SIDE) N/A N/A 6" (152mm) X 17-3/16" (437mm)
53kW (15TONS) 70 & 77kW (20 & 22TONS)
L1 LIQUID LINE SYSTEM 1 94-11/16 (2405)
16-3/4 (425) 1/2" O.D. Cu 5/8" O.D. Cu
L2 LIQUID LINE SYSTEM 2 91-7/8 (2334)
G1 6 HOT GAS DISCHARGE 1 88-3/4 (2254)
16-3/8 (416) 7/8" O.D. Cu 1-1/8" O.D. Cu
G2 6 HOT GAS DISCHARGE 2 85-9/16 (2173)
CGD 4 CONDENSATE GRAVITY DRAIN N/A N/A 3/4" NPT FEMALE
CPD CONDENSATE PUMP DISCHARGE (OPT) 11-7/8 (302) 1/2" O.D. Cu
79-5/16 (2015)
HUM HUMIDIFIER SUPPLY LINE 9-7/8 (251) 1/4" O.D. Cu
ECS 5 ECON-O-COIL SUPPLY 7-7/8 (200)
78-5/8 (1997) 2-1/8" O.D. Cu
ECR 5 ECON-O-COIL RETURN 4-5/8 (117)
E1 ELECTRICAL CONN. (HIGH VOLT) 78-1/8 (1984)
30 (762) 2-1/2"
E2 ELECTRICAL CONN. (HIGH VOLT) 74-3/8 (1889)
LV1 ELECTRICAL CONN. (LOW VOLT) 28-9/16 (725)
Form No.: DPN001040_REV4
HUM
35"
889mm CPD 3
EC Fan Outlet Y
2 7/8"
73mm
LV1
E1 E2 LV2
LV3
WS
WS WR
3 7/8"
98mm WR
CGD 4
3. EC fan shown. See submittal DPN003453 for EC fan outlet & plenum dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only (four-pipe system).
2 R2 HUM
3
35"
889mm CPD EC Fan Outlet
L1 L2 G1G2
LV2 LV1
LV4 LV3
E1 E2
Y
Top View FRONT OF UNIT
132"
2 R3 3353mm
9 7/8" 4 CGD
Front View
251mm
14 1/4"
(Left front panel not shown)
362mm
Notes:
Left Side View
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of u 1/2" (13mm).
2. Field routed alternatives for refrigerant gas and liquid line connection points.
3. EC fans shown. See submittal page DPN003459 for EC fan outlet and plenum dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only.
6. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
7. Digital Scroll Compressor not available on DS105.
POINT DESCRIPTION X in. (mm) Y in. (mm) CONNECTION SIZE / OPENING
R1 REFRIGERANT ACCESS (TOP) 2 106-7/8 (2715) 1-7/8 (48) 22-1/2"(572mm) X 15-3/16" (386mm)
R2 REFRIGERANT ACCESS (BOTTOM) 2 109-1/8 (2772) 13-7/8 (352) 16-7/16" (418mm) X 4" (102mm)
R3 REFRIGERANT ACCESS (SIDE) 2 N/A N/A 6" (152mm) X 17-3/16" (437mm)
L1 LIQUID LINE SYSTEM 1 121-3/4 (3092)
16-3/4 (425) 5/8" O.D. Cu
L2 LIQUID LINE SYSTEM 2 118-1/8 (3000)
G1 HOT GAS DISCHARGE 1 6 118-1/4 (3004)
14-1/4 (362) 1-1/8" O.D. Cu
G2 HOT GAS DISCHARGE 2 6 115-5/8 (2937)
CGD CONDENSATE GRAVITY DRAIN 4 N/A N/A 3/4" NPT FEMALE
CPD CONDENSATE PUMP DISCHARGE (OPT) 102-3/8 (2600) 13-5/8 (346) 1/2" O.D. Cu
HUM HUMIDIFIER SUPPLY LINE 13-1/8 (333) 1/4" O.D. Cu
ECS ECON-O-COIL SUPPLY 5 10-1/4 (260)
101-1/8 (2569) 2-5/8" O.D. Cu
ECR ECON-O-COIL RETURN 5 5-1/4 (133)
E1
ELECTRICAL CONN. (HIGH VOLT) 30 (762) 2-1/2"
E2 97-7/8 (2486)
LV1 30-1/4 (768)
34-1/8 (867)
LV2 31-3/4 (806)
ELECTRICAL CONN. (LOW VOLT) 7/8"
Form No.: DPN001040_REV4
HUM
35" CPD
889mm 3
EC Fan Outlet
2 7/8" LV2 LV1
73mm LV3
E1 E2 LV4
Y
2 W3 Top View FRONT OF UNIT
132"
3353mm
WS
WR
3 7/8" WS
98mm WR
CGD 4
9 7/8"
251mm CGD 4 Front View
14 1/4"
362mm
(Left Front Panel not shown)
Left Side View
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
3. EC fans shown. See submittal DPN003459 for EC fan outlet & plenum dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only (four-pipe system).
Solenoid
Valve
Sensing Bulb
Isolation Sight
3 Valves Glass External
Filter Equalizer
Dryer
Service
Liquid Valves
Return Muffler
to Unit
3. Components not supplied by Liebert, but are required for proper circuit operation and maintenance.
4. Components supplied by Liebert and must be field installed (70kW, 77kW, and 105Kw models only).
Form No.: DPN001040_REV4
DPN003047 REV : 1
Page :1 /1 REV DATE : 12/16
LIEBERT DS
FLOORSTAND & FLOOR PLANNING DIMENSIONAL DATA
UPFLOW 35-42kW (10-12 TONS) MODELS W/ FORWARD CURVED BLOWERS
A + 1-1/2" (38mm)
(with feet)
33"
838mm
34 1/2"
876mm
(with feet)
1"
25mm
Typ.
2
C
7/8"
23mm
3"
Height in ( mm )
76mm C 2
Dimensional Data in (mm) 9 (229)
A B 12 (305)
Water/Glycol/GLYCOOL™ cooled 15 (381)
85 (2159) 26 (660)
Scroll & Digital Scroll Models 18 (457)
Air-Cooled Scroll and 21 (533)
72 (1829) 13 (330)
Digital Scroll Models 24 (610)
Notes:
1. Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang floorstand 1" (25mm).
Form No.: DPN001040_REV4
2. Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C.
DPN003134 REV : 3
Page :1 /1 REV DATE : 5/17
LIEBERT DS
FLOORSTAND & FLOOR PLANNING DIMENSIONAL DATA
UPFLOW 53-77kW (15-22 TONS) MODELS W/ FORWARD CURVED BLOWERS
A + 1-1/2" (38mm)
(with feet)
A
34 1/2"
876mm
(with feet)
33"
838mm
1" TYP.
25mm
7/8"
23mm
C*
3"
76mm
2. Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C.
Form No.: DPN001040_REV4
DPN003141 REV : 3
Page :1 /1 REV DATE : 5/17
LIEBERT DS
FLOORSTAND & FLOOR PLANNING DIMENSIONAL DATA
UPFLOW 105kW (30 TONS) MODELS W/ FORWARD CURVED BLOWERS
132 1/2"
3366mm
(with feet)
131"
3327mm
26"
660mm
34 1/2"
876mm
(with feet)
33"
838mm
1" TYP.
25mm
7/8"
23mm
A 2
3"
76mm
Height in. ( mm )
A 2
9 (229)
12 (305)
15 (381)
18 (457)
Notes:
1. Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang floorstand 1" (25mm). 21 (533)
Form No.: DPN001040_REV4
24 (610)
2. Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height A.
DPN003149 REV : 3
Page :1 /1 REV DATE : 5/17
LIEBERT DS
UPFLOW PLENUM DIMENSIONAL DATA
35kW-105kW (10-30 TONS) MODELS W/ FORWARD CURVED BLOWERS
FRONT VIEWS - CHECK ONE (1): REAR VIEWS - CHECK ONE (1):
1" H
25mm
76"
1930mm
31 1/2"
800mm 32"
Center of Feet 813mm
at each end Center of Feet
between each end
1"
25mm
Typ.
D 32 3/4"
Center of Feet 832mm
Center of Feet 4
C
Center of Feet
33"
A 838mm
6
19 1/4"
5 489mm
F
7/8"
23mm
Typ.
34 1/2"
3" Typ. 876mm
76mm At each end
B
Overall Length 35"
889mm
Overall Depth
77kW, All Semi-hermetic Models 108 (2743) 109-1/2 (2781) 106-1/2 (2705) 24-3/4 (629) 42 (1067)
77kW, Air-Cooled Scroll Models 97 (2464) 98-1/2 (2502) 95-1/2 (2426) 13-3/4 (349 48 (1219)
DPN003173 REV : 4
Page :1 /1 REV DATE : 5/17
LIEBERT DS
FLOORSTAND DIMENSIONAL DATA
105kW (30 TONS) MODELS W/ EC FANS
31 1/2" 32"
800mm 813mm
Center of Feet Center of Feet
Typ. Both Ends between each end
24 3/4"
629mm 1"
Center of Feet 25mm
73 3/4" Typ.
1873mm
Center of Feet 129 1/2"
3289mm Center of Feet
4
131" 33"
3327mm 838mm
6
19 1/4"
489mm
A 5
34 1/2"
7/8" 876mm
3" 23mm
76mm At each end
132 1/2" Overall Length
3366mm 35"
889mm
Notes: Overall Depth
1. This floorstand should be used when EC fans are intended to be lowered under Height in ( mm )
a raised floor. A 5
2. Right side of paneled unit is flush with right side of floorstand. All other paneled sides 24 (610)
overhang floorstand 1" (25mm). 30 (762)
3. The floorstand used with EC units is not symmetrical and its orientation to the 36 (914)
Liebert DS is critical for lowering the EC fans. Unless the floorstand is installed in 42 (1067)
the correct position, the blowers will not lower into the floorstand.
48 (1219)
4. Jack and jack support are shipped loose and are intended to be placed into position
under each fan and utilized to lower or raise that fan as needed for Downflow units.
5. Leveling feet are provided with u 1-1/2” (38mm) adjustment from nominal height “A”.
DPN003174 REV : 5
Page :1 /1 REV DATE : 6/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
DOWNFLOW AIR COOLED 35-42kW (10-12 TONS)
SCROLL OR DIGITAL SCROLL COMPRESSOR MODELS
A A
X
O
1
R
L1 L2 G1 G2
35"
889mm EC FAN
OUTLET
ECS 3 LV1
4
LV2
HUM CD 2 LV3
E1 E2 ECR 3
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
3. Supplied on Dual Cooling systems only.
4. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
DPN003239 REV : 3
Page :1 /1 REV DATE : 5/17
LIEBERT DS
FLOORSTAND DIMENSIONAL DATA
35kW - 42kW (10-12 TONS) W/ EC FANS
Notes:
1. This floorstand should be used when EC fans are intended to be lowered under
a raised floor. 24-48" floorstands allow fan to be lowered under the raised floor.
2. Right side of paneled unit is flush with right side of floorstand. All other paneled sides
overhang floorstand 1" (25mm).
3. The floorstand used with EC units is not symmetrical and its orientation to the
Liebert DS is critical for lowering the EC fans. Unless the floorstand is installed in
the correct position, the blowers will not lower into the floor stand.
4. Jack and jack support are shipped loose and are intended to be placed into position
under each fan and utilized to lower or raise that fan as needed for Downflow units.
5. Leveling feet are provided with u 1-1/2” (38mm) adjustment from nominal height “E”.
31 1/2" 32"
800mm 813mm
Center of Feet Center of Feet
at each end
1" TYP
25mm
D
Center of Feet 4
C Center of Feet
A
Gussets supplied on floorstands
12" (305 mm) tall and greater. 33"
838mm
6
5
E 23 1/4"
591mm
7/8"
23mm
34 1/2"
876mm
3" At Each End
76mm
B Overall Length 35"
889mm
Overall Depth
48 (1219)
DPN003240 REV : 5
Page :1 /1 REV DATE : 9/17
LIEBERT DS
CANbus & INTERLOCK CONNECTIONS
BETWEEN LIEBERT DS & LIEBERT MC CONDENSER (PREMIUM)
P80 B A P15
TB50
CONDENSER
H
J6 TERMINATION JUMPER
1
CAN H
TB50
1
OUTPUT 2 D58
J6
3 CAN L MUST BE SET TO PINS 1 AND 2.
L
3
H
J4
TB49
3
TB49
1
INPUT TB50
3
2 OUTPUT
1
2
3
CAN H
CAN L
L
3
CANbus ADDRESSING SWITCH
1
TB49
ON INPUT
1
2
3
J6
3
CAN SW6
BOOTPSWD SYS APP
ON
CAN SW6
DETAIL 3
SHIELD CONNECTION
CAN CABLE CONNECTION (A)
DPN003267 REV : 4
Page :1 /1 REV DATE : 4/18
LIEBERT MC CONDENSER
CABINET & ANCHOR DIMENSIONAL DATA
575V 2 FAN (MCS056, MCM080, MCL110) DUAL CIRCUIT
Option 575V
Option
H
TOP OF
G FAN GUARD
A F
A*
A
Anchor Plan
Main
Full height leg supplied for Electric M L K
each Lee-Temp or Box
DSE Receiver required End
3
3 6 1/2"
6 1/2" 165mm Ref.
165mm Ref.
