UGC05-BOQ-STATIONS (E & M)

S. No. Area Code Description Unit Quantity


Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
1 LV Switchboards and Switchgears lN lS lN lS N el S lN S on nel el S ply
N
General Notes for LV Main Switchboards, Sub Main Switchboards and
Local Electrical Panels
a. All the items, parts mentioned in relevant clauses of the Technical
Specifications and not specifically mentioned in BOQ shall be deemd to be
included in the quoted rates, unless specifically excluded.
b. The degree of ingress protection shall be IP54
c. All busbars shall be electrolytic high conductivity TP & N (full size)
copper conductor busbars (as specified in Technical Specification)
d. In case of any contradiction between BOQ / Tech Spec and Drawings, the most
stringent conditions of the above will apply

e. The Switchboards shall be provided with detachable gland plates for entry of
cables from the top / bottom as required
f. All live accessible parts shall be shrouded and all equipment shall be finger
tocuh proof. SMC/DMC shrouds and busbar supports suitably spaced.

g. The panel shall have copper busbars as specified in Tech Spec with bar type
feeder connections, spacers etc.

h. Earthing all components, frames etc. to a common internal earth bar of size
50x4mm Cu of higher, as required by the fault withstand level

i. All accessories & supporting structures such as channels, ISMC 100 base
frame, mounting brackets, lifting lugs, panel heaters, ventilation

j. Each incomer and outgoing feeder shall be provided with LED type
status indication lamps suitable for 240V AC as approved

k. Space / spare provision as specified in Tech Spec for future expansion

l. The make of all switchgear (ACB / MCCB / MCB etc.) must be same to have
total discrimination
m. Components and accessories shall be same for switchboards and panels for
uniformity, standardization and replaceability and shall be applicable to all
n. panels
All interconnections, labelling, earthing associated foundation / masonry work,
/sealing
boardsofunder
gapsthe scope
around theofpanels
work by chequered plates and erection

o. MCCBs shall have adjustable protection against overload and


adjustable protection against short circuit as specified in Tech Spec

p. ACBs / MCCBs shall be compact, suitably designed to provide protection of


motors, cables, busbars to suit rated current, unbalanced power

q. Panel / Switchboard design shall be compact and components / accessories of


compact sizes shall be used to economize the room space

r. Incomer ACBs / MCCBs / MCBs of switchboards / panels shall be provided with


NO/NC contacts as specified in specification for interface with

s. ACBs shall have microprocessor based releases as specified in the Tech Spec

t. In case of higher frame sizes (then those specified in BOQ) are required to be
provided to achieve the requirement of total discrimination

u. Contractor must carry out cable sizing based on actual lengths of cables and
discrimination study for selection of trip units and settings for the

v. All motor feeders, having separate thermal overload relay, shall be provided
with Reset puch button
w. The size of Panel / DBs shall be such that all the components / meters shall be
neatly placed for easy approach and maintainability

x. Even though ratings of MPCB / Contactors for Motor Feeders are mentioned in
y. BOQ
If the items
numberbelow, after are
of cables selection
more, of a particular
then necessary make of
additional space arrangement
and other necessary provision like busbar extension and

z. Price quoted against the line item shall include but not limited to the following
item listed. It is deemed that price quoted includes other components

Digital Multi function Meter should be having 1) 4Line Display screen, 2) 2


digital Outputs, 3) 64bits/ sec sampling rate, 4) RS485 Communication port, 5)
Individual harmonics upto 31st harmonic, 6) 4 nos Time of day metering feature.

The following specification shall be covered & conform to Tender Tech Spec etc
as required

(a) The switchboards shall be totally type tested assemblies (TTA) and minimum of
Form 4b Type 5 with galvanized sheet steel of 2 mm. All main panel
shall be of draw out type design. All type
tests shall be as defined in IEC 61439-1 & 2 or EN 61439-1 & 2, built-up from
compartments housing circuit breakers, control gear, relays, busbars, controls
and other items of equipment. All LV
switchboards shall be confirming to IEC61439 - 1 & 2 and according to the
same all type test reports has to furnished. All LV switchboards
shall be tested for Internal Arc performance as per IEC 61641. All LV
switchboards shall be tested for Seismic compliance for Zone 4 as per AS

(b) All ACB shall be provided with the following:

(1) Communication capability


(2) Provision for measurement of V, A, W, VAR, VA, Wh, VARh, Hz, power
factor
(3) etc.
Protection against long time + short time + earth fault (all with adjustable
time delays) + instantaneous, over and under voltage, minimum and maximum
frequency, voltage and current imbalance, phase sequence, load shedding and
(4) Measurement of interrupted currents, differentiated fault indications,
reconnection. The Control Unit shall not be a peak sensing device and shall
maintenance
measure the trueindicators
RMS values to make the measurement free from the influence
of harmonics.
(5) Last few trippings and event histories and time stamping with facility for
consulting the history file, maintenance indicator register etc.
(6) Communication options to remotely read and set parameters for the
protection functions, transmission of all the calculated indicators and
measurements.
(7) Signaling of the cause of the tripping and alarm

(8) NO/NC contacts for interlocks and indications

(9) Electrically operated Drawout type ACB, complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases
(10) The Air circuit Breaker shall be of moulded case design and with single
frame size up to 4000A for uniformity in the switchboard and take care of
replacement of any lower rated ACB with the higher rated ACB in the event of
(11) The ACB shall have front face with Insulation Class II for safety as per IEC
breakdown.
60947-2 allowing class II installations with breaker control from outside.
(12) Trip time shall be below 30msec
(13) ACB shall conform to stringent environmental directives i.e.ROHS and
WEEE norms
(14) ACB shall be provided with Arc Chute Cover and stainless steel filters to
absorb all gases which are released in the event of Short circuit which ensures
better safety
(15) All ACBs shall be provided with Ready to Close Contacts as standard
feature to check in the event of Closing under the following conditions:
a.ACB is in OFF position b.Spring Mechanism is Charged c.Opening order is
(15) There shall be 3 distinct locking position on the ACB in
not present
Connected/test/Service
d. device not completely positions
racked in
(16) The closing time shall be less than or equal to 70 milliseconds for rating
<4000A.
(17) The circuit breaker shall be equipped with a safety interlock which keeps
the circuit breaker open if the trip unit is not installed.
(18) ACB shall be equipped with anti pumping function: If opening and closing
orders occur simultaneously, the circuit breaker shall remain in the open
position. After fault tripping or intentional opening using the manual or electrical
(19) Each position shall be acknowledged before moving to a new position.
controls, the closing order must first be discontinued, then reactivated to close
the circuit breaker.
(20) The drawout mechanism shall be part of the fixed frame to reduce the
weight of withdrawable part.
(21) In electronic trip units, protection functions shall be electronically managed
independently of measurement function.
(22) The test shall be carried out with a breaking performance during operation
(Ics) and admissible short time withstand (Icw) equal to the ultimate breaking
capacity (Icu).) i.e Ics = Icu = Icw
( 23) Screws that held removable parts shall be self-contained
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(24) Coils shall be designed for continuous-duty. lN lS lN lS N el S lN S on nel el S ply
N
(25) It shall be possible to adjust protections with a knob without any power
supply or when the main is off
(26)All ACBs shall have segregated LED fault indications and Mp fault
indication.
(27) All ACBs shall be set for different protection settings using Rotary
Dial potentiometer and navigation keys
( 28)All Microprocessor trip unit shall have thermal memory.

(29)Also trip unit shall provide last 10 trip histories which include date and time
stampings
(30) Zone Selective Interlocking shall be provided in the Breakers for logic
discrimination Which reduces the thermal/electrodynamic stresses in the event
of Short Circuit and earthfault.
(31) It shall be possible to upgrade the breakers with Communication feature at
Site With RS485-2 way communication and further upgradable to Ethernet
connectivity.Control of breaker shall be possible through IFE module.
(32) Manufacturers shall ensure Total Discrimination and co-ordination between
ACBs,MCCBs and MCBs with subnission of proper charts
All MCCB shall be provided with the following:
(1) MCCBs shall be designed according to Eco-design complying with ISO
14062 Especially MCCB’s materials shall be of halogen free type
(2) It shall be possible to supply power either from the upstream or downstream
side
(3) Protection against long time + short time + earth fault (all with adjustable
time delays) + instantaneous. The Control Unit shall not be a peak sensing
device and shall measure the true RMS values to make the measurement free
(4)
fromMCCBs shall comprise
the influence a device, designed to trip the circuit-breaker in the
of harmonics.
event of high-value short-circuit currents. This device shall be additional &
independent of the thermal-magnetic or electronic trip unit.
(5) The self-test will be of positive logic and visible through the flashing of a
green LED in case the self-test occurred correctly (on the complete tripping
chain, including current transformers, PCB and actuator) and the extinction of
(6) For rating frame higher than 250 A MCCBs shall be fitted with metallic filters
the LED in case the self-test failed
to reduce effects perceptible from the outside during current interruption
(7) The MCCB shall have Insulation Class II front face.
(8) Cross Bolt Termination facility shall be provided to avoid loose termination.

(9) Electronic trip unit shall be fitted with thermal memory

(10) Trip unit shall be easily interchangeable without removing the breaker from
the panel
(11) For a MCCB rating frame given , MCCBs dimensions shall be the same
whatever the ultimate breaking capacity
(12) MCCBs shall be designed to prevent access to live parts when the front
cover is removed
(13) It shall be possible to equip MCCBs with an auxiliary contact signalizing an
electrical fault operated by the trip unit
(14) It shall be possible to use the same field installable auxiliary contacts for
signalising different functions, as: open/ closed position, fault signal, electrical
fault (including electrical leakage) signal
(15) Auxiliary location and function shall be clearly identified inside the MCCBs

(16) When using the electronic trip unit it shall be possible to differentiate
remotely the type of fault (overload or short-circuit)
(17) The operating mechanism shall be of the stored-energy type only

(18) Four-pole devices shall be equipped with adjustable neutral protection:


as standard with a 3-position setting : - neutral not protected - neutral tripping
threshold equal to half the phase value - neutral threshold equal to the phase
(19) It shall be possible to adjust the long time protection with a knob without
value
any additional power supply or when the main is off
(20) Earth fault protection
It shall be possible to deactivate the earth fault protection. It shall be possible to
adjust the earth fault protection down to 16A.
(21) The addition of an add-on earth leakage module shall not be changed
MCCB accessories or options possibilities
(22) ZSI i.e.logic discrimination shall be possible for all Micrologic LSI and LSIG
breakers
(23) Manufacturers shall ensure Total Discrimination and co-ordination between
ACBs,MCCBs and MCBs with proper charts
(c) TNC (Trip / Neutral / Close) switch
(d) Auto / Local / Remote Selector switch key operated
(e) LED indication lamps for ON, OFF, TRIP, spring charged & phase indication (R-
Y-B)
(f) Contractor shall carryout interface with Incomer Protection CTs, to ensure that
these CTs are matching with the CT provided in the neutral section of the
Transformer by the Power Supply Contractor. In case any changes are required
in the Specifications given above due to interface, including the rating of the
CTs, same shall be done at no extra cost to the Employer

(g) SCADA Connectivity: All the breakers should be provided with communication
facilities and E&M contractor should provide single point to communicate with
BMS/SCADA for all system parameters of the panel. DC source and other
accessories including software and hardware required for this connectivity is in
the scope of this contract only

(h) Total Harmonic Distortion of Switchboard shall not exceed 5%. Devices with
local
& remote displays for measuring the percentage of Total Harmonic Distortion in
voltage and current shall be provided at each incomer ACB

(i) Panel Flooding System: Fire trace linear heat sensing polymer tube with inert
clean Agent panel flooding system shall be provided for fire supression for the
Electrical Panels. The system shall be of direct flooding type with HFC 227ea or
equal and approved extinguishant as per Tech Spec complete with gas
cylinders, valves, annunciation

(j) Suitable Capacity of Surge arrestor to be provided with main incomer from
prevention of surges. Supply, erection, testing and commissioning of the
following:

1.01 51, 53 Main Distribution Board (MDB) ASS1, as per Tender Tech Spec and Station Set 1 1 1 1
Drawings and as per following details

A Incomer from Transformer shall be equipped with


(i) 1 no. 6300A, 415V, 65kA, 4 Pole, Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Metering

Digital multifunction energy meter for measurement of voltage, line current,


power factor, power & energy
4 nos. CTs 6300/1A, 15VA, Class-1 for metering
1 no. CT 6300/1A, 15VA, Class-1 for APFCR relay

(iii) Protection
4 nos. CTs 6300/1A, CL-PS, in the MDB. Contractor carry out interface, to
ensure that these CT's are matching with the CT provided in the neutral section
of the Transformer by the Power Supply Contractor. In case any changes are
required in the Specifications given above due to interface, including the rating
of the CT's, same shall be done at no extra cost to the Employer.

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
ON, OFF, TRIP, spring charged & phase indication (R-Y-B). lN lS lN lS N el S lN S on nel el S ply
N

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B ASS1 to ASS2 (Tie Breaker for connecting DBs)

(i) 1 no. 4000A, 415V, 65kA, 4 Pole, Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Digital multifunction energy meter for measurement of voltage, line current,
power factor, power & energy

(iii) 3 nos. CTs, 4000/1A, 15VA, Class-1 for metering

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

C Interconnector Bus-section Circuit Breaker (Bus Coupler)

(i) 1 no. 4000A, 415V, 65kA, 4 Pole, Electrically operated Draw Out type, ACB
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Provision for measurement of three
phase and neutral current (2) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous (3) Zone Selective
Interlocking Unit for Total Discrimination (4) Last 15 nos. trippings and event
histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (5) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, signailing of the cause of tripping and alarms, maximeter reset
etc (6) NO / NC contacts for interlocks and indications. (8) Status Indication ON,
OFF, TRIP.

(ii) TNC switch

(iii) Auto / Local / Remote Selector Switch key operated.

(iv) LED indication lamp for ON, OFF & TRIP.

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

D DG Supply incoming Feeder

(i) 1 no. 2000A, 415V, 65kA, 4 Pole, Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocksand indications. (8) Status
Indication ON, OFF, TRIP

(ii) Digital ammeter with inbuilt selector switch

(iii) Digital voltmeter with inbuilt selector switch

(iv) 3 nos. CTs, 2000/1A, 15VA, Class-1 for metering

(v) TNC switch

(vi) Auto / Local / Remote Selector Switch key operated.

(vii) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

E Outgoing Feeders

(i) 2 nos. 1250A, 415V, 65kA, 3-pole ACB (one no. for MDB 108 & MDB
111) consisting of the following:
Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital Ammeter with inbuilt Selector Switch

3 nos. CTs, 1250/1A, 15VA, Class-1 for metering

TNC switch
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Auto / Local / Remote Selector Switch key operated. lN lS lN lS N el S lN S on nel el S ply
N

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(ii) 1 no. 800A, 415V, 65kA, 3-pole, ACB (one for MDB 104) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 800/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iii) 1no. 630A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for Capacitor Bank ) consisting of the following:
motorised MCCB with 240V AC shunt trip coil and having electronics releases
with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 630/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iv) 1no. 630A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 103) consisting of the following:
motorised MCCB with 240V AC shunt trip coil and having electronics releases
with
(1) Communication
Digital ammeter withprovision throughswitch
inbuilt selector RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
3 nos.
time CTs, 630/1A,
delays) 15VA, Class-1
+ Instantaneous for metering options to remotely read and
(4) Communication
set parameters for the protection functions transmission of ammeter
measurements,
TNC switch signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.
Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(v) 2 nos. 400A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 101 & one Spare) consisting of the
following:

motorised MCCB with 240V AC shunt trip coil and having electronics releases
with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs,400/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(vi) 3 nos. 250A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil lN lS lN lS N el S lN S on nel el S ply
and having electronics releases (two for MDB 106 & one for MDB 107) N
consisting of the following:

motorised MCCB with 240V AC shunt trip coil and having electronics releases
with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 250/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vii) 3 nos. 200A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB109 & two spare) consisting of the
following: motorised MCCB with 240V AC shunt trip coil and having electronics
releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 200/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(viii) 1 no. 125A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 105) consisting of the following:

motorised MCCB with 240V AC shunt trip coil and having electronics releases
with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 125/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP


Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(ix) 2 no. 100A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 110 & one spare) consisting of the
following:

motorised MCCB with 240V AC shunt trip coil and having electronics releases
with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 100/1A, 15VA, Class-1 for metering


TNC switch
Auto / Local / Remote Selector Switch key operated.
LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(x) 1 no. 63A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 112) consisting of the following:
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
motorised MCCB with 240V AC shunt trip coil and having electronics releases lN lS lN lS N el S lN S on nel el S ply
with N
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 63/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

F PLC for Interlocking Arrangement

PLC unit, suitable for interlocking 16 nos. circuit breakers, complete with all
hardware and software

G SCADA/BMS CONNECTIVITY

All the breakers should be provided with communication facilities & contractor
should provide single point to the marshalling box to communicate with
BMS/SCADA for all system parameters of the panel. DC source & other
accessories
Battery including
Charger software
Unit with and hardware
provisions of "Boostrequired forand
Charging" this"Float
is in the scope of
Charging",
contractor.
suitable for 240V, single phase, AC, 50Hz supply system & 24V DC including
2VX 12 100AH SMF VRLA Battery bank

H Busbars

VElectrolytic high conductivity T P & N (full size) copper conductor bus-bars


rated 7000Amps, suitable to withstand symetrical fault level of 65 KA for 1
second at 415 volts.

1.01 52 Main Distribution Board (MDB) ASS1, as per Tender Tech Spec and Station Set 1 1
Drawings and as per following details

A Incomer from Transformer shall be equipped with

(i) 1 no. 6300A, 415V, 65kA, 4 Pole, Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Metering

Digital multifunction energy meter for measurement of voltage, line current,


power factor, power & energy
4 nos. CTs 6300/1A, 15VA, Class-1 for metering

1 no. CT 6300/1A, 15VA, Class-1 for APFCR relay

(iii) Protection

4 nos. CTs 6300/1A, CL-PS, in the MDB. Contractor carry out interface, to
ensure that these CT's are matching with the CT provided in the neutral section
of the Transformer by the Power Supply Contractor. In case any changes are
required in the Specifications given above due to interface, including the rating
of the CT's, same shall be done at no extra cost to the Employer.

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B ASS1 to ASS2 (Tie Breaker for connecting DBs)

(i) 1 no. 4000A, 415V, 65kA, 4 Pole, Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Digital multifunction energy meter for measurement of voltage, line current,
power factor, power & energy
(iii) 3 nos. CTs, 4000/1A, 15VA, Class-1 for metering

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
ON, OFF, TRIP, spring charged & phase indication (R-Y-B). lN lS lN lS N el S lN S on nel el S ply
N

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

C Interconnector Bus-section Circuit Breaker (Bus Coupler)

(i) 1 no. 4000A, 415V, 65kA, 4 Pole, Electrically operated Draw Out type, ACB
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Provision for measurement of three
phase and neutral current (2) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous (3) Zone Selective
Interlocking Unit for Total Discrimination (4) Last 15 nos. trippings and event
histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (5) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, signailing of the cause of tripping and alarms, maximeter reset
etc (6) NO / NC contacts for interlocks and indications. (8) Status Indication ON,
OFF, TRIP.

(ii) TNC switch

(iii) Auto / Local / Remote Selector Switch key operated.

(iv) LED indication lamp for ON, OFF & TRIP.

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

D DG Supply incoming Feeder

(i) 1 no. 2500A, 415V, 65kA, 4 Pole, Electrically operated Draw Out type ACB,
(ii) complete with safety
Digital ammeter shutters,
with inbuilt 240V switch
selector AC shunt trip coil & closing coil and having

(iii) Digital voltmeter with inbuilt selector switch

(iv) 3 nos. CTs, 2500/1A, 15VA, Class-1 for metering

(v) TNC switch

(vi) Auto / Local / Remote Selector Switch key operated.

(vii) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall beport
Communication wired
fordirectly to the marshalling
serial RS-485 box withcommunication
standard protocol provision of BMS
E (MODBUS RTU) shall be wired upto the BMS interface terminal chamber.
Outgoing Feeders

(i) 2 nos. 1250A, 415V, 65kA, 3-pole ACB (one no. for MDB 108 & MDB
111) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt
Digital trip coilwith
Ammeter & closing
inbuilt coil and having
Selector Switchmicroprocessor based releases with

3 nos. CTs, 1250/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(ii) 1 no. 800A, 415V, 65kA, 3-pole, ACB (one for MDB 104) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 800/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal.
Communication Allfor
port terminal for BMSstandard
serial RS-485 interfaceprotocol
shall be communication
marked with signal and
equipment
(MODBUS tag RTU)forshall
BMSbe interface.
wired upto the BMS interface terminal chamber.

(iii) 2no. 630A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (1 nos. for MDB114 & Capacitor Bank )
consisting of the following:

motorised MCCB with 240V AC shunt trip coil and having electronics releases
with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 630/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
LED indication lamp for ON, OFF, TRIP lN lS lN lS N el S lN S on nel el S ply
N

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iv) 3 nos. 400A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 101, MDB 103 & one Spare)
consisting of the following:

motorised MCCB with 240V AC shunt trip coil and having electronics releases
with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs,400/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(v) 4 nos. 250A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (two for MDB 106, one for MDB 107 & one for
MDB
112) consisting of the following: motorised MCCB with 240V AC shunt trip coil
and having electronics releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 250/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vi) 4 nos. 200A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB109 & two spare) consisting of the
following: motorised MCCB with 240V AC shunt trip coil and having electronics
releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
Digital ammeter
measurement ofwith
threeinbuilt
phase selector
currentswitch
(3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time
3 nos.delays) + Instantaneous
CTs, 200/1A, (4) Communication
15VA, Class-1 for metering options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
TNC switch
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.
Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vii) 2 no. 125A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 105 & MDB 110) consisting of the
following:
motorised MCCB with 240V AC shunt trip coil and having electronics releases
with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 125/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(viii) 1 no. 100A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (spare) consisting of the following:
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
motorised MCCB with 240V AC shunt trip coil and having electronics releases lN lS lN lS N el S lN S on nel el S ply
with N
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 100/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(ix) 1 no. 63A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (spare) consisting of the following:

motorised MCCB with 240V AC shunt trip coil and having electronics releases
with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against Overload (with base
setting and fine adjustment), Short Circuit and earth fault (all with adjustable
time delays) + Instantaneous (4) Communication options to remotely read and
set parameters for the protection functions transmission of ammeter
measurements, signaling of cause of tripping, maximeter reset etc. (5) NO / NC
contacts for interlocks and indications (6) Neutral sensor for earth fault
protection.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 63/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
Communication
equipment tag forport
BMS for interface.
serial RS-485 standard protocol communication
(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

F PLC for Interlocking Arrangement

PLC unit, suitable for interlocking 16 nos. circuit breakers, complete with all
hardware and software

G SCADA/BMS CONNECTIVITY

All the breakers should be provided with communication facilities & contractor
should provide single point to the marshalling box to communicate with
BMS/SCADA for all system parameters of the panel. DC source & other
accessories including software and hardware required for this is in the scope of
contractor.

Battery Charger Unit with provisions of "Boost Charging" and "Float Charging",
suitable for 240V, single phase, AC, 50Hz supply system & 24V DC including
2VX 12 100AH SMF VRLA Battery bank

H Busbars

VElectrolytic high conductivity T P & N (full size) copper conductor bus-bars


rated 7600Amps, suitable to withstand symetrical fault level of 65 KA for 1
second at 415 volts.

1.01 54 Main Distribution Board (MDB) ASS1, as per Tender Tech Spec and Station Set 1 1
A Drawingsfrom
Incomer andTransformer
as per following
shalldetails
be equipped with

(i) 1 no. 6300A, 415V, 65kA, 4-pole, Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Metering

Digital multifunction energy meter for measurement of voltage, line current,


power factor, power & energy

4 nos. CTs 6300/1A, 15VA, Class-1 for metering

1 no. CT 6300/1A, 15VA, Class-1 for APFCR relay

(iii) Protection

4 nos. CTs 6300/1A, Class-PS in the MDB. Contractor carry out interface, to
ensure that these CT's are matching with the CT provided in the neutral section
of the Transformer by the Power Supply Contractor. In case any changes are
required in the Specifications given above due to interface, including the rating
of the CT's, same shall be done at no extra cost to the Employer.

(iv) TNC switch


(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-


ON, OFF, TRIP, spring charged & phase indication (R-Y-B).
Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B ASS1 to ASS2 (Tie Breaker for connecting DBs)


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(i) 1 no. 4000A, 415V, 65kA, 4-pole Electrically operated Draw Out type ACB, lN lS lN lS N el S lN S on nel el S ply
complete with safety shutters, 240V AC shunt trip coil & closing coil and having N
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Digital ammeter with inbuilt selector switch

(iii) 3 nos. CTs, 4000/1A, 15VA, Class-1 for metering

(iii) TNC switch

(iv) Auto / Local / Remote Selector Switch key operated.

(v) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.
Communication port for serial RS-485 standard protocol communication
(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

C Interconnector Bus-section Circuit Breaker (Bus Coupler)

(i) 1 no. 4000A, 415V, 65kA, 4-pole Electrically operated Draw Out type, ACB
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Provision for measurement of three
phase and neutral current (2) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous (3) Zone Selective
Interlocking Unit for Total Discrimination (4) Last 15 nos. trippings and event
histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (5) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, signailing of the cause of tripping and alarms, maximeter reset
etc (6) NO / NC contacts for interlocks and indications. (8) Status Indication ON,
OFF, TRIP.

(ii) TNC switch

(iii) Auto / Local / Remote Selector Switch key operated.

(iv) LED indication lamp for ON, OFF & TRIP.

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

D DG Supply incoming Feeder

(i) 1 no. 2000A, 415V, 65kA, 4-pole Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocksand indications. (8) Status
Indication ON, OFF, TRIP

(ii) Digital multifunction energy meter for measurement of voltage, line current,
power factor, power & energy

(iii) 3 nos. CTs, 2000/1A, 15VA, Class-1 for metering

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

E Outgoing Feeders

(i) 2 nos. 1250A, 415V, 65kA, 3-pole ACB (one no. for MDB 108 & MDB
111) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital Ammeter with inbuilt Selector Switch

3 nos. CTs, 1250/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal.
Communication Allfor
port terminal for BMSstandard
serial RS-485 interfaceprotocol
shall be communication
marked with signal and
equipment tag
(MODBUS RTU)forshall
BMSbe interface.
wired upto the BMS interface terminal chamber.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(ii) 1 no. 800A, 415V, 65kA, 3-pole, ACB (one for MDB 104) consisting of the lN lS lN lS N el S lN S on nel el S ply
following: N

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 800/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iii) 1no. 630A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for Capacitor Bank ) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 630/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iv) 2 nos. 400A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 101 & one Spare) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs,400/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(v) 3 nos. 250A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (two for MDB 106 & one for MDB 107)
consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements,
Digital ammeter Signailing
with inbuilt of the cause
selector of tripping and alarms, maximeter reset
switch
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect
3 nos. CTs, with
250/1A, the trip
15VA, unit. for metering
Class-1

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vi) 4 nos. 200A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 103, MDB109 & two spare) consisting
of the following:
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Electrically operated Draw Out type, ACB complete with safety shutters, 240V lN lS lN lS N el S lN S on nel el S ply
AC shunt trip coil & closing coil and having microprocessor based releases with N
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 200/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vii) 1 no. 125A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 105) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 125/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(viii) 3 nos. 100A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 110 & MDB 112 & one spare)
consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 100/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

F PLC for Interlocking Arrangement

PLC unit, suitable for interlocking 16 nos. circuit breakers, complete with all
hardware and software

G SCADA/BMS CONNECTIVITY

All the breakers should be provided with communication facilities & contractor
should provide single point to the marshalling box to communicate with
BMS/SCADA for all system parameters of the panel. DC source & other
accessories including software and hardware required for this is in the scope of
contractor.

Battery Charger Unit with provisions of "Boost Charging" and "Float Charging",
suitable for 240V, single phase, AC, 50Hz supply system & 24V DC including
2VX 12 100AH SMF VRLA Battery bank

H Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
7000Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

1.01 55 Main Distribution Board (MDB) ASS2, as per Tech Spec and Station Drawings Set 1 1
drawings and as per following details

A Incomer from Transformer shall be equipped with


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(i) 2 nos. 1250A, 415V, 65kA, 4-pole, Electrically operated Draw Out type ACB, lN lS lN lS N el S lN S on nel el S ply
complete with safety shutters, 240V AC shunt trip coil & closing coil and having N
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Metering

Digital multifunction energy meter for measurement of voltage, line current,


power factor, power & energy

4 nos. CTs 1250/1A, 15VA, Class-1 for metering

1 no. CT 1250/1A, 15VA, Class-1 for APFCR relay

(iii) Protection

4 nos. CTs 1250/1A, Class-PS in the MDB. Contractor carry out interface, to
ensure that these CT's are matching with the CT provided in the neutral section
of the Transformer by the Power Supply Contractor. In case any changes are
required in the Specifications given above due to interface, including the rating
of the CT's, same shall be done at no extra cost to the Employer.

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Interconnector Bus-section Circuit Breaker (Bus Coupler)

(i) 1 no. 1250A, 415V, 65kA, 4-pole Electrically operated Draw Out type, ACB
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Provision for measurement of three
phase and neutral current (2) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous (3) Zone Selective
Interlocking Unit for Total Discrimination (4) Last 15 nos. trippings and event
histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (5) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, signailing of the cause of tripping and alarms, maximeter reset
etc (6) NO / NC contacts for interlocks and indications. (8) Status Indication ON,
OFF, TRIP.

(ii) TNC switch

(iii) Auto / Local / Remote Selector Switch key operated.

(iv) LED indication lamp for ON, OFF & TRIP.

