You are on page 1of 13

GOA INTERNATIONAL AIRPORT, MOPA

Total Load Requirement for HVAC,PHE & FF System


Client : Megawide Construction DMCC
Contractor : Unique Engineers Pvt Ltd.

ELECTRICAL LOAD OF HVAC ITEMS


BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY

CENTRIFUGAL WATER COOLED CHILLING MACHINE WITH VFD 700TR


1.1 Nos 3 2 1 530 1060 530
(2Working + 1 Standby) , VFD starter panel

CONSTANT FLOW PRIMARY CHILLED WATER PUMPS


Flow Rate : 1554 USGPM Minimum Head: 19M WC Note: 2W+1S
2.1.1 Nos 3 2 1 30
(Starter Panel,Power Cabling,Earhting,Cable Tray work,Termination shall be
provided by Electrical Contrator)

CONSTANT FLOW CONDENSER WATER PUMPS Flow


Rate : 2100 USGPM Minimum Head: 27M WC Note: 2W+1S (Starter
2.2.1 Nos 3 2 1 55
Panel,Power Cabling,Earhting,Cable Tray work,Termination shall be provided by
Electrical Contrator)

VARIABLE FLOW SECONDARY CHILLED WATER PUMPS Flow Rate


2.3.1 Nos 3 2 1 55
: 1554 USGPM Minimum Head : 40M WC Note : 2W+1S ( VFD Panel)

COOLING TOWER : Heat rejection: 26,46,000 kCal/hr Flow Rate : 2100 USGPM
3.1 Nos 3 37.2
Minimum Note: 2W+1S
VFD controlled power panel, inclusive of automatic bypass starters The HVAC
subcontractor shall consider all the necessary power & control cabling, cable tray
works,conduits, double earthing with GI wire,terminations etc from CT panel to
motors.However incoming power cable & earthing upto each CT Panel shall be
provided by Electrical Subcontractor

4.1 Expansion Tank -2500 LTRS Nos 1 1.1 KW

• 230 V, 50 HZ
Power Supply –
Automatic chemical dosing .The necessary power panel and corresponding Preferable UPS
cabling ( in the cable tray) with necessary supports upto the system from power SupplyPower
4.3.1 Nos 2 2 4 - #VALUE!
source to be considered by the HVAC sub-contractor.Panel should be BMS point should be
compatible. within 1 meter
from the
controller.
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY

AIR HANDLING UNITS (Floor Mounted AHU)


5.1.1 GL-ZONE-01-01, 35.8TR(SA-16100CFM,FA-1700CFM) Each 1 2 3 3 3
5.1.2 GL-ZONE-01-02, 35.8TR(SA-16100CFM,FA-1700CFM) Each 1 2 3 3 3
5.1.3 GL-ZONE-01-03, 35.1TR(SA-15800CFM,FA-1250CFM) Each 1 2 3 3 3
5.1.4 GL-ZONE-01-04, 13.3TR(SA-6000CFM) Each 1 2 3 3 3
5.1.5 GL-ZONE-01-05, 13.3TR(SA-6000CFM) Each 1 2 3 3 3
5.1.6 GL-ZONE-03-01, 43.0TR(SA-17950CFM,FA-1300CFM) Each 1 2 3 3 3
5.1.7 GL-ZONE-03-02, 43.0TR(SA-17950CFM,FA-1300CFM) Each 1 2 3 3 3
5.1.8 GL-ZONE-03-03, 43.0TR(SA-17950CFM,FA-1300CFM) Each 1 2 3 3 3
5.1.9 GL-ZONE-04-01, 70.0TR(SA-27000 CFM,FA-2510 CFM) Each 1 2 3 3 3
5.1.10 GL-ZONE-05-01, 36.1TR(SA-16250 CFM,FA-3100 CFM) Each 1 2 3 3 3
5.1.11 GL-ZONE-05-02, 36.1TR(SA-16250 CFM) Each 1 2 3 3 3
5.1.12 GL-ZONE-05-03, 36.1TR(SA-16250 CFM) Each 1 2 3 3 3
5.1.13 GL-ZONE-05-04, 36.1TR(SA-16250 CFM) Each 1 2 3 3 3
5.1.14 GL-ZONE-05-05, 22.7TR(SA-10200 CFM) Each 1 2 3 3 3
5.1.15 GL-ZONE-05-06, 40.4TR(SA-18200 CFM,FA-3100CFM) Each 1 2 3 3 3
5.1.16 GL-ZONE-08-01, 54.0TR(SA-14500 CFM,FA-1300 CFM) Each 1 2 3 3 3
5.1.17 GL-ZONE-09A-01, 45.0TR(SA-12100CFM,FA-2725CFM) Each 1 2 3 3 3
5.1.18 GL-ZONE-11-01, 15.6TR(SA-7000CFM,FA-120CFM) Each 1 2 3 3 3
5.1.19 GL-ZONE-12A-01, 33.2TR(SA-12200 CFM,FA-2120 CFM) Each 1 2 3 3 3
5.1.20 GL-ZONE-09-01, 13.8TR(SA-6200CFM,FA-800CFM) Each 1 2 3 3 3
5.1.21 L1-ZONE-01-01, 22.8TR(SA-9100CFM,FA-1200CFM) Each 1 2 3 3 3
5.1.22 L1-ZONE-01-02, 22.8TR(SA-9100CFM,FA-1200CFM) Each 1 2 3 3 3
5.1.23 L1-ZONE-01-03, 22.8TR (SA-9100CFM,FA-1200CFM) Each 1 2 3 3 3
5.1.24 L1-ZONE-01-04, 22.8TR (SA-9100CFM,FA-1500CFM) Each 1 2 3 3 3
5.1.25 L1-ZONE-02-01, 37.8TR (SA-17000 CFM,FA-1850 CFM) Each 1 2 3 3 3
L1-ZONE-03-01, 32.0 TR (SA-11600CFM,FA-1950CFM)
5.1.26 Each 1 2 3 3 3
5.1.27 L1-ZONE-03-02, 32.0TR (SA-11600 CFM,FA-1950 CFM) Each 1 2 3 3 3
5.1.28 L2-ZONE-01-01, 34.0TR(SA-15000CFM,FA-1450CFM) Each 1 2 3 3 3
5.1.29 L2-ZONE-01-02, 34.0TR (SA-15000 CFM,FA-1450CFM) Each 1 2 3 3 3
5.1.30 L2-ZONE-01-03, 23.0TR (SA-10000CFM,FA-1450CFM) Each 1 2 3 3 3
5.1.31 L2-ZONE-01-04, 18.0TR (SA-8000CFM,FA-1450CFM) Each 1 2 3 3 3
5.1.32 L2-ZONE-01-05, 34.0TR (SA-15000CFM,FA-2600CFM) Each 1 2 3 3 3
5.1.33 L2-ZONE-02-01, 60.2TR (SA-22000CFM,FA-4150CFM) Each 1 2 3 3 3
5.1.34 L2-ZONE-03-01, 40.0TR (SA-17800CFM,FA-2175CFM) Each 1 2 3 3 3
5.1.35 L2-ZONE-04-01, 34.0TR (SA-15000 CFM,FA-1600 CFM) Each 1 2 3 3 3
5.1.36 L2-ZONE-04-02, 34.0TR (SA-15000CFM,FA-1600 CFM) Each 1 2 3 3 3
5.1.37 L2-ZONE-04-03, 34.0TR (SA-15000CFM,FA-1600CFM) Each 1 2 3 3 3
5.1.38 L2-ZONE-04-04, 34.0TR (SA-15000CFM,FA-1600CFM) Each 1 2 3 3 3
5.1.39 L2-ZONE-04-05, 34.0TR (SA-15000CFM,FA-1600CFM) Each 1 2 3 3 3
5.1.40 L2-ZONE-04-06, 34.0TR (SA-15000CFM,FA-1600CFM) Each 1 2 3 3 3
5.1.41 L2-ZONE-04-07, 34.0TR (SA-15000CFM,FA-1600CFM) Each 1 2 3 3 3
5.1.42 L2-ZONE-04-08, 34.0TR (SA-15000CFM,FA-1600CFM) Each 1 2 3 3 3
5.1.43 L2-ZONE-04-09, 34.0TR (SA-15000CFM,FA-1600CFM) Each 1 2 3 3 3
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY
5.1.44 L2-ZONE-04-10, 34.0TR (SA-15000CFM,FA-1600CFM) Each 1 2 3 3 3
5.1.45 L2-ZONE-04-11, 34.0TR (SA-15000CFM,FA-1600CFM) Each 1 2 3 3 3
5.1.46 L2-ZONE-04-12, 34.0TR (SA-15000CFM,FA-1600CFM) Each 1 2 3 3 3
AHU local control panel