Dual Circuit Only
15 1/4" K 15 1/4"
387mm 387mm
Dual Circuit Only
J 3
Left Side of Unit
Lee-Temp or DSE Only Front View (Lee-Temp Shown) 3
3 5/8"
93mm LIEBERT
13/16" Typ. F
21mm MODEL
2
Typ. All primary dimensions (LEG HEIGHT DIMENSIONS)
NUMBER
in tables are in inches
(Secondary are in mm) MCS056
18 (457) 36 (914) 48 (1219) 60 (1524)
except where specified MCM080
7" 1 7/8"
178mm 48mm DIM "G" 31-5/8 (803) 49-5/8 (1260) 61-5/8 (1565) 73-5/8 (1870)
Typ. Typ. DIM "H" 39-5/8 (1006) 57-5/8 (1464) 69-5/8 (1768) 81-5/8 (2073)
1/2" (13mm) X 1" (25mm) MCL110
Obround Typ. DIM "G" 35-7/8 (911) 53-7/8 (1368) 65-7/8 (1673) 77-7/8 (1978)
DIM "H" 43-5/8 (1108) 61-5/8 (1565) 73-5/8 (1870) 85-5/8 (2175)
DETAIL A
Typical All Legs
Note: J
1. Liebert recommends a clearance of LIEBERT Lee-Temp
36” (915mm) on each side for proper A*
MODEL A C D or K L M
operation and component access. (575V ONLY)
NUMBER DSE Receivers
2 Cross bracing required for legs longer Only
than 18" (457mm). Quantity varies per
MCS056 94-7/8 (2411) 103-1/8 (2619) 88-3/8 (2245) 86-3/4 (2203) 42-1/2 (1079) 42-1/2 (1080) 40-7/8 (1038) 35-7/8 (910)
model & options selected.
MCM080 105-1/4 (2674) 113-7/16 (2882) 96-1/16 (2440) 94-7/16 (2398) 46-5/16 (1177) 46 (1168) 44-3/8 (1127) 39-5/16 (999)
3 For DSE models only, 6-1/2" (165mm)
Form No.: DPN001040_REV4
MCL110 124-1/8 (3152) 133-1/8 (3381) 112-1/8 (2848) 110-1/2 (2806) 54-3/8 (1381) 55-1/2 (1410) 53-7/8 (1368) 48-3/4 (1238)
dimension is 9-1/4" (235mm) and
15-1/4 (387mm) dimension is not applicable.
DPN003437 REV : 4
Page :1 /1 REV DATE : 12/16
LIEBERT MC CONDENSER
CABINET & ANCHOR DIMENSIONAL DATA
575V
Option 4 FAN (MCM160, MCL220)
B
575V
Option
Lifting Eyebolts
Typ. (4) Places
F
H
A* TOP OF
A FAN GUARD
G
A
Main
Full height Leg Electric
Anchor Plan supplied for each Box M L K
Lee-Temp or DSE End
Receiver required 3
6 1/2"
165mm Ref.
J
Left Side of Unit Lee-Temp or DSE Only
15 1/4"
387mm
6 1/2"
165mm Ref.
3
Note: Dual Circuit Only 15 1/4"
3 387mm
3 5/8" 1. Liebert recommends a clearance of 36” (915mm)
3 Dual
93mm on each side for proper operation and component access.
13/16" Circuit
21mm Typ. K Only
1 7/8" 2 Cross bracing required for legs longer than 18" (457.2mm).
Typ. 48mm
Typ. Quantity varies per model & options selected. Front View (Lee-Temp shown)
3 For DSE models only, 6-1/2" (165mm) dimension is 9-1/4" (235mm)
and 15-1/4 (387mm) dimension is not applicable.
7" LIEBERT
F 2
178mm MODEL
Typ. LEG HEIGHT DIMENSIONS in. (mm)
NUMBER
18 (457) 36 (914) 48 (1219) 60 (1524)
1/2" (13mm) X 1" (25mm) MCM160
Obround Typ. DIM "G" 31-5/8 (803) 49-5/8 (1260) 61-5/8 (1565) 73-5/8 (1870)
DETAIL A DIM "H" 39-5/8 (1006 57-5/8 (1464) 69-5/8 1768) 81-5/8 (2073)
Typical all legs MCL220
DIM "G" 35-7/8 (911) 53-7/8 (1368) 65-7/8 (1673) 77-7/8 (1978)
DIM "H" 43-5/8 (1108) 61-5/8 (1565) 73-5/8 (1870) 85-5/8 (2175)
MCM160 202-7/16 (5142) 210-5/8 (5350) 113-1/2 (2883) 192-1/4 (4883) 94-7/16 (2398) 96-3/16 (2444) 46-5/16 (1177) 46 (1168) 44-3/8 (1127) 39-5/16 (999)
MCL220 236-5/16 (6003) 245-5/16 (6231) 129-9/16 (3291) 224-3/8 (5699) 110-1/2 (2806) 112-1/4 (2851) 54-3/8 (1381) 55-1/2 (1410) 53-7/8 (1368) 48-3/4 (1238)
DPN003439 REV : 4
Page :1 /1 REV DATE : 3/17
LIEBERT DS
PLENUM DIMENSIONAL DATA
Notes: UPFLOW 53-77kW (15-22 TONS) W/ EC FANS
1. All Plenums must be field assembled and fans wired to unit.
2. Shaded areas indicate a recommended minimum clearance of 36" (914mm) from the bottom of the unit to the top of the plenum.
4. Top duct flanges on plenum top for Supply Air ducting when solid panel plenum is used. 7/8" 4
22mm
D
5. Compressor Plenum is optional and must be ordered separately.
5 H
L
3
F
E
2
7/8"
22mm
A
F
B
Note:
Both top duct opening
and grilles shown. See
spec sheet for specific
application.
DPN003453 REV : 4
Page :1 /1 REV DATE : 5/17
LIEBERT DS
PLENUM DIMENSIONAL DATA
Notes:
UPFLOW 35-42kW (10-12 TONS) MODELS W/ EC FANS
1. All Plenums must be field assembled and EC Fans wired to unit.
D 7/8"
2. Shaded areas indicate a recommended minimum CLEARANCE OF 22mm 4
36" (914mm) from the bottom of the unit to the top of the plenum.
3. Must have access to remove Front Grill or panel to remove EC Fans. C
4. Top duct flanges on plenum top for Supply Air ducting when
solid panel plenum is used. J
5. Compressor Plenum is optional and must be
G
ordered separately.
6. Air Cooled Scroll or Digital Scroll Compressor.
F 3
5 E Note:
7/8" Both top duct opening
22mm
and grilles shown. See
spec sheet for specific
A application.
F
2
B
59-1/4 (1505) 33-3/4 (857) 57-9/16 (1463) 32-1/16 (815) 56-11/16 (1440) 1-5/16 (33) 19-11/16 (500) 4-5/16 (109)
DPN003458 REV : 4
Page :1 /1 REV DATE : 5/17
LIEBERT DS
PLENUM DIMENSIONAL DATA
UPFLOW 105kW (30 TONS) MODELS W/ EC FANS
Note:
1. All Plenums must be field assembled and EC Fans wired to unit.
D
2. Shaded areas indicate a recommended minimum CLEARANCE OF 7/8"
36" (914mm) from the bottom of the unit to the top of the plenum. 22mm 4
3. Must have access to remove Front Grill or panel to remove EC Fans.
4. Top duct flanges on plenum top for Supply Air ducting when
solid panel plenum is used. C
5. Compressor Plenum is optional and must be ordered separately. L
J
5
3
G
N H
F Note:
Both top duct opening
and grilles shown. See
spec sheet for specific
M application.