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

C DG Supply incoming Feeder

(i) 1 no. 1250A, 415V, 65kA, 4-pole Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocksand indications. (8) Status
Indication ON, OFF, TRIP

(ii) Digital multifunction energy meter for measurement of voltage, line current,
power factor, power & energy
(iii) 3 nos. CTs, 2000/1A, 15VA, Class-1 for metering

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

D Outgoing Feeders

(i) 1 no. 1250A, 415V, 65kA, 3-pole, ACB (for MDB 207) consisting of the following
:
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Electrically operated Draw Out type, ACB complete with safety shutters, 240V lN lS lN lS N el S lN S on nel el S ply
AC shunt trip coil & closing coil and having microprocessor based releases with N
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital Ammeter with inbuilt Selector Switch

3 Nos. CTs, 1250/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.


LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(ii) 2 nos. 400A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for Capacitor Bank & one Spare) consisting of
the following:
Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs,400/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iii) 4nos. 200A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 104, MDB 106 & 2 spare) consisting
of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch


3 nos. CTs, 200/1A, 15VA, Class-1 for metering
TNC switch
Auto / Local / Remote Selector Switch key operated.
LED indication lamp for ON, OFF, TRIP, spring charged
Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iv) 2 nso. 100A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 105 & spare) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 100/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(v) 1 no. 63A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 208) consisting of the following:
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Electrically operated Draw Out type, ACB complete with safety shutters, 240V lN lS lN lS N el S lN S on nel el S ply
AC shunt trip coil & closing coil and having microprocessor based releases with N
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 63/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vi) 1 no. 32A, 415V, 10kA, TPN MCB (for MDB 103) consisting of the following:

Digital ammeter with inbuilt selector switch

3 nos. CTs, 63/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

E PLC for Interlocking Arrangement

PLC unit, suitable for interlocking 16 nos. circuit breakers, complete with all
hardware and software

F SCADA/BMS CONNECTIVITY

All the breakers should be provided with communication facilities & contractor
should provide single point to the marshalling box to communicate with
BMS/SCADA for all system parameters of the panel. DC source & other
accessories including software and hardware required for this is in the scope of
contractor.

Battery Charger Unit with provisions of "Boost Charging" and "Float Charging",
suitable for 240V, single phase, AC, 50Hz supply system & 24V DC including
2VX 12 100AH SMF VRLA Battery bank
G Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
1700Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

1.02 51, 53 Main Distribution Board (MDB) ASS2, as per Tech Spec and Station Drawings Set 1 1 1 1
drawings and as per following details

A Incomer from Transformer shall be equipped with

(i) 1 no. 6300A, 415V, 65kA, 4-pole, Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Metering

Digital multifunction energy meter for measurement of voltage, line current,


power factor, power & energy

4 nos. CTs 6300/1A, 15VA, Class-1 for metering

1 no. CT 6300/1A, 15VA, Class-1 for APFCR relay

(iii) Protection

4 nos. CTs 6300/1A, Class-PS in the MDB. Contractor carry out interface, to
ensure that these CT's are matching with the CT provided in the neutral section
of the Transformer by the Power Supply Contractor. In case any changes are
(iv) TNC switch
required in the Specifications given above due to interface, including the rating
of the CT's, same shall be done at no extra cost to the Employer.

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B ASS2 to ASS1 (Tie Breaker for connecting DBs)

(i) 1 no. 4000A, 415V, 65kA, 4-pole Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(ii) Digital multifunction energy meter for measurement of voltage, line current, lN lS lN lS N el S lN S on nel el S ply
power factor, power & energy N

(iii) 3 nos. CTs, 4000/1A, 15VA, Class-1 for metering

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
Communication
equipment tag forport
BMS for interface.
serial RS-485 standard protocol communication
(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

C Interconnector Bus-section Circuit Breaker (Bus Coupler)


(i) 1 no. 4000A, 415V, 65kA, 4-pole Electrically operated Draw Out type, ACB
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Provision for measurement of three
phase and neutral current (2) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous (3) Zone Selective
Interlocking Unit for Total Discrimination (4) Last 15 nos. trippings and event
histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (5) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, signailing of the cause of tripping and alarms, maximeter reset
etc (6) NO / NC contacts for interlocks and indications. (8) Status Indication ON,
OFF, TRIP.

(ii) TNC switch

(iii) Auto / Local / Remote Selector Switch key operated.

(iv) LED indication lamp for ON, OFF & TRIP.

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

D DG Supply incoming Feeder

(i) 1 no. 2000A, 415V, 65kA, 4-pole Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocksand indications. (8) Status
Indication ON, OFF, TRIP

(ii) Digital multifunction energy meter for measurement of voltage, line current,
power factor, power & energy
(iii) 3 nos. CTs, 2000/1A, 15VA, Class-1 for metering

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

E Outgoing Feeders

(i) 1 no. 2000A, 415V, 65kA, 3-pole, ACB (for MDB 207) consisting of the following
:
Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital Ammeter with inbuilt Selector Switch

3 Nos. CTs, 2000/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.
Communication port for serial RS-485 standard protocol communication
(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(ii) 1 no. 1250A, 415V, 65kA, 3-pole ACB (one no. for MDB 201) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Digital Ammeter with inbuilt Selector Switch lN lS lN lS N el S lN S on nel el S ply
N
3 nos. CTs, 1250/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iii) 1 no. 800A, 415V, 65kA, 3-pole, ACB (one for MDB 203) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 800/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iv) 2nos. 630A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for Capacitor Bank & MDB 205) consisting of
the following:
Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 630/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal.
Communication Allfor
port terminal for BMSstandard
serial RS-485 interfaceprotocol
shall be communication
marked with signal and
equipment tag
(MODBUS RTU)forshall
BMSbe interface.
wired upto the BMS interface terminal chamber.

(v) 2 nos. 400A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 206 & one Spare) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs,400/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vi) 1 no. 250A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 204) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch


3 nos. CTs, 250/1A, 15VA, Class-1 for metering
TNC switch

Auto / Local / Remote Selector Switch key operated.


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
LED indication lamp for ON, OFF, TRIP, spring charged lN lS lN lS N el S lN S on nel el S ply
N

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vii) 2nos. 200A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for spare) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 200/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(viii) 1 no. 100A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for spare) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 100/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vii) 1 no. 63A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 208) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 63/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

F PLC for Interlocking Arrangement

PLC unit, suitable for interlocking 16 nos. circuit breakers, complete with all
hardware and software
G SCADA/BMS CONNECTIVITY

All the breakers should be provided with communication facilities & contractor
should provide single point to the marshalling box to communicate with
BMS/SCADA for all system parameters of the panel. DC source & other
accessories including software and hardware required for this is in the scope of
contractor.

Battery Charger Unit with provisions of "Boost Charging" and "Float Charging",
suitable for 240V, single phase, AC, 50Hz supply system & 24V DC including
2VX 12 100AH SMF VRLA Battery bank

H Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
7000Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

1.02 52 Main Distribution Board (MDB) ASS2, as per Tech Spec and Station Drawings Set 1 1
drawings and as per following details

A Incomer from Transformer shall be equipped with


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(i) 1 no. 6300A, 415V, 65kA, 4-pole, Electrically operated Draw Out type ACB, lN lS lN lS N el S lN S on nel el S ply
complete with safety shutters, 240V AC shunt trip coil & closing coil and having N
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Metering

Digital multifunction energy meter for measurement of voltage, line current,


power factor, power & energy
4 nos. CTs 6300/1A, 15VA, Class-1 for metering

1 no. CT 6300/1A, 15VA, Class-1 for APFCR relay

(iii) Protection

4 nos. CTs 6300/1A, Class-PS in the MDB. Contractor carry out interface, to
ensure that these CT's are matching with the CT provided in the neutral section
of the Transformer by the Power Supply Contractor. In case any changes are
required in the Specifications given above due to interface, including the rating
of the CT's, same shall be done at no extra cost to the Employer.

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B ASS2 to ASS1 (Tie Breaker for connecting DBs)

(i) 1 no. 4000A, 415V, 65kA, 4-pole Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Digital multifunction energy meter for measurement of voltage, line current,
power factor, power & energy
(iii) 3 nos. CTs, 4000/1A, 15VA, Class-1 for metering

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

C Interconnector Bus-section Circuit Breaker (Bus Coupler)

(i) 1 no. 4000A, 415V, 65kA, 4-pole Electrically operated Draw Out type, ACB
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Provision for measurement of three
phase and neutral current (2) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous (3) Zone Selective
Interlocking Unit for Total Discrimination (4) Last 15 nos. trippings and event
histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (5) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, signailing of the cause of tripping and alarms, maximeter reset
etc (6) NO / NC contacts for interlocks and indications. (8) Status Indication ON,
OFF, TRIP.

(ii) TNC switch

(iii) Auto / Local / Remote Selector Switch key operated.

(iv) LED indication lamp for ON, OFF & TRIP.

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

D DG Supply incoming Feeder

(i) 1 no. 2000A, 415V, 65kA, 4-pole Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocksand indications. (8) Status
Indication ON, OFF, TRIP

(ii) Digital multifunction energy meter for measurement of voltage, line current,
power factor, power & energy
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(iii) 3 nos. CTs, 2000/1A, 15VA, Class-1 for metering lN lS lN lS N el S lN S on nel el S ply
N

(iv) TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

E Outgoing Feeders

(i) 1 no. 2500A, 415V, 65kA, 3-pole, ACB (for MDB 207) consisting of the following
:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital Ammeter with inbuilt Selector Switch

3 Nos. CTs, 2500/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(ii) 1 no. 1250A, 415V, 65kA, 3-pole ACB (one no. for MDB 201) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital Ammeter with inbuilt Selector Switch

3 nos. CTs, 1250/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iii) 1 no. 800A, 415V, 65kA, 3-pole, ACB (one for MDB 203) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 800/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iv) 3nos. 630A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 105, MDB 106 & Capacitor Bank)
consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Digital ammeter with inbuilt selector switch lN lS lN lS N el S lN S on nel el S ply
N
3 nos. CTs, 630/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(v) 2 nos. 400A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 208 & one Spare) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs,400/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vi) 1 no. 250A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 204) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 250/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vii) 3nos. 200A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 209 & 2spare) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 200/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(viii) 1 no. 100A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for spare) consisting of the following:
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Electrically operated Draw Out type, ACB complete with safety shutters, 240V lN lS lN lS N el S lN S on nel el S ply
AC shunt trip coil & closing coil and having microprocessor based releases with N
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 100/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal.
Communication Allfor
port terminal for BMSstandard
serial RS-485 interfaceprotocol
shall be communication
marked with signal and
equipment
(MODBUS tag RTU)forshall
BMSbe interface.
wired upto the BMS interface terminal chamber.

F PLC for Interlocking Arrangement

PLC unit, suitable for interlocking 16 nos. circuit breakers, complete with all
hardware and software

G SCADA/BMS CONNECTIVITY

All the breakers should be provided with communication facilities & contractor
should provide single point to the marshalling box to communicate with
BMS/SCADA for all system parameters of the panel. DC source & other
accessories including software and hardware required for this is in the scope of
contractor.

Battery Charger Unit with provisions of "Boost Charging" and "Float Charging",
suitable for 240V, single phase, AC, 50Hz supply system & 24V DC including
2VX 12 100AH SMF VRLA Battery bank

H Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
7600Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

1.02 54 Main Distribution Board (MDB) ASS2, as per Tech Spec and Station Drawings Set 1 1
drawings and as per following details

A Incomer from Transformer shall be equipped with

(i) 1 no. 6300A, 415V, 65kA, 4-pole, Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Metering

Digital multifunction energy meter for measurement of voltage, line current,


power factor, power & energy

4 nos. CTs 6300/1A, 15VA, Class-1 for metering

1 no. CT 6300/1A, 15VA, Class-1 for APFCR relay

(iii) Protection

4 nos. CTs 6300/1A, Class-PS , in the MDB. Contractor carry out interface, to
ensure that these CT's are matching with the CT provided in the neutral section
of the Transformer by the Power Supply Contractor. In case any changes are
required in the Specifications given above due to interface, including the rating
of the CT's, same shall be done at no extra cost to the Employer.
TNC switch

(v) Auto / Local / Remote Selector Switch key operated.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B ASS2 to ASS1 (Tie Breaker for connecting DBs)

(i) 1 no. 4000A, 415V, 65kA, 4-pole Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocks and indications. (8) Status
Indication ON, OFF, TRIP.

(ii) Digital multifunction energy meter for measurement of voltage, line current,
power factor, power & energy

(iii) 3 nos. CTs, 4000/1A, 15VA, Class-1 for metering

(iii) TNC switch

(iv) Auto / Local / Remote Selector Switch key operated.

(v) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.
Communication port for serial RS-485 standard protocol communication
(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

C Interconnector Bus-section Circuit Breaker (Bus Coupler)


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(i) 1 no. 4000A, 415V, 65kA, 4-pole Electrically operated Draw Out type, ACB lN lS lN lS N el S lN S on nel el S ply
complete with safety shutters, 240V AC shunt trip coil & closing coil and having N
microprocessor based releases with (1) Provision for measurement of three
phase and neutral current (2) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous (3) Zone Selective
Interlocking Unit for Total Discrimination (4) Last 15 nos. trippings and event
histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (5) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, signailing of the cause of tripping and alarms, maximeter reset
etc (6) NO / NC contacts for interlocks and indications. (8) Status Indication ON,
OFF, TRIP.

(ii) TNC switch

(iii) Auto / Local / Remote Selector Switch key operated.

(iv) LED indication lamp for ON, OFF & TRIP.

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

D DG Supply incoming Feeder

(i) 1 no. 2000A, 415V, 65kA, 4-pole Electrically operated Draw Out type ACB,
complete with safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS / SCADA (2) Provision for measurement of V, A, W, VAR, VA, Wh,
VARh, Hz, power factor etc (3) Protection against long time + short time + earth
fault (all with adjustable time delays) + instantaneous, over and under voltage,
minimum and maximum frequency, voltage and current imbalance, phase
sequence, load shedding and reconnection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15 nos.
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements, signalling of the cause of
tripping and alarms (7) NO/NC contacts for interlocksand indications. (8) Status
Indication ON, OFF, TRIP

(ii) Digital multifunction energy meter for measurement of voltage, line current,
power factor, power & energy

(iv) 3 nos. CTs, 2000/1A, 15VA, Class-1 for metering

(iii) TNC switch

(iv) Auto / Local / Remote Selector Switch key operated.

(v) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

E Outgoing Feeders

(i) 1 no. 2000A, 415V, 65kA, 3-pole, ACB (for MDB 207) consisting of the following
:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital Ammeter with inbuilt Selector Switch

3 Nos. CTs, 2000/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(ii) 1 no. 1250A, 415V, 65kA, 3-pole ACB (one no. for MDB 201) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital Ammeter with inbuilt Selector Switch

3 nos. CTs, 1250/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Communication port for serial RS-485 standard protocol communication lN lS lN lS N el S lN S on nel el S ply
(MODBUS RTU) shall be wired upto the BMS interface terminal chamber. N

(iii) 1 no. 800A, 415V, 65kA, 3-pole, ACB (one for MDB 203) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 800/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(iv) 1no. 630A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for Capacitor Bank) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 630/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(v) 3 nos. 400A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 205, MDB 206 & one Spare)
consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs,400/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vi) 1 no. 250A, 415V, 50kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 204) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 250/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Voltage Free Contactor (VFC) of different signal and remote control interface lN lS lN lS N el S lN S on nel el S ply
terminal shall be wired directly to the marshalling box with provision of BMS N
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(vii) 2nos. 200A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for spare) consisting of the following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 200/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

(viii) 2 nos. 100A, 415V, 35kA, 3-pole motorized MCCB with 240V AC shunt trip coil
and having electronics releases (for MDB 208 & spare) consisting of the
following:

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

Digital ammeter with inbuilt selector switch

3 nos. CTs, 100/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF, TRIP, spring charged

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

F PLC for Interlocking Arrangement

PLC unit, suitable for interlocking 16 nos. circuit breakers, complete with all
hardware and software

G SCADA/BMS CONNECTIVITY

All the breakers should be provided with communication facilities & contractor
should provide single point to the marshalling box to communicate with
BMS/SCADA for all system parameters of the panel. DC source & other
accessories including software and hardware required for this is in the scope of
contractor.

Battery Charger Unit with provisions of "Boost Charging" and "Float Charging",
suitable for 240V, single phase, AC, 50Hz supply system & 24V DC including
2VX 12 100AH SMF VRLA Battery bank

H Busbars

7000A suitable to withstand symmetrical fault level of 65kA for 1 second at 415V

II The following specification shall be covered for (Sub Distribution Panels) &
conform to Tender Tech Spec

(a) All incoming & outgoing breakers shall be provided with the following:

(1) Communication capability

(2) Provision for measurement of three phase current

(3) Protection against long time + short time + earth fault (all with adjustable
time delays) - instantaneous

(4) Zone selective interlocking Unit for Total Distribution

(5) Communication options to remotely read and set parameters for the
protection functions, transmission of ammeter measurements

(6) Signaling of the cause of tripping and alarms, maximeter reset etc.

(7) NO/NC contacts for interlocks and indications

(8) 1 no. CT in the neutral to connect with the trip unit

(b) LED indication lamps for ON, OFF, TRIP and Phase Indication (R, Y, B)

(c) 1 no. digital voltmeter for remote operation

(d) 1 no. digital ammeter with inbuilt selector switch

(e) All outgoing breakers MCCBs shall be provided with the following:

(1) Electronic adjustable trip unit for overload and short circuit protection

(2) NO/NC contacts for remote operation


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(3) Neutral sensor for earth fault protection lN lS lN lS N el S lN S on nel el S ply
N

(f) Panel Flooding System: Fire trace linear heat sensing polymer tube with inert
clean Agent panel flooding system shall be provided for fire supression for the
Electronic Panels. The system shall be of direct flooding type with HFC 227ea
(g) ATS shall be provided with the following:
or equal and approved extinguishant as per Tech Spec complete with gas
cylinders, valves, annunciation
(1) 2 nos. motorized MCCBs, electrically and mechanically interlocked with base
frame and controller having selector switch for automatic & forced operation on
normal and emergency sources.

(2) The controller should have communication capability with BMS/SCADA

(3) The MCCBs must have Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit, shunt trip coil,
auxiliary contacts for ON, OFF, TRIP indication etc.

(4) LED indication lamps for ON, OFF, TRIP and Phase Indication (R, Y, B)

1.03 51, 54 Sub-Main Distribution Board MDB 108 as per Technical Specifications & typical Set 1 1 1 1
station drawings and as per following details

A Incoming

(i) Auto Transfer Switch with 2 nos. 1250A, 415V, 65kA, 3-pole, Motorised
ACB consisting of the following :

Electrically operated Draw Out type ACB, complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS / SCADA (2) Provision
(ii) for measurement
Digital of energy
multifunction V, A, W,meter
VAR,for
VA, Wh, VARh, Hz,
measurement power factor
of voltage, etc (3)
line current,
Protection
power against
factor, powerlong time + short time + earth fault (all with adjustable time
& energy
delays) + instantaneous, over and under voltage, minimum and maximum
frequency, voltage and current imbalance, phase sequence, load shedding and
3 Nos. CTs,
reconnection 1250/1A, 15VA, Class-1 for metering
(4) Measurement of inturrepted currents, differenciated fault indications,
maintenance indicators (5) Last 15 nos. trippings and event histories and time
TNC switch
stamping with facility for consulting the history file, maintenance indicator
register etc (6) Communication options to remotely read and set parameters for
the protection functions, transmission of all the calculated indicators and
measurements, signalling
Auto / Local / Remote of theSwitch
Selector causekey
of tripping and alarms (7) NO/NC
operated.
contacts for interlocks and indications. (8) Status Indication ON, OFF, TRIP.

LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
1600Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

C Outgoing

(i) 1 No. 250 A, 50 kA 3-Pole MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit

(ii) 2 Nos., 200A, 35 KA 3-Pole MCCB (Fire Pumps) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit

2 sets of Star Delta starter unit for Fire Hydrant Pumps (90kW each) (1 working
+ 1 standby). Each starter unit shall be equipped with the following:

(a) 1 no. 3-pole, 415V, 200A, 50kA, 3P Motor Duty MCCB with Magnetic Trip Unit
only (having short circuit protection only) and auxiliary contacts

(b) 1 No. Digital Ammeter, CT operated with communication provision for BMS
interface over MODBUS-RTU Serial ( RS485, 2 wire) wire up to the BMS
interface chamber/compartment.

(c) 1 no. CT, 200/1A, 10VA, Class-1 for metering

(d) Auto / Local / Remote Selector Switch key operated

(e) Door mounted push buttons for Start and Stop functions

(f) Emergency Stop push button lockable type

(g) LED indication lamp for ON, OFF, TRIP

(h) 3 nos. 200A, AC-3 Duty, 3-pole Contactor with Auxiliary Contacts and Operating
Coil of 240V AC
(i) One no. Star Delta Timer

(j) Auxiliary contactors for Auto / Local / Remote Operation

(k) Triple Pole, saturable CT operated, bimetal overload relays (with in built single
phasing protection) suitable for above mentioned motor feeder having
arrangement for bypassing the overload relay in case the pump is running
during an emergency scenario with all accessories including 3 nos. saturable
CTs, auxiliary contactors etc.

(l) Power and Control terminals for cable connections

(m) Equipment common for both feeders is indicated below:

(i) 1 no. working / standby selector switch

(ii) Auxiliary contactors with 240V AC operating coil (for working / standby
selection)

(iii) 3 Nos, 200 A, 35 kA, 3-Pole MCCB (two spare) Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit

(iv) 2 Nos., 100A, 35 KA 3-Pole MCCB (One for battery Chjarger & one spare)
having Electronic Trip Unit with adjustable protection against Overload and
adjustable protection against Short Circuit

(v) 1 No, 100 A, 35 kA, 3-Pole MCCB (Jockey Pump)

1 set of Star-Delta Starter Unit (one set for Hydrant Jockey Pump of 20kW).
Each Starter Unit shall be equipped with the following:

(a) 1 no. 3 pole, 415V, 100A, 35kA Motor Duty MCCB with Magnetic Trip Unit only
(having short circuit protection only) and auxiliary contacts.

(b) 1 no. digital ammeter, CT operated

(c) 1 no. CT, 30/1A, 10VA, Class-1 for metering

(d) Auto / Local / Remote Selector Switch key operated

(e) Door mounted push buttons for Start and Stop functions
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(f) Emergency Stop push button lockable type lN lS lN lS N el S lN S on nel el S ply
N

(g) LED indication lamp for ON, OFF and TRIP

(h) 3 nos. 40A, AC3 Duty, 3-pole Contactor with Auxiliary Contacts and Operating
Coil of 240V AC

(i) One no. Star Delta Timer

(j) Auxiliary Contactors for Auto / Local / Remote operation

(k) Triple Pole, saturable CT operated, bimetal overload relays (with in built single
phasing protection) suitable for above mentioned motor feeder having
arrangement for bypassing the overload relay in case the pump is running
during an emergency scenario with all accessories including 3 nos. saturable
CTs, auxiliary contactors etc.

(l) Power and Control terminals for cable connections

(vi) 2 Nos, 63 A, 35 kA, 3-Pole MCCB Electronic Trip Unit with adjustable protection
against Overload and adjustable protection against Short Circuit
(vii) 1 No. 63A 10 kA TPN MCB

(viii) 1 No. 32A 10 kA TPN MCB

1.03 53 Sub-Main Distribution Board MDB 108 as per Technical Specifications & typical Set 1 1
station drawings and as per following details
A Incoming

(i) Auto Transfer Switch with 2 nos. 1250A, 415V, 65kA, 3-pole, Motorised
ACB consisting of the following :

Electrically operated Draw Out type ACB, complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS / SCADA (2) Provision
for measurement of V, A, W, VAR, VA, Wh, VARh, Hz, power factor etc (3)
Protection against long time + short time + earth fault (all with adjustable time
delays) + instantaneous, over and under voltage, minimum and maximum
frequency, voltage and current imbalance, phase sequence, load shedding and
reconnection
(4) Measurement of inturrepted currents, differenciated fault indications,
maintenance indicators (5) Last 15 nos. trippings and event histories and time
stamping with facility for consulting the history file, maintenance indicator
register etc (6) Communication options to remotely read and set parameters for
the protection functions, transmission of all the calculated indicators and
measurements, signalling of the cause of tripping and alarms (7) NO/NC
contacts for interlocks and indications. (8) Status Indication ON, OFF, TRIP.

(ii) Digital multifunction energy meter for measurement of voltage, line current,
power factor, power & energy

3 Nos. CTs, 1250/1A, 15VA, Class-1 for metering

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
1600Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

C Outgoing

(i) 1 No. 250 A, 50 kA 3-Pole MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit

(ii) 2 Nos., 200A, 35 KA 3-Pole MCCB (Fire Pumps) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit

2 sets of Star Delta starter unit for Fire Hydrant Pumps (90kW each) (1 working
+ 1 standby). Each starter unit shall be equipped with the following:

(a) 1 no. 3-pole, 415V, 200A, 50kA, 3P Motor Duty MCCB with Magnetic Trip Unit
only (having short circuit protection only) and auxiliary contacts

(b) 1 No. Digital Ammeter, CT operated with communication provision for BMS
interface over MODBUS-RTU Serial ( RS485, 2 wire) wire up to the BMS
interface chamber/compartment.

(c) 1 no. CT, 200/1A, 10VA, Class-1 for metering

(d) Auto / Local / Remote Selector Switch key operated

(e) Door mounted push buttons for Start and Stop functions

(f) Emergency Stop push button lockable type

(g) LED indication lamp for ON, OFF, TRIP

(h) 3 nos. 200A, AC-3 Duty, 3-pole Contactor with Auxiliary Contacts and Operating
Coil of 240V AC

(i) One no. Star Delta Timer

(j) Auxiliary contactors for Auto / Local / Remote Operation

(k) Triple Pole, saturable CT operated, bimetal overload relays (with in built single
phasing protection) suitable for above mentioned motor feeder having
arrangement for bypassing the overload relay in case the pump is running
during an emergency scenario with all accessories including 3 nos. saturable
CTs, auxiliary contactors etc.

(l) Power and Control terminals for cable connections

(m) Equipment common for both feeders is indicated below:

(i) 1 no. working / standby selector switch

(ii) Auxiliary contactors with 240V AC operating coil (for working / standby
selection)
(iii) 3 Nos, 200 A, 35 kA, 3-Pole MCCB (two spare) Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit

(iv) 2 Nos., 100A, 35 KA 3-Pole MCCB (One for battery Chjarger & one spare)
having Electronic Trip Unit with adjustable protection against Overload and
adjustable protection against Short Circuit

(v) 1 No, 100 A, 35 kA, 3-Pole MCCB (Jockey Pump)

1 set of Star-Delta Starter Unit (one set for Hydrant Jockey Pump of 20kW).
Each Starter Unit shall be equipped with the following:
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(a) 1 no. 3 pole, 415V, 100A, 35kA Motor Duty MCCB with Magnetic Trip Unit only lN lS lN lS N el S lN S on nel el S ply
(having short circuit protection only) and auxiliary contacts. N

(b) 1 no. digital ammeter, CT operated

(c) 1 no. CT, 30/1A, 10VA, Class-1 for metering

(d) Auto / Local / Remote Selector Switch key operated

(e) Door mounted push buttons for Start and Stop functions

(f) Emergency Stop push button lockable type

(g) LED indication lamp for ON, OFF and TRIP

(h) 3 nos. 40A, AC3 Duty, 3-pole Contactor with Auxiliary Contacts and Operating
Coil of 240V AC

(i) One no. Star Delta Timer

(j) Auxiliary Contactors for Auto / Local / Remote operation

(k) Triple Pole, saturable CT operated, bimetal overload relays (with in built single
phasing protection) suitable for above mentioned motor feeder having
arrangement for bypassing the overload relay in case the pump is running
during an emergency scenario with all accessories including 3 nos. saturable
CTs, auxiliary contactors etc.

(l) Power and Control terminals for cable connections

(vi) 2 Nos, 63 A, 35 kA, 3-Pole MCCB Electronic Trip Unit with adjustable protection
against Overload and adjustable protection against Short Circuit

(vii) 1 No. 32A 10 kA TPN MCB

1.03 52 Sub-Main Distribution Board MDB 108 as per Technical Specifications & typical Set 1 1
station drawings and as per following details
A Incoming

(i) Auto Transfer Switch with 2 nos. 1250A, 415V, 65kA, 3-pole, Motorised
ACB consisting of the following :
Electrically operated Draw Out type ACB, complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with
(1) Communication provision through RS-485 for BMS / SCADA (2) Provision
(ii) Digital multifunction
for measurement of energy
V, A, W,meter
VAR,for
VA,measurement of voltage,
Wh, VARh, Hz, line current,
power factor etc (3)
power factor,
Protection powerlong
against & energy
time + short time + earth fault (all with adjustable time
delays) + instantaneous,
3 Nos. CTs, 1250/1A, 15VA, overClass-1
and under voltage, minimum and maximum
for metering
frequency, voltage and current imbalance, phase sequence, load shedding and
reconnection
TNC
(4) switch
Measurement of inturrepted currents, differenciated fault indications,
maintenance indicators (5) Last 15 nos. trippings and event histories and time
stamping with facility for consulting the history file, maintenance indicator
Auto / Local / Remote Selector Switch key operated.
register etc (6) Communication options to remotely read and set parameters for
the protection functions, transmission of all the calculated indicators and
measurements, signalling
LED indication lamp for theoffollowing-
the cause of tripping and alarms (7) NO/NC
contacts for interlocks and indications. (8) Status Indication ON, OFF, TRIP.
ON, OFF, TRIP, spring charged & phase indication (R-Y-B).

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the marshalling box with provision of BMS
interface terminal. All terminal for BMS interface shall be marked with signal and
equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
1600Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

C Outgoing

(i) 1 No. 315A, 50 kA 3-Pole MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit
(ii) 1 No. 250A, 50 kA 3-Pole MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit
(iii) 2 Nos., 200A, 35 KA 3-Pole MCCB (Fire Pumps) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit
2 sets of Star Delta starter unit for Fire Hydrant Pumps (90kW each) (1 working
+ 1 standby). Each starter unit shall be equipped with the following:

(a) 1 no. 3-pole, 415V, 200A, 50kA, 3P Motor Duty MCCB with Magnetic Trip Unit
only (having short circuit protection only) and auxiliary contacts

(b) 1 No. Digital Ammeter, CT operated with communication provision for BMS
interface over MODBUS-RTU Serial ( RS485, 2 wire) wire up to the BMS
interface chamber/compartment.
(c) 1 no. CT, 200/1A, 10VA, Class-1 for metering

(d) Auto / Local / Remote Selector Switch key operated

(e) Door mounted push buttons for Start and Stop functions

(f) Emergency Stop push button lockable type

(g) LED indication lamp for ON, OFF, TRIP

(h) 3 nos. 200A, AC-3 Duty, 3-pole Contactor with Auxiliary Contacts and Operating
Coil of 240V AC

(i) One no. Star Delta Timer

(j) Auxiliary contactors for Auto / Local / Remote Operation

(k) Triple Pole, saturable CT operated, bimetal overload relays (with in built single
phasing protection) suitable for above mentioned motor feeder having
arrangement for bypassing the overload relay in case the pump is running
(l) during
Power an
andemergency scenario
Control terminals forwith all connections
cable accessories including 3 nos. saturable
CTs, auxiliary contactors etc.

