VRF MV6R

MV6R-XMi 252T÷1500T
NEW
OUTDOOR UNITS

HR AIR R-410A

Heat recovery outdoor units


High efficiency
HEAT RECOVERY TECHNOLOGY

MV6R heat recovery outdoor units can perform both cooling and heating operation simultaneously and independently within the same
system, ensuring the maximum operating flexibility for the users. Heat recovery is achieved by diverting exhaust heat from indoor
units in cooling mode to areas requiring heating, minimizing the heat exchange with outside environment. As a result, power input
and electricity costs are minimized, ensuring the best energy efficiency. In addition, inverter technology allows to adapt precisely to
variable capacity loads.

EER7.8
8.0

7.0
EER

6.0

5.0

100% cooling 75% cooling 50% cooling 25% cooling 100% heating
25% heating 50% heating 75% heating
EER in simultaneous cooling and heating mode are based on the following condition:
Outdoor temperature 7°C DB/6°C WB, indoor temperature 27°C DB/19°C WB for cooling, indoor temperature 20°C DB for heating.
EVI (ENHANCED VAPOR INJECTION) COMPRESSOR

Thanks to the vapor injection DC inverter compressor, the MV6R series can run heating mode stably down to -25°C, furthermore
strongly increasing the heating capacity especially at low ambient temperature. Compressor is designed to run at 7% modulation
minimum, highly improving system efficiency at part load operation.

P m+ Δm Refrigerant circulation increased

Δm

Outdoor evaporation
Vapor injection DC capacity increased h

OUTDOOR UNITS
inverter compressor

EMS (ENERGY MANAGEMENT SYSTEM)

Floating refrigerant temperature for balancing comfort and Capacity output limitation for shortage of electricity
efficiency
With the integration of EMS, for projects with limited electricity supply,
The evaporating temperature (in cooling) and condensing MV6R can be set to output 40-100% capacity.
temperature (in heating) are automatically adjusted according
to both indoor and outdoor temperature to maximize the
comfort and energy efficiency, increasing the seasonal
efficiency by 30%.

Fixed Tc
Optimized
Fixed Te 100%
90%
Max.thermalcapacity

80%
70%
60%
VariableTc/Te
50%
Fixed Tc/Te 40%

Selectable steps

MR. DOCTOR

Force cooling /heating commissioning: force cooling or force heating operation can check the system comprehensively
and quickly.

Self-diagnosys: all new diagnosis software to monitor all operating parameters and detailed information.

Automatic data backup: automatic data backup of last 30 minute’s operation record.

Auxiliary PCB for quick access: placed on side column of the unit, it provides easy access to LED display and main
settings without removing the front panel.

INDEPENDENT CONTROL OF HEAT EXCHANGERS AND COMPRESSORS

Both in cooling and heating mode, the outdoor heat exchanger and
compressor are independently controlled to improve performances. Operation MV6Rsystem
So, in a multiple-unit system, when the compressor of an outdoor unit compressor

does not operate due to a lower thermal load, its heat exchanger is Standby
compressor
kept active to maximize heat exchange surface and efficiency.

Standardsystem
PHE (PLATE HEAT EXCHANGER) SUBCOOLING

Plate Heat Exchanger as a secondary intercooler boosts up refrigerant


subcooling and improves 10% energy efficiency.
1 2

HIGH EER AND COP VALUES

4,5 5,5
OUTDOOR UNITS

3,6 4,4

2,7 3,3

1,8 2,2

0,9 1,1
4,3 3,9 3,9 3,1 4,1 3,8 3,6 8 5,7 5,1 4,1 5,1 4,8 4,6 4,2
EER COP
22 kW 28 kW 34 kW 40 kW 45 kW 50 kW 22kW 28kW 34kW 40kW 45kW 50kW

Wide Application range


WIDE CAPACITY RANGE

VRF MV6R series capacity is up to 18HP with a single unit and up to a maximum of 54HP for a single system with a combination of 3
modules, covering all possible applications and building dimensions.

8/10/12 HP 14/16/18 HP
(with single fan) (with dual fan) 20-36HP 38-54HP

LONG PIPING CAPABILITY

Piping length Capability


Total piping length 1000 m
Longest length between outdoor and indoor units - actual (equivalent) 175 m (200 m)
Longest length after first branch 90 m*
175m⁽¹⁾

Longest length between MS box and IDU 40 m


110m⁽²⁾

Largest height difference between outdoor and indoor units - ODU above (below) 110 m (110 m)
90m

Largest height difference between indoor units 30 m


30m⁽³⁾

*Thelongestlengthafterfirstbranchis40masstandardbutcanbeextendedtoupto90mundercertainconditions.Pleaserefertotechnicalmanualforfurtherinformation.

