SERVICE ENTRANCE:

GENERAL ELECTRICAL NOTES


AND SPECIFICATION :
1. ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST EDITION THE PHILIPPINE ELECTRICAL CONVENIENCE OUTLET
CODE, TO THE RULES AND REGULATIONS OF LOCAL AND NATIONAL AUTHORITIES CONCERNED
AND THE REQUIREMENTS OF LOCAL UTILITY COMPANIES.
2. ALL PIPE EMBEDDED IN CONCRETE SHALL BE POLYVINYL CHLORIDE (PVC) AND ALL EXPOSED WEATHER PROOF OUTLET
SHALL BE ELECTRICAL METALLIC CONDUIT (EMT).
3. MINIMUM SIZE OF WIRE AND CONDUIT SHALL2BE 2.0 mm THHN AND 20MM (1/2") NOMINAL DIA.
RESPECTIVELY. UNLESS OTHERWISE SPECIFIED ON PLANS. AIR CONDITIONING OUTLET
4. NO BRANCH CIRCUIT WIRING IN LIGHTING AND POWER SHALL HAVE A LOAD MORE THAN 80%
OF ITS RATING.
125AT/AF; 2P; 230V; 60 Hz
5. LIGHT CONTROL SWITCHES SHALL BE RATED 16 AMPERES, 230 Vac. REFRIGIRATOR OUTLET PLUG-IN TYPE G.E CIRCUIT BREAKER
6. UNLESS OTHERWISE SPECIFIED PULLBOXES OR JUNCTION BOXES SHALL BE PROVIDED 15A/2P 15A/2P
WHENEVER REQUIRED AND NECESSARY, ALTHOUGH SUCH BOXES ARE NOT INDICATED
LIGHTING OUTLET LIGHTING OUTLET
ON PLANS.
7. FOR EACH SPARE CIRCUIT IN PANELBOARD, PROVIDE AN EMPTY CONDUIT 20MM (3/4") DIA.
RANGE OUTLET 20A/2P 20A/2P
TERMINATING TO A COVERED SQUARE BOX.
CONVENIENCE OUTLET CONVENIENCE OUTLET
8. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL BE BRAND NEW AND OF APPROVED
TYPE FOR BOTH LOCATION AND PURPOSES.
RANGE HOOD OUTLET 20A/2P 20A/2P
9. ALL METAL FRAMES SHALL BE PROPERLY AND ADEQUATELY GROUNDED. GROUND WIRE SHALL AIRCON:SPLIT TYPE AIRCON:SPLIT TYPE
BE PROVIDED ON ALL EQUIPMENT FEEDER. MAIN LIGHT 30A/2P 30A/2P
10. MOUNTING HEIGHTS SHALL BE AS FOLLOWS:
a. LIGHT SWITCHES 1.20m A.F.F. AT CENTER
CIRCUIT HOMERUN RANGE OUTLET RANGE / RANGE HOOD
b. RECEPTACLES 0.30m A.F.F. N 20A/2P 30A/2P
c. COUNTER TOP OUTLET 1.10m A.F.F.
d. RANGEHOOD OUTLET
e. PANELBOARDS
1.30m A.F.F.
AS REQUIRED UNDERFIELD CONDITION
SINGLE GANG SWITCH REFRIGERATOR WASHING MACHINE
S1 30A/2P
f. GROUND FAULT INTERRUPTER 1.10m A.F.F.
g. RANGE OUTLET 0.50m A.F.F. DRYER SPARE-1
h. REFRIGERATOR OUTLET
i. ACU's ( WINDOW TYPE )
0.50m A.F.F.
AS REQUIRED UNDERFIELD CONDITION
TWO GANG SWITCH
S2
11.OUTLET BOXES SHALL BE AS FOLLOWS:
LIGHT OUT 1-1/2" DEEP, 4" OCTAGONAL BOX 1 OR 2 WAY ENTRIES
2-1/8" DEEP, 4" OCTAGONAL BOX 3 OR 4 WAY ENTRIES PB PANEL BOARD
RECEPTACLES AND TELEVISION ANT.