(m) Equipment common for both feeders is indicated below:

(i) 1 no. working / standby selector switch

(ii) Auxiliary contactors with 240V AC operating coil (for working / standby
selection)

(iv) 2 Nos., 100A, 35 KA 3-Pole MCCB (One for battery Chjarger & one spare)
having Electronic Trip Unit with adjustable protection against Overload and
adjustable protection against Short Circuit

(v) 1 No, 100 A, 35 kA, 3-Pole MCCB (Jockey Pump)

1 set of Star-Delta Starter Unit (one set for Hydrant Jockey Pump of 20kW).
Each Starter Unit shall be equipped with the following:

(a) 1 no. 3 pole, 415V, 100A, 35kA Motor Duty MCCB with Magnetic Trip Unit only
(having short circuit protection only) and auxiliary contacts.

(b) 1 no. digital ammeter, CT operated

(c) 1 no. CT, 30/1A, 10VA, Class-1 for metering

(d) Auto / Local / Remote Selector Switch key operated


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(e) Door mounted push buttons for Start and Stop functions lN lS lN lS N el S lN S on nel el S ply
N

(f) Emergency Stop push button lockable type

(g) LED indication lamp for ON, OFF and TRIP

(h) 3 nos. 40A, AC3 Duty, 3-pole Contactor with Auxiliary Contacts and Operating
Coil of 240V AC

(i) One no. Star Delta Timer

(j) Auxiliary Contactors for Auto / Local / Remote operation

(k) Triple Pole, saturable CT operated, bimetal overload relays (with in built single
phasing protection) suitable for above mentioned motor feeder having
arrangement for bypassing the overload relay in case the pump is running
during an emergency scenario with all accessories including 3 nos. saturable
CTs, auxiliary contactors etc.

(l) Power and Control terminals for cable connections

(vi) 3 Nos, 63 A, 35 kA, 3-Pole MCCB Electronic Trip Unit with adjustable protection
against Overload and adjustable protection against Short Circuit

1.04 51, 52, 53, 54, Sub-Main Distribution Board MDB 111 as per Technical Specifications & typical Set 1 1 1 1 1 1 1 1 1 1
55 station drawings and as per following details

A Incoming

(i) 1 no. 1250A, 415V, 65kA, 3-pole, ACB consisting of the following :

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil and having microprocessor based releases with (1)
Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 Nos. CTs, 1250/1A, 15VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
1600Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

C Outgoing

(i) 2 nos. 630A, 3-pole, 50 kA MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit.

(ii) 2 Nos., 200A, 35 KA 3-Pole MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 1 No., 100A, 35 KA 3-Pole MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.05 51, 53, 54 Sub-Main Distribution Board MDB 104 as per Technical Specifications & typical Set 1 1 1 1 1 1
station drawings and as per following details

A Incoming

(i) 1 no. 800A, 415V, 65kA, 3-pole, ACB consisting of the following :

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil and having microprocessor based releases with (1)
Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 Nos. CTs, 800/1A, 15VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
B Busbars lN lS lN lS N el S lN S on nel el S ply
N

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
1000Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 400A, 3-pole, 50 kA, MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1 No., 250A, 50 kA, 3-Pole MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit.

(iii) 2 Nos., 200A, 35 kA, 3-Pole MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(vi) 2 nos. 100A, 3-pole, 35kA MCCB (one spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.05 52 Sub-Main Distribution Board MDB 104 as per Technical Specifications & typical Set 1 1
station drawings and as per following details

A Incoming

(i) 1 no. 800A, 415V, 65kA, 3-pole, ACB consisting of the following :

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil and having microprocessor based releases with (1)
Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 Nos. CTs, 800/1A, 15VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
1000Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 400A, 3-pole, 50 kA, MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1 No., 250A, 50 kA, 3-Pole MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit.

(iii) 2 Nos., 200A, 35 kA, 3-Pole MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iv) 1 nos. 125A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(v) 1 nos. 100A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.06 51, 53 Sub-Main Distribution Board MDB 103 as per Technical Specifications & typical Set 1 1 1 1
station drawings and as per following details

A Incoming

(i) 1 no. 630A, 415V, 50kA, 3-pole motorised MCCB having (1) Electronic Trip Unit
with adjustable Overload, adjustable Short Circuit and adjustable Earth Fault
(All with adjustable time delays) protection; (2) Provision for remote tripping of
MCCB;
(3) NO/NC contacts for operation and (4) Neutral sensor for earth fault
protection
(5) Communication provision through RS-485 for BMS.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 nos. CTs, 630/1A, 10VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated lN lS lN lS N el S lN S on nel el S ply
800Amps, suitable to withstand symetrical fault level of 50 KA for 1 second at N
415 volts.

C Outgoing

(i) 1 no. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1no. 100A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 8 nos. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.06 52 Sub-Main Distribution Board MDB 103 as per Technical Specifications & typical Set 1 1
station drawings and as per following details

A Incoming

(i) 1 no. 400A, 415V, 50kA, 3-pole motorised MCCB having (1) Electronic Trip Unit
with adjustable Overload, adjustable Short Circuit and adjustable Earth Fault
(All with adjustable time delays) protection; (2) Provision for remote tripping of
MCCB;
(3) NO/NC contacts for operation and (4) Neutral sensor for earth fault
protection
(5) Communication provision through RS-485 for BMS.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 nos. CTs, 630/1A, 10VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
500Amps, suitable to withstand symetrical fault level of 50 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1no. 100A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 8 nos. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.06 54 Sub-Main Distribution Board MDB 103 as per Technical Specifications & typical Set 1 1
station drawings and as per following details

A Incoming

(i) 1 no. 200A, 415V, 50kA, 3-pole motorised MCCB having (1) Electronic Trip Unit
with adjustable Overload, adjustable Short Circuit and adjustable Earth Fault
(All with adjustable time delays) protection; (2) Provision for remote tripping of
MCCB;
(3) NO/NC contacts for operation and (4) Neutral sensor for earth fault
protection
(5) Communication provision through RS-485 for BMS.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 nos. CTs, 200/1A, 10VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
250Amps, suitable to withstand symetrical fault level of 50 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(ii) 1no. 100A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with lN lS lN lS N el S lN S on nel el S ply
adjustable protection against Overload and adjustable protection against Short N
Circuit.

(iii) 4 nos. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.06 55 Sub-Main Distribution Board MDB 104 as per Technical Specifications & typical Set 1 1
station drawings and as per following details

A Incoming

(i) 1 no. 200A, 415V, 50kA, 3-pole motorised MCCB having (1) Electronic Trip Unit
with adjustable Overload, adjustable Short Circuit and adjustable Earth Fault
(All with adjustable time delays) protection; (2) Provision for remote tripping of
MCCB;
(3) NO/NC contacts for operation and (4) Neutral sensor for earth fault
protection
(5) Communication provision through RS-485 for BMS.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 nos. CTs, 200/1A, 10VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
250Amps, suitable to withstand symetrical fault level of 50 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 3nos. 100A, 3-pole, 35kA MCCB (one spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.06 55 Sub-Main Distribution Board MDB 106 as per Technical Specifications & typical Set 1 1
station drawings and as per following details

A Incoming

(i) 1 no. 200A, 415V, 50kA, 3-pole motorised MCCB having (1) Electronic Trip Unit
with adjustable Overload, adjustable Short Circuit and adjustable Earth Fault
(All with adjustable time delays) protection; (2) Provision for remote tripping of
MCCB;
(3) NO/NC contacts for operation and (4) Neutral sensor for earth fault
protection
(5) Communication provision through RS-485 for BMS.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 nos. CTs, 200/1A, 10VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
250Amps, suitable to withstand symetrical fault level of 50 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1no. 100A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 1 no. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iv) 6 Nos. 32 A, 10 KA SPMCB

1.07 51, 53, 54 Sub-Main Distribution Board MDB 101 as per Technical Specifications & typical Set 1 1 1 1 1 1
station drawings and as per following details
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
A Incoming lN lS lN lS N el S lN S on nel el S ply
N

(i) Automatic Transfer Switch (ATS) with 2 nos. 400A, 4-pole, 35kA motorised
MCCBs with following

(i) motorised MCCB having (1) Electronic Trip Unit with adjustable Overload,
adjustable Short Circuit and adjustable Earth Fault (All with adjustable time
delays) protection; (2) Provision for remote tripping of MCCB; (3) NO/NC
contacts for operation and (4) Neutral sensor for earth fault protection (5)
Communication provision through RS-485 for BMS.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 nos. CTs, 400/1A, 10VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
600Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 3 nos. 100A, 3-pole, 35kA MCCB (one spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 1 no. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iv) 1 No. 32A 10 kA TPN MCB

(v) 4 Nos. 16A 10 kA TPN MCB

1.07 52 Sub-Main Distribution Board MDB 101 as per Technical Specifications & typical Set 1 1
station drawings and as per following details

A Incoming

(i) Automatic Transfer Switch (ATS) with 2 nos. 400A, 4-pole, 35kA motorised
MCCBs with following

(i) motorised MCCB having (1) Electronic Trip Unit with adjustable Overload,
adjustable Short Circuit and adjustable Earth Fault (All with adjustable time
delays) protection; (2) Provision for remote tripping of MCCB; (3) NO/NC
contacts for operation and (4) Neutral sensor for earth fault protection (5)
Communication provision through RS-485 for BMS.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 nos. CTs, 400/1A, 10VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
500Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 3 nos. 100A, 3-pole, 35kA MCCB (one spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 1 no. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iv) 6 No. 32A 10 kA TPN MCB

1.08 51, 52, 53, 54 Sub-Main Distribution Board MDB 106 as per Technical Specifications & typical Set 1 1 1 1 1 1 1 1
station drawings and as per following details

A Incoming

(i) 1 no. 250A, 415V, 35kA, 3-pole motorised MCCB motorised MCCB having (1)
Electronic Trip Unit with adjustable Overload, adjustable Short Circuit and
adjustable Earth Fault (All with adjustable time delays) protection; (2) Provision
for remote tripping of MCCB; (3) NO/NC contacts for operation and (4) Neutral
sensor for earth fault protection (5) Communication provision through RS-485
for BMS.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(ii) TNC switch lN lS lN lS N el S lN S on nel el S ply
N

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 nos. CTs, 250/1A, 10VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
320Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 4 nos. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1 No. 32A 10 kA TPN MCB

(iii) 6 Nos. 16A 10 kA TPN MCB

(iv) 1 No. 10A 10 kA TPN MCB

1.09 51, 52, 53, 54 Local Control Panels MDB 107 as per Technical Specifications & typical station Set 1 1 1 1 1 1 1 1
drawings and as per following details

A Incoming

(i) 1 no. 250A, 415V, 35kA, 4-pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 250/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
320Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 2 nos. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1 No. 40A 10 kA TPN MCB

(iii) 2 Nos. 32A 10 kA TPN MCB

(iv) 5 Nos. 16A 10 kA TPN MCB

1.10 51, 52, 53, 54 Local Control Panels MDB 109 as per Technical Specifications & typical station Set 1 1 1 1 1 1 1 1
drawings and as per following details

A Incoming

(i) 1 no. 200A, 415V, 35kA, 4-pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 200/1A, 10VA, Class-1 for metering

B Busbars
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated lN lS lN lS N el S lN S on nel el S ply
250Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at N
415 volts.

C Outgoing

(i) 3 nos. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.11 51, 53, 54 Local Control Panels MDB 105 as per Technical Specifications & typical station Set 1 1 1 1 1 1
drawings and as per following details

A Incoming

(i) 1 no. 125A, 415V, 35kA, 4-pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 125/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
160Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 2 Nos. 40A 10 kA TPN MCB

(ii) 1 No. 32A 10 kA TPN MCB

(iii) 1 No. 16A 10 kA TPN MCB

1.11 52 Local Control Panels MDB 105 & MDB 110 as per Technical Specifications & Set 2 2
typical station drawings and as per following details

A Incoming

(i) 1 no. 125A, 415V, 35kA, 4-pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 125/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
160Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 2 Nos. 40A 10 kA TPN MCB

(ii) 3 No. 32A 10 kA TPN MCB

1.12 51, 53, 54 Local Control Panels MDB 110 as per Technical Specifications & typical station Set 1 1 1 1 1 1
drawings and as per following details

A Incoming

(i) 1 no. 100A, 415V, 35kA, 4-pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 100/1A, 10VA, Class-1 for metering

B Busbars
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated lN lS lN lS N el S lN S on nel el S ply
125Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at N
415 volts.

C Outgoing

(i) 2 Nos. 40A 10 kA TPN MCB

(ii) 1 No. 32A 10 kA TPN MCB

(iii) 1 No. 16A 10 kA TPN MCB

1.12 52 Local Control Panels MDB 114 as per Technical Specifications & typical station Set 1 1
drawings and as per following details

A Incoming

(i) 1 no. 630A, 415V, 35kA, 4-pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 630/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
800Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 315A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1 no. 250A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 1 no. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iv) 1 no. 125A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(v) 1 no. 63A, 3-pole, 35kA TPN MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit.

(vi) 1 no. 40A 10kA TPN MCB

1.12 55 Local Control Panels MDB 105 as per Technical Specifications & typical station Set 1 1
drawings and as per following details

A Incoming

(i) 1 no. 100A, 415V, 35kA, 4-pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 100/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
125Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(ii) 3Nos. 32A 10 kA TPN MCB

(iii) 1 No. 20A 10 kA TPN MCB

1.13 51, 53 Local Control Panels MDB 112 as per Technical Specifications & typical station Set 1 1 1 1
drawings and as per following details

A Incoming

(i) Automatic Transfer Switch (ATS) with 2 nos. 63A, 4-pole, 35kA motorised
MCCBs

Motorized MCCB having Electronic Trip Unit with adjustable protection against
Overload, adjustable protection against Short Circuit and having NO/NC
contacts for operation.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(ii) LED indication lamp for ON, OFF & TRIP. lN lS lN lS N el S lN S on nel el S ply
N

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 63/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
100Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 2 Nos. 40A 10 kA TPN MCB

(ii) 1 No. 16A 10 kA TPN MCB

1.13 52 Local Control Panels MDB 112 as per Technical Specifications & typical station Set 1 1
drawings and as per following details

A Incoming

(i) Automatic Transfer Switch (ATS) with 2 nos. 250A, 4-pole, 35kA motorised
MCCBs

Motorized MCCB having Electronic Trip Unit with adjustable protection against
Overload, adjustable protection against Short Circuit and having NO/NC
contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 250/5A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
320Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 160A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1 no. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 1 No. 32A 10 kA TPN MCB

1.13 54 Local Control Panels MDB 112 as per Technical Specifications & typical station Set 1 1
drawings and as per following details

A Incoming

(i) Automatic Transfer Switch (ATS) with 2 nos. 100A, 4-pole, 35kA motorised
MCCBs

Motorized MCCB having Electronic Trip Unit with adjustable protection against
Overload, adjustable protection against Short Circuit and having NO/NC
contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 100/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
100Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 1 No. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1 No. 40A 10 kA TPN MCB

(iii) 1 No. 16A 10 kA TPN MCB


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
1.13 52 Local Control Panels MDB 113 as per Technical Specifications & typical station Set lN lS 1 lN lS 1 N el S lN S on nel el S ply
drawings and as per following details N

A Incoming

(i) Automatic Transfer Switch (ATS) with 2 nos. 63A, 4-pole, 35kA motorised
MCCBs

Motorized MCCB having Electronic Trip Unit with adjustable protection against
Overload, adjustable protection against Short Circuit and having NO/NC
contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 63/5A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
100Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 4 No. 32A 10 kA TPN MCB

1.13 55 Local Control Panels MDB 101 as per Technical Specifications & typical station Set 1 1
drawings and as per following details

A Incoming

(i) Automatic Transfer Switch (ATS) with 2 nos. 63A, 4-pole, 35kA motorised
MCCBs

Motorized MCCB having Electronic Trip Unit with adjustable protection against
Overload, adjustable protection against Short Circuit and having NO/NC
contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 63/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
100Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 3 Nos. 20A 10 kA TPN MCB

(ii) 2 Nos. 16A 10 kA TPN MCB

(iii) 1 No. 10A 10 kA TPN MCB

1.14 51, 53, 54 Local Control Panels MDB 207 as per Technical Specifications & typical station Set 1 1 1 1 1 1
drawings and as per following details

A Incoming

(i) 1 no. 2000A, 415V, 65kA, 3-pole, ACB consisting of the following :

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil and having microprocessor based releases with (1)
Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(vii) 3 Nos. CTs, 2000/1A, 15VA, Class-1 for metering lN lS lN lS N el S lN S on nel el S ply
N

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
2500Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

C Outgoing

(i) 3 Nos., 630 A 50 kA 3-Pole MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit.

(ii) 1 No. 400 A 50 kA 3-Pole MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 4 Nos., 200A, 35 KA 3-Pole MCCB (two spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(v) 2 Nos., 100A, 35 KA 3-Pole MCCB (one spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(vi) 1 No, 63 A, 35 kA, 3-Pole MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.14 52 Local Control Panels MDB 207 as per Technical Specifications & typical station Set 1 1
drawings and as per following details

A Incoming

(i) 1 no. 2500A, 415V, 65kA, 3-pole, ACB consisting of the following :

Electrically operated Draw Out type, ACB complete with safety shutters, 240V
AC shunt trip coil and having microprocessor based releases with (1)
Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 Nos. CTs, 2500/1A, 15VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
3200Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

C Outgoing

(i) 3 Nos., 630 A 50 kA 3-Pole MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit.

(ii) 1 No. 400 A 50 kA 3-Pole MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 3 Nos., 250A, 35 KA 3-Pole MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit.

(iv) 2 Nos., 200A, 35 KA 3-Pole MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(v) 2 Nos., 100A, 35 KA 3-Pole MCCB (one spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.15 51, 52, 53, 54 Local Control Panels MDB 201 as per Technical Specifications & typical station Set 1 1 1 1 1 1 1 1
drawings and as per following details

A Incoming

(i) 1 no. 1250A, 415V, 65kA, 3-pole, ACB consisting of the following :
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Electrically operated Draw Out type, ACB complete with safety shutters, 240V lN lS lN lS N el S lN S on nel el S ply
AC shunt trip coil and having microprocessor based releases with (1) N
Communication provision through RS-485 for BMS (2) Provision for
measurement of three phase current (3) Protection against long time + short
time + earth fault (all with adjustable time delays) + instantaneous (4) Zone
Selective Interlocking Unit for Total Discrimination (5) Last 15 nos. trippings and
event histories and time stamping with facility for consulting the history file,
maintenance indicator register etc (6) Communication options to remotely read
and set parameters for the protection functions, transmission of ammeter
measurements, Signailing of the cause of tripping and alarms, maximeter reset
etc (7) NO / NC contacts for interlocks and indications (8) 1 No. CT in the
neutral to connect with the trip unit.

(ii) TNC switch

(iii) LED indication lamp for ON, OFF & TRIP.

(iv) Phase Indication for R, Y and B

(v) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(vi) Digital Ammeter with inbuilt Selector Switch

(vii) 3 Nos. CTs, 1250/1A, 15VA, Class-1 for metering

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
1600Amps, suitable to withstand symetrical fault level of 65 KA for 1 second at
415 volts.

C Outgoing

(i) 2 Nos., 630 A 50 kA 3-Pole MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit.

(ii) 2 nos. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 1 no. 100A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.16 51, 53, 54 Local Control Panels MDB 203 as per Technical Specifications & typical station Set 1 1 1 1 1 1
drawings and as per following details

A Incoming

(i) 1 no. 800A, 415V, 50kA, TPN MCCB having Electronic Trip Unit with adjustable
protection against Overload, adjustable protection against Short Circuit and
having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 800/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
800Amps, suitable to withstand symetrical fault level of 50 KA for 1 second at
415 volts.

C Outgoing

(i) 1 No., 400 A 50 kA 3-Pole MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit.

(ii) 1 nos. 250A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 2 nos. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iv) 2 nos. 100A, 3-pole, 35kA MCCB (one spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.16 52 Local Control Panels MDB 203 as per Technical Specifications & typical station Set 1 1
drawings and as per following details

A Incoming

(i) 1 no. 800A, 415V, 65kA, TPN MCCB having Electronic Trip Unit with adjustable
protection against Overload, adjustable protection against Short Circuit and
having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 800/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
1000Amps, suitable to withstand symetrical fault level of 50 KA for 1 second at
415 volts.

C Outgoing

(i) 1 No., 400 A 50 kA 3-Pole MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(ii) 1 nos. 250A, 3-pole, 35kA MCCB having Electronic Trip Unit with lN lS lN lS N el S lN S on nel el S ply
adjustable protection against Overload and adjustable protection against Short N
Circuit.

(iii) 1 no. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iv) 1 nos. 125A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iv) 1 nos. 100A, 3-pole, 35kA MCCB (one spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.17 51, 52, 53 Local Control Panels MDB 205 as per Technical Specifications & typical station Set 1 1 1 1 1 1
drawings and as per following details

A Incoming

(i) 1 no. 630A, 415V, 35kA, 4pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 630/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
800Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1 no. 100A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 12 nos. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.17 54 Local Control Panels MDB 205 as per Technical Specifications & typical station Set 1 1
drawings and as per following details

A Incoming

(i) 1 no. 400A, 415V, 35kA, 4pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 400/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
500Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 10 nos. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.18 51, 53, 54 Local Control Panels MDB 206 as per Technical Specifications & typical station Set 1 1 1 1 1 1
drawings and as per following details

A Incoming

(i) 1 no. 400A, 415V, 35kA, 4-pole MCCB

(i) 1 no. 400A, 415V, 35kA, 4pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 400/1A, 10VA, Class-1 for metering

B Busbars
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated lN lS lN lS N el S lN S on nel el S ply
500Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at N
415 volts.

C Outgoing

(i) 1 no. 400A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1 no. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.18 52 Local Control Panels MDB 206 as per Technical Specifications & typical station Set 1 1
drawings and as per following details

A Incoming

(i) 1 no. 630A, 415V, 50kA, 4pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 630/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
800Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 400A, 3-pole, 50kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(ii) 1 no. 200A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(iii) 1 no. 100A, 3-pole, 35kA MCCB (spare) having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

(vi) 1 nos. 63A, 3-pole, 35kA MCCB having Electronic Trip Unit with
adjustable protection against Overload and adjustable protection against Short
Circuit.

1.19 51, 52, 53, 54 Local Control Panels MDB 204 as per Technical Specifications & typical station Set 1 1 1 1 1 1 1 1
drawings and as per following details

A Incoming

(i) 1 no. 250A, 415V, 35kA, 4pole MCCB having Electronic Trip Unit with
adjustable protection against Overload, adjustable protection against Short
Circuit and having NO/NC contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(vi) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 250/1A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
320Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 1 no. 160/200A, 3-pole, 35kA MCCB

(ii) For Water Supply System

A 2 sets of Star Delta starter unit of 5.5kW each for Water Supply pumps (1
working + 1 standby), 6 sets of Star-Delta Starter Unit of 3.75kW each for
Softener Feed Pump (1 working + 1 standby), Portable Water Pump (1 working
+ 1 standby) and 2 nos. spare feeder. Each Starter Unit shall be equipped with
the following:

(a) 1 no. 3-pole, 20A, MPCB (with inbuilt single phasing preventor) having 6-10A
overload release and having auxiliary contacts for indications for ON, OFF and
TRIP

(b) 1 no. 4-pole, RCCB with 40A rating and 100mA sensitivity

© 1 no. digital ammeter, CT operated

(d) 1 no. CT, 20/1A, 10VA, Class-1 for metering

€ Auto / Local / Remote Selector Switch key operated

(f) Door mounted push buttons for Start and Stop functions
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(g) Emergency Stop push button lockable type lN lS lN lS N el S lN S on nel el S ply
N

(h) LED indication lamp for ON, OFF, TRIP

(i) 2 nos. 18A, AC-3 Duty, 3-pole Contactor with Auxiliary Contacts and Operating
Coil of 240V AC

(j) One no. Star Delta Timer

(k) Running hour meter

(l) Auxiliary contactors for Auto / Local / Remote Operation

(m) Power and Control terminals for cable connections

1.20 54 Local Control Panels MDB 208 as per Technical Specifications & typical station Set 1 1
drawings and as per following details

A Incoming

(i) Automatic Transfer Switch (ATS) with 2 nos. 100A, 4-pole, 35kA motorised
MCCBs

Motorised MCCB having Electronic Trip Unit with adjustable protection against
Overload, adjustable protection against Short Circuit and having NO/NC
contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 100/5A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
125Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 1 No. 63A, 3-pole, 35kA MCCB

(ii) 1 No. 40A 10 kA TPN MCB

(iii) 1 No. 16A 10 kA TPN MCB

1.20 52 Local Control Panels MDB 209 as per Technical Specifications & typical station Set 1 1
drawings and as per following details

A Incoming

(i) Automatic Transfer Switch (ATS) with 2 nos. 200A, 4-pole, 35kA motorised
MCCBs

Motorised MCCB having Electronic Trip Unit with adjustable protection against
Overload, adjustable protection against Short Circuit and having NO/NC
contacts for operation.

(ii) LED indication lamp for ON, OFF & TRIP.

(iii) Phase Indication for R, Y and B

(iv) 1 No Digital Voltmeter with Inbuilt Selector Switch.

(v) Digital Ammeter with inbuilt Selector Switch

(vi) 3 nos. CTs, 200/5A, 10VA, Class-1 for metering

B Busbars

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
250Amps, suitable to withstand symetrical fault level of 35 KA for 1 second at
415 volts.

C Outgoing

(i) 2 Nos. 40A 10 kA TPN MCB

(ii) 8 Nos. 32A 10 kA TPN MCB

III The following specification shall be covered for (DG Synchronizing Panels -
DGMDB 1 & DGMDB 2) & conform to Tech Spec
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
A Main (Grid) Supply Incomer shall be provided with the following: lN lS lN lS N el S lN S on nel el S ply
N

(a) 415V, 65 kA, 4 Pole, Electrically operated Draw Out type, ACB complete with
safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of three phase and neutral current
(3) Protection against long time + short time + earth fault (all with adjustable
time delays) + instantaneous (4) Zone Selective Interlocking Unit for Total
Discrimination (5) Last 15 nos. trippings and event histories and time stamping
with facility for consulting the history file, maintenance indicator register etc (6)
Communication options to remotely read and set parameters for the protection
functions, transmission of ammeter measurements ,signailing of the cause of
tripping and alarms, maximeter reset etc (7) NO / NC contacts for interlocks
and indications. (8) Status Indication ON, OFF, TRIP.

(b) TNC (Trip / Neutral / Close) switch

(c) Auto / Local / Remote Selector Switch key operated

(d) LED indication lamp for ON, OFF, TRIP, Spring Charged & Phase Indication R,
Y, B

(e) Digital ammeter with inbuilt Selector Switch

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

B DG Incomer shall be provided with the following:

(a) Electrically operated Drawout type ACB, complete with safety shutters, 240V
AC shunt trip coil & closing coil and having microprocessor based releases with:

415V, 65 kA, 3 Pole, Electrically operated Draw Out type ACB, complete with
safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of V, A, W, VAR, VA, Wh, VARh,
Hz, power factor etc
(3) Protection against long time + short time + instantanious + earth fault (all
with adjustable time delays), over and under voltage, minimum and maximum
frequency, voltage and current imbalance, phase sequence, load shedding and
reconnection & reverse power protection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements , Signailing of the cause of
tripping and alarms (7) NO / NC contacts for interlocks and indications.

(b) TNC (Trip / Neutral / Close) switch

(c) Selector switch for Auto / Local / Remote operation of breaker, Manual / Auto
Synchronization, Online set selection

(d) LED indication lamp for ON, OFF, TRIP, Spring Charged & Phase Indication R,
Y, B

(e) Push buttons for Fault Accept, Annunciator Reset, Lamp Test

(f) Metering

Digital multifunction energy meter for measurement of voltage, line current,


power factor, power & energy

(g) Protection

(i) Microprocessor based restricted earth fault relay

(ii) Microprocessor based differential protection relay

(iii) Master trip lockout relay

(h) 8 window annunciator with heater

C Synchronizing equipment

(a) Provision and installation of auto synchronizing module for each DG set with
AMF, active & reactive auto load sharing & auto load management, with 16 nos.
digital inputs & digital outputs, with provision for BMS / SCADA connectivity

(b) 1 no. double voltmeter, 1 no. double frequency meter, 1 no. synchronoscope, 1
no. synchro check relay, set of dark lamps with auxiliary transformer, 1 no.
selector switch for set to be synchronized (one set for total no. of DG sets)

(c) Voltage rasie / lower & frequency raise / lower switch

(d) Solid state / motorized potentiometer for AVR and speed control (as per
manufacturer's requirement)

(e) 1 no. 24V DC source unit, 24V DC battery (for 8 hours backup) with battery
charging circuit (common for all DG synchronization system)

NOTE: All components required for DG synchronization unit shall be provided


by DG supplier. LV panel builder shall provide necessary space in panel
supplied by him for mounting all necessary equipments required for mounting
DG synchronizing unit. LV panel builder shall install all components (free issue)
required for synchronization unit and suitable wire for functional requirement as
specified by the DG supplier.

D All outgoing MCCBs shall be provided with the following:

(a) 3P MCCB having Electronic Trip Unit with adjustable protection against
overload, adjustable protection against short circuit and earth fault (with
adjustable time delays); having NO/NC contacts for operation and neutral
sensor for earth fault protection.

(b) LED indication lamp for ON, OFF, TRIP, Phase Indication R, Y, B
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(c) Digital ammeter with inbuilt Selector Switch lN lS lN lS N el S lN S on nel el S ply
N

1.21 51, 53, 54 DG Set Power Control and Synchronizing Panel DGMDB as per Tech Spec and Set 1 1 1 1 1 1
drawings complete and as per following details

A DG Incomer 1

(i) 1 no. 2000A, 415V, 50kA, 4-pole ACB

415V, 65 kA, 3 Pole, Electrically operated Draw Out type ACB, complete with
safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of V, A, W, VAR, VA, Wh, VARh,
Hz, power factor etc
(3) Protection against long time + short time + instantanious + earth fault (all
with adjustable time delays), over and under voltage, minimum and maximum
frequency, voltage and current imbalance, phase sequence, load shedding and
reconnection & reverse power protection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements , Signailing of the cause of
tripping and alarms (7) NO / NC contacts for interlocks and indications.

