CONTINUITY / MEGGER TEST FORM
PROJECT :
LOCATION :
Trade: Date Conducted : Control No. :
Electrical
Attachment:
Plan Diagram Product Data Methodology Mill Certificate Calibration Certificate
Bldg. # / Loc. / Unit : Brand / Contractor :
Specification: Initial Test Date:
3 PHASE TEST RESULT
CIRCUIT
DESCRIPTION WIRE SIZE L1-L2 L1-G L2-G REMARKS
NO.
A-B B-C C-A A-G B-G C-G PASS FAIL
1 Lighting Outlets 2-2.0mm dia THHN cu 598 MΩ 611 MΩ 603 MΩ N/A N/A N/A N/A N/A N/A Note: if Failed - Re-test
2 Water Feature Loads 3-8.0mm2 THW cu 2.2GΩ 2.1 GΩ 2.1GΩ N/A N/A N/A N/A N/A N/A
3 CCTV 3-2.0mm dia THHN cu 2.2GΩ 2.2GΩ 2.2GΩ N/A N/A N/A N/A N/A N/A Subcontractor / Supplier must conduct initial or
4 Hand Dryer 3-2.0mm dia THHN cu 2.2GΩ 2.2GΩ 2.2GΩ N/A N/A N/A N/A N/A N/A internal testing first before notice for final test
5 Convenience Outlets 3-2.0mm dia THHN cu 652 MΩ 645 MΩ 595 MΩ N/A N/A N/A N/A N/A N/A
6 2.0HP Split Type ACU 2-2.6&1-2.0mm dia THW 2.2GΩ 2.2GΩ 2.2GΩ N/A N/A N/A N/A N/A N/A
7 1.0HP Split Type ACU 3-2.0mm dia THHN cu 2.2GΩ 2.2GΩ 2.2GΩ N/A N/A N/A N/A N/A N/A
9 1.5HP ACU (Window Type) 3-2.0mm dia THHN cu 2.2GΩ 2.2GΩ 2.2GΩ N/A N/A N/A N/A N/A N/A
10 3/4HP ACU (Window Type) 3-2.0mm dia THHN cu 2.2GΩ 2.2GΩ 2.2GΩ N/A N/A N/A N/A N/A N/A
11 FACP 3-2.0mm dia THHN cu 1.4 GΩ 1.5 GΩ 1.6 GΩ N/A N/A N/A N/A N/A N/A
12 MAIN FEEDER LINE 2-50.0&1-14.0mm THW
2
1.4 GΩ 1.5 GΩ 1.6 GΩ N/A N/A N/A N/A N/A N/A
CONDUCTED BY: WITNESSED BY: APPROVED BY: NOTED BY:
(Contractor Representative) ( MEPF / Client) ( QA / QC) ( PIC / PM / MEPF HEAD)
DISTRIBUTION : Subcon Document control Client