You are on page 1of 1

GENERAL NOTES ONE LINE DIAGRAM SCHEDULE OF LOADS

SCALE NTS SCALE NTS SCALE NTS


PANEL BOARD A
2 - 80 mm²,
1. ALL ELECRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH THW wire
THESE PLANS AND SPECIFICATIONS. THE APPLICABLE PROVISIONS OF Type Of Load Amps Volt-Amps Circuit Type of
Circuit No. No. of Outlet S1 S2 S1w S3w Volts Size of Wire Conduit Size
Protection Wire
THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC). THE M
RULES AND REGULATION OF THE LOCAL ENFORCING AUTHORITY AND 1 General Lighting 12 4 1 2 4 230 11.05 2540.48 20A, AT, 2P TW 3.5mm²
Main Circuit 2 General Lighting 10 2 0 0 2 230 7.51 1726.54 20A, AT, 2P TW 3.5mm²
THE REQUIREMENTS OF THE LOCAL POWER COMPANY. THE Breaker
2 - 22 mm², 3 General Lighting 9 2 0 0 2 230 11.58 2663.81 20A, AT, 2P TW 3.5mm²
ELECTRICAL WORKS SHALL BE DONE UNDER THE IMMEDIATE 2 - 38 mm²,
TW wire
150 AT
THW wire
4 General Lighting 10 4 0 0 2 230 14.80 3403.75 20A, AT, 2P TW 3.5mm²
SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER.
5 General Lighting 12 5 0 0 4 230 10.52 2419.62 20A, AT, 2P TW 3.5mm²
6 General Lighting 11 2 1 4 0 230 13.61 3129.97 20A, AT, 2P TW 3.5mm²
2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE, 230V AC, 60Hz
7 General Lighting 12 6 1 3 5 230 9.83 2261.76 20A, AT, 2P TW 3.5mm²
Panel A Circuit Panel B Circuit
Breaker Breaker 8 Small Appliance 10 0 2 4 0 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
3. ALL TERMINATION, SPLICING DEVICES AND OTHER 125 AT 100 AT 4 THW
9 Small Appliance 8 0 2 0 230 6.52 1500.00 20A, AT, 2P 3.5mm²
APPURTENANCES TO BE USED ON THE ENTIRE ELECTRICAL 10 Small Appliance 10 0 2 4 0 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
INSTALLATION SHALL BE OF STANDARD TYPE EXCEPT OTHERWISE 20 AT 20 AT 11 Small Appliance 7 3 0 2 2 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
SPECIFIED. General Lighting C1 C2 General Lighting General Lighting C1 C2 General Lighting 12 Laundry 2 1 0 1 0 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
20 AT 20 AT 20 AT 20 AT
13 Small Appliance 1 4 1 2 4 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED General Lighting C3
20 AT 20 AT
C4 General Lighting General Lighting C3
20 AT 20 AT
C4 General Lighting
14 Small Appliance 1 0 2 - - 230 6.52 1500.00 20A, AT, 2P TW 3.5mm²
TYPE "THW" UNLESS INDICATED IN THE PLAN. THE MINIMUM SIZE OF 15 8kw Stove 1 0 2 - - 230 27.83 6400.00 40A, AT, 2P TW 3.5mm²
General Lighting General Lighting General Lighting General Lighting
WIRE FOR POWER AND LIGHTING CIRCUIT HOMERUN SHALL BE 3.5mm² C5
20 AT 20 AT
C6 C5
20 AT 20 AT
C6
16 1.5hp Refrigerator 1 0 2 - - 230 10.00 2300.00 20A, AT, 2P TW 3.5mm²
AND INSULATED FOR 600 VOLTS. SMALL RACEWAY SHALL BE 15mmØ General Lighting C7 C8 Small Appliance Small Appliance C7 C8 Small Appliance 17 SPARE
TRADE/NOMINAL SIZE.. 20 AT 20 AT 20 AT 20 AT 18 SPARE
Small Appliance C9 C10 Small Appliance Small Appliance C9 C10 Small Appliance 19 SPARE
