w w w. d a i k i n . e u
ENVIRONMENTAL
AWARENESS
Air Conditioning and the Environment
Air conditioning systems provide a significant level of indoor comfort, mak-
ing possible optimum working and living conditions in the most extreme
climates. In recent years, motivated by a global awareness of the need to
reduce the burdens on the environment, some manufacturers including
Daikin have invested enormous efforts in limiting the negative effects associ-
ated with the production and the operation of air conditioners. Hence, mod-
els with energy saving features and improved eco-production techniques
have seen the light of day, making a significant contribution to limiting the
impact on the environment.
2
TABLE OF CONTENTS
Introduction 4
Features 10
1. Wide Application Range 10
2. Environmental Awareness 20
3. Installation & Maintenance Friendly Design 23
Outdoor units 28
1. VRV®III 28
2. VRV®-WII 40
3. Accessories 42
Indoor units 44
1. Features 44
2. Specifications 51
Ventilation 64
1. HRV - Heat Reclaim Ventilation 64
2. FXMQ-MFV1 - Outdoor Air Processing Unit 66
3. VRV®+EXV-kit - VRV® Air Handling Applications 67
3
The History of VRV® Systems
1999
1994 The VRV® Plus series
Consistent high quality and using R-22 has been
efficiency lead to the designed around leading
wide-spread acceptance edge technologies to
of the VRV® concept accommodate high capacity
1987 and Daikin becomes air conditioning networks of
The original VRV® air 1991 the first Japanese air up to 30 indoor units from
conditioning system A further step forward is conditioning manufacturer a single refrigerant circuit.
developed by Daikin taken in 1991 with the to be awarded the ISO9001
Industries Ltd. in 1982 is introduction of the VRV® certification. Daikin applies Another step forward has
introduced into Europe heat recovery system, yet another quantum leap been taken with the launch
in VRV® standard format. offering simultaneous to VRV® technology: the of the VRV® heat recovery
VRV® D series can supply cooling and heating from VRV® Inverter-H series, series using R-407C and
conditioned air from up to 4 different indoor units on operate up to 16 indoor connecting up to 16 indoor
indoor units connected to a the same refrigeration units from just 1 outdoor units to
single outdoor unit. circuit. unit. 1 single outdoor unit.
5
What is
?
In recent years, design styles for intelligent buildings such
as hotels, banks and offices etc. have increasingly featured
large areas of glazing with attendant high solar heat gains
that can only be dissipated by means of air conditioning.
Not surprisingly therefore, air conditioning has grown in
importance and is now widely accepted as an integral
component of most modern architectural concepts.
AIR CONDITIONING
The increasing use of electronic office equipment raises
thermal loadings still further to a point whereby, even in
winter, internal temperatures can reach uncomfortable
levels. The demand for cooling or heating can also
vary considerably through-out the day depending on the
number and occupation of personnel on the premises. But
NETWORK SOLUTION
end users have come to expect far more than just cooling
and heating from their air
conditioning. VENTILATION CONTROL AND
MANAGEMENT
The ideal modern system must be energy efficient, easy
to install, flexible, reliable and user friendly. Fresh air must
be supplied without increasing energy consumption and
the role of central management facilities should also
be considered in this respect for medium to large sized
buildings. The Daikin Hi-VRV® system meets all these
demands.
6
›› Heat Reclaim Ventilation ›› Variable Refrigerant Volume
Heat and humidity are exchanged between supply and - available in cooling only, heat pump and heat
exhaust air, which recovery formats.
- brings outdoor air close to indoor air conditions - a rapid response system in which up to 64 indoor
- recovers energy loss units can operate on the same refrigerant circuit.
- realises considerable reduction of air conditioning - an inverter driven compressor enables the output
capacity of the outdoor unit to be modulated in accordance
with the cooling/heating demand of the zone which
it controls.
NETWORK SOLUTION
The ideal solution for control and management of up to 2,000 indoor units.
The ideal solution for control and management of maximum 1,024 VRV® indoor units.
Open network integration of VRV® monitoring and control functions into LonWorks®
networks.
Integrated control system for seamless connection between VRV® and BMS systems.
7
The VRV® Systems
›› VRV®III Inverter Heat Recovery
8
›› VRV®-WII Inverter Heat Recovery
9
Features
1. Wide Application Range
8,10,12HP 14,16HP
10
5HP 8,10,12HP 14,16,18HP
11
5. Wide Range of Indoor Units
VRV® air conditioning brings summer freshness and winter warmth to offices, hotels, department stores and
many other commercial premises. It enhances the indoor environment and creates a basis for increased business
prosperity and whatever the air conditioning requirement, a Daikin indoor unit will provide the answer. VRV®
air conditioning can be supplied via 13 DIFFERENT INDOOR UNIT MODELS in a total of
75 VARIATIONS.
12
Indoor units 20 25 32 40 50 63 71 80 100 125 200 250
Roundflow ceiling mounted cassette FXFQ 8 8 8 8 8 8 8 8 8
4-way blow ceiling mounted cassette FXZQ 8 8 8 8 8
2-way blow ceiling mounted cassette FXCQ 8 8 8 8 8 8 8 8
Ceiling mounted corner cassette FXKQ 8 8 8 8
Small concealed ceiling unit FXDQ 8 8
Slim concealed ceiling unit FXDQ 8 8 8 8 8 8
Concealed ceiling unit FXSQ 8 8 8 8 8 8 8 8 8
NEW Concealed ceiling unit FXMQ 8 8 8 8 8 8 8 8
Wall mounted unit FXAQ 8 8 8 8 8 8
Ceiling suspended unit FXHQ 8 8 8
4-way blow ceiling suspended unit FXUQ 8 8 8
Floor standing unit FXLQ 8 8 8 8 8 8
Concealed floor standing unit FXNQ 8 8 8 8 8 8
13
6. RA extension of the indoor range
With the new RA connection (through BP-box) it is possible to connect RA indoors to the VRVIII heat pump.
Available outdoor range: VRVIII heat pump 8 - 18 HP (single unit systems)
Connectable BP-units: BPMKS967A2/A3
No leak check function available
No automatic charging available
note: for more technical information contact your local dealer
14
7. Multi tenant function
This function ensures that the entire VRV® system doesn’t shut down
when the main power supply of an indoor is switched off.
This means that the indoor unit’s main fuse can be turned off when leaving
a hotel room, when a part of the office building is on holidays, …
TV TV TV
CARD CARD
HOLDER
220 V
CARD CARD
HOLDER
TV TV TV
15
9. integrated ventilation
Daikin offers a variety of solutions for the provision of fresh air ventilation to offices, hotels, stores and other commercial
outlets – each one complementary to and as flexible as the VRV® system itself.
›› Heat and humidity are exchanged between supply and exhaust air, which brings
- outdoor air close to indoor air conditions
- recovers energy loss
- realises considerable reduction of air conditioning capacity
›› The heat exchanger modulates the humidity and temperature of incoming fresh air to match indoor conditions.
›› The balance achieved between indoor and outdoor ambients, enables the cooling/heating load placed on the air
conditioning system to be reduced. (Heat and humidity are exchanged)
›› Most energy saving solution as smaller indoor units can be selected:
- Size down of indoor units down to 40 %
- Payback total VAM system: ±2.5 years*
*conditions:
- outside cooling conditions: 30°C / outside heating conditions: - 8°C
- Inside cooling conditions: 24°C / inside heating conditions: 22°C
- Ventilation per room: 150m3/h
16
9. Extended Piping Length
ng
ipin
g pipi
al p lent 0 m
Actu h 165 m i v a
Equ gth 19
t
leng len
VRV®III
maximum
differences up to maximum 90m are possible*.
90m
After the first branch, the difference between the
longest piping length and the shortest piping length
can be maximum 40m, provided that the longest piping
length amounts to maximum 90m.
* For more information, please contact your local Daikin dealer.
g ing
al p
ipin t pip
Actu h 120 m u i v alen 40 m
t Eq th 1
leng leng
VRV®-WII
The water-cooled VRV®-WII uses water as its heat
Actual piping length
source and since there are no limitations on water between the VRV®-WII and indoor units: 120m Water piping
(Equivalent piping length: 140m)
piping length, is eminently suitable for application to tall Refrigerant piping
multi storey or large buildings. Considerable flexibility (Total piping length: 300m)
Indoor installation
17
10. Super Silent Mode
Step 1 fixes the operating sound value at 50dBA. When the sound level of an 8HP outdoor unit is fixed at 50dBA it will
operate at 98 % of its nominal capacity. Step 2 fixes the operating sound value at 45dBA. When the sound level of the
same 8HP outdoor unit is fixed at 45dBA it will operate at 74 % of its nominal capacity.
For some applications the operating sound level of the outdoor unit might be too high. VRV®III super silent mode
however, allows the sound level to be fixed in order to avoid noise pollution.
18
12. Back-up Function
(*unfix) capacity
M
CMY
›› Designed to provide simultaneous year round cooling and/or heating, VRV® heat recovery systems
are modular in concept and are therefore, ideal for use in rooms or zones that generate varying
thermal loads according to building orientation or local hot or cold spots.
›› It is possible for the same meeting room to give rise to differing thermal loads depending on the time of day, number
of occupants present, location and usage pattern of lighting and electronic office equipment.
›› The colder it is outside, the warmer it needs to be indoors, which means that the capacity of the air-cooled
outdoor unit drops. Water-cooled air conditioners are not subject to this problem. The boiler ensures that
sufficient enough additional heat is always available indoors.
19
15. Anti Corrosion Treatment
Hydrophilic film
Aluminium
Corrosion-resistant
Acrylic resin
Heat exchanger
Performed tests:
VDA Wechseltest
8
Contents of 1 cycle (7 days):
Degree of corrosion
6
›› 24 hours salt spray test SS DIN 50021
4
›› 96 hours humidity cycle test KFW DIN 50017
2
›› 48 hours room temperature & room humidity
0
testing period : 5 cycles 1 2 3 4 5
Cycle
to DIN50018 (0.21) 6
›› testing period : 40 5
4
cycles
3
Bare
aluminium 2
1
DAIKIN P.E. 0
1 2 3 4 5 6 10 20 30 40
Cycle
20
16. Operation Range
VRV®III
Standard operation down to -20°C outdoor 50 Cooling 50 Cooling Cooling
43°CDB 43°CDB 43°CDB
ambient temperature. Advanced PI control 40 40
Cooling Cooling
of the outdoor unit enables VRV®III series to 30
Heating 15.5°CWB
30
& Heating & Heating Heating
20 20 15.5°CWB 15.5°CWB 15.5°CWB
operate at outdoor ambients down to -5°C in
10 10
Technical cooling
cooling mode and down to -20°C in heating -5 -5
Technical cooling
mode. -10
-5°CDB
-10
-5°CDB -5°CWB
-15 -15
30
VRV®-WII 20
Wide operation range of the water-cooled
10
units between 10°C & 45°C, both in cooling 10°C 10°C
and heating. 0
VRV®-WII
heat pump / heat recovery
›› Continuous research by Daikin into reducing operation sound levels has resulted in the development of a purpose
designed inverter scroll compressor and fan.
