MUMBAI METRO RAIL CORPORATION LTD.

UPS RATING CALCULATION PANEL WISE


VA TOTAL QTY. OF 100% VA TOTAL VA
ADVANCE ASSUMUPTION
S.NO. PANEL NAME ACCESSORIES (CONSUPTION) EQUIPMENT (CONSUPTION) (ASSUMED)
1 MDB-1 CLOSING COIL 200 4 800 480 60% LOAD IN RUNNING
SHUNT COIL 200 4 800 480 60% LOAD IN RUNNING
SPRING CHARGING 300 4 1200 720 60% LOAD IN RUNNING
MOTOR
INDICATING LIGHT 4 33 132 79.2 60% LOAD IN RUNNING
AUX. RELAY 5 4 20 12 60% LOAD IN RUNNING
AUX. CONTACTOR 9 4 36 21.6 60% LOAD IN RUNNING
TOTAL VA 2988
TOTAL ASSUMED LOAD RUNNING 1792.8
APROX. TOTAL BURDAN (IN kVA) OF UPS 1.7928

2 MDB-2 CLOSING COIL 200 5 1000 600 60% LOAD IN RUNNING


SHUNT COIL 200 5 1000 600 60% LOAD IN RUNNING
SPRING CHARGING 300 5 1500 900 60% LOAD IN RUNNING
MOTOR
INDICATING LIGHT 4 36 144 86.4 60% LOAD IN RUNNING
AUX. RELAY 5 5 25 15 60% LOAD IN RUNNING
AUX. CONTACTOR 9 5 45 27 60% LOAD IN RUNNING
TOTAL VA 3714
TOTAL ASSUMED LOAD RUNNING 2228.4
APROX. TOTAL BURDAN (IN kVA) OF UPS 2.2284

3 EMDB-1 CLOSING COIL 200 2 400 240 60% LOAD IN RUNNING


SHUNT COIL 200 2 400 240 60% LOAD IN RUNNING
SPRING CHARGING 300 2 600 360 60% LOAD IN RUNNING
MOTOR
INDICATING LIGHT 4 54 216 129.6 60% LOAD IN RUNNING
AUX. RELAY 5 2 10 6 60% LOAD IN RUNNING
AUX. CONTACTOR 9 2 18 10.8 60% LOAD IN RUNNING
TOTAL VA 1644
TOTAL ASSUMED LOAD RUNNING 986.4
APROX. TOTAL BURDAN (IN kVA) OF UPS 0.9864

4 EMDB-2 CLOSING COIL 200 2 400 240 60% LOAD IN RUNNING


SHUNT COIL 200 2 400 240 60% LOAD IN RUNNING
SPRING CHARGING 300 2 600 360 60% LOAD IN RUNNING
MOTOR
INDICATING LIGHT 4 57 228 136.8 60% LOAD IN RUNNING
AUX. RELAY 5 2 10 6 60% LOAD IN RUNNING
AUX. CONTACTOR 9 2 18 10.8 60% LOAD IN RUNNING
TOTAL VA 1656
TOTAL ASSUMED LOAD RUNNING 993.6

Page 1 of 2
APROX. TOTAL BURDAN (IN kVA) OF UPS 0.9936

Page 2 of 2