5.3.1 GL-CSU-03, 5.0 TR(SA-1000 CFM,FA-500CFM) ESP : 20MM Each 1 2 3 3 3


5.3.2 GL-CSU-06,6.5TR(SA-2800CFM,FA-300CFM) ESP : 20MM Each 1 2 3 3 3
5.3.3 GL-CSU-07,8.0TR(SA-3000CFM,FA-305CFM) ESP : 20MM Each 1 2 3 3 3
5.3.4 GL-CSU-04, 8.5TR(SA-3800CFM,FA-400CFM) ESP : 20MM Each 1 2 3 3 3
5.3.5 GL-CSU-05,12.5TR(SA-5000CFM,FA-1500CFM) ESP : 20MM Each 1 2 3 3 3
5.3.6 GL-CSU-01,17.3TR(SA-7800CFM,FA-511CFM) ESP : 20MM Each 1 2 3 3 3
Ceiling Suspended AHU local control panel

5.5.1 Treated fresh air unit (12.0TR/ 3100 CFM) ESP : 25mm WC Each 2 2 4 4 4
Treated Fresh Air Handling Unit local control panel

6.0.1 1.0 TR Fan Coil Units covering all the above items. Each 33 48 81 81 81
6.0.2 1.5 TR Fan Coil Units covering all the above items. Each 19 36 55 55 55
6.0.3 2.0 TR Fan Coil Units covering all the above items. Each 40 77 117 117 117
6.0.4 2.5 TR Fan Coil Units covering all the above items. Each 18 35 53 53 53
6.0.5 3.0 TR Fan Coil Units covering all the above items. Each 2 2 4 4 4

Cassette Unit 4 Way Discharge (Chilled Water) -For Fixed Linked Bridges (FLB)

6.1.1 3.5TR/1140cfm Nos 16 32 48 48 48


6.1.2 1.8TR/650cfm Nos 8 16 24 24 24
6.1.3 1.5TR/450cfm Nos 2 4 6 6 6
Control cabling from actuators to logic controller and power cabling for
thermostat ,tray work will be in HVAC sub contractor's scope of work.