›› Daikin indoor units have very low sound operation levels, down to 25dB(A)
21
2. Environmental Awareness
1. Higher EER/COP
HP 16 18 20 22 24 26 28 30 32 34 36
8 1 1
10 1 1
12 1 1 2 1
14 1
16 1 1
18 1 1 1 1 1 1 2
EER/COP Values
HP 16 18 20 22 24 26 28 30 32 34 36
EER 3.17 3.02 3.68 3.62 3.49 3.28 3.26 3.20 3.11 3.09 3.02
COP 3.88 3.69 4.08 4.04 3.47 3.84 3.83 3.81 3.83 3.79 3.69
30 % rise
Optimised EER/COP Values
HP 16 18 20 22 24 26 28 30 32 34 36
EER 4.04 3.88 3.78 3.62 4.02 3.94 3.84 3.77 3.60 3.56 3.49
COP 4.27 4.15 4.09 4.04 3.97 4.20 4.13 4.09 4.05 4.02 3.99
Compared to previous series VRV®III has the smallest refrigerant amount in the system.
All flange and flare connections in the unit have been replaced by brazing
connections to ensure improved refrigerant containment. Brazing
22
4. Refrigerant Containment Check
The refrigerant volume of the complete system is calculated from the following data:
›› outdoor temperature
›› reference system temperatures
›› reference pressure temperatures
›› refrigerant density
›› types and number of indoor units
When activating the refrigerant containment check, the unit switches into cooling mode and duplicates certain
reference conditions based on memory data. The result indicates whether or not refrigerant leakage has occurred.
5. RoHS Compliance
Although RoHS regulations are only applicable to small and large household equipment, Daikin environmental policy
nevertheless ensures that VRV®III will be totally in line with RoHS.
6. Inverter Technology
The linear VRV® system makes use of a variable Proportional Integral (PI) control system which uses refrigerant pressure
sensors to give added control over inverter and ON/OFF control compressors in order to abbreviate control steps into
smaller units to provide precise control in both small and larger areas. This in turn enables individual control of up to
60 indoor units of different capacity and type at a ratio of 50~200 % in comparison with outdoor units capacity. 5 HP
outdoor units use inverter control compressors only. VRV® systems have low running costs because it permits each zone
to be controlled individually. That is, only those rooms that require air conditioning will be heated or cooled, while the
system can be shut down completely in rooms where no air conditioning is required.
18 Steps 24 Steps
1 1
24% 19%
Load Load
Small Large Small Large
1 1
1
Compressor Capacity Control
1 3 1 3
14%
1 2 10%
1 2 2 9%
1 2 2
Load Load Load
Small Large Small Large Small Large
23
7. Smart Control Brings Comfort
Cooling
Slow start
Temperature remains stable VRV® SERIES (DAIKIN PID Controls)
ON/OFF controlled air conditioner (2.5HP)
Air conditioning
with Inverter
Note: the graph shows the data, measured in a test room assuming actual heating load.
Air conditioning without
Inverter
24
3. Installation &
Maintenance Friendly
Design
1. Automatic Charge Function
Conventional Way:
1. calculation of additional refrigerant charging volume
2. charging the unit with additional refrigerant
3. measuring the weight of the cylinder
4. judgment based on pressure (test operation)
VRV ®III
With VRV®III however, these 4 steps are omitted since VRV®III unit can be
charged with the necessary amount of refrigerant automatically via a push
Indoor temperature
button on the PCB. Automatic charging will cease once the appropriate
32°C
amount of refrigerant has been transferred.
Automatic
charge
If temperature drops below 10°C manual charging is necessary. After function
10°C
having switched to heating and once the indoor temperature rises above
Manual
10°C, push the auto charge button to activate auto charge function. charge
Refrigerant containment is only available after performing the automatic
Outdoor temperature
charge function. 0°C 43°C
2. Automatic Test
When refrigerant charging has ceased, pushing the test operation button
on the PCB will initiate a check on the wiring, shut off valves, sensors and
refrigerant volume. This test ceases automatically when completed.
3. Easy Maintenance
25
4. Duty Cycling
Thanks to small refrigerant pipes and REFNET piping options, the VRV®
piping system can be installed very easily and quickly.
26
8. Refrigerant Piping
Around 30%
reduction in
installation
costs for
refrigerant piping.
›› VRV®-WII System
Max. 32 indoor units
R-410A
H2O
27
9. Unified REFNET piping
The unified Daikin REFNET piping system is especially designed for simple
installation
REFNET joint Attached insulators for REFNET joint
The use of REFNET piping in combination with electronic expansion
valves, results in a dramatic reduction in imbalance in refrigerant flowing
between indoor units, despite the small diameter of the piping.
REFNET header Attached insulators
REFNET joints and headers (both accessories) can cut down on installation for REFNET header
The cross wiring check facility available on the VRV® is the first of its type
in the industry to warn operatives of connection errors in inter unit wiring
and piping. This function identifies and alerts system errors by means of
on/off LEDs on the outdoor unit’s PC boards.
28
13. “Super Wiring” System
Wiring can be fed from the front panel, both left and right side panels and
bottom panel of the outdoor unit.
Left
Right
Front
15. Auto Address Setting Function
Bottom
Allows wiring between indoor and outdoor units, as well as group control
wiring of multiple indoor units, to be performed without the bothersome
task of manually setting each address.
29
Outdoor Units
1. VRV®III
1. VRV®III Technology
40
AC motor
20
0
200 300 400 500 600 700 800 900 1000
Motor speed (rpm)
30
4
3
5
10
›› Increased output and reduced pressure loss 8.1
Three-dimensional integrated woven soft
Internal resistance (mmH2O)
1.3
Increased heat exchange area
4.9 2.5 • Increase in heat exchange effectiveness
0 VRV®II VRV®III
Substantial reduction in pressure loss
prevents heat transferring from the overheated gas 27°C 55°C 27°C
37°C 43°C
55°C
section towards the sub cooled liquid section - a 27°C 55°C 27°C 60°C
more efficient use of the heat exchanger. 27°C 50°C 27°C 55°C
OUT 45°C
6 i-Demand Function
consumption (KVV)
31
2. VRV®III HEAT RECOVERY
REYQ-P8 8 10 12 14 16 18 20 22 24 26 28
Modules REYQ8P8 1
REYQ10P8 1
REYQ12P8 1 Not Applicable
REYQ14P8 1
REYQ16P8 1
Modules REMQ8P8 1 1
REMQ10P8 1 1 1
REMQ12P8 Not Applicable 1 1 2 1
REMQ14P8
REMQ16P8 1 1
Number of outdoor units 1 1 1 1 1 2 2 2 2 2 2
Equivalent horsepower HP 8 10 12 14 16 18 20 22 24 26 28
Capacity cooling kW 22.4 28 33.5 40 45 50.4 55.9 61.5 67.0 73.0 78.5
heating kW 25 31.5 37.5 45 50 56.5 62.5 69 75 81.5 87.5
Nominal input cooling kW 5.46 7.09 9.08 11.4 14.1 13.0 15.2 17.0 19.2 21.6 23.8
heating kW 5.81 7.38 8.93 11.0 12.8 13.6 15.3 17.1 18.9 20.6 22.3
EER cooling 4.10 3.95 3.69 3.51 3.19 3.88 3.68 3.61 3.49 3.38 3.3
COP heating 4.30 4.27 4.20 4.10 3.90 4.15 4.08 4.03 3.97 3.96 3.92
Max. number of connectable indoor units 13 16 19 22 26 29 32 35 39 42 45
Minimum capacity index 100 125 150 175 200 225 250 275 300 325 350
Maximum capacity index - 130 % 260 325 390 455 520 585 650 715 780 845 910
Capacity steps 30 37 37 26 26 31 31 38 38 41 41
Dimensions height mm 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680
width mm 1,300 1,300 1,300 1,300 1,300 930 + 930 930 + 930 930 + 930 930 + 930 930 + 1,240 930 +1,240
depth mm 765 765 765 765 765 765 765 765 765 765 765
Weight kg 331 331 331 339 339 204 + 254 204 + 254 254 + 254 254 + 254 254 + 334 254 + 334
Casing painted galvanised steel
Colour ivory white
Sound pressure level dB(A) 58 58 60 62 63 61 62 62 63 62 63
Sound power level dB(A) * * * * * 81.0 82.0 82.0 83.0 82.0 83.0
Fan type propeller fan
air flow rate 190 190 210 235 240 180 + 185 180 + 200 185 + 200 200 + 200 185 + 230 200 + 230
Refrigerant name R-410A
charge kg 10.3 10.6 10.8 11.1 11.1 8.2 + 9.0 8.2 + 9.1 9.0 + 9.1 9.1 + 9.1 9.0 + 11.7 9.1 + 11.7
control electronic expansion valve
Refrigerant oil type synthetic ether oil
charge l * * * * * 8.2 8.4 10.4 10.6 12.6 12.8
Compressor type hermetically sealed scroll compressor
starting method soft start
Piping connections liquid mm 9.52 9.52 12.7 12.7 12.7 15.9 15.9 15.9 15.9 19.1 19.1
gas mm 19.1 22.2 28.6 28.6 28.6 28.6 28.6 28.6 34.9 34.9 34.9
discharge gas mm 15.9 19.1 19.1 22.2 22.2 22.2 28.6 28.6 28.6 28.6 28.6
pressure equalizer tube mm none none none none none 19.1 19.1 19.1 19.1 19.1 19.1
Operation range cooling °CDB -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43
heating °CWB -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5
Power supply W1 3~, 50Hz, 380-415V
Safety devices HPS, fan motor overcurrent protector, inverter overload protector, overcurrent relay, PC board fuse
32
REYQ-P8 30 32 34 36 38 40 42 44 46 48
Modules REYQ8P8
REYQ10P8
REYQ12P8 Not Applicable
REYQ14P8
REYQ16P8
Modules REMQ8P8 1 1
REMQ10P8 1 1 1
REMQ12P8 1 1 2 1
REMQ14P8 1 1
REMQ16P8 1 2 1 1 1 1 2 2 2 3
Number of outdoor units 2 2 3 3 3 3 3 3 3 3
Equivalent horsepower HP 30 32 34 36 38 40 42 44 46 48
Capacity cooling kW 85.0 90.0 95.4 101.0 107.0 112.0 118.0 124.0 130.0 135.0
heating kW 95 100 107 113 119 125 132 138 145 150
Nominal input cooling kW 26.6 28.4 27.2 29.4 31.2 33.4 35.8 38.0 40.8 42.6
heating kW 24.2 25.8 26.5 28.2 30.0 31.8 33.5 35.2 37.1 38.7
EER cooling 3.2 3.17 3.51 3.43 3.43 3.35 3.3 3.26 3.19 3.17
COP heating 3.93 3.88 4.04 4.01 3.97 3.93 3.94 3.92 3.91 3.88
Max. number of connectable indoor units 48 52 55 58 61 64 64 64 64 64
Minimum capacity index 375 400 425 450 475 500 525 550 575 600
Maximum capacity index - 130 % 975 1,040 1,105 1,170 1,235 1,300 1,365 1,430 1,495 1,560
Capacity steps 46 46 36 36 41 41 46 46 51 51
Dimensions height mm 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680
width mm 1,240 + 1,240 1,240 + 1,240 930 + 930 + 1,240 930 + 930 + 1,240 930 + 930 + 1,240 930 + 930 + 1,240 930 + 1,240 + 1,240 930 + 1,240 + 1,240 1,240 + 1,240 + 1,240 1,240 + 1,240 + 1,240
