3 4

1100 1100 230 230


1 2-Y12+ 2 2-Y12 2-Y12+ 2-Y12+ 2-Y12
2-Y16 2-Y16 2-Y16

450
Y8 @ 100 C/C Y8 @ 200 C/C

450

450
2-Y12+
2 1-Y16
2-Y12+ 2-Y12+
Y8 @ 100 C/C Y8 @ 100 C/C 1-Y16 1-Y16
(900) Y8 @ 200 C/C (900)
1 SECTION "1-1" SECTION "2-2"
L.S OF BEAM "LB1-1" ( 230 X 450 ) ( 230 X 450 )
( 230 X 450 )

B A
1800 1800 230 230

3 2-Y16+ 4 2-Y16 2-Y16+ 2-Y16+ 2-Y16


4-Y16 4-Y16 4-Y16

450
LB2 LB5 Y8 @ 100 C/C Y8 @ 200 C/C

450

450
3-Y16
4 3-Y16 3-Y16 BEAM SCHEDULE
Y8 @ 100 C/C Y8 @ 100 C/C
(900) Y8 @ 200 C/C (900)
SECTION "3-3" SECTION "4-4" Sl.NO NAME SIZE in "mm"
3
( 230 X 450 ) ( 230 X 450 )
L.S OF BEAM "LB1-2"
01 LB1-1 230 x 450
( 230 X 450 )
02 LB1-2 230 x 450
1 2 3 03 LB2 230 x 450
230 230
1100 1100 1100 1100 04 LB5 230 x 450
3-Y12+ 3-Y12
5 3-Y12+ 6 3-Y12 3-Y12+ 3-Y12+ 3-Y12 3-Y12+ 2-Y16
2-Y16 2-Y16 2-Y16 2-Y16
450

450

LB1-2 Y8 @ 100 C/C Y8 @ 200 C/C

450

450
2-Y12+ 2-Y12+
6 1-Y16 2-Y12+ 2-Y12+
1-Y16
Y8 @ 100 C/C Y8 @ 100 C/C Y8 @ 100 C/C Y8 @ 100 C/C 1-Y16 1-Y16
(900) Y8 @ 200 C/C (900) (900) Y8 @ 200 C/C (900)
SECTION "5-5" SECTION "6-6"
5
( 230 X 450 ) ( 230 X 450 )
L.S OF BEAM "LB2"
( 230 X 450 )

1 2 3 4 5
1100 1100 1100 1100 1100 1100 1100 1100 1100
7 3-Y12+ 8 3-Y12 3-Y12+ 3-Y12+ 3-Y12 3-Y12+ 3-Y12+ 3-Y12 3-Y12+ 3-Y12+ 3-Y12 3-Y12+ 3-Y12+ 3-Y12
2-Y16 2-Y16 2-Y16 2-Y16 2-Y16 2-Y16 2-Y16 2-Y16 2-Y16
450

450

450

450

450
LB1-2

REFERENCE DRGS (LATEST APPROVED):-


2-Y12+ 2-Y12+ 2-Y12+ 2-Y12+ 2-Y12+
8 1-Y16 1-Y16 1-Y16 1-Y16
1. GENERAL ARRANGEMENT DRAWING -19-EPE-CMWSSB-STP-120MLD-GA-ABR-14
1-Y16
Y8 @ 100 C/C Y8 @ 100 C/C Y8 @ 100 C/C Y8 @ 100 C/C Y8 @ 100 C/C Y8 @ 100 C/C Y8 @ 100 C/C Y8 @ 100 C/C Y8 @ 100 C/C 2. FOR OTHER NUMERATION & R.C DETAILS OF AIR BLOWER ROOM -
(900) Y8 @ 200 C/C (900) Y8 @ 200 C/C (900) (900) Y8 @ 200 C/C (900) Y8 @ 200 C/C 19- EPE- CMWSSB- STP- 120MLD- ABR- NU & RC- 14 (SHEET 01 -09)
(900) Y8 @ 200 C/C (900) (900) (900)
7
L.S OF BEAM "LB5"
( 230 X 450 )

230 230
SPACER BARS SHALL BE
3-Y12+ 3-Y12 MAX. DIA. OF TOP ROD.
2-Y16
CLIENT :
ALL STIRRUPS ARE 2 LEGGED CHENNAI METROPOLITAN WATER SUPPLY AND SEWERAGE BOARD
Y8 @ 100 C/C Y8 @ 200 C/C UNLESS OTHERWISE SPECIFIED.
450

450

135° END HOOKS ALTERNATELY PROJECT :


PLACED AS PER IS 13920 : 1993 DESIGN, ENGINEERING,BUILD AND COMMISSION OF 120MLD CAPACITY SEWAGE
TREATMENT PLANT IN ZONE II AT KODUNGAIYUR WITH SEQUENTIAL BATCH
2-Y12+ 2-Y12+ SPACER BARS SHALL BE
REACTOR (SBR) WITH POWER GENERATION FROM BIO-GAS INCLUDING
1-Y16 1-Y16 MAX. DIA. OF BOTTOM ROD.
OPERATION AND MAINTENANCE FOR TEN YEARS AT KODUNGAIYUR, CHENNAI.
SUPPLIER / CONTRACTOR :
SECTION "7-7" SECTION "8-8" ECO PROTECTION ENGINEERS PVT LTD.,
TYP. DETAIL NO. 943, 54TH STREET, TVS COLONY,
( 230 X 450 ) ( 230 X 450 )
ANNA NAGAR WEST EXTN. CHENNAI.
TITLE :
R.C DETAILS OF LINTEL BEAM
FOR AIR BLOWER BUILDING IN 120 MLD
STP AT KODUNGAIYUR ,CHENNAI

DRAWING No.