7.0 PRECISION AIR CONDITIONING UNITS ( DX TYPE PAU)

7.0.1 Capacity : 5.5 TR / 2200 CFM / ESP : 25mm WC - PTB Server room Each 4 4 8 8 8
Capacity : 3.0 TR / 1900 CFM / ESP : 25mm WC - ATCT - Data Equipment Room ,
7.0.2 Each 4 8 12 12 12
UFC Link Room,IT & C Room,UPS & Battery Room
7.0.3 Capacity : 8.5TR / 4560 CFM / ESP : 25MM WC - ATCTB - CNS Equipment Room Each 2 4 6 6 6
7.0.4 Capacity : 4.0TR / 2625 CFM / ESP : 25MM WC - ATCTB - CNS Rooms Each 6 12 18 18 18
7.0.5 Capacity : 3.0TR / 1880CFM / ESP : 25MM WC - ATCTB - IT Server Room Each 2 4 6 6 6
7.0.6 Capacity : 2.0TR / 1175 CFM / ESP : 25MM WC - ATCTB - CNS Rooms Each 20 40 60 60 60
Power & Control cabling between indoor & Outdoor units - HVAC Scope

(VAV) control units


8.18
8.18.1 100 - 750 cfm Each 5 5 10 10 10
8.18.2 120 - 1000 cfm Each 3 3 6 6 6
8.18.3 150 - 1500 cfm Each 2 2 4 4 4
8.18.4 320 - 3000 cfm Each 1 1 2 2 2

12.1 VRF OUTDOOR UNITS


12.1.1 Actual Capacity : 32HP Nos 3 6 9 9 9
12.1.2 Actual Capacity : 30HP Nos 2 3 5 5 5
12.1.3 Actual Capacity : 26HP Nos 1 0 1 1 1
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY
12.1.4 Actual Capacity : 20HP Nos 2 3 5 5 5
12.1.5 Actual Capacity : 18HP Nos 1 0 1 1 1
12.1.6 Actual Capacity : 16HP Nos 2 2 4 4 4
12.1.7 Actual Capacity : 14HP Nos 1 2 3 3 3
12.1.8 Actual Capacity : 12HP Nos 2 4 6 6 6
12.1.9 Actual Capacity : 10HP Nos 2 4 6 6 6
12.1.10 Actual Capacity : 8HP Nos 3 6 9 9 9
12.1.11 Actual Capacity : 6HP Nos 4 8 12 12 12
12.1.12 Actual Capacity : 5HP Nos 1 2 3 3 3
12.1.13 Actual Capacity : 4HP Nos 1 2 3 3 3
Power cabling/ wiring from MCB/MCCB/ELMCB to the Outdoor unit .
12.2 VRF INDOOR UNITS
(a) Power & control cabling from nearest socket outlet to the indoor unit.
d) All the wiring interconnecting the indoor & outdoor unit shall be laid through MS
Conduits, junction boxes etc.
CEILING SUSPENDED AIR HANDLING UNIT WITH DX COILS MIN 6 ROW
12.2.1
(DOUBLE SKIN AS PER ABOVE AHU SPECIFICAITON)
12.2.1.1 ACTUAL CAPACITY : 14 TR / 5000 CFM / ESP : 25MM Nos 2 2 4 4 4

CEILING SUSPENDED TREATED FRESH AIR UNITS WITH DX COILS MIN 8


12.2.2
ROW (DOUBLE SKIN AS PER ABOVE TFA SPECIFICATION)
12.2.2.1 ACTUAL CAPACITY : 7.6TR / 1200 CFM / ESP : 25MM Nos 1 2 3 3 3
12.2.2.2 ACTUAL CAPACITY : 6.9TR / 1100 CFM / ESP : 25MM Nos 1 2 3 3 3
12.2.2.3 ACTUAL CAPACITY : 6.3TR / 950 CFM / ESP : 25MM Nos 5 10 15 15 15
12.2.2.4 ACTUAL CAPACITY : 5.2TR / 800 CFM / ESP : 25MM Nos 1 2 3 3 3

12.2.3 Hi-wall Unit


Power & control cabling from indoor to Outdoor unit
12.2.3.1 Actual Capacity : 2.1TR / 650CFM Nos 23 44 67 67 67
12.2.3.2 Actual Capacity : 2.0TR / 600CFM Nos 1 2 3 3 3
12.2.3.3 Actual Capacity : 1.5TR / 535CFM Nos 3 6 9 9 9
12.2.3.4 Actual Capacity : 1.3TR / 424CFM Nos 8 16 24 24 24
12.2.3.5 Actual Capacity : 1.0TR / 350CFM Nos 3 -6 -3 -3 -3
12.2.3.6 Actual Capacity : 1.0TR / 300CFM Nos 5 10 15 15 15
12.2.3.7 Actual Capacity : 0.8TR / 177CFM Nos 1 0 1 1 1
12.2.3.8 Actual Capacity : 0.6TR / 160CFM Nos 7 14 21 21 21

12.2.4 Cassette Unit


Power & Control Cabling between indoor & outdoor units. All cassettes units are
with cordless remote control
12.2.4.1 4 WAY TYPE
12.2.4.1.1 Actual Capacity :0.8TR/353cfm Nos 15 20 35 35 35
12.2.4.1.2 Actual Capacity :1.2TR/530cfm Nos 10 18 28 28 28
12.2.4.1.3 Actual Capacity :1.6TR/777cfm Nos 19 24 43 43 43
12.2.4.1.4 Actual Capacity :2.0TR/830cfm Nos 15 22 37 37 37
12.2.4.1.5 Actual Capacity :2.5TR/830cfm Nos 5 0 5 5 5
12.2.4.1.6 Actual Capacity :3TR/1130cfm Nos 6 12 18 18 18
12.2.4.1.7 Actual Capacity :3.2TR/1165cfm Nos 8 15 23 23 23
12.2.4.1.8 Actual Capacity :4TR/1218cfm Nos 2 4 6 6 6
12.2.4.1.9 Actual Capacity :4.5TR/1471cfm Nos 3 3 6 6 6

12.2.4.2 2WAY TYPE


12.2.4.2.1 Actual Capacity :0.6TR/177cfm Nos 6 12 18 18 18
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY
12.2.4.2.2 Actual Capacity :0.8TR/318cfm Nos 4 8 12 12 12
12.2.4.2.3 Actual Capacity :1.2TR/424cfm Nos 2 4 6 6 6
12.2.4.2.4 Actual Capacity :2.0TR/582cfm Nos 1 2 3 3 3
12.2.4.2.5 Actual Capacity :2.5TR/741cfm Nos 1 2 3 3 3
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY

12.2.4.3 1WAY TYPE


12.2.4.3.1 Actual Capacity :0.8TR/388cfm Nos 5 10 15 15 15
12.2.4.3.2 Actual Capacity :2.0TR/635cfm Nos 6 12 18 18 18

13.0 DX SPLIT UNIT SYSTEM

13.1 Hi-Wall Units


.
The indoor and outdoor unit motors should be suitable for operation on 220 V +
10%, 50 Hz, 1 phase AC supply. The necessary power cabling from indoor to
outdoor unit and from indoor to socket shall be considered. The cabling shall be
routed in the MS conduit.
13.1.1 Actual Capacity :2.0 TR/600cfm Wall mounted Hi-wall unit Nos 19 22 41 41 41
13.1.2 Actual Capacity :1.7 TR/500cfm Wall mounted Hi-wall unit Nos 3 6 9 9 9
13.1.3 Actual Capacity :1.5 TR/500cfm Wall mounted Hi-wall unit Nos 51 90 141 141 141
13.1.4 Actual Capacity :1.0 TR/350cfm Wall mounted Hi-wall unit Nos 8 14 22 22 22

13.2 4 WAY Cassette Units (ATC - Apron Control Room)


Power, earthing and Control cabling from indoor unit to outdoor unit should be
included.
The indoor and outdoor unit motors should be suitable for operation on 220 V +
10%, 50 Hz, 1 phase AC supply.
13.2.1 Actual Capacity :2TR/4W/830cfm Nos 1 2 3 3 3

14.1 Axial Fan (Fresh air)

14.1.1 8550CFM/15mmwg ESP (Transformer room & LT Panel) Nos 2 2 4 4 4


14.1.2 7400CFM/15mmwg ESP ( LT Panel) Nos 1 1 2 2 2
14.1.3 1800CFM/15mmwg ESP ( Transformer room , LT Panel) Nos 3 4 7 7 7
14.1.4 4150CFM/15mmwg ESP (DG Change over Panel room) Nos 7 11 18 18 18
14.1.5 2100CFM/15mmwg ESP (HT Panel room) Nos 4 6 10 10 10
14.1.6 23100CFM/15mmwg ESP (Pump room) Nos 2 3 5 5 5
14.1.7 1500CFM/15mmwg ESP (HT Panel room) Nos 2 3 5 5 5
14.1.8 1400CFM/15mmwg ESP ( Transformer room) Nos 2 3 5 5 5
14.1.9 2500CFM/15mmwg ESP (LT Panel room) Nos 2 3 5 5 5
14.1.10 8750CFM/20mmwg ESP(FA-ATC-STAIRCASE PRESS FAN-01) Nos 1 1 2 2 2
14.1.11 20000CFM/25mmwg ESP(FA-ATC-LIFT LOBBY PRESS FAN-01) Nos 1 1 2 2 2
14.1.12 LG-FA-07/16400CFM/20mm(GL SUBSTATION 01 PRESS. (91-94,C-E) Nos 1 2 3 3 3
14.1.13 L1-FA-11/3450CFM/20mm(SWITCH ROOM (Grid 85-86,E-F) Nos 1 2 3 3 3
14.1.14 LG-FA-30/15600CFM/20mm(GL SUBSTATION 03 PRESS. (110-114,C-E) Nos 1 2 3 3 3
14.1.15 L1-FA-33/12600CFM/20mm(LIFT LOBBY 01 LL-01 (E-F/89-90)-FIRE RATED Nos 1 2 3 3 3
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY

14.1.16 L1-FA-34/12200CFM/20mm(LIFT LOBBY 02 LL-02 (E-F/102-103)-FIRE RATED Nos 1 2 3 3 3

14.1.17 L1-FA-35/12200CFM/20mm(LIFT LOBBY 03 LL-03 (E-F/108-109)-FIRE RATED Nos 1 2 3 3 3


L1-FA-36,37,38,39,40,41,42,43/10100CFM/25 mm WG(STAIRCASES 01 TO 08)-
14.1.18 Nos 8 16 24 24 24
FIRE RATED
14.1.19 L1-FA-44,45,46,47/8750CFM/20mm(FIX LING BRIDGE 01 02 03 04 (CODE C) Nos 4 8 12 12 12
14.1.20 L1-FA-48/12600CFM/20mm(FIX LING BRIDGE 05 (MARS STAND) Nos 1 2 3 3 3
14.1.21 L1-FA-99/975CFM/20mm(SWITCH ROOM (Grid 101-102, Q-R) Nos 1 2 3 3 3
14.1.22 LG-FA-27/2850CFM/15mm WG(GL BATTERY ROOM FA) Nos 1 2 3 3 3

Pressurization fans Fire Rated (dual speed) - For Protected Corridor

L1-FA-59/7700CFM/20mm-PROTECTED CORRIDOR 01 (86-89,D-E)(DUAL


14.1.23 Nos 3 6 9 9 9
MODE)
L1-FA-60/11900CFM/20mm-PROTECTED CORRIDOR 02 (91-99,D-E)(DUAL
14.1.24 Nos 1 2 3 3 3
MODE)
L1-FA-61/13650CFM/20mm-PROTECTED CORRIDOR 03 (100-108,D-E)(DUAL
14.1.25 Nos 1 2 3 3 3
MODE)
L1-FA-62/8910CFM/20mm-PROTECTED CORRIDOR 04 (100-108,H-J)(DUAL
14.1.26 Nos 1 2 3 3 3
MODE)
L1-FA-72/9750CFM/20mm-PROTECTED CORRIDOR 06 (96-105,J-G)(DUAL
14.1.27 Nos 1 2 3 3 3
MODE)
LG-FA-73/12450CFM/20mm-(PROTECTED CORRIDOR 07 (90-100,L-M)(DUAL
14.1.28 Nos 1 2 3 3 3
MODE)

control panel for Axial Fans (Fresh Air & Dual speed)