depth mm 765 765 765 765 765 765 765 765 765 765
Weight kg 334 + 334 334 + 334 204 + 254 + 334 204 + 254 + 334 254 + 254 + 334 254 + 254 + 334 254 + 334 + 334 254 + 334 + 334 334 + 334 + 334 334 + 334 + 334
Casing painted galvanised steel
Colour ivory white
Sound pressure level dB(A) 63 63 63 64 64 65 64 65 65 65
Sound power level dB(A) 83.0 83.0 83.0 84.0 84.0 85.0 84.0 85.0 85.0 85.0
Fan type propeller fan
air flow rate 230 + 230 230 + 230 180 + 185 + 230 180 + 200 + 230 185 + 200 + 230 200 + 200 + 230 185 + 230 + 230 200 + 230 + 230 230 + 230 + 230 230 + 230 + 230
Refrigerant name R-410A
charge kg 11.7 + 11.7 11.7 + 11.7 8.2 + 9.0 + 11.7 8.2 + 9.1 + 11.7 9.0 + 9.1 + 11.7 9.1 + 9.1 + 11.7 9.0 + 11.7 + 11.7 9.1 + 11.7 + 11.7 11.7 + 11.7 + 11.7 11.7 + 11.7 + 11.7
control electronic expansion valve
Refrigerant oil type synthetic ether oil
charge l 14.9 15.0 15.7 15.9 17.9 18.1 20.1 20.3 22.4 22.5
Compressor type hermetically sealed scroll compressor
starting method soft start
Piping connections liquid mm 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1
gas mm 34.9 34.9 34.9 41.3 41.3 41.3 41.3 41.3 41.3 41.3
discharge gas mm 28.6 28.6 28.6 28.6 34.9 34.9 34.9 34.9 34.9 34.9
pressure equalizer tube mm 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1
Operation range cooling °CDB -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43
heating °CWB -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5
Power supply W1 3~, 50Hz, 380-415V
Safety devices HPS, fan motor overcurrent protector, inverter overload protector, overcurrent relay, PC board fuse
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m • level difference: 0m
• Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB/6°CWB • equivalent refrigerant piping: 7.5m • level difference: 0m
33
3. VRV®III HEAT PUMP - HIGH COP COMBINATION
Combination RXYQ8P7W1B 2 1
RXYQ10P7W1B 1 2 1
RXYQ12P7W1B 1
Nominal capacity cooling kW 44.8 50.4 56.0 61.5
heating kW 50.0 56.5 63.0 69.0
COP cooling 4.04 3.88 3.78 3.62
heating 4.27 4.15 4.09 4.04
Capacity range HP 16 18 20 22
Power input (nominal) cooling kW 11.1 13.0 14.8 17.0
heating kW 11.7 13.6 15.4 17.1
Max n° of indoor units to be connected 26 29 32 35
Indoor index connection minimum 200 225 250 275
maximum 520 585 650 715
Casing colour Daikin White
material Painted galvanised steel
Fan type Propeller
air flow rate cooling m /min
3
171 + 171 171 + 185 185 + 185 185 + 185
(nominal at 230V) heating m /min
3
171 + 171 171 + 185 185 + 185 185 + 185
external static pressure (MAX) Pa 78Pa in high static pressure
Compressor type Hermetically sealed scroll compressor
Operation range cooling minimum °CDB -5.0 -5.0 -5.0 -5.0
maximum °CDB 43.0 43.0 43.0 43.0
heating minimum °CWB -20.0 -20.0 -20.0 -20.0
maximum °CWB 15.0 15.0 15.0 15.0
Refrigerant type R-410A
charge kg 7.7 + 7.7 7.7 + 8.4 8.4 + 8.4 8.4 + 8.6
control Expansion valve (electronic type)
Maximum total refrigerant charge in the system kg Less than 100 (calculated charge less than 95)
Refrigerant Oil type Synthetic (ether) oil
charged Volume l 2.1 + 2.1 2.1 + 3.9 3.9 + 3.9 3.9 + 3.9
Piping Connections liquid type Braze connection
diameter (OD) mm 12.7 15.9 15.9 15.9
gas type Braze connection
diameter (OD) mm 28.6 28.6 28.6 28.6
heat insulation Both liquid and gas pipes
max. total length m 1,000 1,000 1,000 1,000
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control method Inverter controlled
Capacity control [%] ~ 100 ~ 100 ~ 100 ~ 100
Safety devices HPS, fan motor driver overload protector, overcurrent relay, inverter overload protector, PC board fuse
Power supply name W1 W1 W1 W1
phase 3N~ 3N~ 3N~ 3N~
frequency Hz 50 50 50 50
voltage V 400 400 400 400
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent systems,
each containing less than 95 kg refrigerant charge. For factory charge, refer to the namplate of the unit.
34
RXYQ-P RXYQ24P7W1B RXYQ26P7W1B RXYQ28P7W1B RXYQ30P7W1B RXYQ32P7W1B RXYQ34P7W1B RXYQ36P7W1B
Combination RXYQ8P7W1B 3 2 1 1
RXYQ10P7W1B 1 2 3 1
RXYQ12P7W1B 2 2 3
Nominal capacity cooling kW 67.2 72.8 78.4 84.0 89.4 95.0 101.0
heating kW 75.0 81.5 88.0 94.5 100.0 107.0 113.0
COP cooling 4.02 3.94 3.84 3.77 3.60 3.56 3.49
heating 3.97 4.20 4.13 4.09 4.05 4.02 3.99
Capacity range HP 24 26 28 30 32 34 36
Power input (nominal) cooling kW 16.7 18.5 20.4 22.3 24.8 26.7 28.9
heating kW 18.9 19.4 21.3 23.1 24.7 26.6 28.3
Max n° of indoor units to be connected 39 42 45 48 52 55 58
Indoor index connection minimum 300 325 350 375 400 425 450
maximum 780 845 910 975 1,040 1,105 1,170
Casing colour Daikin White
material Painted galvanised steel
Fan type Propeller Propeller Propeller Propeller Propeller Propeller Propeller
air flow rate cooling m /min
3
171 + 171 + 171 171 + 171 + 185 171 + 185 + 185 185 + 185 + 185 171 + 196 + 196 185 + 196 + 196 196 + 196 + 196
(nominal at 230V) heating m /min
3
171 + 171 + 171 171 + 171 + 185 171 + 185 + 185 185 + 185 + 185 171 + 196 + 196 185 + 196 + 196 196 + 196 + 196
external static pressure (MAX) Pa 78Pa in high static pressure
Compressor type Hermetically sealed scroll compressor
Operation range cooling minimum °CDB -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0
maximum °CDB 43.0 43.0 43.0 43.0 43.0 43.0 43.0
heating minimum °CWB -20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0
maximum °CWB 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Refrigerant type R-410A
charge kg 7.7 + 7.7 + 7.7 7.7 + 7.7 + 8.4 7.7 + 8.4 + 8.4 8.6 + 8.6 + 8.6 7.7 + 8.6 + 8.6 8.4 + 8.6 + 8.6 8.6 + 8.6 + 8.6
control Expansion valve (electronic type)
Maximum total refrigerant charge in the system kg Less than 100 (calculated charge less than 95)
Refrigerant Oil type Synthetic (ether) oil
charged volume l 2.1 + 2.1 + 2.1 2.1 + 2.1 + 3.9 2.1 + 3.9 + 3.9 3.9 + 3.9 + 3.9 2.1 + 3.9 + 3.9 3.9 + 3.9 + 3.9 3.9 + 3.9 + 3.9
Piping Connections liquid type Braze connection
diameter (OD) mm 15.9 19.1 19.1 19.1 19.1 19.1 19.1
gas type Braze connection
diameter (OD) mm 34.9 34.9 34.9 34.9 34.9 34.9 41.3
heat insulation Both liquid and gas pipes
max. total length m 1,000 1,000 1,000 1,000 1,000 1,000 1,000
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control method Inverter controlled
Capacity control [%] ~ 100 ~ 100 ~ 100 ~ 100 ~ 100 ~ 100 ~ 100
Safety devices HPS, fan motor driver overload protector, overcurrent relay, inverter overload protector, PC board fuse
Power supply name W1 W1 W1 W1 W1 W1 W1
phase 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
frequency Hz 50 50 50 50 50 50 50
voltage V 400 400 400 400 400 400 400
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent systems,
each containing less than 95 kg refrigerant charge. For factory charge, refer to the namplate of the unit.
35
5. VRV®III HEAT PUMP - SMALL FOOTPRINT COMBINATION
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are measured in a semi-anechoic room.
36
RXYQ-P(A) RXYQ20P7W1B RXYQ22P7W1B RXYQ24P7W1B RXYQ26P7W1BA RXYQ28P7W1BA RXYQ30P7W1BA RXYQ32P7W1BA RXYQ34P7W1BA RXYQ36P7W1BA
Combination RXYQ8P7W1B 1 1
RXYQ10P7W1B 1 1
RXYQ12P7W1B 1 1 2 1
RXYQ14P7W1BA 1
RXYQ16P7W1BA 1
RXYQ18P7W1BA 1 1 1 1 1 2
Nominal capacity cooling kW 55.9 61.5 67.0 71.4 77.0 82.5 89.0 94.0 98.0
heating kW 62.5 69.0 75.0 81.5 88.0 94.0 102.0 107.0 113.0
COP cooling 3.68 3.62 3.49 3.28 3.26 3.20 3.11 3.09 3.02
heating 4.08 4.04 3.97 3.84 3.83 3.81 3.83 3.79 3.69
Capacity range HP 20 22 24 26 28 30 32 34 36
Power input (nominal) cooling kW 15.2 17.0 19.2 21.8 23.6 25.8 28.6 30.4 32.4
heating kW 15.3 17.1 18.9 21.2 23.0 24.7 26.6 28.2 30.6
Max n° of indoor units to be connected 32 35 39 42 45 49 52 55 58
Indoor index connection minimum 250 275 300 325 350 375 400 425 450
maximum 650 715 780 845 910 975 1,040 1,105 1,170
Casing colour Daikin White
material Painted galvanised steel
Fan type Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller
air flow rate cooling m /min
3
171 + 196 185 + 196 196 + 196 171 + 239 185 + 239 196 + 239 233 + 239 233 + 239 239 + 239
(nominal at 230V) heating m /min
3
171 + 196 185 + 196 196 + 196 171 + 239 185 + 239 196 + 239 233 + 239 233 + 239 239 + 239
External static pressure (MAX) Pa 78Pa in high static pressure
Compressor type Hermetically sealed scroll compressor
Operation range cooling minimum °CDB -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0
maximum °CDB 43.0 43.0 43.0 43.0 43.0 43.0 43.0 43.0 43.0
heating minimum °CWB -20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0
maximum °CWB 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Refrigerant type R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
charge kg 7.7 + 8.6 8.4 + 8.6 8.6 + 8.6 7.7 + 11.7 8.4 + 11.7 8.6 + 11.7 11.3 + 11.7 11.5 + 11.7 11.7 + 11.7
control Expansion valve (electronic type)
Maximum total refrigerant charge in the system kg Less than 100 (calculated charge less than 95)
Refrigerant Oil type Synthetic (ether) oil
charged volume l 2.1 + 3.9 3.9 + 3.9 3.9 + 3.9 2.1 + 5.8 3.9 + 5.8 3.9 + 5.8 5.7 + 5.8 5.7 + 5.8 5.8 + 5.8
Piping Connections liquid type Braze connection
diameter (OD) mm 15.9 15.9 15.9 19.1 19.1 19.1 19.1 19.1 19.1
gas type Braze connection
diameter (OD) mm 28.6 28.6 34.9 34.9 34.9 34.9 34.9 34.9 41.3
heat insulation Both liquid and gas pipes
max. total length m 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control method Inverter controlled
Capacity control [%] ~ 100 ~ 100 ~ 100 ~ 100 ~ 100 ~ 100 ~ 100 ~ 100 ~ 100
Safety devices HPS, fan motor driver overload protector, overcurrent relay, inverter overload protector, PC board fuse
Power supply name W1 W1 W1 W1 W1 W1 W1 W1 W1
phase 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
frequency Hz 50 50 50 50 50 50 50 50 50
voltage V 400 400 400 400 400 400 400 400 400
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent systems,
each containing less than 95 kg refrigerant charge. For factory charge, refer to the namplate of the unit.
37
RXYQ-P(A) RXYQ38P7W1BA RXYQ40P7W1BA RXYQ42P7W1BA RXYQ44P7W1BA RXYQ46P7W1BA RXYQ48P7W1BA RXYQ50P7W1BA RXYQ52P7W1BA RXYQ54P7W1BA
Combination RXYQ8P7W1B 1 1
RXYQ10P7W1B 1 1
RXYQ12P7W1B 1 1 2 1
RXYQ14P7W1BA 1
RXYQ16P7W1BA 1
RXYQ18P7W1BA 1 1 1 2 2 2 2 2 3
Nominal capacity cooling kW 105.0 111.0 116.0 120.0 126.0 132.0 138.0 143.0 147.0
heating kW 119.0 126.0 132.0 138.0 145.0 151.0 158.0 163.0 170.0
COP cooling 3.34 3.34 3.28 3.16 3.17 3.14 3.08 3.07 3.02
heating 3.89 3.89 3.86 3.78 3.79 3.78 3.77 3.75 3.70
Capacity range HP 38 40 42 44 46 48 50 52 54
Power input (nominal) cooling kW 31.4 33.2 35.4 38.0 39.8 42.0 44.8 46.6 48.6
heating kW 30.6 32.4 34.2 36.5 38.3 40.0 41.9 43.5 45.9
Max n° of indoor units to be connected 61 64 64 64 64 64 64 64 64
Indoor index connection minimum 475 500 525 550 575 600 625 650 675
maximum 1,235 1,300 1,365 1,430 1,495 1,560 1,625 1,690 1,755
Casing colour Daikin White
material Painted galvanised steel
Fan type Propeller
air flow rate cooling m /min 3
171 + 196 + 239 185 + 196 + 239 196 + 196 + 239 171 + 239 + 239 185 + 239 + 239 196 + 239 + 239 233 + 239 + 239 233 + 239 + 239 239 + 239 + 239
(nominal at 230V) heating m /min 3
171 + 196 + 239 185 + 196 + 239 196 + 196 + 239 171 + 239 + 239 185 + 239 + 239 196 + 239 + 239 233 + 239 + 239 233 + 239 + 239 239 + 239 + 239
external static pressure (MAX) Pa 78 Pa in high static pressure
Compressor type Hermetically sealed scroll compressor
Operation range cooling minimum °CDB -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0
maximum °CDB 43.0 43.0 43.0 43.0 43.0 43.0 43.0 43.0 43.0
heating minimum °CWB -20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0
maximum °CWB 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Refrigerant type R-410A
charge kg 7.7 + 8.6 + 11.7 8.4 + 8.6 + 11.7 8.6 + 8.6 + 11.7 7.7 + 11.7 + 11.7 8.4 + 11.7 + 11.7 8.6 + 11.7 + 11.7 11.3 + 11.7 + 11.7 11.5 + 11.7 + 11.7 11.7 + 11.7 + 11.7
control Expansion valve (electronic type)
Maximum total refrigerant charge in the system kg Less than 100 (calculated charge less than 95)
Refrigerant Oil type Synthetic (ether) oil
charged Volume l 2.9 + 3.9 + 5.8 3.9 + 3.9 + 5.8 3.9 + 3.9 + 5.8 2.1 + 5.8 + 5.8 3.9 + 5.8 + 5.8 3.9 + 5.8 + 5.8 5.7 + 5.8 + 5.8 5.7 + 5.8 + 5.8 5.8 + 5.8 + 5.8
Piping Connections liquid type Braze connection
diameter (OD) mm 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1
gas type Braze connection
diameter (OD) mm 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3
heat Insulation Both liquid and gas pipes
max. total length m 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control method Inverter controlled
Capacity control [%] ~ 100 ~ 100 ~ 100 ~ 100 ~ 100 ~ 100 ~ 100 ~ 100 ~ 100
Safety devices HPS, fan motor driver overload protector, overcurrent relay, inverter overload protector, PC board fuse
Power supply name W1 W1 W1 W1 W1 W1 W1 W1 W1
phase 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
frequency Hz 50 50 50 50 50 50 50 50 50
voltage V 400 400 400 400 400 400 400 400 400
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent systems,
each containing less than 95 kg refrigerant charge. For factory charge, refer to the nameplate of the unit.
38
6. VRV®III COOLING ONLY
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are measured in a semi-anechoic room.
39
2. VRV®-WII
1. VRV®-WII Technology
Neodymium magnet
3 i-Demand Function
consumption
Power
(KVV)
40
2. VRV®-WII HEAT RECOVERY / HEAT PUMP
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • inlet water temperature: 30°C • equivalent refrigerant piping: 7.5m • level difference: 0m
• Nominal heating capacities are based on: indoor temperature: 20°CDB • inlet water temperature: 20°C • equivalent refrigerant piping: 7.5m • level difference: 0m
• This unit should not be installed outdoors, but indoors eg. in a machine room, etc.
• Indoor operating ambient temperature: 0 ~ 40°C. Heat rejection from the outdoor unit: 0,71kW/10HP
• *Dimensions of 20HP and 30HP units depend on the method of stacking
• **Data were not available at the time of publication
41
3. ACCESSORIES
42
VRV®-WII HEAT PUMP RWEYQ10M RWEYQ20M RWEYQ30M
Cool/heat selector KRC19-26A
Fixing box KJB111A
KHRQ22M29H KHRQ22M29H KHRQ22M29H
REFNET header - KHRQ22M64H KHRQ22M64H
- KHRQ22M75H KHRQ22M75H
KHRQ22M20T KHRQ22M20T KHRQ22M20T
KHRQ22M29T KHRQ22M29T KHRQ22M29T
REFNET joint
- KHRQ22M64T KHRQ22M64T
- KHRQ22M75T KHRQ22M75T
Outdoor unit multi piping connection kit - BHFP22MA56 BHFP22MA84
Strainer kit BWU26A15, BWU26A20
External control adapter for outdoor unit DTA104A62
43
Indoor Units
1. Features
FXFQ-P Round Flow ceiling mounted cassette
20-25-32-40-50-63-80- Comfort
100-125 ›› Modern style decoration panel in white (RAL9010)
›› 360° air discharge ensures uniform air flow and temperature
distribution
›› Air discharge from the corners avoids dead zones that may be subject
to temperature differences
›› Comfortable horizontal air discharge ensures draughtfree operation
and prevents ceiling soiling
›› 23 different air flow patterns possible
›› Fresh air intake: up to 20%
20-25-32-40-50 Comfort
›› Modern style decoration panel in white (RAL9010) Ceiling void
is 295 mm
›› Extremely quiet in operation
0°
›› Excellent low draught characteristics. Since the flaps can move to a 0°
60°
position, virtually no draught can be experienced
›› Any one of 5 different air flow patterns can be freely selected between
0° and 60° and will then be maintained during the operational cycle
of the air conditioner
Comfort
20-25-32-40-50-63-
›› Quiet in operation
80-125
›› Leaves maximum floor and wall space for furniture, decorations and
fittings
›› Automatic air flow director ensures uniform air flow and temperature
distribution
›› Anti-ceiling soiling technology
Filter
›› Standard long life filter
Flexible Installation and Easy Maintenance
minimum ceiling
›› Easy installation in false ceilings of only 355mm height is 355mm
20-32-40-63 Comfort
›› Equipped with special draught prevention and anti-ceiling soiling
technology
1 2 3
Standard Draught Anti-ceiling
prevention soiling technology
›› Automatic air flow director ensures uniform air flow and temperature
distribution
›› Air flow by either downward air discharge, frontal discharge or a
combination of both Combination
Frontal discharge
Downward discharge
Flexible Installation
›› Compact dimensions, can easily be mounted in a narrow ceiling void
(only 220mm ceiling space required, 195 with Panel spacer
20 mm 500 mm
45
FXDQ-M8 Small concealed ceiling unit
20-25 Comfort
›› Designed for hotel bedrooms
›› Blends unobtrusively with any interior décor: only the suction and
discharge grilles are visible
›› Extremely quiet in operation
Filter
›› Air suction filter fitted as standard
Flexible Installation
›› Compact dimensions (230mm high & 652mm deep), can easily be
mounted in a ceiling void
›› The air suction direction can be altered from rear to bottom suction
›› For easy mounting, the drain pan can be located to the left or the
right of the unit
20-25-32-40-50-63 Comfort
›› Quiet in operation
›› Blends unobtrusively with any interior décor
›› Leaves maximum floor and wall space for furniture, decorations and
fittings
Flexible Installation
›› Slim design, can easily be mounted in a ceiling void of only 240mm
Ceiling
46
FXSQ-M8 Concealed ceiling unit
20-25-32-40-50-63- Comfort
80-100-125 ›› High flexibility for a wide variety of applications
›› Quiet in operation
›› Blends unobtrusively with any interior décor
Filter
›› Long life filter fitted as standard
›› High efficiency filters (65% and 95%) available as accessory
40-50-63-80-100-125- Comfort
200-250 ›› Leaves maximum floor and wall space for furniture, decorations and
fittings
Flexible Installation
›› Compact unit (a height of 300 mm), allows installation in narrow ceiling
voids
›› More than 200 Pa external static pressure allows extensive ductwork
runs and flexible application: ideal for use in large areas
›› Built-in drain pump (standard for sizes 40 to 125) increases reliability of
the drain system
›› Complete range of models (FXMQ-PVE: 4.5 - 14 kW)
(FXMQ-MAVE: 22.40 - 28 kW)
›› Possibility to change ESP through wired remote control allows
optimisation of the supply air volume
›› Reduction of power consumption of 20 % (compared to FXMQ-MAVE
series) through use of new DC Fan
47
FXAQ-MA Wall mounted unit Ä
Ä
20-25-32-40-50-63 Comfort
Ä
Ä
(initial setting 10 degrees for cooling and 70 degrees for heating) 70° Heating
Filter
›› Mildew proof polystyrene filter and drain pan
Height of drain-up
1,000mm
Drain-up kit
Indoor unit
Drain-up kit
32-63-100 Comfort
›› Quiet in operation
›› Leaves maximum floor and wall space for furniture, decorations and
fittings
›› Enhanced horizontal and vertical air circulation in all directions thanks
to an air flow pattern of 100°
100°
Filter
›› Long life filter fitted as standard
48
FXUQ-MA 4-way blow ceiling suspended unit
71-100-125 Comfort
›› Group control with other VRV® indoor units possible
›› Cool heat selection
›› Prevention of cold draught at hot start, defrost and oil return in
heating
›› Air can be discharged in any of 4 directions
›› Air can be discharged at 5 different angles between 0 and
60 degrees
Filter
›› Air filter, drain pan and heat exchanger fin are mildew proof and anti-
bacterial treated
Flexible Installation
›› Ideal for installation in new and existing buildings
›› 5m maximum distance between FXUQ unit and junction box
›› Possibility to shut 1 or 2 flaps for easy installation in corners
›› Drain-up pump with 500mm lift fitted as standard
49
FXLQ-MA Floor standing unit
Comfort
20-25-32-40-50-63
›› Ideal for installation beneath a window
›› Compact dimensions (only 222mm deep and 600mm high)
›› All models are available with remote control
Filter
›› Long life filter fitted as standard
20-25-32-40-50-63 Comfort
›› Ideal for perimeter air conditioning
›› Ideal for installation below a window
›› All models are available with remote control
Filter
›› Long life filter fitted as standard
Connecting
port
Refrigerant
piping
50
2. specifications & accessories
FXFQ-P
Roundflow ceiling mounted cassette
specifications
FXFQ-P 20 25 32 40 50 63 80 100 125
cooling kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0
Capacity
heating kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0
cooling kW 0.053 0.063 0.083 0.095 0.120 0.173 0.258
Power input
heating kW 0.045 0.055 0.067 0.114 0.108 0.176 0.246
Dimensions (H x W x D) mm 204 x 840 x 840 246 x 840 x 840 288 x 840 x840
Weight unit kg 20.0 21.0 24.0 26.0
Casing Galvanised steel
cooling high / low m3 /min 12.5 / 9.0 13.5 / 9.0 15.5 / 10.0 16.5 / 11.0 23.5 / 14.5 26.5 / 17.0 33.0 / 20.0
Air Flow Rate
heating high / low m3 /min 12.5 / 9.0 13.5 / 9.0 15.0 / 9.5 17.5 / 12.0 23.5 / 14.5 28.0 / 17.5 33.0 / 20.0
Sound power (nominal) cooling dB(A) 49 50 51 52 55 58 61
cooling high / low dB(A) 31 / 28 32 / 28 33 / 28 34 / 29 38 / 32 41 / 33 44 / 34
Sound pressure
heating high / low dB(A) 31 / 28 32 / 28 33 / 28 36 / 30 38 / 32 42 / 34 44 / 34
Refrigerant name R-410A
Power Supply 1~ / 220-240V / 50Hz
Piping Connections L / G / D diameter mm 6.35 / 12.7 / 32 6.4 / 12.7 / 32 9.5 / 15.9 / 32
Air Filter Resin net with mold resistance
Drain-up Height mm 750
model BYCQ140CW1
colour RAL9010
Decoration Panel
(H x W x D) mm 50x950x950
weight kg 5.5
Notes:
The sound pressure values are mentioned for a unit installed with rear suction
The sound power level is an absolute value indicating the power wich a sound source generates.