E
2
7/8" A
22mm
G
B
Partial View
Compressor Plenum
Main unit Plenum Main unit Plenum weight lb. (kg) Width Height
Height L Weight
N M
in. (mm) Non-grilled plenum Front discharge Rear discharge lb. (kg)
in. (mm) in. (mm)
24 (610) 131 (59) 206 (93 kg) 220 (100) 24 (610) 33 (15)
30 (762) 162 (74) 26 30 (762) 37 (17)
N/A 36 (914) 42 (19)
36 (914) 188 (85)
Plenum Dimensional Data in. (mm) EC Fan Assembly Weight
No. of Fans/Unit
Form No.: DPN001040_REV4
A B C D E F G H J K lb. (kg)
105 (2673) 34 (864) 104 (2641) 32 (813) 80 (2032) 22 (559) 1 (25) 2 (51) 20 (508) 4 (102) 3 93 (42)
DPN003459 REV : 4
Page :1 /1 REV DATE : 6/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
DOWNFLOW WATER/GLYCOL/GLYCOOL™ 35-42kW (10-12 TONS)
ALL COMPRESSOR MODELS
A A
X
O
1
W Y
WS
35" EC FAN
889mm WR OUTLET
ECS 3
LV1
HUM CD 2 LV2
LV3
E1 E2 ECR 3
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
3. Supplied on Dual Cooling systems only (four-pipe system).
4. Semi-Hermetic Compressor not available on 35kW - 42kW models.
DPN003530 REV : 3
Page :1 /1 REV DATE : 5/17
LIEBERT DS
CABINET DIMENSIONAL DATA
DOWNFLOW 35-105kW (10-30 TONS) MODELS
C Opening
Condenser Cleanout Access
Model Number Compressor Type Cooling Type A in. (mm) B in. (mm) C in. (mm)
Air Cooled & AirCooled w/ Dual Cool 73 (1854) 72 (1854)
35kW - 42kW Scroll or Digital Scroll 56-7/8 (1445)
Water/Glycol/GLYCOOL™/Dual Cool 86 (2184) 85 (2184)
Air Cooled & AirCooled w/ Dual Cool 98 (2489) 97 (2489)
53kW - 70kW Scroll or Digital Scroll
Water/Glycol/GLYCOOL™/Dual Cool 109 (2769) 108 (2743)
Air Cooled & AirCooled w/ Dual Cool 98 (2489) 97 (2489)
Scroll 80 (2032)
Water/Glycol/GLYCOOL™/Dual Cool
77kW
Air Cooled & AirCooled w/ Dual Cool 109 (2769) 108 (2743)
Semi-Hermetic
Water/Glycol/GLYCOOL™/Dual Cool
Air Cooled & AirCooled w/ Dual Cool
Scroll
Water/Glycol/GLYCOOL™/Dual Cool
105kW 132 (3353) 131 (3327) 102-13/16 (2611)
Air Cooled & AirCooled w/ Dual Cool
Semi-Hermetic
Water/Glycol/GLYCOOL™/Dual Cool
Form No.: DPN001040_REV4
DPN003643 REV : 3
Page :1 /1 REV DATE : 5/17
LIEBERT DS
CABINET DIMENSIONAL DATA
UPFLOW 35-105kW (10-30 TONS) W/ FORWARD CURVED BLOWERS
Alternate Refrigerant or
Condenser fluid C
Piping Entrance
33"
838mm
35"
889mm
5/16" Bezel
8mm
76"
1930mm
Model Number Compressor Type Cooling Type A in. (mm) B in. (mm) C in. (mm) 34"
864mm
AirCooled/Air Cooled w/Dual Cool 73 (1854) 72 (1829)
35kW - 42kW Scroll or Digital Scroll 59-1/4 (1504)
Water/Glycol/GLYCOOL™/Dual Cool 86 (2184) 85 (2159) 105kW (30 Tons)
AirCooled/Air Cooled w/Dual Cool 98 (2489) 97 (2464)
53kW - 70kW Scroll or Digital Scroll
Water/Glycol/GLYCOOL™/Dual Cool 109 (2769) 108 (2743)
AirCooled/Air Cooled w/Dual Cool 98 (2489) 97 (2464)
Scroll 82-1/8 (2086)
Water/Glycol/GLYCOOL™/Dual Cool
77kW
AirCooled/Air Cooled w/Dual Cool 109 (2769) 108 (2743)
Semi-hermetic
Water/Glycol/GLYCOOL™/Dual Cool
AirCooled/Air Cooled w/Dual Cool
Scroll
Water/Glycol/GLYCOOL™/Dual Cool
105kW 132 (3353) 131 (3327) 105-1/4 (2673)
AirCooled/Air Cooled w/Dual Cool
Semi-hermetic
Water/Glycol/GLYCOOL™/Dual Cool
Form No.: DPN001040_REV4
DPN003646 REV : 4
Page :1 /1 REV DATE : 5/17
LIEBERT DS
DISASSEMBLY DIMENSIONAL DATA
DOWNFLOW 35-42kW (10-12 TONS) MODELS
W/ SCROLL & DIGITAL SCROLL COMPRESSORS
FILTER &
ELECTRIC BOX ASSEMBLY
39"
991mm
76"
1930mm 59 7/16"
1509mm
37"
940mm
33" A 59"
838mm 1499mm
B Assembled Length
Cooling Ty pe A in. (mm) B in. (mm) APPROXIMATE DRY WEIGHT lb (kg) (Includes Panels)
Assembly
Air Cooled Air Cooled A/C w / Dual Cool Water/Gly col GLYCOOL™/Dual Cool
13 (330) 72 (1829)
Air Cooled w /Dual Cool Compressor Assembly 490 (223) 490 (223) 800 (364) 800 (364)
Water/Gly col Filter & Electric Box Assembly 210 (96) 210 (96) 210 (96) 210 (96)
26 (660) 85 (2159)
GLYCOOL™/Dual Cool Blow er & Coil Assembly 770 (350) 920 (418) 770 (350) 920 (418)
Notes:
1. Drawing Views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual.
Form No.: DPN001040_REV4
DPN003647 REV : 2
Page :1 /1 REV DATE : 5/17
LIEBERT DS
DISASSEMBLY DIMENSIONAL DATA
DOWNFLOW 53-77kW (15-22 TONS) MODELS
76"
1930mm
59 7/16"
1510mm
37"
940mm
33" A
838mm 82"
2083mm
B Assembled Length
Compressor Ty pe Cooling Ty pe A in. (mm) B in. (mm)
Air Cooled Notes:
15 (381) 97 (2464)
Air Cooled w / Dual Cool 1. Drawing Views are simplified with panels removed
Scroll or Digital Scroll to show overall dimensions. See disassembly and
Water/Gly col
handling instructions in installation manual.
