You are on page 1of 1

1-25 KVA DISTRIBUTION

SERVICE ENTRANCE
TRANSFORMER
230V, 3PHASE, 60HZ.

GENERAL NOTES:
2-38.0 MM SQ.THW CU. WIRE
SCHEDULE OF LOADS 1. ALL ELECTRICAL WORKS HEREIN SHALL BE EXECUTED IN ACCORDANCE WITH THE
LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC), THE NEW ELECTRICAL
PANEL BOARD 1 ENGINEERING LAW (R.A. 7920), LAWS AND ORDINANCES OF THE LOCAL GOVERNMENT
M UNIT AND RULES AND REGULATIONS OF THE LOCAL ELECTRICAL POWER UTILITY
CB RATING FIXTURE LOAD DESIGN ANALYSIS: KILOWATT HOUR METER COMPANY.
CKT. NO. OF AMPERE WIRE SIZE AND
AT AF POLES VOLT QTY VA RATING
NO. KAIC CONDUIT
GENERAL LIGHTING LOAD: 2. ALL WIRING SHALL BE IN INTERMEDIATE METALLIC CONDUIT (IMC) FOR THE
1 20 20 10 LIGHTING OUTLET @20 WATTS 2 230 19 380 1.65 FEEDERLINE, ELECTRICAL METALLIC TUBING (EMT) FOR LOAD SIDE EMBEDDED IN
SMALL APPLIANCE LOAD = 7,500.00 VA MAIN: FLOOR AND EXPOSED WIRING AND UNPLASTICIZED POLYVINYL CHLORIDE (PVC) FOR
2 20 20 10 LIGHTING OUTLET @20 WATTS 2 230 29 580 2.52
125AT,2P AUXILLARY CONDUITS. UNLESS OTHERWISE SPECIFIED.
_________________________________________________
3 20 20 10 LIGHTING OUTLET @20 WATTS 2 230 19 380 1.65 MCCB
14,585.28 VA 3. PANELBOARDS AND OVERCURRENT PROTECTION ENCLOSURES SHALL BE NEMA-1
4 20 20 10 LIGHTING OUTLET @20 WATTS 2 230 19 380 1.65 FOR INDOOR USE AND NEMA-3R FOR OUTDOOR USE. UNLESS OTHERWISE SPECIFIED.
5 20 20 10 CONVENIENCE OUTLET 2 230 12 2160 9.39 APPLY DEMAND FACTOR
4. POWER SERVICE ENTRANCE TO THE BUILDING SHALL BE 230V, 60HZ, THREE PHASE,
6 20 20 10 CONVENIENCE OUTLET 2 230 11 1980 8.61 2-30.0 MM SQ.THW CU. WIRE 2-30.0 MM SQ.THW CU. WIRE 3-WIRE + GROUND SYSTEM.
FIRST 3000 VA @100% D.F = 3,000.00 VA
7 20 20 10 CONVENIENCE OUTLET 2 230 14 2520 10.96 REMAINING @35% D.F = 4,054.85 VA 5. ALL WIRING INSTALLATION SHALL BE CONCEALED FROM VIEW.
230
_________________________________________________
8 20 20 10 CONVENIENCE OUTLET 2 10 1800 7.83
6. UNLESS OTHERWISE INDICATED, BRANCH CIRCUIT CONDUCTORS SHALL NOT BE
7,054.85 VA MAIN: MAIN:
9 20 20 10 CONVENIENCE OUTLET 2 230 10 1800 7.83 SMALLER THAN 2.0mm DIAMETER, SOLID COPPER, MEDIUM DRAWN, THHN TYPE, 600
100AT,2P 100AT,2P VOLTS INSULATIONS.
10 20 20 10 REFRIGERATOR OUTLET 2 230 9 500
9 UNITS AIR CONDITION UNIT 1.0 HP = 14,580.00 VA MCCB MCCB
2.17
1 UNIT REFRIGERATOR OUTLET = 500.00 VA 7. MINIMUM SIZE OF CONDUIT SHALL BE 20mm DIA. FOR RSC AND uPVC. 15mm DIA. FOR
