Commercial Air Conditioner Division
Clivet Group
Add.: Clivet Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China Commercial Air Conditioners
ASEAN VRF Catalogue
Postal code: 528311

Tel: +86-757-26338346 Fax: +86-757-22390205

Note: Product specifications change from time to time as product improvements and developments are released and may vary from those in this document.
Clivet CAC
Clivet CAC is a key division of the Clivet Group, a leading producer of consumer appliances and provider of We have three production bases: Shunde, Chongqing and Hefei.
heating, ventilation and air conditioning solutions. Midea CAC has continued with the tradition of MCAC Shunde: 38 product lines focusing on VRF, Split Products, Heat Pump Water Heaters, and AHU/FCU.
innovation upon which it was founded, and emerged as a global leader in the HVAC industry. A strong MCAC Chongqing: 14 product lines focusing on Water Cooled Centrifugal/Screw/Scroll Chillers, Air Cooled
drive for advancement has created a groundbreaking R&D department that has placed Midea CAC at the Screw/Scroll Chillers, and AHU/FCU.
forefront of a competitive field. Through these independent efforts and joint cooperation with other MCAC Hefei: 11 product lines focusing on VRF, Chillers, and Heat Pump Water Heaters.
global enterprises, Midea has supplied thousands of innovative solutions to customers worldwide.

2018 Launched the new generation VRF globally, leading in VRF market
2016 Acquired 80% stake in Clivet
2014-2015 Win FIFA World Cup Stadiums project in Brazil Beira Rio, Olympic Games Stadiums project in Brazil
Rio de Janeiro and Africa games Stadiums project in Congo Brazzaville successively
2014 Launched the All DC Inverter V5X globally, outstanding product performance helps Midea leading
VRF market
2011-2014 Launched the DC Inverter V4 Plus Series successively, complete product lines help Midea
successfully enter the mainstream VRF market
2011-2012 J.V. with Carrier LA and Carrier India successively
2009 Launched the DC Inverter V4 globally
2008 Developed DC inverter technology with Toshiba
2000-2001 Cooperated with Toshiba and Copeland, enter VRF field
1999 Entered the CAC field
INDEX
OUTDOOR UNITS 2nd Generation
11 VX Series VRF VRF INDOOR UNITS
29 VX-i Series VRF 65 One-way Cassette
31 Side Discharge VRF 66 Two-way Cassette
67 Compact Four-way Cassette
68 Four-way Cassette
69 Medium Static Pressure Duct
70 High Static Pressure Duct
71 Fresh Air Processing Unit
72 Wall Mounted
73 Ceiling & Floor
74 Floor Standing
76 Console

1st Generation CONTROL SOLUTIONS


VRF INDOOR UNITS 81 Wireless Remote Controllers
40 One-way Cassette 85 Wired Controllers
41 Two-way Cassette 89 Centralized Controllers
42 Four-way Cassette 95 Network Control System
45 Medium Static Pressure Duct 101 BMS Gateways
47 High Static Pressure Duct
113 Diagnosis Software
50 Fresh Air Processing Unit
51 Wall Mounted 117 VRF AHU Control Box
53 Ceiling & Floor 120 Heat Recovery Ventilator
56 Floor Standing 124 Branch Joints
58 Console

03 04
OUTDOOR UNIT LINEUP
VX Series VRF
HP 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102

VX SERIES

VX-I SERIES

Side Discharge VRF


HP 3 4 4.5 5 6 7 8 10 14 16

COOLING ONLY MINI SERIES

VRF V4 PLUS I SERIES

Single unit

Multi combination

05 06
INDOOR UNIT LINEUP
kW 1.8 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 10.0 11.2 12.5 14.0 16.0 20.0 25.0 28.0 40.0 45.0 56.0

Btu/h 6k 7k 9k 12k 15k 19k 24k 27k 30k 34k 38k 42k 48k 55k 68k 85k 96k 136k 154k 191k

One-way
cassette

Two-way
cassette

Cassette

Four-way
cassette

Compact
four-way
cassette

Medium static
pressure

Duct High static


pressure

Fresh air
processing
unit

Wall mounted

Ceiling & floor

Floor standing

Console

1st Gen. VRF IDU

2nd Gen. VRF IDU

07 08
OUTDOOR UNITS

OUTDOOR UNITS
VX Series VRF

VX-i Series VRF


OUTDOOR UNITS Side Discharge VRF

09 10
OUTDOOR UNITS

OUTDOOR UNITS
3 Unique Innovations
High Efficiency

High Reliability

Wide Application Range

Enhanced Comfort Easy Installation and Service

11 12
3 Unique Innovations High Efficiency
OUTDOOR UNITS

OUTDOOR UNITS
Energy Management System (EMS) Plate Heat Exchanger (PHE) Subcooling
Floating evaporating
Floating refrigerant temperature to balance comfort and efficiency 15 temperature °C Plate Heat Exchanger as a secondary intercooler boosts up refrigerant subcooling and improves 10% energy efficiency.

temperature oC
Evaporating
The evaporating temperature (in cooling) and condensing temperature (in
10
heating) are automatically adjusted according to both indoor and outdoor
5
temperature to maximize the comfort and energy efficiency.
17 32
Temperature oC
Output limitation during electricity supply restrictions
100%
With the integration of EMS, for projects with temporary electricity supply
90%
restrictions, VX can be set to output 40-100% capacity. 80% 1st stage
2nd stage

70%
60%
50%
40%

Enhanced Vapor Injection (EVI) Compressor


High Efficiency G-Type Heat Exchanger
Thanks to the vapor injection DC inverter
m+Δm Refrigerant circulation increased
compressor, the VX VRF can run heating mode P 26-34HP units use a high efficiency 3-row G-type heat exchanger with a heat exchange area 1.5 times that of the 24HP unit. The
stably down to -25oC, and the heating capacity 26-34HP units also use super big size fan which diameter is up to 750mm.
Δm
can be improved greatly.
m
Outdoor evaporation
capacity increased
h
EVI compressor

Triple Configurations

Triple (local/remote/network) configurations greatly simplified installation, commissioning and servicing.

Field local configuration achieves quick and easy on-site settings,


3-rows G-type heat exchanger
simplifies installation and commissioning.

System checking and settings also can be easily achieved via wired
and centralized controller, making the configuration more flexible
and convenient.

A desktop or laptop PC can be used for browser-based access to


achieve system configurations through IMM Pro gateway via a LAN
connection.

Super big size fan

01 01
13 14
Wide Application Range High Reliability
OUTDOOR UNITS

OUTDOOR UNITS
Wide Capacity Range Duty Cycling

Starting at 8HP, capacity increases in 2HP increments up to 102HP, which is the world's largest single-system VRF capacity. Duty cycling equalizes the running time of the outdoor units in a multiple-unit system and of the compressors in each unit,
significantly extending compressor lifespan.
8/10/12/14HP 16/18HP 20/22/24HP 26/28/30/32/34HP
(with single fan) (with single fan) (with dual fans) (with dual fans)

1 2 3 3 1 2 2 3 1

1st cycle 2nd cycle 3rd cycle

16-68HP 24-102HP

Precise Oil Control Technology

Four stages of oil control technology ensure all outdoor compressor oil is always kept at a safe level, eliminating any compressor
oil shortage problems.

Compressor internal oil separation.


Wide Operation Range
High-efficiency centrifugal oil separator (with separation efficiency of up to 99%) ensures that oil is separated from the
-5°C 54°C discharge gas and returned to the compressors in a timely fashion.
The VX VRF can operate stably in a wide ambient temperature range:
from -5oC to 54oC in cooling mode and from -25oC to 24oC in heating Oil balance pipes between compressors ensure even oil distribution to keep compressors running normally.
mode. COOLING MODE
Auto oil return program monitors the running time and system status to ensure reliable oil return.
-25°C 24°C

HEATING MODE

Long Piping Capability

Total piping length: 1000m 2nd stage

Longest piping length – actual (equivalent): 175m (200m)


Level difference between IDU~ODU 110m
Longest actual piping length 175m

Longest piping length after first branch: 40/90*m

Level difference between IDUs and ODU – ODU above (below):


90m (110m) 4th stage
between IDU~IDU 30m

1st stage
Level difference between IDUs: 30m
Level difference
90m

3rd stage

*The longest length after rst branch is 40m as standard but can be extended to
up to 90m under certain conditions. Please contact your local Midea dealer for
further information.

01 01
15 16
High Reliability High Reliability
OUTDOOR UNITS

OUTDOOR UNITS
Backup Operation Refrigerant Cooling PCB

In units with two compressors, if one compressor fails, the other compressor can run on its own for up to 4 days, allowing time The VX VRF uses refrigerant cooling technology to cool the
for maintenance or repair whilst maintaining comfort. electric control box. It decreases the average temperature of
electrical control components by about 8 degrees, guaranteeing
the stable and safe running of the control system.

Operation compressor

Standby compressor
Real-time Refrigerant Amount Monitoring
Failed compressor

The temperature and pressure of refrigerant can be real-time monitored by the outdoor unit. When the level of refrigerant is too
low or too high, this can cause damage to the unit and poor performance. VX outdoor unit can detect excessive or insufficient
amounts of refrigerant, to ensure consistent performance.

Compressor backup
Detects excessive Detects insufficient
Detects normal
refrigerant refrigeran
refrigerant

Anti-corrosion Protection

Outdoor units are given anti-corrosion treatment for non-extreme conditions as standard and can also be customized with 110% 90% R410A

heavy anti-corrosion treatment on main components for surface protection against corrosive air, acid rain and saline air (for
installations in coastal regions) to extend overall useful life. The integrity of the anti-corrosion treatment is ensured by subjecting
major components and parts to salt mist testing, moisture and heating testing and light aging testing.
Auto Snow-blowing Function*

The innovatively designed auto snow-blowing function enables


the outdoor unit to prevent the accumulation of snow by itself.
Fan motor
Standard products:
72h of neutral salt mist *This function is available as a customization option.
Heat exchanger aluminum foil
Heavy anti-corrosion products: Standard products:
240h of neutral salt mist 72h of neutral salt mist

Heavy anti-corrosion products:


1000h of neutral salt mist
140h of acid salt mis

Dust-clean function*
Heat exchanger copper pipe
Painted sheet metal
Standard products:
Standard products: 24h of neutral salt mist
500h of neutral salt mist The innovatively designed dust-clean function enables
1000h of moisture and heating test
500h of light aging test
Heavy anti-corrosion products: the outdoor unit to prevent the dust by itself.
120h of neutral salt mist

Heavy anti-corrosion products:


1000h of neutral salt mist
*This function is available as a customization option.
2000h of moisture and heating test
720h of light aging test
Screws / bolts / gaskets Electric control box case
Standard products: Standard products: Self-clean
300h of neutral salt mist 96h of neutral salt mist

Heavy anti-corrosion products: Heavy anti-corrosion products:


720h of neutral salt mist 240h of neutral salt mist
01 01
17 18
Enhanced Comfort Easy Installation and Service
OUTDOOR UNITS

OUTDOOR UNITS
Night Silent Mode Non-polarized Communication Wiring*

The night silent mode feature, which is easily configured on the outdoor unit's PCB, includes various scheduling options that can Only one chain of 2-core non-polarized shielded communication wiring required for indoor and outdoor unit communication.
be used to reduce noise levels at times when low noise operation is required.
*In installations where relatively strong electromagnetic fields are present, 3-core shielded wiring should be used in order to prevent interference.

Q P Q P Q P Q P

Load

Q P

Off
Sound
level
Judgment time Low-noise operation time Auto Addressing
6hrs 10hrs

Max. 15dB(A) reduction Outdoor units can distribute addresses to indoor units automatically. Remote and wired controllers can be used to query or
6:00 12:00 14:00 18:00 20:00 0:00 6:00 modify each indoor unit's address.
Highest Start End
outdoor temp.

Automatic Refrigerant Charging/Recycling Function*


Enhanced Heating Capacity
Automatic refrigerant charging and
Heating capacity is 100% of rated capacity at ambient 120%
recycling make installation and service
temperatures as low as -5oC and 90% of rated capacity at -15oC.
100% easier and more efficient.

80%
*This function is available as a customization option.
60%

40%

20%

0%
-20 -15 -10 -5 0 5
Intelligent Defrosting Technology

The intelligent defrosting program calculates the Optional Multifunctional PCB


Intelligent defrosting
time required for defrosting according to the actual
system status, eliminating heat losses from An optional multifunctional small PCB can be installed on the unit's
Heating capacity

unnecessary defrosting. A specialized defrosting Usual defrosting side columns, enabling installation and service engineers to
valve reduces time required for defrosting to as little activate Auto-commissioning or check the operating status
at four minutes. without removing the front panel. It can also perform automatic
t min Δt
data backup of the last 30 minutes' operating record.

Time

01
19 20
VX Specifications VX Specifications
OUTDOOR UNITS

OUTDOOR UNITS
HP 8 10 12 14 HP 20 22 24
Model name MVX-252WV2GN1 MVX-280WV2GN1 MVX-335WV2GN1 MVX-400WV2GN1 Model name MVX-560WV2GN1 MVX-615WV2GN1 MVX-670WV2GN1
Power supply V/Ph/Hz 380-415/3/50(60) Power supply V/Ph/Hz 380-415/3/50(60)
kW 25.2 28.0 33.5 40.0 kW 56.0 61.5 67.0
Capacity Capacity
kBtu/h 86.0 95.5 114.3 136.5 kBtu/h 191.1 209.8 228.6
Cooling1 Cooling1
Power input kW 5.30 6.21 7.77 9.50 Power input kW 13.83 15.38 17.87
EER 4.75 4.51 4.31 4.21 EER 4.05 4.00 3.75
kW 27.0 31.5 37.5 45.0 kW 63.0 69.0 75.0
Capacity Capacity
2 kBtu/h 92.1 107.5 128.0 153.5 2 kBtu/h 215.0 235.4 255.9
Heating Heating
Power input kW 4.82 5.92 7.55 9.57 Power input kW 14.48 16.43 18.07
COP 5.60 5.32 4.97 4.70 COP 4.35 4.20 4.15
Total capacity 50-130% of outdoor unit capacity Total capacity 50-130% of outdoor unit capacity
Connected indoor unit Connected indoor unit
Maximum quantity 13 16 20 23 Maximum quantity 33 36 39
Type DC inverter Type DC inverter
Compressors Compressors
Quantity 1 Quantity 2
Type DC Type DC
Fan motors Quantity 1 Fan motors Quantity 2
Static pressure Pa 0-20 (default); 20-60 (customized) Static pressure Pa 0-20 (default); 20-60 (customized)
Type R410A Type R410A
Refrigerant Refrigerant
Factory charge kg 11 Factory charge kg 17
Liquid pipe mm Φ12.7 Φ15.9 Φ15.9 Liquid pipe mm Φ19.1
Pipe connections3 Pipe connections3
Gas pipe mm Φ25.4 Φ28.6 Φ31.8 Gas pipe mm Φ31.8
3 Air flow rate 3 17000
Air flow rate m /h 11000 m /h
4
Sound pressure level 4 dB(A) 58 58 60 60 Sound pressure level dB(A) 62 63 63
Net dimensions (W×H×D) mm 990×1635×790 Net dimensions (W×H×D) mm 1340×1635×825
Packed dimensions (W×H×D) mm 1090×1805×860 Packed dimensions (W×H×D) mm 1405×1805×910
Net weight kg 227 Net weight kg 348
Gross weight kg 242 Gross weight kg 368
o o -5 ~ 54
Ambient temp. Cooling C -5 ~ 54 Ambient temp. Cooling C
operation range o operation range o -25 ~ 24
Heating C -25 ~ 24 Heating C

HP 16 18 HP 26 28 30
Model name MVX-450WV2GN1 MVX-500WV2GN1 Model name MVX-730WV2GN1 MVX-785WV2GN1 MVX-850WV2GN1
Power supply V/Ph/Hz 380-415/3/50(60) Power supply V/Ph/Hz 380-415/3/50(60)
kW 45.0 50.0 kW 73.0 78.5 85.0
Capacity Capacity
1 kBtu/h 153.5 170.6 1 kBtu/h 249.1 267.8 290.0
Cooling Cooling
Power input kW 10.92 12.20 Power input kW 18.48 20.13 22.91
EER 4.12 4.10 EER 3.95 3.90 3.71
kW 50.0 56.0 kW 81.5 87.5 95.0
Capacity Capacity
2 kBtu/h 170.6 191.1 2 kBtu/h 278.1 298.6 324.1
Heating Heating
Power input kW 10.87 12.44 Power input kW 18.15 19.98 22.09
COP 4.60 4.50 COP 4.49 4.38 4.30
Total capacity 50-130% of outdoor unit capacity Total capacity 50-130% of outdoor unit capacity
Connected indoor unit Connected indoor unit
Maximum quantity 26 29 Maximum quantity 43 46 50
Type DC inverter Type DC inverter
Compressors Compressors
Quantity 1 Quantity 2
Type DC Type DC
Fan motors Quantity 1 Fan motors Quantity 2
Static pressure Pa 0-20 (default); 20-60 (customized) Static pressure Pa 0-20 (default); 20-60 (customized)
Type R410A Type R410A
Refrigerant Refrigerant
Factory charge kg 13 Factory charge kg 22
3 Liquid pipe mm Φ15.9 Φ19.1 3 Liquid pipe mm Φ22.2 Φ22.2
Pipe connections Pipe connections
Gas pipe mm Φ31.8 Φ31.8 Gas pipe mm Φ31.8 Φ38.1
Air flow rate 3 13000 Air flow rate 3 25000
m /h m /h
4 4
Sound pressure level dB(A) 60 61 Sound pressure level dB(A) 64
Net dimensions (W×H×D) mm 1340×1635×850 Net dimensions (W×H×D) mm 1730×1830×850
Packed dimensions (W×H×D) mm 1405×1805×910 Packed dimensions (W×H×D) mm 1800×2000×910
Net weight kg 277 Net weight kg 430
Gross weight kg 304 Gross weight kg 453
o -5 ~ 54 o -5 ~ 54
Ambient temp. Cooling C Ambient temp. Cooling C
operation range o -25 ~ 24 operation range o -25 ~ 24
Heating C Heating C
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit's stop valve. 3. Diameters given are those of the unit's stop valve.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. 4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

21 22
VX Specifications VX Specifications
OUTDOOR UNITS

OUTDOOR UNITS
HP 32 34 HP 44 46 48
Model name MVX-900WV2GN1 MVX-950WV2GN1 Model name MVX-1230WV2GN1 MVX-1285WV2GN1 MVX-1340WV2GN1
Power supply V/Ph/Hz 380-415/3/50(60) Combination type 22HP+22HP 22HP+24HP 24HP+24HP
kW 90.0 95.0 Power supply V/Ph/Hz 380-415/3/50(60)
Capacity
kBtu/h 307.1 324.1 kW 123.0 128.5 134.0
Cooling1 Capacity
Power input kW 24.66 27.14 1 kBtu/h 419.7 438.4 457.2
Cooling
EER 3.65 3.50 Power input kW 30.76 33.25 35.74
kW 100.0 106.0 EER 3.75 3.86 3.75
Capacity
kBtu/h 341.2 361.7 kW 138.0 144.0 150.0
Heating2 Capacity
Power input kW 23.36 26.37 2 kBtu/h 470.9 491.3 511.8
Heating
COP 4.28 4.02 Power input kW 32.9 34.5 36.1
Total capacity 50-130% of outdoor unit capacity COP 4.20 4.17 4.15
Connected indoor unit
Maximum quantity 53 56 Total capacity 50-130% of outdoor unit capacity
Connected indoor unit
Type DC inverter Maximum quantity 64
Compressors
Quantity 2 Type DC inverter
Compressors
Type DC Quantity 4
Fan motors Quantity 2 Type DC
Static pressure Pa 0-20 (default); 20-60 (customized) Fan motors Quantity 4
Type R410A Static pressure Pa 0-20 (default); 20-60 (customized)
Refrigerant
Factory charge kg 25 Type R410A
Refrigerant
Liquid pipe mm Φ22.2 Factory charge kg 17×2
Pipe connections3
Gas pipe mm Φ38.1 3 Liquid pipe mm Φ19.1
Pipe connections
Air flow rate 3
m /h 24000 Gas pipe mm Φ38.1
Sound pressure level
4
dB(A) 64 Air flow rate m3/h 34000
4
Net dimensions (W×H×D) mm 1730×1830×850 Sound pressure level dB(A) 66
Packed dimensions (W×H×D) mm 1800×2000×910 Net dimensions (W×H×D) mm (1340×1635×825)×2
Net weight kg 475 Packed dimensions (W×H×D) mm (1405×1805×910)×2
Gross weight kg 507 Net weight kg 348×2
Ambient temp. Cooling o
C -5 ~ 54 Gross weight kg 368×2
o -5 ~ 54
operation range Heating o
C -25 ~ 24 Ambient temp. Cooling C
operation range o -25 ~ 24
Heating C

HP 36 38 40 42 HP 50 52 54
Model name MVX-1005WV2GN1 MVX-1070WV2GN1 MVX-1120WV2GN1 MVX-1170WV2GN1 Model name MVX-1400WV2GN1 MVX-1455WV2GN1 MVX-1520WV2GN1
Combination type 12HP+24HP 14HP+24HP 16HP+24HP 18HP+24HP Combination type 24HP+26HP 24HP+28HP 24HP+30HP
Power supply V/Ph/Hz 380-415/3/50(60) Power supply V/Ph/Hz 380-415/3/50(60)
kW 100.5 107.0 112.0 117.0 kW 140.0 145.5 152.0
Capacity Capacity
kBtu/h 342.9 365.1 382.1 399.2 kBtu/h 477.7 496.4 518.6
Cooling1 Cooling1
Power input kW 25.64 27.37 28.79 30.07 Power input kW 36.35 38.00 40.78
EER 3.92 3.91 3.89 3.89 EER 3.85 3.83 3.73
kW 112.5 120.0 125.0 131.0 kW 156.5 162.5 170.0
Capacity Capacity
2 kBtu/h 383.9 409.4 426.5 447.0 2 kBtu/h 534.0 554.5 580.0
Heating Heating
Power input kW 25.6 27.6 28.9 30.5 Power input kW 36.2 38.0 40.2
COP 4.39 4.34 4.32 4.29 COP 4.32 4.27 4.23
Total capacity 50-130% of outdoor unit capacity Total capacity 50-130% of outdoor unit capacity
Connected indoor unit Connected indoor unit
Maximum quantity 59 63 64 Maximum quantity 64
Type DC inverter Type DC inverter
Compressors Compressors
Quantity 3 Quantity 4
Type DC Type DC
Fan motors Quantity 3 Fan motors Quantity 4
Static pressure Pa 0-20 (default); 20-60 (customized) Static pressure Pa 0-20 (default); 20-60 (customized)
Type R410A Type R410A
Refrigerant Refrigerant
Factory charge kg 11+17 13+17 Factory charge kg 17+22
Liquid pipe mm Φ19.1 Liquid pipe mm Φ19.1
Pipe connections3 Pipe connections3
Gas pipe mm Φ38.1 Gas pipe mm Φ38.1
Air flow rate m3/h 28000 30000 Air flow rate m3/h 42000
4 4
Sound pressure level dB(A) 65 Sound pressure level dB(A) 66
Net dimensions (W×H×D) mm (990×1635×790)+(1340×1635×825) (1340×1635×850)+(1340×1635×825) Net dimensions (W×H×D) mm (1340×1635×825)+(1730×1830×850)
Packed dimensions (W×H×D) mm (1090×1805×860)+(1405×1805×910) (1405×1805×910)×2 Packed dimensions (W×H×D) mm (1405×1805×910)+(1800×2000×910)
Net weight kg 227+348 277+348 Net weight kg 348+430
Gross weight kg 242+368 304+368 Gross weight kg 368+453
o -5 ~ 54 o -5 ~ 54
Ambient temp. Cooling C Ambient temp. Cooling C
operation range o -25 ~ 24 operation range o -25 ~ 24
Heating C Heating C
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less 3. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less
than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to the VX Series Engineering Data for connection piping diameters.. than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to the VX Series Engineering Data for connection piping diameters..
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. 4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