(ii) 4 nos. CTs,2000/1A, 15VA, Class-1 for metering

(iii) Protection

4 nos. CTs, 2000/1A, 15VA, Class-PS (3 nos. in panel and one no. in DG
neutral) for REF protection

6 nos. CTs, 2000/1A, 15VA, Class-PS (3 nos. in panel and 3 nos. in Alternator
winding) for differential protection

(iv) 1 no. 2000A, AC3 duty, power contactor with auxiliary contacts for neutral

B DG Incomer 2

(i) 1 nos. 2000A, 415V, 50kA, 3-pole ACB

415V, 50 kA, 3 Pole, Electrically operated Draw Out type ACB, complete with
safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of V, A, W, VAR, VA, Wh, VARh,
Hz, power factor etc
(3) Protection against long time + short time + instantanious + earth fault (all
with adjustable time delays), over and under voltage, minimum and maximum
frequency, voltage and current imbalance, phase sequence, load shedding and
reconnection & reverse power protection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements , Signailing of the cause of
tripping and alarms (7) NO / NC contacts for interlocks and indications.

(ii) 1 no. 400A, AC3 duty, power contactor with auxiliary contacts for neutral

(iii) TNC switch

(iv) Selector switch for following operation-

(v) Auto / Local / Remote operation of Breaker, Manual / Auto Synchronization, On


line set selection.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication R-Y-B.

(vii) Push Buttons for the following functions-

(viii) Fault Accept, Annunciator Reset, Lamp test.

(ix) Metering

Multifunction energy meter for measurement of voltage, line current, power


factor, power & energy, kVa, KVAh etc. , 4 nos. TOD Type(Time of Day
metering with Tariff)

4 Nos. CTs, 2000/5A, 15VA, CL-1 for metering.

(x) Protection-

Microprocessor base restricted earth fault relay.

Microprocessor base differential protection relay.

Master Trip Lockout Relay.

4 Nos. CTs, 2000/5A, 15VA, CL-PS.(3 Nos in Panel and One No in DG neutral)
for REF protection.

6 Nos. CTs, 2000/5A, 15VA, CL-PS. (3 Nos in Panel and 3 Nos in Alternator
Winding) for Differential protection.

(xi) 8 Window Annunciator with Hooter.

(xii) Synchronizing equipment-

Provision & Installation of Auto Synchronising Module for each DG Set with
AMF, Active & Reactive Auto load sharing & Auto Load Management, adequate
Digital Inputs & Digital Outputs, with provision for BMS / SCADA connectivity.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
1 No Double Voltmeter, 1 No Double frequency Meter, 1 No Synchronoscope,1 lN lS lN lS N el S lN S on nel el S ply
No Synchro Check Relay, Set of dark lamps with auxiliary transformer, 1 No N
Selector Switch for set to be synchronised (One set for Total No of DG sets)

Voltage Raise / Lower & Frequency Raise / Lower Switch.

Solid state / Motorised Potentiometer for AVR and Speed control ( as per
manufacturer's requirement).

1 No 24V DC source unit, 24V DC battery (for 8 hours back up) with battery
charging circuit. (Common for all DG synchronization system).

NOTE-All component required for DG synchronization unit shall be provided by


DG supplier. LV panel builder shall provide necessary space in panel supplied
by him for mounting all necessary equipments required for mounting DG
synchronizing unit. LV panel builder shall installed all components ( free issue )
required for synchronization unit and suitable wire for functional requirement as
specified by the DG supplier.

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

C Busbar

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
4000Amps, suitable to withstand symetrical fault level of 50 KA for 1 second at
415 volts.

D Outgoings

(i) 2 nos. 2000A, 415V, 65kA, 4-pole ACB

415V, 65 kA, 4 Pole, Electrically operated Draw Out type, ACB complete with
safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of three phase and neutral current
(3) Protection against long time + short time + earth fault (all with adjustable
time delays) + instantaneous (4) Zone Selective Interlocking Unit for Total
Discrimination (5) Last 15 nos. trippings and event histories and time stamping
with facility for consulting the history file, maintenance indicator register etc (6)
Communication options to remotely read and set parameters for the protection
functions, transmission of ammeter measurements ,signailing of the cause of
tripping and alarms, maximeter reset etc (7) NO / NC contacts for interlocks
and indications. (8) Status Indication ON, OFF, TRIP.

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF & TRIP.

ON, OFF, TRIP, spring charged & phase indication R-Y-B.

Digital Ammeter with Inbuilt Selector Switch

3 Nos. CTs, 2000/1A, 15VA, CL-1 for metering.

Digital voltmeter with inbuilt selector switch

(ii) 1 no. 1250A, 415V, 65kA, 4-pole ACB

415V, 65 kA, 4 Pole, Electrically operated Draw Out type, ACB complete with
safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of three phase and neutral current
(3) Protection against long time + short time + earth fault (all with adjustable
time delays) + instantaneous (4) Zone Selective Interlocking Unit for Total
Discrimination (5) Last 15 nos. trippings and event histories and time stamping
with facility for consulting the history file, maintenance indicator register etc (6)
Communication options to remotely read and set parameters for the protection
functions, transmission of ammeter measurements ,signailing of the cause of
tripping and alarms, maximeter reset etc (7) NO / NC contacts for interlocks
and indications. (8) Status Indication ON, OFF, TRIP.

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF & TRIP.

ON, OFF, TRIP, spring charged & phase indication R-Y-B.

Digital ammeter with inbuilt selector switch

Digital voltmeter with inbuilt selector switch

3 nos. CTs, 1250/1A, 15VA, Class-1 for metering

(iv) 1 no. 400A, 415V, 35kA, 3P MCCB (spare)

415V, 65kA, 3P, MCCB having Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit and Earth Fault
(With Adjustable time delay); having NO/NC contacts for operation and neutral
sensor for earth fault protection.

LED Phase Indication for R, Y & B

Digital Ammeter with Inbuilt Selector Switch


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
3 nos. CTs, 400/1A, 10VA, Class-1 for metering lN lS lN lS N el S lN S on nel el S ply
N

(v) 2 nos. 200A, 415V, 35kA, 3P MCCB (spare)

415V, 65kA, 3P, MCCB having Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit and Earth Fault
(With Adjustable time delay); having NO/NC contacts for operation and neutral
sensor for earth fault protection.

LED Phase Indication for R, Y & B

Digital Ammeter with Inbuilt Selector Switch

3 nos. CTs, 200/1A, 10VA, Class-1 for metering

(vi) 3 nos. 100A, 415V, 35kA, 3P MCCB (one spare)

415V, 65kA, 3P, MCCB having Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit and Earth Fault
(With Adjustable time delay); having NO/NC contacts for operation and neutral
sensor for earth fault protection.

LED Phase Indication for R, Y & B

Digital Ammeter with Inbuilt Selector Switch

3 nos. CTs, 100/1A, 10VA, Class-1 for metering

1.21 52 DG Set Power Control and Synchronizing Panel DGMDB as per Tech Spec and Set 1 1
drawings complete and as per following details

A DG Incomer 1

(i) 1 no. 2500A, 415V, 50kA, 4-pole ACB

415V, 65 kA, 3 Pole, Electrically operated Draw Out type ACB, complete with
safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of V, A, W, VAR, VA, Wh, VARh,
Hz, power factor etc
(3) Protection against long time + short time + instantanious + earth fault (all
with adjustable time delays), over and under voltage, minimum and maximum
frequency, voltage and current imbalance, phase sequence, load shedding and
reconnection & reverse power protection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements , Signailing of the cause of
tripping and alarms (7) NO / NC contacts for interlocks and indications.

(ii) 4 nos. CTs,2500/1A, 15VA, Class-1 for metering

(iii) Protection

4 nos. CTs, 2500/1A, 15VA, Class-PS (3 nos. in panel and one no. in DG
neutral) for REF protection

6 nos. CTs, 2500/1A, 15VA, Class-PS (3 nos. in panel and 3 nos. in Alternator
winding) for differential protection

(iv) 1 no. 400A, AC3 duty, power contactor with auxiliary contacts for neutral

B DG Incomer 2

(i) 1 nos. 2000A, 415V, 50kA, 3-pole ACB

415V, 50 kA, 3 Pole, Electrically operated Draw Out type ACB, complete with
safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of V, A, W, VAR, VA, Wh, VARh,
Hz, power factor etc
(3) Protection against long time + short time + instantanious + earth fault (all
with adjustable time delays), over and under voltage, minimum and maximum
frequency, voltage and current imbalance, phase sequence, load shedding and
reconnection & reverse power protection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements , Signailing of the cause of
tripping and alarms (7) NO / NC contacts for interlocks and indications.

(ii) 4 nos. CTs,2000/1A, 15VA, Class-1 for metering

(iii) Protection

4 nos. CTs, 2000/1A, 15VA, Class-PS (3 nos. in panel and one no. in DG
neutral) for REF protection

6 nos. CTs, 2000/1A, 15VA, Class-PS (3 nos. in panel and 3 nos. in Alternator
winding) for differential protection

(ii) 1 no. 400A, AC3 duty, power contactor with auxiliary contacts for neutral

(iii) TNC switch

(iv) Selector switch for following operation-

(v) Auto / Local / Remote operation of Breaker, Manual / Auto Synchronization, On


line set selection.

(vi) LED indication lamp for the following-


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
ON, OFF, TRIP, spring charged & phase indication R-Y-B. lN lS lN lS N el S lN S on nel el S ply
N

(vii) Push Buttons for the following functions-

(viii) Fault Accept, Annunciator Reset, Lamp test.

(ix) Metering

Multifunction energy meter for measurement of voltage, line current, power


factor, power & energy, kVa, KVAh etc. , 4 nos. TOD Type(Time of Day
metering with Tariff)

4 Nos. CTs, 2000/5A, 15VA, CL-1 for metering.

(x) Protection-

Microprocessor base restricted earth fault relay.

Microprocessor base differential protection relay.

Master Trip Lockout Relay.

4 Nos. CTs, 2000/5A, 15VA, CL-PS.(3 Nos in Panel and One No in DG neutral)
for REF protection.

6 Nos. CTs, 2000/5A, 15VA, CL-PS. (3 Nos in Panel and 3 Nos in Alternator
Winding) for Differential protection.

(xi) 8 Window Annunciator with Hooter.

(xii) Synchronizing equipment-

Provision & Installation of Auto Synchronising Module for each DG Set with
AMF, Active & Reactive Auto load sharing & Auto Load Management, adequate
Digital Inputs & Digital Outputs, with provision for BMS / SCADA connectivity.

1 No Double Voltmeter, 1 No Double frequency Meter, 1 No Synchronoscope,1


No Synchro Check Relay, Set of dark lamps with auxiliary transformer, 1 No
Selector Switch for set to be synchronised (One set for Total No of DG sets)

Voltage Raise / Lower & Frequency Raise / Lower Switch.

Solid state / Motorised Potentiometer for AVR and Speed control ( as per
manufacturer's requirement).

1 No 24V DC source unit, 24V DC battery (for 8 hours back up) with battery
charging circuit. (Common for all DG synchronization system).

NOTE-All component required for DG synchronization unit shall be provided by


DG supplier. LV panel builder shall provide necessary space in panel supplied
by him for mounting all necessary equipments required for mounting DG
synchronizing unit. LV panel builder shall installed all components ( free issue )
required for synchronization unit and suitable wire for functional requirement as
specified by the DG supplier.

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

C Busbar

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
4000Amps, suitable to withstand symetrical fault level of 50 KA for 1 second at
415 volts.

D Outgoings

(i) 1 nos. 2500A, 415V, 65kA, 4-pole ACB

415V, 65 kA, 4 Pole, Electrically operated Draw Out type, ACB complete with
safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of three phase and neutral current
(3) Protection against long time + short time + earth fault (all with adjustable
time delays) + instantaneous (4) Zone Selective Interlocking Unit for Total
Discrimination (5) Last 15 nos. trippings and event histories and time stamping
with facility for consulting the history file, maintenance indicator register etc (6)
Communication options to remotely read and set parameters for the protection
functions, transmission of ammeter measurements ,signailing of the cause of
tripping and alarms, maximeter reset etc (7) NO / NC contacts for interlocks
and indications. (8) Status Indication ON, OFF, TRIP.

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF & TRIP.

ON, OFF, TRIP, spring charged & phase indication R-Y-B.

Digital Ammeter with Inbuilt Selector Switch

3 Nos. CTs, 2500/1A, 15VA, CL-1 for metering.

Digital voltmeter with inbuilt selector switch


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(ii) 1 no. 2000A, 415V, 65kA, 4-pole ACB lN lS lN lS N el S lN S on nel el S ply
N

415V, 65 kA, 4 Pole, Electrically operated Draw Out type, ACB complete with
safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of three phase and neutral current
(3) Protection against long time + short time + earth fault (all with adjustable
time delays) + instantaneous (4) Zone Selective Interlocking Unit for Total
Discrimination (5) Last 15 nos. trippings and event histories and time stamping
with facility for consulting the history file, maintenance indicator register etc (6)
Communication options to remotely read and set parameters for the protection
functions, transmission of ammeter measurements ,signailing of the cause of
tripping and alarms, maximeter reset etc (7) NO / NC contacts for interlocks
and indications. (8) Status Indication ON, OFF, TRIP.

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF & TRIP.

ON, OFF, TRIP, spring charged & phase indication R-Y-B.

Digital ammeter with inbuilt selector switch

Digital voltmeter with inbuilt selector switch

3 nos. CTs, 2000/1A, 15VA, Class-1 for metering

(iii) 1 no. 1250A, 415V, 65kA, 3P MCCB (spare)

415V, 65kA, 3P, MCCB having Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit and Earth Fault
(With Adjustable time delay); having NO/NC contacts for operation and neutral
sensor for earth fault protection.

LED Phase Indication for R, Y & B

Digital Ammeter with Inbuilt Selector Switch

3 nos. CTs, 1250/1A, 10VA, Class-1 for metering

(iv) 1 nos. 400A, 415V, 35kA, 3P MCCB (spare)

415V, 65kA, 3P, MCCB having Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit and Earth Fault
(With Adjustable time delay); having NO/NC contacts for operation and neutral
sensor for earth fault protection.

LED Phase Indication for R, Y & B

Digital Ammeter with Inbuilt Selector Switch

3 nos. CTs, 400/1A, 10VA, Class-1 for metering

(v) 2 nos. 200A, 415V, 35kA, 3P MCCB ( spare)

415V, 65kA, 3P, MCCB having Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit and Earth Fault
(With Adjustable time delay); having NO/NC contacts for operation and neutral
sensor for earth fault protection.

LED Phase Indication for R, Y & B

Digital Ammeter with Inbuilt Selector Switch

3 nos. CTs, 200/1A, 10VA, Class-1 for metering

(vi) 3 nos. 100A, 415V, 35kA, 3P MCCB ( spare)

415V, 65kA, 3P, MCCB having Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit and Earth Fault
(With Adjustable time delay); having NO/NC contacts for operation and neutral
sensor for earth fault protection.

LED Phase Indication for R, Y & B

Digital Ammeter with Inbuilt Selector Switch

3 nos. CTs, 100/1A, 10VA, Class-1 for metering

1.21 55 DG Set Power Control and Synchronizing Panel DGMDB as per Tech Spec and Set 1 1
drawings complete and as per following details

A DG Incomer 1

(i) 1 no. 1250A, 415V, 50kA, 4-pole ACB


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
415V, 65 kA, 3 Pole, Electrically operated Draw Out type ACB, complete with lN lS lN lS N el S lN S on nel el S ply
safety shutters, 240V AC shunt trip coil & closing coil and having N
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of V, A, W, VAR, VA, Wh, VARh,
Hz, power factor etc
(3) Protection against long time + short time + instantanious + earth fault (all
with adjustable time delays), over and under voltage, minimum and maximum
frequency, voltage and current imbalance, phase sequence, load shedding and
reconnection & reverse power protection (4) Measurement of inturrepted
currents, differenciated fault indications, maintenance indicators (5) Last 15
trippings and event histories and time stamping with facility for consulting the
history file, maintenance indicator register etc (6) Communication options to
remotely read and set parameters for the protection functions, transmission of
all the calculated indicators and measurements , Signailing of the cause of
tripping and alarms (7) NO / NC contacts for interlocks and indications.

(ii) 4 nos. CTs,1250/1A, 15VA, Class-1 for metering

(iii) Protection

4 nos. CTs, 1250/1A, 15VA, Class-PS (3 nos. in panel and one no. in DG
neutral) for REF protection

6 nos. CTs, 1250/1A, 15VA, Class-PS (3 nos. in panel and 3 nos. in Alternator
winding) for differential protection

(iv) 1 no. 400A, AC3 duty, power contactor with auxiliary contacts for neutral

(iv) TNC switch

(v) Selector switch for following operation-

(v) Auto / Local / Remote operation of Breaker, Manual / Auto Synchronization, On


line set selection.

(vi) LED indication lamp for the following-

ON, OFF, TRIP, spring charged & phase indication R-Y-B.

(vii) Push Buttons for the following functions-

(viii) Fault Accept, Annunciator Reset, Lamp test.

(ix) Metering

Multifunction energy meter for measurement of voltage, line current, power


factor, power & energy, kVa, KVAh etc. , 4 nos. TOD Type(Time of Day
metering with Tariff)

4 Nos. CTs, 1250/5A, 15VA, CL-1 for metering.

(x) Protection-

Microprocessor base restricted earth fault relay.

Microprocessor base differential protection relay.

Master Trip Lockout Relay.

4 Nos. CTs, 1250/5A, 15VA, CL-PS.(3 Nos in Panel and One No in DG neutral)
for REF protection.

6 Nos. CTs, 1250/5A, 15VA, CL-PS. (3 Nos in Panel and 3 Nos in Alternator
Winding) for Differential protection.

(xi) 8 Window Annunciator with Hooter.

(xii) Synchronizing equipment-

Provision & Installation of Auto Synchronising Module for each DG Set with
AMF, Active & Reactive Auto load sharing & Auto Load Management, adequate
Digital Inputs & Digital Outputs, with provision for BMS / SCADA connectivity.

1 No Double Voltmeter, 1 No Double frequency Meter, 1 No Synchronoscope,1


No Synchro Check Relay, Set of dark lamps with auxiliary transformer, 1 No
Selector Switch for set to be synchronised (One set for Total No of DG sets)

Voltage Raise / Lower & Frequency Raise / Lower Switch.

Solid state / Motorised Potentiometer for AVR and Speed control ( as per
manufacturer's requirement).

1 No 24V DC source unit, 24V DC battery (for 8 hours back up) with battery
charging circuit. (Common for all DG synchronization system).

NOTE-All component required for DG synchronization unit shall be provided by


DG supplier. LV panel builder shall provide necessary space in panel supplied
by him for mounting all necessary equipments required for mounting DG
synchronizing unit. LV panel builder shall installed all components ( free issue )
required for synchronization unit and suitable wire for functional requirement as
specified by the DG supplier.

Voltage Free Contactor (VFC) of different signal and remote control interface
terminal shall be wired directly to the separate chamber/ compartment with
provision of BMS interface terminal. All terminal for BMS interface shall be
marked with signal and equipment tag for BMS interface.

Communication port for serial RS-485 standard protocol communication


(MODBUS RTU) shall be wired upto the BMS interface terminal chamber.

C Busbar

Electrolytic high conductivity T P & N (full size) copper conductor bus-bars rated
1700Amps, suitable to withstand symetrical fault level of 50 KA for 1 second at
415 volts.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
D Outgoings lN lS lN lS N el S lN S on nel el S ply
N

(i) 2 nos. 1250A, 415V, 65kA, 4-pole ACB

415V, 65 kA, 4 Pole, Electrically operated Draw Out type, ACB complete with
safety shutters, 240V AC shunt trip coil & closing coil and having
microprocessor based releases with (1) Communication provision through RS-
485 for BMS (2) Provision for measurement of three phase and neutral current
(3) Protection against long time + short time + earth fault (all with adjustable
time delays) + instantaneous (4) Zone Selective Interlocking Unit for Total
Discrimination (5) Last 15 nos. trippings and event histories and time stamping
with facility for consulting the history file, maintenance indicator register etc (6)
Communication options to remotely read and set parameters for the protection
functions, transmission of ammeter measurements ,signailing of the cause of
tripping and alarms, maximeter reset etc (7) NO / NC contacts for interlocks
and indications. (8) Status Indication ON, OFF, TRIP.

TNC switch

Auto / Local / Remote Selector Switch key operated.

LED indication lamp for ON, OFF & TRIP.

ON, OFF, TRIP, spring charged & phase indication R-Y-B.

Digital Ammeter with Inbuilt Selector Switch

3 Nos. CTs, 2000/1A, 15VA, CL-1 for metering.

Digital voltmeter with inbuilt selector switch

(ii) 1 no. 400A, 415V, 35kA, 3P MCCB (spare)

415V, 65kA, 3P, MCCB having Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit and Earth Fault
(With Adjustable time delay); having NO/NC contacts for operation and neutral
sensor for earth fault protection.

LED Phase Indication for R, Y & B

Digital Ammeter with Inbuilt Selector Switch

3 nos. CTs, 400/1A, 10VA, Class-1 for metering

(iii) 2 nos. 200A, 415V, 35kA, 3P MCCB (spare)

415V, 65kA, 3P, MCCB having Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit and Earth Fault
(With Adjustable time delay); having NO/NC contacts for operation and neutral
sensor for earth fault protection.

LED Phase Indication for R, Y & B

Digital Ammeter with Inbuilt Selector Switch

3 nos. CTs, 200/1A, 10VA, Class-1 for metering

(iv) 3 nos. 100A, 415V, 35kA, 3P MCCB (one spare)

415V, 65kA, 3P, MCCB having Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit and Earth Fault
(With Adjustable time delay); having NO/NC contacts for operation and neutral
sensor for earth fault protection.

LED Phase Indication for R, Y & B

Digital Ammeter with Inbuilt Selector Switch

3 nos. CTs, 100/1A, 10VA, Class-1 for metering

1.22 51, 52, 53, 54, DG Auxiliary Panel DGDB 1 as per Tech Spec and drawings complete and as Set 1 1 1 1 1 1 1 1 1 1
55 per the following details:

A Incoming

(a) 1 no. 100A, 415V, 35kA, 3P MCCB having Electronic Trip Unit with adjustable
protection against overhead, adjustable protection against short circuit and
earth fault and having NO/NC contacts for operation and neutral sensor for
earth fault protection

(b) LED indication lamp for ON, OFF, TRIP and Phase Indication R, Y, B

(c) Metering

(i) 1 no. digital voltmeter with inbuilt selector switch

(ii) 1 no. digital ammeter with inbuilt selector switch

(iii) 3 nos. CTs, 100/1A, 10VA, Class-1 for metering

B Busbars

100A suitable to withstand symmetrical fault level of 35kA for 1 second at 415V
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
C Outgoings lN lS lN lS N el S lN S on nel el S ply
N

[1] 3 sets of DOL Starter units of 0.75kW each for Engine Lube Oil priming pump (2
working + 1 spare) & each shall be equipped as detailed below:

(a) 1 no. 3-pole 10A MPCB (with inbuilt single phasing preventor) having 1.6-2.4A
overload release and having contacts for indications - On, Off, Trip

(b) 1 no. 4-pole, RCCB with 40A rating and 100mA sensitivity

(c) Auto / Local / Remote Selector Switch key operated

(d) Door mounted push buttons for Start and Stop functions

(e) Emergency stop push button lockable type

(f) LED indication lamp for ON, OFF, TRIP

(g) 1 no. 9A, AC3 Duty, 3-pole contactor with auxiliary contacts and operating coil
of 240V AC

(h) Auxiliary contactors for Auto / Local / Remote Operation

(i) Power & Control terminals for cable connections

[2] 2 sets of DOL Starter units of 2.2kW each for Fuel Transfer Pumps (1 working
+1 standby) & each shall be equipped as detailed below:

(a) 1 no. 3-pole 20A MPCB (with inbuilt single phasing preventor) having 4.0-6.0A
overload release and having contacts for indications - ON, OFF, TRIP

(b) 1 no. 4-pole RCCB with 40A rating and 100mA sensitivity

(c) 1 no. digital ammeter, CT operated

(d) 1 no. CT, 20/1A, 10VA, Class-1 for metering

(e) Auto / Local / Remote Selector Switch key operated

(f) Door mounted push buttons for Start and Stop functions

(g) Emergency stop push button lockable type

(h) LED indication lamp for ON, OFF, TRIP

(i) 1 no. 16A, AC3 Duty, 3-pole contactor with Auxiliary Contacts and Operating
Coil of 240V AC

(j) One no. timer with instantaneous and Time Delay Contact (for programming in
case selected pump is not operative then next shall be switched on
automatically)

(k) Running hour meter

(l) Auxiliary contactors for Auto / Local / Remote Operation

(m) Power & Control terminals for cable connections

[3] Equipment common for feeders as below:

(a) 1 no. Working / Standby Selector Switch

(b) Auxiliary Contactors with 240V AC operating coil (for Working / Standby
selection)

[4] 3 nos. 40A, 415V, 3P MCB

IV The following specification shall be covered for (Sub Main Distribution Boards)
& conform to Tech Spec

(a) ATS shall be provided with the following:

(1) 2 nos. motorized MCCBs, electrically and mechanically interlocked with base
frame and controller having selector switch for automatic & forced operation on
normal and emergency sources.

(2) The controller should have communication capability with BMS/SCADA

(3) The MCCBs must have Electronic Trip Unit with adjustable protection
against Overload, adjustable protection against Short Circuit, shunt trip coil,
auxiliary contacts for ON, OFF, TRIP indication etc.

(4) LED indication lamps for ON, OFF, TRIP and Phase Indication (R, Y, B)

(b) 1 no. digital voltmeter with inbuilt selector switch

(c) 1 no. digital ammeter with inbuilt selector switch

(d) All outgoing breakers MCCBs shall be provided with the following:

Electronic adjustable trip unit for overload and short circuit protection

1.23 51, 52, 53, 54 Local Motor Control Panel for Storm/Waste Water Pumps MDB WP as per Tech Set 2 2 3 0 0 3 3 3 0 6 3 3 0 6
Spec and drawings complete and as per following details
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
A Incoming lN lS lN lS N el S lN S on nel el S ply
N

(i) Automatic Transfer Switch (ATS) with 2 nos. 160/100A, 4-pole, 35kA motorised
MCCBs

(ii) Metering

3 nos. CTs, 160/1A, 10VA, Class-1 for metering

B Busbars

1000A suitable to withstand symmetrical fault level of 35kA for 1 second at 415V

C Outgoing

3 sets of Star Delta starter unit for Storm Water Pumps (5.5/7.5kW each) - two
working and one as standby. Each starter unit shall be equipped with the
following:

(a) 1 no. 3-pole, 20A, MPCB (with inbuilt single phasing preventor) having 10-15A
overload release and having auxiliary contacts for indications for ON, OFF and
TRIP

(b) 1 no. 4-pole, RCCB with 40A rating and 100mA sensitivity

(c) 1 no. digital ammeter, CT operated

(d) 1 no. CT, 20/1A, 10VA, Class-1 for metering

(e) Auto / Local / Remote Selector Switch key operated

(f) Door mounted push buttons for Start and Stop functions

(g) Emergency Stop push button lockable type

(h) LED indication lamp for ON, OFF, TRIP

(i) 3 nos. 20A, AC-3 Duty, 3-pole Contactor with Auxiliary Contacts and Operating
Coil of 240V AC

(j) One no. Star Delta Timer

(k) One no. timer with instantaneous and Time Delay Contact (for programming in
case selected pump is not operative then next shall be switched on
automatically)

(l) Running hour meter

(m) Auxiliary contactors for Auto / Local / Remote Operation

(n) Power and Control terminals for cable connections

(o) Equipment common for all feeders as indicated below:

1 no. 3-position Selector Switch with all other accessories and auxiliary
contactors with 240V AC operating coil (for level indication multiplication) to
change the sequence of operation of three motors automatically.

1.24 51, 52, 53, 54 Local Motor Control Panel for Sewage Pump MDB SW as per Tech Spec and Set 1 1 2 2 2 2 1 1
drawings complete and as per following details

A Incoming

(i) Automatic Transfer Switch (ATS) with 2 nos. 63A, 4-pole, 35kA motorised
MCCBs

(ii) Metering

3 nos. CTs, 63/1A, 10VA, Class-1 for metering

B Busbars

1000A suitable to withstand symmetrical fault level of 35kA for 1 second at 415V

C Outgoing

2 sets of Star Delta starter unit for Seepage Pumps (5 kW each) - one working
and one as standby. Each starter unit shall be equipped with the following:

(a) 1 no. 3-pole, 40A, MPCB (with inbuilt single phasing preventor) having 16-25A
overload release and having auxiliary contacts for indications for ON, OFF and
TRIP

(b) 1 no. 4-pole, RCCB with 40A rating and 100mA sensitivity

(c) 1 no. digital ammeter, CT operated

(d) 1 no. CT, 40/1A, 10VA, Class-1 for metering

(e) Auto / Local / Remote Selector Switch key operated

(f) Door mounted push buttons for Start and Stop functions

(g) Emergency Stop push button lockable type


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(h) LED indication lamp for ON, OFF, TRIP lN lS lN lS N el S lN S on nel el S ply
N

(i) 3 nos. 25A, AC-3 Duty, 3-pole Contactor with Auxiliary Contacts and Operating
Coil of 240V AC

(j) One no. Star Delta Timer

(k) One no. timer with instantaneous and Time Delay Contact (for programming in
case selected pump is not operative then next shall be switched on
automatically)

(l) Running hour meter

(m) Auxiliary contactors for Auto / Local / Remote Operation

(n) Power and Control terminals for cable connections

(o) Equipment common for all feeders as indicated below:

1 no. 3-position Selector Switch with all other accessories and auxiliary
contactors with 240V AC operating coil (for level indication multiplication) to
change the sequence of operation of three motors automatically.