GLYCOOL™/Dual Cool 2. Semi-Hermetic Compressor options only available on
Air Cooled 77kW models.
26 (660) 108 (2743)
Air Cooled w / Dual Cool
Semi-Hermetic 2
Water/Gly col
GLYCOOL™/Dual Cool
APPROXIMATE DRY WEIGHT lb (kg) (Includes Panels)
Assembly Semi-Hermetic Compressor 2 Scroll or Digital Scroll Compressor Semi-Hermetic Compressor 2 Scroll or Digital Scroll Compressor
Air Cooled A/C w / Dual Cool Air Cooled A/C w / Dual Cool Water/Gly col GLYCOOL™/Dual Cool Water/Gly col GLYCOOL™/Dual Cool
Compressor Assembly 970 (441) 970 (441) 540 (246) 540 (246) 1270 (578) 1270 (578) 840 (382) 840 (382)
Form No.: DPN001040_REV4
Filter & Electric Box Assembly 250 (114) 250 (114) 250 (114) 250 (114) 250 (114) 250 (114) 250 (114) 250 (114)
Blow er & Coil Assembly 1230 (560) 1410 (641) 1230 (560) 1410 (641) 1230 (560) 1410 (641) 1230 (560) 1410 (641)
DPN003648 REV : 2
Page :1 /1 REV DATE : 5/17
LIEBERT DS
DISASSEMBLY DIMENSIONAL DATA
DOWNFLOW 105kW (30 TONS) MODELS
Unit w/ Scroll
Unit w/ Semi-Hermetic Compressor Section
Compressor Section FILTER & ELECTRIC BOX ASSEMBLY
39"
991mm
41 11/16"
Compressor Section Assembly 1059mm
Semi-Hermetic shown
for reference
76"
BLOWER & COIL ASSEMBLY 1930mm
Assembled Height
76"
1930mm
59 7/16"
1509mm
37"
940mm
Blow er & Coil Assembly 1560 (708) 1915 (870) 1560 (708) 1915 (870) 1560 (708) 1915 (870)
DPN003649 REV : 1
Page :1 /1 REV DATE : 1/17
LIEBERT DS
DISASSEMBLY DIMENSIONAL DATA
UPFLOW 35-42kW (10-12 TONS) MODELS
W/ SCROLL & DIGITAL SCROLL COMPRESSORS
76"
1930mm
Assembled
76" Height
1930mm
45 13/16"
1163mm
33" 59"
A 1499mm
838mm
B Assembled Length
Cooling Ty pe A in (mm) B in. (mm) APPROXIMATE DRY WEIGHT lb (kg) (Includes Panels)
Assembly
Air Cooled Air Cooled A/C w / Dual Cool Water/Gly col GLYCOOL™/Dual Cool
13 (330) 72 (1829)
Air Cooled w / Dual Cool Compressor Assembly 490 (223) 490 (223) 800 (364) 800 (364)
Water/Gly col Forw ard Curv ed Blow er
26 (660) 85 (2159) 510 (231) 510 (231) 510 (231) 510 (231)
GLYCOOL™/Dual Cool & Electric Box Assembly
EC Fan & 2
360 (163) 360 (163) 360 (163) 360 (163)
Electric Box Assembly
Filter & Coil Assembly 520 (236) 670 (304) 520 (236) 670 (304)
Notes:
1. Drawing Views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual. EC Fan unit shown.
2. EC Fan wieght not included in this unit weight. Fan is installed in plenum. See DPN003458.
Form No.: DPN001040_REV4
DPN003650 REV : 3
Page :1 /1 REV DATE : 5/17
LIEBERT DS
DISASSEMBLY DIMENSIONAL DATA
UPFLOW 53-77kW (15-22 TONS) MODELS
76"
1930mm
FILTER & COIL ASSEMBLY Assembled Height
76"
1930mm
45 13/16"
1163mm
33" 82"
838mm A 2083mm
B Assembled Length
Compressor Ty pe Cooling Ty pe A in. (mm) B in. (mm)
Air Cooled Notes:
15 (381) 97 (2464) 1. Drawing Views are simplified with panels removed to show overall dimensions.
Air Cooled w / Dual Cool See disassembly and handling instructions in installation manual. EC Fan unit shown.
Scroll or Digital Scroll
Water/Gly col 2. EC Fan weight not included in this unit weight. Fan is installed in plenum.
See DPN003453.
GLYCOOL™/Dual Cool
3. Semi-Hermetic Compressor options only available on 77kW models.
Air Cooled
26 (660) 108 (2743)
Air Cooled w / Dual Cool
Semi-hermetic 3
Water/Gly col
GLYCOOL™/Dual Cool
APPROXIMATE DRY WEIGHT lb (kg) (Includes Panels)
Assembly Semi-Hermetic Compressor 3 Scroll or Digital Scroll Compressor Semi-Hermetic Compressor 3 Scroll or Digital Scroll Compressor
Air cooled A/C w / Dual Cool Air Cooled A/C w / Dual Cool Water/Gly col GLYCOOL™/Dual Cool Water/Gly col GLYCOOL™/Dual Cool
Compressor Assembly 970 (441) 970 (441) 540 (246) 540 (246) 1270 (578) 1270 (578) 840 (382) 840 (382)
Blow er & Electric Box
770 (349) 770 (349) 770 (349) 770 (349) 770 (349) 770 (349) 770 (349) 770 (349)
Assembly
Blow er & Electric Box
600 (272) 600 (272) 600 (272) 600 (272) 600 (272) 600 (272) 600 (272) 600 (272)
Form No.: DPN001040_REV4
Assembly 2
Filter & Coil Assembly 760 (345) 940 (426) 760 (345) 940 (426) 760 (345) 940 (426) 760 (345) 940 (426)
DPN003657 REV : 2
Page :1 /1 REV DATE : 5/17
LIEBERT DS
DISASSEMBLY DIMENSIONAL DATA
UPFLOW 105kW (30 TONS) MODELS
31 1/4"
Compressor Section Assembly 794mm
Semi-Hermetic shown
for reference
76"
FILTER & COIL ASSEMBLY 1930mm
Assembled
Height
76"
1930mm
45 13/16"
1164mm
2. EC Fan weight not included in this unit weight. Fan is installed in plenum. See DPN003459.
Form No.: DPN001040_REV4
DPN003658 REV : 3
Page :1 /1 REV DATE : 6/17
LIEBERT DS
CABINET DIMENSIONAL DATA
UPFLOW 35-105kW (10-30 TONS) MODELS W/ EC FANS
Alternate Refrigeration or
Condenser Fluid
Piping Entrance
33"
838mm
35" 5/16"
889mm 8mm 35-42kW (10-12 Tons)
Bezel
Condenser cleanout 1 3/4"
access 44mm
Low Volt Connection(s)
High Volt connection(s)
3 1/4"
TOP VIEW
83mm
Typ.
