PRODUCT LAUNCH

LIEBERT® CRV –
NEW MODELS
20th December 2018
Michal Podmaka
Fabio Franchin

1
AGENDA

1. Key Drivers

2. News in Liebert CRV Family

3. Technical Details

4. Price Positioning

5. Ordering Information

6. Summary

*Additional Notes 2
KEY DRIVERS

Improved Total Cost of


Ownership Shorter Lead Times
Improved price positioning
Lower Operating Costs

One Vertiv Higher Cooling Capacity


Globalzation of the design From the same footprint

*Additional Notes 3
NEWS IN
LIEBERT CRV FAMILY
LIEBERT CRV – ROW BASED COOLING
▪ DX and CW Version
▪ 300 and 600 mm wide frame
▪ Wide Range: 4 basic capacities in DX and 5 in CW version
▪ High Efficiency:
▪ EC Fans
▪ Inverter driven scroll compressor on the 300mm frame
▪ Digital Scroll on the 600 mm frame
▪ High Density Applications: up to 10kW/Rack in open architecture
▪ Rich features: Humidifier, Re-heat, ATS, and more…
Direct Expansion (DX) Chilled Water (CW)
New New New New
2019 2019 2019 2019
CR012RA CR025RA CR020RA/W CR035RA/W CR030RC CR052RC CR060RC CR040RC CR050RC
kW 13,6 21,8 23.4 36.4 39,2 54 57.0 46.6 58.0
Humidity
No Yes Yes Yes Yes No Yes Yes No
Control
Width 300 mm Frame 600 mm Frame 300 mm Frame 600 mm Frame
Rating Conditions: DX – 38 °C, 22% RH, 35 °C Outdoor temperature; CW – 38 °C, 22% RH, 7/12 °C CW Temperature

*Additional Notes 5
NEW MODELS
Phasing Out New Models
Direct Expansion

CR011 CR012

CR021 CR025

Chilled Water

CR032/38 CR030

CR052

*Additional Notes 6
TECHNICAL DETAILS
PERFORMANCE OVERVIEW - DX

CR011 CR012 APC


Max NS Cooling Capacity (kW) 10,3 11,4 10
Airflow (m3/h) 2700 3200
Efficiency* 2,71 3,32 2,9
Noise* 2m f.f. (dBA) 69,3 72 82,2

CR021 CR025 APC


Max NS Cooling Capacity (kW) 18,8 19,2
Airflow (m3/h) 4050 4000
n/a
Efficiency* 2,93 3,1
Noise* 2m f.f. (dBA) 71 77
@29,4C; 32%RH; 35C outdoor
* Values at the same capacity as APC

*Additional Notes 8
PERFORMANCE OVERVIEW - CW

CR032/38 CR030 APC


Max NS Cooling Capacity (kW) 32 / 35 34,5 28,2
Max Airflow (m3/h) 4950 / 5650 6000 5436
Efficiency* 29 / 28 38,6 31,3
Noise* 2m f.f. (dBA) 76 / 72 85 77

CR052 APC
Max NS Cooling Capacity (kW) 44,7 43,1
Max Airflow (m3/h) 6788 7135
Efficiency* 19 23
Noise* 2m f.f. (dBA) 75 81

Conditions: 37,8C DB, 23,4%RH, CW 10/15,5C, Filter G2; CR030 data with G4 filter
* Values at the same capacity as APC

*Additional Notes 9
AIRFLOW & FANS
CR012; CR025; CR030 CR052

• Axial fans with EC motors • Centrifugal fans with EC


• 48VDC power supply motors
• Impeller from composite • Impeller from composite
material material
• 4 fans in DX models • 230VAC power supply
• 6 fans in CW models • 5 fans

Customer Benefits Customer Benefits


• Variable airflow to meet server
requirements • Variable airflow to meet server
• High Efficiency, low energy requirements
consumption • High Efficiency, low energy
• Low noise consumption
• Hot swappable on CR030 • Low noise