1.24 55 Local Motor Control Panel for DomesticPump MDB 103 as per Tech Spec and Set 1 1
drawings complete and as per following details

A Incoming

(i) Automatic Transfer Switch (ATS) with 2 nos. 32A, TP MCB

(ii) Metering

3 nos. CTs, 32/1A, 10VA, Class-1 for metering

B Busbars

60A suitable to withstand symmetrical fault level of 35kA for 1 second at 415V

C Outgoing

2 sets of Star Delta starter unit for Seepage Pumps (5 kW each) - one working
and one as standby. Each starter unit shall be equipped with the following:

(a) 1 no. 3-pole, 32A, MPCB (with inbuilt single phasing preventor) having 16-25A
overload release and having auxiliary contacts for indications for ON, OFF and
TRIP

(b) 1 no. 4-pole, RCCB with 32A rating and 100mA sensitivity

(c) 1 no. digital ammeter, CT operated

(d) 1 no. CT, 32/1A, 10VA, Class-1 for metering

(e) Auto / Local / Remote Selector Switch key operated

(f) Door mounted push buttons for Start and Stop functions

(g) Emergency Stop push button lockable type

(h) LED indication lamp for ON, OFF, TRIP

(i) 3 nos. 25A, AC-3 Duty, 3-pole Contactor with Auxiliary Contacts and Operating
Coil of 240V AC

(j) One no. Star Delta Timer

(k) One no. timer with instantaneous and Time Delay Contact (for programming in
case selected pump is not operative then next shall be switched on
automatically)

(l) Running hour meter

(m) Auxiliary contactors for Auto / Local / Remote Operation

(n) Power and Control terminals for cable connections

(o) Equipment common for all feeders as indicated below:

1 no. 3-position Selector Switch with all other accessories and auxiliary
contactors with 240V AC operating coil (for level indication multiplication) to
change the sequence of operation of three motors automatically.

A Incoming

(i) Automatic Transfer Switch (ATS) with 2 nos. 32A, TP MCBs

(ii) Metering

3 nos. CTs, 32/1A, 10VA, Class-1 for metering

B Busbars

60A suitable to withstand symmetrical fault level of 35kA for 1 second at 415V
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
C Outgoing lN lS lN lS N el S lN S on nel el S ply
N

2 sets of Star Delta starter unit for Seepage Pumps (5 kW each) - one working
and one as standby. Each starter unit shall be equipped with the following:

(a) 1 no. 3-pole, 40A, MPCB (with inbuilt single phasing preventor) having 16-25A
overload release and having auxiliary contacts for indications for ON, OFF and
TRIP

(b) 1 no. 4-pole, RCCB with 40A rating and 100mA sensitivity

(c) 1 no. digital ammeter, CT operated

(d) 1 no. CT, 40/1A, 10VA, Class-1 for metering

(e) Auto / Local / Remote Selector Switch key operated

(f) Door mounted push buttons for Start and Stop functions

(g) Emergency Stop push button lockable type

(h) LED indication lamp for ON, OFF, TRIP

(i) 3 nos. 25A, AC-3 Duty, 3-pole Contactor with Auxiliary Contacts and Operating
Coil of 240V AC

(j) One no. Star Delta Timer

(k) One no. timer with instantaneous and Time Delay Contact (for programming in
case selected pump is not operative then next shall be switched on
automatically)

(l) Running hour meter

(m) Auxiliary contactors for Auto / Local / Remote Operation

(n) Power and Control terminals for cable connections

(o) Equipment common for all feeders as indicated below:

1 no. 3-position Selector Switch with all other accessories and auxiliary
contactors with 240V AC operating coil (for level indication multiplication) to
change the sequence of operation of three motors automatically.

1.25 51, 52, 53, 54 Power Factor Correction Panel of 250 400 kVAR as per Tech Spec and Set 2 2 2 2 2 2 2 2
Drawing complete and as per the following details

A Incoming

(a) 1 no. 630 1000A, 415V, 50kA, 3-pole motorised MCCB EDO ACB with 240V
AC shunt trip coil and having electronics releases with

(1) Communication capability

(2) Provision for measurement of three phase current

(3) Protection against overload (with base setting and fine adjustment), short
circuit and earth fault (all with adjustable time delays) + Instantaneous

(4) Communication options to remotely read parameters for the protection


functions transmission of ammeter measurements, signaling of cause of
tripping, maximeter reset etc.

(5) NO/NC contacts for interlocks and indications

(6) Neutral sensor for earth fault protection

(b) LED indication lamp for ON, OFF, TRIP and Phase Indication for R, Y, B

(c) 10 step APFCR relay

(d) 1 no. auto / manual selector switch

(e) Metering

(i) 1 no. digital voltmeter with inbuilt Selector Switch

(ii) 1 no. digital Ammeter with Inbuilt Selector Switch

B Busbars

1000A suitable to withstand symmetrical fault level of 50kA for 1 second at 415V

C Outgoings

(a) 10 nos. feeders with each feeder containing the following:

1 no. 100A, 3-pole, 35kA, MCCB having Electronic Trip Unit with adjustable
protection against Overhead and adjustable protection against short circuit

(b) Capacitor Duty, 3-pole Contactor suitable for 25kVAR capacitor with auxiliary
contacts
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(c) 2 nos. push button for ON & OFF lN lS lN lS N el S lN S on nel el S ply
N

(d) 2 nos. LED indication lamp for ON & OFF indication

(e) 1 no. 25 kVAR, 3-phase, 480V, hermitically sealed metallized polypropylene


capacitor (heavy duty) with 7% harmonic D-tuned filters
3-100 kVAR
1-50 kVAR
2-25 Kvar

Capacitor Banks of 0.5 watts per KVAR loss with suitable capacity to maintain
0.95 PF with APFC Relay

1.25 55 Power Factor Correction Panel of 150 kVAR as per Tech Spec and Drawing Set 1 1
complete and as per the following details

A Incoming

(a) 1 no.400A, 415V, 50kA, 3-pole motorised MCCB with 240V AC shunt trip coil
and having electronics releases with

(1) Communication capability

(2) Provision for measurement of three phase current

(3) Protection against overload (with base setting and fine adjustment), short
circuit and earth fault (all with adjustable time delays) + Instantaneous

(4) Communication options to remotely read parameters for the protection


functions transmission of ammeter measurements, signaling of cause of
tripping, maximeter reset etc.

(5) NO/NC contacts for interlocks and indications

(6) Neutral sensor for earth fault protection

(b) LED indication lamp for ON, OFF, TRIP and Phase Indication for R, Y, B

(c) 10 step APFCR relay

(d) 1 no. auto / manual selector switch

(e) Metering

(i) 1 no. digital voltmeter with inbuilt Selector Switch

(ii) 1 no. digital Ammeter with Inbuilt Selector Switch

B Busbars

500A suitable to withstand symmetrical fault level of 50kA for 1 second at 415V

C Outgoings

(a) 10 nos. feeders with each feeder containing the following:

1 no. 63A, 3-pole, 35kA, MCCB having Electronic Trip Unit with adjustable
protection against Overhead and adjustable protection against short circuit

(b) Capacitor Duty, 3-pole Contactor suitable for 25kVAR capacitor with auxiliary
contacts

(c) 2 nos. push button for ON & OFF

(d) 2 nos. LED indication lamp for ON & OFF indication

(e) 1 no. 25 kVAR, 3-phase, 480V, hermitically sealed metallized polypropylene


capacitor (heavy duty) with 7% harmonic D-tuned filters

Capacitor Banks of 0.5 watts per KVAR loss with suitable capacity to maintain
0.95 PF with APFC Relay

1.26 Isolator Box for Lifts & Escalators as per Technical Specifications & Drawing
complete and as per the following details

51, 52, 53, 54 1 no. 63A, 415V, 35kA, 3P, MCCB having Electronic Trip Unit with adjustable Set 22 22 22 22 22 22 22 22
protection against overload, adjustable protector against Short Circuit and Earth
Fault (with adjustable time delay); having NO/NC contacts for operation and
neutral sensor for earth fault protection

(a) 1 no. 4-pole RCCB with 63A rating and 100mA sensitivity

(b) LED phase indication lamp for R, Y, B

(c) Digital ammeter with inbuilt Selector Switch

(d) Digital voltmeter with inbuilt Selector Switch

(e) 3 nos. CTs, 63/1A, 10VA, Class-1 for metering

(f) 1 no. ON/OFF Selector Switch

(g) 2 nos. 16A, SPN MCB (B curve for single supply)


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Outgoing terminals for cable connection to be provided lN lS lN lS N el S lN S on nel el S ply
N

1.27 51, 52, 53, 54, Supply and installing of key lockable emergency stop push button box (including Nos. 40 40 50 50 40 40 40 40 5 5
55 Emergency push button with contact, gland plate at both end for cable
connection) conforming to IP-55 protection for each Motor & pump

1.28 51, 52, 53, 54, Supply and placing of ribbed surface rubber mat 12mm thick or more suitable to Mtr 80 80 100 100 80 80 80 80 10 10
55 withstand 11kV voltahe grade and 900mm width as required including cutting to
required lengths, of approved make, with test certificates for LT panels

1.29 51, 52, 53, 54, Providing and fixing of MV danger plate of 200 x 150mm of mild steel at least Nos. 12 12 15 15 12 12 12 12 5 5
55 2mm thick and vitreous enamelled white on both side and with inscription in
signal red colour on front side as required

1.30 51, 52, 53, 54, Providing and fixing of wall mounted wooden cabinet of suitable size with glazed Nos. 3 3 4 4 3 3 3 3 1 1
55 front-opening door, equipment with hooks to house all keys

2 DISTRIBUTION BOARD

The Distribution Boards specified herein, must conform to the Technical


Specifications, in addition to the description given in respective items of BOQ,
whether explicity specified or not. In case of contradiction between Technical
Specifications and description in BOQ, the most stringent of the specified
conditions will prevail

All the items / parts mentioned in relevant clauses of the Technical


Specifications and not specifically mentioned in BOQ shall be deemed to be
included in the quoted rates, unless specifically excluded.

DBs shall be provided with suitable timers & Contactors to meet out the
requirement of lighting/power as per technical specifications & BMS
compatability should be there

The size of the Panel / DBs shall be such that all the components / meters shall
be neatly placed for easy approach and maintainability

Supply, installation, testing and commissioning of front operated, indoor, front


access cubicle type, dead rear, wall / recess / surface mounted Distribution
Boards (conforming to specifications given in Tech Spec.) The Distribution
Boards must have ingress protection classification of IP54, current rating of
100A, and must be suitable to withstand symmetrical fault current level of 10kA
for 1 second at 415V, with the configurations detailed below. Distribution boards
must be provided with electrolytic, high conductivity, TPN copper busbars as
specified in Tech Spec (with full sized Neutral busbar), gland plates at both
ends, blanking plates etc. as required. All internal wiring within the DIstribution
Boards must be with Copper Conductor, LSZH wires (conforming to BS 7211
and Tech Spec) for Normal Lighting and Socket Distribution Boards and with
Fire Survival wires (conforming to BS 7848 and Tech Spec) for Emergency
Lighting Distribution Boards.

2.1 51, 53, 54 TPN Distribution Boards for Concourse level areas Nos. 3 3 3 3 3 3

SDB - 6 , 7, spare

Incoming

(i) 1 no. 100A, 4P, Onload Manual/Auto Changeover Switch with 2 nos. auxiliary
contacts for position signaling

(ii) 1 no. 63A, TPN MCB

(iii) 3 nos. 40A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 10A, SP MCB

Terminals blocks for power and control cables

2.2 51, 53, 54 TPN Distribution Boards No. 2 2 2 2 2 2

SDB - 5, spare

Incoming

(i) 1 no. 63A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary contacts
for position signaling

(ii) 1 no. 50A, TPN MCB

(iii) 3 nos. 40A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 10A, SP MCB

Terminals blocks for power and control cables

2.3 51, 53, 54 TPN Distribution Boards Nos. 9 9 9 9 9 9

SDB - 10, 11, 15, 16, 18, 20, 21, 23, spare

Incoming

(i) 1 no. 63A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary contacts
for position signaling

(ii) 1 no. 40A, TPN MCB

(iii) 3 nos. 40A, DP RCCB (30mA sensitivity)


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Outgoing lN lS lN lS N el S lN S on nel el S ply
N

(i) 24 nos. 16/10A, SP MCB

Terminals blocks for power and control cables

2.4 51, 53, 54, 55 TPN Distribution Boards Nos. 5 5 5 5 5 5 3 3

SDB - 8, 9, 13, 14, spare (7,8,9 for 55)

Incoming

(i) 1 no.32A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary contacts
for position signaling

(ii) 1 no.32A, TPN MCB

(iii) 3 nos. 32A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 6/10/ 16A, SP MCB

Terminals blocks for power and control cables

2.5 51, 53, 54, 55 TPN Distribution Boards Nos. 12 12 12 12 12 12 3 3

SDB - 1, 2, 3, 4, 12, 17, 19, 22, 4 spare (4,5,6 for 55)

Incoming

(i) 1 no. 16A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary contacts
for position signaling

(ii) 1 no. 16A, TPN MCB

(iii) 3 nos. 16A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 6/10/16 A, SP MCB

2.5 55 TPN Distribution Boards Nos. 4 4

SDB - 1,2,3,10, spare

Incoming

(i) 1 no. 20A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary contacts
for position signaling

(ii) 1 no. 16A, TPN MCB

(iii) 3 nos. 16A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 6/10/16 A, SP MCB

2.6 52 TPN Distribution Boards Nos. 1 1

SDB - 29

Incoming

(i) 1 no. 315A, 4P, Onload Manual/Auto Changeover Switch with 2 nos. auxiliary
contacts for position signaling

(ii) 1 no. 250A, TPN MCCB

(iii) 3 nos. 63A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 10A, SP MCB

Terminals blocks for power and control cables

2.7 52 TPN Distribution Boards No. 1 1

SDB - 26

Incoming
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(i) 1 no. 315A, TPN MCCB lN lS lN lS N el S lN S on nel el S ply
N

2.8 52 TPN Distribution Boards No. 1 1

SDB - 25

Incoming

(i) 1 no. 250A, TPN MCCB

2.9 52 TPN Distribution Boards No. 1 1

SDB - 22

Incoming

(i) 1 no. 125A, TPN MCCB

2.10 52 TPN Distribution Boards No. 1 1

SDB - 23

Incoming

(i) 1 no. 63A, TPN MCCB

2.11 52 TPN Distribution Boards No. 1 1

SDB - 24

Incoming

(i) 1 no. 40A, TPN MCCB

2.12 52 TPN Distribution Boards Nos. 1 1

SDB - 21

Incoming

(i) 1 no. 160A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary
contacts for position signaling

(ii) 1 no. 100A, TPN MCB

(iii) 3 nos. 63A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 16A, SP MCB

Terminals blocks for power and control cables

2.13 52 TPN Distribution Boards Nos. 2 2

SDB - 5, 27

Incoming

(i) 1 no.100A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary
contacts for position signaling

(ii) 1 no.63A, TPN MCB

(iii) 3 nos. 40A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 10A, SP MCB

Terminals blocks for power and control cables


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
lN lS lN lS N el S lN S on nel el S ply
N

2.14 52 TPN Distribution Boards Nos. 2 2

SDB - 19, spare

Incoming

(i) 1 no. 63A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary contacts
for position signaling

(ii) 1 no. 50A, TPN MCB

(iii) 3 nos. 40A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 10A, SP MCB

2.15 52 TPN Distribution Boards Nos. 6 6

SDB - 9, 10, 15, 34, 35, spare

Incoming

(i) 1 no. 40A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary contacts
for position signaling

(ii) 1 no. 40A, TPN MCB

(iii) 3 nos. 40A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 16/10A, SP MCB

Terminals blocks for power and control cables

2.16 52 TPN Distribution Boards Nos. 19 19

SDB - 1,2,3,4,6,7,11,12,14,17,18,20,28,30,31,32,33, 2spare

Incoming

(i) 1 no.32A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary contacts
for position signaling

(ii) 1 no.32A, TPN MCB

(iii) 3 nos. 32A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 6/10/ 16A, SP MCB

Terminals blocks for power and control cables

2.17 52 TPN Distribution Boards Nos. 2 2

SDB - 2 spare

Incoming

(i) 1 no. 16A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary contacts
for position signaling

(ii) 1 no. 16A, TPN MCB

(iii) 3 nos. 16A, DP RCCB (30mA sensitivity)

Outgoing

(i) 24 nos. 6/10/16 A, SP MCB

2.18 51, 52, 53, 54, Emergency TPN Distribution Boards Nos. 7 7 7 7 7 7 7 7 1 1
55

UDB - 2, 3, 11, 12, 16, 17, spare (UDB 3 for 55)


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Incoming lN lS lN lS N el S lN S on nel el S ply
N

1 no. 63A TPN MCB

Outgoing

12 nos. 6/10A SP MCB

Terminals blocks for power and control cables

2.19 51, 52, 53, 54 Emergency Lighting TPN Distribution Boards Nos. 4 4 4 4 4 4 4 4

UDB - 8, 19, 20, spare

Incoming

1 no. 32A TPN MCB

Outgoing

12 nos. 6/10A SP MCB

Terminals blocks for power and control cables

2.20 51, 52, 53, 54 Emergency Lighting TPN Distribution Boards Nos. 2 2 2 2 2 2 2 2

UDB - 21, spare

Incoming

1 no. 40A TPN MCB

Outgoing

12 nos. 6/10A SP MCB

Terminals blocks for power and control cables

2.21 51, 52, 53, 54, Emergency Lighting TPN Distribution Boards Nos. 14 14 14 14 14 14 14 14 6 6
55

UDB - 1, 4, 5, 6, 7, 9, 10, 13, 14, 15, 22, 23, 2 spare (UDB 1,2,4,5,6,7 for 55)

Incoming

1 no. 16 A TPN MCB

Outgoing

12 nos. 6/10A SP MCB

Terminals blocks for power and control cables

2.22 51, 53, 54 Emergency Lighting TPN Distribution Boards for Cuffe Parade Side Tunnel Nos. 1 1 1 1 1 1
Lighting

UDB

Incoming

One no.32A, 3-pole, 10kA MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit. The
MCCB should be suitable for remote ON and OFF and auxiliary ON and OFF
contacts should be provided for remote monitoring.

Outgoing

12 nos. 6/10A SP MCB

Terminals blocks for power and control cables

2.23 52 Emergency Lighting TPN Distribution Boards Nos. 1 1

UDB

Incoming

One no.32A, 3-pole, 10kA MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit. The
MCCB should be suitable for remote ON and OFF and auxiliary ON and OFF
contacts should be provided for remote monitoring.

Outgoing
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
12 nos. 6/10A SP MCB lN lS lN lS N el S lN S on nel el S ply
N

Terminals blocks for power and control cables

2.24 51, 53, 54 Emergency Lighting TPN Distribution Boards for Kalba Devi Side Tunnel Nos. 1 1 1 1 1 1
Lighting

UDB

Incoming

One no. 40A, 3-pole, 10kA MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit. The
MCCB should be suitable for remote ON and OFF and auxiliary ON and OFF
contacts should be provided for remote monitoring.

Outgoing

12 nos. 6/10A SP MCB

Terminals blocks for power and control cables

2.25 52 Emergency Lighting TPN Distribution Boards Nos. 1 1

UDB

Incoming

One no. 40A, 3-pole, 10kA MCCB having Electronic Trip Unit with adjustable
protection against Overload and adjustable protection against Short Circuit. The
MCCB should be suitable for remote ON and OFF and auxiliary ON and OFF
contacts should be provided for remote monitoring.

Outgoing

12 nos. 6/10A SP MCB

Terminals blocks for power and control cables

2.26 51, 52, 53, 54 Lighting TPN Distribution Boards for External Lighting Feeder Pillar IP 65 Nos. 2 2 2 2 2 2 2 2
Protection

LDB (one Spare)

Incoming

(i) 1 no. 63/32A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary
contacts for position signaling

(ii) 1 no. 40A, TPN MCB

(iii) 3 nos. 25A, DP MCB + RCCB (30mA sensitivity)

(iv) 3 nos. 25A, 3-pole AC3 duty contactor

(v) Auxiliary contactors, 4 nos. push buttons, indication lamp for 50%, 75% and
100% selection, Local / Remote selector switch for Auto / Local Operation and
lighting control from control desk located at Station Control Room or through
BMS/SCADA

Outgoing

(i) 24 nos. 10A, SP MCB

Terminals blocks for power and control cables

2.27 51, 52, 53, 54, Lighting TPN Distribution Boards for Invertor Nos. 1 1 1 1 1 1 1 1 1 1
55

IDB

Incoming

(i) 1 no. 63/32A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary
contacts for position signaling

(ii) 1 no. 40A, TPN MCB

(iii) 3 nos. 25A, DP MCB + RCCB (30mA sensitivity)

(iv) 3 nos. 25A, 3-pole AC3 duty contactor

(v) Auxiliary contactors, 4 nos. push buttons, indication lamp for 50%, 75% and
100% selection, Local / Remote selector switch for Auto / Local Operation and
lighting control from control desk located at Station Control Room or through
BMS/SCADA

Outgoing

(i) 6 nos. 63/32A, SP MCB

(ii) 6 nos. 16A, SP MCB


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Terminals blocks for power and control cables lN lS lN lS N el S lN S on nel el S ply
N

Total

3 LV Cables, Cable Trays, Bus Trunking, Lighting Track & Steel Works

The cable and cable containment system specified herein must conform to the
Tech Spec, in addition to the description given in respective items of BOQ,
whether explicitly specified or not. In case of contradiction between Tech Spec
and description in BOQ, the most stringent of the condition will prevail.

All the items / parts mentioned in relevant clauses of the Tech Spec and not
specifically mentioned in BOQ shall be deemed to be included in the quoted
rates, unless specifically excluded.

It may be noted that Contractor will be required to carry out cable sizing based
on actual cable lengths, as per working drawings developed by him and after
incorporating any changes in load requirements from the tendering stage.
Optimization must be carried out during cable sizing to reduce the cable
requirement and size. Further, contractor must obtain Engineer's approval on
the Cable SIzing Calculation.

Cable Supply

3.01 Supply, laying, testing and commissioning at the site of 600/1000V grade,
copper conductor, XLPE insulated, armoured, low smoke zero halogen (LSZH),
type cables conforming to BS 6724 and Tech Spec of the following sizes:

(a) 51, 52, 53, 54, 4-core, 400 sqmm Mtr 2550 2550 6500 6500 2550 2550 2200 2200 150 150
55

(b) 51, 52, 53, 54, 4-core, 300 sqmm Mtr 1300 1300 800 800 1300 1300 1600 1600 75 75
55

(c) 51, 52, 53, 54, 4-core, 240 sqmm Mtr 2200 2200 1800 1800 2200 2200 1000 1000 140 140
55

(d) 51, 52, 53, 54 4-core, 185 sqmm Mtr 1500 1500 800 800 1500 1500 1250 1250 0

(e) 51, 52, 53, 54 4-core, 150 sqmm Mtr 150 150 1500 1500 150 150 200 200 0

(f) 51, 52, 53, 54 4-core, 120 sqmm Mtr 1600 1600 1200 1200 1600 1600 700 700 0

(g) 51, 52, 53, 54, 4-core, 95 sqmm Mtr 1200 1200 3000 3000 1200 1200 1400 1400 40 40
55

(h) 51, 52, 53, 54 4-core, 70 sqmm Mtr 300 300 900 900 300 300 1250 1250 0

(i) 51, 52, 53, 54 4-core, 50 sqmm Mtr 3600 3600 300 300 3600 3600 60 60 0

(j) 51, 52, 53, 54 4-core, 35 sqmm Mtr 1200 1200 900 900 1200 1200 1600 1600 0

(k) 51, 52, 53, 54, 4-core, 25 sqmm Mtr 1200 1200 3800 3800 1200 1200 1400 1400 180 180
55

(l) 51, 52, 53, 54, 4-core, 16 sqmm Mtr 200 200 2400 2400 200 200 1200 1200 75 75
55

(m) 51, 52, 53, 54, 4-core, 10 sqmm Mtr 2100 2100 700 700 2100 2100 2000 2000 240 240
55

(n) 51, 52, 53, 54, 4-core, 6 sqmm Mtr 500 500 1200 1200 500 500 300 300 300 300
55

(o) 52, 54, 55 4-core, 4 sqmm Mtr 0 0 100 100 0 0 150 150 100 100

(p) 4-core, 2.5 sqmm Mtr 0 0 0 0 0 0 0 0

3.02 Supply, laying, testing and commissioning at the site 600/1000V grade, copper
conductor, XLPE insulated, armoured Fire Survival Type Cables conforming to
BS 7846 Category F2 meeting the criteria of withstanding 950 degree C at a
rated voltage of 600/1000V and Tech Spec, of the following sizes:

Note: In case of any contradiction between BS 7846 and Tech Spec, the
stringent conditions of the two will apply.

(a) 51, 52, 53, 54, 3-core, 240 sqmm Mtr 200 200 200 200 200 200 200 200 30 30
55

(b) 51, 52, 53, 54, 3-core, 185 sqmm Mtr 100 100 100 100 100 100 100 100 30 30
55

(c) 51, 52, 53, 54, 3-core, 95sqmm Mtr 60 60 60 60 60 60 60 60 30 30


55

(d) 51, 52, 53, 54, 3-core, 35 sqmm Mtr 50 630 680 50 50 50 240 290 50 390 440 30 30
55

(g) 51, 52, 53, 54, 3-core, 16 sqmm Mtr 50 50 50 50 50 50 50 50 30 30


55

(j) 51, 52, 53, 54, 3-core, 6 sqmm Mtr 100 100 100 100 100 100 100 100 30 30
55

(k) 51, 52, 53, 54, 2-core, 4 sqmm Mtr 50 50 50 50 50 50 50 50 30 30


55

(l) 51, 52, 53, 54, 2-core, 2.5 sqmm Mtr 50 50 50 50 50 50 50 50 30 30


55

3.03 Supply, laying, testing and commissioning at the site of 600/1000V grade,
copper conductor, XLPE insulated, armoured Fire Survival Type Auxiliary /
Control Cables conforming to BS 7846 Category F2 meeting the criteria of
withstanding 950 degree C for 3 hours at a rated voltage of 600/1000V and
Tech Spec, of the following sizes:

Note: In case of any contradiction between BS 6724 and Tech Spec, the
stringent conditions of the two will apply.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(a) 51, 52, 53, 54, 4-core, 2.5 sqmm copper cable Mtr 100 lN l S 100 100 lN l S 100 100 N el S 100 100 lN S 100 on
30 nel el S 30 ply
55 N

(b) 51, 52, 53, 54, 3-core, 2.5 sqmm copper cable Mtr 100 100 100 100 100 100 100 100 30 30
55

(c) 51, 52, 53, 54, 4-core, 2.5 sqmm copper cable Mtr 100 100 100 100 100 100 100 100 30 30
55

(d) 51, 52, 53, 54, 5-core, 2.5 sqmm copper cable Mtr 100 100 100 100 100 100 100 100 30 30
55

(e) 51, 52, 53, 54, 7-core, 2.5 sqmm copper cable Mtr 100 100 100 100 100 100 100 100 30 30
55

(f) 51, 52, 53, 54, 9-core, 2.5 sqmm copper cable Mtr 100 100 100 100 100 100 100 100 30 30
55

(g) 51, 52, 53, 54, 12-core, 2.5 sqmm copper cable Mtr 300 300 300 300 300 300 300 300 30 30
55

(h) 51, 52, 53, 54, 16-core, 2.5 sqmm copper cable Mtr 300 300 300 300 300 300 300 300 30 30
55

(i) 51, 52, 53, 54, 25-core, 2.5 sqmm copper cable Mtr 600 600 600 600 600 600 600 600 30 30
55

Cable Terminations

3.07 Supply and providing terminations conforming to Tech Spec for XLPE insulated,
LSZH and Fire Survival, armoured / unarmoured cables of sizes given below
including the cost of supplying, fixing and crimping copper lugs, double
compression flame proof brass glands, insulation tape etc. This also includes
making holes in gland plate complete as per specifications and as required

(a) 51, 52, 53, 54, 4-core, 400 sqmm Nos. 180 180 70 70 180 180 40 40 10 10
55

(b) 51, 52, 53, 54, 4-core, 300 sqmm Nos. 24 24 15 15 24 24 20 20 6 6


55

(c) 51, 52, 53, 54, 4-core, 240 sqmm Nos. 40 40 36 36 40 40 20 20 10 10


55

(d) 51, 52, 53, 54 4-core, 185 sqmm Nos. 20 20 10 10 20 20 30 30 0

(e) 51, 52, 53, 54 4-core, 150 sqmm Nos. 10 10 16 16 10 10 10 10 0

(f) 51, 52, 53, 54 4-core, 120 sqmm Nos. 14 14 16 16 14 14 12 12 0

(g) 51, 52, 53, 54, 4-core, 95 sqmm Nos. 18 18 30 30 18 18 20 20 4 4


55

(h) 51, 52, 53, 54 4-core, 70 sqmm Nos. 4 4 18 18 4 4 4 4 0

(i) 51, 52, 53, 54 4-core, 50 sqmm Nos. 12 12 4 4 12 12 30 30 0

(j) 51, 52, 53, 54 4-core, 35 sqmm Nos. 46 46 18 18 46 46 30 30 0

(k) 51, 52, 53, 54, 4-core, 25 sqmm Nos. 20 20 36 36 20 20 32 32 12 12


55

(l) 51, 52, 53, 54, 4-core, 16 sqmm Nos. 14 14 40 40 14 14 50 50 6 6


55

(m) 51, 52, 53, 54, 4-core, 10 sqmm Nos. 48 48 28 28 48 48 8 8 14 14


55

(n) 51, 52, 53, 55 4-core, 6 sqmm Nos. 20 20 36 36 20 20 0 0 18 18

(o) 52, 55 4-core, 4 sqmm Nos. 0 0 4 4 0 0 0 0 8 8

(p) 54 4-core, 2.5 sqmm Nos. 0 0 0 0 0 0 12 12 0

(q) 51, 52, 53, 54 3-core, 240 sqmm Nos. 12 12 12 12 12 12 12 12 0

(r) 51, 52, 53, 54 3-core, 185 sqmm Nos. 12 12 12 12 12 12 12 12 0

(s) 51, 52, 53, 54 3-core, 95sqmm Nos. 12 12 12 12 12 12 12 12 0

(t) 51, 52, 53, 54 3-core, 35 sqmm Nos. 12 6 18 12 12 12 6 18 12 6 18 0

(u) 51, 52, 53, 54, 3-core, 16 sqmm Nos. 12 12 12 12 12 12 12 12 12 12


55

(v) 51, 52, 53, 54, 3-core, 6 sqmm Nos. 12 12 12 12 12 12 12 12 12 12


55

(w) 51, 52, 53, 54, 2-core, 4 sqmm Nos. 12 12 12 12 12 12 12 12 12 12


55

(x) 51, 52, 53, 54, 2-core, 2.5 sqmm Nos. 12 12 12 12 12 12 12 12 12 12


55

3.08 Supply and providing terminations conforming to the Tech Spec for XLPE,
LSZH, armoured / unarmoured cables a of sizes given below including the cost
of supplying, fixing and crimping copper lugs, double compression flame proof
brass glands, insulation tape etc. This also includes making holes in gland plate
complete as per specifications and as required