Nominal cooling capacities are based on: indoor temperature: 270CDB, 190CWB, outdoor temperature: 350CDB, equivalent refrigerant piping: 5m, level difference: 0m.
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Accessories
FXFQ-P 20 25 32 40 50 63 80 125
Wired remote control BRC1D52
Infrared remote control cooling only BRC7F533F
heat pump BRC7F532F
Decoration panel BYCQ140CW1
Replacement long life filter (non-woven type) KAFP551K160
Fresh air intake kit (20 % fresh air intake) (chamber type) KDDQ5C140
Air discharge outlet sealing member KDBHQ55C140
51
FXZQ-M8
4-way blow ceiling mounted cassette (600mm x 600mm)
specifications
FXZQ-M8 20 25 32 40 50
Cooling capacity kW 2.2 2.8 3.6 4.5 5.6
Heating capacity kW 2.5 3.2 4.0 5.0 6.3
Nominal input cooling W 73 73 76 89 115
heating W 64 64 68 80 107
Dimensions (H x W x D) mm 286 x 575 x 575
Weight kg 18
Casing galvanised steel plate
Air flow rate (H / L) m3 /min 9.0 / 7.0 9.0 / 7.0 9.5 / 7.5 11.0 / 8.0 14.0 / 10.0
Sound pressure level (H / L) (220V) dB(A) 30 / 25 30 / 25 32 / 26 36 / 28 41 / 33
Sound power level dB(A) 47 47 49 53 58
Refrigerant type R-410A
Piping connections liquid / gas mm ø6.4 / ø12.7
Air filter resin net with mold resistant
Drain-up height mm 500
Power supply V1 1~, 50Hz, 220-240V
Decoration panel dimensions (H x W x D) mm 55 x 700 x 700
weight kg 2.7
colour white (RAL 9010)
Notes:
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent piping length: 7.5m (horizontal).
Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent piping length: 7.5m (horizontal).
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Accessories
FXZQ-M8 20 25 32 40 50
Wired remote control BRC1D52
Infrared remote control cooling only BRC7E531
heat pump BRC7E530
Decoration panel BYFQ60B
Sealing member of air discharge outlet KDBH44B60
Panel spacer KDBQ44B60
Replacement long life filter KAFQ441B60
Fresh air intake kit direct installation type KDDQ44X60
52
FXCQ-M8
2-way blow ceiling mounted cassette
specifications
FXCQ-M8 20 25 32 40 50 63 80 125
Cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.0
Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 16.0
Nominal input cooling W 77 92 92 130 130 161 209 256
heating W 44 59 59 97 97 126 176 223
Dimensions (H x W x D) mm 305 x 780 x 600 305 x 995 x 600 305 x 1,180 x 600 305 x 1,670 x 600
Weight kg 26 31 32 35 47 48
Casing galvanised steel plate
Air flow rate (H / L) m3 /min 7 / 5 9 / 6.5 9 / 6.5 12 / 9 12 / 9 16.5 / 13 26 / 21 33 / 25
Sound pressure level (H / L) dB(A) 33 / 28 35 / 29 35 / 29 35.5 / 30.5 35.5 / 30.5 38 / 33 40 / 35 45 / 39
Sound power level dB(A) 45 50 50 50 50 52 54 60
Refrigerant type R-410A
Piping connections liquid / gas mm ø6.4 / ø12.7 ø9.5 / ø15.9
Air filter resin net with mold resistant
Drain-up height mm 600
Power supply V3 1~, 50Hz, 230V
Decoration panel dimensions (H x W x D) mm 53 x 1,030 x 680 53 x 1,245 x 680 53 x 1,430 x 680 53 x 1,920 x 680
weight kg 8 8.5 9.5 12
colour ivory white
Notes:
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 8m • level difference: 0m.
Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 8m • level difference: 0m.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Accessories
FXCQ-M8 20 25 32 40 50 63 80 125
Wired remote control BRC1D52
Infrared remote control cooling only BRC7C67
heat pump BRC7C62
Decoration panel BYBC32G BYBC50G BYBC63G BYBC125G
High efficiency filter 65% *1 KAFJ532G36 KAFJ532G56 KAFJ532G80 KAFJ532G160
High efficiency filter 90% *1 KAFJ533G36 KAFJ533G56 KAFJ533G80 KAFJ533G160
Filter chamber for bottom suction KDDFJ53G36 KDDFJ53G56 KDDFJ53G80 KDDFJ53G160
Replacement long life filter KAFJ531G36 KAFJ531G56 KAFJ531G80 KAFJ531G160
Note:
*1. Filter chamber is required when installing a high efficiency filter.
53
FXKQ-MA
Ceiling mounted corner cassette
specifications
FXKQ-MA 25 32 40 63
Cooling capacity kW 2.8 3.6 4.5 7.1
Heating capacity kW 3.2 4.0 5.0 8.0
Nominal input cooling W 66 66 76 105
heating W 46 46 56 85
Dimensions (H x W x D) mm 215 x 1,110 x 710 215 x 1,310 x 710
Weight kg 31 34
Casing galvanised steel plate
Air flow rate (H / L) m3 /min 11 / 9 11 / 9 13 / 10 18 / 15
Sound pressure level (H / L) (220V) dB(A) 38 / 33 38 / 33 40 / 34 42 / 37
Sound power level dB(A) * * * *
Refrigerant type R-410A
Piping connections liquid / gas mm ø6.4 / ø12.7 ø9.5 / ø15.9
Air filter resin net with mold resistant
Drain-up height mm 500
Power supply VE 1~, 50Hz, 220-240V
Decoration panel dimensions (H x W x D) mm 70 x 1,240 x 800 70 x 1,440 x 800
weight kg 8.5 9.5
colour ivory white
Notes:
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m (horizontal).
Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 7.5m (horizontal).
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*Data were not available at time of publication.
Accessories
FXKQ-MA 25 32 40 63
Wired remote control BRC1D52
Infrared remote control cooling only BRC4C63
heat pump BRC4C61
Decoration panel BYK45F BYK71F
Panel spacer KPBJ52F56 KPBJ52F80
Replacement long life filter KAFJ521F56 KAFJ521F80
Air discharge grille K-HV7AW K-HV9AW
Air discharge blind panel KDBJ52F56W KDBJ52F80W
Flexible duct (with shutter) KFDJ52F56 KFDJ52F80
54
FXDQ-M8
Small concealed ceiling unit
specifications
FXDQ-M8 20 25
Cooling capacity kW 2.2 2.8
Heating capacity kW 2.5 3.2
Nominal input cooling W 50
heating W 50
Dimensions (HxWxD) mm 230x502x652
Weight kg 17
Casing galvanised steel plate
Air flow rate (H/L) m3/min 6.7/5.2 7.4/5.8
Sound pressure level (H/L) dB(A) 37/32
Sound power level dB(A) 50
Refrigerant type R-410A
Piping connections liquid/gas mm ø6.4/ø12.7
Air filter resin net with mold resistant
Power supply V3 1~, 50Hz, 230V
Notes :
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 8m • level difference : 0m
Nominal heating capacities are based on: indoor air temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 8m • level difference : 0m
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Accessories
FXDQ-M8
Wired remote control BRC1D52, BRC2C51, BRC3A61
Infrared remote control cooling BRC4C64
heating BRC4C62
55
FXDQ-P / NA
Slim concealed ceiling unit
specifications
Notes:
Nominal cooling capacities are based on: • Indoor temperature: 27°CDB, 19°CWB • Outdoor temperature: 35°CDB • Equivalent piping length: 7.5m (horizontal).
Nominal heating capacities are based on: • Indoor temperature: 20°CDB • Outdoor temperature: 7°CDB, 6°CWB • Equivalent piping length: 7.5m (horizontal).
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
The sound pressure values are mentioned for a unit installed with rear suction.
* Data were not available at time of publication.
Accessories
56
FXSQ-M8
Concealed ceiling unit
specifications
FXSQ-M8 20 25 32 40 50 63 80 100 125
Cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0
Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0
Nominal input cooling W 110 110 114 127 143 189 234 242 321
heating W 90 90 94 107 123 169 214 222 301
Dimensions (H x W x D) mm 300 x 550 x 800 300 x 700 x 800 300 x 1,000 x 800 300 x 1,400 x 800
Weight kg 30 30 30 30 31 41 51 51 52
Casing galvanised steel plate
Air flow rate (H / L) m3 /min 9 / 6.5 9 / 6.5 9.5 / 7 11.5 / 9 15 / 11 21 / 15.5 27 / 20 28 / 20.5 38 / 28
Sound pressure level (H / L) dB(A) 32 / 28 32 / 28 33 / 28 33 / 29 35 / 31 35 / 30 37 / 31 38 / 33 40 / 35
Sound power level dB(A) 50 50 51 56 58 56 55 56 65
Refrigerant type R-410A
Piping connections liquid / gas mm ø6.4 / ø12.7 ø9.5 / ø15.9
Air filter resin net with mold resistant
Drain-up height mm 625
Power supply V3 1~, 50Hz, 230V
Decoration panel dimensions (H x W x D) 55 x 650 x 500 55 x 800 x 500 55 x 1,100 x 500 55 x 1,500 x 500
weight kg 3 3.5 4.5 6.5
colour ivory white
Notes:
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 8m • level difference: Om.
Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 8m • level difference: Om.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
The sound pressure values are mentioned for a unit installed with rear suction.