*Additional Notes 10
COMPRESSORS AND EXPANSION VALVE

CR012 CR025

• Mitsubishi DC Inverter • Copeland DC Inverter


Rotary Compressor Scroll Compressor
• Electronic Expansion valve • Electronic Expansion valve
(EEV) (EEV)

Customer Benefits Customer Benefits


• Cooling Capacity quickly adopts APC • Cooling Capacity quickly adopts
to changing heat loads does not offer to changing heat loads
• High efficiency on full and partial • High efficiency on full and partial
load
inverter in this load
• Low Inrush Current model • Low Inrush Current
• Quiet Operation • Quiet Operation

*Additional Notes 11
COMPRESSORS
DC Inverter Compressor

ModBus Power

PACC Controller board Inverter Drive Variable Speed


Control the unit based on Changes the Compressor
setpoints and readings compressor speed • Quiet Operation
from sensors through frequency • High reliability
modulation • No noise and small
vibration
*Additional Notes 12
CW VALVE AND CONNECTIONS

CR030 CR052

• 3-way valve field • 3-way valve or 2 way valve


adjustable to 2 way (configurable from factory)
• 0-10V actuator for precise • 0-10V actuator for precise
water flow regulation water flow regulation
• Top or Bottom • Top, Bottom or
Connections Simultaneous Top / Bottom
connections

Customer Benefits Customer Benefits


• Servomotor automatically adjusts waterflow
to match the changing cooling demand of IT • Servomotor automatically adjusts waterflow
equipment to match the changing cooling demand of IT
• Installation flexibility – Top or bottom piping equipment
• On-site valve reconfiguration for constant • Installation flexibility – Top or bottom piping
flow or variable flow systems

*Additional Notes 13
HUMIDIFICATION AND RE-HEATING
Electrode Humidifier Electric Heater
• Stable temperature even during
• Automatic humidification
dehumidification
and dehumidification
• PTC ceramic type electrical heater.
• Electrode steam
• Automatic over-temperature
generating humidifier
protection - surface is configured
• Humidifier control board –
with a temperature switch to cut off
controls humidifier and
when the heater surface
feedbacks alarms to unit
temperature exceed 120 ℃
controller

APC
CR012 CR025 CR030 CR052 CR060 (300mm
models)
Humidifier - Yes Yes - Yes -
Heater Yes Yes Yes - Yes -

*Additional Notes 14
ICOM CONTROLLER AND DISPLAY

CR012; 25; 30 CR052


• Vertiv ICOM controller
• Vertiv ICOM controller based based on ICOM Medium
on PACC board hardware board hardware
• New Software • Same software as current
• New local graphical display models
• Multiple display options

Standard Large No Display HCS12


Display Coldfire Display
Local Network Local

*Additional Notes 15
SENSORS

CR012; 25; 30 CR052


• Each unit is as standard equipped
• Each unit is as standard equipped from
from the factory with:
the factory with: o 1 x Return Air temperature and
o 1 x Return Air temperature and humidity humidity sensor
sensor o 1 x Supply Temperature Sensor
o 1 x Supply Temperature Sensor o 1 x Rack temperature sensor
o 1 x Rack temperature sensor Rack Sensor o Leak detection sensor available as
Rack Sensor o 1 x Leak detection sensor an accessory

• Max number of Rack • Max number of Rack


temperature sensors temperature sensors
connected to 1 unit connected to 1 unit
DX units CW units
CW units
10 6
10

*Additional Notes 16
SIX CONTROL MODES

⚫ Six control modes to independently match the server heat load and airflow as
server operations change

Cooling Capacity
(via Digital Scroll Compressor or CW Valve)
Sensors Supply Air Remote Rack Return Air
Airflow Supply Air
(via
Variable Speed Remote Rack
EC Plug Fans)
Return Air