(a) 51, 52, 53, 54, 4-core, 2.5 sqmm copper cable Nos. 10 10 10 10 10 10 10 10 4 4
55

(b) 51, 52, 53, 54, 3-core, 2.5 sqmm copper cable Nos. 10 10 10 10 10 10 10 10 4 4
55
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(c) 51, 52, 53, 54, 4-core, 2.5 sqmm copper cable Nos. 10 lN lS 10 10 lN lS 10 10 N el S 10 10 lN S 10 on
4 nel el S 4 ply
55 N

(d) 51, 52, 53, 54, 5-core, 2.5 sqmm copper cable Nos. 10 10 10 10 10 10 10 10 4 4
55

(e) 51, 52, 53, 54, 7-core, 2.5 sqmm copper cable Nos. 10 10 10 10 10 10 10 10 4 4
55

(f) 51, 52, 53, 54, 9-core, 2.5 sqmm copper cable Nos. 10 10 10 10 10 10 10 10 4 4
55

(g) 51, 52, 53, 54, 12-core, 2.5 sqmm copper cable Nos. 20 20 20 20 20 20 20 20 4 4
55

(h) 51, 52, 53, 54, 16-core, 2.5 sqmm copper cable Nos. 30 30 30 30 30 30 30 30 4 4
55

(i) 51, 52, 53, 54, 25-core, 2.5 sqmm copper cable Nos. 30 30 30 30 30 30 30 30 4 4
55

3.09 Supply installation testing and commissioning of following sizes of Hotdip


galvalized Wire mesh cable tray with Coupler ( Kitaster/Kitinox Type) and
Supports C41S/RCSN/CSN type Channel with all accessories for wall/ceiling
mounting/vertical mounting support at distance as required and not more than
1.5 meter with threaded rod , supporting bracket, clamps , hardware etc as
required including turns bends and T joints accessories. Cable tray should be
made of steel wires welded together and bent into final shape. - Hot dipped
galvanized after manufacture in accordance with the standard EN ISO 14 61: at
least 360 h of SST.Cable tray should be E30-90 Certified for fire resistance. The
cable tray of 450mm and above should be provided with 50mm Cu Earthing
strip both side and 25mm copper Strip upto 300mm size.
Makes:- Cablofil, Cooper, Tyco

(a) 51, 52, 53, 54, 50*150*50 mm Mtr 1595 500 8250 10345 1750 8250 5180 15180 1595 5180 4120 10895 1310 4120 10800 16230 110 110
55

(b) 52, 54 50*200*50mm Mtr RO 0 950 950 RO 0 150 150 0

(c) 51, 52, 53, 54, 50*300*50 mm Mtr 865 200 3300 4365 1950 3300 2072 7322 865 2072 1648 4585 410 1648 4320 6378 110 110
55

(d) 50*400*50 mm Mtr RO 0 0 RO 0 0 0 0

(e) 51, 52, 53, 54 50*450*50mm Mtr 1425 1425 1050 1050 1425 1425 650 650 0

(f) 50*500*50mm Mtr RO 0 0 0 RO 0 0 0 0

(g) 51, 52, 53, 54, 50*600*50mm Mtr 165 165 250 250 165 165 610 610 60 60
55

3.10 Supply installation testing and commissioning of following sizes of Hotdip


galvalized support for various application in tunnel. Model C41 S legrand or
equivalent type

(a) 51, 52, 53, 54 C41S 150 Mtr 0 600 9900 10500 9900 6216 16116 0 6216 4944 11160 0 4944 12960 17904 0

(b) 51, 52, 53, 54 C41S 200 Mtr 0 400 6600 7000 6600 4144 10744 0 4144 3296 7440 0 3296 8640 11936 0

(c) 51, 52, 53, 54 C41S 300 Mtr 0 200 3300 3500 3300 2072 5372 0 2072 1648 3720 0 1648 4320 5968 0

3.11 51, 52, 53, 54, Supply, design, fabrication and installation of fabricated GI steel work including kg 3000 0 0 3000 3000 0 0 3000 3000 0 500 3500 3000 0 0 3000 50 50
55 fixing arrangement etc. confiorming to Tech Spec, to support GI cable trays, bus
duct, light fixtures, conduit wirings, bracket, cable hangers & other electrical
works, preparation of shop drawings, including Tunnel Services etc. as required.
This includes all the fixing accessories like fasteners and all masonry works

3.12 Fire Sealants

51, 52, 53, 54, Supply and installation of Fire Resistant sealing thermal insulation material, 2 sqm 40 20 20 80 40 20 20 80 40 20 20 80 40 20 20 80 20 20
55 hours fire rated, for sealing all the openings of electrical cable shafts, cutouts in
concrete / brick wall / ceiling etc. as required

Lighting Bus Trunking

3.13 51, 52, 53, 54 Supply, installation, testing and commisioning of 63 A, Copper, Lighting Bus mtr 0 100 1650 1750 1650 1036 2686 0 1036 824 1860 0 824 2160 2984 0
Trunking System in easy detachable and conveninet assembly suitable for 3
Phase and Single Phase, 8 Wire, 50 Hz A C System with galvanised steel
enclosure, with tap off provision every 1 mtr. The Lighting Bus Trunking shall
be confirming to latest IEC Standards. It shall be with IP-55 Protection. The Bus
Trunking shall be complete with accessories like supporting clamps(modular) for
Installation at Tunnel, Fixing Clamps for lumanaries and cable & one run of Cu
earthing of 25x3 sqmm. etc as required. There should be arrangement of MCBs
single pole 6 Ampere for Lighting & Single Phase Tap Off Box and 32 Ampere 4
Pole MCB & 3 Phase 32 Ampere Tap Off Box for Maintenance Sockets at an
interval of 15 meters each.
Make: Legrand/Schneider/Siemens/GE

Bus Trunking

3.14 Supply, Installation, Testing & Commissioning of sandwich type bus trunking
with
1.5 mm thick sheet galavnised steel housing of following capacities, as per IEC
60439 suitable for 415Volt 3 Phase 4 wire (with 100 % Neutral) 50Hz AC supply
system of aluminum bus bars including elbows and bends etc., including end
feed units on both sides, including flexible jumpers on both sides, including
necessary modular supports and fire barriers as per specifications attached and
as per site conditions.
Make: Legrand/Schneider/Siemens/GE

(a) 51, 52, 53, 54 ASS-1(From Transformer to LT Panel 1)-5500 A, Al 3 Phase 4 Wire System mtr 50 50 50 50 50 50 50 50 0

(b) 51, 52, 53, 54 ASS-2(From Transformer to LT Panel 2)-5500 A, Al 3 Phase 4 Wire System mtr 50 50 50 50 50 50 50 50 0
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(c) 51, 52, 53, 54 From ASS-1(LT Panel) to ASS-2(LT Panel)-4000 A, Al 3 Phase 4 Wire System mtr 330 lN l S 330 350 lN l S 350 330 N el S 330 330 lN S 330 on nel el S 0 ply
N

(d) 51, 52, 53, 54 From DG-1 to ASS-1(LT Panel)-2000 A, Al 3 Phase 4 Wire System mtr 120 120 330 330 120 120 120 120 0

(e) 51, 52, 53, 54 From DG-2 to ASS-2(LT Panel)-2000 A, Al 3 Phase 4 Wire System mtr 310 310 120 120 310 310 310 310 0

(f) 51, 52, 53, 54 From LT Panel-1 to Tunnel Ventilation-800 A, Al 3 Phase 4 Wire System mtr 50 50 40 40 50 50 30 30 0

(g) 51, 52, 53, 54 From LT Panel-2 to Tunnel Ventilation-800 A, Al 3 Phase 4 Wire System mtr 50 50 40 40 50 50 110 110 0

(h) 51, 52, 53, 54 From LT Panel-1 to Emergency Fire Panel -800 A, Al 3 Phase 4 Wire System mtr 390 390 150 150 390 390 390 390 0

3.15 Supply, laying in position of corrugated DWC HDPE pipe confirming to IS 14930
(Part II) of following sizes for crossing of cables under the track, including filling
of water proof sealant around the cables to prevant in rush of sub-soil, water etc
and as per outline construction of E&M works.

200 mm dia mtr 50 50 50 50 50 50 50 50


a

160 mm dia mtr 200 200 200 200 200 200 200 200
b

100 mm dia mtr 200 200 200 200 200 200 200 200
c

Supply & Fixing of factory fabricated pre-galvanised sheet steel raceway in


2mm thickness for bottom & sides and 2mm/ 3mm thick top cover as called for
including necessary civil work such as chase cutting in screed, fixing/ jamming
the raceway, aligning & leveling and finishing with sand cement plaster &
chicken wire mesh:

40mm Depth

i 200mm x 40mm (3mm top cover) mtr 100 100 100 100 100 100 100 100

Floor Junction Box

Supply & Fixing of openable top cover floor junction boxes made from 2mm
thick pre-galvanised GI sheets for bottom & sides & 3mm thick GI top cover
complete with rubber gasketing beneath the top cover. The junction box shall be
suitable to accommodate GI floor raceways as specified above, necessary civil
work as described in earlier item to be included here too.

For 40mm Depth raceway

i 250 x 250 x 50 Nos. 40 40 40 40 40 40 40 40

4 Wiring and Accessories

Whether explicitly stated in the schedules below or not, the following must be
complied with:

(a) For supply and installation of conduits, cable trunking, raceway, flexible conduits
and wiring, relevant clauses of the Tech Spec must be complied

(b) All the items / parts mentioned in relevant clauses of the Technical Spec and
not specifically mentioned in BOQ shall be demmed to be included in the quoted
rates, unless specifically excluded

(c) Wiring accessories must conform to the Tech Spec

(d) In case of any contradiction between BOQ and Tech Spec, the most stringent
condition of the two shall apply

(e) All the items / parts mentioned in relevant clauses of the Technical Spec and
not specifically mentioned in BOQ shall be demmed to be included in the quoted
rates, unless specifically excluded

(f) Note: Fire survival cables shall be used for cables pertaining to Emergency
Lighting, signages, Emergency Trip system (ETS) and Emergency Stop Plunger
(ESP)

4.1 51, 52, 53, 54, Supply, installation, testing and commissioning of conduiting & wiring for primary Points 125 0 0 125 200 200 125 0 0 125 125 0 0 125 40 40
55 point (MCB to first point) for light / fan / exhaust fan / call bell point with (3x2.5 +
2x1.5) sq mm single core, copper conductor, LSZH wires, conforming to BS
7211 and Tech Spec, in cable trunking / conduits / flexible conduits / raceway
complete, as required, as per Tech Spec

4.2 51, 52, 53, 54, Supply, installation, testing and commissioning of conduiting & wiring for Points 800 0 0 800 1200 1200 800 0 0 800 700 0 0 700 200 200
55 secondary point for light / fan / exhaust fan / call bell point with (3x2.5 + 2x1.5)
sq mm single core, copper conductor, LSZH wires, conforming to BS 7211 and
Tech Spec, in cable trunking / conduits / flexible conduits / raceway complete,
as required, as per Tech Spec

4.3 51, 52, 53, 54 Supply, installation, testing and commissioning of conduiting & wiring for primary Points 0 5 35 40 20 65 85 0 5 35 40 0 70 70 140 0
point (MCB to first point) for light / fan / exhaust fan / call bell point with (3x2.5 +
2x1.5) sq mm single core, copper conductor, fire survival type wires conforming
to BS 7846 Category F2 meeting the criteria of withstanding 950 degree C for 3
hours at a rated voltage of 600/1000V and Tech Spec, in cable trunking /
conduits / flexible conduits / raceway complete, as required, as per Tech Spec

4.4 51, 52, 53, 54 Supply, installation, testing and commissioning of conduiting & wiring for Points 0 20 80 100 80 200 280 0 20 80 100 0 160 160 320 0
secondary point for light / fan / exhaust fan / call bell point with (3x2.5 + 2x1.5)
sq mm single core, copper conductor, fire survival type wires conforming to BS
7846 Category F2 meeting the criteria of withstanding 950 degree C for 3 hours
at a rated voltage of 600/1000V and of Tech Spec, in cable trunking / conduits /
flexible conduits / raceway complete, as required, as per Tech Spec

4.5 51, 52, 53, 54 Supply, installation, testing and commissioning of conduiting & wiring for primary Points 3 3 3 3 3 3 3 3 0
point (MCB to first point) for light / fan / exhaust fan / call bell point with 3 x 4
sqmm single core, copper conductor, LSZH wires, conforming to BS 7211 and
of Tech Spec, in cable trunking / conduits / flexible conduits / raceway complete,
as required, as per Tech Spec (for flood lighting)
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
4.6 51, 52, 53, 54 Supply, installation, testing and commissioning of conduiting & wiring for Points 3 lN lS 3 3 lN lS 3 3 N el S 3 3 lN S 3 on nel el S 0 ply
secondary point for light / fan / exhaust fan / call bell point with 3 x 4 sqmm N
single core, copper conductor, LSZH wires, conforming to BS 7211 and of Tech
Spec, in cable trunking / conduits / flexible conduits / raceway complete, as
required, as per Tech Spec (for flood lighting)

4.7 51, 52, 53, 54 Supply, installation, testing and commissioning of conduiting and wiring for Points 200 200 200 200 200 200 200 200 0
primary point controlled by 16A switch / 10A MCB (from DB to switchboard and
switchboard to first point) for light / fan / exhaust fan / call bell point with 3 x 2.5
sqmm single core, copper conductor, LSZH wires, conforming to BS 7211 and
of Tech Spec, in hot dipped galvanized welded steel conduit / flexible conduit,
recessed / surface mounted complete with accessories such as bends, junction
boxes, flexible conduit, pull boxes, saddles including cutting, chasing and
refiling etc. complete as required with modular type switch, front plate, box etc.
as per Tech Spec

4.8 51, 52, 53, 54 Supply, installation, testing and commissioning of conduiting and wiring for Points 150 150 150 150 150 150 150 150 0
primary point controlled by 16A switch / 10A MCB (from DB to switchboard and
switchboard to first point) for light / fan / exhaust fan / call bell point with 3 x 2.5
sqmm single core, copper conductor, Fire survival type wires, conforming to BS
7848 Category F2 meeting the criteria of withstanding 950 degree C for 3 hours
at a rated voltage of 600/1000V and Tech Spec, in hot dipped galvanized
welded steel conduit / flexible conduit, recessed / surface mounted complete
with accessories such as bends, junction boxes, flexible conduit, pull boxes,
saddles including cutting, chasing and refiling etc. complete as required with
modular type switch, front plate, box etc. as per Tech Spec

4.9 51, 52, 53, 54 Supply, installation, testing and commissioning of conduiting and wiring for Points 250 250 250 250 250 250 250 250 0
secondary / loop point for light / fan / exhaust fan / call bell point with (3x2.5) sq
mm single core, copper conductor, LSZH wires, conforming to BS 7211 and
Tech Spec, in hot dipped galvanized welded steel conduit / flexible conduit,
recessed / surface mounted complete with accessories such as bends, junction
boxes, flexible conduit, pull boxes, saddles including cutting, chasing and
refiling etc. complete as required as per Tech Spec

4.10 51, 52, 53, 54 Supply, installation, testing and commissioning of conduiting and wiring for Points 75 75 75 75 75 75 75 75 0
secondary / loop point for light / fan / exhaust fan / call bell point with (3x2.5) sq
mm single core, copper conductor, Fire survival type wires, conforming to BS
7848 Category F2 meeting the criteria of withstanding 950 degree C for 3 hours
at a rated voltage of 600/1000V and of Tech Spec, in hot dipped galvanized
welded steel conduit / flexible conduit, recessed / surface mounted complete
with accessories such as bends, junction boxes, flexible conduit, pull boxes,
saddles including cutting, chasing and refiling etc. complete as required with
modular type switch, front plate, box etc. as per Tech Spec

4.11 Supply, installation, testing and commissioning of wiring for tunnel light with 3
core, 4 sqmm armoured XLPE insulated Fire Survival Type Cables conforming
to BS 7846 Category F2 meeting the criteria of withstanding 950 degree C for 3
hours at a rated voltage of 600/1000V and of Tech Spec, for tunnel lights
including termination, saddles, earthing etc. complete as required

(a) 51, 52, 53, 54, Primary point Points 50 50 50 50 50 50 50 50 5 5


55

(b) 51, 52, 53, 54, Secondary point Points 50 50 50 50 50 50 50 50 10 10


55

4.12 51, 52, 53, 54, Supply and fixing of MS electro-galvanized box in recess / surface for power Nos. 30 30 30 30 30 30 30 30 60 60
55 points including providing and fixing of moulded plate type, universal 6 pin,
5/15A shrouded socket outlet (shuttured) as specified in Tech Spec with 16A
switch including connections, earthing and testing etc. as required

4.13 51, 52, 53, 54 Supplying and fixing of 3 phase, 5 pin, 32/63A industrial switch (as specified in Nos. 20 20 90 90 20 20 20 20 0
Tech Spec) controlled socket outlet with straight plugs in IP65 enclosure
including connections, earthing and testing etc. complete as required

4.14 51, 52, 53, 54 Supplying and fixing of 1 phase, 3 pin, 16A industrial switch (as specified in Nos. 30 30 30 30 30 30 30 30 0
Tech Spec) controlled socket outlet with straight plugs in IP65 enclosure for
tunnel including termination, earthing and testing etc. complete as required

4.15 51, 52, 53, 54 Supplying and fixing of 1 phase, 3 pin, 16A industrial switch (as specified in Nos. 50 50 50 50 50 50 50 50 0
Tech Spec) controlled socket outlet with straight plugs in IP65 enclosure for
tunnel including termination, earthing and testing etc. complete as required

4.16 51, 52, 53, 54 Supplying and fixing of 50mm x 200mm (w), rectangular, GI cable trunking Mtr 150 150 150 150 150 150 150 150 0
including pull boxes minimum at 500 mm distance as required at site, 2mm thick
as specified in Tech Spec, with one side having continuous hinged cover with
locking arrangement, earthing arrangement including provision of earthing strips
at joints etc. complete as required

4.17 51, 52, 53, 54 Supplying and fixing of 50mm x 50mm (w), rectangular, GI cable trunking Mtr 50 50 50 50 50 50 50 50 0
including pull boxes as required at site, 2mm thick as specified in Tech Spec,
with one side having continuous hinged cover with locking arrangement,
earthing arrangement including provision of earthing strips at joints etc.
complete as required

4.18 Supply and installation of following sizes of hot dipped galvanized welded steel
conduit in surface / recess with GI junction boxes, pull box, saddles including
cutting, chasing and refilling etc. complete as required
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
(a) 51, 52, 53, 54, 25mm dia conduit Mtr 500 lN l S 500 500 lN l S 500 500 N el S 500 500 lN S 500 on
50 nel el S 50 ply
55 N

(b) 51, 52, 53, 54, 32mm dia conduit Mtr 500 500 500 500 500 500 500 500 50 50
55

4.19 Supply and installation of following sizes of galvanized steel flexible conduit in
surface / recess with coupler, saddles including cutting, chasing and refiling etc.
complete as required

(a) 51, 52, 53, 54 25mm dia conduit Mtr 100 100 100 100 100 100 100 100 0

(b) 51, 52, 53, 54 32mm dia conduit Mtr 100 100 100 100 100 100 100 100 0

4.20 Supply, installation, testing and commissioning of conduiting and wiring for
advertisement point with 3-core x 4 sqmm armoured, XLPE insulated LSZH
copper conductor cable / wire as per BS 6724 and Tech Spec including saddles
etc. complete as required

(a) 51, 52, 53, 54 Primary point Points 20 0 0 20 20 20 20 0 0 20 20 0 0 20 0

(b) 51, 52, 53, 54 Secondary point Points 20 0 0 20 20 20 20 0 0 20 20 0 0 20 0

4.21 Supply, installation, testing and commissioning of conduiting & wiring for single
phase, 3 pin, 16A industrial socket outlet with 3 core x 6 sqmm armoured, XLPE
insulated, LSZH copper conductor cable as per BS 6724 and Tech Spec,
including saddles, eathing etc. complete as required

(a) 51, 52, 53, 54, Primary point Points 0 5 10 15 5 10 15 0 5 10 15 0 10 10 20 30 30


55

(b) 51, 52, 53, 54, Secondary point Points 0 5 10 15 10 20 30 0 5 10 15 0 10 10 20 30 30


55

4.22 Supply, installation, testing and commissioning of conduiting and wiring for
single phase 6 pin, 6/16A socket outlet with 3-core x 4-sqmm armoured XLPE
insulated, LSZH, copper conductor cable / wires as per BS 6724 and Tech
Spec, including saddles, earthing etc. complete as required

(a) 51, 52, 53, 54 Primary point Points 55 5 10 70 55 5 10 70 55 5 10 70 55 10 10 75 0

(b) 51, 52, 53, 54 Secondary point Points 55 5 10 70 55 5 10 70 55 5 10 70 55 10 10 75 0

4.23 51, 52, 53, 54 Supply, installation, testing and commissioning of conduiting and wiring for 3- Points 0 10 25 35 10 25 35 0 10 25 35 10 45 45 100 0
phase, 5-pin, 32/63A industrial socket outlet with 4-core x 6-sqmm armoured,
XLPE insulated, LSZH, copper conductor cable as per BS 6724 and Tech Spec,
including saddles, earthing etc. complete as required

4.24 Supply, installation, testing and commissioning of conduiting & wiring for single
phase 3-pin 16A industrial socket outlet at an interval of every 15 m (approx) in
tunnel with 3-core x 6-sqmm armoured, XLPE insulated, LSZH, copper
conductor cable as per BS 6724 and Tech Spec, including saddles, earthing
etc. complete as required (inside tunnel)

(a) 51, 52, 53, 54 Primary point Points 0 2 8 10 2 8 10 0 2 8 10 0 8 8 16 0

(b) 51, 52, 53, 54 Secondary point Points 0 2 8 10 2 8 10 0 2 8 10 0 8 8 16 0

4.25 51, 52, 53, 54, Supply, laying, testing and commissioning of 4-core x 4-sqmm armoured, XLPE Mtr 800 150 800 1750 800 150 800 1750 800 150 800 1750 400 800 800 2000 50 50
55 insulated, LSZH, copper conductor cable as per BS 6724 and Tech Spec
including terminations, saddles, earthing etc. complete as required

4.26 51, 52, 53, 54, Supply, laying, testing and commissioning of 2-core x 4-sqmm armoured, XLPE Mtr 50 50 100 200 50 50 100 200 50 50 100 200 50 50 100 200 50 50
55 insulated, LSZH, copper conductor cable as per BS 6724 and Tech Spec
including terminations, saddles, earthing etc. complete as required

5 Lighting

The lighting system specified herein must conform to the Tech Spec, in addition
to the description given in respective items of BOQ, whether explicitly specified
or not. In case of contradiction between Tech Spec and description in BOQ, the
most stringent of the condition will prevail.

All light fittings must comply with:

BS 4533: Specification for general requirements and tests", BS 6226,


"Photometric data for luminaires"

BS 2818: Ballasts for tubular fluorescent lamps

IEC 60081 / EN 60081: Double capped fluoroscent lamps - Performance


specifications

IEC 60928 / EN 60928: Auxillaries for lamps, AC supplied dielectric ballasts for
tubular fluoroscent lamps - General and safety requirements

IEC 60929 / EN 60929: Specification for AC supplied electronic ballasts for


tubular fluorescent lamps - Peformance requirements
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
BS 4017 for power factor correction capacitors and lN lS lN lS N el S lN S on nel el S ply
N

IEC 60529 / EN 60529: Specification for degrees of protection provided


by enclosures (IP code)

Colour temperature of lamps shsll be 40000K

The total harmonic content for the ballast / control gear should not exceed 10%.
Ballast shall withstand line transients as per IEC 61547 (immunity standards).
Ballast case temperature shall not exceed 25 degree C temperature rise over
45 degree C ambient. Ballast power factor shall be 95% of above. Ballast shall
provide continuous heating voltage to lamp cathodes and operate lamps on a
rapid start circuit unless otherwise noted.

All the items / parts mentioned in relevant clauses of the Tech Spec and not
specifically mentioned in BOQ shall be deemed to be included in the quoted
rates, unless specifically excluded

5.1 Supply, installation, testing and commissioning of the following luminaires


including all accessories like HF electronic ballast, holder & lamp etc. with
surface / recess mounting arrangement and all fixing accessories. All luminaires
and accessories shall be as per Tech Spec.

The Tubular Fluorescent lamps to be used must be High Efficacy (Lumen output
/ watt), High Efficiency, Excellent Colour Rendering Index, Long Life and other
technical parameters.

All wiring within the luminaries must be with Low Smoke ero Halogen Type
wires for Normal light fixtures and with Fire Survival Type wires for Emergency
light fixtures and signages, as per requirements of Tech Spec

A 5,152,535,455 Supply, installation, testing and commissioning of Mirror Optic, surface mounted No 0 0 0 89 89 12 0
Luminaries (Similar to Philips catalogue No.TCS 255/228 SK EBP with housing
made of white powder coated CRCA Sheet Steel, accomodating all electrical
accessories

B 51,525,354 Supply, installation, testing and commissioning of Mirror Optic, surface mounted No 656 656 492 492 450 450 496 496
Luminaries (Similar to Philips catalogue No.TCS 255/228 SK with housing made
of white powder coated CRCA Sheet Steel, accomodating all electrical
accessories

C 5,152,535,455 Supply, installation, testing and commissioning of Mirror Optic Surface mounted No 240 240 496 496 240 240 124 124 20 20
luminaries (Similar to Philips catalogue.No TCS 256/228 SK-AK with housing
made of white powder coated CRCA sheet steel, accommodating all electrical

D 5,152,535,455 Supply, installation, testing and commissioning of general purpose basic batten No 295 295 575 575 235 235 554 554 180 180
luminaries with Powder coated reflector (Similar to Philips catalogue. No.TMS
122/228W for 'TL'5 fluorescent lamp, with surface mounting arrangement on
wall

E 51,525,354 Supply, installation, testing and commissioning of general purpose basic batten No 0 0 0 0
luminaries with Powder coated reflector (Similar to Philips catalogue. No.TMS
122/228W for 'TL'5 fluorescent lamp, with surface mounting arrangement on
wall

F 51,525,354 Supply, installation, testing and commissioning of LED Tunnel Lighting No 108 5 82 113 360 83 52 443 190 51 41 241 150 42 108 192
Luminaire
with LM6 PDC Housing, system lumen output of 3378 lumens and system
efficacy of >85 Lm/Watt. The Luminaire should be supplied with a High
Efficiency glass

G 5,152,535,455 Supply, installation, testing and comissioning of Recessed Mounted Luminaire No 0 0 29 29 156 156 50 50
with
housing maded up of CRCA sheet, powder coated white, accomodating all
electrical accessories pre-wired up to a terminal block. The luminaire should be

H 51,525,354 Supply, installation, testing and comissioning of Recessed Mounted Luminaire No 0 0 10 10 10 10


with
housing maded up of CRCA sheet, powder coated white, accomodating all
electrical accessories pre-wired up to a terminal block. The luminaire should be

I 51,525,354 Supply, installation, testing and comissioning of Recessed Mounted Luminaire No 85 85 47 47 28 28 13 13


with
direct indirect diffused optics, with sturdy housing made from CRCA.The
luminaires should be suitable for 4x14 TL-5 lamps and supplied with 2 No 14 W
TL-

J 51,525,354 Supply, installation, testing and comissioning of Recessed Mounted Luminaire No 20 20 11 11 0 4 4


with
direct indirect diffused optics, with sturdy housing made from CRCA.The
luminaires should be suitable for 4x14 TL-5 lamps and supplied with 2 No 14 W
TL-

K 51,525,354 Supply, installation, testing and commissioning of Recessed Downlighters with No 64 64 18 18 12 12 0


high efficiency 145mm internal diameter reflector for 2x18 W PL-C Compact
Fluorescent Lamps and height of only 100mm. The luminaire should be
supplied

L 51,525,354 Supply, installation, testing and commissioning of efficient, low glare, No 40 40 0 28 28 28 28


recessed/surface mounted, cast aluminium luminaire suitable for High Pressure
Double Ended Metal Halide 70 W. Gear Tray housed in die cast aluminium

M 51,525,354 Supply, installation, testing and commissioning of surface/ suspension mounted No 150 150 150 150 150 150 150 150
waterproof luminaire suitable for 1x28 W TL-5 Lamp. Designed for applications
in demanding operating environments. TCW450 is dust, jet and shock proof with
all accessories mounted in a CRCA Gear Plate and Polycarbonate housing. The
luminaire conforms to Ingress Protection Classification of IP65 for protection
against dust and water. Luminaire shall be pre-wired and terminated at the
N 51,525,354 terminal installation,
Supply, block housed outside
testing andthe luminaire. Loop-in
commissioning of BulkLoop
Headoutluminaries
shall also similar
be No 10 10 65 65 42 42 38 38
provided
to Philips for ease of installation.
Catalogue No FXC 101, suitable for mounting on wall / ceiling having
(i) Single piece pressure die cast Aluminium housing, (ii) Wire Guard made of
powder coated MS, (iii) Heat resistant Glass cover. The luminaries must
conform to Ingress Protection Classification of IP 54 (for dust and Moisture
Protection ). The luminaries should be suitable for 1 x 9W CFL lamp and
O 51,525,354 supplied with 1No.
CRCA housing kept9W CFL lamp
in close and control
proximity accessories.
to the light fixture suitable for operation No 225 225 260 260 150 150 230 230
with T5 14-28W lamps. The battery pack used shall be suitable for providing up
to 3 hours of backup with 5 X 4Ah NiMH modules. The system shall be
designed to

H External Lighting

1 51, 52,53, 54, Supply, Installation, testing and Commioning of 60 W LED 3000 k IP 65 Pole No 5 5 8 8 5 5 5 5 3 3
55 Light (Equivalent to Ledra model of Legero make) including supply of 4.5 mtr
pole Complete with erection of poles with suitable mounting including the
digging & making concrete foundations as required. Cost should include supply
& instalation of 2 Nos. suiable length of 50 mm dia GI pipe bend to shape for
cable entry with all fixing arrangement & 16 SWG surface mounted MS painted
box complete with terminal block & one no. 10 Amp 10 KA SPMCB,
interconnections, hinged lockable door etc as required.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
2 51, 52,53, 54, Supply, Installation, Testing & Commissioning of Step light with 3 W LED 3000 No 10 lN lS 10 16 lN lS 16 10 N el S 10 10 lN S 10 on
6 nel el S 6 ply
55 K IP 65 (Equivalent to VOLANS model of Legero make) complete with housing, N
inbuilt driver, reflectors, all accessories etc as required

3 51, 52,53, 54, Supply, Installation, Testing & Commissioning of BOLLARD LUMINAIRE AS No 10 10 16 16 10 10 10 10 6 6
55 PER SAMPLE APPROVED, WITH ANODIC ALUMINUM REFLECTOR,
RADIATION RESISTANT SILICON RUBBER RING, Height: 800mm, LAMP:
LED 10 Watt,
PROTECTION IP55 (Equivalent to Halomax lighting model HL 2020) complete
with housing, inbuilt driver, reflectors, lamp, all accessories etc as required

I Lighting Control & Distribution System

The Distribution Boards specified herein, must conform to the Technical


Specifications, in addition to the description given in respective items of BOQ,
whether explicity specified or not. In case of contradiction between Technical
Specifications and description in BOQ, the most stringent of the specified
conditions will/ parts
All the items prevail
mentioned in relevant clauses of the Technical
Specifications and not specifically mentioned in BOQ shall be deemed to be
included in the quoted rates, unless specifically excluded.

