You are on page 1of 1

1.

ALL ELECTRICAL WORKS HEREIN SHALL BE EXECUTED IN ACCORDANCE WITH THE PROVISIONS OF
THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODES, REQUIREMENTS OF THE LOCAL POWER
COMPANY, RULES AND REGULATION OF THE LOCAL ENFORCING AUTHORITY.

2. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE BY EXPERIENCED WORKMEN UNDER THE DIRECT
SUPERVISION BY A DULY LICENSED ELECTRICAL ENGINEER.

3. THE CONTRACTOR SHALL VERIFY THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION
TO POWER AND COMMUNIOCATION SUPPLY.
4. THE TYPE OF POWER TO BE USED WILL BE 230 V AC, TWO PHASE, THREE WIRE PLUS GROUND, 60
HERTZ.
SERVICE ENTRANCE
5. THE MINIMUM SIZE OF WIRE SHALL BE 3.50 mm THHN/THWN AND CONDUIT SHALL BE 15mm
ØVRSC AND 20 mm Ø PVC.

6. ALLL MATERIALS USED SHALL BE NEW AND OF THE APPROVED TYPE FOR BOTH LOCATION AND
PURPOSE.

7. POLYVINYL CHLORIDE (PVC) SHALL BE USED FOR EMBEDDED WIRING AND RIGID STEEL (RSC) FOR 60 A
EXPOSED WIRING.
20A 20A
8. GROUND FAULT CIRCUIT INTERCEPTOR WAS PROVIDED WITH WEATHER PROOF OUTLETS. L.O. ckt 1 ckt 2 L.O
20A 20A
9. ALL WIRES USED SHALL BE COPPPER AND THERMOPLASTIC INSULATED TYPE "THHN/THWN", THE
MINIMUM SIZE FOR POWER AND LIGHTING WAS 3.50 mm AND MANUFACTURER BY PHELPS DODGE. C.O. ckt 3 ckt 4 C.O.
30A 30A
10. ALL OUTLET BOXES SHALL BE GALVANIZED GAUGE NO. 16, DEEP TYPE WITH FACTORY KNOCKOUT. REF ckt 5 ckt 6 REF
30A 30A
11. ALL ELECTRICAL PANEL BOARD AND CIRCUIT BREAKER SHALLL BE "SQUARE - D". SPARE ckt 7 ckt 8 SPARE
12. ALL MOUNTING HEIGHTS WERE SUBJECTED TO ARCHITECTS APPROVAL INSTALLATION.

MOUNTING HEIGHTS:
PANEL BOARD 1.830 m FROM TOP OF PANEL FINISH FLOOR LINE GROUND

CONVENIENCE OUTLET 0.305 m FROM CENTER OF DEVICE TO FINISH FLOOR LINE

WALL SWITCH 1.372 m FROM CENTER OF DEVICE TO FINISH FLOOR LINE

CONVENIENCE OUTLET 1.400 m FROM CENTER OF DEVICE TO FINISH FLOOR LINE


AT T&B

E GENERAL SPECIFICATIONS E GROUND FLOOR POWER LINE DIAGRAM


1 10 2 10

ENTRACE SERVICE

M KILOWATT HOUR METER

CKT NO. NO. OF OUTLET


WATTS VOLTAGE COMPUTED BREAKER SIZE OF WIRE CONDUIT SIZE PANEL BOARD
AMPERE RATING
LO CO OTHERS
DUPLEX CONVENIENT
1 11 220 230 1.04 20 AT 3.5 mm2 THW 3 OUTLET
4" DIA. PVC CONDUIT

2 15 300 230 1.30 20 AT 3.5 mm2 THW 3


4" DIA. PVC CONDUIT
REFRIGERATOR OUTLET
3 7 230 2.60 3 REF
600 20 AT 3.5 mm2 THW 4" DIA. PVC CONDUIT

9 800 3.50 3
4 230 20 AT 3.5 mm2 THW 4" DIA. PVC CONDUIT RANGE OUTLET
RANGE
5 REF 1000 230 4.35 30 AT 5.5 mm2 THW 1" DIA. PVC CONDUIT

6 1000 230 4.35 30 AT 5.5 mm2 THW 1" DIA. PVC CONDUIT AIR CONDITIONING UNIT
REF
ACU OUTLET
7 SPARE 1000 230 4.35 30 AT 5.5 mm2 THW 1" DIA. PVC CONDUIT

8 SPARE 1000 230 4.35 30 AT 5.5 mm2 THW 1" DIA. PVC CONDUIT
LIGHTING OUTLET

IE = 11.31 X 85% DF =9.61 AMP


PROVIDE 60A, 250 VOLTS CIRCUIT BREAKER
5920 25.84 AMP SERVICE ENTRANCE:
CIRCUIT BREAKER
USE 2-14mm²THW CONDUCTOR, with
1"Ø RIGID STEEL CONDUIT 5 WATTS PINLIGHT, COOL WHITE

S1 SINGLE POLE SWITCH

S2 TWO - GANG SWITCH

S3W THREE WAY SWITCH

E GROUND FLOOR SCHEDULE OF LOADS AND COMPUTATION


3 10
E LEGENDS AND SYMBOLS
4 10

PREPARED FROM THE OFFICE OF : R.A. 9266 PROFESSIONAL ELECTRICAL ENGINEER : OWNER : PROJECT TITLE : SHEET CONTENTS : REVISIONS : SHEET NO . :

DRAWING SPECIFICATIONS DULY SIGNED, SYMBOL DESCRIPTION DATE


STAMPED OR SEALED AS INSTRUMENT OF SERVICE,
SCHEDULE OF LOADS AND COMPUTATION
E
ARE INTELLECTUAL PROPERTIES AND DOCUMENTS
OF THE ARCHITECT WHETHER THE OBJECT FOR WHICH
THEY ARE MADE IS EXECUTED FOR ANY PERSON
POWER LINE RISER DIAGRAM
# 179 Alejo St. Poblacion East, Asingan, Pangasinan WITHOUT THE CONSENT OF THE ARCHITECT OR GENERAL SPECIFICATIONS
olidoarki@gmail.com.

1 2
AUTHOR OF SAID DOCUMENTS, TO DUPLICATE OR TO
MAKE COPIES OF SAID DOCUMENTS FOR USE
LEGEND AND SYMBOLS
PRC. NO. : VALIDITY.
IN THE REPETITION OF AND FOR OTHER PROJECTS OR
BUILDING PTR NO. : DATE ISSUED :
WHETHER PARTLY OR IN WHOLE. ADDRESS : ADDRESS :
TIN :

You might also like