Model Number Compressor Type Cooling Type A in. (mm) B in. (mm)
AirCooled/Air Cooled w/Dual Cool 73 (1854) 72 (1829)
35kW - 42kW Scroll or Digital Scroll
Water/Glycol/GLYCOOL™/Dual Cool 86 (2184) 85 (2159)
AirCooled/Air Cooled w/Dual Cool 98 (2489) 97 (2464)
53kW - 70kW Scroll or Digital Scroll
Water/Glycol/GLYCOOL™/Dual Cool 109 (2769) 108 (2743)
AirCooled/Air Cooled w/Dual Cool 98 (2489) 97 (2464)
Scroll
Water/Glycol/GLYCOOL™/Dual Cool
77kW
AirCooled/Air Cooled w/Dual Cool 109 (2769) 108 (2743)
Semi-hermetic
Water/Glycol/GLYCOOL™/Dual Cool
AirCooled/Air Cooled w/Dual Cool
Scroll
Water/Glycol/GLYCOOL™/Dual Cool
105kW 132 (3353) 131 (3327)
AirCooled/Air Cooled w/Dual Cool
Semi-hermetic
Water/Glycol/GLYCOOL™/Dual Cool
Form No.: DPN001040_REV4
DPN003681 REV : 3
Page :1 /1 REV DATE : 5/17
LIEBERT DS
COMPONENT LOCATION
DOWNFLOW MODELS
10
11
12
8
6
13
13. EC Fans
DPN003706 REV : 2
Page :1 /1 REV DATE : 1/17
LIEBERT DS
COMPONENT LOCATION
UPFLOW 28-42kW (8-12 TONS) MODELS
14 18
Plenum shown is included
with EC Fan option.
11 7
2
5
1
15
16
17
12 13
10 4
units only)
18. EC Fans (optional)
DPN003707 REV : 1
Page :1 /1 REV DATE : 1/17
LIEBERT DS
PIPING SCHEMATIC W/ LIEBERT MC CONDENSER
AIR COOLED SCROLL OR DIGITAL SCROLL COMPRESSOR MODELS
Optional Field Installed Relief Valve
Fusible Plug Check Valve Service Head Pressure
Valve Control Valve
Pressure Transducer LIQUID RETURN
LIEBERT DS
LIQUID
Sensing
Bulb EVAPORATOR
35-42kW digital COIL
Solenoid Valve
SUCTION
53-70kW digital
Solenoid Valve
3
Service
Valve For rises over
25ft. (7.6m), trap
Check 3 every 20ft. (6m)
Valve Service Field installed relief valve(s) required or evenly divided
Valve for 50Hz EU CE units rated maximum
COMPRESSOR
External 480 PSIG (33 Bar).
Equalizer
3. Components are not supplied by Liebert, but are required for proper operation and maintenance.
4. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor. Pitch horizontal hot gas piping at a minimum of
1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.
Form No.: DPN001040_REV4
DPN003730 REV : 3
Page :1 /1 REV DATE : 12/17
LIEBERT DRYCOOLER
PIPING SCHEMATIC
MULTIPLE DRYCOOLERS & COOLING UNITS ON COMMON GLYCOL LOOP
HP GPM (L/s) FT.
(kW) Per Pump @ (kPa)
PUMP PACKAGE
TANK
Gal. (L)
Total
GPM
FS (L/s):
DRYCOOLER NO. 1 MODEL Pipe
COOLING UNIT # Diam.: Inches (mm)
GPM (L/s) P: Ft (kPa) MODEL
GPM (L/s) P: Ft. (kPa)
P Ft (kPa):
COOLING UNIT #
MODEL
GPM (L/s)
COOLING UNIT #
P Ft (kPa):
MODEL
GPM (L/s)
P Ft (kPa):
COOLING UNIT #
SEE NOTE 3 MODEL
COOLING UNIT # GPM (L/s)
MODEL P Ft (kPa):
GPM (L/s)
P Ft (kPa):
COOLING UNIT #
MODEL
GPM (L/s)
P Ft (kPa):
DRYCOOLER NO. 2 MODEL
GPM (L/s) P: Ft (kPa)
LEGEND
GATE VALVE NOTES:
1. PRESSURE AND TEMPERATURE GAUGES (OR PORTS FOR SAME) ARE RECOMMENDED TO MONITOR
CHECK VALVE COMPONENT PRESSURE DROPS AND PERFORMANCE.
2. FLOW MEASURING DEVICES, DRAIN AND BALANCING VALVES TO BE SUPPLIED BY OTHERS AND
BUTTERFLY VALVE LOCATED AS REQUIRED.
3. SEE PRODUCT LITERATURE FOR INSTALLATION GUIDELINES AND CLEARANCE DIMENSIONS.
RELIEF VALVE 4. DRAWING SHOWS DUAL PUMP PACKAGE. ALTERNATE PUMP PACKAGES WITH MORE PUMPS MAY BE
CONSIDERED, CONSULT SUPPLIER.
UNION 5. DEPENDING ON THE DRYCOOLER COIL CIRCUITING IT MAY HAVE 2 IN/OUT OR 4 IN/OUT CONNECTION
POINTS.
BALL OR FLOW CONTROL VALVE 6. INSTALL EXPANSION OR COMPRESSION TANK AT THE HIGHEST POINT OF THE SYSTEM.
FS FLOW SWITCH
P: PRESSURE DROP
STRAINER/FILTER
Form No.: DPN001040_REV4
DPN003822 REV : 2
Page :1 /1 REV DATE : 6/17
LIEBERT DRYCOOLER
GENERAL ARRANGEMENT DIAGRAM & DIMENSIONAL DATA
ASME COMPRESSION TANK KITS GLYCOL/GLYCOOL™ SYSTEMS
1 Compression Tank Air Tube
Gauge Glass w/
1 Shutoff Valves
Pitch minimum 1" per foot
Drain Tank
1 Fitting
1 Airtrol Tank Fitting
(Combination Air Vent Shutoff Valve 1
& Liquid Control)
Notes:
Pressure Relief Valve 2
1. These components are factory supplied and shipped loose.
Field installtion and piping by others. 3
2. These components are not factory supplied by Liebert, but are
required for proper system operation and maintenance. Field
installation and piping by others.
3. Field to provide a means for adding pre-mixed Glycol to system.
Drain
4. Install compression tank at the highest point of the system.
B
W
D A
W
T T
C
DPN003898 REV : 2
Page :1 /1 REV DATE : 5/17
LIEBERT MC CONDENSER
AIR COOLED PIPING SCHEMATIC
CONDENSER ABOVE INDOOR UNIT
Liquid
Gas
Gas
Notes:
Field piping
1
Gas
Gas
4
2 Liquid
Liquid
Form No.: DPN001040_REV4
DPN003954 REV : 3
Page :1/3 REV DATE : 5/17
LIEBERT MC CONDENSER
AIR COOLED PIPING SCHEMATIC
CONDENSER AND INDOOR UNIT AT SAME LEVEL
Indoor Unit
Gas 1
Liquid
Field piping
Notes:
DPN003954 REV : 3
Page :2/3 REV DATE : 5/17
LIEBERT MC CONDENSER
AIR COOLED PIPING SCHEMATIC
CONDENSER BELOW INDOOR UNIT
Indoor Unit
Gas
15'
4.6m Liquid
Maximum
Vertical Drop
Gas
Field piping
Notes:
Gas 1. Pitch horizontal hot gas piping at a minimum of
1/2" per 10 feet (42mm per 10m) so that gravity will
aid in moving oil in the direction of the refrigeration flow.