14.3 Axial Fan (Exhaust)

14.3.1 16750CFM/20mmwg ESP(EX FAN 01 & 02) SWH Nos 2 4 6 6 6


14.3.2 1800CFM/15mmwg (LT PANEL AND TRANSFORMER ROOM)-CFRS Nos 2 2 4 4 4
14.3.3 13500CFM/ 25mmwg ESP (EX-UB-PR FAN 02) Nos 1 1 2 2 2
14.3.4 20000CFM/ 25mmwg ESP (EX-UB-PLR FAN 03) Nos 3 3 6 6 6
14.3.5 30000CFM/ 20mmwg ESP (EX-UB-ELR FAN 04) Nos 1 1 2 2 2
14.3.6 10000CFM/ 20mmwg ESP (EX-UB-PR FAN 02) Nos 1 1 2 2 2
14.3.7 L1-EX-16-3450 CFM/20mm(SWITCH ROOM (Grid 85-86,E-F) Nos 1 2 3 3 3
14.3.8 L1-EX-98/975CFM/20mm(SWITCH ROOM (Grid 101-102, Q-R) Nos 1 2 3 3 3
14.3.9 CL-EX-77/5250CFM/20mm(CULVERT LEVEL AREA) Nos 1 2 3 3 3
14.3.10 101000CFM/20mmwg ESP(CFRM-PUMP ROOM) Nos 1 1 2 2 2
14.3.11 2400CFM/15mmwg ESP ( Transformer room & LT Panel) Nos 1 1 2 2 2
14.3.12 23100CFM/15mmwg ESP (Pump room) Nos 1 2 3 3 3
14.3.13 4150CFM/15mmwg ESP (DG Change over Panel room) Nos 3 3 6 6 6
14.3.14 2100CFM/15mmwg ESP (HT Panel room) Nos 2 2 4 4 4
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY

BATTERY ROOM FANS


14.3.15 1700CFM/15mmwg ESP (PLC+BATTERY ROOM) Nos 1 2 3 3 3
14.3.16 1350CFM (GF battery Room) Nos 2 4 6 6 6
14.3.17 1500CFM/15mmwg ESP (HT Panel room) Nos 1 1 2 2 2
14.3.18 1400CFM/15mmwg ESP ( Transformer room) Nos 1 1 2 2 2
14.3.19 2500CFM/15mmwg ESP (LT Panel room) Nos 1 1 2 2 2
LG-EX-26/3053CFM/20mm-AXIAL FLOW (SMOKE SPILL)GL BATTERY ROOM
14.3.20 Nos 1 2 3 3 3
EX (104-105,C-E)

control panel for Axial Fans (Exhast Fans)

14.5 Centrifugal Fan


14.5.1 LG-EX-08/7000CFM/60mm (DOM. F&B KITCHEN EX. (97-98,C-E) Nos 1 2 3 3 3
14.5.2 LG-FA-09/5900CFM/60mm(DOM F&B KITCHEN FA. (97-98,C-E) Nos 1 2 3 3 3
14.5.3 L1-EX-86/2600CFM/15mm(SMOKING ROOM 02 (Grid 90-92,E-F)(FIRE RATED) Nos 1 2 3 3 3

14.5.4 L1-EX-88/1600CFM/15mm (SMOKING ROOM 01 (110-111,E-F)(FIRE RATED) Nos 1 2 3 3 3


14.5.5 L1-EX-49/5650CFM/50mm(L2 DOM. F&B01 KITCHEN EX. (101-103,F-H) Nos 1 2 3 3 3
14.5.6 L1-FA-50/4800CFM/30mm(L2 DOM. F&B01 KITCHEN FA (101-103,F-H) Nos 1 2 3 3 3
14.5.7 L1-EX-51/2700CFM/50mm(L2 DOM. FINE DINE KITCHEN EX. (97-98,F-G) Nos 1 2 3 3 3
14.5.8 L1-FA-52/2300CFM/15mm(L2 DOM. FINE DINE KITCHEN FA (97-98,F-G) Nos 1 2 3 3 3
14.5.9 L1-EX-53/2400CFM/50mm(L2 COM. FINE DINE KITCHEN EA (108-109,F-G) Nos 1 2 3 3 3
14.5.10 L1-FA-54/2050CFM/15mm(L2 COM. FINE DINE KITCHEN FA (108-109,F-G) Nos 1 2 3 3 3
14.5.11 L1-EX-55/3050CFM/50mm(L2 INT. F&B01 KITCHEN EX. (109-110,J-G) Nos 1 2 3 3 3
14.5.12 L2-FA-56/2600CFM/15mm(L2 INT. F&B01 KITCHEN FA (109-110,J-G) Nos 1 2 3 3 3
14.5.13 L1-EX-57/3300CFM/50mm(L2 DEP. F&B KITCHEN EX. (93-95,E-F) Nos 1 2 3 3 3
14.5.14 L2-FA-58/2800CFM/15mm(L2 DEP. F&B KITCHEN FA. (93-95,E-F) Nos 1 2 3 3 3
14.5.15 LG-EX-75/9100CFM/50mm-(INT. F&B KITCHEN EXH)(DUAL MODE) Nos 1 2 3 3 3
14.5.16 LG-FA-76/7700CFM/15mm-(INT. F&B KITCHEN FA)(DUAL MODE) Nos 1 2 3 3 3
14.5.17 GL-EX-102/4300CFM/20mm-F&B - EA (AIRPORT VILLAGE) Nos 1 2 3 3 3
14.5.18 2450CFM/20mmwg ESP (Toilets/Pantry/Housekeeping-ATCTB) Nos 1 1 2 2 2
14.5.19 1800CFM/20mmwg ESP (EX-ATCT-SWITCH ROOMS) Nos 1 1 2 2 2