DBs shall be provided with suitable timers & Contactors to meet out the
requirement of lighting/power as per technical specifications & BMS
compatability should be there

The size of the Panel / DBs shall be such that all the components / meters shall
be neatly placed for easy approach and maintainability

Supply, installation, testing and commissioning of front operated, indoor, front


access cubicle type, dead rear, wall / recess / surface mounted Distribution
Boards (conforming to specifications given in Tech Spec.) The Distribution
Boards must have ingress protection classification of IP54, current rating of
100A, and must be
The Distribution suitable
Boards to withstand
specified symmetrical
herein, fault current
must conform to the level of 10kA
Technical
for 1 second at 415V, with the configurations detailed below. Distribution boards
must be provided with electrolytic, high conductivity, TPN copper busbars as
specified in Tech Spec (with full sized Neutral busbar), gland plates at both
ends,
All theblanking plates
items / parts etc. as required.
mentioned All internal
in relevant clauses wiring
of the within the DIstribution
Technical
Boards must be with Copper Conductor, LSZH wires (conforming to BS 7211
Specifications
and Tech Spec) for Normal Lighting and Socket Distribution Boards and with
Fire Survival wires (conforming to BS 7848 and Tech Spec) for Emergency
Lighting Distribution Boards.
DBs shall be provided with suitable timers & Contactors to meet out the

The size of the Panel / DBs shall be such that all the components / meters shall
be

Supply, installation, testing and commissioning of front operated, indoor, front

1 51,525,354 TPN Distribution Boards No 2 2 6 6 4 4 4 4

Incoming

1 no.32A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary contacts
for

1 no.32A, TPN MCB

3 nos. 32A, DP RCCB (30mA sensitivity)

Outgoing

12 nos. 6/10/ 16A, SP MCB

Terminals blocks for power and control cables

Lighting Control Components

Supply, Installation, testing & commissioning of 1 Channel x20A Dali HF Ballast

Supply, Installation, testing & commissioning of 12 channel 20 amps DDRC1220

Supply, Installation, testing & commissioning of DIN Rail mount Network


Pwr

Interconnections of above with Cat 6 wire

2 51 TPN Distribution Boards No 2 2 0 0 0 0 0 0

Incoming

1 no.40A, 4P, Onload Manual Changeover Switch with 2 nos. auxiliary contacts
for

1 no.40A, TPN MCB

3 nos. 40A, DP RCCB (30mA sensitivity)

Outgoing

24 nos. 6/10/ 16A, SP MCB

Terminals blocks for power and control cables

Lighting Control Components

Supply, Installation, testing & commissioning of 1 Channel x20A Dali HF Ballast

Supply, Installation, testing & commissioning of 12 channel 20 amps DDRC1220

Supply, Installation, testing & commissioning of DIN Rail mount Network


Pwr
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Interconnections of above with Cat 6 wire lN lS lN lS N el S lN S on nel el S ply
N

3 51, 53, 54, 55 Supply, Installation, testing & commissioning of 10 Button Keypad Push type No 5 5 7 7 5 5 5 5 5 5
with Pattern lock programming including Supplying & Fixing 3"x3" GI Box

4 51, 53, 54, 55 Supply, Installation, testing & commissioning of Time clock DDTC001 module No 2 2 2 2 2 2 2 2 2 2
with inbuilt battery backup & support for 250 time events for switching, dimming

5 51, 53, 54, 55 Supply, Installation, testing & commissioning of DIN Rail mount Network No 2 2 2 2 2 2 2 2 2 2
Pwr Supply 15 V 1.5A DDNP1501 Power supply shall provide 15 V DC 1.5 A
Current

6 51, 53, 54, 55 Supply, Installation, testing & commissioning of Network Interface for No 2 2 3 3 2 2 2 2 2 2
Connection between Platform & Concourse Level

7 51, 53, 54, 55 Supply, Installation, testing & commissioning of GUI software for visualisation of No 0 0 0 0 0 0 0 0 0 0
Connected DALI Lamps & monitoring of Fault alarms like Lamp Failure, Ballast
Failure, Dimming Level / Status, Device Online/Offline status etc

8 51, 53, 54, 55 Supply, Installation, testing & commissioning of PC Interface Envision Gateway No 0 0 0 0 0 0 0 0 0 0
for GUI Visualisation software

9 51, 53, 54, 55 integration of Lighting Control System with BMS System (provided separately). No 1 1 1 1 1 1 1 1 1 1
Make Philips DDNG BACNET-1000

10 51, 53, 54, 55 Supply, Installation, Testing and Commissioning of RS232 PC node. Make No 1 1 1 1 1 1 1 1 1 1
Philips DTK622-RS232

11 51, 53, 54, 55 Supplying, laying, testing and commissioning of 4-pair Non-plenum Enhanced Mtr 600 600 900 900 600 600 600 600 600 600
Cat 6 unshielded twisted pair computer cable with 24 AWG in GI Conduit
Confirming to tender Specifications etc as required

Total

6 Earthing and Lightning Protection

The earthing and lightning protection system specified herein, must conform to
Tech Spec in addition to the description given in the respective items of BOQ,
whether explicitly specified or not. In case of contradiction between Tech Spec
and descriptions in BOQ, the most stringent of the condition will prevail.

All the items / parts mentioned in relevant clauses of the Tech Spec and not
specifically mentioned in BOQ shall be deemed to be included in the quoted
rates, unless specifically excluded.

6.01 Supply, laying, testing and commissioning at the site of copper strips / wires
(minimum 97% conductivity) of the following sizes (as specified in Tech Spec)
for provision of earthing system

(a) 51, 52, 53, 54, 50mm x 6 mm copper strip Mtr 2800 2800 2800 2800 2800 2800 2800 2800 500 500
55

(b) 51, 52, 53, 54, 32mm x 5mm copper strip Mtr 600 600 600 600 600 600 600 600 200 200
55

(c) 51, 52, 53, 54, 25mm x 3mm copper strip Mtr 400 400 400 400 400 400 400 400 10 10
55

d) 51, 52, 53, 54, 8 SWG / 4mm diameter copper wire Mtr 100 100 100 100 100 100 100 100 50 50
55

6.02 Supply, laying and testing of unarmoured, stranded copper conductor, low
smoke zero halogen, green coloured cables of following sizes, conforming to BS
7211 and Tech Spec, for earthing, including termination of the same by copper
lugs at both ends

(a) 51, 52, 53, 54, 1-core, 6-sqmm Mtr 50 50 50 50 50 50 50 50 20 20


55

(b) 51, 52, 53, 54, 1-core, 10-sqmm Mtr 50 50 50 50 50 50 50 50 20 20


55

(c) 51, 52, 53, 54, 1-core, 16-sqmm Mtr 50 50 50 50 50 50 50 50 20 20


55

(d) 51, 52, 53, 54, 1-core, 70-sqmm Mtr 100 100 100 100 100 100 100 100 20 20
55

(e) 51, 52, 53, 54, 1-core, 150-sqmm Mtr 50 50 50 50 50 50 50 50 20 20


55

6.03 51, 52, 53, 54, Supply and making of copper main earth connection / terminal of size 50mm x Nos. 20 20 20 20 20 20 20 20 20 20
55 10mm, 500mm mounted on 2 nos. SMC/DMC insulator for connection with
Principal Earth Terminal / Connection including copper nut-bolts, washers etc.
complete as per Tech Spec and drawings for protective earthing.

6.04 51, 52, 53, 54, Supply and making of copper main earth connection / terminal of size 50mm x Nos. 10 10 10 10 10 10 10 10 5 5
55 4mm, 500mm mounted on 2 nos. SMC/DMC insulated for connection with
Principal Earth Terminal / connection including copper but-bolts, washers etc.
complete as per Tech Spec and drawings for clean earthing.

6.05 51, 52, 53, 54, Supply and laying of copper air terminations of 25mm diameter, 600mm length, Nos. 10 10 10 10 10 10 10 10 5 5
55 copper tube having five prong at top, 3mm thick, 100mm diameter, copper base
plate with holes, making foundation and fixing hardware, as required and as per
Tech Spec and drawings
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
6.05 Supply and installation of 20mm diameter 3m long copper earth electrode as lN lS lN lS N el S lN S on nel el S ply
per IS 3043 in 450mm x 450mm RCC inspection chamber, RCC cover, N
complete with nut, bolts & washers for terminations, GI pipe sleeves as
required, and as per Tech Spec & drawings

(a) 51, 52, 53, 54, 20mm diameter 3000mm long copper earth electrode Nos. 10 10 10 10 10 10 10 10 5 5
55

6.09 Supplying and making of test joints with the following sizes of copper strip of
length 125mm with 4 nos. bolts, nuts and washers of brass, DMC support, as
required, and as per Tech Spec and drawings etc.

(a) 51, 52, 53, 54, 25mm x 3mm copper strip Nos. 20 20 20 20 20 20 20 20 5 5
55

6.10 Supply, laying and testing of braided flexible copper conductor cable of following
sizes including termination of the same using copper lugs at both ends

(a) 51, 52, 53, 54, 1-core, 70-sqmm Mtr 25 25 25 25 25 25 25 25 5 5


55

(b) 1-core,185-sqmm Mtr 25 25 25 25 25 25 25 25 5 5


100 100 100 100 100 100 100 100 30 30

(c) 1-core,400-sqmm Mtr 500 500 500 500 500 500 500 500 50 50

Earth Mat

6.11 51, 52, 53, 54, Supply, Instalation, testing & Commissioning of Earth Mat asper technical 2 2 2 2 2 2 2 2 2 2
55 specifications with following items

a Pure Electrolytic Grade Copper rods 20mm dia length 1.8mtr. - 54 Nos.

b Coupler Gun metal - 27 Nos

c Electrolytric Grade Bare Copper cable 95 sqmm stranded single core, for grid
formation with exothermic joints to Rod electrodes as per drawing - 150 mtrs.

d Heavy duty Pit cover 450x450mm CI covers - 10 Nos.

e 185 sq mm Electrolytic copper cable XLPE for risers from earth grid - 300 mtrs.

f Epoxy Resin Coated ,Tinned copper waterProtecting Sleeve - 10 Nos.

g Exothermic Welding Powder and accessories for Exothermic bonding of


Grid 95sqmm Cable to ROD and 185 sqmm cable to rod - 7-0 Nos.

h Low resistivity, Moisture retaining, water in soluble All Weather stable


Envoirnment friendly SOIL ENHENCEMENT MATERIAL "ASEM GB" with
resistivity below 0.5 ohm m to support the earth electrode and Grid cable - 104
Bags

i Bentonite Powder - 25000 Kgs

j A single pit of 60mx 15m x 3.5 mtr will be required to be dug for placing the
earth grid after treating the excavated soil - 3150 Cu mtrs

6.11 51, 52, 53, 54, Supply, Instalation, testing & Commissioning of Clean Earth Mat as per 1 1 1 1 1 1 1 1 Clean Earth mat missing.
55 technical specifications with following items

a Pure Electrolytic Grade Copper rods 13mm dia length 1.8mtr. - 54 Nos.

b Coupler Gun metal - 24 Nos

c Electrolytric Grade Bare Copper cable 95 sqmm stranded single core, for grid
formation with exothermic joints to Rod electrodes as per drawing - 150 mtrs.

d Heavy duty Pit cover 450x450mm CI covers - 10 Nos.

e 185 sq mm Electrolytic copper cable XLPE for risers from earth grid - 300 mtrs.

f Epoxy Resin Coated ,Tinned copper waterProtecting Sleeve - 10 Nos.

g Exothermic Welding Powder and accessories for Exothermic bonding of


Grid 95sqmm Cable to ROD and 185 sqmm cable to rod - 7-0 Nos.

h Low resistivity, Moisture retaining, water in soluble All Weather stable


Envoirnment friendly SOIL ENHENCEMENT MATERIAL "ASEM GB" with
resistivity below 0.5 ohm m to support the earth electrode and Grid cable - 104
Bags

i Bentonite Powder - 25000 Kgs

j A single pit of 60mx 15m x 3.5 mtr will be required to be dug for placing the
earth grid after treating the excavated soil - 3150 Cu mtrs

Lightning Protection
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
6.12 51, 52, 53, 54, Supply, Erection, Installation and Commissioning of ERICO Lightning Protection Set 1 lN lS 1 1 lN lS 1 1 N el S 1 1 lN S 1 on
2 nel el S 2 ply
55 System 3000 comprising of Dynasphere MK-IV SS Air Terminal, AL Mast 2 M N
with Base Plate welded together, Insulated 2 M FRP Mast, U-Bolts and 7 M Guy
Kit with accessories for providing support to withstand wind speed. The
Dynasphere Air Terminal should be Controlled Streamer Emission CSE Type
with Stainless Steel Semi Spherical shape to reduce the build up of sharp point
corona discharge under static field thunderstorm conditions. It should have no
power requirement for its operation and be based on controlled emission of
streamer technology and taking into account the intensification factor and effect
of e-field and collection volume modeling. The solution should be compliant to
UL-96 Lightning Protection Safety Standards. The FRP Mast should be with min
height of 2 mts and thickness of 4 mm with the Down conductor to pass through
centre of the FRP Mast.

The Aluminium Mast Light of suitable height 2 mtrs minimum along with fixing
arrangements including U-Bolts for connecting FRP Mast with AL Mast and 4 M
Guy Kit with accessories for withstanding wind speed.

6.13 51, 52, 53, 54, Supply, Instalation, Testing and comisioning of earthing material comprising Set 1 1 1 1 1 1 1 1 2 2
55 Maintenance free earth pits made of ground enhancing material(GEM) of
Required qty and copper bonded ground rods (3nos) of size 1/2" and 10 length
and one earth rod clamp including all fixing accessories as required.

6.14 51, 52, 53, 54, DOWN CONDUCTOR:Supply, Erection, Installation and Commissioning of the Mtr 50 50 50 50 50 50 50 50 50 50
55 ERICORE Down Conductor which is a Multi Layered stranded cable with
Maximum outer diameter of 36 mm, Stranded Copper Conductor of Cross
Sectional Area of maximum 55 sq. mm, Characteristics impedance of less than
12 ohms, Inductance of maximum 37 nH/m, Capacitance of 0.75 pF/m, Voltage
Withstand of maximum
250 kV, Resistance of 0.5 mΩ/m. The ERICORE Down Conductor should be
supplied with saddles and screws for fixing. The ERICORE Down Conductor
should be compliant to UL-96 Lightning Protection Safety Standards.

6.15 51, 52, 53, 54, TERMINATIONS OF DOWN CONDUCTOR: The ERICORE Down conductor Set 1 1 1 1 1 1 1 1 11 11
55 should come with Upper Termination (Model: ERICORE /UTKIT/A) for
connecting the down conductor to the Dynasphere Air terminal and Lower
Termination (Model: ERICORE/LTKIT/A) for connecting the down conductor to
Lightning Protection Earth Pit.

6.16 51, 52, 53, 54, LIGHTNING EVENT COUNTER: Supply, Erection, Installation and Set 1 1 1 1 1 1 1 1 1 1
55 Commissioning of Lightning Event Counter (Model: LEC-IV) for counting the
number of lightning strikes without any power supply. The Counter should be
mounted on the Down Conductor and the triggering impulse should be >= 1.5
KA for 8/20µs. The Lightning Event Counter should be robust, non-resettable
mechanical counter with IP65 rated enclosure suitable for external application.

Total

7 Diesel Generator Sets

The Diesel Generators specified herein must conform to the Tech Spec, in
addition to the description given in respective items of BOQ, whether explicitly
specified or not. In case of contradiction between Tech Spec and description in
BOQ, the most stringent of the conditions will prevail.

All the items / parts mentioned in relevant clauses of the Tech Spec and not
specifically mentioned in BOQ shall be deemed to be included in the quoted
rates, unless specifically excluded.

Notes:

(a) The Contractor shall be responsible for providing a complete workable DG set
system as per detailed Tech Spec including necessary interfacing with the other
contractors (BMS, civil works etc.)

(b) Engine shall include flywheel to suit direct / flexible coupling with guard, air
cleaner, blower / radiator fan, radiator, fuel pump, electronic governor, fuel filter,
lube oil filter & pump, battery charger, Genset Controller, isolator and logic
panel etc. as required, suitable for cold start, suitable for remote starting.

(c) Alternator shall be brushless, self excited, self regulated, drip proof, and
continuously rated at 0.8 pf suitable for 3-phase, 415V, 50Hz, 4-wire system,
class H insulation provided with static excitation unit, protection, microprocessor
/ software controlled annunciation and sef-diagnostic module and shall generally
complying to specification and relevant standards.

(d) DG set shall have overload capacity not less than 110% of rated capacity for 1
hour in every 12 hours.

(e) DG sets and sound proof enclosures (including the one for capacity more than
1000kVA) shall be fully compliant to the norms of CPCB for Noise and
Emissions.

(f) DG set in sound attenuated enclosure shall be mounted on a fabricated rigid


common base frame with resilient anti-vibration mounting pads to provide 90%
vibration efficiency. The associated civil foundation for the DG sets will be
provided by Civil Contractor, necessary interfacing for the same will be done by
the DG set / E&M Contractor.

(g) DG sets shall include all accessories, fittings, instruments, isolator panel, logic
panel etc. complete as per specifications and as required. DG set design
temperature shall be 50 degree C

(h) Genset Controller and Isolator Panel should preferably be located inside the
sound proof enclosure in a separate section. If they are to be located outside
the sound proof enclosure, a separate enclosure for the isolator panel is to be
constructed by the Contractor of the same material and finish (except the
Acoustic insulation) at no extra cost to BMRCL.

(i) DG set should be suitable for parallel operation as per the detailed Tech Spec

Logic Panel for parallel operation of the DG sets will be provided by the DG set /
E&M Contractor. Interfacing for accommodating the Logic Panel and control and
data cabling in the DG panel room will be done by the DG set / E&M Contractor.

(j) Detailed technical proposal for the DG sets, Genset controller, Logic Panel,
Isolator Panel and acoustic enclosure etc. are to be submitted to the Engineer-
in-charge for approval before start of manufacturing.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
lN lS lN lS N el S lN S on nel el S ply
N

7.1 51, 52, 53, 54 Supply, load, transport to site, receive and unload at site, store, unpack, Set 2 2 1 1 2 2 2 2 0
erection, testing and commissioning of DG set of 1250kVA capacity (at 40 0 0
degree C ambient temperature), with electronic governor as per specification.
Also the cost shall include the freight & insurance. DG to be of prime /
continuous duty application as per IS. Alternator to be provided with Class H
insulation & with cable termination box for LT cables. Alternator to be provided
with local isolator indoor / outdoor type for maintenance purpose. DG set
coupling to be with single bearing type, teethed gear coupling. The cost shall
also include Engine Control Panel (Type EGCP
/ Power Command Control) with RS 485 common port.

DG sets shall be suitable for auto synchronizing with auto load sharing and
remote monitoring & control arrangement compatible with the existing electrical
system.

DG set with Alternator with Integral Acoustic Enclosure shall include the
following components and accessories complete:

a. Residential type silencer

b. Anti-vibration mounts (as required)

c. Battery and charger dynamo (24V, 150AH minimum with leads)

d. 990 Ltrs MS Fuel tanks with float / limit switch indicator for low and high fuel
level. Required number of contacts to be provided for connecting the level limit
switch for indication in DG control panel

e. Fuel system consisting of Connect Fuel Pipe with MS "C" class pipe with flange
& gas welded joint & pipe fittings like valves & other accessories and breather
drain pipes if required to be provided.

h. Liasioning charges for obtaining approval from CEIG/HID for installing and
running DG sets

i. Liasioning charges for obtaining approval from Pollution Control Board

7.2 52 Supply, load, transport to site, receive and unload at site, store, unpack, Set 0 0 1 1 0 0 0 0 0 0 Due to syncronisation issue
erection, testing and commissioning of DG set of 1500kVA capacity (at 40 2 2 same rating of dg to be
degree C ambient temperature), with electronic governor as per specification. consider.
Also the cost shall include the freight & insurance. DG to be of prime /
continuous duty application as per IS. Alternator to be provided with Class H
insulation & with cable termination box for LT cables. Alternator to be provided
with local isolator indoor / outdoor type for maintenance purpose. DG set
coupling to be with single bearing type, teethed gear coupling. The cost shall
also include Engine Control Panel (Type EGCP
/ Power Command Control) with RS 485 common port.

DG sets shall be suitable for auto synchronizing with auto load sharing and
remote monitoring & control arrangement compatible with the existing electrical
system.

DG set with Alternator with Integral Acoustic Enclosure shall include the
following components and accessories complete:

a. Residential type silencer

b. Anti-vibration mounts (as required)

c. Battery and charger dynamo (24V, 150AH minimum with leads)

d. 990 Ltrs MS Fuel tanks with float / limit switch indicator for low and high fuel
level. Required number of contacts to be provided for connecting the level limit
switch for indication in DG control panel

e. Fuel system consisting of Connect Fuel Pipe with MS "C" class pipe with flange
& gas welded joint & pipe fittings like valves & other accessories and breather
drain pipes if required to be provided.

f. Liasioning charges for obtaining approval from CEIG/HID for installing and
running DG sets

g. Liasioning charges for obtaining approval from Pollution Control Board

7.2 55 Supply, load, transport to site, receive and unload at site, store, unpack, Set 0 0 0 0 0 0 0 0 1 1
erection, testing and commissioning of DG set of 750kVA capacity (at 40 degree
C ambient temperature), with electronic governor as per specification. Also the
cost shall include the freight & insurance. DG to be of prime / continuous duty
application as per IS. Alternator to be provided with Class H insulation & with
cable termination box for LT cables. Alternator to be provided with local isolator
indoor / outdoor type for maintenance purpose. DG set coupling to be with
single bearing type, teethed gear coupling. The cost shall also include Engine
Control Panel (Type EGCP
/ Power Command Control) with RS 485 common port.

DG sets shall be suitable for auto synchronizing with auto load sharing and
remote monitoring & control arrangement compatible with the existing electrical
system.

DG set with Alternator with Integral Acoustic Enclosure shall include the
following components and accessories complete:

a. Residential type silencer

b. Anti-vibration mounts (as required)

c. Battery and charger dynamo (24V, 150AH minimum with leads)

d. 990 Ltrs MS Fuel tanks with float / limit switch indicator for low and high fuel
level. Required number of contacts to be provided for connecting the level limit
switch for indication in DG control panel

e. Fuel system consisting of Connect Fuel Pipe with MS "C" class pipe with flange
& gas welded joint & pipe fittings like valves & other accessories and breather
drain pipes if required to be provided.

f. Liasioning charges for obtaining approval from CEIG/HID for installing and
running DG sets

g. Liasioning charges for obtaining approval from Pollution Control Board


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
7.3 Exhaust System lN lS lN lS N el S lN S on nel el S ply
N

7.3.1 Supply, installation of the following size of Class B MS piping for exhaust
system as per IS 3588 and IS 1239 Part 1 including providing silencer / muffler,
suitable bends, expansion joints (bellows), reducers, flexibles, flanges, fire fly
gaskets, hardware, glass wool and aluminium sheet cladding etc. complete as
per Tech Spec. The cost shall also include the following:

(i) Providing suitable flange at a reachable height for flue gas sampling as per
CPCB requirement.

(ii) Painting of exhaust pipe with two coats of primer and two coats of approved
enamel paint

(iii) Providing of 75mm thick Rockwool LBR mattress insulation (of 150 kg/m3
density) over the exhaust pipes of following diameter including cladding with
aluminium sheet of 24 SWG and covering from outside complete as required
suitable for DG exhaust pipe temperature upto 450 degree C etc.

(iv) Supply, fabrication and erection of steel structure, hardware for generator
exhaust piping & painting with two coats of primer and two coats of approved
enamel paint as per requirement and providing

Notes:

(a) The rate for the MS exhaust pipe should be inclusive of supply and fixing of
SS expansion joints (bellows) according to size of horizontal / vertical exhaust
pipes of DG sets as required at site (it shall not be payable separately)

(b) Measurement for MS Exhaust piping will be taken excluding the length of
Expansion Joints (SS Bellows)

(a) 51, 52, 53, 54, 250mm diameter (NB) MS ERW pipe 4.85mm Mtr 60 60 33 33 60 60 60 60 30 30
55

(b) 52 350mm diameter (NB) MS ERW pipe 6.30mm Mtr 0 0 45 45 0 0 0 0 0 0

7.4 51, 52, 53, 54, Supply, installation, testing and commissioning of intake / exhaust fans, Nos. 2 2 2 2 2 2 2 2 1 1
55 industrial type high performance, reduced turbulance, low sound level (less than
75 dBA), compact, direct drive Vane axial flow fan with attenuator, 1.6 cubic
meter per second (CMS) air flow capacity at 200 Pascal static pressure. The
casing shall be double flanged made of galvanized sheet steel and the impellor
having manually adjustable pitch blades made of aluminium. The motor shall be
totally enclosed Class F insulation to a minimum, IP55 protection, 3-phase,
50Hz, 4-pole, 1450rpm, with suitable starter. The fan shall be suitable for wall
mounting complete with bird guard and with all necessary accessories, starters
as required for DG room ventilation.

Similar to Kruger model TDA-V series

The system should be designed to provide suitable ventilaton of efficient air


circulation, to ensure that the temperature rise in the DG room with respect to
the ambient is less than 5 degree C.

Required openings with mounting frames and filters shall also be considered.

7.5.0 Supply, installation, testing and commissioning of Monoblock Pumps with


bronze impeller and with base frame complete for 1010KVA at site including
necessary civil work. The pump motor set shall be suitable for 415(+10%) volt,
50cycle/sec (+3%) 3 phase power supply. Pump performance characteristics
shall be as follows

a Water flow rate - 1300LPM

Head = 35Mtrs

Motor Rating= 20HP or as required

51, 53, 54, 55 Pump set as described above 4 4 2 2 4 4 4 4 2 2

b Water flow rate - 2200LPM

Head = 35Mtrs

Motor Rating= 30HP or as required

Pump set as described above 0 0 0 0 0 0 0 0

c Water flow rate - 900LPM

Head = 35Mtrs

Motor Rating= 20HP or as required

Pump set as described above 0 0 0 0 0

d Water flow rate - 1800LPM

Head = 35Mtrs
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Motor Rating= 30HP or as required lN lS lN lS N el S lN S on nel el S ply
N

52 Pump set as described above 0 0 2 2 0 0

Important Notes

Contractor /Vendor to check the pump head, discharge & its selection & confirm
its suitability or else suggest an alternate suitable model

7.5.1 Supply, installation, testing & commissioning of FRP included draught cooling
tower suitable for 1250KVA Dg Set. Cooling tower shall be shell type of 100TR
capacity with common basin and provision for individual CT fan and provision of
seperation of basin in case of CT failure. Cooling tower shall be complete with
sump, casing, distribution system, filling louvers, base frame, fan motor and
ladder etc. Motor shall be suitable for 415+10%, 50cyles/sec, 3 phase AC
supply system the major shall be TEFC, weather proof IP56. TP isolator
switches of suitable capacity in weather proof enclosure for each fan motor to
be provided near cooling tower for local isolation. The cooling towers complete
in all respect shall be suitable for:

Water recirculation for each DG Sets required:

a 51, 53, 54 1250KVA - 1300LPM 2 2 1 1 2 2 2 2 0


0 0

Heat rejection required 18degree F (10degree C)

(Necessary civil work including steel girders for foundation to be included)

7.5.2 52 Supply, installation, testing & commissioning of FRP included draught cooling
tower suitable for 1500KVADg Set. Cooling tower shall be shell type of 150TR
capacity with common basin and provision for individual CT fan and provision of
seperation of basin in case of CT failure. Cooling tower shall be complete with
sump, casing, distribution system, filling louvers, base frame, fan motor and
ladder etc. Motor shall be suitable for 415+10%, 50cyles/sec, 3 phase AC
supply system the major shall be TEFC, weather proof IP56. TP isolator
switches of suitable capacity in weather proof enclosure for each fan motor to
be provided near cooling tower for local isolation. The cooling towers complete
in all respect shall be suitable for:

Water recirculation for each DG Sets required:

a 1500KVA - 1800LPM 0 0 1 1 0 0 0 0 0
2 2

Heat rejection required 18degree F (10degree C)

(Necessary civil work including steel girders for foundation to be included)

Important Note:

Contractor/Vendor to check the selection & rating & confirm its suitabilityor else
suggest an alternate suitable model/selction

7.5.2 Supply, installation, testing & commissioning of FRP included draught cooling
tower suitable for 750KVA Dg Set. Cooling tower shall be shell type of 150TR
capacity with common basin and provision for individual CT fan and provision of
seperation of basin in case of CT failure. Cooling tower shall be complete with
sump, casing, distribution system, filling louvers, base frame, fan motor and
ladder etc. Motor shall be suitable for 415+10%, 50cyles/sec, 3 phase AC
supply system the major shall be TEFC, weather proof IP56. TP isolator
switches of suitable capacity in weather proof enclosure for each fan motor to
be provided near cooling tower for local isolation. The cooling towers complete
in all respect shall be suitable for:

Water recirculation for each DG Sets required:

a 750KVA - 900LPM 0 0 0 0 0 0 0 1 1

Heat rejection required 18degree F (10degree C)

(Necessary civil work including steel girders for foundation to be included)

Important Note:

Contractor/Vendor to check the selection & rating & confirm its suitabilityor else
suggest an alternate suitable model/selction

7.5.3 Providing & fixing in position the following MS "C" class pipe cut to required
lenghts and installed with all ER welded joints including providing and fixing in
position with necessary supports and fittings like elbows, tees and reducers,
sockets, clamps, painting etc as required

a 51, 53, 54 250mm (NB) MS ERW pipe 40 40 60 60 40 40 40 40 30 30

b 51, 53, 54 150mm (NB) MS ERW pipe 10 10 10 10 10 10 10 10 5 5


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
c 51, 53, 54 100mm (NB) MS ERW pipe 10 lN lS 10 10 lN lS 10 10 N el S 10 10 lN S 10 on
5 nel el S 5 ply
N

7.5.4 Supply, installation, testing & commissioning of Flexible connections including


118 flange, necessary hardware for water piping connnection to heat exchanger of
following pipe sizes

a 51, 53, 54 100mm dia 4 4 4 4 4 4 4 4 2 2

b 51, 53, 54 150mm dia 4 4 4 4 4 4 4 4 2 2

7.5.5 Providing and fixing in position the following `Check` valves(Non return) Dual
plate type with necessary hardwares

a 51, 53, 54 150 mm NB MS Valves 4 4 4 4 4 4 4 4 2 2

7.5.6 51, 53, 54 Providing and fixing in position the `industrial type` pressure guage with gun 6 6 6 6 6 6 6 6 3 3
metal valves

7.5.7 51, 53, 54, 55 Providing and fixing in position the Dial type thermo meter 6 6 6 6 6 6 6 6 3 3

7.5.8 Providing and fixing in position the required `Y` stainers with necessary
hardwares

a 51, 53, 54 150 mm dia 2 2 2 2 2 2 2 2 1 1

7.5.9 Providing and fixing in position the following `Butterfly` valves including
providing flanges and hardware as required

a 51, 53, 54, 55 100mm dia 2 2 2 2 2 2 2 2 1 1

b 51, 53, 54 150mm dia 2 2 2 2 2 2 2 2 1 1

7.5.10 Providing and fixing in position the following `Balancing` valves including
providing flanges and hardware as required

a 51, 53, 54 150mm dia valves 2 2 2 2 2 2 2 2 1 1

7.5.11 Providing & fixing in position one coat of 4mm thick `pyp kot` antirust pipe
protection including suitable adhesive, lap of 25mm on underground pipes etc.
complete as required at site of work

a 51, 53, 54 250mm (NB) MS ERW pipe 40 40 60 60 40 40 40 40 30 30

b 51, 53, 54 150mm (NB) MS ERW pipe 10 10 10 10 10 10 10 10 5 5

c 51, 53, 54, 55 100mm (NB) MS ERW pipe 10 10 10 10 10 10 10 10 5 5

Total

8 Uninterruptible Power Supply (UPS)

The UPS set specified herein must conform to the Tech Spec, in addition to the
description given in respective items of BOQ, whether explicitly specified or not.
In case of contradiction between Tech Spec and description in BOQ, the most
stringent of the condition will prevail.