Liquid 2. This Configuration is not valid for Liebert MC with Lee-Temp
or unheated receiver.
3. Single circuit condenser shown.
DPN003954 REV : 3
Page :3/3 REV DATE : 5/17
LIEBERT DS
REAR RETURN FILTER BOX DIMENSIONAL DATA
UPFLOW 35-105kW (10-30 TONS) W/ EC FANS ALL COMPRESSOR MODELS
FILTER FILTER
ACCESS ACCESS
DOOR DOOR
7 7/8"
201mm
40"
1016mm
38 1/4"
971mm
Duct Size
3 1/2"
89mm D Duct Size
A B C
Notes:
1. Filters can be accessed from either side.
2. 25" (635mm) minimum clearance provided on one side for filter access.
3. Filter boxes are shipped flat and must be field assembled.
105kW, All Models 2-1/4 (57) 100-1/4 (2546) 29-1/2 (749) 97-1/8 (2467) 8
DPN003974 REV : 3
Page :1 /1 REV DATE : 5/18
LIEBERT DRYCOOLER
GENERAL ARRANGEMENT DIAGRAM & DIMENSIONAL DATA
EXPANSION TANK FOR GLYCOL/GLYCOOL™ SYSTEMS
1 Expansion Tank
Shutoff
2 Valve
Shutoff Valve 2
Pressure 2
Shutoff Relief Valve - Piped
2 Valve to To Drain
3
Drain
Tank
Notes:
30 1/2"
775mm
O 9"
229mm
1/2" NPT FEMALE
FITTING
2 3/4" 7"
70mm 178mm
DPN004183 REV : 0
Page :1 /1 REV DATE : 5/17
LIEBERT DS, DSE, CW, PDX & PCW
UNIT TO UNIT NETWORK CONNECTIONS
RS485
SITE AND BMS
COMMUNICATION
ETHERNET CONNECTIONS
+ -
1 2 P
2 TB3
A DETAIL A
P71 P72 E5
ETHERNET CABLE
2 TB3 P74 P64 (FIELD SUPPLIED)
P67
(FIELD SUPPLIED)
P76 iCOM
P12
P11
MICROPROCESSOR
AND I/O BOARD
P75 TO / FROM OTHER
P21
P20
NETWORKED UNITS
P95
P7 P13
P100
DPN004351 REV : 2
Page :1 /2 REV DATE : 6/18
LIEBERT DS, DSE, CW, PDX & PCW
UNIT TO UNIT NETWORK CONNECTIONS
ETHERNET CABLE
(FIELD SUPPLIED)
P67
P66
P66
P76 iCOM P76 iCOM
P12
P11
P12
P11
MICROPROCESSOR MICROPROCESSOR
AND I/O BOARD AND I/O BOARD
P75 P75
P21
P20
P21
P20
P95 P95
P7 P13
P7 P13
P100 P100
DPN004351 REV : 2
Page :2 /2 REV DATE : 6/18
LIEBERT DS
ELECTRICAL FIELD CONNECTION DESCRIPTION
UPFLOW AND DOWNFLOW MODELS
STANDARD ELECTRICAL CONNECTIONS
1) Primary high voltage entrance - 2.50” (64mm); 1.75” (44mm); 1.375” (35mm) diameter concentric knockouts located in bottom of box
2) Secondary high voltage entrance - 2.50” (64mm); 1.75” (44mm); 1.375” (35mm) diameter concentric knockouts located in top of box
3) Primary low voltage entrance - Quantity (3) 1.375” (35mm) diameter knockouts located in bottom of unit
4) Secondary low voltage entrance - Quantity (3) 1. 375” (35mm) diameter knockouts located in top of box
5) Three phase electrical service - Terminals are on main fuse block (disregard if unit has optional disconnect switch). Three phase service
not by Liebert.
6) Earth ground - Terminal for field supplied earth grounding wire. Earth grounding required for Liebert units.
7) Remote unit shutdown - Replace existing jumper between terminals 37 & 38 with field supplied normally closed switch having a
minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring.
8) Customer alarm inputs - Terminals for field supplied, normally open contacts, having a minimum 75VA, 24VAC rating, between
terminals 24 & 50, 51, 55, 56. Use field supplied Class 1 wiring. Terminal availability varies by unit options.
9) Common alarm - On any alarm, normally open dry contact is closed across terminals 75 & 76 for remote indication. 1 AMP, 24VAC max
load. Use Class 1 field supplied wiring.
10) Heat rejection interlock - On any call for compressor operation, normally open dry contact is closed across terminals 70 & 71(circuit 1),
230 (circuit 2) to heat rejection equipment. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. When DS unit is paired with a
Liebert MC series condenser, remove jumper between terminal 71 and terminal 230. Three wires must connect terminals 70, 71 and 230
of the indoor unit to terminals 70, 71 and 230 of the Liebert MC series condenser.
11) Unit factory installed disconnect switch, Fuse Block and Main Fuses – “Locking Type” consists of a non-automatic molded case
switch operational from the outside of the unit. Access to the high voltage electric panel compartment can be obtained only with the
switch in the “off” position. Units with fused disconnects are provided with a defeater button that allows access to the electrical panel
when power is on. The molded case switch disconnect models contain separate main fuses.
DPN004352 REV : 1
Page :1 /3 REV DATE : 6/18
LIEBERT DS
ELECTRICAL FIELD CONNECTION DESCRIPTION
UPFLOW AND DOWNFLOW MODELS
OPTIONAL ELECTRICAL CONNECTIONS
16) Smoke sensor alarm - Factory wired dry contacts from smoke sensor are 91-common, 92-NO, and 93-NC. Supervised contacts, 80 &
81, open on sensor trouble indication. This smoke sensor is not intended to function as, or replace, any room smoke detection system that
may be required by local or national codes. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
17) Reheat and humidifier lockout - Remote 24VAC required at terminals 82 & 83 for lockout of reheat and humidifier.
18) Condensate alarm (with condensate pump option) - On pump high water indication, normally open dry contact is closed across terminals
88 & 89 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
19) Remote humidifier - On any call for humidification, normally open dry contact is closed across terminals 11 & 12 to signal field supplied
remote humidifier. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
20) Auxiliary cool contact - On any call for econ-o-coil operation, normally open dry contact is closed across terminals 72 & 73 on dual cool
units only. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
21) Analog Inputs- Terminals 41, 42, 43, 44 are user configurable for 0-10V, 0-5V, or 4-20MA.