23 24
VX Specifications VX Specifications
OUTDOOR UNITS

OUTDOOR UNITS
HP 56 58 60 62 HP 70 72
Model name MVX-1570WV2GN1 MVX-1635WV2GN1 MVX-1700WV2GN1 MVX-1750WV2GN1 Model name MVX-1955WV2GN1 MVX-2020WV2GN1
Combination type 28HP+28HP 28HP+30HP 30HP+30HP 30HP+32HP Combination type 12HP+24HP+34HP 14HP+24HP+34HP
Power supply V/Ph/Hz 380-415/3/50(60) Power supply V/Ph/Hz 380-415/3/50(60)
kW 157.0 163.5 170.0 175.0 kW 195.5 202.0
Capacity Capacity
kBtu/h 535.7 557.9 580.0 597.1 kBtu/h 667.0 689.2
Cooling1 Cooling1
Power input kW 40.26 43.04 45.82 47.57 Power input kW 52.79 54.51
EER 3.90 3.80 3.71 3.68 EER 3.70 3.71
kW 175.0 182.5 190.0 195.0 kW 218.5 226.0
Capacity Capacity
2 kBtu/h 597.1 622.7 648.3 665.3 2 kBtu/h 745.5 771.1
Heating Heating
Power input kW 40.0 42.1 44.2 45.5 Power input kW 52.0 54.0
COP 4.38 4.34 4.30 4.29 COP 4.20 4.18
Total capacity 50-130% of outdoor unit capacity Total capacity 50-130% of outdoor unit capacity
Connected indoor unit Connected indoor unit
Maximum quantity 64 Maximum quantity 64
Type DC inverter Type DC inverter
Compressors Compressors
Quantity 4 Quantity 5
Type DC Type DC
Fan motors Quantity 4 Fan motors Quantity 5
Static pressure Pa 0-20 (default); 20-60 (customized) Static pressure Pa 0-20 (default); 20-60 (customized)
Type R410A Type R410A
Refrigerant Refrigerant
Factory charge kg 22×2 22+25 Factory charge kg 11+17+25
Liquid pipe mm Φ19.1 Liquid pipe mm Φ22.2
Pipe connections3 Pipe connections
3
Gas pipe mm Φ41.3 Gas pipe mm Φ44.5
Air flow rate m3/h 50000 49000 Air flow rate m3/h 52000
4
Sound pressure level dB(A) 67 Sound pressure level 4 dB(A) 68
Net dimensions (W×H×D) mm (1730×1830×850)×2 Net dimensions (W×H×D) mm (990×1635×790)+(1340×1635×825)+(1730×1830×850)
Packed dimensions (W×H×D) mm (1800×2000×910)×2 Packed dimensions (W×H×D) mm (1090×1805×860)+(1405×1805×910)+(1800×2000×910)
Net weight kg 430×2 430+475 Net weight kg 227+348+475
Gross weight kg 453×2 453+507 Gross weight kg 242+368+507
o -5 ~ 54 o -5 ~ 54
Ambient temp. Cooling C Ambient temp. Cooling C
operation range o -25 ~ 24 operation range o -25 ~ 24
Heating C Heating C

HP 64 66 68 HP 74 76
Model name MVX-1800WV2GN1 MVX-1850WV2GN1 MVX-1900WV2GN1 Model name MVX-2070WV2GN1 MVX-2120WV2GN1
Combination type 30HP+34HP 32HP+34HP 34HP+34HP Combination type 16HP+24HP+34HP 18HP+24HP+34HP
Power supply V/Ph/Hz 380-415/3/50(60) Power supply V/Ph/Hz 380-415/3/50(60)
kW 180.0 185.0 190.0 kW 207.0 212.0
Capacity Capacity
1 kBtu/h 614.2 631.2 648.3 1 kBtu/h 706.3 723.3
Cooling Cooling
Power input kW 50.05 51.80 54.29 Power input kW 54.82 57.21
EER 3.60 3.57 3.50 EER 3.70 3.71
kW 201.0 206.0 212.0 kW 231.0 237.0
Capacity Capacity
2 kBtu/h 685.8 702.9 723.3 2 kBtu/h 788.2 808.6
Heating Heating
Power input kW 48.5 49.7 52.7 Power input kW 55.3 56.9
COP 4.15 4.14 4.02 COP 4.18 4.17
Total capacity 50-130% of outdoor unit capacity Total capacity 50-130% of outdoor unit capacity
Connected indoor unit Connected indoor unit
Maximum quantity 64 Maximum quantity 64
Type DC inverter Type DC inverter
Compressors Compressors
Quantity 4 Quantity 5
Type DC Type DC
Fan motors Quantity 4 Fan motors Quantity 5
Static pressure Pa 0-20 (default); 20-60 (customized) Static pressure Pa 0-20 (default); 20-60 (customized)
Type R410A Type R410A
Refrigerant Refrigerant
Factory charge kg 22+25 25×2 Factory charge kg 13+17+25
3 Liquid pipe mm Φ19.1 Φ22.2 Liquid pipe mm Φ22.2
Pipe connections Pipe connections3
Gas pipe mm Φ41.3 Φ44.5 Gas pipe mm Φ44.5
Air flow rate m3/h 49000 48000 Air flow rate m3/h 54000
Sound pressure level 4 dB(A) 67 Sound pressure level 4 dB(A) 68
Net dimensions (W×H×D) mm (1730×1830×850)×2 Net dimensions (W×H×D) mm (1340×1635×850)+(1340×1635×825)+(1730×1830×850)
Packed dimensions (W×H×D) mm (1800×2000×910)×2 Packed dimensions (W×H×D) mm (1405×1805×910)×2+(1800×2000×910)
Net weight kg 430+475 475×2 Net weight kg 277+348+475
Gross weight kg 453+507 507×2 Gross weight kg 304+368+507
o -5 ~ 54 o -5 ~ 54
Ambient temp. Cooling C Ambient temp. Cooling C
operation range Heating o
C -25 ~ 24 operation range Heating o
C -23 ~ 24
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less 3. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less
than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to the VX Series Engineering Data for connection piping diameters.. than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to the VX Series Engineering Data for connection piping diameters..
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. 4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

25 26
VX Specifications VX Specifications
OUTDOOR UNITS

OUTDOOR UNITS
HP 78 80 82 HP 90 92 94 96
Model name MVX-2180WV2GN1 MVX-2235WV2GN1 MVX-2290WV2GN1 Model name MVX-2520WV2GN1 MVX-2585WV2GN1 MVX-2650WV2GN1 MVX-2700WV2GN1
Combination type 22HP+22HP+34HP 22HP+24HP+34HP 24HP+24HP+34HP Combination type 28HP+28HP+34HP 28HP+30HP+34HP 30HP+30HP+34HP 30HP+32HP+34HP
Power supply V/Ph/Hz 380-415/3/50(60) Power supply V/Ph/Hz 380-415/3/50(60)
kW 218.0 223.5 229.0 kW 252.0 258.5 265.0 270.0
Capacity Capacity
1 kBtu/h 743.8 762.6 781.3 1 kBtu/h 859.8 882.0 904.2 921.2
Cooling Cooling
Power input kW 57.90 60.39 62.88 Power input kW 67.40 70.18 72.96 74.71
EER 3.76 3.70 3.78 EER 3.74 3.68 3.63 3.61
kW 244.0 250.0 256.0 kW 281.0 288.5 296.0 301.0
Capacity Capacity
2 kBtu/h 832.5 853.0 873.5 2 kBtu/h 958.8 984.4 1010.0 1027.0
Heating Heating
Power input kW 59.2 60.9 62.5 Power input kW 66.3 68.4 70.6 71.8
COP 4.12 4.11 4.10 COP 4.24 4.22 4.20 4.19
Total capacity 50-130% of outdoor unit capacity Total capacity 50-130% of outdoor unit capacity
Connected indoor unit Connected indoor unit
Maximum quantity 64 Maximum quantity 64
Type DC inverter Type DC inverter
Compressors Compressors
Quantity 6 Quantity 6
Type DC Type DC
Fan motors Quantity 6 Fan motors Quantity 6
Static pressure Pa 0-20 (default); 20-60 (customized) Static pressure Pa 0-20 (default); 20-60 (customized)
Type R410A Type R410A
Refrigerant Refrigerant
Factory charge kg 17×2+25 Factory charge kg 22×2+25 22+25×2
Liquid pipe mm Φ22.2 Liquid pipe mm Φ25.4
Pipe connections3 Pipe connections
3
Gas pipe mm Φ44.5 Gas pipe mm Φ50.8
Air flow rate m3/h 58000 Air flow rate m3/h 74000 73000
Sound pressure level 4 dB(A) 69 Sound pressure level 4 dB(A) 70
Net dimensions (W×H×D) mm (1340×1635×825)×2+(1730×1830×850) Net dimensions (W×H×D) mm (1730×1830×850)×3
Packed dimensions (W×H×D) mm (1405×1805×910)×2+(1800×2000×910) Packed dimensions (W×H×D) mm (1800×2000×910)×3
Net weight kg 348×2+475 Net weight kg 430×2+475 430+475×2
Gross weight kg 368×2+507 Gross weight kg 453×2+507 453+507×2
o -5 ~ 54 o -5 ~ 54
Ambient temp. Cooling C Ambient temp. Cooling C
operation range o -25 ~ 24 operation range o -25 ~ 24
Heating C Heating C

HP 84 86 88 HP 98 100 102
Model name MVX-2350WV2GN1 MVX-2405WV2GN1 MVX-2470WV2GN1 Model name MVX-2750WV2GN1 MVX-2800WV2GN1 MVX-2850WV2GN1
Combination type 24HP+26HP+34HP 24HP+28HP+34HP 24HP+30HP+34HP Combination type 30HP+34HP+34HP 32HP+34HP+34HP 34HP+34HP+34HP
Power supply V/Ph/Hz 380-415/3/50(60) Power supply V/Ph/Hz 380-415/3/50(60)
kW 235.0 240.5 247.0 kW 275.0 280.0 285.0
Capacity Capacity
kBtu/h 801.8 820.6 842.8 1 kBtu/h 938.3 955.4 972.4
Cooling 1 Cooling
Power input kW 63.49 65.14 67.92 Power input kW 77.20 78.94 81.43
EER 3.70 3.69 3.64 EER 3.56 3.55 3.50
kW 262.5 268.5 276.0 kW 307.0 312.0 318.0
Capacity Capacity
kBtu/h 895.7 916.1 941.7 kBtu/h 1047.5 1064.5 1085.0
Heating 2 Heating2
Power input kW 62.6 64.4 66.5 Power input kW 74.8 76.1 79.1
COP 4.19 4.17 4.15 COP 4.10 4.10 4.02
Total capacity 50-130% of outdoor unit capacity
Connected indoor unit Total capacity 50-130% of outdoor unit capacity Connected indoor unit
Maximum quantity 64 Maximum quantity 64
Type DC inverter Type DC inverter
Compressors Compressors
Quantity 6 Quantity 6
Type DC Type DC
Fan motors Quantity 6 Fan motors Quantity 6
Static pressure Pa 0-20 (default); 20-60 (customized) Static pressure Pa 0-20 (default); 20-60 (customized)
Type R410A Type R410A
Refrigerant Refrigerant
Factory charge kg 17+22+25 Factory charge kg 22+25×2 25×3
Liquid pipe mm Φ25.4 3 Liquid pipe mm Φ25.4
Pipe connections3 Pipe connections
Gas pipe mm Φ50.8 Gas pipe mm Φ50.8
Air flow rate m3/h 66000 Air flow rate m3/h 73000 72000
4
Sound pressure level4 dB(A) 69 Sound pressure level dB(A) 71
Net dimensions (W×H×D) mm (1340×1635×825)+(1730×1830×850)×2 Net dimensions (W×H×D) mm (1730×1830×850)×3
Packed dimensions (W×H×D) mm (1405×1805×910)+(1800×2000×910)×2 Packed dimensions (W×H×D) mm (1800×2000×910)×3
Net weight kg 348+430+475 Net weight kg 430+475×2 475×3
Gross weight kg 368+453+507 Gross weight kg 453+507×2 507×3
o -5 ~ 54
Ambient temp. Cooling o
C -5 ~ 54 Ambient temp. Cooling C
operation range o -25 ~ 24
operation range Heating o
C -25 ~ 24 Heating C
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less 3. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less
than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to the VX Series Engineering Data for connection piping diameters.. than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to the VX Series Engineering Data for connection piping diameters..
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. 4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

27 28
VX-i Specifications VX-i Specifications
OUTDOOR UNITS

OUTDOOR UNITS
HP 8 10 12 14 HP 22 24
Model name MVX-i252WV2GN1 MVX-i280WV2GN1 MVX-i335WV2GN1 MVX-i400WV2GN1 Model name MVX-i615WV2GN1 MVX-i670WV2GN1
Power supply V/Ph/Hz 380-415/3/50(60) Power supply V/Ph/Hz 380-415/3/50(60)
kW 25.2 28.0 33.5 40.0 kW 61.5 67.0
Capacity Capacity
1 kBtu/h 86.0 95.5 114.3 136.5 1 kBtu/h 209.8 228.6
Cooling Cooling
Power input kW 5.79 7.20 8.93 10.96 Power input kW 19.04 21.61
EER 4.35 3.89 3.75 3.65 EER 3.23 3.10
kW 27.0 31.5 37.5 45.0 kW 69.0 75.0
Capacity Capacity
kBtu/h 92.1 107.5 128.0 153.5 kBtu/h 235.4 255.9
Heating2 Heating2
Power input kW 5.19 6.18 8.43 10.98 Power input kW 18.02 18.75
COP 5.20 5.10 4.45 4.10 COP 3.83 4.00
Total capacity 50-130% of outdoor unit capacity Total capacity 50-130% of outdoor unit capacity
Connected indoor unit Connected indoor unit
Maximum quantity 13 16 20 23 Maximum quantity 36 39
Type DC inverter Type DC inverter
Compressors Compressors
Quantity 1 Quantity 2
Motor type DC Motor type DC
Fan motors Quantity 1 Fan motors Quantity 2
Static pressure Pa 0-20 (default); 20-60 (customized) Static pressure Pa 0-20 (default); 20-60 (customized)
Type R410A Type R410A
Refrigerant Refrigerant
Factory charge kg 11 Factory charge kg 17
3 Liquid pipe mm Φ12.7 Φ15.9 Φ15.9 3 Liquid pipe mm Φ19.1
Pipe connections Pipe connections
Gas pipe mm Φ25.4 Φ28.6 Φ31.8 Gas pipe mm Φ31.8
Air flow rate 3 11000 Air flow rate 3 17000
m /h m /h
4 4
Sound pressure level dB(A) 58 58 60 60 Sound pressure level dB(A) 63
Net dimensions (W×H×D) mm 990×1635×790 Net dimensions (W×H×D) mm 1340×1635×825
Packed dimensions (W×H×D) mm 1090×1805×860 Packed dimensions (W×H×D) mm 1405×1805×910
Net weight kg 227 Net weight kg 344
Gross weight kg 242 Gross weight kg 364
o -5 ~ 54 o -5 ~ 54
Ambient temp. Cooling C Ambient temp. Cooling C
operation range o -25 ~ 24 operation range o -25 ~ 24
Heating C Heating C

HP 16 18 20 HP 26 28 30 32 34
Model name MVX-i450WV2GN1 MVX-i500WV2GN1 MVX-i560WV2GN1 Model name MVX-i730WV2GN1 MVX-i785WV2GN1 MVX-i850WV2GN1 MVX-i900WV2GN1 MVX-i950WV2GN1
Power supply V/Ph/Hz 380-415/3/50(60) Power supply V/Ph/Hz 380-415/3/50(60)
kW 45.0 50.0 56.0 kW 73.0 78.5 85.0 90.0 95.0
Capacity Capacity
1 kBtu/h 153.5 170.6 191.1 1 kBtu/h 249.1 267.8 290.0 307.1 324.1
Cooling Cooling
Power input kW 13.04 14.71 16.47 Power input kW 21.47 24.01 27.42 28.48 30.65
EER 3.45 3.40 3.40 EER 3.40 3.27 3.10 3.16 3.10
kW 50.0 56.0 63.0 kW 81.5 87.5 95.0 100.0 106.0
Capacity Capacity
kBtu/h 170.6 191.1 215.0 kBtu/h 278.1 298.6 324.1 341.2 361.7
Heating2 Heating2
Power input kW 11.90 13.66 15.75 Power input kW 20.63 24.31 27.14 29.41 32.12
COP 4.20 4.10 4.00 COP 3.95 3.60 3.50 3.40 3.30
Total capacity 50-130% of outdoor unit capacity Total capacity 50-130% of outdoor unit capacity
Connected indoor unit Connected indoor unit
Maximum quantity 26 29 33 Maximum quantity 43 46 50 53 56
Type DC inverter Type DC inverter
Compressors Compressors
Quantity 1 Quantity 2
Motor type DC Motor type DC
Fan motors Quantity 1 Fan motors Quantity 2
Static pressure Pa 0-20 (default); 20-60 (customized) Static pressure Pa 0-20 (default); 20-60 (customized)
Type R410A Type R410A
Refrigerant Refrigerant
Factory charge kg 13 Factory charge kg 22 25
3 Liquid pipe mm Φ15.9 Φ19.1 Φ19.1 3 Liquid pipe mm Φ22.2
Pipe connections Pipe connections
Gas pipe mm Φ31.8 Φ31.8 Φ31.8 Gas pipe mm Φ31.8 Φ38.1
Air flow rate 3 13000 Air flow rate 3 25000 24000
m /h m /h
4
Sound pressure level dB(A) 60 61 62 Sound pressure level 4 dB(A) 64
Net dimensions (W×H×D) mm 1340×1635×850 Net dimensions (W×H×D) mm 1730×1830×850
Packed dimensions (W×H×D) mm 1405×1805×910 Packed dimensions (W×H×D) mm 1800×2000×910
Net weight kg 277 295 Net weight kg 407 429 475
Gross weight kg 304 322 Gross weight kg 430 452 507
o -5 ~ 54 o -5 ~ 54
Ambient temp. Cooling C Ambient temp. Cooling C
operation range o -25 ~ 24 operation range o -25 ~ 24
Heating C Heating C
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit's stop valve. 3. Diameters given are those of the unit's stop valve.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. 4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

29 30
High Efficiency
OUTDOOR UNITS

OUTDOOR UNITS
High EER Values
SIDE DISCHARGE VRF EER
4.39 4.47 4.00 4.06 4.26 3.28 3.29 3.42 3.35 3.32

7.2kW 9.2kW 11.0kW 14.5kW 17kW 20kW 22.4kW 26kW 40kW 45kW

All DC Inverter Compressors


The DC inverter compressor adopts innovative design and numerous high performance key parts which can reduce power
consumption by 25%.

Highly Efficient DC Motor:


- Creative motor core design
- High density neodymium magnet
- Concentrated type stator
- Wider operating frequency range
Better balance and Extremely Low Vibration:
- Twin eccentric cams
- 2 balance weights
Highly Stable Moving Parts:
- Optimal material matching rollers and vanes
- Optimize compressor drive technology
High Efficiency - Highly robust bearings
Compressor
(Twin Rotary) structure - Compact structure
Wide Application Range
DC Fan Motors
Easy Installation and Service The system controls the speed of the fan motor according to the system pressure and system load achieving the minimum
power consumption.
Specifications

Motor speed(RPM)
850
DC inverter stepless
800 adjustment
600
AC inverter
multistep adjustment
400

200
System pressure

31 32
Wide Application Range Long Piping Length
OUTDOOR UNITS

OUTDOOR UNITS
Level difference between IDU and ODU is 30m
Wide Capacity Range Side Discharge VRF provides a total piping
length possibility of up to 250m, a maximum
The outdoor units’ capacity range from 7.2kW to 45kW which is ideal for small offices, villas, apartment and shops, making it

Level difference between IDUs is 8m


height difference between outdoor and indoor

The longest piping length is 70m


perfect for commercial and residential application.
units of 30m. The height difference between

The first branch joint to the


indoor units can be up to 8m. These generous

The IDU to the nearest


branch joint is 15m

farthest IDU is 20m


allowances facilitate an extensive array of
system designs.

Permitted value(m) 7.2/9.2/11kW 14.5/17kW

Total piping length 100m 100m


Piping length
Actual length 45m 60m
Longest piping (L)
Equivalent length 50m 70m
7.2kW, 9.2kW, 11kW 14.5kW, 17kW Equivalent piping length (from the farthest IDU to the first indoor
20m 20m
branch joint)

Outdoor unit up 30m 30m


Level difference Level difference between
IDU~ODU Outdoor unit down 20m 20m

Level difference between IDU~IDU 8m 8m

Piping length 20/22.4/26kW 40/45kW

Level difference between IDU~ODU 30m


Longest actual piping length 100m
Total piping length 120m 250m

Longest length - actual (equivalent) 60m (70m) 100m (120m)

between IDU~IDU 8m
Longest length after first branch 20m 40m

Level difference
Longest length after nearest branch 15m 15m

40m
20,22.4,26kW 40,45kW Largest height difference between
30m (20m) 30m (20m)
indoor and outdoor units - ODU up (down)
Largest height difference
8m 8m
between indoor units

Wide Operation Range


Side Discharge VRF operates stably under extreme conditions, ranging from minus 5°C to 48°C. 1 Total pipe length is equal to all the liquid pipe or all the gas pipe length.
2 When the total equivalent pipe length of liquid side plus gas side is more than 90m,
-5°C 48°C it needs to meet the specific conditions according to the installation part of the technical manual.