AND TELEPHONE OUT 2-1/8" DEEP, 2"X4" UTILITY BOX 1 OR 2 RACEWAY ENTRIES
1-1/2" DEEP, 4" SQUARE BOX WITH 1-GANG RAISED
LEGEND
E E ONE-LINE DIAGRAM
1 2 SCALE NTS 2 2 SCALE NTS
PLASTIC COVER FOR 3 OR 4 RACEWAY ENTRIES
12. ALL FLUORESCENT LAMPS SHALL BE PROVIDED WITH POLYESTER FILLED PRE-HEAT
THERMALLY PROTECTED HIGH POWER BALLAST. PANELPB
CKT. LOAD DESCRIPTION
13.DUPLEX RECEPTACLES SHALL BE RATED 10 AMP, 250 VOLTS, ROUNDED SLOT FOR 220 VOLTS AND
CKT. BREAKER SIZE OF WIRE, GROUNDING AND CONDUIT
SPECIAL OUTLETS SHALL BE RATED 15AMP.,250 VOLTS AS REQUIRED. NO. VOLT. PH L.O FULL LOAD
C.O WATTS
14. THE CONTRACTOR SHALL SECURE ALL PERMITS AND PAY FEES REQUIRED FOR THE WORKS, AND SHALL
FURNISH THE OWNER THROUGH THE ENGINEER'S FINAL CERTIFICATE OF INSPECTION AND APPROVAL AMPHERES P AT AF
FROM PROPER GOVERNMENT AUTHORITIES FOR COMPLETE WORKS. 2
15. EXPOSED CONDUIT RUN SHALL BE INSTALLED PARALLEL TO OR PERPENDICULAR WITH THE FLOOR AND 1 LIGHTING OUTLET 230 1 9 900 3.91 2 15 50 2-2.0mm THHN WIRE IN 15mmØ PVC
SUPPORTED BY CLAMPS EVERY 152.4 CM, DIAGONAL RUN SHALL NOT BE ACCEPTED. (THIS IS ALSO 2
APPLICABLE TO CONDUITS RUNNING OVERHEAD INSIDE CEILING ). 2 LIGHTING OUTLET 230 1 8 800 3.48 2 15 50 2-2.0mm THHN WIRE IN 15mmØ PVC
2 2
2-3.5mm THHN WIRE + 1-3.5mm THHN
16. ALL 30-AMPERES CIRCUIT HOMERUN TO PANELBOARD MORE THAN 30 METERS IN LENGTH 3 CONVENIENCE OUTLET 230 1 12 2160 9.39 2 20 50 GROUND IN 15mmØ PVC
2 2 2
SHALL BE 5.5mm THHN (#10 AWG), UNLESS OTHERWISE SPECIFIED ON PLANS. 2-3.5mm THHN WIRE + 1-3.5mm THHN
17. ADDITIONAL MATERIALS SPECIFICATIONS: 4 CONVENIENCE OUTLET 230 1 8 1440 6.26 2 20 50 GROUND IN 15mmØ PVC
2 2
2-5.5mm THHN WIRE + 1-3.5mm THHN
a. WIRES AND CABLES PHILFLEX OR APPROVED EQUAL 5 AIRCONDITION OUTLET 230 1 1 1HP 8.00 2 20 50 GROUND IN 15mmØ PVC
b. CIRCUIT BREAKER (BOLT-ON TYPE) MITSUBISHI/SQUARE D/ABB/SIEMENS 2 2
2-5.5mm THHN WIRE + 1-3.5mm THHN
c. WIRING DEVICES CLIPSAL C-CONCEPT / NATIONAL WIDE SERIES 6 AIRCONDITION OUTLET 230 1 1 1HP 8.00 2 20 50 GROUND IN 15mmØ PVC
d. POLYVINYL CHLORIDE CONDUIT (PVC) CROWN SUPREME SCH. 40 2 2
2 30 50 2-5.5mm THHN WIRE + 1-3.5mm THHN
e. JUNCTION / UTILITY BOX GA.16 FUMACO 7 RANGE 230 1 1 4000 17.39 GROUND IN 15mmØ PVC
18. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE PROPER IDENTIFICATION AND LABELING OF ALL 2 2