Accessories
FXSQ-M8 20 25 32 40 50 63 80 100 125
Wired remote control BRC1D52, BRC2C51, BRC3A61
Infrared remote control cooling only BRC4C64
heat pump BRC4C62
Decoration panel BYBS32D BYBS45D BYB571D BYBS125D
Service access panel KTBJ25K36W KTBJ25K56W KTBJ25K80W KTBJ25K160W
High efficiency filter 65% *1 KAFJ252L36 KAFJ252L56 KAFJ252L80 KAFJ252L160
High efficiency filter 90% *1 KAFJ253L36 KAFJ253L56 KAFJ253L80 KAFJ253L160
Filter chamber for bottom suction KAJ25L36D KAJ25L56D KAJ25L80D KAJ25L160D
Filter chamber rear suction KAJ25L36B KAJ25L56B KAJ25L80B KAJ25L160B
Air suction canvas KSA-25K36 KSA-25K56 KSA-25K80 KSA-25K160
Screening door / blind board KBBJ25K36 KBBJ25K56 KBBJ25K80 KBBJ25K160
Air discharge adapter for round duct KDAJ25K36 KDAJ25K56 KDAJ25K71 KDAJ25K140
Notes:
*1. If installing a high efficiency filter in the unit, an assembly chamber for either bottom or rear suction is required.
57
FXMQ-P/MA
Concealed ceiling unit
specifications
Notes:
Nominal cooling (static pressure).
Nominal heating (static pressure).
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
The air filter is not standard accessory, but please mount it in the duct system at the suction side. Select its colorimetric method (gravity method) 50% or more.
(1) 50Hz, 220-240V
(2) 60Hz, 220V
(3) Data were not available at time of publication.
(4) The air filter is not standard accessory, but please mount it in the duct system at the suction side. Select its colorimetric method (gravity method) 50% or more.
*Data were not available at time of publication.
Accessories
FXMQ-P/MA 40 50 63 80 100 125 200 250
Wired remote control BRC1D52
Infrared remote control cooling only BRC4C66
heat pump BRC4C65 KDU-30L250
High efficiency filter 65% KAF372AA56 KAF372AA80 KAF372AA160 KAFJ372L280
High efficiency filter 90% KAF373AA56 KAF373AA80 KAF373AA160 KAFJ373L280
Filter chamber KDDF3AA56 KDDF37AA80 KDDF37AA160 KDJ3705L280
Longlife replacement filter KAF371AA56 KAF371AA80 KAF371AA160 KAFJ371L280
58
FXAQ-MA
Wall mounted unit
specifications
FXAQ-MA 20 25 32 40 50 63
Cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1
capacity kW 2.5 3.2 4.0 5.0 6.3 8.0
Nominal input cooling W 16 22 27 20 27 50
heating W 24 27 32 20 32 60
Dimensions (HxWxD) mm 290 x 795 x 230 290 x 1,050 x 230
Weight kg 11 14
Colour white
Air flow rate (H / L) m3 /min 7.5 / 4.5 8 / 5 9 / 5.5 12 / 9 15 / 12 19 / 14
Sound pressure level (H / L) (220V) dB(A) 35 / 29 36 / 29 37 / 29 39 / 34 42 / 36 46 / 39
Sound power level dB(A) * * * * * *
Refrigerant type R-410A
Piping connections liquid / gas mm ø6.4 / ø12.7 ø9.5 / ø15.9
Air filter resin net washable
Power supply VE 1~, 50Hz, 220-240V
Notes:
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 5m (horizontal).
Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 5m (horizontal).
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*Data were not available at time of publication.
Accessories
FXAQ-MA 20 25 32 40 50 63
Wired remote control BRC1D52
Infrared remote control cooling only BRC7E619
heat pump BRC7E618
Drain pump kit K-KDU572DVE
59
FXHQ-MA
Ceiling suspended unit
specifications
FXHQ-MA 32 63 100
Cooling capacity kW 3.6 7.1 11.2
Heating capacity kW 4.0 8.0 12.5
Nominal input cooling W 111 115 135
heating W 111 115 135
Dimensions (HxWxD) mm 195 x 960 x 680 195 x 1,160 x 680 195 x 1,400 x 680
Weight kg 24 28 33
Colour ivory white
Air flow rate (H / L) m3 /min 12 / 10 17.5 / 14 25 / 19.5
Sound pressure level (H / L) (220V) dB(A) 36 / 31 39 / 34 45 / 37
Sound power level dB(A) * * *
Refrigerant type R-410A
Piping connections liquid / gas mm ø6.4 / ø12.7 ø9.5 / ø15.9
Air filter resin net with mold resistant
Power supply VE 1~, 50Hz, 220-240V
Notes:
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m (horizontal).
Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 7.5m (horizontal).
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*Data were not available at time of publication.
Accessories
FXHQ-MA 32 63 100
Wired remote control BRC1D52
Infrared remote control cooling only BRC7E66
heat pump BRC7E63
Drain pump kit KDU50M60 KDU50M125 KDU50M125
Replacement long life filter resin net KAFJ501DA56 KAFJ501DA80 KAFJ501DA112
L-type piping kit for upward direction KHFP5M35 KHFP5M63 KHFP5M63
60
FXUQ-MA
4-way blow ceiling suspended unit
specifications
FXUQ-MA 71 100 125
Cooling capacity kW 8.0 11.2 14.0
Heating capacity kW 9.0 12.5 14.0
Nominal input cooling W 180 289 289
heating W 160 269 269
Dimensions (HxWxD) mm 165 x 895 x 895 230 x 895 x 895 230 x 895 x 895
Weight kg 25 31 31
Colour white
Air flow rate (H / L) 19 / 14 29 / 21 32 / 23
Sound pressure level (H / L) (220V) dB(A) 40 / 35 43 / 38 44 / 39
Sound power level (H) dB(A) 56 59 60
Refrigerant type R-410A
Piping connections liquid / gas mm ø9.5 / ø15.9 ø9.5 / ø15.9 ø9.5 / ø15.9
Air filter resin net with mold resistant
Power supply V1 1~, 50Hz, 230V
Combination with junction box BEVQ71MA BEVQ100MA BEVQ125MA
Notes:
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB, 24° CWB.
Nominal heating capacities are based on: indoor temperature: 20°CDB, 15° CWB • outdoor temperature: 7°CDB, 6°CWB.
Capacities are net including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Accessories
FXUQ-MA 71 100 125
Wired remote control BRC1D52
Infrared remote control cooling only BRC7C529
heat pump BRC7C528
Sealing member of air discharge outlet KDBHJ49F80 KDBHJ49F140
Air discharge decoration panel KDBTJ49F80 KDBTJ49F140
Vertical flap kit KDGJ49F80 KDGJ49F140
Replacement long life filter KAFJ495F140
L-type connection piping kit KHFP49M63 KHFP49M140
JUNCTION BOX FOR CONNECTION TO VRV®
BEVQ-MA
61
FXLQ-MA
Floor standing unit
specifications
FXLQ-MA 20 25 32 40 50 63
Cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1
Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0
Nominal input cooling W 49 49 90 90 110 110
heating W 49 49 90 90 110 110
Dimensions (H x W x D) mm 600 x 1,000 x 222 600 x 1,140 x 222 600 x 1,420 x 222
Weight kg 25 30 36
Colour ivory white
Air flow rate (H/L) m3 /min 7/6 7/6 8/6 11/8.5 14/11 16/12
Sound pressure level (H/L) (220V) dB(A) 35/32 35/32 35/32 38/33 39/34 40/35
Sound power level dB(A) * * * * * *
Refrigerant type R-410A
Piping connections liquid/gas mm ø6.4/ø12.7 ø9.5/ø15.9
Air filter resin net with mold resistant
Power supply VE 1~, 50Hz, 220-240V
Notes:
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m (horizontal).
Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 7.5m (horizontal).
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*Data were not available at time of publication.
Accessories
FXLQ-MA 20 25 32 40 50 63
Wired remote control BRC1D52, BRC2C51, BRC3A61
Infrared remote control cooling only BRC4C64
heat pump BRC4C62
Long life replacement filter KAFJ361K28 KAFJ361K45 KAFJ361K71
62
FXNQ-MA
Concealed floor standing unit
specifications
FXNQ-MA 20 25 32 40 50 63
Cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1
Heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0
Nominal input cooling W 49 49 90 90 110 110
heating W 49 49 90 90 110 110
Dimensions (HxWxD) mm 600 x 1,00 x 222 600 x 1,140 x 222 600 x 1,420 x 222
Weight kg 25 30 36
Casing ivory white
Air flow rate (H/L) m3/min 7/6 7/6 8/6 11/8.5 14/11 16/12
Sound pressure level (H/L)(220V) dB(A) 35/32 35/32 35/32 38/33 39/34 40/35
Sound power level dB(A) * * * * * *
Refrigerant type R-410A
Piping connections liquid/gas mm ø6.4/ø12.7 ø9.5/ø15.9
Air filter resin net with mold resistant
Power supply VE 1~, 50Hz, 220-240V
Notes:
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 8m • level difference: Om.
Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 8m • level difference: Om.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
The sound pressure values are mentioned for a unit installed with rear suction.
Accessories
FXNQ-MA 20 25 32 40 50 63
Wired remote control BRC1D52, BRC2C51, BRC3A61
Infrared remote control cooling only BRC4C64
heat pump BRC4C62
Replacement long life filter KAFJ361K28 KAFJ361K45 KAFJ361K71
63
Ventilation
1. HRV-Heat Reclaim
Ventilation
1. VAM-FA8 Clean outdoor air
Total heat
exchanged
foul air
VAM-FA
VENTILATION VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA VAM800FA VAM1000FA VAM1500FA VAM2000FA
Air flow rate m /h
3
150 250 350 500 650 800 1,000 1,500 2,000
Sound pressure level (max.) (1) dBA 27/28.5 28/29 32/34 33/34.5 34.5/35.5 36/37 36/37 39.5/41.5 40/42.5
External static pressure (max.) Pa 69 64 98 98 93 137 157 137 137
Temperature exchange efficiency % 74 72 75 74 74 74 75 75 75
Enthalpy exchange efficiency heating % 58 58 61 58 58 60 61 61 61
cooling % 64 64 65 62 63 65 66 66 66
Dimensions H mm 269 269 285 285 348 348 348 710 710
W mm 760 760 812 812 988 988 988 1,498 1,498
D mm 509 509 800 800 852 852 1,140 852 1,140
Weight kg 24 24 33 33 48 48 61 132 158
Duct diameter mm Ø 100 Ø 150 Ø 150 Ø 200 Ø 200 Ø 250 Ø 250 Ø 350 Ø 350
Power supply VE 1~, 50Hz, 220-240V
64
2. VKM-GA / VKM-GAM
VKM-GAM
VENTILATION, DX coil & humidifier VKM50GAM VKM80GAM VKM100GAM
Fresh air conditioning load cooling kW 4.71 7.46 9.12
heating kW 5.58 8.79 10.69
Air flow rate ultra high - high - low m /h
3
500 - 500 - 440 750 - 750 - 640 950 - 950 - 820
Sound pressure level - 220V ultra high - high - low dBA 37 - 35.5 - 32 38.5 - 36 - 33 39 - 37 - 34
Sound pressure level - 240V ultra high - high - low dBA 38 - 36 - 34 40 - 37.5 - 35.5 40 - 38 - 35.5
Static pressure ultra high - high - low Pa 160 - 120 - 100 140 - 90 - 70 110 - 70 - 60
Temperature exchange efficiency ultra high - high - low % 76 - 76 - 77.5 78 - 78 - 79 74 - 74 - 76.5
Enthalpy exchange efficiency - cooling ultra high - high - low % 64 - 64 - 67 66 - 66 - 68 62 - 62 - 66
Enthalpy exchange efficiency - heating ultra high - high - low % 67 - 67- 69 71 - 71 - 73 65 - 65 -69
Humidifier type natural evaporating humdifier
Humidification capacity kg/h 2.70 4.00 5.40
Dimensions height mm 387 387 387
width mm 1,764 1,764 1,764
depth mm 832 1,214 1,214
Weight kg 102 120 125
Power supply V1 1~, 220-240V, 50Hz
VKM-GA
VENTILATION & DX coil VKM50GA VKM80GA VKM100GA
Fresh air conditioning load cooling kW 4.71 7.46 9.12
heating kW 5.58 8.79 10.69
Air flow rate ultra high - high - low m /h 3
500 - 500 - 440 750 - 750 - 640 950 - 950 - 820
Sound pressure level - 220V ultra high - high - low dBA 38 - 36 - 33.5 40 - 37.5 - 34.5 40 - 38 - 35
Sound pressure level - 240V ultra high - high - low dBA 39 - 37 - 35.5 41.5 - 39 - 37 41 - 39 - 36.5
Static pressure ultra high - high - low Pa 180 - 150 - 110 170 - 120 - 80 150 - 100 - 70
Temperature exchange efficiency ultra high - high - low % 76 - 76 - 77.5 78 - 78 - 79 74 - 74 - 76.5
Enthalpy exchange efficiency - cooling ultra high - high - low % 64 - 64 - 67 66 - 66 - 68 62 - 62 - 66
Enthalpy exchange efficiency - heating ultra high - high - low % 67 - 67- 69 71 - 71 - 73 65 - 65 -69
Dimensions height mm 387 387 387
width mm 1,764 1,764 1,764
depth mm 832 1,214 1,214
Weight kg 96 109 114
Power supply V1 1~, 220-240V, 50Hz
65
2. FXMQ-MFV1 - Outdoor Air
Processing Unit
Combined fresh air treatment
and air conditioning via a single system.
Both fresh air treatment and air conditioning can be achieved successfully
in a single system via heat pump technology without the usual design
problems associated with balancing air supply and discharge. Air conditioning
fan coil units and an outdoor air treatment unit can be connected to the
same refrigerant line, resulting in enhanced design flexibility and a significant
reduction in total system costs.
FXMQ-MFV1
indoor Units FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
cooling kw 14.0 22.4 28.00
Capacity
heating kw 8.9 13.9 17.40
cooling kw 0.359 0.548 0.638
Power Input
heating kw 0.359 0.548 0.638
Dimensions HxWxD mm 470x744x1,100 470x1380x1,100
Weight kg 86 123
cooling medium m3/min 18.0 28.0 35.0
Air Flow Rate
heating medium m3/min 18.0 28.0 35.0
Refrigerant -
Power Supply 220-240V/50Hz
Piping Connections liquid (od)/gas/drain mm 9.5 / 15.9 / PS1B 9.5 / 19.1 / PS1B 9.5 / 22.2 / PS1B
66
3. VRV®+EXV-kit -
VRV® Air Handling Applications
›› A new range of R-410A inverter condensing units for ›› Control z: control of air temperature (suction
multi application with air handling units. temperature, room temperature) via Daikin control
›› Inverter controlled units (no DDC controller needed)
›› Large capacity range (from 5 to 18HP) ›› Large range of expansion valve kits available
›› Cooling only ›› BRC1D52 is used to set the set point
›› R-410A temperature (connected to the EKEXMCB).
EXV-kit
Air handling unit
Cooling only
RXQ-P(A) 5 8 10 12 14 16 18
Capacity range HP 5 8 10 12 14 16 18
Capacity cooling kw 14.0 22.4 28.0 33.5 40.0 45.0 49.0
Power input (Nominal) cooling kw 3.52 5.56 7.42 9.62 12.4 14.2 16.2
Dimensions HxWxD mm 1,680x635x765 1,680x930x765 1,680x1,240x765
Weight kg 157 185 238 315 323
sound power cooling dBA 72 78 80 83
Sound Level
sound pressure cooling dBA 54 57 58 60 63
Air Flow Rate (nominal at 230V) cooling m³/min 95 171 185 196 233 239
Operation Range cooling min~max °CDB -5.0~43.0
Refrigerant R-410A
Power Supply 3N~/400V/50Hz
Max n° of indoor units to be connected 8 13 16 19 23 26 29
Piping connections liquid (OD)/gas mm 9.5 / 15.9 9.5 / 19.1 9.5 / 22.2 12.7 / 22.2 12.7 / 28.6 15.9 / 28.6
Combination table
Control
Expansion valve kit
box
Outdoor unit
control z class 50 class 63 class 80 class 100 class 125 class 140 class 200 class 250
68
2. VRV® pro
›› Features:
69
User Friendly
Control Systems
1. Individual
control systems
BRC7* Operation buttons: ON / OFF, timer mode start / stop, timer mode on / off,
programme time, temperature setting, air flow direction (FXHQ, FXFQ, FXCQ
and FXAQ models only), operating mode, fan speed control, filter sign reset,
inspection / test indication
Simple, compact and easy to operate unit, suitable for use in hotel bedrooms
72
3. Network Solutions
DS-NET
adapter
P1 - P2 F1 - F2
RS485
Malfunction
P1 - P2 F1 - F2
Modem
RS232C
Max. of 10 DS-NET
adapters
73
Allows detailed and easy monitoring and operation of VRV® systems (max. 2 x 64 control groups)
Control
›› Individual control (set point, start / stop, fan speed)
(max. 2 x 64 indoor units / groups)
›› Schedule control (8 schedules, 17 patterns)
›› Flexible grouping in zones
›› Yearly schedule
›› Fire emergency stop control
›› Interlocking control
›› Increased HRV monitoring and control function
›› Automatic cooling / heating changeover
›› Quick selection and full control
›› Simple navigation
›› Heating optimization
›› Temperature limit
›› Password security: 3 levels
(general, administration & service)
74
[iPU]
Monitoring
››Visualisation via Graphical User Interface (GUI)
››Icon colour display change function
Fire alarm ››Indoor units operation mode
››Error messages via e-mail & mobile phone (option)
Forced OFF contact input ››Indication filter replacement
››Multi PC
DIII-NET
Cost performance
›› Labour saving
Indoor units
HRV ›› Easy installation
DIO unit
›› Compact design: limited installation space
›› Overall energy saving
Controls drain
pump, lighting etc. Open interface
››Communication to any third party controller (domotics,
Monitoring of room
enter/exit sign BMS, etc.) is possible via open interface.
DI unit
Connectable to
DIII-NET Allows monitoring/control
RS-232C of up to 64 units (groups) ›› VRV®
›› HRV
DIII-NET PLUS ›› Sky Air (via interface adapter)
adapter
›› Split (via interface adapter)
Indoor unit HRV
75
The ideal solution for control and management
of maximum 1,024 VRV® indoor units
Web Access
Malfunction report
by E-Mail
Air Conditioning
Network Service System
(Via Internet) (Optional Maintenance Service)
Ai unit
DAM602B51/52
DIII-NET
DIII-NET
Daikin Central
Air Conditioning System
VRV® System
DMS502A51
Local monitoring
BACnet Gateway HRV
~ & control
(monitoring only)
Sub PC
76
LON BMS
ETHERNET (TCP/IP)
HRV
(twisted pair wire)
›› 64 units connectable per DMS-IF
›› Unlimited site size LonTalk
adapter
›› Quick and easy installation Remote Control
LonPoint LonPoint
BUILDING
DAIKIN A / C INFRASTRUCTURE
CONTROL
NETWORK
Security
Fire alarm
System
BMS DMS502A51
DIII- NET
HRV
Remote Control
BUILDING
CONTROL
NETWORK Pump Lighting Elevator
77
4. accessories
Individual control systems
DESCRIPTION FXFQ FXZQ FXCQ FXKQ FXDQ FXDQ-N FXSQ FXMQ FXUQ FXHQ FXAQ FXLQ FXNQ
Wired remote control BRC1D52
Infrared remote control cooling only BRC7F533 BRC7E531 BRC7C67 BRC4C63 BRC4C64 BRC4C64 BRC4C64 BRC4C66 BRC7C529 BRC7E66 BRC7E619 BRC4C64 BRC4C64
heat pump BRC7F532 BRC7E530 BRC7C62 BRC4C61 BRC4C62 BRC4C62 BRC4C62 BRC4C65 BRC7C528 BRC7E63 BRC7E618 BRC4C62 BRC4C62
Simplified remote control - - - - BRC2C51 BRC2C51 BRC2C51 BRC2C51 - - - BRC2C51 BRC2C51
Simplified remote control for hotel use - - - - BRC3A61 BRC3A61 BRC3A61 BRC3A61 - - - BRC3A61 BRC3A61
DESCRIPTION FXFQ FXZQ FXCQ FXKQ FXDQ FXDQ-N FXSQ FXMQ FXUQ FXHQ FXAQ FXLQ FXNQ
Centralised remote control DCS302C51
Unified ON/OFF control DCS301B51
Schedule timer DST301B51
Others
DESCRIPTION FXFQ FXZQ FXCQ FXKQ FXDQ FXDQ-N FXSQ FXMQ FXUQ FXHQ FXAQ FXLQ FXNQ
Wiring adapter - KRP1B57*1 - KRP1B61 KRP1B61 KRP1B56 - KRP1B61 KRP4A53 KRP1B3 - KRP1B61 KRP1B61
Wiring adapter (hour meter) EKRP1C11*1 - EKRP1B2 - EKRP1B2*2 -EKRP1B2 - - - - -
Wiring adapter for electrical appendices (1) KRP2A526*1 KRP2A526*1 KRP2A516*1 KRP2A61 KRP2A516 KRP2A53
KRP2A516 KRP2A61 KRP2A62* KRP2A51 KRP2A51 KRP2A51
Wiring adapter for electrical appendices (2) KRP4AA53*1 KRP4A536*1 KRP4A516*1 KRP4A51 KRP4A516 KRP4A54
KRP4A516 KRP4A51 KRP4A52* KRP4A51 KRP4A51 KRP4A51
Remote sensor KRCS01-4 KRCS01-1
Installation box for adapter PCB KRP1H98 KRP1BA101 KRP1B96*3/4 - - KRP1BA101 - KRP1B97 KRP1C93*3 KRP4A93*3/4 - -
Electrical box with earth terminal (3 blocks) - KJB311A
Electrical box with earth terminal (2 blocks) KJB212AA KJB212A
Noise filter (for electromagnetic interface only) - KEK26-1A
External control adapter - DTA104A52 DTA104A51*1 DTA104A61 DTA104A51 DTA104A53 DTA104A51 DTA104A61 DTA104A62 DTA104A51 DTA104A61 DTA104A61
Interface adapter for Sky Air series - - - - - - - - DTA102A52 - - - -
Connector for forced on/forced off - - - - - - - - EKRORO - - - -
Notes:
*1: Installation box is required
*2: Fixing box is KRP1A90
*3: Up to 2 adapters can be fixed per installation box
*4: Only 1 installation box can be installed per indoor unit
78
DESCRIPTION REFERENCE COMMENTS
Intelligent Processing unit DAM602B51 256 indoor units per IPU
DAM602B52 128 indoor units per IPU
Software IM3.XX Up to 1,024 indoor units
Interface adapters KRP928A2S For connection to Split units
DTA102A52 For connection to R-407C/R-22 Sky Air units
dta112b51 For connection to R-410A Sky Air units
DIII Ai DAM101A51 Outdoor temperature sensor
Digital input DEC10151* Input contacts: 16 points
Digital input / output DEC10251* Input contacts: 8 points; output contacts: 4 points
Power Proportional Distribution DAM002A51
ECO Mode DAM003A51
Web Acces Function DAM004A51
Temperature setting units DPF201A53 enables temperature setting input for 16 groups; 0~5VDC.»
Unification adapter for computerised control DCS302A52 used for combining of air conditioning control computer and central remote controller (ON/OFF, display)
Wiring adapter for electrical appendices (1) KRP2A51 simultaneously controls air conditioning control computer and up to 64 groups of indoor units.
KRP2A52
Wiring adapter for electrical appendices (2) KRP4A51-53 to control the group of indoor units collectively, which are connected by the transmission wiring of remote controller.
External control adapter for outdoor unit DTA104A51
cooling/heating mode change over, demand control and low noise control are available between the plural outdoor units.
DTA104A52
DIII-net expander adapter DTA109A51 a maximum of 10 outdoors or 128 indoors can be connected to 1 DTA109A51
a maximum of 8 DTA109A51 can be connected to DIII-net
Mounting kit KRP4A92 for easy installation of the DTA109A51
79
Daikin’s unique position as a manufacturer of Daikin Europe N.V. is approved by LRQA for its Quality The present leaflet is drawn up by way of information only and
air conditioning equipment, compressors and Management System in accordance with the ISO9001 does not constitute an offer binding upon Daikin Europe N.V.. Daikin
refrigerants has led to its close involvement in standard. ISO9001 pertains to quality assurance Europe N.V. has compiled the content of this leaflet to the best
environmental issues. regarding design, development, manufacturing as of its knowledge. No express or implied warranty is given for the
For several years Daikin has had the intention well as to services related to the product. completeness, accuracy, reliability or fitness for particular purpose
to become a leader in the provision of products of its content and the products and services presented therein.
that have limited impact on the environment. Specifications are subject to change without prior notice. Daikin
This challenge demands the eco design and Europe N.V. explicitly rejects any liability for any direct or indirect
Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende
development of a wide range of products ISO14001 assures an effective environmental damage, in the broadest sense, arising from or related to the use
and an energy management system, resulting management system in order to help protect human and/or interpretation of this leaflet. All content is copyrighted by
in energy conservation and a reduction of health and the environment from the potential impact Daikin Europe N.V.
waste. of our activities, products and services and to assist
in maintaining and improving the quality of the
Printed on non-chlorinated paper. Prepared by La Movida, Belgium
environment.
Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Oostende, Belgium
www.daikin.eu
BTW: BE 0412 120 336
RPR Oostende
RXYHQ-P8
RXYQ-P(8)
RXYQ-P8
Pipe size selection A,B,C. Piping between outdoor unit and refrigerant branch kit D. Piping between refrigerant branch kits E. Piping between refrigerant branch kit and indoor
For an outdoor unit multi installation • Choose from the following table in accordance with the outdoor unit • Choose from the following table in accordance with the total capacity of unit
(RXYQ20~54P + RXYHQ16~36), select the pipe total capacity type, connected downstream. all the indoor units connected below this. • Pipe size for direct connection to indoor unit must be the
size in accordance with the following figure. Outdoor unit connection piping size • Do not let the connection piping exceed the refrigerant piping size same as the connection size of indoor unit.
chosen by general system model name.
Outdoor unit Piping size (outer diameter) (mm) Piping size (outer
capacity type Gas pipe Liquid pipe Indoor or outdoor unit Piping size (outer diameter) (mm) Indoor capacity diameter) (mm)
RX(Y)Q5 Ø15.9 total capacity Gas pipe Liquid pipe type Gas pipe Liquid pipe
RX(Y)Q8 Ø19.1 Ø9.5 ⬍150 Ø15.9 20~50 Ø12.7 Ø6.4
RX(Y)Q10 Ø22.2 150⭐x⬍200 Ø19.1 Ø9.5 63~125 Ø15.9
A B B B RX(Y)Q12~16 + 200⭐x⬍290 Ø22.2
Ø12.7 200 Ø19.1 Ø9.5
RXYHQ12+16
D E C 290⭐x⬍420 Ø12.7 250 Ø22.2
RX(Y)Q18 + Ø28.6 Ø28.6
RXYQ20+22 + 420⭐x⬍640 Ø15.9
RXYHQ18~22 Ø15.9 640⭐x⬍920 Ø34.9
Ø19.1
RXY(H)Q24 ⭓920 Ø41.3
Ø34.9
RXY(H)Q26~34
RXYQ36~54 + Ø19.1
Ø41.3
RXYHQ36
When the equivalent pipe length between outdoor and indoor units is 90 m or more, the size of the main pipes (both gas side and liquid side) must be increased.
Depending on the length of the piping, the capacity may drop, but even in such a case it is possible to increase the size of the main pipes.
Note 1 Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to 90 m if all the following conditions are fulfilled.
Required conditions Example drawings
It is necessary to increase the pipe size of the liquid and the gas pipe if the pipe length between the first and the final indoor unit 8: Increase the pipe size as follows
branch kit is over 40 m (reducers must be procured on site). b+c+d+e+f+g+p⭐90 m
Ø9.5 ➞ Ø12.7 Ø15.9 ➞ Ø19.1 Ø22.2 ➞ Ø25.4*
If the increased pipe size is larger than the pipe size of the main pipe, then the pipe size of the main pipe needs to be increase the pipe size
Ø12.7 ➞ Ø15.9 Ø19.1 ➞ Ø22.2 Ø28.6 ➞ Ø31.8*
increased as well. of b, c, d, e, f, g
Ø34.9 ➞ Ø38.1*
* If available on the site. Otherwise it can not be increased.
For calculation of total extension length, the actual length of above pipes must be doubled. (except main pipe and the a+b*2+c*2+d*2+e*2+f*2+g*2 1 1 Outdoor unit
pipes that not increase the pipe size) +h+i+j+k+l+m+n+p⭐1000 m
2 Refnet joints
Indoor unit to the nearest branch kit ⭐40 m
g
h, i, j....... p⭐40 m a b c d e f H1
(a~g)
2 A B C D E F G
p
The difference between the distance of the outdoor unit to the farthest indoor unit and the distance of the outdoor unit The farthest indoor unit 8 3
h
1
i
2
j
3
k
4
l
5
m
6
n
7 H2 3 Indoor units (1~8)
to the nearest indoor unit ⭐40 m The nearest indoor unit 1
4PW48461-1
(a+b+c+d+e+f+g+p)–(a+h)⭐40 m
Note 2 If the pipe size above the refnet header is Ø34.9 or more, KHRQ22M75H is required.
RXYHQ-P8
RXYQ-P(8)
RXQ-P(A)
Example of connection Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header
(Connection of 8 indoor units Heat pump system)
•Use the outdoor unit multi connection piping kit that is sold separately
One outdoor
as an option (BHFQ22P1007+1517) for the multi installation of outdoor unit installed i
a
units. Selection method is as shown in the right table. (RX(Y)Q5~18 a b c d e f g H1
a
A B
k
•Do not use the outdoor unit multi connection piping kit (BHFQ22M909) + RXYHQ12) A B C D E F G
p
H1 b j
7 8 H1
that are sold separately as an option of the M-type series and do not use h i j k l m n
c d e f g h
H2
b c d e f g h i
1 2 3 4 5 6 7 H2
T-joints. 8 1 2 3 4 5 6 1 2 3 4 5 6 7 H2
8
system p H1 b j
k H1
outdoor multi connection piping kit
A B C D E F G
(RXYQ20~54+ h i j k l m n 7 8
H2 b c d e f g h i
1 2 3 4 5 6 7 H2 c g h
RXYHQ16~36) 8 1
d
2
e
3 4
f
5 6
1 2 3 4 5 6 7 H2
8
Install the joint part ( part in the figure) of the outdoor unit multi connection piping
kit horizontally with attention to the installation restrictions described in "connecting
the refrigerant piping".
(*) If the system capacity is RXY(H)Q20 or more, re-read to the first outdoor branch
as seen from the indoor unit.
Actual pipe Pipe length between outdoor(*) and indoor units ⭐165 m
length [Example] unit 8: a+b+c+d+e+f+g+p⭐165 m [Example] unit 6: a+b+h⭐165 m, unit 8: a+i+k⭐165 m [Example] unit 8: a+i⭐165 m
Between outdoor and indoor units Equivalent Equivalent pipe length between outdoor(*) and indoor units 190 m (Assume equivalent pipe length of refnet joint to be 0.5 m and of the refnet headerheader branch
Maximum allowable length pipe to be 1.0 m. (for calculation purposes))
length
Total extension
Total piping length from outdoor unit* to all indoor units ⭐ 1000 m
length
Between outdoor branch and outdoor unit Actual pipe
Piping length from outdoor branch to outdoor unit ⭐ 10 m. Approximate length: max. 13 m
(Only for RXY(H)Q20 or more) length
Difference in Difference in height between outdoor and indoor units (H1)⭐50 m (⭐40 m if outdoor unit is located in a lower r⭐10 m (Approximate length:
Between outdoor and indoor units
height position). max. 13 m)
Difference in s⭐10 m (Approximate length:
Allowable height Between indoor and indoor units Difference in height between adjacent indoor units (H2)⭐15 m max: 13 m)
height r s t
t⭐10 m (Approximate length:
Difference in max: 13 m)
Between outdoor and outdoor units Difference in height between outdoor unit (main) and outdoor unit (sub) (H3)⭐5 m
height
Actual pipe Pipe length from first refrigerant branch kit (either refnet jointline branch pipe or refnet headerheader branch pipe) to indoor unit ⭐40 m (See note 1 on next page)
Allowable length after the branch
length [Example] unit 8: b+c+d+e+f+g+p⭐40 m [Example] unit 6: b+h4⭐0 m, unit 8: i+k⭐40 m [Example] unit 8: i⭐40 m
Refrigerant branch kit selection How to select the refnet joint How to select the refnet header
• When using refnet joints at the first branch counted from the outdoor unit side. • Choose from the following table in accordance with the total capacity of all the
Refrigerant branch kits can only be used with R410A. Choose from the following table in accordance with the capacity of the outdoor unit. indoor units connected below the refnet header.
• Note: 250 type cannot be connected below the refnet header.
Outdoor unit capacity type Refrigerant branch kit name
RX(Y)Q5 KHRQ22M20TCZ-P20BK12Q Indoor capacity type Refrigerant branch kit name
RX(Y)Q8+10 KHRQ22M29T9CZ-P29BK12QA <290 KHRQ22M29H (Max. 8 branch)
RX(Y)Q12~18U KHRQ22M64TCZ-P64BK12Q 290⭐x<640 KHRQ22M64H (Max. 8 branch)a
RXYQ20+22 ⭐640 KHRQ22M75H (Max. 8 branch)
RXYHQ12 + RXYHQ16~22 a. See note 2 on next page
RXYQ24~54 KHRQ22M75TCZ-P75BK12Q How to choose an outdoor multi connection piping kit (needed if the
RXYHQ24~36 outdoor unit capacity type is RXY(H)Q20 or more.)
• For refnet jointsline branch pipes other than the first branch, select the proper branch kit • Choose from the following table in accordance with the number of outdoor units.
model based on the total capacity index. Number of outdoor units Branch kit name
Indoor capacity type Refrigerant branch kit name 2 BHFQ22P1007
<200 KHRQ22M20T 3 BHFQ22P1517
200⭐x<290 KHRQ22M29T9
290⭐x<640 KHRQ22M64T
⭓640 KHRQ22M75T
4PW48461-1