COOLING MODE

33 34
Easy Installation and Service Specifications
Mini VRF 50/60Hz - Cooling Only
OUTDOOR UNITS

OUTDOOR UNITS
Easy Installation
Easy installation: No special area is required for outdoor units. 220-240V,1ph,50Hz MDVC-V72W/DN1 MDVC-V92W/DN1 MDVC-V110W/DN1 MDVC-V145W/DN1 MDVC-V170W/DN1
Model name
Easy transportaion: All outdoor units can be transported by elevator, which greatly simplifies installation and reduces time and 208-230V,1ph,60Hz MDVC-V72W/DVN1 MDVC-V92W/DVN1 MDVC-V110W/DVN1 MDVC-V145W/DVN1 MDVC-V170W/DVN1
Capacity kW 7.2 9.2 11 14.5 17
labor. Cooling1 Power input kW 1.64 2.06 2.75 3.57 3.99
EER 4.39 4.47 4 4.06 4.26
Easy to transport
Total capacity 45-130% of outdoor unit capacity
Connected indoor units
Maximum quantity 4 5 6 8 9
Type DC inverter
Compressor
Quantity 1
Motor Type DC
Fan motor
Quantity 1
Type R410A
Refrigerant
Factory charging kg 1.4 1.4 1.4 2.6 2.6
Liquid pipe mm Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53
Pipe connections
Gas pipe mm Ф15.9 Ф15.9 Ф15.9 Ф15.9 Ф15.9
Airflow rate m3/h 3400 3400 3400 5100 5100
Sound pressure level2 dB(A) 54 54 54 55 55
Net dimensions (W×H×D) mm 973×862×302 973×862×302 973×862×302 1053×865×523 1053×865×523
Packed dimensions (W×H×D) mm 1025×910×410 1025×910×410 1025×910×410 1120×890×560 1120×890×560
Net weight kg 58 58 58 85 85
Space Saving Design Gross weight kg 63 63 63 92 92
Operating temperature range °C Cooling: -5 to 48

The VRF units are slimmer and more compact, resulting in significant savings in installation space.
In some large residential and light commercial areas, such as villas, restaurants, usually it need more than one indoor unit,
which in turn requires multiple outdoor units. VRF V4 Plus I Series - Heat Pump
Midea's VRF system solves this problem, and retains buildings' original aesthetics.

HP 7 8 10 14 16
Model MDV- V200W/DRN1 V224W/DRN1 V260W/DRN1 V400W/DRN1 V450W/DRN1
Power supply V/Ph/Hz 380-415/3/50
Cooling Capacity kW 20.0 22.4 26.0 40.0 45.0
Power input kW 6.1 6.8 7.6 11.9 13.6
EER 3.28 3.29 3.42 3.35 3.32
Heating Capacity kW 22.0 24.5 28.5 45.0 50.0
Power input kW 6.1 5.9 6.8 11.1 12.7
Auto Addressing Connectable
COP
Total capacity
3.61 4.15 4.19
50~130% of outdoor unit capacity
4.05 3.93

indoor unit Max. quantity 10 11 12 14 15


Outdoor unit can distribute addresses for indoor units automatically. Compressor Type DC inverter
Quantity 1 1 1 2 2
Wireless and wired controllers can query and modify each indoor unit's address. Fan motor Type DC motor DC motor+AC motor
Quantity 2 2 2 2 2
Refrigerant Type R410A
Factory charging kg 4.8 6.2 6.2 9 12
4 Pipe Liquid pipe mm Ф9.53 Ф9.53 Ф9.53 Ф12.7 Ф12.7
connections Gas pipe mm Ф19.1 Ф19.1 Ф22.2 Ф22.2 Ф25.4
Air flow rate m3/h 10999 10494 10494 16575 16575
3 Sound pressure level dB(A) 59 59 60 62 62
Net dimension (W×H×D) mm 1120×1558×528 1360×1650×540 1460×1650×540
5
Packing size (W×H×D) mm 1270×1720×565 1450×1785×560 1550×1785×560
Net weight kg 137 146.5 147 240 275
2 Gross weight kg 153 162.5 163 260 290
Operating temperature range °C Cooling: -15~46; Heating: -15~24 Cooling: -5~48; Heating: -15~24
1

Notes:
1. Indoor air temperature 27°C (80.6℉) DB, 19°C (66.2℉) WB; outdoor air temperature 35°C (95℉) DB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
2. Sound pressure level is measured at a position 1m (3.28ft.) in front of the unit and 1.3m (4.26ft.) above the floor in a semi-anechoic chamber.
6
3. For a system with more than one IDU, to ensure even distribution of refrigant, the capacity of each indoor unit should not exceed 8kW.
4. 60Hz model can be customized.

35 36
1 Generation
st

VRF INDOOR UNITS

One-way Cassette Fresh Air Processing Unit

Two-way Cassette Wall Mounted

Four-way Cassette Ceiling & Floor

Medium Static Pressure Duct Floor Standing

High Static Pressure Duct Console

37 38
One-way Cassette
Cassette Units Only 153mm high
The slim, compact design make the One-way Cassette ideal for interiors with 153mm UItra thin

limited ceiling space. Models 18 to 36 are just 153mm high whilst models 45 to
71 are 189mm high.

High-lift Drain Pump 750mm

One-way Cassette
A drain pump with a 750mm pump head is fitted as standard.
1st Generation VRF INDOOR UNITS

1st Generation VRF INDOOR UNITS


Fresh Air Intake
A reserved outside air intake port allows outdoor air to be introduced directly
into the unit, negating the need for a separate ventilation system.

Specifications
50Hz AC fan motors
Model MDV-D18Q1/N1-D MDV-D22Q1/N1-D MDV-D28Q1/N1-D MDV-D36Q1/N1-D MDV-D45Q1/N1-D MDV-D56Q1/N1-D MDV-D71Q1/N1-D
Power supply 1-phase,220-240V,50Hz
Cooling kW 1.8 2.2 2.8 3.6 4.5 5.6 7.1
Capacity
Two-way Cassette Heating kW 2.2 2.6 3.2 4.0 5.0 6.3 8.0
Cooling W 41 41 41 41 48 48 60
Power input
Heating W 41 41 41 41 48 48 60
Airflow rate(H/M/L) m3/h 523/404/275 523/404/275 573/456/315 573/456/315 693/600/476 792/688/549 933/749/592
Sound pressure level(H/M/L) dB(A) 37/34/30 38/34/30 39/37/34 40/38/34 41/39/35 42/40/36 44/41/37
Net dim.(W×H×D) mm 1054×153×425 1054×153×425 1054×153×425 1054×153×425 1275×189×450 1275×189×450 1275×189×450
Main body Packing dim.(W×H×D) mm 1155×245×490 1155×245×490 1155×245×490 1155×245×490 1370×295×505 1370×295×505 1370×295×505
Net/gross weight kg 12.5/16 12.5/16 13/16.5 13/16.5 18.5/22.8 18.8/23.1 19.5/23.8
Net dim.(W×H×D) mm 1180×25×465 1180×25×465 1180×25×465 1180×25×465 1350×25×505 1350×25×505 1350×25×505
Panel Packing dim.(W×H×D) mm 1232×107×517 1232×107×517 1232×107×517 1232×107×517 1410×95×560 1410×95×560 1410×95×560
Net/gross weight kg 3.5/5.2 3.5/5.2 3.5/5.2 3.5/5.2 4/5.4 4/5.4 4/5.4
Piping Liquid/gas pipe mm Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф9.53/Ф15.9 Ф9.53/Ф15.9
connections Drain pipe mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25
Standard controller Wireless remote controller
Compact Four-way Cassette
60Hz AC fan motors
Model MDV-D18Q1/VN1-D MDV-D22Q1/VN1-D MDV-D28Q1/VN1-D MDV-D36Q1/VN1-D MDV-D45Q1/VN1-D MDV-D56Q1/VN1-D MDV-D71Q1/VN1-D
Power supply 1-phase,208-230V,60Hz
kW 1.8 2.2 2.8 3.6 4.5 5.6 7.1
Cooling capacity
Btu/h 6100 7500 9600 12300 15400 19100 24200
kW 2.2 2.6 3.2 4.0 5.0 6.3 8.0
Heating capacity
Btu/h 7500 8900 10900 13600 17100 21500 27300
Cooling W 41 41 41 41 54 60 75
Power input
Heating W 41 41 41 41 54 60 75
m3/h 523/404/275 523/404/275 573/456/315 573/456/315 693/600/476 792/688/549 933/749/592
Airflow rate(H/M/L)
CFM 308/238/162 308/238/162 337/268/185 337/268/185 408/353/280 466/405/323 549/441/349
Sound pressure level(H/M/L) dB(A) 37/34/30 38/34/30 39/37/34 40/38/34 41/39/35 42/40/36 44/41/37
Net dim.(W×H×D) mm(in.) 1054×153×425(41-1/2×6-1/32×16-47/64) 1275×189×450(50-13/64×7-7/16×17-23/32)
Main body Packing dim.(W×H×D) mm(in.) 1155×245×490(45-15/32×9-41/64×19-19/64) 1370×295×505(53-15/16×11-39/64×19-7/8)
Four-way Cassette Net/gross weight kg(lbs.) 12.5/16(27.8/35.3) 13/16.5(28.8/36.4) 18.5/22.8(40.8/50.3) 18.8/23.1(41.4/50.9) 19.5/23.8(43.0/52.5)
Net dim.(W×H×D) mm(in.) 1180×25×465(46-29/64×63/64×18-5/16) 1350×25×505(53-5/32×63/64×19-7/8)
Panel Packing dim.(W×H×D) mm(in.) 1232×107×517(48-1/2×4-7/32×20-23/64) 1410×95×560(55-33/64×3-47/64×22-3/64)
Net/gross weight kg(lbs.) 3.5/5.2(7.7/11.5) 4/5.4(8.8/11.9)
Piping Liquid/gas pipe mm(in.) Ф6.35/Ф12.7(Ф1/4/Ф1/2) Ф9.53/Ф15.9(Ф3/8/Ф5/8)
connections Drain pipe mm(in.) Ф25(OD 63/64)
Standard controller Wireless remote controller
Notes:
1. Nominal capacities are based on the following conditions:
Auto Restart Auto Fresh Auto Easy-cleaning Follow Anti-cold Air Built-in Drain LED Built-in Independent Timer Auto Wired - Cooling: indoor temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor temperature 35°C (95.0°F) DB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
Function Addressing Air Defrosting Panel Me Function Pump Display Filter Dehumidification Swing Controller
- Heating: indoor temperature 20°C (68.0°F) DB; outdoor temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
2. Sound pressure level is measured 1.4m (4.59ft) below the unit in a semi-anechoic chamber.
3. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.

39 40
Two-way Cassette Four-way Cassette
Low Sound Level High-lift Drain Pump Multiple Options
The Two-way Cassette's optimized, low resistance air A drain pump with a 750mm pump head is fitted as stan- Three different versions of Four-way Cassette can be selected based on ceiling arrangements and user preference: Compact
outlets reduce noise levels to as low as 24dB(A). dard, simplifying installation of the drain piping. Higher Four-way Cassette, Four-way Cassette and Silent Four-way Cassette
pump heads are available as a customization option.
Stylish Design and Slim Body
A stylish design and slim body make the Two-way Cassette High Airflow Multiple Airflow Patterns
suited to any room's decor and ambience. At only 300mm A high airflow rate ensures even airflow and temperature Seven airflow patterns with up to four flow directions can selected to suit the requirements of the installation site or the shape
high, it can be installed in most ceiling spaces. throughout the room, even in high ceiling installations. of the room. Sub-ducts may also be connected.
1st Generation VRF INDOOR UNITS

1st Generation VRF INDOOR UNITS


305mm
300mm

Specifications
50Hz AC fan motors
Model MDV-D22Q2/N1 MDV-D28Q2/N1 MDV-D36Q2/N1 MDV-D45Q2/N1 MDV-D56Q2/N1 MDV-D71Q2/N1
Power supply 1-phase,220-240V,50Hz
Cooling kW 2.2 2.8 3.6 4.5 5.6 7.1
Capacity
Heating kW 2.6 3.2 4.0 5.0 6.3 8.0
Cooling W 57 57 60 92 108 154
Power input
Heating W 57 57 60 92 108 154
Airflow rate(H/M/L) m3/h 654/530/410 725/591/458 725/591/458 850/670/550 980/800/670 1200/1000/770
Sound pressure level(H/M/L) dB(A) 33/29/24 36/32/29 36/32/29 39/35/30 39/35/30 44/40/34
Net dim.(W×H×D) mm 1172×299×591 1172×299×591 1172×299×591 1172×299×591 1172×299×591 1172×299×591
Main body Packing dim.(W×H×D) mm 1355×400×675 1355×400×675 1355×400×675 1355×400×675 1355×400×675 1355×400×675
Net/gross weight kg 34/42.5 34/42.5 34/42.5 36/44.5 36/44.5 36/44.5 Sub Duct
Net dim.(W×H×D) mm 1430×53×680 1430×53×680 1430×53×680 1430×53×680 1430×53×680 1430×53×680
Panel Packing dim.(W×H×D) mm 1525×130×765 1525×130×765 1525×130×765 1525×130×765 1525×130×765 1525×130×765
Connecting a sub-duct enables an indoor unit to be used to also cool a smaller nearby space.
Net/gross weight kg 10.5/15 10.5/15 10.5/15 10.5/15 10.5/15 10.5/15
Liquid/gas pipe mm Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф9.53/Ф15.9 Ф9.53/Ф15.9
Piping connections
Drain pipe mm OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32
Standard controller Wireless remote controller

60Hz AC fan motors


Model MDV-D22Q2/VN1 MDV-D28Q2/VN1 MDV-D36Q2/VN1 MDV-D45Q2/VN1 MDV-D56Q2/VN1 MDV-D71Q2/VN1
Power supply 1-phase,208-230V,60Hz
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6 7.1 360° Airflow
Btu/h 7500 9600 12300 15400 19100 24200
kW 2.6 3.2 4.0 5.0 6.3 8.0
Heating capacity The Compact Four-way Cassette's 360° air outlets provide strong airflow circulation to cool or heat every corner of a room and
Btu/h 8900 10900 13600 17100 21500 27300
Power input
Cooling W 78 78 83 115 133 205 evenly control temperature.
Heating W 78 78 83 115 133 205
m3/h 674/509/381 740/577/435 740/577/435 878/689/561 941/776/654 1236/1110/864
Airflow rate(H/M/L)
CFM 397/300/224 436/340/256 436/340/256 517/406/330 554/457/385 727/653/509
Sound pressure level(H/M/L) dB(A) 33/29/24 36/32/29 36/32/29 39/35/30 39/35/30 44/40/34
Net dim.(W×H×D) mm(in.) 1172×299×591(46-9/32×11-49/64×23-17/64)
Main body Packing dim.(W×H×D) mm(in.) 1355×400×675(53-11/32×15-3/4×26-37/64)
Net/gross weight kg(lbs.) 34/42.5(75/94) 36/44.5 (79.2/97.9)
Net dim.(W×H×D) mm(in.) 1430×53×680(56-19/64×2-3/32×26-49/64)
Panel Packing dim.(W×H×D) mm(in.) 1525×130×765(60-3/64×5-1/8×30-1/8)
Net/gross weight kg(lbs.)
Ф6.35/Ф12.7(Ф1/4/Ф1/2)
10.5/15(23/33)
Ф9.53/Ф15.9(Ф3/8/Ф5/8)
High-lift Drain Pump
Liquid/gas pipe mm(in.)
Piping connections
Drain pipe mm(in.) Ф32(OD 1-17/64) A drain pump with a 500mm pump head is fitted as standard to the Compact Four-way Cassette. Higher pump heads (of up to
Standard controller Wireless remote controller
Notes: 600mm) are available as a customization option. On the Four-way Cassette and Silent Four-way Cassette a drain pump with a
1. Nominal capacities are based on the following conditions:
- Cooling: indoor temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor temperature 35°C (95.0°F) DB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
750mm pump head is fitted as standard, simplifying installation of the drain piping.
- Heating: indoor temperature 20°C (68.0°F) DB; outdoor temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
2. Sound pressure level is measured 1.4m (4.59ft) below the unit in a semi-anechoic chamber.
3. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.

41 42
Compact Four-way Cassette (50Hz AC fan motors)
Model MDV-D80Q4/N1-E MDV-D90Q4/N1-E MDV-D100Q4/N1-E MDV-D112Q4/N1-E MDV-D140Q4/N1-E
Model MDV-D22Q4/N1-A3 MDV-D28Q4/N1-A3 MDV-D36Q4/N1-A3 MDV-D45Q4/N1-A3 Power supply 1-phase,220-240V,50Hz
Power supply 1-phase,220-240V,50Hz
Cooling kW 8.0 9.0 10.0 11.2 14.0
Cooling kW 2.2 2.8 3.6 4.5 Capacity
Capacity Heating kW 9.0 10.0 11.1 12.5 16.0
Heating kW 2.4 3.2 4.0 5.0 Cooling W 110 140 165 165 176
Cooling W 50 50 56 56 Power input
Power input Heating W 110 140 165 165 176
Heating W 50 50 56 56
Airflow rate(H/M/L) m3/h 1200/1021/789 1332/1129/908 1651/1304/1127 1651/1304/1127 1658/1335/1130
Airflow rate(H/M/L) m3/h 414/313/238 414/313/238 521/409/314 521/409/314
Sound pressure level(H/M/L) dB(A) 42/39/37 43/39/38 45/42/40 45/42/40 46/41/39
Sound pressure level(H/M/L) dB(A) 36/33/23 36/33/23 42/36/29 42/36/29 Net dim.(W×H×D) mm 840×230×840 840×300×840 840×300×840 840×300×840 840×300×840
Net dim.(W×H×D) mm 570×260×570 570×260×570 570×260×570 570×260×570 Main body Packing dim.(W×H×D) mm 955×260×955 955×330×955 955×330×955 955×330×955 955×330×955
Main body Packing dim.(W×H×D) mm 675×285×675 675×285×675 675×285×675 675×285×675 Net/gross weight kg 23.7/28.9 28.7/34.1 28.7/34.1 28.7/34.1 30.9/36.3
1st Generation VRF INDOOR UNITS

