Note:
(1) Values for chilled water and cooling water in the above table are for nominal operation conditions, and
can be properly adjusted in actual operation.
(2) The lowest outlet temperature for chilled water is 5℃.
(3) Cooling capacity can be adjusted in a range of 20 ~100%. Chilled water flow can be adjusted in the
range of 60 ~120%.
(4) On the chilled and cooling water side scale factor will be 0.0001m2h℃/kcal.
(5) Chilled and cooling water box has the maximum pressure bearing capacity of 0.8MPa (G).
(6) The material of tubes in Evaporator, Absorber and Condenser is S31603 (316L), but the material of
tube-sheet and water box is still carbon steel.
2021.12.3