control panel for Centrifugal Fans

14.7 Propeller Fan

14.7.1 550CFM/8mmwg ESP (Battery room) Nos 2 2 4 4 4


14.7.2 100CFM/5mmwg ESP (Toilet, Washroom) Nos 5 4 9 9 9
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY
14.7.3 1000CFM/10mmwg ESP (Pumproom) Nos 6 6 12 12 12
14.7.4 200CFM/5mmwg ESP (Stores, Foam store) / Switch Room Nos 7 12 19 19 19
14.7.5 150CFM/5mmwg ESP (Stores) Nos 2 3 5 5 5
14.7.6 400CFM/5mmwg ESP (Hose repair) Nos 2 3 5 5 5
14.7.7 150CFM/5mmwg ESP (Pantry) Nos 1 1 2 2 2
14.7.8 100CFM/5mmwg ESP (Store) Nos 3 5 8 8 8
14.7.9 150CFM/5mmwg ESP (toilet) Nos 6 7 13 13 13
14.7.10 100CFM/5mmwg ESP (Foam) Nos 2 3 5 5 5
14.7.11 700CFM/8mmwg ESP (Maintenance room) Nos 2 3 5 5 5
14.7.12 300CFM/5mmwg ESP (Store) Nos 2 3 5 5 5
14.7.13 100CFM/5mmwg ESP (Toilet) Nos 5 7 12 12 12
14.7.14 380CFM/8mmwg ESP (Battery room) Nos 2 3 5 5 5
14.7.15 150CFM/5mmwg ESP (Toilet) Nos 1 -1 0 0 0
Battery
14.7.16 450CFM (Battery Room) Nos 1 2 3 3 3

control panel Propellar Fans

14.9 Inline Fan

14.9.1 450CFM/15mm WG ESP (Toilet) Nos 1 1 2 2 2


14.9.2 300CFM/10mm WG ESP (Toilet) Nos 1 0 1 1 1
14.9.3 950CFM/20mm WG ESP Corridor Nos 1 2 3 3 3
14.9.4 650CFM/20mm WG ESP Corridor Nos 1 2 3 3 3
14.9.5 L1-EX-01/150CFM/15mm WG(VIP PANTRY 01 (83-84)- MIXED FLOW Nos 1 2 3 3 3
14.9.6 L1-EX-02/4800CFM/20mm WG(MALE TOILET (87-89,E-F) Nos 1 2 3 3 3
LG-EX-03/2100CFM/15mm WG(GL COmm WGERCIAL WAREHOUSE 01 EX (87-
14.9.7 Nos 1 2 3 3 3
89,C-E)
14.9.8 LG-EX-05/1500CFM/20mm WG(BOH MALE TOILET (93-94,E-F) Nos 1 2 3 3 3
LG-EX-06/1250CFM/15mm WG(CUSTOM WAREHOUSE (106-109,E-F)- MIXED
14.9.9 Nos 1 2 3 3 3
FLOW
LG-EX-10/1400CFM/15mm WG(DOM COmm WGERCIAL WAREHOUSE EX. (96-
14.9.10 Nos 1 2 3 3 3
97,C-E)
14.9.11 L1-EX-12/1040CFM/20mm WG(GL BOH TOILET (MALE TOILET) (98-99,E-F) Nos 1 2 3 3 3
14.9.12 L1-FA-04/290CFM/20mm WG(GL BOH TOILET (MALE TOILET) (98-99,E-F) Nos 1 2 3 3 3
14.9.13 L1-EX-14/450CFM/25mm WG(DOMESTIC F&B EXHAUST (Grid 84-85,E-F) Nos 1 2 3 3 3
14.9.14 L1-FA-15/400CFM/20mm WG(DOMESTIC F&B FRESH AIR (Grid 84-85,E-F) Nos 1 2 3 3 3
14.9.15 L1-EX-13/2880CFM/20mm WG(MALE TOILETS (97-99,E-F) Nos 1 2 3 3 3
14.9.16 L1-EX-18/650CFM/15mm WG(REFUGE STORAGE (90-92,E-F) Nos 1 2 3 3 3
14.9.17 L1-EX-19/2225CFM/20mm WG(BOH MALE TOILET (105-106,E-F) Nos 1 2 3 3 3
14.9.18 L1-EX-20/1750CFM/20mm WG(MALE TOILETS (104-106,E-F) Nos 1 2 3 3 3
14.9.19 L1-EX-21/800CFM/10mm WG(TOILET (102-103,G-H) Passport control Nos 1 2 3 3 3
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY

L1-EX-22/5825CFM/25mm WG(FEMALE TOILETS (104-106,E-F) - DUCTED


14.9.20 Nos 1 2 3 3 3
INLINE FAN
LG-EX-23/300CFM/15mm WG(GL ENGG. & MAINTAINANCE STORE EX (92-
14.9.21 Nos 1 2 3 3 3
93,E-F)
LG-FA-25/18300CFM/20mm WG(GL SUBSTATION 02 PRESS. (101-105,C-E) -
14.9.22 Nos 1 2 3 3 3
MIXED FLOW
LG-EX-28/1400CFM/15mm WG (INT. COmm WG. WARE HOUSE EX. (107-
14.9.23 Nos 1 2 3 3 3
108,C-E)
14.9.24 L1-EX-31/1000CFM/25mm WG(MALE TOILET (111-113) Nos 1 2 3 3 3
14.9.25 GL-EX-17/1500CFM/25mm WG(MALE TOILET (110-111,D-F) Nos 1 2 3 3 3
14.9.26 L1-EX-63/2000CFM/25mm WG(AOCC FEMALE TOILET (115-1116,D-E) Nos 1 2 3 3 3
14.9.27 L1-EX-32/950CFM/15mm WG(DUTY FREE STORAGE (104-105,H-J) Nos 1 2 3 3 3
14.9.28 L1-EX-64/1700CFM/20mm WG(STORAGE (91-93,L-M) Nos 1 2 3 3 3
14.9.29 L1-EX-24/3125CFM/25mm WG(STORAGE (97-100,L-M) Nos 1 2 3 3 3
14.9.30 L1-FA/1300CFM/15mm WG(SWITCH ROOM (K-L/ 99-100) Nos 1 2 3 3 3
L1-EX-82/3000CFM/20mm WG(TOILET BLOCK 01 (FEMALE TOILET) (97-98,P-
14.9.31 Nos 1 2 3 3 3
N)
14.9.32 L1-EX-83/2600CFM/25mm WG(FEMALE TOILET (100-102,R-S) Nos 1 2 3 3 3
14.9.33 GL-EX-104/100CFM/10mm WG(PANTRY FOR LOUNGES (106-107,R-S) Nos 1 2 3 3 3
14.9.34 L1-EX-84/2570CFM/20mm WG(MALE TOILET (109-110,Q-S) Nos 1 2 3 3 3
14.9.35 L1-EX-85/3680CFM/20mm WG(MALE TOILET (PLAZA) Nos 1 2 3 3 3
14.9.36 L1-FA-87/2210CFM/20mm WG(SMOKING ROOM 02 (Grid 90-92,E-F) Nos 1 2 3 3 3
14.9.37 L1-FA-89/2635CFM/20mm WG(SMOKING ROOM 01 (110-111,E-F) Nos 1 2 3 3 3
14.9.38 L1-EX-90/350CFM/20mm WG(CUSTOM OFFICE TOILET (Grid 108-109,E-F) Nos 1 2 3 3 3
14.9.39 L1-EX-91/550CFM/20mm WG(BOH MALE & FEMALE TOILET (97-98,J-H) Nos 1 2 3 3 3
L1-EX-65/800CFM/20mm WG(SWITCH ROOM (Grid H-J/95-97) -DUCTED
14.9.40 Nos 1 2 3 3 3
INLINE FAN
L1-FA-92/800CFM/20mm WG(SWITCH ROOM (Grid H-J/95-97) -DUCTED INLINE
14.9.41 Nos 1 2 3 3 3
FAN
L1-EX-66/2225CFM/20mm WG(SWITCH ROOM (Grid 101-102,E-F) -DUCTED
14.9.42 Nos 1 2 3 3 3
INLINE FAN
L1-FA-93/2225CFM/20mm WG(SWITCH ROOM (Grid 101-102,E-F) -DUCTED
14.9.43 Nos 1 2 3 3 3
INLINE FAN
L1-EX-67/2230CFM/20mm WG(SWITCH ROOM (Grid 107-108,E-F) -DUCTED
14.9.44 Nos 1 2 3 3 3
INLINE FAN
L1-FA-94/2230CFM/20mm WG(SWITCH ROOM (Grid 107-108,E-F) -DUCTED
14.9.45 Nos 1 2 3 3 3
INLINE FAN
L1-EX-68/2950CFM/20mm WG(SWITCH ROOM (Grid 117-118,E-F) -DUCTED
14.9.46 Nos 1 2 3 3 3
INLINE FAN
L1-FA-95/2950CFM/20mm WG(SWITCH ROOM (Grid 117-118,E-F) -DUCTED
14.9.47 Nos 1 2 3 3 3
INLINE FAN
L1-EX-69/1850CFM/20mm WG(SWITCH ROOM (Grid 90-91,N-P) -DUCTED
14.9.48 Nos 1 2 3 3 3
INLINE FAN
L1-FA-96/1850CFM/20mm WG(SWITCH ROOM (Grid 90-91,N-P) -DUCTED
14.9.49 Nos 1 2 3 3 3
INLINE FAN
L1-EX-70/2550CFM/20mm WG(SWITCH ROOM (Grid 92-93,E-F) -DUCTED
14.9.50 Nos 1 2 3 3 3
INLINE FAN
L1-FA-97/2550CFM/20mm WG(SWITCH ROOM (Grid 92-93,E-F) -DUCTED
14.9.51 Nos 1 2 3 3 3
INLINE FAN
14.9.52 LG-EX-74/1650CFM/20mm WG(OEM/ SERVICE OFFICE STORE (101-104,E-F) Nos 1 2 3 3 3
14.9.53 GL-EX-100/500CFM/15mm WG(SWITCH ROOM (Grid 93-94,T-U) Nos 1 2 3 3 3
14.9.54 GL-EX-101/400CFM/15mm WG(SWITCH ROOM (Grid 109-110,T-U) Nos 1 2 3 3 3
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY
14.9.55 GL-FA-103/3660CFM/20mm WG(SWITCH ROOM (Grid 109-110,T-U) Nos 1 2 3 3 3
14.9.56 363CFM (Toilet&Store Room) Nos 1 2 3 3 3
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY
14.9.57 200CFM (Pac& Corridor)-Fresh Air Nos 1 2 3 3 3
14.9.58 600CFM (GF Switch Room) Nos 1 2 3 3 3
14.9.59 220CFM (Tiolet) Nos 4 8 12 12 12
14.9.60 350CFM (switch Room) Nos 1 2 3 3 3
14.9.61 100CFM (Pantry) Nos 3 6 9 9 9
Battery
14.9.62 311CFM/20mm WG WG -Battery ROOM ATC Nos 1 2 3 3 3
14.9.63 750CFM (EFBAX Battery Room) Nos 1 2 3 3 3