All items / parts mentioned in relevant clauses of the Tech Spec and not
specifically mentioned in BOQ shall be deemed to be included in the quoted
rates, unless specifically excluded.

8.01 51, 52, 53, 54 Supply, Installation, testing and commissioning of 2x60 kVA True Online Double Set 2 2 2 2 2 2 2 2 0 UPS for S&T missing.
Conversion, 3-phase AC Input, 3-phase AC output. UPS system having an 3 3 3 3 3 3 3 3
ingress protection rating of IP33 (as per Tech Spec) each consisting of the
following:

125kVA 415V UPS

Galvanic Isolation Transformer at Inveter output with Delta Connection of


primary to separate input and output neutral

6-pulse Rectifier Modules to achieve less than 5% Input Current Distortion and
greater than 0.9 power factor at input
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
Completely microprocessor based with diagnostics capability lN lS lN lS N el S lN S on nel el S ply
N

Input phase Reversal Correction without switching to batteries

Maintenance bypass module

Set of SMF VRLA battery each having 30 minutes backup time at full load with
interconnecting cables, racks and standard accessories (2V Cells with 20 years
design life)

Other features as specified in of Tech Spec

Note: 1 Set = 2 nos. 125 kVA units with batteries with 2 hours back up for each
unit

8.02 51, 52, 53, 54 Design manufacture, supply installation testing and commissioning of 12.5 KVA Set 1 1 1 1 1 1 1 1 0
rating of Inverter system for a constant secondary voltage of 120 V DC/ 415 V
AC 240 volts at 50 Hz, on single phase, batteries backup of minimum 2 hour
duration including, batteries, battery chargers, rectifiers, transformers, controls,
protection and instruments etc complete as required.

8.01 55 Supply, Installation, testing and commissioning of 40 kVA True Online Double Set 1 1
Conversion, 3-phase AC Input, 3-phase AC output. UPS system having an
ingress protection rating of IP33 (as per Tech Spec) each consisting of the
following:

40kVA 415V UPS

Galvanic Isolation Transformer at Inveter output with Delta Connection of


primary to separate input and output neutral

6-pulse Rectifier Modules to achieve less than 5% Input Current Distortion and
greater than 0.9 power factor at input

Completely microprocessor based with diagnostics capability

Input phase Reversal Correction without switching to batteries

Maintenance bypass module

Set of SMF VRLA battery each having 30 minutes backup time at full load with
interconnecting cables, racks and standard accessories (2V Cells with 20 years
design life)

Other features as specified in of Tech Spec

Note: 1 Set = 1no. 405 kVA units with batteries with 2 hours back up for each
unit

8.02 55 Design manufacture, supply installation testing and commissioning of 1.2 KVA Set 1 1
rating of Inverter system for a constant secondary voltage of 120 V DC/ 415 V
AC 240 volts at 50 Hz, on single phase, batteries backup of minimum 2 hour
duration including, batteries, battery chargers, rectifiers, transformers, controls,
protection and instruments etc complete as required.

Total

9 Signage

1 Escape Signage : Photoluminescent rigid plastic, 2 mm thickness, Printed on


High Quality gloss paint with UV resistance,Material Used - Non Radioactive,
non-phosphorous, non toxic and lead free.

a 51, 52, 53, 54, Exit Route Signage Direction Indication - Size 60X20cm Nos. 104 104 100 100 90 90 46 46 8 8
55

b 51, 52, 53, 54, Exit Route Signage Both side Direction Indication - Size 60X20cm Nos. 67 67 50 50 57 57 34 34 4 4
55

c 51, 52, 53, 54, Exit Route Signage Direction Indication - Size 60X20cm Nos. 18 18 36 36 18 18 10 10 6 6
55

d 51, 52, 53, 54, Exit Route Signage Single side Direction Indication - Size 60X20cm Nos. 65 65 40 40 44 44 28 28 4 4
55

e 51, 52, 53, 54, Evacution Plan - Size 60X40cm Nos. 34 34 18 18 34 34 16 16 4 4


55

2 Emergency Signages

i 51, 52, 53, 54, Supply,Erection, Testing & Commissioning Conforms to SFS - EN-50172 either Nos 1 1 1 3 1 1 1 3 1 1 1 3 1 1 1 3 1 1
55 locally or remote access, Emergency Lighting Control Panel with two lighting
lines with maximum of 254 devices on both lines, up to 127 devices per line,
luminare line length 500/1000 Metres including Graphic Equaliser compatable to
BMS.The System shall work on Extra Low Voltage and shall be Addressable.

ii 51, 52, 53, 54, Supply,Erection, Testing & Commissioning ELS Panel Transformer 230 V with Nos 1 1 1 3 1 1 1 3 1 1 1 3 1 1 1 3 1 1
55 an output of 35V AC and is placed between mains and EL2 Control panel

iii 51, 52, 53, 54, Supply,Erection, Testing & Commissioning Key pad with an LCD to control, Nos 1 1 1 3 1 1 1 3 1 1 1 3 1 1 1 3 1 1
55 read and configure the Main ELS Control Panel.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
iv 51, 52, 53, 54, Supply,Erection, Testing & Commissioning Addressable Exit Signage along with Nos 64 l 4N l70
S 138 76 l44
N l70
S 190 54 N
70 el
70S 194 48 l 8N S
40 96 on
8 nel el S 8 ply
55 Base visible from 48 mtrs with integral battery capacity of 2 hrs and bicoloured N
LED status indicator. Available in Left, Right, Down signs

v 51, 52, 53, 54 Supply,Erection, Testing & Commissioning Configuration and programming Nos 1 1 1 3 1 1 1 3 1 1 1 3 1 1 1 3 1 1
software tool for use with Emergency lighting control panel. Software is used to
configure light levels,set up lighting areas and create input and output
parameters during set up and commissioning.

vi 51, 52, 53, 54 Supply,Erection, Testing & Commissioning Hand held Address Programmer Nos 1 1 1 3 1 1 1 3 1 1 1 3 1 1 1 3 1 1
designed to address the luminaires and exit signs. Designed to be light, robust
and easy to use it operates from a single PP3 size battery.

vii 51, 52, 53, 54, Supply,Erection, Testing & Commissioning 2 X 1.5 sq mm Shielded & Screened RMT 3000 200 4000 7200 3000 200 4000 7200 3000 4000 4000 11000 3000 200 1400 4600 1200 1200
55 Flexible (for Looping)fire survival type wires conforming to BS 7846 Category F2
meeting the criteria of withstanding 950 degree C for 3 hours at a rated voltage
of 600/1000V and Tech Spec, in cable trunking / conduits / flexible conduits /
raceway complete, as required, as per Tech Spec

viii 51, 52, 53, 54, Supply,Erection, Testing & Commissioning 4 X 1.5 Sq mm Flexible (for RMT 800 100 1200 2100 800 100 1200 2100 800 1200 1200 3200 600 100 400 1100 300 300
55 Keypad)fire survival type wires conforming to BS 7846 Category F2 meeting the
criteria of withstanding 950 degree C for 3 hours at a rated voltage of
600/1000V and Tech Spec, in cable trunking / conduits / flexible conduits /
raceway complete, as required, as per Tech Spec

Ix 51, 52, 53, 54, Supply,Erection, Testing & Commissioning 25 mm dia. GI Conduit RMT 3800 300 5200 9300 3800 300 5200 9300 3800 5200 5200 14200 3600 300 1800 5700 1500 1500
55

Total

A FIRE PANELS & SOFTWARE

1 51, 52, 53, 54, Supply, installation, testing & commissioning of microprocessor based intelligent Nos. 1 1 1 1 1 1 1 1 1 1
55 4, loop Networkable Analogue addressable type fire alarm control panel with 0 0 0 0 0 0 0 0
minimum 80 character LCD display. The panel should be equipped with
sufficient numbers of loop with 20 % spare capacity in each loop. Each panel
shall have a minimum capacity of 254 addressable devices, 254 user defined
zones, Alphanumeric keypad for the field programming and control of the fire
alarm system, panel shall maintain a history file of the last 1000 events, 240
volts AC power supply, automatic battery charger, 24 volts sealed lead acid
maintainence free batteries sufficient for 24 hours normal working and then be
capable of operating the system for 1/2 hours during an emergency conditions
as required. (BS EN/LPCB/UL Approved)

2 51, 52, 53, 54, Supply, installation, testing and commissioning of wall recess/surface mounting Nos. 2 2 2 2 2 2 2 2 2 2
55 microprocessor based networkable Active Repeater Panel which provide the 1 1 1 1 1 1 1 1 1 1
same displays as the main display on the fire alarm control panels with LCD
display. The Repeater Panel shall include the cost of all mounting accessories,
connectors etc. and shall be as per specifications complete as required.

Supply,Installation,Testing and Commissioning of Intelligent Addressable Fire Nos. 1 1 1 1 1 1 1 1 1 1


Alarm Control Panel (a maximum of 318 addressable points/modules per loop
with maximum 159 detectors +159 Devices ) with 6 Loops. 640 character LCD,
inbuilt QWERTY and numeric keypad to program and edit user databasse and
other functions. Control Panel shall include facility of Emergency 2-way
communication and suitable for interfacing with local SCADA. Control Panel
shall include NAC circuits, RS 485 port, fire/fault indicators, audio-visual signals,
battery, battery charger and Network card and complete in all respects. The
Panel shall have sealed maintenance free batteries capable of running for a
minimum of 12 hours without charging complete with battery charger, rectifier,
Loop cards, Keypad operation, L C D unit to indicate Fire / Fault Signal of
individual unit, built- in/ external printer to log all incoming data etc complete in
all respects. Panel shall provide interface to BMS on Backnet protocol.

Supply, Installing, Testing and Commissioning of Fire Alarm PC Station Nos. 1 1 1 1 1 1 1 1 1 1


consisting of Pentium 5 or better processor, 17"/19" colour LCD/LED/TFT
monitor, 4 GB RAM, 1TB Hard Disk, DVD Drive, USB Port, mouse, Windows
7 or better based Software, Graphic software including copy in CD ROM
complete as required. PC Work Station shall include complete Fire Alarm
Graphics Software including floor plans with location of detectors and other
devices. All Floors shall be available as drawing files with location of detectors
and devices complete with Loop number and other details as available on the
Software.

Supply, Installing, Testing and Commissioning of Passive type Sub Alarm Panel Nos. 5 5 12 12 5 5 5 5 2 2
for Fire Alarm System with sounder, LCD/LED alpha numeric 80 character
display with accept / reset buttons for alarm address of any sensor / field device.
The Sub Alarm Panel shall only provide field device address with room number.

Fire Man Box ( Size Suitable for A- 3 size drawings) Nos. 5 5 12 12 5 5 5 5 2 2

3 51, 52, 53, 54, Supply, installation, testing and commissioning of Mimic Panels complete Nos. 3 3 3 3 3 3 3 3 3
55 as required 5 5 12 12 5 5 5

4 51, 52, 53, 54, SOFTWARE WORKSTATION Nos 1 1 1 1 1 1 1 1 1 1


55 Supply, installation, testing and commissioning of the manufacturer provided 0 0 0 0 0 0 0 0 0 0
GUI Software Workstation to monitor & control the entire Fire Alarm Panel
network from a central location with necessary licenses. The Workstation shall
provide “Take Action” messages to first responders with specific, real-time
information about alarms at the site including notes about hazardous materials,
vulnerable building occupants, and management contacts, Upload/download
configuration files without taking the whole system off-line and shall have auto-
watch option to allow the operator to automatically scan individual buildings.
The software shall have the following minimum additional features:
- Graphics can be imported from all current graphics and CAD programs
- Password system with individual priviledge and password allocation Complete
with PC, Monitor keyboard and mouse as required

B DETECTORS & INITIATING DEVICES


UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
1 51, 52, 53, 54, Supply, installation, testing & commissioning of Intelligent addressable Nos. 269 lN l S 269 420 lN l S 420 249 N el S 249 272 lN S 272 on
49 nel el S 49 ply
55 multsensing detectors (Smoke + ROR + Fixed temp Heat) with fault isolator 50 50 50 50 50 50 50 50 N
either built in detector or in base. (BS EN/LPCB/UL Approved)

2 51, 52, 53, 54, Supply, installation, testing & commissioning of intelligent addressable Nos. 9 9 12 12 9 9 19 19 4 4
55 Manual Pulll Station for initiation of fire alarm complete as required and as per 35 35 90 90 35 35 35 35 8 8
specification (BS EN/LPCB/UL Approved)

Supply, Installing, Testing and Commissioning of Intelligent Addressable Nos. 20 20


Optical Smoke Detector with dual chamber complying with Codes as
mentioned above, solid state design, indicating lamp, rotary switch for
addressing and mounting base as per specifications. The detectors shall all be 380 380 775 775 380 380 380 380
Listed.

Supply, Installing, Testing and Commissioning of Intelligent Addressable Rate of Nos. 20 20


Rise cum Fixed Temperature Heat Detector with solid state design, rotary
switch and mounting base complying with Codes as mentioned above. The 50 50 50 50 50 50 50 50
detector shall all be Listed.

3 51, 52, 53, 54 Supply, installation, testing & commissioning of 68 Deg LHS Cable complete as Mtr 1646 100 1746 1700 1100 2800 824 1036 1860 2150 824 2974 0
required and as per specification (BS / EN approved)

4 51, 52, 53, 54 Supply, installation, testing & commissioning of 88 Deg LHS Cable complete as Mtr 1646 100 1746 1700 1100 2800 824 1036 1860 2150 824 2974 0
required and as per specification (BS / EN approved)

5 51, 52, 53, 54 Supply, installation, testing & commissioning Interface Unit for LHS Cable (BS / Mtr 8 8 14 14 10 10 14 14 0
EN approved)

6 51, 52, 53, 54, Supply, installation, testing & commissioning of Early Detection Vesda System Nos. 3 3 3 3 3 3 3 3 3 3
55 complete as required and as per specification (BS / EN approved) 0 0 0 0 0 0 0 0 0 0

7 51, 52, 53, 54, Supply, installation, testing & commissioning of Vesda System Tube Pipes Nos. 85 85 70 70 85 85 75 75 75 75
55 complete as required and as per specification 0 0 0 0 0 0 0 0 0 0

C MODULES & NOTIFICATION DEVICES

1 51, 52, 53, 54, Supply, installation, testing & commissioning of relay modules for driving Nos. 81 81 98 98 81 81 80 80 45 45
55 outputs like Fans, Dampers, AHU etc. complete as required and as per 115 115 165 165 115 115 115 115
specification (BS EN/LPCB/UL Approved).

2 51, 52, 53, 54, Supply, installation, testing & commissioning of addressable monitor modules to Nos. 45 45 55 55 45 45 33 33 25 25
55 give input to FAS like Sprinkler Flow switch complete as required and as per
specification. (BS EN/LPCB/UL Approved)

3 Supply, installation, testing & commissioning of response indicator complete as Nos. RO 0 RO 0 RO 0 RO 0 RO 0


required and as per specification. 50 50 70 70 50 50 50 50

Supply, Installing, Testing and Commissioning of Addressable type Fault Nos. 150 150 165 165 150 150 150 150
Isolator for isolating shorted, de-linked and loose circuits between two
successive fault isolators with automatic resetting arrangement to be
interconnecting to loop cable complete as required.

4 51, 52, 53, 54, Supply, installation, testing & commissioning of Hooter cum Strobe with Nos. 9 9 12 12 9 9 19 19 5 5
55 minimum 75DB output complete with control module, monitored power supply 50(Hoot 50(Hoote 96(Hooter) 96(Hooter 50(Hooter 50(Hoote 50(Hoo 50(Ho
unit of same make as panel. The strobes shall be synchronized for better er) r) +54Strobe) ) ) r) ter) oter)
evacuation, complete as required and as per specification. (BS EN/LPCB/UL +40Stro +40Strob +54Strobe +40Strob +40Strob +40Str +40Str
Approved) be) e) ) e) e) obe) obe)

D CABLES AND CONDUITS

1 SITC of cat 5 cable. Complete with termination and testing as per requirement. Rm. RO 0 RO 0 RO 0 RO 0 RO 0
as per specification 500 500 500 500 500 500 500 500 200 500
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
lN lS lN lS N el S lN S on nel el S ply
N
2 51, 52, 53, 54, SITC of 2 C X 1.5 Sq mm Fire Survival Cables (Armoured) (300/500V) with Rm. 4905 4905 8955 8955 4905 4905 6345 6345 1920 1920
55 twisted copper conductor having Glass Mica (Fire barrier) tape covered by an 21000 21000 31000 31000 21000 21000 21000 21000
extruded layer of Cross Linkable LSZH insulation as per BS 7629-1:2008. Outer
sheath should be LSZH with Anti-Rodent / Anti Termite properties (60 Minute
Fire Rating). Fire test as per BS 8434-2. Complete with termination and testing
as per requirement and as per specification.

3 SITC of 2 mm thick GI conduit complete with all required accessories like


bends, elbows, fixing clamps etc. of the following dia: as per specification

i 20 mm Rm. RO 0 RO 0 RO 0 RO 0 RO RO
7000 7000 8000 8000 7000 7000 7000 7000 600 600

ii 51, 52, 53, 54, 25 mm Rm. 150 150 150 150 150 150 150 150 100 100
55

Gas Release Panel- Addressable one loop Fire Alarm Gas Release panel, 80 Nos. 1 1 1 1 1 1 1 1 1 1
character LCD display, Inbuilt QWERTY keypad, Inbuilt NAC circuit for Gas
release application & UL listed for Gas Release application as well

VESDA Panel - Single /Multi zone, Active Laser / Blue ray Aspiration Detection Nos. 3 3 3 3 3 3 3 3 3 3
Unit. The unit should be UL/ FM / VDS/LPCB approved complete with bar graph
display, dual stage filter, instant fault finder, on-board 18,000 event log memory,
RS-232 port / RS-485 port / TCP-IP networking capability (Total Flooding)

VESDA Panel - Single /Multi zone, Active Laser / Blue ray Aspiration Detection Nos. 5 5 10 10 5 5 5 5 2 2
Unit. The unit should be UL/ FM / VDS/LPCB approved complete with bar graph
display, dual stage filter, instant fault finder, on-board 18,000 event log memory,
RS-232 port / RS-485 port / TCP-IP networking capability (Panel flooding)

Supply, Installation,Testing and Commissioning of Capillary Sampling tube of Set 150 150 250 250 150 150 150 150 50 50
1.5 Meters each.

Supply,Installation,Testing and Commissioning of CPVC 25 mm internal dia Rm. 300 300 350 350 300 300 300 300 75 75
air sampling pipe complete with all fittings to give an airtight piping and
including all clamping and hanging system complete.

Supplying and fixing of 20mm GI conduit along with accessories in surface/ Rm. 200 200 350 350 200 200 200 200 50 50
recess including painting in case of surface conduit, or cutting the wall and
making good the same in case of recessed conduit as required.

Total

13 BMS

1 Supply Instalaltion Testing Comissioning of PLC System.Duly wired IP 65


Control panel fabricated out of 2 mm C.R.C.A M.S sheet for housing above
hardware, Redundant 24V DC power supply, Interposing Relay Board for
DigitalOutput and fuseterminals.
The PLC System should be a rack based system .
The system design must ensure openness at information level but security at
control level to ensure safeguard against unauthorized entries and virus attacks.
The processor must be battery free using flash technology built in SD card.
The control system must be capable to operate between 0 to 60 Deg Celsius.
The control system must be able to withstand Mechanical shocks up to 30g,
Vibrations up to 3g, Electrical immunity radiated field up to 15V/m and
Electrostatic discharges up to 8KV.
The controller must support web server capability for remote diagnostics of
control system using Internet Explorer.
The controller must support IEC61131-3 multi tasking to optimize the overall
process performance.
It shall support 64 Event tasks, 1 Master task, 1 Fast task. Event task should
have the top most priority for execution.
The application memory shall be at least 2MB and shall be expandable to
128MB for storing the process events, recipes, data logging etc.
The controller must have diagnostic onboard status for run, stop,
communication, memory health, CPU error, IO err indication.
The controller must have native USB communication port for upload / download,
debugging and monitoring.
The controller shall have Modbus Serial, Can Open, Ethernet port for
connecting field devices, BMS Scada.
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
IOs Should be considered as per the equipment schedule (3 DI and 2 Do per lN lS lN lS N el S lN S on nel el S ply
ACB, Motor/Pump Starters, VCB and MCCB, 2 DI per Selector Switch, 2 DI and N
2DO per contactor and 1DI per Auxillary Contact for getting status of the
equipment) for the equipments (electrical system, Plumbing, Fire alarm system,
Fire Fighting system and Tunnel Ventilation and Underground Air conditioning
works. etc. as per the scope) For Analog Inputs of the sensors AI with 4-20mA
inputs should be considered• Shall be rack based and hot swappable • LED
indication to indicate status of field signals, card healthiness and communication
healthiness shall be provided. • Channel to channel , Channel to Bus and
Channel to ground isolation shall be provided for Analog IO. The I/O cards shall
be intelligent type and shall be connected to the terminals preferably by means
of prefab cables.
I/O cards shall have built in galvanic / optical isolation for input and output. The
Isolation shall be provided between each of the channels or groups in I/O rack.
Spare IO's Should be Cconsidered as per the specification

a 51, 52, 53, 54, PLC Panel for Station Lighting for South Side Lot 1 1 1 1 1 1 1 1 1 1

b 51, 52, 53, 54, PLC Panel for Tunnel Lighting for South Side Lot 1 1 1 1 1 1 1 1 1 1

c 51, 52, 53, 54, PLC Panel for Tunnel Emergency Evacuation Signage for South Side Lot 1 1 1 1 1 1 1 1 1 1

d 51, 52, 53, 54, PLC Panel for Station Lighting for North Side Lot 1 1 1 1 1 1 1 1 1 1

e 51, 52, 53, 54, PLC Panel for Tunnel Lighting for North Side Lot 1 1 1 1 1 1 1 1 1 1

f 51, 52, 53, 54, PLC Panel for Tunnel Emergency Evacuation Signage for North Side Lot 1 1 1 1 1 1 1 1 1 1

g 51, 52, 53, 54, PLC Panel for LV Distribution Panels Lot 1 1 1 1 1 1 1 1 1 1

h 51, 52, 53, 54, PLC Panel for Sump Pump Lot 1 1 1 1 1 1 1 1 1 1

i 51, 52, 53, 54, PLC Panel for Drainage System Lot 1 1 1 1 1 1 1 1 1 1

j 51, 52, 53, 54, PLC Panel for DG System Lot 1 1 1 1 1 1 1 1 1 1

k 51, 52, 53, 54, PLC Panel for Advertising System Lot 1 1 1 1 1 1 1 1 1 1

l 51, 52, 53, 54, IO Selection should be as per equipment Schedule Lot 1 1 1 1 1 1 1 1 1 1

2 Integration gateway for Third Party Communication Devices on Modbus


.Integration Gateway should be seamlessly integrated with the PLC System.

a 51, 52, 53, 54, Integration gateway for Fire Alarm Panel Lot 1 1 1 1 1 1 1 1 1 1

b 51, 52, 53, 54, Integration gateway for UPS Lot 1 1 1 1 1 1 1 1 1 1

c 51, 52, 53, 54, Integration gateway for Energy Meters Lot 1 1 1 1 1 1 1 1 1 1

3 51, 52, 53, 54, 8 Port Industrial Grade Ethernet Switch Lot 1 1 1 1 1 1 1 1 1 1

4 Supply Installation and Comissioning of Cable

a 51, 52, 53, 54, 3 Core 2.5 Sqmm FRLS Anneled Tinned Copper Armoured Cable for Power. Lot 1 1 1 1 1 1 1 1 1 1

b 51, 52, 53, 54, 2 Core 1.5 Sqmm FRLS Sheilded Anneled Tinned Copper Armoured Cable for Lot 1 1 1 1 1 1 1 1 1 1
55 Singnal.

c 51, 52, 53, 54, 3 Core 1.5 Sqmm FRLS Sheilded Anneled Tinned Copper Armoured Cable for Lot 1 1 1 1 1 1 1 1 1 1
55 Communication.

d 51, 52, 53, 54, Armored FRLS Cat6 Communication cable. Lot 1 1 1 1 1 1 1 1 1 1

5 51, 52, 53, 54, Supply Erection of Hot Dip Galvanized 2mm thickness Perforeted Cable Trays Lot 1 1 1 1 1 1 1 1 1 1
55 with cover

6 51, 52, 53, 54, ERECTION HARDWARE LIKE BASE FRAME OF PANEL, CABLE GLANDS, Lot 1 1 1 1 1 1 1 1 1 1
55 LUGS, FERRULES,MCBS , Tray Support Etc.

7 51, 52, 53, 54, Local Station Control for ITESS/XPESS as per tender Specs Lot 1 1 1 1 1 1 1 1 1 1
55

14 Sump Pump

1 51, 52, 53, 54 Supply, Installation, Testing & Commissioning of Submersible / Centrifugal non No. 2 0 0 2 2 0 0 2 2 0 0 2 2 2 0
clog type open impellar Sewage Sludge Transfer pump from Ejector sump to
main/municipal sewer line. Sludge transfer pump should be capable of solid
handling up to 25 mm as per manufacture specifications & other assosiated
works
& accessories of 5 H. P capacity etc as required as per site condition. Minimum
& maximum flow velocities allowed in discharge pipe should be 1.0 m/sec & 2.4
m/sec respecgtively. (1W+1 Std. by) (D. P. / Grund Foss / Wilo make)
2 51, 52, 53, 54 Supply, Installation, Testing & Commissioning of Submersible / Centrifugal No. 3 0 0 3 3 0 0 3 3 0 0 3 3 0 0 3 0
water pump for waste water Transfer pump from sumps to Municipal Storm
water / Sweage network. Sump pumps should be suitable for 480 LPM and 15
mtr head complete as per manufacture specifications & other assosiated works
& accessories etc as required as per site condition. (2W+1 Std. by) (D. P. /
Grund Foss / Wilo make)
UGC05-BOQ-STATIONS (E & M)
S. No. Area Code Description Unit Quantity
Dharavi BKC Vidyanagari Santacruz Mid Ventilation Shaft Unit
Rates in
INR
51 52 53 54 55
Station Tunne Tunne Total Station Tunne Tunne Total Station Tunnel Tunn Total Station Tunne Tunnel Total Stati Tun Tunn Total Sup ITC Remarks
lN lS lN lS N el S lN S on nel el S ply
N

3 51, 52, 53, 54 Supply, Installation, Testing & Commissioning of Submersible / Centrifugal No. 0 0 3 3 0 0 0 0 0 3 0 3 0 3 0 3 0
wateer pump for waste water Transfer pump for tunnel sump to Municipal Storm
water / Sweage network. Sump pumps should be suitable for 1080 LPM and 20
mtr head complete as per manufacture specifications & other assosiated works
& accessories etc as required as per site condition. (2W+1 Std. by) (D. P. /
Grund Foss / Wilo make)

Total

15 Liasioning

1 51, 52, 53, 54, Liasioning for taking required license (s) for Electrical Instalation covered under Job 1 0 0 1 1 0 0 1 1 0 0 1 1 1 1 1
55 this contract from Local / Govt. bodies/Authorities and fire clearance from local
fire authorities etc as required. Statutory fees payble to authorities will only be
reimbursed to the contactor.

Total