1st Generation VRF INDOOR UNITS


Net/gross weight kg 16/20 16/20 18/22 18/22 Net dim.(W×H×D) mm 950×54.5×950 950×54.5×950 950×54.5×950 950×54.5×950 950×54.5×950
Net dim.(W×H×D) mm 647×50×647 647×50×647 647×50×647 647×50×647 Panel Packing dim.(W×H×D) mm 1035×90×1035 1035×90×1035 1035×90×1035 1035×90×1035 1035×90×1035
Panel Packing dim.(W×H×D) mm 715×123×715 715×123×715 715×123×715 715×123×715 Net/gross weight kg 6/9 6/9 6/9 6/9 6/9
Net/gross weight kg 2.5/4.5 2.5/4.5 2.5/4.5 2.5/4.5 Liquid/gas pipe mm Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9
Liquid/gas pipe mm Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Piping connections
Piping connections Drain pipe mm OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32
Drain pipe mm OD Ф25 OD Ф25 OD Ф25 OD Ф25
Standard controller Wireless remote controller
Standard controller Wireless remote controller
Four-way Cassette (60Hz AC fan motors)
Compact Four-way Cassette (60Hz AC fan motors) Model MDV-D28Q4/VN1-E MDV-D36Q4/VN1-E MDV-D45Q4/VN1-E MDV-D56Q4/VN1-E MDV-D71Q4/VN1-E
Power supply 1-phase,208-230V,60Hz
Model MDV-D22Q4/VN1-A3 MDV-D28Q4/VN1-A3 MDV-D36Q4/VN1-A3 MDV-D45Q4/VN1-A3
kW 2.8 3.6 4.5 5.6 7.1
Power supply 1-phase,208-230V,60Hz Cooling capacity
Btu/h 9600 12300 15400 19100 24200
kW 2.2 2.8 3.6 4.5
Cooling capacity kW 3.2 4.0 5.0 6.3 8.0
Btu/h 7500 9600 12300 15400 Heating capacity
Btu/h 10900 13600 17100 21500 27300
kW 2.4 3.2 4.0 5.0
Heating capacity Cooling W 80 80 88 88 105
Btu/h 8200 10900 13600 17100 Power input
Heating W 80 80 88 88 105
Cooling W 50 50 60 60
Power input m3/h 791/674/596 791/674/596 942/777/662 942/777/662 1235/1013/805
Heating W 50 50 60 60 Airflow rate(H/M/L)
CFM 465/396/351 465/396/351 554/457/389 554/457/389 726/596/474
m3/h 397/292/215 408/310/231 496/359/263 496/359/263
Airflow rate(H/M/L) Sound pressure level(H/M/L) dB(A) 30/25/22 30/25/22 35/31/27 35/31/27 43/37/31
CFM 234/172/127 240/182/136 292/211/155 292/211/155
Net dim.(W×H×D) mm(in.) 840×230×840(33-1/16×9-1/16×33-1/16)
Sound pressure level(H/M/L) dB(A) 36/33/23 36/33/23 42/36/29 42/36/29 Main body Packing dim.(W×H×D) mm(in.) 955×260×955(37-19/32×10-1/4×37-19/32)
Net dim.(W×H×D) mm(in.) 570×260×570(22-7/16×10-15/64×22-7/16)
Net/gross weight kg(lbs.) 21.5/26.7(47.3/58.7) 23.7/28.9(52.1/63.6)
Main body Packing dim.(W×H×D) mm(in.) 675×285×675(26-9/16×11-7/32×26-9/16)
Net dim.(W×H×D) mm(in.) 950×54.5×950(37-13/32×2-9/64×37-13/32)
Net/gross weight kg(lbs.) 16/20(35.3/44.1) 18/22(39.7/48.5)
Panel Packing dim.(W×H×D) mm(in.) 1035×90×1035(40-3/4×3-9/16×40-3/4)
Net dim.(W×H×D) mm(in.) 647×50×647(25-15/32×1-31/32×25-15/2)
Net/gross weight kg(lbs.) 6/9(13.2/19.8)
Panel Packing dim.(W×H×D) mm(in.) 715×123×715(28-5/32×4-27/32×28-5/32 )
Liquid/gas pipe mm(in.) Φ6.35/Φ12.7(Φ1/4/Φ1/2) Ф9.53/Ф15.9(Ф3/8/Ф5/8)
Net/gross weight kg(lbs.) 2.5/4.5(5.5/9.9) Piping connections
Drain pipe mm(in.) Ф32(OD 1-17/64)
Liquid/gas pipe mm(in.) Ф6.35/Ф12.7(Ф1/4/Ф1/2)
Piping connections Standard controller Wireless remote controller
Drain pipe mm(in.) Ф25(OD 63/64)
Standard controller Wireless remote controller
Model MDV-D80Q4/VN1-E MDV-D90Q4/VN1-E MDV-D100Q4/VN1-E MDV-D112Q4/VN1-E MDV-D140Q4/VN1-E
Four-way Cassette (50Hz AC fan motors) Power supply
kW 8.0 9.0
1-phase,208-230V,60Hz
10.0 11.2 14.0
Cooling capacity
Model MDV-D28Q4/N1-E MDV-D36Q4/N1-E MDV-D45Q4/N1-E MDV-D56Q4/N1-E MDV-D71Q4/N1-E Btu/h 27300 30700 34100 38200 47800
Power supply 1-phase,220-240V,50Hz kW 9.0 10.0 11.1 12.5 16.0
Heating capacity
Cooling kW 2.8 3.6 4.5 5.6 7.1 Btu/h 30700 34100 37900 42700 54600
Capacity Cooling W 120 187 200 200 220
Heating kW 3.2 4.0 5.0 6.3 8.0 Power input
Heating W 120 187 200 200 220
Cooling W 80 80 88 88 88 m3/h 1235/1013/805 1333/1158/957 1634/1219/1139 1634/1219/1139 1692/1243/1157
Power input Airflow rate(H/M/L)
Heating W 80 80 88 88 88 CFM 726/596/474 784/681/563 961/717/670 961/717/670 995/731/681
Airflow rate(H/M/L) 764/638/554 764/638/554 905/740/651 905/740/651 950/767/663 Sound pressure level(H/M/L) dB(A) 43/37/31 43/38/32 45/37/35 45/37/35 46/38/37
m3/h
Net dim.(W×H×D) mm(in.) 840×230×840(33-1/16 840×300×840(33-1/16×11-13/16×33-1/16)
Sound pressure level(H/M/L) dB(A) 32/31/30 32/31/30 36/34/33 36/34/33 38/36/35 ×9-1/16×33-1/16)
Net dim.(W×H×D) mm 840×230×840 840×230×840 840×230×840 840×230×840 840×230×840 Main body Packing dim.(W×H×D) mm(in.) 955×260×955(37-19/32 955×330×955(37-19/32×11-13/16×37-19/32)
×10-15/64×37-19/32)
Main body Packing dim.(W×H×D) mm 955×260×955 955×260×955 955×260×955 955×260×955 955×260×955 Net/gross weight kg(lbs.) 23.7/28.9(52.1/63.6) 28.7/34.1(63.1/75) 30.9/36.3(68/79.9)
Net/gross weight kg 21.5/26.7 21.5/26.7 23.7/28.9 23.7/28.9 23.7/28.9 Net dim.(W×H×D) mm(in.) 950×54.5×950(37-13/32×2-9/64×37-13/32)
Panel Packing dim.(W×H×D) mm(in.) 1035×90×1035(40-3/4×3-35/64×40-3/4)
Net dim.(W×H×D) mm 950×54.5×950 950×54.5×950 950×54.5×950 950×54.5×950 950×54.5×950
Net/gross weight kg(lbs.) 6/9(13.2/19.8)
Panel Packing dim.(W×H×D) mm 1035×90×1035 1035×90×1035 1035×90×1035 1035×90×1035 1035×90×1035 Liquid/gas pipe mm(in.) Ф9.53/Ф15.9(Ф3/8/Ф5/8)
Piping connections
Net/gross weight kg 6/9 6/9 6/9 6/9 6/9 Drain pipe mm(in.) Ф32(OD 1-17/64)
Liquid/gas pipe mm Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Standard controller Wireless remote controller
Piping connections
Drain pipe mm OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32 Notes:
Standard controller Wireless remote controller 1. Nominal capacities are based on the following conditions:
- Cooling: indoor temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor temperature 35°C (95.0°F) DB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
- Heating: indoor temperature 20°C (68.0°F) DB; outdoor temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
2. Sound pressure level is measured 1.4m (4.59ft) below the unit in a semi-anechoic chamber.
3. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.

43 44
Medium Static Pressure Duct Model
Power supply
MDV-D71T2/N1-DA5 MDV-D80T2/N1-BA5 MDV-D90T2/N1-BA5
1-phase,220-240V,50Hz
MDV-D112T2/N1-BA5 MDV-D140T2/N1-BA5

Compact Design Capacity


Cooling kW 7.1 8.0 9.0 11.2 14.0
Heating kW 8.0 9.0 10.0 12.5 15.5
Models 22 to 71 are just 210mm high whilst models 80 to 112 are 270mm high and model 140 is 300mm high.
Cooling W 140 198 200 313 274
Power input
Heating W 140 198 200 313 274
Min.5mm
Airflow rate(H/M/L) m /h
3 1029/934/781 1345/1165/1013 1345/1165/1013 1800/1556/1400 1905/1636/1400
External static pressure(Min/Std/Max) Pa 0/10/30 10/20/50 10/20/50 10/40/80 10/40/100
210mm
Sound pressure level(H/M/L) dB(A) 41/39/35 45/40/37 45/40/37 48/42/38 48/43/39
or 270mm
or 300mm Net dimension(W×H×D) mm 1220×210×500 1230×270×775 1230×270×775 1230×270×775 1290×300×865
Packing dimension(W×H×D) mm 1335×285×525 1355×350×795 1355×350×795 1355×350×795 1400×375×925
1st Generation VRF INDOOR UNITS

1st Generation VRF INDOOR UNITS


Ceiling Net/gross weight kg 28/31.5 38/46.5 40/48 40/48 49/58
Liquid/gas pipe mm Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9
High-lift Drain Pump Piping connections
Drain pipe mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25
Standard controller Wired controller
A drain pump with a 750mm pump head is fitted as standard, simplifying installation of the drain piping.
60Hz AC fan motors
Easy Maintenance Access, Flexible Control
Model MDV-D22T2/VN1-DA5 MDV-D28T2/VN1-DA5 MDV-D36T2/VN1-DA5 MDV-D45T2/VN1-DA5 MDV-D56T2/VN1-DA5
As a customization option, for ease of access the electric control box can be separated from the unit by up to 1m. Functional Power supply 1-phase,208-230V,60Hz
ports including remote on/off dry contact and 220V alarm signal output are included as standard, providing control flexibility. Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6
Btu/h 7500 9600 12300 15400 19100
kW 2.6 3.2 4.0 5.0 6.3
Flexibility Heating capacity
Btu/h 8900 10900 13600 17100 21500
Cooling W 66 72 77 100 100
To provide the flexibility to adapt to differing installation situations, the air inlet may be positioned either on the underside or Power input
Heating W 66 72 77 100 100
the rear of the unit. m3/h 538/456/375 538/456/375 597/514/429 811/684/575 811/684/575
Airflow rate(H/M/L)
CFM 317/268/221 317/268/221 351/303/253 477/403/338 477/403/338
External static pressure(Min/Std/Max) Pa 0/10/30 0/10/30 0/10/30 0/10/30 0/10/30
Air intake Air intake
Sound pressure level(H/M/L) dB(A) 36/35/32 36/35/32 39/38/34 39/38/34 39/38/34
from rear from below
Net dimension(W×H×D) mm(in.) 780×210×500(30-45/64×8-17/64×19-11/16) 1000×210×500(39-3/8×8-17/64×19-11/16)
Packing dimension(W×H×D) mm(in.) 870×285×525(34-1/4×11-7/32×20-43/64) 1115×285×525(43-57/64×11-7/32×20-43/64)
Net/gross weight kg(lbs.) 17.5/20(38.6/44.1) 22.5/26(49.6/57.3)
Liquid/gas pipe mm(in.) Ф6.35/Ф12.7(Ф1/4/Ф1/2) Ф9.53/Ф15.9(Ф3/8/Ф5/8)
Piping connections
Drain piping mm(in.) Ф25(OD 63/64)
Standard controller Wired controller
Auto Restart Auto Fresh Auto Built-in Follow Anti-cold Air Built-in Drain Timer Independent Wired Super High
Function Addressing Air Defrosting Filter Me Function Pump Dehumidification Controller Air Flow
Model MDV-D71T2/VN1-DA5 MDV-D80T2/VN1-BA5 MDV-D90T2/VN1-BA5 MDV-D112T2/VN1-BA5 MDV-D140T2/VN1-BA5

Specifications
Power supply 1-phase,208-230V,60Hz
kW 7.1 8.0 9.0 11.2 14.0
Cooling capacity
Btu/h 24200 27300 30700 38200 47800
50Hz AC fan motors Heating capacity
kW 8.0 9.0 10.0 12.5 15.5
Btu/h 27300 30700 34100 42700 52900
Model MDV-D22T2/N1-DA5 MDV-D28T2/N1-DA5 MDV-D36T2/N1-DA5 MDV-D45T2/N1-DA5 MDV-D56T2/N1-DA5 Cooling W 125 133 134 378 352
Power input
Power supply 1-phase,220-240V,50Hz Heating W 125 133 134 378 352
Cooling kW 2.2 2.8 3.6 4.5 5.6 m3/h 1029/934/781 1345/1165/1013 1345/1165/1013 1800/1556/1400 1905/1636/1400
Airflow rate(H/M/L)
Capacity CFM 606/550/460 792/686/596 792/686/596 1059/916/824 1121/963/824
Heating kW 2.6 3.2 4.0 5.0 6.3
External static pressure(Min/Std/Max) Pa 0/10/30 10/20/50 10/20/50 10/40/80 10/40/100
Cooling W 57 57 61 98 103 Sound pressure level(H/M/L) dB(A) 41/39/35 45/40/37 45/40/37 48/42/38 48/43/39
Power input
1220×210×500 1290×300×865(50-25/32×
Heating W 57 57 61 98 103 Net dimension(W×H×D) mm(in.) 1230×270×775(48-27/64×10-5/8×30-33/64)
(48-1/32×8-17/64×19-11/16) 11-13/16×34-1/16)
Airflow rate(H/M/L) m/h
3 538/456/375 538/456/375 597/514/429 811/684/575 811/684/575 1335×285×525(52-9/16× 1400×375×925(55-1/8×14-
Packing dimension(W×H×D) mm(in.) 1355×350×795(53-11/32×13-25/31×31-19/64)
External static pressure(Min/Std/Max) Pa 0/10/30 0/10/30 0/10/30 0/10/30 0/10/30 11-7/32×20-43/64) 49/64×36-27/64)
Net/gross weight kg(lbs.) 28/31.5(61.8/69.5) 38/46.5(84/102.5) 40/48(88.2/105.8) 49/58(108.0/127.9)
Sound pressure level(H/M/L) dB(A) 36/35/32 37/35/32 39/38/34 39/38/34 39/38/34
Liquid/gas pipe mm(in.) Ф9.53/Ф15.9(Ф3/8/Ф5/8)
Net dimension(W×H×D) mm 780×210×500 780×210×500 780×210×500 1000×210×500 1000×210×500 Piping connections
Drain piping mm(in.) Ф25(OD 63/64)
Packing dimension(W×H×D) mm 870×285×525 870×285×525 870×285×525 1115×285×525 1115×285×525 Standard controller Wired controller

Net/gross weight kg 17.5/20 17.5/20 17.5/20 22.5/26 22.5/26 Notes:


1. Nominal capacities are based on the following conditions:
Liquid/gas pipe mm Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф9.53/Ф15.9 - Cooling: indoor temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor temperature 35°C (95.0°F) DB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
Piping connections
Drain pipe mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 - Heating: indoor temperature 20°C (68.0°F) DB; outdoor temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
2. Sound pressure level is measured 1.4m (4.59ft) below the unit in a semi-anechoic chamber.
Standard controller Wired controller
3. External static pressure is based on high speed indoor airflow.
4. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.

45 46
Specifications
High Static Pressure Duct
50Hz AC fan motors
Flexible Duct Design Model MDV-D71T1/N1-B MDV-D80T1/N1-B MDV-D90T1/N1-B MDV-D112T1/N1-B MDV-D140T1/N1-B MDV-D160T1/N1-B

The High Static Pressure Duct indoor unit offers external static pressures of up to 196Pa (models 71 to 160) or 280Pa Power supply 1-phase,220-240V,50Hz
(models 200 to 560). With a height of just 420mm (models 71 to 160), only 450mm of ceiling space is required.
Cooling kW 7.1 8.0 9.0 11.2 14.0 16.0
Capacity
Heating kW 8.0 9.0 10.0 12.5 16.0 17.0

Cooling W 263 263 423 524 724 940


Power input
1st Generation VRF INDOOR UNITS

1st Generation VRF INDOOR UNITS


Air return
Min. Heating W 263 263 423 524 724 940
420mm
INDOOR UNIT 450mm
Airflow rate(H/M/L) m3/h 1443/1361/1218 1416/1338/1220 1951/1741/1518 2116/1936/1520 3000/2618/2226 3620/3044/2744
Air supply Excellent coverage of rooms
up to 6.5m in height External static pressure(Min/Std/Max) Pa 25/25/196 37/37/196 37/37/196 50/50/196 50/50/196 50/50/196
INDOOR UNIT

Sound pressure level(H/M/L) dB(A) 48/46/44 48/46/45 52/49/47 52/49/47 53/50/48 54/52/50

Net dimension(W×H×D) mm 952×420×690 952×420×690 952×420×690 952×420×690 1300×420×690 1300×420×690

Double-skin Drainage Pan Drain Pumpn Packing dimension(W×H×D) mm 1090×440×768 1090×440×768 1090×440×768 1090×440×768 1436×450×768 1436×450×768

Net/gross weight kg 45/50 45/50 46.5/52.4 50.6/56 68/70 70/77.5


A double-skin drainage pan provides double protection for A drain pump with a 750mm pump head is available
ceilings (models 71 to 160 and models 400 to 560). as a customization option (models 71 to 160). Liquid/gas pipe mm Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9
Piping connections
Drain pipe mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25

Standard controller Wired controller


750mm

Model MDV-D200T1/N1-B MDV-D250T1/N1-B MDV-D280T1/N1-B MDV-D400T1/N1 MDV-D450T1/N1 MDV-D560T1/N1

Ceiling Power supply 1-phase,220-240V,50Hz

Cooling kW 20.0 25.0 28.0 40.0 45.0 56.0


Capacity
Heating kW 22.5 26.0 31.5 45.0 50.0 63.0

Easy Installation Power input


Cooling W 1516 1516 1516 2700 2700 3400

Heating W 1516 1516 1516 2700 2700 3400


Flanges for air inlet/outlet ducts are fitted as standard on the High Static Pressure Duct. On models 71 to 160, the expansion
valve is fitted inside the unit, requiring no extra connection. Airflow rate(H/M/L) m3/h 4700/4100/3599 4700/4100/3599 4700/4100/3599 7472/6072/4995 7472/6072/4995 9550/7950/6600

External static pressure(Min/Std/Max) Pa 50/200/280 50/200/280 50/200/280 50/200/280 50/200/280 50/200/280

Easy Maintenance Access, Flexible Control Sound pressure level(H/M/L) dB(A) 59/55/52 59/55/52 59/55/52 61/59/56 61/59/56 63/60/57

The wired remote controller is provided as standard and the wireless remote controller is available as a customization option. Net dimension(W×H×D) mm 1440×505×925 1440×505×925 1440×505×925 1970×668×902.5 1970×668×902.5 1970×668×902.5

Functional ports including remote on/off dry contact are included as standard, providing additional control flexibility. For ease Packing dimension(W×H×D) mm 1509×550×990 1509×550×990 1509×550×990 2095×800×964 2095×800×964 2095×800×964
of installation, the electric control box's display board is factory-fitted and the filter can be accessed either from the rear of from
Net/gross weight kg 115/129 115/129 115/129 232/245 232/245 235/250
below.
Liquid/gas pipe mm Ф9.53×2/Ф15.9×2 Ф9.53×2/Ф15.9×2 Ф9.53×2/Ф15.9×2 Ф9.53×2/Ф22.2×2 Ф9.53×2/Ф22.2×2 Ф9.53×2/Ф22.2×2
Piping connections
Drain pipe mm OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32

Standard controller Wired controller


Auto Restart Auto Independent Auto Built-in Follow Anti-cold Air Wired Timer Built-in Drain
Function Addressing Dehumidification Defrosting Filter Me Function Controller Pump Notes:
1. Nominal capacities are based on the following conditions:
- Cooling: indoor temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor temperature 35°C (95.0°F) DB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
- Heating: indoor temperature 20°C (68.0°F) DB; outdoor temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
2. Sound pressure level is measured 1.4m (4.59ft) below the unit in a semi-anechoic chamber.
3. External static pressure is based on high speed indoor airflow.
4. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.

47 48
60Hz AC fan motors
Model
Fresh Air Processing Unit
Power supply
MDV-D71T1/VN1-B MDV-D80T1/VN1-B MDV-D901T1/VN1-B MDV-D112T1/VN1-B MDV-D140T1/VN1-B MDV-D160T1/VN1-B
1-phase,208-230V,60Hz
Fan Motor Options
Choose either AC or DC fan motors.
kW 7.1 8 9 11.2 14 15
Cooling capacity
Btu/h 24200 27300 30700 38200 47800 51200
100% Fresh Air Processing Unit
kW 8 9 10 12.5 16 16.5
Heating capacity
Btu/h 27300 30700 34100 42700 54600 56300
Both fresh air filtration and heating/cooling can be achieved in a single system.
Fresh air

Cooling W 414 402 409 409 527 532


Indoor units and the Fresh Air Processing Unit can be connected to the same
INDOOR UNIT
Power input
Heating W 414 402 409 409 527 532 refrigerant system, increasing design flexibility and greatly reducing total system Excellent coverage of rooms
Air supply
up to 6.5m in height
costs.
1st Generation VRF INDOOR UNITS

1st Generation VRF INDOOR UNITS


m3/h 1720/1532/1338 1690/1560/1320 2252/2030/1610 2198/1978/1570 2969/2694/2469 2969/2694/2469
Airflow rate(H/M/L)
CFM 1012/902/788 994/918/777 1326/1195/948 1294/1164/924 1746/1586/1453 1746/1586/1453 Flexible Duct Design
External static pressure(Min/Std/Max) Pa 25/25/196 37/37/196 37/37/196 50/50/196 50/50/196 50/50/196
The Fresh Air Processing unit offers external static pressures of up to 196Pa (models 125 to 140) or 280Pa (models 200 to 280).
Sound pressure level(H/M/L) dB(A) 48/46/45 48/46/45 52/49/47 52/49/47 53/50/48 54/52/50

Net dimension(W×H×D) mm(in.) 952×420×690(37-31/64×16-17/32×27-11/64) 1300×420×690(51-3/16×15-3/4×27-5/32) The Comfort of Fresh Air


Enjoy the comfort and health benefits of fresh air being drawn into your working or living environment.
Packing dimension(W×H×D) mm(in.) 1090×440×768(42-29/32×17-21/64×30-15/64) 1436×450×768(56-17/32×17-23/32×30-15/64)

Net/gross weight kg(lbs.) 46.5/52(102.6/114.7) 50/56.5(110.3/124.6) 68/70(149.9/154.3) 69.5/76(153.3/167.6)


Auto Restart Auto Independent Auto Built-in Follow Anti-cold Air Wired Timer Built-in Drain
Liquid/gas pipe mm(in.) Ф9.53/Ф15.9(Ф3/8/Ф5/8) Function Addressing Dehumidification Defrosting Filter Me Function Controller Pump
Piping connections

Specifications
Drain piping mm(in.) Ф25(OD 63/64)