11 30 30 10 RANGE AND RANGE HOOD OUTLET 2 230 1 1000 4.35 1 UNIT RANGE OUTLET = 1,000.00 VA 20AT 20AT 20AT 20AT EMT.
12 30 30 10 AIR CONDITION UNIT 1.0HP 2 230 1 1620 7.04 2 UNITS WATER HEATER OUTLET = 3,600.00 VA L.O. 1 2 L.O. L.O. 1 2 L.O.
_________________________________________________ 8. NO BRANCH CIRCUIT CONDUCTORS SHALL BE LOADED MORE THAN 80% OF ITS RATED
13 30 30 10 AIR CONDITION UNIT 1.0HP 2 230 1 1620 7.04 20AT 20AT 20AT 20AT AMPACITY.
26,734.85 VA
L.O. 3 4 L.O. L.O. 3 4 C.O.
14 30 30 10 AIR CONDITION UNIT 1.0HP 2 230 1 1620 7.04 MAIN BREAKER RATING: 9. BOXED SHALL BE PRESSED STEEL WITH REQUIRED THICKNESS IN CONFORMANCE
la = ( 26,734.85/ 230 ) AMP 20AT 20AT 20AT 20AT WITH THE LATEST EDITION OF THE PEC.
15 30 30 10 AIR CONDITION UNIT 1.0HP 2 230 1 1620 7.04
la = 116.24 AMP
C.O. 5 6 C.O. C.O. 5 6 C.O.
16 30 30 10 SPARE 2 230 1
20AT 20AT 20AT 30AT 10. MOUNTING HEIGHT OF PANEL AND DEVICES ARE AS FOLLOWS; (FROM FLOOR FINISH TO
17 30 30 10 SPARE 2 230 1 PIPE w/ 1 - 125AT/125/AF/25KAIC, 2P, 230V, MCCB CENTER OF UNIT)
C.O. 7 8 C.O. C.O. 7 8 HEATER
18 30 30 10 SPARE 2 230 1
KVA RATING: 20AT 20AT 30AT 30AT A. WALL SWITCHES 1400 mm
TOTAL 93.30 B. WALL CONVENIENCE OUTLETS 300 mm
KVA = ( 116.24 X 230 ) / ( 1000 X 1.2 ) KVA C.O. 9 10 REF HEATER 9 10 HEATER C. COUNTER-TOP OUTLETS VERIFY ARCHITECT
KVA = 22.28 KVA 30AT 30AT 30AT 30AT D. TELEPHONE/CATV OUTLET VERIFY ARCHITECT
E. EMERGENCY LIGHT OUTLET VERIFY ARCHITECT
LOAD COMPUTATION USE = 1- 25 KVA, 60 Hz, 7620/230 VOLTS, DISTRIBUTION RANGE 11 12 ACU ACU 11 12 ACU F. kWHr METER 1830 mm
G. PANELBOARD 1830 mm
TOTAL CONNECTED LOADS: TRANSFORMER 30AT 30AT 30AT 30AT
ITOTAL= (10.96 x 1.25) + 82.34 @80% D.F USE: 2-30.0 MM SQ.THW CU. WIRE ACU 13 14 ACU ACU 13 14 ACU 11. GROUND ROD OF 15mm DIA. SHOULD BE CONNECTED BY GROUND CONNECTOR 14.0mm2
ITOTAL= 76.83 Amp. (MAXIMUM) TO THE NEUTRAL BAR AT THE METER CENTER.
30AT 30AT 30AT 30AT
MAIN: 100AT/100AF/18KAIC, 230V, 1PH, MCCB
ACU 15 16 SPARE ACU 15 16 SPARE 12. GROUND WIRE FROM THE NEUTRAL BAR AT THE METER CENTER SHOULD BE TAP TO THE
BUILDING REINFORCING BAR OF NOT LESS THAN 1/2 INCHES DIAMETER LENGTH SHOULD
30AT 30AT 30AT 30AT BE MORE THAN 20ft. USE SOLDERLESS CONNECTOR FOR EXPOSED CONNECTIONS.
18 18 THEREMOWELD IN CONCEALED IN CONCRETE OR EMBEDDED IN CONCRETE.
SCHEDULE OF LOADS SPARE 17 SPARE SPARE 17 SPARE
13. CONDUITS/RACEWAYS SHALL BE ADEQUATELY SUPPORTED AS REQUIRED IN
PANEL BOARD 2 CONFORMANCE WITH THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC).