(1) Longest length between outdoor and indoor units


(2) Level difference between indoor units and outdoor units
(3) Level difference between indoor units

WIDE OPERATION RANGE


-15°C 52°C
VRF MV6R can operate in a wide ambient temperature range.
COOLING
It can operate stably from -15°C up to 52°C in cooling mode and from -25°C to 19°C in
-15°C 27°C
heating mode. MAIN COOLING
Simultaneous heating and cooling operation is guaranteed from -15°C to 27°C in main -15°C 19°C
cooling and from -15°C to 19°C in main heating.*
MAIN HEATING
-25°C 19°C
HEATING
*Cooling mode down to -15°C available in combination with single MS box MS01.
Wet-bulb temperatures in cooling mode, dry-bulb in heating mode.
High Reliability
DUTY CYCLING

Duty cycling equalizes the running time of the outdoor units in a multiple-unit system and of the compressors in each unit, significantly
extending compressor lifespan.

1 2 3 3 1 2 2 3 1

1st cycle 2ndcycle 3rdcycle

PRECISE OIL CONTROL TECHNOLOGY

OUTDOOR UNITS
Three stages of oil control technology ensure all outdoor compressor oil is
always kept at a safe level, eliminating any compressor oil shortage problems.
(1) Compressor internal oil separation.
(2) High-efficiency centrifugal oil separator (with separation efficiency of up to
99%) ensures that oil is separated from the discharge gas and returned to Compressorinternaloilseparation High-efficiencycentrifugaloilseparator
the compressors in a timely fashion.
(3) Auto oil return program monitors the running time and system status to
ensure reliable oil return.
Autooilreturnprogram

BACKUP OPERATION

In a multiple-unit system, if one module fails, the other modules provide


backup so that the system can continue operating, maintaining up to 4 days
Failed compressor interim capacity and allowing time for maintenance or repair while comfort
remains guaranteed.
Operation compressor

Standby compressor

Compressor backup

ANTI-CORROSION PROTECTION

Outdoor units are given anti-corrosion treatment for non-extreme conditions as standard and can also be customized with heavy
anticorrosion treatment on main components for surface protection against corrosive air, acid rain and saline air (for installations in
coastal regions) to extend overall useful life. The integrity of the anti-corrosion treatment is ensured by subjecting major components
and parts to salt mist testing, moisture and heating testing and light aging testing.

Please contact your local dealer for further information about customization price and availability.

• Fan motor
• Painted sheet metal
• Screws / Bolts / Gaskets
• Heat exchanger aluminum foil
• Heat exchanger copper pipe
• Electric Control Box Case

REFRIGERANT COOLING PCB

The MV6R series uses refrigerant cooling technology to cool the electric control box. It
decreases the average temperature of electrical control components by about 8 degrees,
guaranteeing the stable and safe running of the control system.
AUTO SNOW-BLOWING FUNCTION DUST-CLEAN FUNCTION

The innovatively designed auto snow-blowing function enables the The innovatively designed dust-clean function enables the
outdoor unit to prevent the accumulation of snow by itself. outdoor unit to prevent the dust by itself.

Enhanced Comfort
OUTDOOR UNITS

NIGHT SILENT MODE

The night silent mode feature includes various scheduling


options that can be used to reduce noise levels when low Load

noise operation is required: only during night hours or


continuously, and with different noise reductions levels limiting Off
Sound
only maximum fan speed or compressor speed also. level
Judgmenttime(hrs) Low-noiseoperationtime(hrs)

6 10

6:00 12:00 14:00 18:00 20:00 0:00 6:00


Highestoutdoor Start End
temperature

ENHANCED HEATING CAPACITY 110%


100%
Thanks to the vapour injection DC Inverter compressor, heating 90%
80%
capacity can achieve 100% output when the ambient temperature
Heating capacity

70%

is down to -5°C and 90% output when ambient temperature is 60%


50%

down to -15°C. 40%


30%
20%
10%
0%
-20 -15 -10 -5 0 5

Outdoor temperature

CONTINUOUS HEATING DURING DEFROST

As an alternative to the traditional defrost technology performed reverting the refrigerant cycle, in a multiple-units MV6R system it is
possible to keep heating by defrosting alternatively and independently the heat exchangers of different units. Thus, it is possible to
supply continuously heating without stopping for defrost operations.

