You are on page 1of 1

GEN.

NOTES & SPECIFICATIONS

2 THIS SITE
1
PB

POWER & LIGHTING LAYOUT


SCALE 1:100

LOCATION MAP
SCALE NTS

LEGEND:
SCHEDULE OF LOADS CUT OUT DISTRIBUTION
20W LED BULB W/ MEDIUM BASE KEYLESS TYPE LIGHTING ARRESTER
PORCELAIN RECEPTACLE OUTLET SEC LINE TO OTHER CONSUMERS
CKT NO. LOAD DESCRIPTION QUANTITY VOLTS WATTS AMPS PRTN WIRE/ CONDUIT SIZE TO SOCOTECO PRIMARY
LINE
S WALL SWITCH
1 1 230 100 0.455 15 A -2P 2- 2.0mm2 THW CU. WIRE/ 50 KVA SERVING VICINITY
LIGHTING OUTLET 2-14 mm2
CIRCUIT HOMERUN 20mm DIAM. PVC PIPE
2- 3.5mm2 THW CU. WIRE/
2 CONVENIENCE OUTLET 1 230 360 1.566 20 A -2P
DUPLEX CONVENIENCE OUTLET, 20A, 250V 20mm DIAM. PVC PIPE
2- 5.5mm2 THW CU. WIRE/
M
DISTRIBUTION PANEL BOARD
3 CUT OUT MACHINE 1 230 1000 4.546 30 A-2P
20mm DIAM. PVC PIPE KWH METER
2- 5.5mm2 THW CU. WIRE/ 2-8.0 mm2 THHN
M ELECTRIC SERVICE METER 4 SPARE 1 230 1000 4.546 30 A-2P STRANDED WIRE MAIN
20mm DIAM. PVC PIPE 30 AT2P
ELECTRICAL SERVICE ENTRANCE TOTAL 11.113 AMPS
15 A 20 A
GROUNDING SYSTEM MAIN WIRE COMPUTATION: MAIN CB COMPUTATION: C1 C2
Ic= 11.113 A x 1.25 AMPS If= 11.113 + 2x 4.546 AMPS 30 A 30 A
13.892 AMPS 20.205 AMPS C3 C4

USE:
30 ACB MAIN PROTECTION

PROJECT/LOCATION SHEET CONTENT PREPARED BY PRC # APPROVED BY COMPANY SHEET NO.


DATE
BUNKHOUSE POWER & LIGHTING LAYOUT, LOCATION MAP, CAV CONSTRUCTION
PAG-ASA, MATINAO SCHEDULE OF LOADS, SINGLE LINE RISER PTR # E
POLOMOLOK DATE
PROVINCE OF SOUTH COTABATO DIAGRAM
ELECTRICAL ENGINEER
PLACE
OWNER/REPRESENTATIVE 1 1