You are on page 1of 1

LEGEND LEGEND DESCRIPTION

8 ELECTRICAL NOTES
E 2 SCALE NTS

OTHER VA PER AMP. LOAD


CKT NO. LOAD DESCRIPTION L.O. C.O. LOADS CIRCUIT PER CIRCUIT
CB RATING WIRE SIZE CONDUIT SIZE LIGHTING OUTLET
LIGHTING OUTLET 1200 5.45 15 A 2.0 mm.sqr. THHN 1 1. ALL ELECTRICAL WORKS SHALL COMPLY WITH
1 12 2" PVC CONDUIT PIPE CONVENIENCE OUTLET
THE LATEST EDITION OF THE PHILIPPINE
2 CONVENIENCE OUTLET 8 2880 13.09 20A 3.50 mm.sqr. THHN 1
2" PVC CONDUIT PIPE s FLUSH TYPE WALL SWITCH
ELECTRICAL CODE WITH THE RULES AND
CONVENIENCE OUTLET 8 2880 13.09 20A 3.50 mm.sqr. THHN 1 S2
3 2" PVC CONDUIT PIPE 2 - GANG SWITCH
REGULATIONS OF THE NATIONAL AND LOCAL
SPARE 1 1000 4.54 20A S3 3 - GANG SWITCH
4 AUTHORITIES CONCERNED.
5 WP WEATHER PROOF C.O. 2. SERVICE VOLTAGE TO THE BUILDING SHALL BE
6 CIRCUIT HOMERUN 20 VOLTS, 60 Hz.
7 SWITCH CONDUIT
3. THE CONTRACTOR SHALL VERIFY AND ORIENT
THE ACTUAL LOCATION OF THE SERVICE
8 CONVENIENCE CONDUIT
TERMINAL POLE FOR THE CONNECTION OF
TOTAL LOAD OF THE BUILDING 36.17 AMPERES LIGHTING & POWER PANELBOARD POWER SUPPLY.
D.F. (DEMAND FACTOR) = 80%
SERVICE ENTRANCE 4. ALL INSTALLATIONS SHALL BE CONCEALED
I t = (36.17 x 0.80) + (8.00 + 0.25) USE: 100AF 2P 70 AT 220 CB (CIRCUIT BREAKER) LINE TO GROUND FROM VIEW.
= 37.186 AMPERES
M SERVICE KILOWATT HOUR METER
5. MINIMUM WIRE AND CONDUIT SIZE SHALL BE
NO. 14 AWG TYPE THHN AND 12.00mm Ø PIPE
UNLESS OTHER SPECIFIED.
6. FULL BOXES OF APPROPRIATE SIZE SHALL BE
3 SCHEDULE OF LOADS AND COMPUTATIONS 4 ELECTRICAL LEGEND PROVIDED EVEN IF NOT INDICATED IN THE
E 2 SCALE NTS
E 2 SCALE NTS
DRAWING TO ACCOMMODATE NO. 8 SIZES OF
WIRE.
7. ALL MATERIALS TO BE USE SHALL BE NEW AND
ENTRANCE WIRES IN
APPROVED TYPE, APPROPRIATE FOR BOTH
RIGID STEEL CONDUIT LOCATION AND INTENDED TO USE.
BRANCH CIRCUIT NO. 8. ALL ACU's SHALL BE PROVIDED WITH SAFETY
SERVICE ENTRANCE M LIGHTING A& POWER SERVICE ENTRANCE M LIGHTING A& POWER SWITCH TO SERVE AS DISCONNECTING MEANS
PANEL BOARD (LPP) PANEL BOARD (LPP)
CIRCUIT NO.
READILY ACCESSIBLE LOCATION WITHIN
1 SIGHT FROM THE EQUIPMENT.
100AF 2P 70 AT MAIN CB
(CIRCUIT BREAKER) 100A 2
9. ALL ELECTRICAL WORKS SHALL BE DONE
100A
SERVICE ENTRANCE UNDER THE DIRECT SUPERVISION OF A DULY
3
ENTRANCE WIRES IN
RIGID STEEL CONDUIT
PROFESSIONAL ELECTRICAL ENGINEER OR A
1 15A 20A 2 (RSC) 4 1 15A 20A 2 MASTER ELECTRICIAN.
SERVICE
KILOWATT HOUR M
10. MOUNTING HEIGHT OF ELECTRICAL DEVICES
METER PB 3 20A 20A 4 ARE AS FOLLOWS:
10.1. WALL SWITCHES - 1.37 METERS ABOVE
FINISHED FLOOR LEVEL.
LINE TO GROUND
10.2. CONVENIENCE OUTLETS - 0.30 METERS
CIRCUIT BREAKER THE NEUTRAL WIRE OF THE SERVICE LINE TO GROUND ABOVE FINISHED FLOOR LEVEL.
ENTRANCE SHOULD BE GROUNDED BY
AMPERE RATING CONNECTING TO A WATER G.I. PIPE OR A ROD
DRIVEN IN THE GROUND
10.3. AIR CONDITIONING UNIT - 1.50 METERS
BRANCH CIRCUIT
ABOVE FINISHED FLOOR LEVEL
10.4. PANEL BOARD - 1.37 ABOVE FINISH FLOOR
LEVEL
10.5. KILOWATT - HOUR METER - 1.85 METERS
5 SCHEMATIC DIAGRAM 6 RISER DIAGRAM DETAIL 7 LIGHTING & POWER PANEL BOARD ABOVE FINISH FLOOR LEVEL.
E 2 SCALE NTS
E 2 SCALE NTS
E 2 SCALE NTS

PREPARED FROM THE OFFICE OF: R.A. 9266 PROJECT TITLE : OWNER : SHEET CONTENT : SHEET NUMBER :
DRAFTED BY : PMS II
THIS DRAWING ACTING AS AN
INSTRUMENT OF SERVICE IS
DATE : JULY 14, 2019 SOLELY OWNED BY THE SCHEDULE OF LOADS AND
PROFESSIONAL ELECTRICAL ENGINEER ARCHITECT/ENGINEER AND NOT PROPOSED 3 BEDROOMS BUNGALOW MELCHOR S. CASTANEDA COMPUTATIONS E-2
TO BE RECOPIED AND
PRC No : Validity : REPRODUCED WITHOUT ELECTRICAL LEGEND
CHECKED BY :
PTR No : Issued : PROPER AUTHORIZATION.
LIGHTING & POWER PANELBOARD 2 2
Issued at : TIN No : LOCATION BRGY. SUCLABAN, MEXICO PAMPANGA ADDRESS BRGY. SUCLABAN, MEXICO, PAMPANGA
DATE : RISER DIAGRAM DETAILS