GENERAL NOTES

ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF
THE LATEST APPROVED EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE LAWS AND
ORDINANCES OF THE LOCAL CODE ENFORCING AUTHORITIES AND REQUIREMENTS OF THE LOCAL
POWER AND TELEPHONE COMPANY.
1. SERVICE POWER SUPPLY TO THE BUILDING SHALL BE 230V, 2-PHASE, 3-WIRES, 60HZ,
SYSTEM.
2. WIRING METHOD SHALL BE DONE IN IMC/EMT PIPE FOR LIGHTING, POWER AND TELEPHONE
SYSTEM.
3. SMALLEST BRANCH CIRCUIT WIRE SHALL BE 3.5 SQMM THHN FOR POWER AND LIGHTING
SYSTEM. AND RACEWAY 15 MM∅ TRADE SIZE CONDUIT, WIRES ARE INSULATED FOR
600 VOLTS.
4. ALL BRANCH CIRCUITS SHALL BE INSTALLED AS INDICATED IN THE PLAN. INDIVIDUAL BRANCH
CIRCUIT HOMERUNS ARE COMBINED IN THE SAME RACEWAY.
5. WHENEVER NECESSARY, PULL BOX OF PROPER SIZE AND DIMENSIONS SHALL BE PROVIDED
ALTHOUGH NOT INDICATED IN THE PLAN.
6. ALL JUNCTION AND PULLBOXES SHALL BE WITH METAL PLATE COVERS.

7. ALL FLOURESCENT LAMP SHALL BE PRE-HEAT TYPE, WITH HIGH POWER FACTOR
BALLAST, CAPACITOR AND SPRING LOADED LAMP HOLDERS.
8. THE MATERIALS USE SHALL BE NEW AND APPROVED TYPE FOR THE LOCATION
AND PURPOSE.
9. ALL WIRES AND CABLES SHALL BE COLOR CODED AS FOLLOWS:
PHASE A RED
PHASE B YELLOW
PHASE C BLUE
GROUND GREEN

10. MOUNTING HEIGHTS NOT SHOWN ON SCHEDULE SHALL BE AS FOLLOWS:


LIGHT CONTROLLED SWITCHES 1.40M. ABOVE FLR. FINISH @ CENTER M
DUPLEX CONVINIENCE OUTLET 0.30M. ABOVE FLR. FINISH @ CENTER
TELEPHONE OUTLET 0.30M. ABOVE FLR. FINISH @ CENTER
PANELBOARD 1.40M. ABOVE FLR. FINISH @ CENTER
UNLESS OTHERWISE INDICATED BY THE 3-14sqmm + 1-8.0sqmm THHN WIRE IN 32mm ∅ IMC PIPE
FIELD CONDITION
11. THE ELECTRICAL CONTRACTOR SHALL SECURE ALL WIRING PERMITS AND ALL FEES 3P, 80 AMP, 400 V
REQUIRED FOR THE WORK AND SHALL FURNISH THE OWNER THROUGH THE ENGINEERS.
FINAL CERTIFICATES OF ELECTRICAL INSPECTION AND APPROVAL FROM PROPER GOVERNMENT

12. THE ELECTRICAL CONTRACTOR REFER TO ARCHITECTURAL DRAWING FOR THE W&D.1 W&D.2
1 30 30 2
EXACT LOCATION AND MOUNTING HEIGHT OF ALL VISIBLE WIRING DEVICES, FIXTURES
AND THE LIKES. W&D.3 3 30 30 4 W&D.4
THIS SITE
13. ALL ELECTRICAL WORKS HEREIN SHALL BE UNDER THE DIRECT AND IMMEDIATE
W&D.5 5 30 30 6 W&D.6
SUPERVISION OF A DULY QUALIFIED LICENSED ELECTRICAL ENGINEER OR MASTER ELECTRICIAN.
AUTHORITIES FOR COMPLETE WORK. ACU 7 30 20 8 C.O.

W&D.7 9 30 20 10 L.O.

L.O. 11 20 20 12 TS SIGNAGE

TRANSFER FAN 13 20 20 14 SPARE

N 8.0sqmm SOLID COPPER GRD. BUS

01 LOCATION MAP
EE.01 SCALE: NTS

DESIGNER/CONSULTANT ENGINEER PROJECT TITLE OWNER SHEET CONTENTS SHEET NO.

FULL SERVICE LAUNDROMAT


EUGENE ROA ESPINUEVA JR. AS SHOWN EE-01
TEDD BUILDZ REG. NO.: T.I.N.:

DATE:
UNIT LL153 AYALA MALLS CIRCUIT, HIPPODROMO, MAKATI, METRO MANILA 1207
PTR NO.:

PLACE: DRAWN BY:JULIUS TEDD PEREZ DATE: SEPT. 18, 2023 CHECK BY: MARK DATE