= Available
TEAMWORKING

CR012, 25, 30 CR052


• Teamworking up to 16 units (APC up to 12 units) • Teamworking up to 32 units
• Can bus connection for unit to unit • Ethernet connection for unit to unit
communication communication

Duty - Duty - Avoid


Rotation Rotation Cascade
STDBY STDBY Fighting
Vertiv Yes Yes Vertiv Yes Yes Yes Yes
APC Yes Yes APC Yes Yes - -
• Cascade and Avoid fighting available via RDU501 –
see next slide

Ethernet
Can bus

*Additional Notes 18
BACKWARDS COMPATIBILITY

RDU501 (from May 2019) SNMP / Modbus / Bacnet


• Teamworking of up to 16 units with BMS
different controller boards
• Duty/Stdby, Rotation, Cascading, Master
Avoid fighting Fail Safe Design
• Teamwork mode 1, 2, 3 • If master fails, slave units
• On site configuration continue to run on local
RDU501
sensors

Modbus 485 Ethernet

Slave Slave Slave Slave

PACC board PACC board Medium board Medium board


19
BMS MONITORING

CR012, 25, 30 CR052


• Via Vertiv RDU-SIC Monitoring Card • Via Vertiv IS-Unity Monitoring Card
• Protocols provided: • Protocols provided:
SNMP MODBUS Bacnet SNMP MODBUS Bacnet
Vertiv Yes Yes * Vertiv Yes Yes Yes

APC Yes Yes - APC Yes Yes -

* Bacnet Protocol will be available with a new Vertiv


RDU101 card from June 2019
RUN LAN
Front panel indicator indicator 1-Wire port COM port Front panel

SIC card inserter RJ45 port USB port

*Additional Notes 20
OPERATING LIMITS - TEMPERATURES

Temperature limits Low Ambient Kit


• Enables safe unit start even in low ambient
Indoor: conditions
• Consists of: Liquid receiver with heater, Low-tex
• From 18°C to 40°C valve, Non Return valve
• Solenoid valve shipped with the unit must be
Outdoor: installed close to CRV
• High limit: +48 °C
• Low limit:
• -15°C
• -20°C with Low Ambient Kit
• -34°C with Low Ambient Kit + Variex
installed indoor (SFA needed)

*Additional Notes 21
OPERATING LIMITS – PIPING LENGTH (DX
MODELS)
Piping Equivalent Lengths
Piping Extension Kit
Installation Equivalent Length
• For piping lengths > 30m
Standard Up to 30m • It’s a solenoid valve to be installed on
With Piping Extension kit Up to 61m liquid line field piping close to the indoor
unit
Note: APC provides max 61 m equivalent
• This valve is shipped with every unit = no
Vertical Position extra cost.

Relative position Value


Outdoor unit higher than
Max.: +30m
indoor unit
Outdoor unit lower than
Max.: -8m
indoor unit

Note: APC does not allow installation where


condenser is located below the indoor unit!!

*Additional Notes 22
DIMENSIONS

⚫ Standard unit dimensions are:


– Depth 1100mm
– Height 2000mm

⚫ Other widths and depths are managed via adapters


• Front adapter (D = 1200mm, H = 2000mm)
• Top adapter (D = 1100mm, H = 2200mm)
• Top and Front adapter (D = 1200mm, H = 2200mm)

Extensions available as ship loose accessories to


be installed on site

*Additional Notes 23
PRICE POSITIONING
PRICE POSITIONING
DX Models CW Models Vertiv Phase out
model
Price

Vertiv New /
Price competitive Existing model
CR021
alternative of the
APC / Schneider
More capacity at popular CR060 equivalent unit
price matching model
CR025 APC
CR011 CR060

CR038
Possibility to get CR032
APC specified!
CR012 APC not offering APC CR052
20kW model.
Extra value -
APC not offering APC CR030
inverter

10kW 20kW 30kW 50 kW Cooling Capacity


*Additional Notes 25
ORDERING
INFORMATION
ORDERING INFORMATION

Part Numbers
• CR012/25/30 – Pre-configured fixed codes
• CR052 – Configurable item

Ordering policy / Lead Times


• CR012/25/30
o Units will be available on Stock in EMEA including
condensers.
o Regular replenishment of stock from China factory.
o Short Lead time

• CR052
o Produced in EMEA factory based on Customer order. Units
o Standard lead time.
available
on stock!