Defrosting Heating Heating Defrosting


operation operation operation operation

Normalheatingoperation Continuousheatingoperation Continuousheatingoperation

Easy Installation and Service


AUTO ADDRESSING

Outdoor unit can distribute addresses to indoor units automatically.


Remote and wired controllers can be used to query or modify each indoor unit’s address.
AUTOMATIC REFRIGERANT CHARGING AND RECYCLING FUNCTION

Automatic refrigerant charging function make the installation and service easier and more efficient, automatically collecting refrigerant
from the tank and stopping the operation when exact refrigerant charge is done. Automatic refrigerant recycling allows to recover
and accumulate the refrigerant inside the outdoor unit or on indoor units side automatically when required before repairing, strongly
simplifying the technical intervention.

OUTDOOR UNITS
Suitable for any application
MAXIMUM APPLICATION FLEXIBILITY

In addition to simultaneously heating and cooling different spaces via different indoor units belonging to the same system, MV6R
series can manage fresh air processing units (A), beside high temperature hydronic modules to supply hot water up to 80°C (B), or
air handling units through specific kits (C). According to the different combinations of units connected, the system can manage up to
200% of outdoor units’ capacity.*

A B C

*Pleaserefertotechnicalmanualforfurtherinformationabouttotalcapacityindexasfunctionofspecificunitsconnected.

FAN ESP UP TO 80 PA

Fan motor can be set to provide an external static pressure up to


80 Pa, facilitating the installation of the unit in technical rooms or
in areas where the proper airflow cannot be ensured, by installing
ducts and directing the air towards the outside.

80Pa max

REFRIGERANT LEAK DETECTION FUNCTION

Refrigerant leakage detectors can be managed through specific


input/output contacts to automatically stop the system operation
and to display the malfunction on remote controllers or via possible
luminous signal and activating also specific exhaust fans if needed.*
Leakage sensor

Alarm

Fan

Stop
Stop

*FunctionavailableincombinationwithsingleMSboxMS01.Refrigerantleakagedetectorsandpossiblealarmlightsorexhaustfanstobesuppliedby3rdparty
Technical data MV6R-XMi 252T÷1500T

VRF MV6R
Size MV6R-XMi 252T 280T 335T 400T 450T 500T
Capacity HP 8 10 12 14 16 18
Capacity kW 22,4 28,0 33,5 40,0 45,0 50,0
Power input kW 5,25 7,18 8,64 9,83 12,00 13,81
EER - 4,27 3,90 3,88 4,07 3,75 3,62
Cooling (1)
SEER - 7,72 7,56 7,30 6,70 6,67 6,88
ηs,c % 305,8 299,4 289 265 263,8 272,2
Operating temperature range (DB) (5) °C -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52
OUTDOOR UNITS

Capacity kW 22,4 28,0 33,5 40,0 45,0 50,0


Power input kW 3,96 5,46 6,57 8,26 9,78 11,90
COP - 5,66 5,13 5,10 4,84 4,60 4,20
Heating (2) SCOP - 4,18 4,25 4,60 4,35 4,33 4,20
ηs,h % 164,2 167 181 171 170,2 165
Operating temperature range (DB) °C -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27
Operating temperature range DHW (DB) (6) °C -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43
Connectable Total Capacity Index (3) - 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200%
indoor units Max quantity - 64 64 64 64 64 64
Type - DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter
Compressor
Quantity - 1 1 1 1 1 1
Factory charge kg 8 8 8 10 10 10
Refrigerant
CO2 equivalence ton 16,70 16,70 16,70 20,88 20,88 20,88
Liquid pipe mm Ø 12,7 Ø 12,7 Ø 12,7 Ø 15,9 Ø 15,9 Ø 15,9
Pipe
Low pressure gas pipe mm Ø 25,4 Ø 25,4 Ø 25,4 Ø 28,6 Ø 28,6 Ø 28,6
connections
High pressure gas pipe mm Ø 19,1 Ø 19,1 Ø 19,1 Ø 22,2 Ø 22,2 Ø 22,2
Quantity - 1 1 1 2 2 2
Fan motor
Static pressure Pa 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80
Dimensions (Width x Height x Depth) mm 990×1635×790 990×1635×790 990×1635×790 1340×1635×825 1340×1635×825 1340×1635×825
Weight kg 232 232 232 300 300 300
Air flow rate m3/h 9000 9500 10000 14000 14900 15800
Sound pressure level (4) dB(A) 58 58 60 61 64 65
Sound power level (4) dB(A) 78 78 81 81 88 88
Power supply V/Ph/Hz 380-415/3/50+N