Standard controller Wired controller


50Hz AC fan motors
Model MDV-D200T1/N1-B MDV-D250T1/N1-B MDV-D280T1/N1-B MDV-D400T1/N1 MDV-D450T1/N1 Model MDV-D125T1/N1-FA MDV-D140T1/N1-FA MDV-D200T1/N1-FA MDV-D250T1/N1-FA MDV-D280T1/N1-FA
Power supply 1-phase,220-240V,50Hz
Power supply 1-phase,208-230V,60Hz
Cooling kW 12.5 14.0 20.0 25.0 28.0
Capacity
kW 20.0 25.0 28.0 40.0 45.0 Heating kW 10.5 12.0 18.0 20.0 22.0
Cooling capacity Cooling W 455 455 1060×2 1126×2 1126×2
Btu/h 68200 85300 95500 136500 153500 Power input
Heating W 455 455 1060×2 1126×2 1126×2
kW 22.5 26.0 31.5 45.0 50.0 Airflow rate(H/M/L) 2142/1870/1611 2142/1870/1611 2870/2620/2150 3005/2700/2250 3005/2700/2250
Heating capacity m3/h
Btu/h 76800 88700 107500 153500 170600 External static pressure(Min/Std/Max) Pa 30/50/196 30/50/196 50/200/280 50/200/280 50/200/280
Sound pressure level(H/M/L) dB(A) 54/52/50 54/52/50 54/53/51 55/54/52 55/54/52
Cooling W 1516 1516 1516 1600 1600
Power input Net dimension(W×H×D) mm 1300×420×690 1300×420×690 1440×505×925 1440×505×925 1440×505×925
Heating W 1516 1516 1516 1600 1600 Packing dimension(W×H×D) mm 1436×450×768 1436×450×768 1509×550×990 1509×550×990 1509×550×990
Net/gross weight kg 69.5/76 69.5/76 115/125 115/125 115/125
m3/h 4700/4100/3599 4700/4100/3599 4700/4100/3599 7180/6150/4600 7180/6150/4600
Airflow rate(H/M/L) Liquid/gas pipe mm Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9
Piping connections
CFM 2766/2413/2118 2766/2413/2118 2766/2413/2118 4226/3620/2708 4226/3620/2708 Drain pipe mm OD Ф25 OD Ф25 OD Ф32 OD Ф32 OD Ф32
External static pressure(Min/Std/Max) Pa 50/200/280 50/200/280 50/200/280 50/200/280 50/200/280 Operation temperature range °C Heating: -5~16; Fan only: 16~20; Cooling: 20~43
Standard controller Wired controller
Sound pressure level(H/M/L) dB(A) 59/55/52 59/55/52 59/55/52 61/59/56 61/59/56
60Hz AC fan motors
Net dimension(W×H×D) mm(in.) 1440×505×925(56-11/16×19-7/8×36-27/6) 1970×668×902.5(77-9/16×15-3/4×35-17/32) Model MDV-D125T1/VN1-FA MDV-D140T1/VN1-FA MDV-D200T1/VN1-FA MDV-D250T1/VN1-FA MDV-D280T1/VN1-FA
Power supply 1-phase,208-230V,60Hz
kW 12.5 14.0 20.0 25.0 28.0
Cooling capacity
Packing dimension(W×H×D) mm(in.) 1509×550×990(59-13/32×21-21/32×38-31/32) 2095×800×964(82-31/64×31-1/2×37-61/64) Btu/h 42600 47800 68200 85300 95500
kW 10.5 12.0 18.0 20.0 22.0
Heating capacity
Btu/h 36000 41000 61400 68200 75000
Net/gross weight kg(lbs.) 115/129(254/284) 235/250(518/551) Cooling W 455 455 1060×2 1126×2 1126×2
Power input
Liquid/gas pipe mm(in.) Ф9.53/Ф15.9×2/(Ф3/8/Ф5/8)×2 Ф9.53/Ф22.2×2/(Ф3/8/Ф7/8)×2 Heating W 455 455 1060×2 1126×2 1126×2
Piping connections m3/h 2142/1870/1611 2142/1870/1611 2870/2620/2150 3005/2700/2250 3005/2700/2250
Drain piping mm(in.) Ф32(OD 1-17/64) Airflow rate(H/M/L)
CFM 1261/1101/948 1261/1101/948 1689/1542/1265 1766/1589/1324 1766/1589/1324
Notes: External static pressure(Min/Std/Max) Pa 30/50/196 30/50/196 50/200/280 50/200/280 50/200/280
Standard controller Wired controller
1. Nominal capacities are based on the following conditions: Sound pressure level(H/M/L) dB(A) 54/52/50 54/52/50 54/53/51 55/54/52 55/54/52
- Cooling: indoor temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor temperature 35°C (95.0°F) DB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
Net dimension(W×H×D) mm(in.) 1300×420×690(51-3/16×16-17/32×27-11/64) 1440×505×925(56-11/16×19-7/8×36-27/6)
- Heating: indoor temperature 20°C (68.0°F) DB; outdoor temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
Packing dimension(W×H×D) mm(in.) 1436×450×768(56-17/32×17-23/32×30-1/4) 1509×550×990(59-13/32×21-21/32×38-31/32)
2. Sound pressure level is measured 1.4m (4.59ft) below the unit in a semi-anechoic chamber.
Net/gross weight kg(lbs.) 69.5/76(153.2/167.5) 114/124(251/274)
3. External static pressure is based on high speed indoor airflow.
Liquid/gas pipe mm(in.) Ф9.53/Ф15.9/(Ф3/8/Ф5/8)
4. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments. Piping connections
Drain piping mm(in.) Ф25(OD 63/64) Ф32(OD 1-17/64)
Standard controller Wired controller
Notes:
1. Nominal capacities are based on the following conditions:
- Cooling: outdoor temperature 33°C (91.4°F) DB, 24°C (75.2°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
- Heating: outdoor temperature 0°C (32°F) DB, -1°C (30.2°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
2. Sound pressure level is measured 1.4m (4.59ft) below the unit in a semi-anechoic chamber.
3. External static pressure is based on high speed indoor airflow.
4. The Fresh Air Processing Unit can be used either independently or in conjunction with other types of indoor unit. If used independently, the total capacity of the Fresh Air
Processing Units must be between 50% and 100% of that of the outdoor units. If used in conjunction with other types of indoor unit, the total capacity of the Fresh Air
Processing Units must not exceed 30% of that of the outdoor units.
49 5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
50
Specifications
Wall Mounted
M Series M Series (DC fan motors)
Model MI-22G/DHN1-M MI-28G/DHN1-M MI-36G/DHN1-M MI-45G/DHN1-M

Power supply 1-phase,220-240V,50/60Hz


M9 M10
Cooling kW 2.2 2.8 3.6 4.5
Capacity
Heating kW 2.4 3.2 4 5

Cooling W 8 9 19 19
1st Generation VRF INDOOR UNITS

1st Generation VRF INDOOR UNITS


Power input
Heating W 8 9 19 19

Airflow rate (H/M/L) m³/h 422/393/356 417/370/316 656/573/488 594/507/424

Sound pressure level (H/M/L) dB(A) 31/30/29 31/30/29 33/32/30 35/33/31


Auto Restart Auto Timer Auto Easy-cleaning Follow Anti-cold Air Auto LED Built-in Independent Wired
Function Addressing Defrosting Panel Me Function Swing Display Filter Dehumidification Controller
Net dimension (W×H×D) mm 835×280×203 835×280×203 990×315×223 990×315×223

Multiple Options High Efficiency, Low Sound Level Packing dimension (W×H×D) mm 935×385×320 935×385×320 1085×420×335 1085×420×335

The elegant new M Series units enhance the aesthetics Advanced brushless DC fan motors in M Series units operate Net/ Gross weight kg 8.4/12.1 9.5/13.1 11.4/15.5 12.8/16.9

of any room and are suitable for a wide variety of instal- highly efficiently without generating excessive noise, saving Liquid/gas pipe mm Ф6.35/Ф12.7
lation space situations. Interchangeable panels (M9, energy at the same time as providing a low-noise work or living Piping connections
Drain pipe mm OD Ф16.5
M10) add extra flexibility to a universal body design. space.
Standard controller Wireless remote controller

Auto Swing Louver Flexibility


Model MI-56G/DHN1-M MI-71G/DHN1-M MI-80G/DHN1-M MI-90G/DHN1-M
Multiple louver positions and the auto swing ensure To increase installation flexibility, the expansion valve is fitted
Power supply 1-phase,220-240V,50/60Hz
precise and flexible airflow control. internally, increasing compactness, and the refrigerant outlet
direction can be left, right or rear as the installation situation Cooling kW 5.6 7.1 8 9
requires. A new fixing plate design speeds installation and Capacity
Heating kW 6.3 8 9 10
provides extra stability.
1
Cooling `W 27 49 53 82
2
Power input
Heating W 27 49 53 82
Step 3

Swing 4
Airflow rate (H/M/L) m³/h 747/648/547 1195/1005/809 1195/1005/809 1421/1067/867
Rear
Left Right
Sound pressure level (H/M/L) dB(A) 38/36/34 44/39/36 44/39/36 48/43/38

Dimension (W×H×D) mm 990×315×223 1194×343×262 1194×343×262 1194×343×262


Optimal Comfort Through Better Flow Control
Packing (W×H×D) mm 1085×420×335 1290×375×460 1290×375×460 1290×375×460
A 2000-stage element mechanical expansion valve ensures
precise flow control whilst generating little modulation noise. A Net/ Gross weight kg 12.8/16.9 17/22.4 17/22.4 17/22.4

multi-blade fan coupled with a dual-blade air guide smooth Liquid/gas pipe mm Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9
output airflow and three fan speeds provide flexibility to Piping connections
Drain pipe mm OD Ф16.5
respond to users' particular comfort requirements.
Standard controller Wireless remote controller

51 52
Ceiling & Floor Specifications
50Hz AC fan motors
Model MDV-D36DL/N1-C MDV-D45DL/N1-C MDV-D56DL/N1-C MDV-D71DL/N1-C MDV-D80DL/N1-C

Power supply 1-phase,220-240V,50Hz

Cooling kW 3.6 4.5 5.6 7.1 8.0


Capacity
Heating kW 4.0 5.0 6.3 8.0 9.0

Cooling W 49 120 122 125 130


1st Generation VRF INDOOR UNITS

1st Generation VRF INDOOR UNITS


Power input
Heating W 49 120 122 125 130

Airflow rate(H/M/L) m3/h 650/570/500 800/600/500 800/600/500 800/600/500 1200/900/700

Auto Restart Auto Timer Auto Easy-cleaning Follow Anti-cold Air Auto LED Built-in Independent Wired Sound pressure level(H/M/L) dB(A) 40/38/36 43/41/38 43/41/38 43/41/38 45/43/40
Function Addressing Defrosting Panel Me Function Swing Display Filter Dehumidification Controller
Net dimension(W×H×D) mm 990×203×660 990×203×660 990×203×660 990×203×660 1280×203×660

Fan Motor Options Packing dimension(W×H×D) mm 1089×296×744 1089×296×744 1089×296×744 1089×296×744 1379×296×744

Choose either AC or DC fan motors. Net/gross weight kg 26/32 28/34 28/34 28/34 34.5/41

Flexibility Piping connections


Liquid/gas pipe mm Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9

Drain pipe mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25


A sleek design suits installation either on the ceiling or floor, providing flexibility to accommodate a wide range of room
Standard controller Wireless remote controller
designs.

>20 Drop ceiling Model MDV-D90DL/N1-C MDV-D112DL/N1-C MDV-D140DL/N1-C MDV-D160DL/N1-C

Power supply 1-phase,220-240V,50Hz


203mm
Cooling kW 9.0 11.2 14.0 16.0
Capacity
The unit can be installed either horizontally on the ceiling or Heating kW 10.0 12.5 15.0 18.0
Air outlet
vertically against the wall. Cooling W 130 182 182 300
Power input
Heating W 130 182 182 300
Wide-Angle Swing
Airflow rate(H/M/L) m3/h 1200/900/700 1980/1860/1730 1980/1860/1730 2300/2100/1800

A wide-angle swing together with bi-directional louver swing allows the Sound pressure level(H/M/L) dB(A) 45/43/40 47/45/42 47/45/42 49/47/44
positioning of the unit to be selected to suit the room's decor, whilst ensuring
Net dimension(W×H×D) mm 1280×203×660 1670×244×680 1670×244×680 1670×285×680
that full-room cooling and heating coverage is achieved.
Packing dimension(W×H×D) mm 1379×296×744 1764×329×760 1764×329×760 1775×377×760

Net/gross weight kg 34.5/41 54/59 54/59 57.5/63.5

Liquid/gas pipe mm Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9


Wide-angle swing
Piping connections

Increased Comfort Drain pipe mm OD Ф25 OD Ф25 OD Ф25 OD Ф25

Standard controller Wireless remote controller


Sound levels as low as 36dB(A) are achieved using electronic expansion valves which ensure precise flow control whilst generat-
Notes:
ing little modulation noise. A multi-blade fan coupled with a dual-louver air guide smooth output airflow. 1. Nominal capacities are based on the following conditions:
- Cooling: indoor temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor temperature 35°C (95.0°F) DB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
- Heating: indoor temperature 20°C (68.0°F) DB; outdoor temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
2. Floor standing: Sound pressure level is measured at a position 1m (3.28ft) in front the unit and 1m (3.28ft) above the floor in a semi-anechoic chamber.
Ceiling mounted: Sound pressure level is measured at a position 1m (3.28ft) in front and 1m (3.28ft) below the unit in a semi-anechoic chamber.

53 54
60Hz AC fan motors
Model MDV-D36DL/N1-C MDV-D45DL/N1-C MDV-D56DL/N1-C MDV-D71DL/N1-C
Floor Standing
Power supply 1-phase, 220-240V, 60Hz

kW 3.6 4.5 5.6 7.1


Cooling capacity
Btu/h 12300 15400 19100 24200

kW 4.0 5.0 6.3 8.0


Heating capacity
Btu/h 13600 17100 21500 27300

Cooling W 50 148 148 148


Power input
Heating W 50 148 148 148
1st Generation VRF INDOOR UNITS

1st Generation VRF INDOOR UNITS


m3/h 600/480/400 750/650/550 750/650/550 750/650/550
Airflow rate(H/M/L)
CFM 353/283/235 441/383/324 441/383/324 441/383/324
Auto Restart Follow Anti-cold Air Auto Auto Independent Timer Wired
Function Me Function Addressing Defrosting Dehumidification Controller
Sound pressure level(H/M/L) dB(A) 40/38/36 43/41/38 43/41/38 43/41/38

Net dimension(W×H×D) mm(in.) 990×203×660(38-31/32×7-63/64×25-63/64)


Fan Motor Options
Packing dimension(W×H×D) mm(in.) 1089×296×744(42-7/8×11-21/32×29-9/32)
Choose either AC or DC fan motors.
Net/gross weight
Flexibility
kg(lbs.) 26/32(57.3/70.6) 28/34(61.7/75.0) 28/34(61.7/75.0) 28/34(61.7/75.0)

Liquid/gas pipe mm(in.) Ф6.35/Ф12.7(Ф1/4/Ф1/2) Ф9.53/Ф15.9(Ф3/8/Ф5/8)


Piping connections The Floor Standing indoor unit can be installed on the floor or, for easier floor cleaning, hung on the wall with piping running from
Drain piping mm(in.) Ф25(OD 63/64)
the rear. The streamlined appearance complements any room's decor.
Standard controller Wireless remote controller

Casing Options
Model MDV-D80DL/N1-C MDV-D90DL/N1-C MDV-D112DL/N1-C MDV-D140DL/N1-C MDV-D160DL/VN1-C At just 212mm deep, the F3B concealed floor standing unit can be installed around the perimeter of a room, hidden behind the
Power supply 1-phase, 220-240V, 60Hz skirting board, and special installation methods can be used to eliminate noise from the room space. The F4 (front air intake) and
Cooling capacity
kW 8.0 9.0 11.2 14.0 16.0 F5 (underside air intake) offer a choice of air intake options.
Btu/h 27300 30700 38200 47800 54600
kW 9.0 10.0 12.5 15.0 18.0
Heating capacity
Btu/h 30700 34100 42700 51200 61400
Cooling W 183 183 245 245 378
Power input
Heating W 183 183 245 245 378

m3/h 1200/900/700 1200/900/700 1980/1860/1730 1980/1860/1730 2300/2100/1800 F5 (underside air intake)


Airflow rate(H/M/L) F3B (concealed) F4 (front air intake)
CFM 706/530/412 706/530/412 1165/1095/1018 1165/1095/1018 1354/1236/1060
Sound pressure level(H/M/L) dB(A) 45/43/40 45/43/40 47/45/42 47/45/42 49/47/44
Specifications
1670×285×680(65-3/4×
Net dimension(W×H×D) mm(in.) 1280×203×660(50-25/64×7-63/64×25-63/64) 1670×244×680(65-3/4×9-39/64×26-49/64)
11-7/32×26-49/64)
50Hz AC fan motors
Model MDV-D22Z/N1-F3B MDV-D28Z/N1-F3B MDV-D36Z/N1-F3B MDV-D45Z/N1-F3B MDV-D56Z/N1-F3B MDV-D71Z/N1-F3B MDV-D80Z/N1-F3B
1775×377×760(69-7/8× Power supply 1-phase,220-240V,50Hz
Packing dimension(W×H×D) mm(in.) 1379×296×744(54-19/64×11-21/32×29-19/64) 1764×329×760(69-29/64×12-61/64×29-59/64)
14-27/32×29-59/64)
Cooling kW 2.2 2.8 3.6 4.5 5.6 7.1 8.0
Capacity
Heating kW 2.4 3.2 4.0 5.0 6.3 8.0 9.0
Net/gross weight kg(lbs.) 34.5/41(76.1/90.4) 54/59(119.0/130.1) 57.5/63.5(126.5/139.7)
Cooling W 40 46 46 49 88 130 130
Liquid/gas pipe mm(in.) Ф9.53/Ф15.9(Ф3/8/Ф5/8) Power input
Piping connections Heating W 40 46 46 49 88 130 130
Drain piping mm(in.) Ф25(OD 63/64)
Standard controller Wireless remote controller Airflow rate(H/M/L) m3/h 530/456/400 569/485/421 624/522/375 660/542/440 1150/970/830 1380/1100/870 1380/1100/870

Sound pressure level(H/M/L) dB(A) 36/33/29 36/33/29 37/34/30 37/34/30 41/35/31 44/39/33 44/39/33
Notes: Net dimension(W×H×D) mm 840×545×212 840×545×212 1040×545×212 1040×545×212 1340×545×212 1340×545×212 1340×545×212
1. Nominal capacities are based on the following conditions:
Packing dimension(W×H×D) mm 939×639×305 939×639×305 1139×639×305 1139×639×305 1425×639×305 1425×639×305 1425×639×305
- Cooling: indoor temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor temperature 35°C (95.0°F) DB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
- Heating: indoor temperature 20°C (68.0°F) DB; outdoor temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference. Net/gross weight kg 25/27 25/27 29.5/34 29.5/34 33/39 33/39 36/40
2. Floor standing: Sound pressure level is measured at a position 1m (3.28ft) in front the unit and 1m (3.28ft) above the floor in a semi-anechoic chamber.
Liquid/gas pipe mm Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9
Ceiling mounted: Sound pressure level is measured at a position 1m (3.28ft) in front and 1m (3.28ft) below the unit in a semi-anechoic chamber. Piping connections
Drain pipe mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25
Standard controller Wireless remote controller

55 56
MDV-D22Z/N1-F4 MDV-D28Z/N1-F4 MDV-D36Z/N1-F4 MDV-D45Z/N1-F4 MDV-D56Z/N1-F4 MDV-D71Z/N1-F4 MDV-D80Z/N1-F4 Console
Model
MDV-D22Z/N1-F5 MDV-D28Z/N1-F5 MDV-D36Z/N1-F5 MDV-D45Z/N1-F5 MDV-D56Z/N1-F5 MDV-D71Z/N1-F5 MDV-D80Z/N1-F5
Auto Restart Auto Timer Auto Easy-cleaning Follow
Function Addressing Defrosting Panel Me

Power supply 1-phase,220-240V,50Hz

Anti-cold Air Auto LED Built-in Independent Wired


Function Swing Display Filter Dehumidification Controller
Cooling kW 2.2 2.8 3.6 4.5 5.6 7.1 8.0

Compact and Stylish High-Efficiency Filter


1st Generation VRF INDOOR UNITS

1st Generation VRF INDOOR UNITS


Capacity

Heating kW 2.4 3.2 4.0 5.0 6.3 8.0 9.0


The elegant, space-saving design of the Console unit Formaldehyde nemesis filter is fitted as standard and
complements any room's decor. The expansion valve is active-carbon and biological anti-virus filter are available as
installed inside the indoor unit for added compactness. a customization option.
Cooling W 40 46 46 49 88 130 130

Power input High Comfort Flexibility


Heating W 40 46 46 49 88 130 130 A wide-angle swing together with auto swing louvers and The Console unit can be installed on the floor or lower part
five fan speed options ensure that airflow reaches every of the wall. Full capacity is still achieved even when the
corner of the room. A 2000-stage element mechanical underside air inlet is unavailable.
Airflow rate(H/M/L) 530/456/400 569/485/421 624/522/375 660/542/440 1150/970/830 1380/1100/870 1380/1100/870 expansion valve ensures precise flow control whilst
m3/h
generating little modulation noise.

F4 dB(A) 36/33/29 36/33/29 37/34/30 37/34/30 41/35/31 44/39/33 44/39/33


Two Air Outlets and Four Air Inlets
Sound pressure level
(H/M/L) The Console unit's combination of four air inlets and two air
outlets ensure that cooling and heating is distributed in all
F5 dB(A) 36/33/29 36/33/29 37/34/30 37/34/30 41/35/31 44/39/33 44/39/33 directions.

Air Outlet
Net dimension
(W×H×D)
F4 mm 1000×596×225 1000×596×225 1200×596×225 1200×596×225 1500×596×225 1500×596×225 1500×596×225
Low-noise Design
A five-speed fan allows airflow customization whilst
F5 mm 1000×677×220 1000×677×220 1200×677×220 1200×677×220 1500×677×220 1500×677×220 1500×677×220 maintaining low-noise, low power consumption operation.

F4 mm 1089×683×312 1089×683×312 1289×683×312 1289×683×312 1589×683×312 1589×683×312 1589×683×312


Packing dimension
(W×H×D) Air Inlet

F5 mm 1182×683×312 1182×683×312 1382×683×312 1382×683×312 1682×683×312 1682×683×312 1682×683×312


Specifications Sound levels as low as 26dB(A)

Model MDV-D22Z/DN1-B MDV-D28Z/DN1-B MDV-D36Z/DN1-B MDV-D45Z/DN1-B


F4 kg 30/35 30/35 36/44 36/44 41/46.5 41/46.5 42.5/48.5
Power supply 1-phase,220-240V,50Hz
Net/gross weight
Cooling kW 2.2 2.8 3.6 4.5
Capacity
F5 kg 30/38 30/38 35.5/41 35.5/41 42/51 42/51 44/53 Heating kW 2.6 3.2 4.0 5.0
Cooling W 20 25 25 45
Power input
Liquid/gas Heating W 20 25 25 45
pipe mm Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф9.53/Ф15.9 Ф9.53/Ф15.9 Ф9.53/Ф15.9
Airflow rate(H/M/L) m /h
3 430/345/229 510/430/229 510/430/229 660/512/400
Piping connections
Sound pressure level(H/M/L) dB(A) 38/32/26 39/33/27 39/33/27 42/39/36
Drain pipe mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 Net dimension(W×H×D) mm 700×600×210 700×600×210 700×600×210 700×600×210
Packing dimension(W×H×D) mm 810×710×305 810×710×305 810×710×305 810×710×305
Net/gross weight kg 14/19 15/20 15/20 15/20
Standard controller Wireless remote controller
Liquid/gas pipe mm Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7
Piping connections
Notes: Drain pipe mm OD Ф16 OD Ф16 OD Ф16 OD Ф16
1. Nominal capacities are based on the following conditions: Standard controller Wireless remote controller
- Cooling: indoor temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor temperature 35°C (95.0°F) DB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference. 1. Nominal capacities are based on the following conditions:
- Heating: indoor temperature 20°C (68.0°F) DB; outdoor temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference. - Cooling: indoor temperature 27°C (80.6°F) DB, 19°C (66.2°F) WB; outdoor temperature 35°C (95.0°F) DB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
2. The specifications of the F3B series are measured at 10Pa external static pressure and those of the F4 and F5 series at 0Pa external static pressure. - Heating: indoor temperature 20°C (68.0°F) DB; outdoor temperature 7°C (44.6°F) DB, 6°C (42.8°F) WB; equivalent refrigerant piping length 7.5m (24.6ft.) with zero level difference.
3. Sound pressure level is measured at a position 1m (3.28ft) in front the unit and 1m (3.28ft) above the floor in a semi-anechoic chamber. 2. Sound pressure level is measured at a position 1m (3.28ft) in front the unit and 1m (3.28ft) above the floor in a semi-anechoic chamber.