CB RATING FIXTURE
PANEL BOARD 1 PANEL BOARD 2
14. ONLY LISTED TOOLS, APPLIANCES AND EQUIPMENT COVERED BY PEC ART. 2.50.6.5 AND
CKT. NO. OF AMPERE WIRE SIZE AND
POLES VOLT QTY VA RATING 2.10.1.8 (EXEMPTION-2) SHALL NOT BE REQUIRED TO BE G.F.C.I PROTECTED.
AT AF KAIC CONDUIT
NO.

1 20 20 10 LIGHTING OUTLET @20 WATTS 2 230 19 380 1.65


SINGLE LINE DIAGRAM 15. DISTRIBUTION PANEL SHALL BE READILY ACCESSIBLE, THAT NO OBSTACLE SHOULD
BLOCK ACCESS TO THE PANEL.
2 20 20 10 LIGHTING OUTLET @20 WATTS 2 230 23 460 2.00

3 20 20 10 LIGHTING OUTLET @20 WATTS 2 230 21 420 1.83 16. THE INSTALLATION SHALL BE DIRECTLY SUPERVISED BY A DULY LICENSED ELECTRICAL
4 20 20 10 CONVENIENCE OUTLET 2 230 7 1260 5.48 SHORT CIRCUIT COMPUTATION PRACTITIONER IN CONFORMANCE WITH R.A.

UTILITY DISTRIBUTION LINE: SERVICE ENTRANCE:


5 20 20 10 CONVENIENCE OUTLET 2 230 9 1620 7.04

6 20 20 10 2 230 8 1440 6.26


IMPEDANCE CALCULATION:
CONVENIENCE OUTLET

7 20 20 10 CONVENIENCE OUTLET 2 230 11 1980 8.61 Zt =


8 30 30 10 WATER HEATER OUTLET 2 230 1 1200 5.22 RESISTANCE CALCULATION: Zt =
Zt =
9 30 30 10 WATER HEATER OUTLET 2 230 1 1200 5.22 UTILITY DISTRIBUTION LINE, 39.37 ft. SERVICE ENTRANCE, 51.27 ft. TOTAL RESISTANCE:
10 30 30 10 WATER HEATER OUTLET 2 230 1 1200 5.22 Ru = Rse = Rt = Ru + Rse
11 30 30 10 AIR CONDITION UNIT 1.0HP 2 230 1 1620 7.04 100ft. 100ft. COMPUTE FOR SHORT CIRCUIT CURRENT:
Ru = Rse =
12 30 30 10 AIR CONDITION UNIT 1.0HP 2 230 1 1620 7.04
Isc = V
13 30 30 10 AIR CONDITION UNIT 1.0HP 2 230 1 1620 7.04
REACTANCE CALCULATION: Zt
14 30 30 10 AIR CONDITION UNIT 1.0HP 2 230 1 1620 7.04 Isc = 230
UTILITY DISTRIBUTION LINE, 39.37 ft. SERVICE ENTRANCE, 51.27 ft. TOTAL REACTANCE: 0.018817
15 30 30 10 AIR CONDITION UNIT 1.0HP 2 230 1 1620 7.04
Xu = Xse = Xt = Xu + Xse Isc = 12,222.99Amps - Symmetrical Short Circuit Current
16 30 30 10 SPARE 2 230 1
100ft. 100ft.
17 30 30 10 SPARE 2 230 1 Xu = Xse = USE: 18,000Amps / 18KAIC, Minimum Interrupting

18 30 30 10 SPARE 2 230 1
Molded Case Circuit Breaker

TOTAL 96.36

VOLTAGE DROP CALCULATION


LOAD COMPUTATION PHASE WIRE
CKT. NO. DESCRIPTION K L I VD %VD
TOTAL CONNECTED LOADS: CM SET
ITOTAL= (8.00 x 1.25) + 88.36 @80% D.F USE: 2-30.0 MM SQ.THW CU. WIRE
ITOTAL= 76.69 Amp. 1 MAIN DISTRIBUTION PANEL 2 12 51.27 116.24 66,360 1 2.16V 0.94
MAIN: 100AT/100AF/18KAIC, 230V, 1PH, MCCB
2 CONVENIENCE OUTLET 2 12 45.70 8.61 6,530 1 1.45V 0.63

3 PANEL BOARD 2 2 12 20.70

TOTAL
76.69 52,620 1 0.72V

4.33V
0.31

1.88%
VICINITY MAP
This computed Voltage Drop of Proposed Two-Storey Residential Building with total of 1.88 percentage (%) of
Voltage drop meet the required allowable VD of Philippine Electrical Code (PEC).