local control panel

FRESH AIR FANS FOR AHU


14.10.1 3850CFM/30mm WG ESP (FA to AHU) Nos 1 1 2 2 2
14.10.2 4500CFM/30mm WG ESP (FA to AHU) Nos 2 2 4 4 4
14.10.3 11800CFM/30mm WG ESP (FA to AHU) Nos 1 1 2 2 2
14.10.4 3500CFM/30mm WG ESP (FA to AHU) Nos 1 1 2 2 2
14.10.5 4140CFM/30mm WG ESP (FA to AHU) Nos 2 2 4 4 4
14.10.6 1400CFM/20mm WG ESP (FA to AHU) Nos 1 1 2 2 2
14.10.7 5130CFM/30mm WG ESP (FA to AHU) Nos 1 1 2 2 2
14.10.8 1270CFM/20mm WG ESP (FA to AHU) Nos 1 1 2 2 2
14.10.9 3500CFM/30mm WG ESP (FA to AHU) Nos 1 1 2 2 2

14.11 local control panel along with VFD Controller

14.12 Jet Fans

14.12.1 CL-EX-78,79,80,81/1313 cfm(Jet Fan)/750CFM/10MM WG ESP Nos 4 8 12 12 12

14.13 local control panel

14.14 Air Curtains

14.14.1 1200mm(W) X 300mm(D) X 300mm(H) Nos 40 40 80 80 80


14.14.2 1500mm(W) X 300mm(D) X 300mm(H) Nos 10 10 20 20 20

A Total Load 3184 3184

ELECTRICAL LOAD OF PLUMBING & FIRE FIGHTING LOAD


5.1.1 Hydro Pneumatic Domestic Water Pump (Main water Tank) Nos. 1 3 1 13 13 Three Phase
Capacity : 950 LPM Head : 80 Mt (3w+1s)
5.1.2 Hydro Pneumatic Flushing Water Pump (Main water Tank) Nos. 1 2 1 10 10 Three Phase
Capacity : 910 LPM Head : 80mt (2w+1s)
5.1.3 Hydro Pneumatic Domestic Water Pump (UB water Tank) Nos. 1 2 1 7 7 Three Phase
Capacity : 650 LPM Head : 100mt (2w+1s)
5.1.4 Hydro Pneumatic Flushing Water Pump (UB water Tank) Nos. 1 2 1 7 7 Three Phase
Capacity : 650 LPM Head : 80mt (2w+1s)
5.1.5 Hydro Pneumatic Drinking Pump (UB water Tank) Nos. 1 1 1 1 1 Three Phase
Capacity : 100 LPM Head : 100mt (1w+1s)
5.1.6 Hydro Pneumatic Drinking Pump (UB water Tank) Nos. 1 1 1 1 1 Three Phase
Capacity : 50 LPM Head : 100mt (1w+1s)
ELECTRICAL LOAD OF HVAC ITEMS
BOQ Item Final Stand Elect Load Elect Load - Elect Load
Description UOM Working SINGLE PHASE
No. Qty BY KW Each Working Stand BY

5.1.7 Hydro Pneumatic Domestic Water Pump (ATC Tower) Nos. 1 1 1 1 1 Three Phase
Capacity : 105 LPM Head : 80mt (1w+1s)
5.1.8 Hydro Pneumatic Flushing Water Pump (ATC Tower) Nos. 1 1 1 1 1 Three Phase
Capacity : 50 LPM Head : 80mt (1w+1s)
5.1.9 Hydro Pneumatic Domestic Water Pump (CFR Main) Nos. 1 1 1 1 1 Three Phase
Capacity : 100 LPM Head : 90mt (1w+1s)
5.2.1 Capacity : 200LPM Head : 20Mt (1w + 1s) - Raw water tank to WTP transfer Nos. 1 1 1 2.2 2.2 Three Phase
5.3.1 Capacity : 20LPM Head : 20Mt (1w) - CFR Satellite Domestic water tranfer Nos. 1 1 1 1 Three Phase
7.1.1 Submersible Pumps (Dewatering Application) Nos. 4 1 1 4 4 Three Phase
Capacity : 100 LPM HEAD : 20mt (1W+1s)
7.1.2 Submersible Pumps (Sewage Application) Nos. 3 1 1 1 1 Three Phase
Capacity : 25 LPM HEAD : 15mt (1W+1s)
7.1.3 Submersible Pumps (Sewage Application) Nos. 1 1 1 1.1 1.1 Three Phase
Capacity : 100 LPM HEAD : 50mt (1W+1s)
7.1.4 Submersible Pumps (Dewatering Application) Nos. 5 1 1 3 3 Three Phase
Capacity : 60 LPM HEAD : 20mt (1W+1s)
7.1.5 Submersible Pumps (Sewage Application) Nos. 1 1 1 1 1 Three Phase
Capacity : 60 LPM HEAD : 40mt (1W+1s)
7.1.6 Submersible Pumps (Main Sewage Near STP Substation) Nos. 1 2 1 1 1 Three Phase
Capacity : 1200 LPM HEAD : 30mt (2W+1s)
Fire Fighting
5.1.1 Sprinkler Pumps Capacity : 3800 LPM Head : 145 Meter Nos. 2 320 320 Three Phase
5.1.2 Hydrant Pumps Capacity : 3800 LPM Head : 145 Meter Nos. 2 320 320 Three Phase
5.1.3 Jockey Pumps Capacity : 180 LPM Head : 145 Meter Nos. 4 30 30 Three Phase

B Total 726.3 726.3

C Tentative Load for Valves and Gyser Nos 70 70 Single Phase

Total Required Load for HVAC, PHE & FF System (A+B+C) 3980 3980