*Additional Notes 27
NEW LIEBERT CRV300 IN CONFIGURE ONE
READY in C1 ON
21 Dec 2018

New CW and DX models can be easily selected


within Liebert CRV300 Product:
CR030 in CW Version
CR012 and CR025 in DX Version

Once models are selected,


the configurator will
automatically display the full
configurations (just
TOP/BOTTOM connections to
be selected by the user)
THERE ARE NO
POSSIBILITY TO
CHANGE THIS FIXED
CONFIGURATION!

ACCESSORIES compatible with CW or DX


versions will be displayed
ATTENTION to the qty of Sensors and of the
related Cables!

28
NEW LIEBERT CRV300 IN CONFIGURE ONE
READY in C1 ON
21 Dec 2018

LOOK AT the NEW BOM!


New CW and DX models are fixed, closed codes:
the BOM does not display the configuration string
and the BOM item by item, but 1 single code!

Customers can
see the unit’s
features in the
quote!

See how the offer


looks like!

29
NEW LIEBERT CRV300 IN CONFIGURE ONE
READY in C1 ON
21 Dec 2018

Together with the new 30kw units, also the new


CR052 can be configured among the CW models

UNIT CONFIGURATION

Together with Large ICOM and Condfire


display & ICOM controller, the New feature
is HCS12 local, graphical display

30
OPTIONS AND CONFIGURATIONS
Options CR012 CR025 CR030 CR052
Humidifier - Standard from Factory Standard from Factory -
Heater Standard from Factory Standard from Factory Standard from Factory -
Condensate pump Standard from Factory Standard from Factory Standard from Factory Optional from Factory
Air filter + clog switch Standard from Factory Standard from Factory Standard from Factory Optional from Factory

Monitor card Standard from Factory Standard from Factory Standard from Factory Optional from Factory

Display Standard from Factory Standard from Factory Standard from Factory Optional from Factory
Dual power supply - - Standard from Factory Optional from Factory
Air discharge baffle Standard from Factory Standard from Factory Standard from Factory Optional from Factory
Cooling Capacity Meter - - Standard from Factory Optional from Factory
1 pcs Standard from 1 pcs Standard from 1 pcs Standard from
1 pcs Standard from Factory,
Remote T sensor Factory, additional 9pcs Factory, additional 9pcs Factory, additional 5pcs
additional 9pcs as accessory
as accessory as accessory as accessory
Water leakage sensor Standard from Factory Standard from Factory Standard from Factory Field installed Accessory
Pipe extension kit Standard from Factory Standard from Factory - -
200mm frame Field installed Accessory Field installed Accessory Field installed Accessory Optional from Factory

Low Ambient kit Field installed Accessory Field installed Accessory - -

*Additional Notes 31
PHASE IN PHASE OUT INFO

Phase Out Phase In


CR011/21/32/38 CR012/25/30/52

• First Quotation: 21-DEC-2018


• Last Quotation: 31-JAN-2019
• First Order: 01-JAN-2019
• Last Order: 15-MAR-2019
• First Shipment: Mid March
• Last Shipment: Lead Time

*Additional Notes 32
AVAILABLE TOOLS AND MATERIALS

Hirating

User
Brochure Manual

Configure
One

*Additional Notes 33
SUMMARY
• Higher capacities
• Higher efficiency
• Shorter Lead times
• Better positioning and customer benefits
• Higher installation flexibility than APC
• Backwards compatibility with existing units
through RDU501

*Additional Notes 34