DPN004352 REV : 1
Page :2 /3 REV DATE : 6/18
LIEBERT DS
ELECTRICAL FIELD CONNECTION DESCRIPTION
2
UPFLOW AND DOWNFLOW MODELS 4
A B
C D
OVERCURRENT PROTECTION DEVICES
5 F
TB3
27
P74
60 Hz P64 26
P67
6
CONTACTORS
5 3
1
DOWNFLOW
Note: Typical orientation of components shown. Component location varies by option and unit size.
LOW VOLT SECTION
17 18 9 23 16 19
82 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 CAUTION:
Risk of broken or shorted low volt
UPFLOW 3 wiring. Field installed low volt wiring
must be routed with loop as shown
A B to allow electric box to swing.
25 24 22 7 8 10 20
58 59 84 85 37C38C37B38B 37 38 24 50 51 55 56 70 71 230 72 73 A B
C D
C 21 D
F
41 42 43 44 12
F
SH
49-1
49-3
13
E
Item 12 Installation Conditions
1. Follow all local installation codes.
E
POINT OF HINGED LOW
2. Do not run CAN cables in same conduit, raceway, or
Form No.: DPN001040_REV4
85
This page intentionally left blank
1.0 GENERAL
1.1 SUMMARY
These specifications describe requirements for a Thermal Management system. The system shall be designed
to control temperature and humidity conditions in rooms containing electronic equipment, with good
insulation and vapor barrier. The manufacturer shall design and furnish all equipment to be fully compatible
with heat-dissipation requirements of the room.
1.3 SUBMITTALS
Submittals shall be provided with the proposal and shall include: Single-Line Diagrams; Dimensional,
Electrical, and Capacity Data; Piping and Electrical Connection Drawings.
1.4 SERVICEABILITY/ACCESS
The cabinet shall be designed so that all components are easily accessible for service and maintenance through
the front of the unit.
2.0 PRODUCT
2.1 FRAME
The frame shall be welded, formed sheet metal. It shall be protected against corrosion using the autophoretic
coating process. The frame shall be capable of being separated into three parts in the field to accommodate
rigging through small spaces.
3.0 CONTROLS
3.1 LIEBERT ICOM™
MICROPROCESSOR CONTROL WITH 7-IN. COLOR TOUCHSCREEN
The Liebert iCOM shall be microprocessor-based with a 7-inch, high definition, capacitive, color touchscreen
display and shall be mounted in an ergonomic, aesthetically pleasing housing. The display and housing shall
be viewable while the front panel is open or closed. The controls shall be menu-driven. The system shall
display user menus for active alarms, event log, graphic data, unit view/status overview (including the
monitoring of room conditions, operational status in percentage of each function, date and time), total run
hours, various sensors, display setup and service contacts. A password shall be required to make system
changes. Service menus shall include setpoints, standby settings (lead/lag), timers/sleep mode, alarm setup,
sensor calibration, maintenance/wellness settings, options setup, system/network setup, auxiliary boards and
diagnostics/service mode. The Liebert iCOM control shall provide Ethernet/RS-485 ports dedicated for BMS
connectivity (i.e. Base-Comms).
• Password Protection - The Liebert iCOM shall contain two unique passwords to protect against
unauthorized changes. An auto hide/show feature shall allow the user to see applicable information
based on the login used.
• Unit Backup/Restore - The Backup function saves a copy of the settings in a file based on the system
name assigned during startup. The backup can be used to restore only the unit where it was created and
serve as a recovery if a display fails. The backup file includes network settings, the unit name, panel
configuration and other details specific to the Liebert iCOM display. The Restore function copies the
backup settings file to a Liebert iCOM/display so that it functions exactly as it did before the unwanted
change or as it did on the Liebert iCOM that was replaced.
• Unit Export/Import - The Export function makes a copy of the settings from the Liebert iCOM display
that may be stored on a local disk or USB drive. The settings may be imported to a second Liebert
iCOM, resulting in two systems with identical display properties. The Liebert iCOM will automatically
recognize USB drives and display them in the relevant screens. Multiple backup files may be put on the
same USB drive as long as each system name is unique. The Import function allows previously
exported settings files to be loaded to a second Liebert iCOM. This allows display settings, including
panel configurations and custom labels, to be copied from one display to another.
• Parameter Download - The Liebert iCOM shall enable the user to download a report that lists parameter
names, factory default settings and user programmed settings in .csv format for remote reference.
• Parameter Search - The Liebert iCOM shall have search fields for efficient navigation and parameter
lookup.
3.2 ALARMS
All unit alarms shall be annunciated through both audio and visual cues, clearly displayed on the screen,
automatically recorded in the event log and communicated to the customers Building Management
System/Building Automation System. The Liebert iCOM control shall activate an audible and visual alarm in
event of any of the following conditions:
• High Temperature
• Low Temperature
• High Humidity
• Low Humidity
• EC Fan Fault
• Change Filters
• Loss of Air Flow
• Loss of Power
• Compressor Overload (Optional)
• Humidifier Problem
• High Head Pressure
• Low Suction Pressure
• Custom Alarms
Custom alarm inputs shall be provided to indicate facility-specific events. Custom alarms can be identified
with programmable labels. Frequently used alarm inputs include:
• Leak Under Floor
• Smoke Detected
• Standby Unit On
Each alarm (unit and custom) shall be separately enabled or disabled, selected to activate the common alarm
and programmed for a time delay of 0 to 255 seconds.
5.1.7 Cabinet
The condenser cabinet shall be constructed of bright aluminum sheet and divided into individual fan sections
by full-width baffles. Internal structural support members, including coil support frame, shall be galvanized
steel for strength and corrosion resistance. Panel doors shall be provided on two sides of each coil/fan section
to permit coil cleaning. An electrical panel shall be contained inside a factory-mounted NEMA 3R
weatherproof electrical enclosure. Units with the 575V option shall include a second, factory-mounted,
NEMA 3R weatherproof electrical enclosure opposite the main electrical enclosure.
5.2.9.1 FAN CYCLING CONTROL (DSO, DDO) DRYCOOLER (ALL FAN QUANTITIES)
WITH INTEGRAL PUMP CONTROL
The DSO/DDO drycooler shall sense the leaving glycol temperature and cycle fixed-speed fans to maintain
glycol temperatures. Aquastats shall have field-adjustable setpoints. The fixed-speed motors shall be 3-phase
and have individual, internal overload protection. Fixed-speed motors shall have a TEAO enclosure. The
DSO/DDO drycooler shall control operation of glycol pumps powered from the electrical panel. The air-
cooled drycooler shall have a ____ volt, 3 ph, ____ Hz power supply.
6.0 EXECUTION
6.1 INSTALLATION OF THERMAL MANAGEMENT UNITS
6.1.1 General
Install Thermal Management units in accordance with manufacturer’s installation instructions. Install units
plumb and level, firmly anchored in locations indicated and maintain manufacturer’s recommended
clearances.