PANE PB

L LOAD DESCRIPTION
CKT. VOLT. PH L.O C.O WATTS FULL LOAD CKT. BREAKER
NO. AMPHERES P AT AF

1 LIGHTING OUTLET 230 1 9 900 3.91 2 15 50


2 LIGHTING OUTLET 230 1 8 800 3.48 2 15 50
3 CONVENIENCE OUTLET 230 1 12 2160 9.39 2 20 50
4 CONVENIENCE OUTLET 230 1 8 1440 6.26 2 20 50
5 AIRCONDITION OUTLET 230 1 1 1HP 8.00 2 20 50
6 AIRCONDITION OUTLET 230 1 1 1HP 8.00 2 20 50

7 RANGE 230 1 1 4000 17.39 2 30 50


8 RANGE AND RANGEHOOD OUTLET 230 1 1 4200 18.26 2 30 50
9 REFRIGERATOR OUTLET 230 1 1 600 2.61 2 20 50

10 WASHING MACHINE OUTLET 230 1 1 1840 8.00 2 30 50


11 DRYER 230 1 1 3000 13.04 2 30 50
12 SPARE 98.35
It = (98.35x(DF=80%)) + 25% (13.04) = 81.94 A
COMPUTATION:
= 81.94 AMPERE
USE: 2-22mm2 THHN CU wire & 1-8.0mm2 THHN ground CU wire; 125AT/AF breaker in a 25mm dia. PVC conduit
SIZE OF WIRE, GROUNDING AND CONDUIT

2 - 2.0mm² THHN WIRE IN 15mmØ PVC


2 - 2.0mm² THHN WIRE IN 15mmØ PVC
2 - 3.5mm² THHN WIRE + 1 - 3.5mm² THHN GROUND IN 15mmØ PVC
2 - 3.5mm² THHN WIRE + 1 - 3.5mm² THHN GROUND IN 15mmØ PVC
2 - 5.5mm² THHN WIRE + 1 - 3.5mm² THHN GROUND IN 15mmØ PVC
2 - 5.5mm² THHN WIRE + 1 - 3.5mm² THHN GROUND IN 15mmØ PVC
2 - 5.5mm² THHN WIRE + 1 - 3.5mm² THHN GROUND IN 15mmØ PVC

2 - 5.5mm² THHN WIRE + 1 - 3.5mm² THHN GROUND IN 15mmØ PVC


2 - 3.5mm² THHN WIRE + 1 - 3.5mm² THHN GROUND IN 15mmØ PVC
2 - 5.5mm² THHN WIRE + 1 - 3.5mm² THHN GROUND IN 15mmØ PVC

2 - 5.5mm² THHN WIRE + 1 - 3.5mm² THHN GROUND IN 15mmØ PVC