You are on page 1of 4

Driving and Connecting Globally

TECO all new series of air-cooled modular chiller,


 Option combine different type of series ( PUCT-D 335/450 ML).

 Capacity range from 335Kw~2250Kw

 Operations on the mini-max system for energy saving and efficiency

 Smart, efficiency, work individually.

 Newly design of fan and fin system, better function and more efficiency.

Model nomenclature
PUCT-D335ML

 PU------------------------Air cooled chiller

 C------------------------------------R410a

 T----------------------Module type chiller

 D-----------------------------Factory code

 335------------------------cooling capacity

 M----------------3Ph-50Hz-380/400/415V

 L-------------------------scroll compressor
Mode
PUCT-D335ML PUCT-D450ML
Iteml

Cooling Capacity (kcal/h) 288100 387000

Cooling Capacity (kW) 335 450

Power Supply (Φ-V-Hz) 3Φ-380V-50Hz

Input Power (kW) 104.7 139.6

Cooling Running Current (A) 185.3 247.9

Starting Current (A) 543 605

Type Hermetic scroll

Quantity 3 4
Compressor
Starting Metthod IR

Oil Recharged (L) 6.7*3 6.7*4

Type x Quantity Axial x6 Axial x8

Fan Power(kW) 1.2*6 1.2*8

Air flow (m3/h) 20000*6 20000*8

Condenser Aluminium Fin-tube

Type Shell - and - tube

Water flow(m3/h) 57.6 77.4


Evaporator
Head Loss (kPa) 60 65

Pipe Size DN125 DN125

Type R410A
Refrigerant
Recharged (kg) 16*3 16*4

Height(mm) 2200 2200

Dimension Width(mm) 3750 4720

Depth(mm) 2300 2300

Net Weight (kg) 2700 3560

Operating Weight (kg) 2808 3700

Note:
1. Cooling capacity is based on the condition of chilled water inlet temperature at 12℃ and outlet temperature at 7℃,
and ambient air dry bulb temperature at 35℃ ;
2.Specifications are subject to change without prior notification.
PUCT-D335ML

PUCT-D450ML

You might also like