EER and COP according EN 14511 regulation, SEER and SCOP according EN14825 regulation (3) Total Capacity Index = indoor unit total capacity/outdoor unit capacity. Please refer to technical manual
(1) Indoor temperature 27°C DB/19°C WB; Outdoor temperature 35°C DB/24°C WB. Interconnecting piping for further information about total capacity index as function of specific units connected.
length is 7,5 m, level difference is zero. (4) Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1,3 m above
(2) Indoor temperature 20°C DB/15°C WB; Outdoor temperature 7°C DB/6°C WB. Interconnecting piping the floor.
length is 7,5 m, level difference is zero. (5) -15 °C to -5 °C operation available in combination with MS box MS01
(6) DHW available in combination with high temperature hydro module HWM-2-XMi 140
VRF MV6R
Size MV6R-XMi 560T 615T 680T 735T 785T 835T 900T 950T 1000T
Capacity HP 20 22 24 26 28 30 32 34 36
Combination HP 10x2 10+12 10+14 12+14 12+16 12+18 16x2 16+18 18x2
Capacity kW 56,0 61,5 68,0 73,5 78,5 83,5 90,0 95,0 100,0
Power input kW 14,36 15,82 17,01 18,46 20,64 22,45 24,00 25,81 28,72
Cooling (1)
EER - 3,90 3,89 4,00 3,98 3,80 3,72 3,75 3,68 3,48
Operating temperature range (DB) (5) °C -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52
Capacity kW 56,0 61,5 68,0 73,5 78,5 83,5 90,0 95,0 100,0

OUTDOOR UNITS
Power input kW 10,92 12,03 13,72 14,83 16,35 18,47 19,57 21,69 21,83
Heating (2)
COP - 5,13 5,11 4,96 4,96 4,80 4,52 4,60 4,38 4,58
Operating temperature range (DB) °C -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27
Operating temperature range DHW (DB) (6) °C -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43
Connectable Total Capacity Index (3) - 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200%
indoor units Max quantity - 64 64 64 64 64 64 64 64 64
Type - DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter
Compressor
Quantity - 2 2 2 2 2 2 2 2 2
Factory charge kg 16 16 18 18 18 18 20 20 20
Refrigerant
CO2 equivalence ton 33,41 33,41 37,58 37,58 37,58 37,58 41,76 41,76 41,76
Liquid pipe mm Ø 15,9 Ø 15,9 Ø 15,9 Ø 19,1 Ø 19,1 Ø 19,1 Ø 19,1 Ø 19,1 Ø 19,1
Piping
Low pressure gas pipe mm Ø 28,6 Ø 28,6 Ø 34,9 Ø 34,9 Ø 34,9 Ø 34,9 Ø 34,9 Ø 34,9 Ø 34,9
connections
High pressure gas pipe mm Ø 28,6 Ø 28,6 Ø 28,6 Ø 28,6 Ø 28,6 Ø 28,6 Ø 28,6 Ø 28,6 Ø 28,6
Quantity - 2 2 3 3 3 3 4 4 4
Fan motor
Static pressure Pa 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80
Dimensions 990×1635 990×1635 990×1635 990×1635× 990×1635 990×1635 1340×1635 1340×1635 1340×1635
Unit 1 mm
(Width x ×790 ×790 ×790 790 ×790 ×790 ×825 ×825 ×825
Height x 990×1635 990×1635 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635
Unit 2 mm
Depth) ×790 ×790 ×825 ×825 ×825 ×825 ×825 ×825 ×825
Weight kg 464 464 532 532 532 532 600 600 600
Air flow rate m3/h 19000 19500 23500 24000 24900 25800 29800 30700 31600
Sound pressure level (4) dB(A) 61 62 63 64 65 66 67 68 68
Sound power level (4) dB(A) 81 83 83 84 89 89 91 91 91
Power supply V/Ph/Hz 380-415/3/50+N