57 58
2nd Generation
VRF INDOOR UNITS

One-way Cassette Fresh Air Processing Unit

Two-way Cassette Wall Mounted

Compact Four-way Cassette Ceiling & Floor

Four-way Cassette Floor Standing

Medium Static Pressure Duct Console

High Static Pressure Duct

59 60
Wide Application Range Comfort and Efficiency

Wide Range of Indoor Units High Efficiency DC Fan Motor

With 11 types and more than 100 models, Midea VRF indoor units meet varied customer requirements in a wide range of The power consumption of DC fan motor can be reduced greatly in comparison to corresponding AC type.
locations including shopping malls, hospitals, office buildings, hotels and airports.

Quiet Operation

The low sound operation DC fan motor and optimized fan


blades guarantees the air discharge smoothly and provides a
quiet living environment.
2nd Generation VRF INDOOR UNITS

2nd Generation VRF INDOOR UNITS


Multiple Appearance Options

For Wall Mounted Units, three interchangeable panels add extra flexibility to a universal body design.

Constant Level of Indoor Air Temperature

The DC Inverter fan motor adjusts of air flow based on thermal load instantly providing less temperature fluctuation and an
M9 panel M10 panel
improved living environment.
For Four-way Cassette and Compact Four-way Cassette Units, interchangeable 360o airflow and four-way airflow panels are Fluctuation of room temperature
available. Temp

Time

360o airflow Four-way airflow DC driven AC driven

For Floor Standing Units, the F3B (concealed) unit is designed to be concealed in walls while the F4 (front air intake) and F5
5-step Swing Louver
(underside air intake) offer a choice of air intake options.
The air is comfortably spread upwards and downwards thanks to
the 5-step swing louver that can be programmed via the
controller.
1

2
F3B (concealed) F4 (front air intake) F5 (underside air intake) Step 3
4
Swing
5

61 62
Comfort and Efficiency Convenience

Static Pressure 20 Steps Control (Duct Unit) High-lift Drain Pump

Depending on the installation environment, medium static pressure duct is controlled the static pressure up to 10 steps and A drain pump with a 750mm or 500mm pump head is fitted as standard or optional, simplifying installation of the drain piping.
high static pressure duct is controlled the static pressure up to 20 steps via wired remote controller, for providing comfortable
environment suitable for any environment.
750mm

Constant airflow discharge


Flexible Installation

For Medium Static Pressure Duct Units, to provide the flexibility to adapt to differing installation situations, the air inlet may be
positioned either on the underside or the rear of the unit.
2nd Generation VRF INDOOR UNITS

2nd Generation VRF INDOOR UNITS


20 steps static pressure control

Air intake Air intake


7-Speed Fan Control from rear from below

7 indoor fan speeds provide control flexibility to meet the needs of different indoor conditions.

For Wall Mounted Units, the refrigerant outlet direction can be left, right or rear as the installation situation requires. A new fixing
plate design speeds installation and provides extra stability.
Rest time Leisure time Exercise time
soft airflow gentle airflow strong airflow

Rear

Right
Fan speed 1 Fan speed 2 Fan speed 3 Fan speed 4 Fan speed 5 Fan speed 6 Fan speed 7 Left

Soft airflow Strong airflow

Ceiling / Floor Units can be installed either on the ceiling or the floor, providing flexibility to accommodate a wide range of room
designs.
Fresh Air Intake

On selected models, a reserved outside air intake port


allows outdoor air to be introduced directly into the unit,
negating the need for a separate ventilation system.

Floor installation Ceiling installation

63 64
One-way Cassette Two-way Cassette
Fresh air intake Two-way air discharge, perfect for limited ceiling space applications
One-way air discharge, ideal for corner locations Drain pump with 750mm pump head fitted as standard
Drain pump with 750mm pump head fitted as standard

Optional wireless remote Optional wired Optional wireless remote Optional wired
controller controller controller controller

RM12D RM05B WDC-86E/KD WDC-120G/WK RM12D RM05B WDC-86E/KD WDC-120G/WK

Model MI2-18Q1DHN1 MI2-22Q1DHN1 MI2-28Q1DHN1 MI2-36Q1DHN1 Model MI2-22Q2DHN1 MI2-28Q2DHN1 MI2-36Q2DHN1


Power supply 1-phase, 220-240V, 50/60Hz Power supply 1-phase, 220-240V, 50/60Hz
kW 1.8 2.2 2.8 3.6 kW 2.2 2.8 3.6
Capacity Capacity
Cooling1 kBtu/h 6.1 7.5 9.6 12.3 Cooling1 kBtu/h 7.5 9.6 12.3
Power input W 25 25 30 30 Power input W 35 40 40
kW 2.2 2.6 3.2 4.0 kW 2.6 3.2 4.0
Capacity Capacity
Heating2 kBtu/h 7.5 8.9 10.9 13.6 Heating2 kBtu/h 8.9 10.9 13.6
Power input W 25 25 30 30 Power input W 35 40 40
Air flow rate 3 m3/h 523/482/448/404/360/312/275 573/531/492/456/420/364/315 Air flow rate 3 m3/h 654/612/571/530/488/449/410 725/679/641/591/554/509/458
Sound pressure level 4 dB(A) 37/36/35/34/32/31/30 39/38/37/36/35/35/34 Sound pressure level 4 dB(A) 33/31/30/29/27/25/24 35/33/32/30/29/27/25
5
Net dimensions (WxHxD) mm 1054×153×425 5
Net dimensions (WxHxD) mm 1172×299×591
2nd Generation VRF INDOOR UNITS

2nd Generation VRF INDOOR UNITS


Main body Packed dimensions (WxHxD) mm 1155×245×490 Main body Packed dimensions (WxHxD) mm 1355×400×675
Net/Gross weight kg 11.8/15.3 12.3/15.8 Net/Gross weight kg 33.5/42.0
Net dimensions (W×H×D) mm 1180×25×465 Net dimensions (W×H×D) mm 1430×53×680
Panel Packed dimensions (W×H×D) mm 1232×107×517 Panel Packed dimensions (W×H×D) mm 1525×130×765
Net/Gross weight kg 3.5/5.2 Net/Gross weight kg 10.5/15
Liquid/Gas pipe mm Ф6.35/Ф12.7 Liquid/Gas pipe mm Ф6.35/Ф12.7
Pipe connections Pipe connections
Drain pipe mm OD Ф32 Drain pipe mm OD Ф32

Model MI2-45Q1DHN1 MI2-56Q1DHN1 MI2-71Q1DHN1 Model MI2-45Q2DHN1 MI2-56Q2DHN1 MI2-71Q2DHN1


Power supply 1-phase, 220-240V, 50/60Hz Power supply 1-phase, 220-240V, 50/60Hz
kW 4.5 5.6 7.1 kW 4.5 5.6 7.1
Capacity Capacity
Cooling1 kBtu/h 15.4 19.1 24.2 Cooling1 kBtu/h 15.4 19.1 24.2
Power input W 40 48 60 Power input W 50 69 98
kW 5.0 6.3 8.0 kW 5.0 6.3 8.0
Capacity Capacity
Heating2 kBtu/h 17.1 21.5 27.3 Heating2 kBtu/h 17.1 21.5 27.3
Power input W 40 48 60 Power input W 50 69 98
Air flow rate 3 m3/h 693/662/638/600/556/510/476 792/763/728/688/643/589/549 933/873/815/749/689/637/592 Air flow rate 3 m3/h 850/792/731/670/631/592/550 980/925/855/800/755/702/670 1200/1115/1068/1000/921/808/770
Sound pressure level 4 dB(A) 41/40/39/38/37/36/35 42/41/40/39/38/37/36 44/43/42/41/39/38/37 Sound pressure level 4 dB(A) 37/36/35/34/32/31/30 39/37/36/35/33/31/30 44/42/41/40/38/36/34
5
Net dimensions (WxHxD) mm 1275×189×450 5
Net dimensions (WxHxD) mm 1172×299×591
Main body Packed dimensions (WxHxD) mm 1370×295×505 Main body Packed dimensions (WxHxD) mm 1355×400×675
Net/Gross weight kg 16.1/20.4 16.4/20.7 17.6/22.4 Net/Gross weight kg 35/43.5
Net dimensions (W×H×D) mm 1350×25×505 Net dimensions (W×H×D) mm 1430×53×680
Panel Packed dimensions (W×H×D) mm 1410×95×560 Panel Packed dimensions (W×H×D) mm 1525×130×765
Net/Gross weight kg 4/5.4 Net/Gross weight kg 10.5/15
Liquid/Gas pipe mm Ф6.35/Ф12.7 Ф9.53/Ф15.9 Liquid/Gas pipe mm Ф6.35/Ф12.7 Ф9.53/Ф15.9
Pipe connections Pipe connections
Drain pipe mm OD Ф32 Drain pipe mm OD Ф32

Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Each model's 7 airflow rate options are listed in order, from highest to lowest. 3. Each model's 7 airflow rate options are listed in order, from highest to lowest.
4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3). 4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3).
Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments. 5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.

65 66
Compact Four-way Cassette Four-way Cassette
Fresh air intake Fresh air intake
360° airflow allows for even, wide-range cooling and heating Four-way airflow, allows wide-angle, equal distribution of cooling and
Drain pump with 500mm pump head fitted as standard heating
Drain pump with 750mm pump head fitted as standard
Brand-new, elegant panel with four independently controlled louvers
Optional wireless remote Optional wired Optional wireless remote Optional wired
controller controller controller controller

RM12D RM05B WDC-86E/KD WDC-120G/WK RM12D RM05B WDC-86E/KD WDC-120G/WK


Brand
new
910mm±5mm
Model MI2-22Q4CDHN1 MI2-28Q4CDHN1 MI2-36Q4CDHN1 MI2-45Q4CDHN1

910mm±5mm

Body
Power supply 1-phase, 220-240V, 50/60Hz Ceiling

15mm
Ceiling
kW 2.2 2.8 3.6 4.5
Capacity New panel appearance New panel installation dimensions
1 Model
Cooling kBtu/h 7.5 9.6 12.3 15.4 MI2-28Q4DHN1 MI2-36Q4DHN1 MI2-45Q4DHN1 MI2-56Q4DHN1 MI2-71Q4DHN1
Power supply 1 phase, 220-240V, 50/60Hz
kW 2.8 3.6 4.5 5.6 7.1
Power input W 35 35 40 50 Capacity
Cooling1 kBtu/h 9.6 12.3 15.4 19.1 24.2
2nd Generation VRF INDOOR UNITS

2nd Generation VRF INDOOR UNITS


Power input W 40 45 50 60 70
kW 2.4 3.2 4.0 5.0
kW 3.2 4.0 5.0 6.3 8.0
Capacity Capacity
Heating2 kBtu/h 10.9 13.6 17.1 21.5 27.3
2
Heating kBtu/h 8.2 10.9 13.6 17.1 Power input W 40 45 50 60 70
Air flow rate 3 m3/h 801/751/711/658/637/611/542 893/866/804/744/714/698/635 977/937/864/800/778/738/671
Power input W 35 35 40 50 Sound pressure level 4 dB(A) 32/31/30/28/28/26/23 35/34/31/31/30/28/26 35/35/34/31/30/28/27
Net dimensions 5 (WxHxD) mm 840×230×840
3 Main body Packed dimensions (WxHxD) mm 955×260×955
Air flow rate 3
m /h 576/552/524/503/462/441/405 604/573/541/516/478/434/400
Net/Gross weight kg 21.3/25.8 23.2/27.6
Net dimensions (W×H×D) mm 950×54.5×950
4
Sound pressure level dB(A) 35/34/33/29/26/23/22 41/38/35/32/30/29/28 Panel 1035×90×1035
Packed dimensions (W×H×D) mm
Net/Gross weight kg 5/8
5
Net dimensions (WxHxD) mm 630×260×570 Liquid/Gas pipe mm Ф6.35/Ф12.7 Ф9.53/Ф15.9
Pipe connections
Drain pipe mm OD Φ32

Main body Packed dimensions (WxHxD) mm 700×330×660


Model MI2-80Q4DHN1 MI2-90Q4DHN1 MI2-100Q4DHN1 MI2-112Q4DHN1 MI2-140Q4DHN1
Power supply 1 phase, 220-240V, 50/60Hz
Net/Gross weight kg 18/23.5 19.2/24.7 kW 8.0 9.0 10.0 11.2 14.0
Capacity
Cooling1 kBtu/h 27.3 30.7 34.1 38.2 47.8
Net dimensions (W×H×D) mm 647×50×647 Power input W 96 100 150 160 170
kW 9.0 10.0 11.0 12.5 16.0
Capacity
Heating2 kBtu/h 30.7 34.1 37.5 42.7 54.6
Panel Packed dimensions (W×H×D) mm 715×123×715
Power input W 96 100 150 160 170
3 1203/1131/1064/ 1349/1294/1230/ 1662/1574/1448/1348
Net/Gross weight kg 2.5/4.5 Air flow rate 3 m /h 977/912/840/774 1201/1111/1029/970
1641/1544/1431/1309/1225/1198/1143
/1253/1219/1170

Sound pressure level 4 dB(A) 36/35/34/31/31/29/28 37/35/34/31/31/30/28 38/36/35/34/31/31/30 39/37/36/35/34/31/31


Liquid/Gas pipe mm Ф6.35/Ф12.7 Net dimensions 5 (WxHxD) mm 840×230×840 840×300×840
Pipe connections Main body Packed dimensions (WxHxD) mm 955×260×955 955×330×955

Drain pipe mm OD Ф32 Net/Gross weight kg 23.2/27.6 28.4/33.8 30.7/35.8


Net dimensions (W×H×D) mm 950×54.5×950
Notes: Panel Packed dimensions (W×H×D) mm 1035×90×1035
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. Net/Gross weight kg 5/8
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. Liquid/Gas pipe mm Ф9.53/Ф15.9
3. Each model's 7 airflow rate options are listed in order, from highest to lowest. Pipe connections
Drain pipe mm OD Φ32
4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3).
Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
Notes:
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Each model's 7 airflow rate options are listed in order, from highest to lowest.
4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3).
Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
67 68
Medium Static Pressure Duct High Static Pressure Duct
Fresh air intake External static pressure up to 400Pa facilitates extensive
6-step static pressure control on 2.2kW to 7.1kW models and 10-step duct and grille network
static pressure control on 8kW to 14kW units (requires latest 20-step static pressure control on all models (requires latest generation wired
generation wired controllers) controllers)
Drain pump with 750mm pump head fitted as standard Optional wireless remote Optional wired A double-skin drainage pan provides double protection for ceilings (models 71 to Optional wireless remote Optional wired
controller controller controller controller
Flexible installation for the air inlet may be positioned either on the 160).
underside or the rear of the unit
RM12D RM05B WDC-86E/KD WDC-120G/WK RM12D RM05B WDC-86E/KD WDC-120G/WK

Model MI2-22T2DHN1 MI2-28T2DHN1 MI2-36T2DHN1 Model MI2-71T1DHN1 MI2-80T1DHN1 MI2-90T1DHN1


Power supply 1 phase, 220-240V, 50/60Hz Power supply 1 phase, 220-240V, 50/60Hz
kW 2.2 2.8 3.6 kW 7.1 8.0 9.0
Capacity 1 Capacity
Cooling1 kBtu/h 7.5 9.6 12.3 Cooling kBtu/h 24.2 27.3 30.7
Power input W 40 40 45 Power input W 180 180 220
kW 2.6 3.2 4.0 kW 8.0 9.0 10.0
Capacity 2 Capacity
Heating2 kBtu/h 8.2 10.9 13.6 Heating kBtu/h 27.3 30.7 34.1
Power input W 40 40 45 Power input W 180 180 220
3
Air flow rate
3
m3/h 520/480/440/400/360/330/300 580/540/500/460/430/400/370 Air flow rate m3/h 1360/1327/1293/1260/1227/1193/1160 1360/1327/1293/1260/1227/1193/1160 1420/1373/1327/1280/1233/1187/1140

External static pressure Pa 10 (0~50) External static pressure Pa 100 (30~ 200)
4
Sound pressure level 4 dB(A) 32/31/29/28/26/25/23 33/32/31/30/28/27/25 Sound pressure level dB(A) 46/46/45/45/44/43/42 46/46/45/45/44/43/42 50/49/48/48/47/46/45
5
Net dimensions (WxHxD) mm 780×210×500 Net dimensions 5 (WxHxD) mm 965x423x690
Unit 870×285×525 Unit Packed dimensions (WxHxD) mm 1090×440×768
Packed dimensions (WxHxD) mm
Net/Gross weight kg 18/21 Net/Gross weight kg 41/47 51/57
Liquid/Gas pipe mm Ф6.35/ Ф12.7 Liquid/Gas pipe mm Ф9.53/Ф15.9
Pipe connections Pipe connections
Drain pipe mm OD Ф25 Drain pipe mm OD Ф25
2nd Generation VRF INDOOR UNITS

2nd Generation VRF INDOOR UNITS


Model MI2-45T2DHN1 MI2-56T2DHN1 MI2-71T2DHN1 Model MI2-112T1DHN1 MI2-140T1DHN1 MI2-160T1DHN1
Power supply 1 phase, 220-240V, 50/60Hz Power supply 1 phase, 220-240V, 50/60Hz
kW 4.5 5.6 7.1 kW 11.2 14.0 16.0
Capacity Capacity
Cooling1 kBtu/h 15.4 19.1 24.2 Cooling
1
kBtu/h 38.2 47.8 54.6
Power input W 92 92 98 Power input W 380 420 700
kW 5.0 6.3 8.0 kW 12.5 16.0 17.0
Capacity Capacity
Heating2 kBtu/h 17.1 21.5 27.3 Heating
2
kBtu/h 42.7 54.6 58.0
Power input W 92 92 98 Power input W 380 420 700
3 3
Air flow rate m3/h 800/740/680/620/540/480/400 830/760/720/680/640/600/560 1000/960/900/840/780/720/680 Air flow rate m3/h 1870/1783/1697/1610/1523/1437/1350 2240/2133/2027/1920/1813/1707/1600 2660/2530/2400/2270/2140/2010/1880
External static pressure Pa 10 (0~50) External static pressure Pa 100 (30~ 200)
Sound pressure level 4 dB(A) 36/34/32/31/29/27/25 36/34/33/32/30/29/28 37/35/33/32/30/29/28 Sound pressure level
4
dB(A) 50/50/49/48/47/46/45 53/52/51/51/50/49/48 54/54/53/52/51/50/50
5
Net dimensions (WxHxD) mm 1000×210×500 1220×210×500 Net dimensions 5 (WxHxD) mm 965x423x690 1322x423x691
Unit Packed dimensions (WxHxD) mm 1115×285×525 1335×285×525 Unit Packed dimensions (WxHxD) mm 1090×440×768 1436×450×768
Net/Gross weight kg 21.5/25 27.5/31.5 Net/Gross weight kg 51/57 68/76
Liquid/Gas pipe mm Ф6.35/ Ф12.7 Ф9.53/Ф15.9 Liquid/Gas pipe mm Ф9.53/Ф15.9
Pipe connections Pipe connections
Drain pipe mm OD Ф25 Drain pipe mm OD Ф25

Model MI2-80T2DHN1 MI2-90T2DHN1 MI2-112T2DHN1 MI2-140T2DHN1 Model MI2-200T1DHN1 MI2-250T1DHN1 MI2-280T1DHN1


Power supply 1 phase, 220-240V, 50/60Hz Power supply 1 phase, 220-240V, 50/60Hz
kW 8.0 9.0 11.2 14.0 kW 20.0 25.0 28.0
Capacity Capacity
Cooling1 kBtu/h 27.3 30.7 38.2 47.8 Cooling
1
kBtu/h 68.2 85.3 95.5
Power input W 110 120 200 250 Power input W 990 1200 1200
kW 9.0 10.0 12.5 15.5 kW 22.5 26.0 31.5
2 Capacity 2 Capacity
Heating kBtu/h 30.7 34.1 42.7 52.9 Heating kBtu/h 76.8 88.7 107.5
Power input W 110 120 200 250 Power input W 990 1200 1200
3
Air flow rate m3/h 1260/1180/1100/1020/940/860/780 1500/1430/1360/1290/1210/1140/1080 1960/1860/1760/1660/1560/1460/1360 Air flow rate
3
m3/h 4330/4230/4130/4030/3930/3830/3730
External static pressure Pa 20 (10~100) 40 (30~150) External static pressure Pa 170 (20~250)
Sound pressure level 4 dB(A) 37/35/34/33/31/29/28 39/38/38/37/35/34/33 41/39/38/37/36/35/33 Sound pressure level
4
dB(A) 57/56/55/54/53/52/50
Net dimensions 5 (WxHxD) mm 1230×270×775 1290×300×865 Net dimensions 5 (WxHxD) mm 1454x515x931
Unit Packed dimensions (WxHxD) mm 1355×350×795 1400×375×925 Unit Packed dimensions (WxHxD) mm 1509×550×990
Net/Gross weight kg 36.5/44.5 37/45 46.5/55.5 Net/Gross weight kg 130/142
Liquid/Gas pipe mm Ф9.53/Ф15.9 Liquid/Gas pipe mm Ф12.7/Ф22.2
Pipe connections Pipe connections
Drain pipe mm OD Ф25 Drain pipe mm OD Ф32

Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Each model's 7 airflow rate options are listed in order, from highest to lowest. 3. Each model's 7 airflow rate options are listed in order, from highest to lowest.
4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3). 4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3).
Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments. 5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
All specifications are measured at standard external static pressure. All specifications are measured at standard external static pressure.

