SCHEDULE OF LOAD SPECIFICATION

The electrical installation shall be done in


accordance with the approved plans and under the
ckt # Load Description Qtyckt VoltageTotalVA cktAmpereckt Breaker size ofwire size ofconduit direct supervision and control of a licensed
(V) (A) (AT) (mm2 ) (mm Ø) professional electrical engineer or master electrician.
1 Light load 7 230 700 3.04 15 2 - 2.0 13 All electrical works and materials shall conform to
the provisions of the latest edition of Philippine or
2 Light load 5 230 500 2.17 15 2 - 2.0 13 the national electrical code.
3 Light load 6 230 600 2.61 15 2 - 2.0 13 The electrical wiring shall be installed thru mold
flex coillable PVC electrical conduit, fittings and
4 Light load 7 230 700 3.04 15 2 - 2.0 13 appurtenances that conform with ISO dimensions.
5 Small Appliance 12 230 2160 9.39 20 2 - 3.5 13 The type of appurtenances to be supplied to the building
shall be 220V AC single phase.
6 Small Appliance 12 230 2160 9.39 20 2 - 3.5 13
There shall be only one service drop from the nearest
7 Refregerator 2 230 350 1.52 20 2 - 3.5 13 ESAMELCO pole to the proposed building. Electric wires
fo light and power shall not be smaller than 13.5 sq.mm.
8 Small Appliance 12 230 2160 9.39 20 2 - 3.5 13 600V insulation.
9 Small Appliance 8 230 1440 6.26 20 2 - 3.5 13 The spare ckt shall be provided with an empty PVC pipe
10 Aircon Outlet 1 230 1492 6.49 30 2 - 5.5 20 size 19mm diameter which should be extend atleast
300 mm above ceiling line. The grounding wires shall be
11 Spare identified and all wires shall be color coded for easy identification.
The panel board shall be provided with a circuit directory.

LEGEND : To San Julian,


RISER DIAGRAM a Compact flourescent lamp, 11W
Eastern Samar

D
POSNECE
PROID E
ESAMELCO RES

M 2 gang conveniece outlet


60AT flush type ( complete )
15 AT 15 AT
1. Total load current of all circuits. C1
I = 3.04 + 2.17 + 2.61 + 3.04 + 9.39 + 9.39 + 1.52
9.39 + 6.26 + 6.49 C3
15 AT 15 AT
C2
C4
Sa switch, subscript letter(s)
I = 53.30 A 20AT 20 AT indicate the number of device Church

C5 C6 Park
2. Apply 80% demand factor. 20 AT 20 AT
C7 C8 1 Branch Ckt home run, the Number NFA
20AT 30 AT indicate the Branch ckt Galaxy N
3. Size of 2conductor C9 C10 Fuel F
8.0mm number A
4.Size of2conduit SPARE CS
20mm Ø
5. Size of circuit breaker service entrance To BORONGAN
60 Amp.
Panel board VICINITY MAP

M kWhr Meter

SHEET N0.

DILAO, ROJIM A. PROPOSED TWO STOREY THREE BEDROOM


ENGR.ROMEL JUSTIN MADRIAGA E
RESIDENTIAL BUILDING
3
BSCE-3B