20 AT 20 AT 20 AT 20 AT
4. ALL OUTLET BOXES SHALL BE GALVANIZED GAGE NO. 15 DEEP TYPE 20 SPARE
Small Appliance Laundry Small Appliance Small Appliance
WITH FACTORY KNOCKOUTS C11
20 AT 20 AT
C12 C11
20 AT 20 AT
C12
Small Appliance C13 C14 Small Appliance Small Appliance C13 C14 1-HP ACU
5. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED 40 AT 20 AT 20 AT 20 AT
TYPE FOR PARTICULAR LOCATION AND PURPOSE OF USAGE Stove C15
20 AT 20 AT
C16 Refrigerator 1-HP ACU C15
20 AT 20 AT
C16 Spare
PANEL BOARD B
Spare Spare Spare Spare
6. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND C17
20 AT 20 AT
C18 C17
20 AT 20 AT
C18
Circuit Type of
POWER CIRCUIT PER PHILIPPINE ELECTRICAL CODE REQUIREMENT. Circuit No. Type Of Load No. of Outlet S1 S2 S1w S3w Volts Amps Volt-Amps Size of Wire Conduit Size
Spare Spare Spare Spare
Protection Wire
C19 C20 C19 C20
20 AT 20 AT 20 AT 20 AT
1 General Lighting 12 0 2 4 0 230 12.34 2838.93 20A, AT, 2P THW 3.5mm²
7. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS: 2 General Lighting 12 0 2 4 0 230 12.34 2838.93 20A, AT, 2P THW 3.5mm²
3 General Lighting 12 0 2 4 0 230 11.52 2651.47 20A, AT, 2P THW 3.5mm²
a. LIGHT SWITCH - 1.20 M ABOVE FINISH FLOOR 4 General Lighting 12 4 0 2 2 230 9.00 2071.85 20A, AT, 2P THW 3.5mm²
b. CONVINIENCE OUTLET - 0.30 M ABOVE FINISH FLOOR
SITE PLAN
5 General Lighting 5 1 0 1 0 230 5.26 1211.05 20A, AT, 2P THW 3.5mm²
c. PANEL BOARD - 1.50 M ABOVE FINISH FLOOR 6 General Lighting 11 4 1 2 4 230 13.42 3085.58 20A, AT, 2P THW 3.5mm²
d. AIRCONDITION OUTLET - 1.50 M ABOVE FINISH FLOOR 7 Small Appliance 9 0 2 - - 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
8 Small Appliance 3 0 2 - - 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
SCALE NTS 9 Small Appliance 10 0 2 - - 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
10 Small Appliance 9 0 2 - - 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
11 Small Appliance 1 0 2 - - 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
12 Small Appliance 1 0 2 - - 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
13 Small Appliance 1 0 2 - - 230 6.52 1500.00 20A, AT, 2P THW 3.5mm²
14 1HP ACU 1 1 0 - - 230 8.00 1840.00 20A, AT, 2P THW 3.5mm²
To Bajada To Sasa
15 1HP ACU 1 1 0 - - 230 8.00 1840.00 20A, AT, 2P THW 3.5mm²
LEGEND 16
17
18

SPARE
SPARE
SPARE
DENR
SCALE NTS 19 SPARE
central warehouse club
Symbol Description
From DLPC service drop,
230V 2 wire, 60 Hz RISER DIAGRAM
Spool Insulator Mounted on Bracket
SCALE NTS
Service Drop wire, 2 wire,
SERVICE ENTRANCE THW 80mm ²
RMC pipe,
mandaue foam showroom
M SERVICE METER 40mm
Conduit Support
Main Panel Board
KWH meter
CKT. BEAKER, RATING AS INDICATED
M
4 feet to 5 feet 4 feet to 5 feet
1feet
MAIN CKT. BEAKER, RATING AS INDICATED
C# CIRCUIT HOMERUN
PROPOSED 2-STOREY
JOHN PAUL R. BAUZON
E
JPRB REALTY & DEV'T. CORP. RESIDENTIAL BUILDING ENGR. EDDIE S. PARAS
1