69 70
Fresh Air Processing Unit Wall Mounted Unit
100% fresh air processing unit, both fresh air filtration and Three interchangeable panels allow units to blend easily with any
heating/cooling can be achieved in a single system interior decoration, perfect for rooms with no false ceilings or free
External static pressure up to 400Pa facilitates extensive duct and grille floor space
network Refrigerant outlet direction can be left, right or rear as the installation
20-step static pressure control on all models (requires latest generation situation requires
wired controllers) Optional wireless remote Optional wired Optional wireless remote Optional wired
controller controller controller controller

RM12D RM05B WDC-86E/KD WDC-120G/WK RM12D RM05B WDC-86E/KD WDC-120G/WK

Model MI2-125FADHN1 MI2-140FADHN1 Model MI2-22GDHN1 MI2-28GDHN1


Power supply 1 phase, 220-240V, 50/60Hz
Power supply 1 phase, 220-240V, 50/60Hz kW 2.2 2.8
Capacity
kW 12.5 14.0 Cooling1 kBtu/h 7.5 9.6
Capacity Power input W 28 28
Cooling1 kBtu/h 42.6 47.8 kW 2.4 3.2
Capacity
Power input W 480 480 Heating2 kBtu/h 8.2 10.9
Power input W 28 28
kW 10.5 12.0
Capacity Air flow rate 3 m3/h 422/411/402/393/380/368/356 417/402/386/370/353/338/316
Heating2 kBtu/h 36.0 41.0 Sound pressure level 4 dB(A) 31/30/30/30/29/29/29 31/30/30/30/29/29/29
Net dimensions 5 (WxHxD) mm 835×280×203
Power input W 480 480
Unit Packed dimensions (WxHxD) mm 935×385×320
3 2000/1917/1833/1750/1667/1583/1500
Air flow rate m3/h Net/Gross weight kg 8.4/12.1 9.5/13.1
External static pressure 180 (30~200) Liquid/Gas pipe mm Ф6.35/Ф12.7
Pa Pipe connections
Drain pipe mm OD Ф16
2nd Generation VRF INDOOR UNITS

2nd Generation VRF INDOOR UNITS


Sound pressure level 4 dB(A) 48/47/46/45/44/43/42
5
Net dimensions (WxHxD) mm 1322x423x691 Model MI2-36GDHN1 MI2-45GDHN1 MI2-56GDHN1
Unit Packed dimensions (WxHxD) mm 1436×450×768 Power supply 1 phase, 220-240V, 50/60Hz
kW 3.6 4.5 5.6
Net/Gross weight kg 68/76 Capacity
Cooling1 kBtu/h 12.3 15.4 19.1
Liquid/Gas pipe mm Ф9.53/Ф15.9 Power input W 30 40 45
Pipe connections kW 4.0 5.0 6.3
Drain pipe mm OD Ф25 Capacity
Heating2 kBtu/h 13.6 17.1 21.5
Power input W 30 40 45
Air flow rate 3 m3/h 656/628/591/573/544/515/488 594/563/535/507/478/450/424 747/713/685/648/613/578/547
Model MI2-200FADHN1 MI2-250FADHN1 MI2-280FADHN1 Sound pressure level 4 dB(A) 33/32/32/31/31/30/30 35/34/33/33/32/31/31 38/37/36/36/35/34/34
Net dimensions 5 (WxHxD) mm 990×315×223
Power supply 1 phase, 220-240V, 50/60Hz Unit Packed dimensions (WxHxD) mm 1085×420×335
kW 20.0 25.0 28.0 Net/Gross weight kg 11.4/15.5 12.8/16.9
Capacity Liquid/Gas pipe mm Ф6.35/Ф12.7 Ф9.53/Ф15.9
Cooling 1
kBtu/h 68.2 85.3 95.5 Pipe connections
Drain pipe mm OD Ф16
Power input W 850 850 850
kW 12.8 16.0 18.0
Capacity Model MI2-71GDHN1 MI2-80GDHN1 MI2-90GDHN1
Heating2 kBtu/h 43.7 54.6 61.4 Power supply 1 phase, 220-240V, 50/60Hz
Power input W 850 850 850 kW 7.1 8.0 9.0
Capacity
3
Cooling1 kBtu/h 24.2 27.3 30.7
Air flow rate 3
m /h 3000/2833/2667/2500/2333/2167/2000 Power input W 55 55 82
External static pressure Pa 200 (30~250) kW 8.0 9.0 10.0
Capacity
Heating2 kBtu/h 27.3 30.7 34.1
Sound pressure level 4 dB(A) 50/49/48/47/46/44/43 Power input W 55 55 82
Net dimensions 5 (WxHxD) mm 1454x515x931 Air flow rate 3 m3/h 1195/1130/1065/1005/940/875/809 1195/1130/1065/1005/940/875/809 1421/1300/1125/1067/1005/934/867
Sound pressure level 4 dB(A) 44/43/42/39/38/37/36 44/43/42/39/38/37/36 48/46/45/43/41/40/38
Unit Packed dimensions (WxHxD) mm 1509×550×990
Net dimensions 5 (WxHxD) mm 1194×343×262
Net/Gross weight kg 130/142 Unit Packed dimensions (WxHxD) mm 1290×375×460
Net/Gross weight kg 17.0/22.4
Liquid/Gas pipe mm Ф12.7/Ф22.2
Pipe connections Liquid/Gas pipe mm Ф9.53/Ф15.9
OD Ф32 Pipe connections
Drain pipe mm Drain pipe mm OD Ф16

Notes: Notes:
1. Outdoor temperature 33°C DB, 28°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Outdoor temperature 0°C DB, -2.9°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Each model's 7 airflow rate options are listed in order, from highest to lowest. 3. Each model's 7 airflow rate options are listed in order, from highest to lowest.
4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3). 4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3).
Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber. Sound pressure level is measured 1m in front and 1m below the unit in a semi-anechoic chamber.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments. 5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
All specifications are measured at standard external static pressure.
The Fresh Air Processing Unit can be used either independently or in conjunction with other types of indoor unit. If used independently, the total capacity of the Fresh Air
Processing Units must be between 50% and 100% of that of the outdoor units. If used in conjunction with other types of indoor unit, the total capacity of the indoor units and
Fresh Air Processing Units must be between 50% and 100% of that of the outdoor units and the total capacity of the Fresh Air Processing Units must not exceed 30% of that of
the outdoor units.

71 72
Ceiling & Floor Floor Standing Unit (Concealed)
Can be installed either on the ceiling or floor Designed to be concealed in walls with only the suction and discharge
grills visible
Optional wireless remote Optional wired
Optional wireless remote Optional wired
controller controller
controller controller

RM12D RM05B WDC-86E/KD WDC-120G/WK RM12D RM05B WDC-86E/KD WDC-120G/WK

Model MI2-22F3DHN1 MI2-28F3DHN1


Model MI2-36DLDHN1 MI2-45DLDHN1 MI2-56DLDHN1 MI2-71DLDHN1
Power supply 1 phase, 220-240V, 50/60Hz
Power supply 1 phase, 220-240V, 50/60Hz kW 2.2 2.8
1 Capacity
Cooling kBtu/h 7.5 9.6
kW 3.6 4.5 5.6 7.1 Power input W 40 45
Capacity
1 kW 2.4 3.2
Cooling kBtu/h 12.3 15.4 19.1 24.2 2 Capacity
Heating kBtu/h 8.2 10.9
Power input W 49 115 115 115 Power input W 40 45
3
Air flow rate m3/h 530/504/478/456/439/418/400 569/540/515/485/462/443/421
kW 4.0 5.0 6.3 8.0 Sound pressure level 4 dB(A) 36/35/34/33/31/30/29 36/35/34/33/31/30/29
Capacity 5
2 Net dimensions (WxHxD) mm 840×545×212
Heating kBtu/h 13.6 17.1 21.5 27.3
Unit Packed dimensions (W×H×D) mm 925×639×305
Power input W 49 115 115 115 Net/Gross weight kg 21/25.5
Liquid/Gas pipe mm Ф6.35/Ф12.7
Air flow rate
3 3
550/525/500/480/460/440/420 930/895/860/830/792/755/720 Pipe connections
m /h Drain pipe mm Φ16
4
Sound pressure level dB(A) 40/39/38/38/37/36/36 43/42/41/41/39/38/38
5
Net dimensions (WxHxD) mm 990×660×203
2nd Generation VRF INDOOR UNITS

2nd Generation VRF INDOOR UNITS


Unit Packed dimensions (WxHxD) mm 1089×744×296 Model MI2-36F3DHN1 MI2-45F3DHN1
Power supply 1 phase, 220-240V, 50/60Hz
Net/Gross weight kg 27/33 28/34
kW 3.6 4.5
1 Capacity
Liquid/Gas pipe mm Ф6.35/Ф12.7 Ф9.53/Ф15.9 Cooling kBtu/h 12.3 15.4
Pipe connections Power input W 55 60
Drain pipe mm OD Φ16 kW 4.0 5.0
2 Capacity
Heating kBtu/h 13.6 17.1
Power input W 55 60
3
Air flow rate m3/h 624/591/557/522/473/420/375 660/625/583/542/501/475/440
Sound pressure level 4 dB(A) 37/36/35/34/32/31/30 37/36/35/34/32/31/30
Model MI2-80DLDHN1 MI2-90DLDHN1 MI2-112DLDHN1 MI2-140DLDHN1 5
Net dimensions (WxHxD) mm 1036×639×305
Power supply 1 phase, 220-240V, 50/60Hz Unit Packed dimensions (W×H×D) mm 1125×639×305
Net/Gross weight kg 25.5/30.5
kW 8.0 9.0 11.2 14.0 Liquid/Gas pipe mm Ф6.35/Ф12.7
Capacity Pipe connections
1 Drain pipe mm Φ16
Cooling kBtu/h 27.2 30.7 38.2 47.8

Power input W 130 130 180 180

kW 9.0 10.0 12.5 15.0


Capacity Model
2 MI2-56F3DHN1 MI2-71F3DHN1 MI2-80F3DHN1
Heating kBtu/h 30.7 34.1 42.7 51.2
Power supply 1 phase, 220-240V, 50/60Hz
Power input W 130 130 180 180 kW 5.6 7.1 8.0
Capacity
Cooling1 kBtu/h 19.1 24.2 27.3
3
Air flow rate 3
m /h 1280/1245/1210/1170/1130/1085/1050 1890/1830/1765/1700/1660/1620/1580 Power input W 88 110 130
4 kW 6.3 8.0 9.0
Sound pressure level dB(A) 45/44/43/43/42/41/40 47/46/45/45/44/43/42 Capacity
Heating2 kBtu/h 21.5 27.3 30.7
5
mm 1280×660×203 1670×680×244 Power input W 88 110 130
Net dimensions (WxHxD)
Air flow rate 3 m3/h 1150/1094/1028/970/925/886/830 1380/1290/1205/1100/1033/955/870 1380/1290/1205/1100/1033/955/870
Unit Packed dimensions (WxHxD) mm 1379×744×296 1915×760×330 Sound pressure level 4 dB(A) 41/39/37/35/33/32/31 44/42/40/39/37/35/33 44/42/40/39/37/35/33
35/41 48/58 Net dimensions 5 (WxHxD) mm 1340×545×212
Net/Gross weight kg
Unit Packed dimensions (W×H×D) mm 1425×639×305
Liquid/Gas pipe mm Ф9.53/Ф15.9 Net/Gross weight kg 30.5/35.5 32/37
Pipe connections Liquid/Gas pipe mm Ф9.53/Ф15.9
OD Φ16 Pipe connections
Drain pipe mm Drain pipe mm Φ16

Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Each model's 7 airflow rate options are listed in order, from highest to lowest. 3. Each model's 7 airflow rate options are listed in order, from highest to lowest.
4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3). 4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3).
Floor standing: Sound pressure level is measured 1m in front and 1m above the floor in a semi-anechoic chamber. Sound pressure level is measured 1m in front and 1m above the floor in a semi-anechoic chamber.
Ceiling mounted: Sound pressure level is measured 1m in front and 1m below the unit in a semi-anechoic chamber. 5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments. All specifications are measured at 10Pa external static pressure.

73 74
Floor Standing Unit (Exposed) Console
The F4 (front air intake) and F5 (underside air intake) offer a choice of air intake Combination of four air inlets and two air outlets ensures that cooling
options and heating are distributed in all directions.

F4 (front air intake)


Optional wireless remote Optional wired Optional wireless remote Optional wired
controller controller controller controller

RM12D RM05B WDC-86E/KD WDC-120G/WK F5 (underside air intake) RM12D RM05B WDC-86E/KD WDC-120G/WK

Model MI2-22F4DHN1 MI2-28F4DHN1


MI2-22F5DHN1 MI2-28F5DHN1
Power supply 1 phase, 220-240V, 50/60Hz Model MI2-22ZDHN1 MI2-28ZDHN1 MI2-36ZDHN1 MI2-45ZDHN1
Capacity kW 2.2 2.8
Cooling1 kBtu/h 7.5 9.6
Power input W 40 45
kW 2.4 3.2 Power supply 1 phase, 220-240V, 50/60Hz
Capacity
Heating2 kBtu/h 8.2 10.9
Power input W 40 45
Air flow rate 3 m3/h 530/504/478/456/439/418/400 569/540/515/485/462/443/421
Sound pressure level 4 dB(A) 36/35/34/33/31/30/29 36/35/34/33/31/30/29 kW 2.2 2.8 3.6 4.5
mm (F4) 1000×596×225
Net dimensions 5 (WxHxD) 1000×677×220 Capacity
mm (F5)
mm (F4) 1089×683×312
Unit Packed dimensions (W×H×D) 1
kBtu/h 7.5 9.6 12.3 15.4
mm (F5) 1182×683×312 Cooling
kg (F4) 28/33
Net/Gross weight
kg (F5) 28/35
Liquid/Gas pipe mm Ф6.35/Ф12.7
Pipe connections
Drain pipe mm Φ16 Power input W 20 25 25 35
2nd Generation VRF INDOOR UNITS

2nd Generation VRF INDOOR UNITS


kW 2.6 3.2 4.0 5.0
Model MI2-36F4DHN1 MI2-45F4DHN1
MI2-36F5DHN1 MI2-45F5DHN1 Capacity
Power supply
Capacity kW 3.6 4.5 Heating
2
kBtu/h 8.9 10.9 13.4 17.1
Cooling1 kBtu/h 12.3 15.4
Power input W 55 60
Capacity kW 4.0 5.0
Heating2 kBtu/h 13.6 17.1
Power input W 20 25 25 35
Power input W 55 60
Air flow rate 3 m3/h 624/591/557/522/473/420/375 660/625/583/542/501/475/440
Sound pressure level 4 dB(A) 37/36/35/34/32/31/30 37/36/35/34/32/31/30
mm (F4) 1200×596×225 3
510/482/456/430/355/286/229
Net dimensions 5 (WxHxD) 1200×677×220 Air flow rate m3/h 430/401/374/345/302/268/229 660/614/561/512/478/436/400
mm (F5)
mm (F4) 1289×683×312
Unit Packed dimensions (W×H×D)
mm (F5) 1382×683×312
kg (F4) 33/38.6 4
Net/Gross weight Sound pressure level dB(A) 38/36/34/32/28/27/26 39/37/35/33/31/29/27 42/41/40/39/37/36/36
kg (F5) 33/40.7
Liquid/Gas pipe mm Ф6.35/Ф12.7
Pipe connections
Drain pipe mm Φ16
5
Net dimensions (WxHxD) mm 700×600×210

Model MI2-56F4DHN1 MI2-71F4DHN1 MI2-80F4DHN1


MI2-56F5DHN1 MI2-71F5DHN1 MI2-80F5DHN1 Unit Packed dimensions (WxHxD) mm 810×710×305
Power supply 1 phase, 220-240V, 50/60Hz
Capacity kW 5.6 7.1 8.0
Cooling1 kBtu/h 19.1 24.2 27.3
Power input W 88 110 130 Net/Gross weight kg 14/19 15/20
kW 6.3 8.0 9.0
2 Capacity
Heating kBtu/h 21.5 27.3 30.7
Power input W 88 110 130
Air flow rate 3 m3/h 1150/1094/1028/970/925/886/830 1380/1290/1205/1100/1033/955/870 1380/1290/1205/1100/1033/955/870 Liquid/Gas pipe mm Ф6.35/Ф12.7
Sound pressure level 4 dB(A) 41/39/37/35/33/32/31 44/42/40/39/37/35/33 44/42/40/39/37/35/33
mm (F4) 1500×596×225 Pipe connections
Net dimensions 5 (WxHxD) 1500×677×220
mm (F5)
mm (F4) 1589×683×312 Drain pipe mm OD Φ16
Unit Packed dimensions (W×H×D)
mm (F5) 1682×683×312
kg (F4) 40/46 41.5/47.5
Net/Gross weight
kg (F5) 40.4/48.6 41.5/49.5 Notes:
Liquid/Gas pipe mm Ф9.53/Ф15.9
Pipe connections 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
Drain pipe mm Φ16
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
Notes: 3. Each model's 7 airflow rate options are listed in order, from highest to lowest.
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3).
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. Sound pressure level is measured 1m in front and 1m above the floor in a semi-anechoic chamber.
3. Each model's 7 airflow rate options are listed in order, from highest to lowest. 5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3).
Sound pressure level is measured 1m in front and 1m above the floor in a semi-anechoic chamber.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.

75 76
Wireless Remote Controllers

CONTROL SOLUTIONS Wired Controllers


Centralized Controllers
Network Control System
BMS Gateways
Heat Recovery Ventilator
Branch Joints
CONTROLLER LINEUP
Wireless Remote Wired Centralized Network
BMS Gateways Accessories
Controllers Controllers Controllers Control System

Hotel Key Card


Interface Module
RM05B WDC-86E/K CCM-180A/WS GW-BAC
IMMP-M

MD-NIM05/E

MD-NIM05B/E

Infrared Sensor
GW-LON Controller
RM12D WDC-86E/KD CCM-270A/WS
IMMP-S

MD-NIM09

WDC-120G/WK CCM-270A/WS GW-MOD Diagnosis software


CONTROL SOLUTIONS

CONTROL SOLUTIONS
MCAC-DIAG-B

IMMP-S

79 80
Wireless Remote Controllers Features

Model

RM05B RM12D

On / Off

Mode selection

Temperature setting (0.5°C or 1°C steps) (0.5°C or 1°C steps)

7-speed fan control

Auto swing

5-step swing louver

Address setting

Follow me

Eco mode

Night silent mode

Display shut-off

Daily timer

Keyboard lock

Background light

Dimensions (H×W×D) (mm) 150×65×20 170×48×20

Batteries 1.5V (LR03/AAA) × 2


CONTROL SOLUTIONS

CONTROL SOLUTIONS
81 82
Temperature Setting 5-step Swing Louver

Set temperature can be adjusted in 0.5°C or 1°C steps, enabling precise comfort control. The air is comfortably spread upwards and downwards thanks to the 5-step swing louver that can be programmed via the
controller.

26oC
25.5 Co
26.5oC
1

2
25oC 27oC
Step 3
4
Swing
5

Follow Me
7-Speed Fan Control
With the follow me function, the indoor unit responds to the temperature measured by the temperature sensor built-in to the
wireless remote controller, rather than the temperature sensor in the indoor unit itself, enabling more precise control of the
7 indoor fan speeds provide control flexibility to meet the needs of different indoor conditions. temperature in the user's immediate environment.

Rest time Leisure time Exercise time


soft airflow gentle airflow strong airflow

Fan speed 1 Fan speed 2 Fan speed 3 Fan speed 4 Fan speed 5 Fan speed 6 Fan speed 7

Soft airflow Strong airflow

Dispaly Shut-off
Eco Mode
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Indoor unit displays can be shut off at night, creating a better environment for rest.
Eco mode saves energy whilst retaining a comfortable indoor environment.

Model

83 84
Wired Controllers Features

Model

WDC-86E/KD WDC-86E/K WDC-120G/WK

On / Off

Mode selection

Temperature setting (0.5°C or 1°C steps) (0.5°C or 1°C steps) (0.5°C or 1°C steps)

Dual temperature set points

7-speed fan control

Auto swing

5-step swing louver

Address setting

Follow me

Eco mode

Room temperature display

°F/°C display

Keyboard lock

Background light

Daily timer

Weekly schedule timer

Auto restart

2 permission levels

Bi-directional communication

Group control

Main or secondary controller setting

Display shut-off

Night silent mode

Remote signal receiver

Clean filter reminder

Extension function
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Daylight saving time

Clock display

Dot matrix display

Error check function

System parameter querying

System setting control

Dimensions (WxHxD) (mm) 86x86x18 86x86x18 120x120x20

Power supply 18V DC 5V DC 18V DC

85 86
Group Control Extension Function

One controller can be used to unify the settings across up to 16 indoor units. The extension function is specifically designed for users working overtime. Pressing the delay button postpones system
shutdown by 1 or 2 hours.

D1D2 D1D2 D1D2 D1D2

24oC Extension
X1X2
Indoor units Up to 16 ON OFF

Main or Secondary Controller Setting Dual Temperature Set Points

Two controllers can be used together, with the indoor units' operating mode and settings being set according to the most recent With dual temperature set point control, the set temperature changes automatically when the operating
instruction received. The controller display screens are synchronized so that both displays update when a setting is adjusted. mode is changed.

Switch
X1X2 X1X2 17oC 30oC

Indoor units
Main Secondary
One indoor unit
Weekly Schedule Timer

D1D2 D1D2 D1D2 D1D2 D1D2


The weekly schedule timer allows users to set multiple schedules each with its own operating mode,
temperature settings and fan speeds.
X1X2 X1X2
Indoor units Up to 16

Main Two or more indoor units Secondary


Weekly Schedule
SUN MON TUE WED THU FRI SAT

OFF HEAT COOL FAN

2 Permission Levels
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Bi-directional Communication
2 permission levels ensure users can easily access control functions and allow administrators convenient access to operating
parameters.
The wired controller can query the system operating parameters thanks to the new bi-directional communication functional-
ity. In addtion, settings including static pressure, cold draft prevention and temperature compensation can be configured on
the wired controller.
Admin
Bi-directional Bi-directional

User

87 88
Centralized Controllers Features

Model

CCM-180A/WS CCM-270A/WS

Max. number of indoor units 64 384

Max. number of outdoor units 32 192

Max. number of refrigerant systems 8 48

Touch screen (6.2-inch) (10.1-inch)

On / Off

Mode selection

Dual temperature set points

7-speed fan control

Auto swing

5-step swing louver

Room temperature display

Outdoor unit Eco mode setting

Holiday setting

°C/°F display

Schdule management

Clock display

2 permission levels

Extension function

Daylight saving time


Unit model recognition

Electricity charge distribution

Visual schematic

Energy management

Group management

Error check function


CONTROL SOLUTIONS

CONTROL SOLUTIONS
System parameter querying

USB output Error report, operation record and


Error report
Report display electricity consumption report

Email output

Operation log

LAN access

languages supported English English

Dimensions (W×H×D) (mm) 181x124x30 270×183×27

Power supply 12V DC 24V AC

89 90
Touch Screen Visual Schematic

Colorful touch screen and vivid display make operation more convenient and simple. By importing floor plans and then dragging and dropping the indoor units to their actual positions on
the floor plan, users can create a tailored system schematic which enables monitoring and control of
the indoor units through a clear visual representation of the system layout.