EEER and COP according EN 14511 regulation (3) Total Capacity Index = indoor unit total capacity/outdoor unit capacity. Please refer to technical manual
(1) Indoor temperature 27°C DB/19°C WB; Outdoor temperature 35°C DB/24°C WB. Interconnecting piping for further information about total capacity index as function of specific units connected.
length is 7,5 m, level difference is zero. (4) Sound values are measured in a semi-anechoic room, at a position 1 m in front of the unit and 1,3 m
(2) Indoor temperature 20°C DB/15°C WB; Outdoor temperature 7°C DB/6°C WB. Interconnecting piping above the floor.
length is 7,5 m, level difference is zero. (5) -15 °C to -5 °C operation available in combination with MS box MS01
(6) DHW available in combination with high temperature hydro module HWM-2-XMi 140
VRF MV6R
Size MV6R-XMi 1070T 1120T 1185T 1235T 1300T 1350T 1400T 1450T 1500T
Capacity HP 38 40 42 44 46 48 50 52 54
Combination HP 12x2+14 12x2+16 12+14+16 12+16x2 14+16x2 16x3 16x2+18 16+18x2 18x3
Capacity kW 107,0 112,0 118,5 123,5 130,0 135,0 140,0 145,0 150,0
Power input kW 27,10 29,27 30,46 32,64 33,83 36,00 37,81 39,62 41,44
Cooling (1)
EER - 3,95 3,83 3,89 3,78 3,84 3,75 3,70 3,66 3,62
Operating temperature range (DB) (5) °C -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52 -15 ~ 52
Capacity kW 107,0 112,0 118,5 123,5 130,0 135,0 140,0 145,0 150,0
OUTDOOR UNITS

Power input kW 21,40 22,92 24,62 26,13 27,83 29,35 31,47 33,59 35,71
Heating (2)
COP - 5,00 4,89 4,81 4,73 4,67 4,60 4,45 4,32 4,20
Operating temperature range (DB) °C -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27 -25~ 27
Operating temperature range DHW (DB) (6) °C -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43 -20~ 43
Connectable Total Capacity Index (3) - 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200% 50 ~ 200%
indoor units Max quantity - 64 64 64 64 64 64 64 64 64
Type - DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter
Compressor
Quantity - 3 3 3 3 3 3 3 3 3
Factory charge kg 26 26 28 28 30 30 30 30 30
Refrigerant
CO2 equivalence ton 54,29 54,29 58,46 58,46 62,64 62,64 62,64 62,64 62,64
Liquid pipe mm Ø 19,1 Ø 19,1 Ø 19,1 Ø 19,1 Ø 19,1 Ø 19,1 Ø 19,1 Ø 19,1 Ø 19,1
Piping
Low pressure gas pipe mm Ø 41,3 Ø 41,3 Ø 41,3 Ø 41,3 Ø 41,3 Ø 41,3 Ø 41,3 Ø 41,3 Ø 41,3
connections
High pressure gas pipe mm Ø 34,9 Ø 34,9 Ø 34,9 Ø 34,9 Ø 34,9 Ø 34,9 Ø 34,9 Ø 34,9 Ø 34,9
Quantity - 4 4 5 5 6 6 6 6 6
Fan motor
Static pressure Pa 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80 0 ~ 80
990×1635 990×1635 990×1635 990×1635 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635
Unit 1 mm
Dimensions ×790 ×790 ×790 ×790 ×825 ×825 ×825 ×825 ×825
(Width x 990×1635 990×1635 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635
Unit 2 mm
Height x ×790 ×790 ×825 ×825 ×825 ×825 ×825 ×825 ×825
Depth) 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635 1340×1635
Unit 3 mm
×825 ×825 ×825 ×825 ×825 ×825 ×825 ×825 ×825
Weight kg 764 764 832 832 900 900 900 900 900
Air flow rate m3/h 34000 34900 38900 39800 43800 44700 45600 46500 47400
Sound pressure level (4) dB(A) 65 67 67 68 68 69 69 69 70
Sound power level (4) dB(A) 86 89 89 91 91 93 93 93 93
Power supply V/Ph/Hz 380-415/3/50+N

EER and COP according EN 14511 regulation (3) Total Capacity Index = indoor unit total capacity/outdoor unit capacity. Please refer to technical manual
(1) Indoor temperature 27°C DB/19°C WB; Outdoor temperature 35°C DB/24°C WB. Interconnecting piping for further information about total capacity index as function of specific units connected.
length is 7,5 m, level difference is zero. (4) Sound values are measured in a semi-anechoic room, at a position 1 m in front of the unit and 1,3 m
(2) Indoor temperature 20°C DB/15°C WB; Outdoor temperature 7°C DB/6°C WB. Interconnecting piping above the floor.
length is 7,5 m, level difference is zero. (5) -15 °C to -5 °C operation available in combination with MS box MS01
(6) DHW available in combination with high temperature hydro module HWM-2-XMi 140
MS box for VRF MV6R
Heat recovery and simultaneous heating and cooling within the same system are possible thanks to specific MS box located between
outdoor units and indoor units, which separate gas-phase and liquid-phase refrigerant diverting it towards different spaces requiring
heating or cooling.
MS box are available in various versions, with single branch or multiple branches.