2-5.5mm THHN WIRE + 1-3.5mm THHN
CIRCUIT BREAKER. EACH PANEL WILL BE PROVIDED WITH A TYPEWRITTEN CIRCUIT DIRECTORY. 8 RANGE AND RANGEHOOD OUTLET 230 1 1 4200 18.26 2 30 50 GROUND IN 15mmØ PVC
19. THE JOB SHALL BE EXECUTED IN THE MOST THROUGH PROMPT AND WORKMAN LIKE MANNER, EMPLOYING 2 2
2-3.5mm THHN WIRE + 1-3.5mm THHN
STANDARD TOOLS, EQUIPMENT, METHODS AND GOOD ENGINEERING PRACTICES. THE JOB SHALL BE DONE 9 REFRIGERATOR OUTLET 230 1 1 600 2.61 2 20 50 GROUND IN 15mmØ PVC
COMPLETE IN ALL ASPECTS AS REQUIRED IN PLANS AND SPECIFICATION AND READY FOR OPERATION. 2 2
2-5.5mm THHN WIRE + 1-3.5mm THHN
20. THE DRAWING AND SPECIFICATIONS ARE INTENDED TO PRESENT A GENERAL LAYOUT AND BROAD OUTLINE
10 WASHING MACHINE OUTLET 230 1 1 1840 8.00 2 30 50 GROUND IN 15mmØ PVC
AND DISTANCES OF EQUIPMENT. THE CONTRACTOR IS HEREBY REQUIRED TO MAKE ADJUSTMENT AT THE 2 2
JOBSITE AS LOCATIONS, LEVELS AND DISTANCES ARE GOVERNED BY ACTUAL FIELD CONDITIONS. 2-5.5mm THHN WIRE + 1-3.5mm THHN
11 DRYER 230 1 1 3000 13.04 2 30 50 GROUND IN 15mmØ PVC
21. WIRES SHALL BE COLOR CODED:
LINE 1 --------- BLACK LINE 2 --------- RED GROUND --------- GREEN
12 SPARE 98.35
22. THERE SHALL BE ONLY ONE SERVICE DROP TO THE PROPOSED BUILDING. SECONDARY
COMPUTATION: It = (98.35x(DF=80%)) + 25% (13.04) = 81.94 A
SERVICE ENTRANCE SHALL BE 230 VOLTS, SINGLE-PHASE, 2WIRE+GROUND, 60Hz.
23. NO REVISION IN THE DESIGN SHALL BE DONE WITHOUT THE PRIOR KNOWLEDGE AND APPROVAL OF
THE DESIGNER AND THE OWNER. ANY SUCH REVISION DONE WITHOUT THE APPROVAL SHALL CAUSE = 81.94 AMPERE
RESPONSIBILITY OF THE DESIGNER TO CEASED AS A WHOLE.
USE: 2-22mm2 THHN CU wire & 1-8.0mm2 THHN ground CU wire; 125AT/AF breaker in a 25mm dia. PVC conduit
24. ALL WEATHER-EXPOSED INSTALLATIONS SHALL USE WEATHERPROOF TYPE MATERIALS, ESPECIALLY
WEATHERPROOF CONVENIENCE OUTLET, CAST-BOXES, JUNCTION BOXES SUBMIT SAMPLE FOR APPROVAL.
25. ALL EQUIPMENT WIRE, ROYAL CORDS, SPECIAL TYPE PLUGS AND RECEPTACLE AS REQUIRED
SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. E-2 LOAD SCHEDULE
26. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED 3 2 SCALE NTS
ELECTRICAL ENGINEER AND / OR MASTER ELECTRICIAN.

GENERAL NOTES LEGENDS


-
E-2
LOAD SCHEDULE ONE-LINE DIAGRAM

- NAME
CADD BY: DESIGNED BY: CHECKED BY: APPROVED BY:

SIGN

DATE