Electricity Charge Distribution

The controllers use the patented Midea Calculation Method to estimate the electricity consumption of
the outdoor units and then divide it among the indoor units so that the electricity charges can be
Group Management
equitably divided among building occupants.
Units can be viewed according to group, system or location, making unit management clearer and
more convenient.

Energy Management

User can set limits or locks on an indoor unit, such as minimum cooling temperature, maximum heating
temperature, fan speed, operation mode, swing lock, remote controller lock and wired controller lock. Outdoor Unit Configuration
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Outdoor unit configuration and settings can be monitored and controlled without having to go outdoors.

Static pressure Operation Priority mode


Silent mode setting
setting capacity control setting Energy
setting

91 92
Unit Model Recognition Wiring Flexibility

The controller recognizes the model of indoor and outdoor units and different models are represented by The controllers can be connected to the master outdoor unit directly.
different icons.

X,Y P,Q,E P,Q,E P,Q,E

6.2-inch
X,Y

P,Q,E P,Q,E P,Q,E

Up to 64
indoor units

X,Y
Schedule Management Up to 8 P,Q,E P,Q,E P,Q,E
refrigerant systems

Daily, weekly or annual schedules can be used to set unit settings such as on/off, operating mode, set
temperature, fan speed and swing.

Up to 8 refrigerant systems

X,Y,E P,Q,E P,Q,E Up to P,Q,E


64

LAN Access
Up to 8 refrigerant systems
10.1-inch
X,Y,E P,Q,E P,Q,E Up to P,Q,E
A desktop or laptop PC can be used for browser-based access via a LAN connection. 64
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Up to 6 XYE
Ports

Up to 8 refrigerant systems

LAN X,Y,E P,Q,E P,Q,E Up to P,Q,E


64

93 94
Network Control System Features

Software model IMMP-S

Hardware model

IMMP-M CCM-270A/WS

Max. number per IMM system 10 10

Max. number of indoor units 2560 3840

Max. number of outdoor units 1280 1920

Max. number of refrigerant systems 320 480

Temperature setting (0.5°C steps) (0.5°C steps)

Dual temperature set points

7-speed fan control

Auto swing

5-step swing louver

Outdoor unit Eco mode setting

Holiday setting

Schedule management

Clock display

2 permission levels

Unit model recognition

Electricity charge distribution

Visual schematic

Energy management

Group management

Error check function

System parameter querying

Report output
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Operation log

LAN access

Data backup

Remote VPN access

Languages supported English English

Dimensions (W×H×D) (mm) 251×319×66 270×183×27

Power supply 1 phase, 100-240V, 50/60Hz 24V AC

95 96
User-friendly Interface Public and Idle Devices

Simple, practical user interface makes for a user-friendly experience even for first-time users. Marking a unit as a public device or idle device ensures the electricity charge distribution is
more accurate and reasonable.

Visual Schematic

Outdoor Unit Configuration By importing floor plans and then dragging and dropping the indoor units to their actual positions on
the floor plan, users can create a tailored system schematic which enables monitoring and control of the
Outdoor unit configuration and settings can be monitored and controlled without having to go outdoors. indoor units through a clear visual representation of the system layout.

Operation Priority mode


Silent mode setting
capacity control setting Energy
setting

Electricity Charge Distribution Schedule Management

The IMMPRO uses the patented Midea Calculation Method to estimate the electricity consumption of
Daily, weekly or annual schedules can be used to set unit settings such as on/off, operating mode, set
the outdoor units and then divide it among the indoor units so that the electricity charges can be
temperature, fan speed and swing.
equitably divided among building occupants.
CONTROL SOLUTIONS

CONTROL SOLUTIONS
97 98
Xpress Installation Up to 10

With the Xpress Installation wizard, IMMPRO can be installed quickly and easily without requiring
LAN
support from a technical support engineer. Desktop

IMMPRO Gateway

Laptop
Up to 4 XYE ports

100%
WLAN Tablet
PQE

Outdoor unit

Indoor unit

Up to 64
PQE indoor units

Up to 8
refrigetant systems

Indoor

Network Flexibility IMMP-M

Up to 10

LAN
WLAN Desktop

Desktop
Desktop
CCM-270A/WS
Laptop

Up to 6 XYE ports

100%
WLAN Tablet
PQE
Laptop Fire Wall
Laptop
Internet
Internet Outdoor unit
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Indoor unit

Up to 64
or PQE
indoor units
or
100%

Up to 8
100%

refrigetant systems
Tablet M-Interface Tablet
M-Interface
Indoor

LAN access Remote VPN access CCM-270A/WS

99 100
BMS Gateway
Monitoring and control of Midea's VRF air conditioners can be integrated into building management systems, enabling air
conditioning to be monitored alongside lighting, power, fire, access and security systems. Clivet's gateway devices provide full
compatibility with the leading BMS protocols: BACnet, LonWorks and Modbus.
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Features

Model
GW-BAC

BACnet Gateway Max. number of indoor units 256

Max. number of outdoor units 128

Max. number of refrigerant systems 32

On / Off

GW-BAC Mode selection

Control Temperature setting

Full Integration Fan speed

Energy management
The GW-BAC Gateway allows Midea VRF systems to be monitored and controlled alongside other
Room temperature display
building management technology that use the BACnet protocol such as access control, fire detection
Indoor unit
and lighting systems. Error status
monitoring
Error alarms

Operating mode

Outdoor ambient temperature

Network Flexibility Fan speed

Outdoor unit Compressor operating frequency


The gateway can be connected to master outdoor units' XYE ports directly. monitoring Discharge temperature

Up to 8 refrigerant systems
System pressure

Up to Error status
X,Y,E P,Q,E P,Q,E P,Q,E
64
Error alarms

LAN access

GW-BAC BTL certification


Up to 8 refrigerant systems

Siemens APOGEE
X,Y,E P,Q,E P,Q,E Up to P,Q,E
64 TRACER
Trane
Up to 4 XYE
Ports Compatibility Honeywell ALERTON
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Schneider Andover Continuum

Up to 8 refrigerant systems Johnson Controls METASYS

LAN X,Y,E P,Q,E P,Q,E Up to P,Q,E Dimensions (HxWxD)( mm) 187×115×28


64
Power supply 1 phase, 100-240V, 50/60Hz
HUB
TCP/IP BACnet/IP protocol

Web acess BACnet BMS

103 104
Features

LonWorks Gateway Model GW-LON

Max. number of indoor units


64
GW-LON
Max. number of outdoor units 32

Full Integration Max. number of refrigerant systems 8

Mode selection
The GW-LON Gateway allows Midea VRF systems to be monitored and controlled alongside other
building management technology on the LonWorks platform such as security, fire safety and lighting Temperature setting
systems.
Control
Fan speed

Group shut down

On / Off

Network Flexibility
Operating mode

Set temperature

X,Y,E P,Q,E P,Q,E P,Q,E


Fan speed

Indoor unit

Online status
GW-LON monitoring
X,Y,E
Operating status
P,Q,E P,Q,E P,Q,E

Room temperature

Up to 64
indoor units
Error status
CONTROL SOLUTIONS

CONTROL SOLUTIONS
X,Y,E

Up to 8 P,Q,E P,Q,E P,Q,E Outdoor unit monitoring Error status


refrigerant systems

Dimensions (HxWxD)( mm) 319×251×61

Power supply 1 phase, 100-240V, 50/60Hz

LonWorks BMS

105 106
Modbus Gateway Features

GW-MOD Model GW-MOD


Full Integration
Max. number of indoor units 64

The GW-MOD Gateway enables seamless connection of Midea VRF systems with building management Max. number of outdoor units 4

systems built on the Modbus communication protocol. Max. number of refrigerant systems 1

On / Off

Mode selection
Network Flexibility
Control Temperature setting

Fan speed

Group on/off

Online status
H1H2E

Option 2 Indoor unit Room temperature


Modbus BMS monitoring
H1H2E Error status

Operating mode

Operating mode

GW-MOD Lock status

X,Y,E
Up to Fan speed
P,Q,E P,Q,E P,Q,E Outdoor unit
64
monitoring
Set temperature

Outdoor ambient temperature


Modbus TCP/IP Modbus RTU

Error status
CONTROL SOLUTIONS

CONTROL SOLUTIONS
LAN access

Dimensions (HxWxD)( mm) 319×251×61

Power supply 1 phase, 100-240V, 50/60Hz

Modbus BMS
Option 1

107 108
Hotel Key Card Interface Modules
Full Integration

The Hotel Key Card Interface Modules enable power supply to indoor units to be integrated with hotel key card power supply
management systems, which are designed to save energy by only running appliances whilst guests are present in their room.

Features

Model MD-NIM05/E MD-NIM05B/E

Appearance

CN20
CN20
Network
CN2
flexibility 220V CN2

220V
Key card
AC contactor
Key card

Auto restart
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Compatiblity Remote and wired controller Remote and wired controller

Dimensions
15.5×86×72.8 87×150×70
(H×W×D) (mm)

Power supply 5V DC (Supplied by indoor unit) 1 phase, 100-240V, 50/60Hz

Note: The Hotel Key Card Interface Modules only compatible while using the infrared communication ports of wired Controllers.

109 110
Infrared Sensor Controller Full Integration

Using infrared sensors to detect movement, the MD-NIM09 Infrared Sensor Controller automatically
turns indoor units on or off upon sensing that the room is occupied or unoccupied. Suitable for hotels,
offices, conference rooms and residences, the Infrared Sensor Controller ensures climate control
whilst minimizing energy consumption.

Features

Model MD-NIM09

Appearance

ABCDE

CN20
Wired controller
Network flexibility
CN2

CN1
control box

Infrared sensor
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Dimensions (H×W×D)(mm) Sensor 46×30×25.6, Control box 86×72.8×15.5

Power supply 5V DC (Supplied by indoor unit)

Note: The Hotel Key Card Interface Modules only compatible while using the infrared communication ports of wired Controllers.

111 112
Diagnosis Software Monitor and Diagnose

Midea’s VRF Diagnosis Software tool is used to monitor VRF systems and diagnose system errors.
System settings and operating parameters can be accessed easily and data logs can be reviewed for
fault prevention purposes.

Features

Model MCAC-DIAG-B
Max. number of indoor units 64

Max. number of outdoor units 4

Max. number of refrigerant systems 1

Mode selection

Control Temperature setting

Fan speed

Operating mode

Capacity

Compressor operating frequency

Outdoor unit Operating current


monitoring
Error status

Temperatures T3,T4,Tp (See note 1)

Valve statuses SV4, SV5, SV6, ST1 (See note 2)

EXV position

Operating mode

Capacity

Fan speed
Indoor unit
monitoring
Address
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Temperatures T1, T2, T2B, TS (See note 3)

EXV position

Error codes

Toubleshooting

Data logs

Diagrams System schematic, refregetrant flow diagram, parameter chart

Languages supported English

Notes:
1. Heat exchanger temperature, outdoor ambient temperature, discharge temperature.
2. Oil return valve, defrosting valve, EXV bypass valve, four-way valve.
3. Indoor ambient temperature, indoor heat exchanger mid-point temperature, indoor heat exchanger outlet temperature, set temperature.

113 114
Expert Diagnosis Parameter Querying

Midea’s VRF Diagnosis Software is specially designed to allow after-sales engineers, Access all the system parameters easily.
to understand the operating status of the system at a glance.

Data Logs

Use-friendly Interface
Data logs including operating records and error reports are saved by the software
which is useful for discovering system issues.
A stylish and simple interface with rich graphical representations makes diagnosing
system issues quick and convenient.

Data logs

Wiring Schematic

Diagrams

A system schematic, refregetrant flow diagram and parameter chart can be generated to provide a graphical H1H2E

interpretation of the system status.


CONTROL SOLUTIONS

CONTROL SOLUTIONS
H1H2E

MCAC-DIAG-B

X,Y,E
P,Q,E P,Q,E Up to P,Q,E
64

115 116
VRF AHU Control Box
High Efficiency Single AHU Control Box Connection

AHU Control Box facilitates raising the EER/COP of the complete AHU system. Blower, T1,T2,T2B
P,Q,E Max- 20 HP
Water pump & sensor

Wide Capacity Range Multi AHU Control Boxes Connection

Four Control Box can be used in parallel, giving an overall capacity range of 3.2HP to 80HP. P,Q,E Blower, T1,T2,T2B
Water pump & sensor

Max- 80 HP

X,Y,E

AHUKZ-01B AHUKZ-02B AHUKZ-03B


3.2-6HP 8-12HP 14-20HP

X,Y,E
Compatible with All VRF Systems

AHU Control Box are compatible with all Midea VRF outdoor units and can be used together with all types of Midea VRF indoor
units. X,Y,E

Specifications
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Model AHUKZ-01B AHUKZ-02B AHUKZ-03B

Capacity HP 3.2-6 8-12 14-20

Power supply 1 phase, 208-230V, 60Hz

Refrigerant R410A

Pipe connections (inlet and outlet) mm Φ8 Φ12.7 Φ15.9

Net dimensions (W×H×D) mm 350×150×375

Packed dimensions (W×H×D) mm 420×240×490

Net weight kg 8.4 8.7 8.9

Gross weight kg 11.4 11.7 11.9

Operating modes Cooling, heating and fan only

Standard controller Wired controller

Optional controller Wireless remote controller; SIEMENS controller

117 118
Selection Software Heat Recovery Ventilator
High Efficiency Fan Motor Options
AC and DC fan versions available.
Civet's advanced design automation tool can be used by designers, consultants and distributors to greatly reduce the time and
effort that must be devoted to the selection process. The software provides quick and convenient selectable options for users, Enhanced Efficiency
supports multiple languages, and greatly improves the selection process.
The Clievt heat recovery ventilator (HRV) can greatly reduce energy losses and room temperature fluctuations caused by the
The Selection Software provides distributors' sales team with a comprehensive selection of system design reports and ventilation process. The Midea HRV's strong performance is a result of the advanced technology incorporated into its design. The
calculations. Based on the indoor units, outdoor units and controllers selected, the software produces detailed system layout heat exchanger core is made of specially treated paper which gives enhanced temperature and humidity control. Temperature
diagrams and piping requirement calculations. exchange efficiency is over 65% and enthalpy exchange efficiency is 50-65%.

HRV-200 HRV-500 HRV-1500


HRV-300 HRV-800 HRV-2000
HRV-400 HRV-1000
Piping diagram Wiring diagram

RA
(Return air from room)
SA
14°C
SA
Heat
Moisture
Cold air
0 0°C (Supply air to room)

Moisture
EA
6°C Warm air
Heat 20°C
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Heat exchange plate

EA
(Exhaust air to outdoors)

OA
Controller selection Report (Fresh air from outdoors)

119 120
Low Noise Specifications
Soundproofing is used to guarantee quiet operation. AC Series
Flexibility Model HRV-200 HRV-300 HRV-400 HRV-500

Power supply V/Ph/Hz 220-240/1/50 220-240/1/50 & 220/1/60


Heights starting from as little as 264mm and weights from as little as 23kg mean that the Midea HRV can be easily installed even
Cooling temp. exchange efficiency (H/M/L) % 55/55/60 55/55/60 55/55/60 55/55/60
where space is limited.
Cooling enthalpy exchange efficiency (H/M/L) % 50/50/55 50/50/55 50/50/55 50/50/55

Heating temp. exchange efficiency (H/M/L) % 60/60/65 60/60/65 60/60/65 65/65/70

Heating enthalpy exchange efficiency (H/M/L) % 55/55/60 55/55/60 60/60/65 60/60/65

Sound pressure level in heat exchange mode (H/M/L) dB(A) 27/26/20 30/29/23 32/31/25 35/34/28
264mm
Sound pressure level in bypass mode (H/M/L) dB(A) 28/27/22 31/30/25 33/32/27 36/35/30

Airflow rate (H/M/L) m3/h 200/200/150 300/300/225 400/400/300 500/500/375

External static pressure (H/M/L) Pa 75/58/35 75/60/40 80/65/43 80/68/45

Multiple Modes Motor type AC

Duct diameter mm Φ144 Φ144 Φ144 Φ194

Heat exchange mode Net dimensions (WxDxH) mm 866×655×264 944×722×270 944×927×270 1038×1026×270
The flows of incoming and outgoing air pass close to each other, allowing Packed dimensions (WxDxH) mm 960×770×445 1020×810×452 1020×1020×452 1120×1120×452
heat transfer between the two channels. During summer, incoming air is
Net weight kg 23 26 31 41
cooled by the indoor air being exhausted and in winter, incoming air is
Gross weight kg 40 44 52 64
warmed.
o
Operating temperature range C -7 to 43 DB, RH 80% or lower

Heat exchange mode


Bypass mode Damper

In mild climates or seasons, where temperature and humidity differences Model HRV-800 HRV-1000 HRV-1500 HRV-2000

between indoors and outdoors are small, the HRV can work as a conventional EA RA
Power supply V/Ph/Hz 220-240/1/50 & 220/1/60 380-415/3/50 & 220/3/60
ventilation fan. In standard bypass mode the supply and exhaust fans run at Cooling temp. exchange efficiency (H/M/L) % 55/55/60 55/55/60 55 55
Element
the same speed.
OA SA Cooling enthalpy exchange efficiency (H/M/L) % 50/50/55 50/50/55 50 50

Heating temp. exchange efficiency (H/M/L) % 65/65/70 65/65/70 65 65


Air supply mode
Heating enthalpy exchange efficiency (H/M/L) % 60/60/65 60/60/65 60 60
Air supply mode is a form of bypass mode where the supply fan is set to run Bypass mode
Damper
faster than the exhaust fan, which is useful in mild climate installations with Sound pressure level in heat exchange mode (H/M/L) dB(A) 39/38/32 40/39/33 51 53

high fresh air ventilation requirements. EA RA Sound pressure level in bypass mode (H/M/L) dB(A) 40/39/34 41/40/35 52 54

Airflow rate (H/M/L) m3/h 800/800/600 1000/1000/750 1500 2000


Element
Exhaust mode External static pressure (H/M/L) Pa 100/82/54 100/85/58 160 170
OA SA
Exhaust mode is a form of bypass mode where the exhaust fan is set to run
CONTROL SOLUTIONS

CONTROL SOLUTIONS
Motor type AC
faster than the supply fan, which is useful in mild climate installations with
Duct dimensions mm Φ242 Φ242 346×326 346×326
large amounts of exhaust air to be expelled.
Net dimensions (WxDxH) mm 1286×1006×388 1286×1256×388 1600×1270×540 1650×1470×540

Auto mode Packed dimensions (WxDxH) mm 1380×1100×573 1400×1370×573 1710×1410×720 1760×1610×720

The controller chooses heat exchange mode or bypass mode according to Net weight kg 62 79 163 182
the temperature difference between outdoors and indoors. Both fans are set Gross weight kg 88 110 224 247
to run at low speed. o
-7 to 43 DB, RH 80% or lower
Operating temperature range C

Note:
1. Models HRV-200 to HRV-1000 each have have 3 airflow settings; the airflow rates of the HRV-1500 and HRV-2000 are not adjustable.
2. Sound level is measured 1.4m below the center of the unit in an semi-anechoic chamber.
3. Efficiency is measured under the following conditions:
Cooling: exhaust air temp 27°C DB, 19.5°C WB; fresh air temp. 35°C DB, 28°C WB.
Heating: exhaust air temp 21°C DB, 13°C WB; fresh air temp. 5°C DB, 2°C WB.

121 122
Specifications Branch Joints
Packed Dimensions Gross Weight
DC Series Type Appearance Model
mm kg
Note

Model HRV-D200 HRV-D300 HRV-D400 HRV-D500

Power supply V/Ph/Hz 220-240/1/50(60)

Cooling temp. exchange efficiency % 76.1 74.8 76.2 76.1

Connecting two
Cooling enthalpy exchange efficiency % 77.3 76.1 78.7 78.2 FQZHW-02N1E 255×150×185 2.0
outdoor units
Heating temp. exchange efficiency % 76.1 74.8 76.2 76.1

Heating enthalpy exchange efficiency % 82.6 79.8 83.6 80.4

Sound pressure level dB(A) 27 30 32 35


Branch joints for
3
Airflow rate m /h 200 300 400 500 outdoor units

External static pressure Pa 75 75 80 80

Motor type DC

Duct diameter mm Φ144 Φ144 Φ144 Φ194


Connecting three
FQZHW-03N1E 345×160×285 4.3
Net dimensions (WxDxH) mm 852×665×264 928×734×270 928×940×270 1020×1036×270 outdoor units

Packed dimensions (WxDxH) mm 910×710×430 980×774×435 1010×1010×440 1120×1120×452

Net weight kg 25 27 32 35

Gross weight kg 37 40 46 51

o
Operating temperature range C -7 to 43 DB, RH 80% or lower
FQZHN-01D 290×105×100 0.4 /

Model HRV-D800 HRV-D1000 HRV-D1500 HRV-D2000

Power supply V/Ph/Hz 220-240/1/50(60)


FQZHN-02D 290×105×100 0.6 /
Cooling temp. exchange efficiency % 76.9 75.8 77.8 77.2

Cooling enthalpy exchange efficiency % 78.1 76.9 79.2 78.7

Heating temp. exchange efficiency % 76.9 75.8 77.8 77.2 FQZHN-03D 310×130×125 0.9 /

Heating enthalpy exchange efficiency % 80.1 78.6 80.5 80.3

Sound pressure level dB(A) 39 40 51 53


Branch joints for
FQZHN-04D 350×180×170 1.5 /
Airflow rate 3
m /h 800 1000 1500 2000 indoor units

External static pressure Pa 100 100 160 170

Motor type DC
CONTROL SOLUTIONS

CONTROL SOLUTIONS
FQZHN-05D 365×195×215 1.9 /
Duct dimensions mm Φ242 Φ242 346×326 346×326

Net dimensions (WxDxH) mm 1276×1020×388 1276×1269×388 1600×1270×540 1650×1470×540

Packed dimensions (WxDxH) mm 1355×1045×560 1400×1370×573 1710×1410×720 1760×1610×720 FQZHN-06D 390×230×255 3.1 /

Net weight kg 58 69 151 165

HRV
Gross weight kg 77 90 184 198
FQZHN-07D 390×230×255 3.4 /
o
Operating temperature range C -7 to 43 DB, RH 80% or lower

Note:
1. All models each have have 3 airflow setting.
2. Sound level is measured 1.4m below the center of the unit in an semi-anechoic chamber.
3. Efficiency is measured under the following conditions:
Cooling: exhaust air temp 27°C DB, 19.5°C WB; fresh air temp. 35°C DB, 28°C WB.
Heating: exhaust air temp 21°C DB, 13°C WB; fresh air temp. 5°C DB, 2°C WB.

123 124