SINGLE MS BOX

REF-SP20D042GB-01
• Cooling mode operation extended down to -15 °C
• 3rd party refrigerant leakage sensors management and possible
leakage insulation through specific shut-off valve
• Up to 8 indoor units connectable with a total capacity up to 32 kW
(running in the same operating mode)
• Compact and light to install
• No drain piping needed
• Extreme control precision through a 3200 step electric ball valve MS01N1-D

• Silent operation

MULTIPLE MS BOX

• 4, 6, 8, 10 and 12 branches versions available


• Up to 5 indoor units connectable for each branch (running in the same
operating mode), for a total of 47 indoor units maximum per MS box for MS04N1-D MS06N1-D MS08N1-D
the 12 branches version
• Up to 16 kW for each branch, or 28 kW by connecting 2 branches

MS10N1-D MS12N1-D

Technical data MS Box for VRF MV6R

MS BOX

Size MS 01N1-D 04N1-D 06N1-D 08N1-D 10N1-D 12N1-D
Number of branches - 1 4 6 8 10 12
Max. number of indoor units per branch (1) - 8 5 5 5 5 5
Max. total number of indoor units per MS box (1) - 8 20 30 40 47 47
Max. capacity per branch (2) kW 32 16 16 16 16 16
Max. total capacity of indoor units per MS box kW 32 49 63 85 85 85
Liquid pipe mm Ø9,53/Ø12,7 Ø9,53/Ø12,7/Ø15,9/Ø19,1 Ø9,53/Ø12,7/Ø15,9/Ø19,1 Ø12,7/Ø15,9/Ø19,1/Ø22,2 Ø12,7/Ø15,9/Ø19,1/Ø22,2 Ø12,7/Ø15,9/Ø19,1/Ø22,2
Connections to
Low pressure gas pipe mm Ø15,9/Ø19,1/Ø22,2 Ø19,1/Ø22,2/Ø28,6 Ø19,1/Ø22,2/Ø28,6 Ø22,2/Ø28,6/Ø34,9 Ø22,2/Ø28,6/Ø34,9 Ø22,2/Ø28,6/Ø34,9
Pipe outdoor units
High pressure gas pipe mm Ø12,7/Ø15,9/Ø19,1 Ø15,9/Ø19,1/Ø22,2/Ø28,6 Ø15,9/Ø19,1/Ø22,2/Ø28,6 Ø19,1/Ø22,2/Ø28,6 Ø19,1/Ø22,2/Ø28,6 Ø19,1/Ø22,2/Ø28,6
connections
Connections to Liquid pipe mm Ø6,35/Ø9,53 Ø6,35/Ø9,53 Ø6,35/Ø9,53 Ø6,35/Ø9,53 Ø6,35/Ø9,53 Ø6,35/Ø9,53
indoor units Gas pipe mm Ø12,7/Ø15,9 Ø12,7/Ø15,9 Ø 12,7/Ø 15,9 Ø12,7/Ø15,9 Ø12,7/Ø15,9 Ø12,7/Ø15,9
Dimensions (Width x Height x Depth) mm 440×195×296 668×250×574 668×250×574 974×250×574 974×250×574 974×250×574
Weight kg 10,5 33 36 48 51 54
Sound pressure level (3) dB(A) 40 44 45 47 47 47
Sound power level (3) dB(A) 60 63 65 65 65 65
Power supply V/Ph/Hz 220-240/1/50

(1) All indoor units connected to the same branch of MS box should operate the same mode. (3) Sound values are measured in a semi-anechoic room, at a position 1m below the MS box in mode switch
(2) For 4 to 12 branches MS box models, 16 kW to 28 kW capacity indoor units can be connected by merging condition.
two branches to one through FQZHN-09A connection kit. It is recommended to avoid the installation of MS box in locations with low-noise requirements.

Data contained in this document are not binding and may be changed by the Manufacturer without notice

www.clivet.com