You are on page 1of 1

Table of Flue Gas Absorption Chiller Technical Parameters

Model YX423.5-265(14/8)(32/37)H2
USRt 752
Cooling capacity kW 2645
10 kcal/h
4
227.5
Inlet/outlet temperature ℃ 14/8
Flux m /h
3
379.2
Chilled water
Pressure loss mH2O 5.8
Connection diameter (DN) mm 250
Inlet/outlet temperature ℃ 32/37
Flux m3/h 769
Cooling water
Pressure loss mH2O 12
Connection diameter (DN) mm 300
Inlet temperature ℃ 423.5
Flux kg/h 24073.5
Flue gas Pressure loss mmH2O 180
Inlet connection diameter (DN) mm 600
Outlet connection diameter (DN) mm 600
Power supply 3ф-400V-50Hz
Electrical data Total current A 26.9
Electric power kW 7.9
Length 5800
Overall
Width mm 4100
dimensions
Height 3800
Operating weight 37.5
t
Shipping weight 28

Note:
(1) Values for chilled water and cooling water in the above table are for nominal operation conditions, and
can be properly adjusted in actual operation.
(2) The lowest outlet temperature for chilled water is 5℃.
(3) Cooling capacity can be adjusted in a range of 20 ~100%. Chilled water flow can be adjusted in the
range of 60 ~120%.
(4) On the chilled and cooling water side scale factor will be 0.0001m2h℃/kcal.
(5) Chilled and cooling water box has the maximum pressure bearing capacity of 0.8MPa (G).
(6) The material of tubes in Absorber and Condenser is S31603 (316L), but the material of tube-sheet and
water box is still carbon steel.

SHUANGLIANG ECO-ENERGY SYSTEMS CO., LTD

2020.12.18

Editor: Checker: Assessor: