Professional Documents
Culture Documents
50MMBTU
Prepared for:
p
II 11(~~) ~;tllw~UdI-jiJ"d.,JJj
, III ~
CONTRACT
WorleYParsons -Arabian Industries (JV)
NO. : C31l0606
CONTRACTNO PROJ NO PAIP00060
C3110606 PROJ.NO.: PAIP00060
Book 5
. .
. .
TABLE OF CONTENT
W.O. # 207009
BOOK 5
MCC I VFD PANEL
TABLE OF CONTENTS
PART DESCRIPTION PAGE
General Information
Receiving. Handling. & Storage
Installing Control Center Sections
Installing Conduit & Wiring
Incoming Line Connections
Overcurrent Protection Devices
Overload Relay Heater Selection
Inspection Prior to Energizing
Unit Installation & Adjustment
Maintenance
Plan Views
Related Instruction Leaflets
and the operating handle in the ON position, personnel, the handle mechanism can b e
another interlock to the divider pan prevents padlocked in the 0FF.position. Space for a
removal of the unit. This same interlock prevents minimum of three padlocks is provided on each
insertion of the unit unless the handle mechanism handle.The device panel (5) is mounted on the
is in the OFF position. To ensure that units are not drawout unit. It will accommodate up to six pilot
energized accidentally or by unauthorized devices. The overload reset button (20) is mounted
on the unit door.
i
RATINGS the motor control center are appropriate for the f3ult
current available.
Each Freedom 2100 Motor Control Center has a
rating nameplate attached to the door of the top QUALIFIED PERSONNEL
horizontal wireway of the primary section. See
Figures 1 and 2. This nameplate shows the general Individuals who install, operate or maintain motor
order number under which the motor control center control centers must be trained and authorized to
was built and its continuous electrical ratings, in operate the equipment associated with the
terms of incoming line voltage, phases, and installation and maintenance of a motor control
frequency, and ampere ratings of the horizontal bus center, as well as the operation of the equipment
and the vertical bus for each section. In addition, this that receives its power from controller units in the
nameplate shows the passive short-circuit motor control center.
(withstand) rating of the horizontal and vertical bus
system. Such individuals must be trained in the proper
procedures with respect to disconnecting and
The active short-circuit (interrupting) ratings of the locking OFF power to the motor control center,
main and unit short-circuit protective devices are wearing protective clothing and equipment, and
shown on labels attached to the inside of each unit. following established safety procedures as outlined
Before installing a motor control center, calculate in the National Electrical Safety Code(ANS1 C2)
and record the fault current available at the incoming and Electrical Equipment Maintenance(NFPA
line terminals. Verify that the short-circuit withstand 708).
and short-circuit interrupting ratings of the units in
Part 2
RECEIVING, HANDLING, AND STORAGE
RECEIVING 4. The control center should remain secured to the
shipping skid until the motor control center is in
Before and after unloading the motor control center, its final location.
inspect each section and unit exterior for evidence of 5. Exercise care during any movement and
damage that may have been incurred during placement operations to prevent falling or
shipment. If there is any indication that the control unintentional rolling or tipping.
center has been mishandled or shipped on its back 6. Lifting angles for handling by overhead crane
or side, remove the drawout units and make a are bolted to the top of each shipping section.
complete inspection of the internal structure, bus Handling by overhead crane is preferable but
bars, insulators and unit components for possible when crane facilities are not available, the motor
hidden damage. Report any damage found to the control center can be positioned with a fork-lift
carrier at once. truck or by using rollers under the shipping skid.
HANDLING OVERHEADCRANE
The following guidelines are provided to help avoid 1. See Figure 3 for recommended lifting
personal injury and equipment damage during configuration.
handling, and to facilitate moving the motor control 2. Select or adjust the rigging lengths to
center at the job site. compensate for any unequal weight distribution,
and to maintain the motor control center in an
GENERAL HINTS upright position.
3. To reduce tension on the rigging and the
1. Handle the motor control center with care, to compressive load on the lifting angles, do not
avoid damage to components and to the allow the angle between the lifting cables and
enclosure or its paint finish. vertical to exceed 45 degrees.
2. Keep the motor control center in an upright 4. Use slings with safety hooks or shackles. Do
position. not pass ropes or cables through lifting
3. Insure that the moving means has the capacity angle holes.
i
I
to handle the weight of the motor control center.
I.B. 8926-1A
ROLLERS
STORAGE
I 1
Figure 3 Correct Use O f Lifting Angle When a motor control center cannot be installed and
placed into operation immediately upon receipt, take
steps to prevent damage by condensation or harsh
environmental conditions. If the motor control center
cannot be installed in its final location, store it in a
clean, dry, ventilated building, heated to prevent
5. Afler removing the lifting angles, replace the condensation, and protected from dirt, dust, water,
mounting hardware to prevent the entrance of dirt. and mechanical damage. When storage conditions
etc. are less than ideal, install temporary electrical
heating, typically in the form of light bulbs, totaling
FORK-LIFTTRUCK 150 watts per section, hung in the vertical wireway,
or by applying power to self-contained space
Motor control centers are normally top and front heaters that the motor control center may be
heavy Balance the load carefully and steady, as equipped with. Remove all loose packing and
necessary, while movlng Always use a safety flammable materials before energizing any of the
strap when handling with a fork-lift. heating elements.
I
Part 3
INSTALLING CONTROL CENTER SECTIONS
GENERAL INSTALLATION
Freedom Series 2100 Motor Control Centers 1. Before any installation work is begun, consult all
(MCC's) are designed for installation in accordance drawings furnished by Cutler-Hammer as well as
with both the National Electrical code (NEC), NFPA all applicable contract drawings for the
70, and the National Electrical Safety Code (NESC), installation. Give particular attention to the
ANSI C2. physical location of units in the control center
and their relation to existing or planned conduit.
Caution - If work i s involved i n connecting the busways, etc. Provide for future conduit
control center with existing equipment, ensure entrance prior to control center installation.
that incoming power is disconnected before 2. Locate the control center in the area shown on
work i s begun. Disconnecting means should be the building floor plans. If in a wet location or
locked out andlor tagged out of service. Where i t outside of the building, protect the control center
Is not feasible to de-energize the system, the from water entering or accumulation within the
following precautions should be taken: enclosure. Recommended clearances or
working spaces are as follows:
A) Persons working near exposed parts that are or a) Clearance from walls (where not rear
may be energized should be instructed and should accessible) - a minimum of '/z inch for
use practices (including appropriate apparel. indoor and 6 inches for outdoor or wet
equipment, and tools) in accordance with the NESC. locations.
b) Clearance from front of MCC (working
B) Persons working on exposed parts that are or space) - minimum of 3 feet for control
may be energized should, in addition, be qualified centers without exposed live parts. See NEC
I persons who have been trained to work on 110-16d. NOTE: This working space should
,I
. ~. energized circuits~
LB. 8926-IA
not be used for storage and should have conductor must be run to the MCC in
adequate lighting. accordance with NEC 250-23(b), and
Since control centers are assembled at the connected to the ground bus terminal.
factory on smooth and level surfaces to assure iii) Do not make any connections to ground
correct alignment of all parts, control centers on the load side of any neutral
should be securely mounted on a level surface. disconnecting line or any sensor used for
The foundation furnished by the purchaser must ground-fault protection. Do not connect
be true and level, or the bottom frames must be outgoing grounding conductors to the
shimmed to support the entire base in a true neutral.
plane. It is recommended that leveled channel b) Motor control centers used as service
sills under both the front and rear of the control equipment for an ungrounded system or as
center be used to provide this level base. Drill an an incoming line section for a separately-
tap the channel sills for mounting bolts in derived previously ungrounded system:
accordance with the applicable floor plan i) Run a grounding electrode conductor
drawing and then either install the MCC level (ground wire) having a size in
with, or on top of, the finished floor. If sills are accordance with NEC 250-94 from the
grouted in concrete, the mounting bolts should grounding electrode to the MCC ground
be screwed in place and remain until the bus terminal. See NEC 250-91(a) and
concrete has hardened. 92(b).
For bottom entry, position the motor control c) Motor control centers not used as service
center so that the conduit stubs or floor equipment nor as an incoming line section
openings are located in the shaded areas shown for a separately-derived system, and used
on the MCC floor plan drawings (refer to pages on either a grounded or ungrounded system:
31 to 32 for floor plan dimensions). The shaded i) Ground the MCC ground bus by means
areas represent the open space available for of equipment grounding conductors
conduit entry through the bottom of each having a size in accordance with NEC
section. A shaded area may be restricted if large 250-95 or by bonding to the raceway
controllers or autotransformers are mounted in enclosing the main supply conductors in
the bottom of the sections. If optional bottom accordance with NEC 250-91(b).
plates are supplied, the plates may be removed 8. When all wiring and adjustments are complete.
and drilled for conduit entry. close all unit and wireway doors.
Install the MCC in its final position, progressively 9. In damp indoor locations, shield the MCC to
leveling each section and bolting the frames prevent moisture and water from entering and
together if they are separated. If necessary, accumulating.
secure the MCC to walls or other supporting 10. Unless the motor control center has been
surfaces. Do not depend on wooden plugs designed for unusual service conditions, it
driven into holes in masonry, concrete, plaster. should not be located where it will be exposed to
or similar materials. See NEC 110-13. ambient temperatures above 40°C (104"F),
If two or more shipping sections are to be joined corrosive or explosive fumes, dust, vapors,
into an integral assembly or a shipping section is dripping or standing water, abnormal vibration,
to be joined to an existing section, refer to shock or tilting.
paragraphs below before proceeding with the
installation. JOINING COMPATIBLE SECTIONS
Ground and bond the motor control center as
follows: If two more shipping blocks are to be joined into an
a) Motor control centers used as service integral assembly, or a section added to an existing
equipment for a grounded system or as an installation, splicing or horizontal bus, ground bus,
incoming line section for a separately- neutral bus and joining of the adjacent vertical
derived previously grounded system: sections must be planned with the installation.
i) Run a grounding electrode conductor 1. Remove the side sheets from adjacent vertical
(ground wire) having a size in sections to be joined. (These sheets will have
accordance with NEC 250-94 from the been removed from factory-assembled
grounding electrode to the MCC ground sections.)
bus or ground terminal provided. See 2. The horizontal bus splice plates and connection
also NEC 250-91(a) and 92(b). hardware will be shipped with the MCC attached
ii) If the system is grounded at any point to one end of shipping section. Refer to Figure
ahead of the MCC, the grounded 4 This method provides the most convenient
, access to the bolts, and eliminates the need to
remove the horizontal bus barriers in that
structure. Should the existing bus be oxidized.
sand lightly with a fine aluminum oxide paper.
CAUTION - Do not use emery cloth or any
abrasive containing metal.
3. Remove the upper horizontal wireway door from
the structure on the right side of the left-
hand(LH) section and remove the two-piece
wireway barrier to provide access to the ends of
the bus in that section.
4. Move the section in place, aligning the upright
structural channels and bottom channels.
Alignment of the section with floor sills and
foundation provisions will be facilitated by
removing the bottom horizontal wireway doors.
Using the "U" type frame clamps provided.
clamp adjacent front upright channels together
at the top, bottom and approximate center of the
vertical structure. This operation will be
facilitated by removing the vertical wireway
doors from the left-hand structure and one or
more drawout units from the right-hand
structure. See Part 9.
5. If rear access is available. "U" clamps should
also be used to clamp the rear upright channels
together. In front-mounted-only structures this
will require removal of the adjacent back sheets.
In a back-to-back mounted structure, remove the
vertical wireway doors and one or more drawout
units as above.
6. Secure the sections to the floor sills or mounting
bolts as provided for the installation.
7. Bolt the horizontal bus splice plates to the bus in
the left-hand structure, torquing all bus splice
bolts to 360 pound-inches (30 pound-feet). See
Figure 5.
8. Replace all unit, bus barriers, and doors.
TYPE 3R ENCLOSURES
1 I
Fig. 8 Triple Bar Splice Kit
I
Fig. 9 Quadruple Bar Splice Kits
I I
SIX %RS PER PH4SE - 20' DEEP
I
E1M1 ahRS PER P i l W - 20- DEEP
Fig. 10 Six and Eight Bar Splice Kits
Consult the assembly instruction supplied with every Freedom 2100 Motor Control Center set up for splice to
Freedom Unitrol or F10 Unitrol.
Part 4
INSTALLING CONDUIT AND WIRING
CONDUIT conductors are not distributed uniformly, eddy
currents will be generated in the steel between the
Install conduit in such a manner as to prevent water conduits.
from entering and accumulating in the conduit or the
enclosure. Eliminate sags in conduit. Have the Locate conductors within the MCC to avoid physical
conduit enter the motor control center (MCC) in the damage and to avoid overheating. Secure incoming
areas designated for conduit entry on the plan power lines in a manner adequate to withstand the
views. See pages 31 and 32 of this booklet and forces which will act to separate the conductors
outline drawings shipped with the MCC. Keeping under short-circuit conditions. Use the cable ties
conduit within the shaded areas shown in the plan furnished in both horizontal and vertical wireways to
views will avoid cable interference with structural support the load and interconnection wire. Use a
members and live bus. See Part 12. shielded communications cable inside of flexible
metal conduit to protect very low voltage signals
WIRING transmitted to or from a computer or programmable
controller.
Install the line and load conductors sized in
accordance with the NEC. Use copper wire only Lugs furnished with the MCC and its components
for control terminations. Use copper wire only are for Class B and Class C stranding. Verify the
for power terminations unless they are marked compatibility of wire size, type. and stranding with
"CUIAL". Use conductors with a temperature rating the lugs furnished. Where they are not compatible,
of 75°C or higher, but regardless of the insulation change the wire or lugs accordingly. If crimp lugs are
temperature rating select the wire size on the basis used, crimp with the tools recommended by the
of 75°C wire ampacity. Using a higher temperature manufacturer.
a
wire ampacity table often res;lts in smallercross-
Use care in stripping insulation to avoid nicking or
ringing the metal.
section of copper available for carrying heat away
from terminals. All field wiring to control units should be made in
accordance with the wiring drawings that are
Install insulated wire and cable at a temperature furnished with the control center. Load and control
sufficiently warm to prevent the insulation from wiring can be brought in through the upper andlor
cracking or splitting. lower horizontal wireways. Determine the type of
wiring installed in the control center (NEMA Type B
When more than one condurt 8s run from a common or C) and proceed per the following appropriate
source or to a common load, be sure to have each paragraph.
I condu~tcarry conductors from each phase and the
same number of conductors per phase If the phase The phase sequence of the power circuit load
terminals (left-to-right: T I , T2, T3) i n units
i mounted on the rear side of the MCC is opposite Each male portion of the pull-apart terminal block
to that of the load terminals i n units mounted on has two cavities adjacent to the center terminal
the front side of a back-to-back MCC. To obtain screw to accept the blade of an electrician's
the same direction of rotation for a motor screwdriver used to cam the block into and out of
connected to a rear-mounted unit as for one engagement. Each male portion also has a rear slot
connected to a front-mounted unit re-label the that can engage the edge of the unit frame where it
terminals i n the rear-mounted unit: 13, . T2.. T I .. can be mounted for ease in trouble-shooting.
and wire accordingly. Refer t o the warning
sticker supplied with rear-side units. NEMA TYPE C WIRING
When making connections to the load terminals, Each control unit is factory assembled with devices
be sure to leave sufficient slack i n the wires s o inter-wired within the unit. In addition, all control
that the unit can be withdrawn t o the detent wiring is carried to unit terminal blocks on the side of
position for maintenance. See page 20. the unit and from these unit blocks, along with load
wiring through Size 3, to master terminal blocks
NEMA TYPE B WIRING located at the top or bottom of the structure. See
Figure 16. Master terminal blocks can be either fixed
Each control unit is factory assembled with devices or drawout mounted. In the drawout design the
inter-wired within the unit. In addition, all control terminal blocks are rack mounted to permit
wiring is carried to unit terminal blocks mounted on withdrawal of the entire assembly for ease of wiring
the right-hand side of the unit. See Figure 15. Bring during installation and maintenance. Bring field
the field wiring of control wires from a horizontal wiring from the horizontal wireway to the master
wireway into the vertical wireway on the right-hand terminal blocks except for load wiring larger than
side of the applicable control unit and terminate Size 3. These latter load wires should be carried into
them at the unit terminal blocks. Bring load wiring the vertical wireway and under the bottom right-hand
from the vertical wireway, under the bottom right- side of the unit to terminations within the unit.
... hand side of the unit, to terminations within the unit.
1
ENGAGING PULL-APART TERMINAL
BLOCKS
i
Part 5
INCOMING LINE CONNECTIONS
OVERCURRENT PROTECTION
-- .--.
,?a:!",
SHORT-CIRCUIT BRACING
i #*&xu,:
Part 6
OVERCURRENT PROTECTION DEVICES
DEVICE SELECTION
Articles 240 and 430 of the NEC contain the rules for
selecting fuses, circuit breakers and overload relays
by type and by voltage and ampere rating. Follow
these rules for feeder circuits, and the instructions
attached to the inside of the left-most vertical
wireway door, for motor branch circuits. Select and 75 mprre
o " ~ ~ ~ s n~mevreovc,8m*
CXW.C%LCma
install overload relay current elements (heaters) CnRo.C30IONls
C306 Overload Relays are provided on Freedom C306 OVERLOAD RELAY SETTING
Starters. Four sizes are available for overload
..
'\ protection up to 114 amperes. Features include: FLA DIAL ADJUSTMENT - For motors having a
'1
Selectable Manual or Automatic Reset operation. 1.15 service factor. rotate the FLA adjustment dial to
Interchangeable Heater Packs adjustable S 4 % correspond to the motor's FLA rating. Estimate the
to match motor FLA and calibrated for use with dial position when the motor FLA falls between two
1.0 and 1.15 service factor motors. letter values as shown in Fig. 23.
Heater packs for 32 ampere overload relay will
mount in 75 ampere overload relay - useful in de- For motors having a 1.0 service factor, rotate the
rating applications such as jogging. FLA dial one-half position counterclockwise (CCW).
Class 10 or 20 heater packs. (Fig. 24) Use Class
10 heaters with fusible or thermal magnetic MANUALIAUTOMATIC RESET -The overload relay
breaker disconnects only. is factory set "M" for manual reset operation as
Bimetallic, ambient compensated operated. Trip shown in Fig. 23. For automatic reset operation, turn
free mechanism. the reset adjustment dial to the "A" position.
Electrically isolated NO - NC contacts (pull
RESET button to test). Automatic reset is not intended to two-wire devices.
Overload trip indication.
I_I
Part 7
OVERLOAD RELAY HEATER SELECTION
HEATER SELECTION AND INSTALLATION To install:
Note: Before installing heater packs, refer to the C. Adjust the FLA adjustment dial to
motor nameplate for F L A (full load amps) and the motor nameplate F L A (full
service factor (1.5 or 1.0). Select the heater pack load amps).
from the proper table on this page.
THE OVERLOAD IS NOW SET FOR 3.11 ~ m i s .
FIC!~
1.15 SERVICE FACTOR.
TTT
MAXIMUM RATINGS
73
Use 75°C copper conductors only
Max. Wire Size - 3 AWG
0 NOTE: After the above reference settings have
been made, rotate the FLA dial one position
258 312 355 419 H2007B
clockwise for these heaters (see table). If less than
one position is available, rotate dial to maximum. 388 468 547 H2WB
This note does not apply when these heaters are MAXIMUM RATINGS
NEMA Size 6 = 540 Amperes
A FLA rating marked on heater pack multiplied
by a transformation ratio. For motor FLA values
not listed, turn the dial clockwise for higher or
counterclockwise for lower ratings.
3 90 14
4* I 135 I I
Minimum Wire Size - 6 AWG
0 NOTES:
Part Windina Starters - Select heater oacks for
50% of the motor FLA
Wye Delta Starters - Select heater packs for 58%
motor FLA
4 For motor FLA values not listed, turn the dial
clockwise for higher or counterclockwise for
lower ratings.
. ...... ....- ..\ .
LB. 8926-1A
Part 8
INSPECTION PRIOR TO ENERGIZING
Before energizing the motor control center attempt to defeat the rejection feature on the
(MCC), conduct a thorough inspection to make fuse clip, when provided.
certain that all foreign materials such as tools, 14. Do not operate a current transformer with its
scraps of wire and other debris are removed secondary circuit open. Insure current
from all units and the structure. Remove any transformer is connected to a load, or a
accumulation of dust and dirt with a vacuum secondary shorting bar is installed.
cleaner. 15. To prevent possible damage to equipment or
All circuit connections are tightened at time of injury to personnel, check to insure that all parts
assembly by power-driven tools with controlled and barriers that may have been removed
torque. However, the vibrations experienced in during wiring and installation have been properly
transit may loosen some of these connections. reinstalled.
Check at least 10% of the total connections for a TABLE 8-1 DRIVING TORQUE
tight connection. Should this spot-check Control Wiring:
reveal some loose connections, it will be
necessary to check all connection points.
The connections to be checked include bus
hardware, circuit breaker and switch terminals.
Auxiliary Contact
contactor and relay terminals and terminal
blocks. Always check the incoming line
connections. Tighten to the torque values shown
in Tables 8-1.
Remove all blocks or other temporary holding
means used for shipment from all component
devices in the MCC interior.
Check the enclosure to see that it has not been
I
14-10 35 Degrees C
damaged so as to reduce electrical spacings. C306GN3 and
Compare all circuits for agreement with the sire 2 Contactor
. .
wiring diagrams which accompany the MCC. Be I 3-2 so I
sure that each motor is connected to its intended
starter.
Make certain that field wiring is clear of live 8 40
busses and physically secured to withstand the 6 .4 45
1-7 50 Use 75
effects of fault current.
Size 3 Sock C~PW
Degrees C
Check to determine that all grounding 'Opper Or
Socket flb-in.!
connections are made properly. 3116
aluminum
Check all devices for damage. Make all I IA lZO
90"
conductors
necessary repairs or replacements, prior to
energizing.
Size N and Size 4 275 Ib-in.
9. Manually exercise all switches, circuit breakers.
and other operating mechanisms to make Fused Switches:
certain that they are properly aligned and 3o~mp Fuse ~ s s .............................................
y 25 lb.-in.
operate freely. 6o~mp Fuse ~ s s .............................................
y 50 1b:n
i.
10. Test anv wound-fault ~rotectionsvstems that 100 Amo Fuse Assv ............................................ 50 1b.-in.
were furnisLed. 200 Amp Fuse Assy ........................................ 300 1b:n
i.
11. Set any adjustable current and voltage trip 400 Amp Fuse Assy ........................................ 300 Ib-in.
mechanisms to the proper values. 600 Amp Fuse Assy ...................................... 300 Ib-in.
12. Ensure that overload relay heater elements are BREAKERS- Refer to Torque Values on Breaker Case
installed and selected to the full-load current
shown on the nameplate of each motor.
13, Install power circuit fuses in the fusible switches
in accordance with NEC application
req~~irements.Make sure that fuses are
,i
... completely inserted in the clips provided. Do not
I
16. Conduct an electrical insulation resistance test to automatic shutters. See Part 9 for adjustments
make sure that the MCC and field wiring are free of this mechanism.
from short circuits and grounds. Do this test 18. Install covers. close doors, and make certain that
phase-to-phase, phase-to-ground, and phase-to- no wires are pinched and that all enclosure parts
neutral, with the switches or circuit breakers are properly aligned and tightened.
opened. 19. Turn all circuit breakers and fusible switches to
17. If the MCC contains a labyrinth vertical bus the OFF position before energizing the bus.
barrier system, verify the operation of the
Part 9
UNlT INSTALLATION AND ADJUSTMENT
DOOR REMOVAL AND INSTALLATION
I.B. 8926-1A
Part 10
MAINTENANCE
PREVENTIVE MAINTENANCE Good conduction requires clean, tight joints, free of
contaminants such as dirt and oxides.
Preventive maintenance should be a program, a
scheduled periodic action that begins with the Good insulation requires the absence of carbon
installation of the equipment. At that time, specific tracking and the absence of contaminants such as
manufacturer's instruction literature should be salt and dust that become hydroscopic and provide
consulted, then stored for future reference. Follow-up an unintended circuit between points of opposite
maintenance should be at regular intervals, as polarity.
frequently as the severity of duty justifies. Time
intervals of one week, or one month, or one year
may be appropriate, depending on the duty. It is also
desirable to establish specific check lists for each
control, as well as a logbook to record the history of
incidents. A supply of renewal parts should be
obtained and stored.
Fia. 36
j (G Rectangular slot for scissors. ( C ) Rotate lock plate for one to three 318 in.
diameter padlock hasp locks.
(0)One 114 in. or 5116 in. diameter padlock hasp.
I.B. 8926-IA
Start of Sewice The contact surface will have a blue coloring. The geometric form of the contact is
unchanged. The sharp outer corners will be rounded with small silver beads. (See
Figure 39).
Intermediate Service The coloring changes to brown or black with distributed small silvery white areas. The
to End of Service Life surface has a finely chiselled appearance. Material transfer causes small peaks and
valleys in the contact button surface. (See Figure 40).
Irregular Contour or One corner of a contact may wear more quickly than the other three corners. This wear
Slantwise Wear is normally due to misalignment of the moving and stationary contacts. Contacts
should be replaced if it is apparent that one contact is nearly making direct contact with
the contact carrier.
) Large Beads of S~lver Breaking an excessive current
On Edges of Contacts
Welded Spot (Core of Making an excessive current. High frequency of operation, i.e., jogging
Smooth. Shining Silver
Surrounded by a
RENEWAL PARTS
Control Center renewal parts identified by part or
When ordering renewal control center parts, give the style number are detailed in cutler-~ammer
complete nameplate reading. Always give the name Renewal Parts Data. The nomenclature to identify
of the part wanted, the part, catalog or style number these parts is shown in Figures 2 and 41. The most
of the individual apparatus on which it is to be used, common renewal parts for components are shown in
and the order number of the complete motor control TablelO-I.
center.
MAGNET COILS
120V60HzorllOV50Hz
34,
mmvl Wlnr..
CROSS SCCTION
CROSS SCCTION
mC4. Y*sma
Bonou ylcw
mmuir ma
(U
"Dr. 1 YO *
-
In
S I I rillc Vieis, A i x r " ~ h , lo, rcniu, dimm,ion, SEC lid^ "~LI. A. T.i"~l,lforv~nirri,,i",e"iio"r
-
24 Inches Wide, 16 Inches Deep
Front Mougete~yJ,y ( 4 7 1 0 ~ 3 3 )
TOP VlCW
24 Inches Wide. 21 Inches Deen
TOP VlCW
W -A,
mm
n
CROSS SECTION
CROSS SNXION
"= -I +------
i-
rnC."UY rn
OTTOM VlEW
S W K .
>It
5.-
--++--='~04k-
6
--
mmc -
Mrc xYlDm s
.
asl
c
BOTTOM VlCW
.
I Minimum icnglhofm~orbolLili.00".I . 1 8 - 1 6 ~ ~ 5 c o q l x d d 3 I I b i l l
A For"."seismic. mo"n,~viU,2mntcrbolir aercn.10,ui.
SlDE VIEW A
Conenlon Notes
mrrim"," hlCC.
"nmruiiird i o " d " i l l p x e >,,hi bominaflll~
5 This mnduil rjucr ir nor rriommendrd \\ibcn r neuinl bur ir ialuind. U l h i m i r rvrilablr
Starters:
Size 5, Non-Reversing and Reversing, vacuum.. ............................. .I.L. 17087
Size 6, Non-Reversing and Reversing, vacuum ............................... I.L. 17089
Contactors:
Size 5, Non-Reversing and Reversing, vacuum ................................ I.L. 16999
Size 5. Non-Reversing and Reversing, vacuum. ............................... I.L. 17088
Circuit Breakers:
Series C, F-frame .................................................................... I.L. 29ClOl
Series C, J-frame .................................................................... I.L. 29C103
Series C, K-frame ................................................................... I.L. 29CI 04
Series C, L-frame ..............
Series C, N-fram
Series C, R-fram
Transfer Switche
User's Manual
I Safety
A Dangerous voltage warning warns of high voltage which can cause physical injury
andlor damage to the equipment.
General warning warns about conditions, other than those caused by electricity,
which can result in physical injury and/or damage to the equipment.
A WARNING! Even when the motor is stopped, dangerous voltage is present at the
power circuit terminals U1, V1, W1 and U2, V2, W2 and, depending on the frame
size, UDC+ and UDC-, or BRK+ and BRK-.
WARNING! Even when power is switched off from the input terminals of the
ACS550, there may be dangerous voltage (from external sources) on the terminals
of the relay outputs R 0 1...R03.
A WARNING! When the control terminals of two or more drives are connected in
parallel, the auxiliary voltage for these control connections must be taken from a
single source which can either be one of the drives or an external supply.
6 ACS550 User's Manual
A WARNING! Do not control the motor with the disconnecting device (disconnecting
means); instead, use the control panel start and stop keys a m,
and or
commands via the 110 board of the drive. The maximum allowed number of charging
cycles of the DC capacitors (i.e. power-ups by applying power) is six in ten minutes.
.)
A WARNING! The ACS550-011U1 is not field repairable. Never attempt to repair a
malfunctioning drive; contact the factory or your local Authorized Service Center for
replacement.
WARNING! The ACS550 will start up automatically afler an input voltage interruption
if the external run command is on.
A WARNING! The heat sink may reach a high temperature. See chapter Technical
data on page 259.
Note: For more technical information, contact the factory or your local ABB
representative.
Safety
ACS550 User's Manual
Table of contents
Safety
Use of warnings and notes
Table of contents
lnstallation
Installation flow chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Preparing for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installing the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Control panels
About control panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
...
Compat~b~l~ty ................................................... 41
Assistant Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
BasicControlPanel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Application macros
ABB Standard macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
3-wiremacro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Alternate macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Motor Potentiometer macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Hand-Automacro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
PID Control macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
PFCmacro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Torque Control macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Connection example of a two-wire sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
User parameter sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Macro default values for parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Parameters
Complete parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Complete parameter descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Embedded fieldbus
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Mechanical and electrical installation . EFB . . . . . . . . . . . . . . . . . . . . . . . . . 190
Communication set-up . EFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Activate drive control functions . EFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Table of contents
ACS550 User's Manual
Fieldbus adapter
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical and electrical installation . FBA
Communication set-up . FBA . . . . . . . . . . . .
Activate drive control functions . FBA . . . . .
Feedback from the drive . FBA . . . . . . . . . .
Diagnostics . FBA . . . . . . . . . . . . . . . . . . . .
ABB Drives profile technical data . . . . . . . . .
Generic profile technical data . . . . . . . . . . . .
Diagnostics
Diagnosticdisplays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Correcting faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Correcting alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Maintenance
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Main fan replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
Internal enclosure fan replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Controlpanel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Technical data
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Input power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Motorconnections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
Brakecomponents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
Controlconnections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
Degrees of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
Ambientconditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
Applicablestandards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
CEmarking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
C-Tick marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
ULICSAmarkings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
IECIEN 61800-3 (2004) Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Compliance with the IECIEN 61800-3 (2004) . . . . . . . . . . . . . . . . . . . . . . . . . 293
Liability limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
Product protection in the USA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
Table of contents
ACS550 User's Manual
Index
Contact A 6 6
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
Producttraining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . . . . . . . . . . . . 309
Table of contents
ACS550 Useis Manual
Table of contents
ACS550 Useis Manual
Installation
Note: The installation must always be designed and made according to applicable
local laws and regulations. ABB does not assume any liability whatsoever for any
installation which breaches the local laws andlor other regulations. Furthermore, if
the recommendations given by ABB are not followed, the drive may experience
problems that the warranty does not cover.
+I
t
I CHECK installation Check installation on page 29
+I
Drive identification
Drive labels
To determine the type of drive you are installing, refer to either:
serial number label attached on upper part of the chokeplate between the
mounting holes, or
ACssswr.OaAG-4 rt Type code
- Serial number
type code label attached on the heat sink- on the right side of the drive cover.
Two examples of the type code label are given below.
P
WW PWPM
0.. sw M
4.0J3.0 kW
1111111l
!l111861MlIliUllill~l
-*I065006704*t-- Serial number
ACS550-01-08A8-4 c--Type code
1 IIIII~IIIIII~
ll~liAUII~III~IIIIII
CS550-U1-031 - 2 -4.- Type code
ACS550 User's Manual 13
Type code
Use the following chart to interpret the type code found on both the type code and
the serial number label.
ACS550-01-08A8-4+J404+ ...
Voltage rating I
2 = 208 ...240 VAC
4 = 380 ...480 VAC
6 = 500 ...600 VAC
Options I
Examples of options:
6055 = IP54 I UL type 12 (no specification = IP21 I UL type 1)
OJ400 = No control oanel
J404 = ACS-CP-C'B~SIC Control Panel
L511 = OREL-01 Relay output extension
K451 = RDNA-01 DevlceNet
K452 = RLON-01 LonWorks
K454 = RPBA-01 PROFIBUS DP
Installation
ACS550 User's Manual
Motor compatibility
The motor, drive and supply power must be compatible:
Motor
Verify Reference
specification
Motor type 3-phase induction motor -
Nominal current Motor value is within this . Type code label on drive, entry for Output Izhd,
range: 0.2 ...2.0. 12hd or
('2hd = drive
current)
- Type code on drive and rating table in chapter
Technical data on page 259.
Nominal frequency 10...500 Hz -
Voltage range Motor is compatible with 208...240 V (for ACS550-XI-XXXX-2) or
the ACS550 voltage range. 380...480 V (for ACS550-XI-XXXX-4) or
500...600 V (for ACS550-U1-XXXX-6)
insulation 500 ...600 V drives: Either For ACS550-U1-XXXXS
the motor complies with
NEMA M G I Part 31. or a
duldt filter is used between
the motor and drive.
Tools required
To install the ACS550 you need the following:
screwdrivers (as appropriate for the mounting hardware used)
wire stripper
tape measure
drill
for installations involving ACS550-U1, frame sizes R5 or R6 and IP54 1 UL type
12 enclosures: punch for creating conduit mounting holes
for installations involving ACS550-U1, frame size R6: appropriate crimping tool
for power cable lugs. See section Power terminal considerations - R6 frame size
on page 269.
mounting hardware: screws or nuts and bolts, four each. The type of hardware
depends on the mounting surface and the frame size:
Installation
ACS550 Useis Manual 15
Confirm that the enclosure is appropriate, based on the site contamination level:
IP21 IUL type 1 enclosure: The site must be free of airborne dust, corrosive
gases or liquids, and conductive contaminants such as dripping water,
condensation, carbon dust and metallic particles.
IP54 1 UL type 12 enclosure: This enclosure provides protection from airborne
dust and light sprays or splashing water from all directions.
If, for some reason, an IP21 drive needs to be installed without the conduit box or
cover, or an IP54 drive without the conduit plate or hood, see the note in chapter
Technical data, page 292.
Installation
16 ACS550 User's Manual
WARNING! Before installing the ACS550, ensure the input power supply to the drive
is OR.
Note: Frame sizes R3 and R4 have four holes along the top. Use only two. If
possible, use the two outside holes (to allow room to remove the fan for
maintenance).
Note: ACS400 drives can be replaced using the original mounting holes. For R1 and
R2 frame sizes, the mounting holes are identical. For R3 and R4 frame sizes, the
inside mounting holes on the top of ACS550 drives match ACS400 mounts.
Installation
ACS550 User's Manual
3 .
IP54 / UL type 12
For the IP54 1 UL type 12 enclosures, rubber plugs are required in the holes
provided for access to the drive mounting slots.
1. As required for access, remove the rubber plugs.
Push plugs out from the back of the drive.
2. R5 & R6: Align the sheet metal hood (not shown) in
front of the drive's top mounting holes. (Attach as
part of next step.)
3. Position the ACS550 onto the mounting screws or
bolts and securely tighten in all four corners.
Installation
ACS550 Useis Manual
Wiring overview
ConduiVGland l i t
Wiring drives with the IP21 IUL type 1 enclosure requires a conduitlgland kit with the
following items:
conduitlgland box
five (5) cable clamps (ACS550-01 only)
- screws
cover.
The kit is included with IP21 IUL type 1 enclosures
Wiring requirements
WARNING! Ensure the motor is compatible for use with the ACS550. The drive must
be installed by a competent person in accordance with the considerations defined in
section Preparing forinstallation on page 12. If in doubt, contact your local ABB
sales or service office.
To locate input power and motor connection terminals, see section Power
connection diagrams on page 20. For specifications on power terminals, see
section Drive's power connection terminals on page 268.
For corner grounded TN systems, see section Cornergrounded TN systems on
page 267.
For IT systems, see section I T systems on page 268.
ACS550 User's Manual 19
For frame size R6, see section Power terminal considerations - R6 frame size on
page 269 to install the appropriate cable lugs.
For drives using braking (optional), refer to the following, as appropriate:
Frame size Terminal Description Braking accessory
R1, R2 BRK+. BRK- Braking resistor Braking resistor. See section Brake
components on page 277.
R3, R4, R5. R6 UDC+. UDC- DC bus Contact your ABB representative to
order either:
braking unit or
- chopper and resistor
Installation
ACS550 User's Manual
Panel connector
FlashDrop option
X I -Digital inputs
(and 24 V aux. voltage output) Power LED (green)
X I -Relay outputs
Optional module 2
R51R6 differ.
Frame Terminal
Brake options
size labels
R1. R2 BRK+, BRK- Brake resistor
R3. R4 UDC+, UDC- Braking unit
I I 1.Chopper and resistor II
Installation
ACS550 User's Manual 21
The following diagram shows the power and ground terminal layout for frame sizes
R5 and R6
R5 R6
Installation
ACS550 User's Manual
15 1 Dl3
1
16 Dl4 I Digital input 4, programmable. ~efault' =constant speed sel (code).
1
17 Dl5 1Digital input 5, programmable. ~efault'= ramp pair selection (code).
18 1 Dl6 I Digital input 6, programmable. ~efault'= not used.
ACS550 User3 Manual 23
XI Hardware description
1 19 1 ROlC I --, I Relay output 1, programmable. ~ e f a u l=t ~Ready
z0 ROIA Maximum: 250 VAC 130 V DC, 2 A
Minimum: 500 m W (12 V, 10 mA)
21 R O l B ,
- n Relay output 2, programmable. ~efault'= Running
3
.25
23 R02A
24 R02B
R03C
- Maximum: 250 VAC 130 V DC. 2 A
Minimum: 500 m W (12 V. 10 mA)
Note: For safety reasons the fault relay signals a "fault" when the ACS550 is
powered down.
WARNING! All ELV (Extra Low Voltage) circuits connected to the drive must be used
within a zone of equipotential bonding, i.e. within a zone where all simultaneously
accessible conductive parts are electrically connected to prevent hazardous voltages
appearing between them. This is accomplished by a proper factory grounding.
The terminals on the control board as well as on the optional modules attachable to
the board fulfil the Protective Extra Low Voltage (PELV) requirements stated in
EN 50178, provided that the external circuits connected to the terminals also fulfil
the requirements and the installation site is below 2000 m (6562 ft)
You can wire the digital input terminals in either a PNP or NPN configuration
PNP connection (source) NPN connection (sink)
Installation
ACS550 Useis Manual
WARNING! Check the motor and motor cable insulation before connecting the drive
to input power. For this test, make sure that motor cables are NOT connected to the
drive.
1. Complete motor cable connections to the motor, but NOT to the drive output
terminals (U2, V2, W2).
2. At the drive end of the motor cable, measure the insulation
resistance between each motor cable phase and Protective
Earth (PE): Apply a voltage of 1 kV DC and verify that
resistance is greater than 1 Mohm.
Installation
ACS550 Useis Manual
7. Connect the pig-tail created from the motor cable screen to the GND terminal.
8. Install conduitlgland box and tighten the cable clamps.
9. Install the cable clamp(s) for the control cable(s).
(Powerlrnotor cables and clamps not shown in the
figure.)
10. Strip control cable sheathing and twist the copper
screen into a pig-tail.
11. Route control cable(s) through clamp(s) and tighten
clamp(s).
12. Connect the ground screen pig-tail for digital and
analog 110 cables at X I - I . (Ground only at drive
end.)
13. Connect the ground screen pig-tail for RS485 cables
at XI-28 or XI-32. (Ground only at drive end.)
14. Strip and connect the individual control wires to the
drive terminals. See section Control terminals table
on page 22.
15. Install the conduit/gland box cover (1 screw).
Installation
ACS550 Useis Manual
Installation
ACS550 Useis Manual
Note: For R5 frame size, the minimum power cable size is 25 rnm2 (4 AWG).
For R6 frame size, refer to section Power terminal considerations - R6 frame size on
page 269.
Installation
ACS550 Usefs Manual
lnslallation
ACS550 User's Manual
Check installation
Before applying power, perform the following checks.
V' Check
Installation environment conforms to the drive's specifications for ambient conditions.
The drive is mounted securelv.
I
I Space around the drive meets the drive's specifications for cooling.
The motor and driven equipment are ready for start.
For IT systems and corner grounded TN systems: The internal EMC filter is disconnected
(screws EM1 8 EM3 or F1 & F2 removed).
The drive is properly grounded.
The input power (mains) voltage matches the drive nominal input voltage.
The input power (mains) connections at U1, V1 and W1 are connected and tightened as
specified.
The i n.~ u.Dower
t (mains) fuses are installed.
1
I The motor connections at U2. V2 and W2 are connected and tightened as specified.
The motor cable is routed away from other cables.
II NO Dower factor ComDensation ca~acitorsare in the motor cable.
The control connections are connected and tightened as specified.
I NO tools or foreign objects (such as drill shavings) are inside the drive.
NO alternate power source for the motor (such as a bypass connection) is connected - no
voltage is applied to the output of the drive.
lnstallation
ACS550 User's Manual
IP54 / UL type 12
1. Align the cover and slide it on.
2. Tighten the captive screws around
the edge of the cover.
3. Slide the hood down over the top
of the cover. (Only needed for UL
type 12 installations.)
4. Install the two screws that attach
the hood. (Only needed for UL
type 12 installations.)
5. Install the control panel.
6. Optional: Add a lock (not supplied) to secure the control panel window.
7. Continue with start-up. See chapter Start-up, control with 110 and ID Run on page
31.
Installation
ACS550 User's Manual
lo I Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
there is a risk of damage in case of incorrect direction of rotation, or
an ID Run needs to be performed during the drive start-up. ID Run is essential only in
applications that require the ultimate in motor control accuracy.
pp y lnpu power.
The Basic Control Panel powers up into the Output mode.
The Assistant Control Panel asks if you want to run the Start-
p Assistant. If you press @,the Start-up Assistant is not
un, and you can continue with manual start-up in a similar
anner as described below for the Basic Control Panel.
IRE.
The general parameter setting procedure:
1. To go to the Main menu, press if the bottom line shows OUTPUT;
othelwise press repeatedly until you see MENU at the bottom. :M
e FWO
2. Press keys 1
- until you see "PA? and press
Enter the motor data from the motor nameplate: Note: Set the motor data to
exactly the same value as on
G ABB Motors CE @ the motor nameplate. For
3 - motor M2AA 200 MLA 4
IEC 200 MiL 55 - example, if the motor nominal
speed is 1470 rpm on the
nameplate, setting the value of
parameter 9908 MOTOR NOM
SPEED to 1500 rpm results in the
wrong operation of the drive.
380 V
supply
voltage
/
PAR FWD
PAR FWD
II PAR FWD
PAR FWD
I I
" ~ . ~ WITH10
I I A RUN
.---.
. T SELECTION
I O N
L .
.
As stated above, the identification magnetization is performed only if:
. .
-----.--
0 (OFFIIDMAGN) :
L
.. II
.
parameter 9904 is set to 1 (VECTOR:SPEED) or 2 (VECTOR:TORQ),
or
parameter 9904 is set to 3 (SCALAR:FREQ) and parameter 2101 is set to 3 (SCALAR
FLYST)
or 5 (FLY+ BOOST).
Press key @ to switch to local control (LOC shown on the left).
Press @ t o start the drive. The motor model is now calculated by magnetizing the motor
for 10 to 15 s at zero speed (motor not rotating).
I I PAR FWD
PAR FWD
01 The starl-uo is now comoleled. However. ~tmiaht " be u s e f ~ar, 1,-oc A n n ?---
I I this stage tb set the required'by your application
and save the settings as a user parameter set as instructed in I
11 YYuL
II I/ section Userparameter sets on page 81.
. .:':-.
.-...-..--
,
.-.. ., ., , '---I
/
1 Check the installation. See the checklist in chapter Instaliation, page 29.
1 Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
there is a risk of damage in case of incorrect direction of rotation, or
an ID Run needs to be performed during the drive start-up. ID Run is essential only in
applications that require the ultimate in motor control accuracy.
..j
Press @ if you do not want to run the Start-up Assistant.
9901 LANGUAGE
I I The Start-up Assistant now guides you through the set-up tasks, 1 ~ R E M C P A R EDIT II
starting with the motor set-up. Set the motor data to exactly the
same value as on the motor nameplate.
Scroll to the desired parameter value with keys 1-- and
press to accept and continue with the Start-up Assistant.
Note: At any time, if you press , the Start-up Assistant is
stopped and the display goes
After completing a set-up task, the Start-up Assistant suggests the REM P I C H O I C E
DO y ~ u wan% t o
next one. contlnue w i t h
ap l i c a t i o n s e t u p ?
Press (when -is highlighted) to continue with the
suggested task.
Press key to highlight and then press to move to
the following task without doing the suggested task.
Press @ to stop the Start-up Assistant.
Ensure that the control connections are wired according to the See section ABB Standard
connection diagram given for the ABB Standard macro. macro on page 72.
Ensure that the drive is in remote control. Press key @ to switch In remote control, the panel
between remote and local control. display shows text REM.
I Basic Control Panel: Text FWD starts flashing slowly. OUTPUT '1
ID Run procedure
The general parameter setting procedure is not repeated here. For Assistant Control
Panel see page 49 and for Basic Control Panel page 67 in chapter Controlpanels.
A WARNING! The motor will run at up to approximately 50 ... 80% of the nominal speed
during the ID Run. The motor will rotate in the forward direction. Ensure that it is
safe t o run the motor before performing the ID Run!
/ /
q Decouple the motor from the driven equipment.
I
Check that the values of the motor data parameters 9905 ... 9909 are equivalent to those on
the motor nameplate, as shown in the steps on page 33.
lo 1
0
If parameter values (Group 01: OPERATING DATA to Group 98: OPTIONS) are changed
before the ID Run, check that the new settings meet the following conditions:
2001 MINIMUM SPEED 5 0 rpm
I
q 2002 MAXIMUM SPEED > 80% of the motor rated speed
0 2017 MAX TORQUE 1 > 50% or 2018 MAX TORQUE 2 > 50%, depending on which limit is in
use according to parameter 2014 MAX TORQUE SEL.
I / Check that the Run Enable signal is on (parameter 1601).
I
1°1 Ensure that the panel is in local control (LOC shown on the left Iat the top). Press key @ to
switch between local and remote control.
m
CANCEL 0o:oo m
If you want to monitor actual values during the ID Run, go to
the Output mode by pressing @ repeatedly until you get 0.0 Hz
there.
0.0 %
DIR 00:oo m
I PAR FWD
PAR an FWD
If you want to monitor actual values during the ID Run, go to
the Output mode by pressing repeatedly until you get
there. OUTPUT
shown.
I Control panels
Compatibility
The manual is compatible with the following panel versions:
Basic Control Panel: ACS-CP-C Rev. K
Assistant Control Panel (Area 1): ACS-CP-A Rev. Y
Assistant Control Panel (Area 2): ACS-CP-L Rev. E
Assistant Control Panel (Asia): ACS-CP-D Rev. M
See page 45 for how to find out the version of your Assistant Control Panel. See
parameter 9901 LANGUAGE to see the languages supported by the different Assistant
Control Panels.
Control panels
ACS550 User's Manual
Features
The Assistant Control Panel features:
alphanumeric control panel with an LCD display
language selection for the display
Start-up Assistant to ease drive commissioning
copy function - parameters can be copied to the control panel memory for later
transfer to other drives or for backup of a particular system.
context sensitive help
real time clock
Overview
The following table summarizes the key functions and displays on the Assistant
Control Panel.
No. Use
1 Status LED -Green for normal operation. If LED is flashing, or red, see
section Diagnostfc displays on page 243.
2 LCD display - Divided into three main areas:
a. Status line - variable, depending on the mode of operation, see section
Status line on page 43.
b. Center- variable; in general, shows signal and parameter values, menus 01
lists. Shows also faults and alarms.
c. Bottom line - shows current functions of the two soft keys and, if enabled,
the clock display.
3 1Soft kev 1 -Function deoends on the context. The text in the lower left corner
of the LCDdisplay indicates the function.
4 Soft key 2 - Function depends on the context. The text in the lower right
corner of the LCD display indicates the function.
5
.uScrolls
p-
up through a menu or list displayed in the center of the LCD display.
Increments a value if a parameter is selected.
.Increments
I ~ o l d i the
the reference value if the upper right corner is highlighted.
n ~ key down changes the value fastei
. .
6 I~own-
Scrolls down through a menu or list displayed in the center of the LCD
display.
Decrements a value if a parameter is selected.
. - -
Decrements the reference value if the upper riqht corner is hiqhliqhted.
l ~ o l d i the
n ~ key down changes the value faster.-
7 ILOCIREM - Changes between local and remote control of the drive.
1 8 IHelw - Disolavs context sensitive infomlation when the kev is Dressed. The I
info'rmatio" dLplayed describes the item currently highlighted'in the center of
the display.
9 STOP - Stops the drive in local control.
10 START- Starts the drive in local control.
Control panels
ACS550 User's Manual
Status line
The top line of the LCD display shows the basic status information of the drive.
LOC & M A I N MENU---- 1
00 @ 00 0 @
No. l ~ i e l d l~lternatives Significance
1 Icontrol location ILOC IDrive control is local, that is, from the control
panel.
REM IDrive control is remote, such as the drive I10 or
-
Rotating arrow [Drive is running at setpoint.
I .,
Dotted stationary arrow Istart command is present, but the motor is not
running, e.g. because start enable is missing.
3 Panel operation Name of the current mode
mode Name of the list or menu shown
Name of the operation state, e.g. PAR EDIT.
4 l~eferencevalue I 1. Reference value in the Outout mode
or number of the Number of the highlighted item, e.g mode,
selected item parameter group or fault.
Operation
You operate the control panel with menus and keys. The keys include two context-
sensitive soft keys, whose current function is indicated by the text shown in the
display above each key.
You select an option, e.g. operation mode or parameter, by scrolling the and a
arrow keys until the option is highlighted (in reverse video) and then pressing
the relevant soft key. With the right soft key you usually enter a mode, accept an
option or save the changes. The left soft key is used to cancel the made changes
and return to the previous operation level.
The Assistant Control Panel has nine panel modes: Output, Parameters, Assistants,
Changed Parameters, Fault Logger, Clock Set, Parameter Backup, I10 Settings and
Fault. The operation in the first eight modes is described in this chapter. When a fault
or alarm occurs, the panel goes automatically to the Fault mode showing the fault or
alarm. You can reset it in the Output or Fault mode (see chapter Diagnostics).
Control panels
ACS550 User's Manual
Controlpanels
ACS550 Useis Manual 45
Keep key @pressed down while you switch on the power and read the PANEL V E R S I O N I N F O
information. The display shows the following panel information: Panel FW:
ROM CRC: XXXXXXXXXX
Panel FW: panel firmware version F l a s h Rev:
XXXXXXXXXXXXXXXXXXXXX
ROM CRC: panel ROM check sum
Flash Rev: flash content version
Flash content comment.
When you release the a key, the panel goes to the Output mode.
Control panels
46 ACS550 User's Manual
How to start, stop and switch between local and remote control
You can start, stop and switch between local and remote control in any mode. To be
able to start or stop the drive, the drive must be in local control.
Step Action I Display I
.TO switch between remote control (REM shown on the status line) and local
control (LOC shown on the status line), press @.
Note: Switching to local control can be disabled with parameter 1606 LOCAL
LOCK.
The very first time the drive is powered up, it is in remote control (REM) and
controlled through the drive I10 terminals. To switch to local control (LOC) and
control the drive using the control panel, press @.The result depends on
how long you press the key:
If you release the key immediately (the display flashes "Switching to the local
control mode"). the drive stoos. Set the local control reference as instructed
on page 48
- The
If you press the key for about two seconds, the drive continues as before.
drive coDies the current remote values for the runistoo status and the
reference, and uses them as the initial local control settings
T o start the drive in local control, press a. The arrow ( bor 4 ) on the
Status line starts rotating. It
is dotted until the drive
reaches the setpoint.
Control panels
ACS550 User's Manual
Output mode
In the Output mode, you can:
monitor actual values of up to three signals in Group 01: OPERATING DATA
change the direction of the motor rotation
set the speed, frequency or torque reference
adjust the display contrast
start, stop, change the direction and switch between local and remote control
You get to the Output mode by pressing @ repeatedly.
The top right corner of the
display shows the reference
value. The center can be
configured to show up to three
signal values or bar graphs; see
page 50 for instructions on
selecting and modifying the monitored signals.
How to change the direction o f the motor rotation
Control panels
ACS550 Useis Manual
display, pressa. The value changes immediately. It is stored in the drive 50.0 HZ
permanent memoly and restored automatically after power switch-off.
To decrease the value, press w. 10.7 %
DIR 00:oo 1MENU
How to adjust the display contrast
Action Display
If you are not in the Output mode, press @ repeatedly until you get there.
4 9 . 1 HZ
10.7 %
To increase the contrast, press keys 9 and simultaneously.
To decrease the contrast, press keys and simultaneously. 4 9 . 1 HZ
10.7 %
Control oanels
ACS550 User's Manual
Parameters mode
In the Parameters mode, you can:
view and change parameter values
start, stop, change the direction and switch between local and remote control.
How to select a parameter and change its value
press ~ [ L O C E P A R EDIT-
9902 APPLIC MACRO
ABB STANDARD
LIJ
CANCEL 00:oo rn
Specify a new value for the parameter with keys and w.
Pressing the key once increments or decrements the value. Holding the key 9902 A P P L I C MACRO
down changes the value faster. Pressing the keys simultaneously replaces the 3-WIRE
displayed value with the default value.
TEiKEr 00:00 m
T o save the new value, press e.
T o cancel the new value and keep the original, press v.
C~~NCEL
9901 LANGUAGE
Control panels
50 ACS550 User's Manual
3408
m1
i
C1041
IICANCEL
SIGNAL^ PARAM
0O:OO
LOC b P A R E D I T
Signal 1: Change the value of parameter 3401 SIGNAL^ PARAM to the index of
the signal parameter in Group 01: OPERATING DATA (= number of the 3 4 1 5 S I G N A L 3 PARAM
parameter without the leading zero). e.g. 105 means parameter O I O ~ T O R O U E . TORQUE
Value 100 means that no signal is displayed.
Repeat for signals 2 ( 3 4 0 8 SIGNAL^ PARAM) and 3 ( 3 4 1 5 SIGNAL^ PARAM).
I
2. Select how you want the signals to be displayed: as a decimal number or a bar LOC b PAR E D I T
graph. For decimal numbers, you can specify the decimal point location, or use 3404 OUTPUTl DSP FORM
the decimal point location and unit of the source signal [setting ( 9 (DIRECT)]. For DIRECT
details, see parameter 3404.
Signal 1: parameter 3 4 0 4 OUTPUT^ DSP FORM CANCEL 00:00 n X F
Signal 2: parameter 3 4 1 1 OUTPUT2 DSP FORM
Signal 3: parameter 3 4 1 8 OUTPUT^ DSP FORM.
3. Select the units to be displayed for the signals. This has no effect if parameter LOC P, PAR E D I T
34041341113418 is set to 9 (DIRECT). For details. see parameter 3 4 0 5 . 3 4 0 5 OUTPUT1 U N I T
Signal 1: parameter 3 4 0 5 OUTPUT^ UNIT
Signal 2: parameter 3412 OUTPUT^ UNIT
Signal 3: parameter 3419 OUTPUT^ UNIT. CANCEL 00: 00 r3xE-
4. Select the scalings for the signals by specifying the minimum and maximum
display values. This has no effect if parameter 34041341113418 is set to 9 3 4 0 6 OUTPUT1 M I N
(DIRECT). For details, see parameters 3 4 0 6 and 3407. 0 . 0 Hz
Signal 1: parameters 3 4 0 6 OUTPUT^ MIN and 3 4 0 7 0 ~ MAX ~ ~ ~ ~ 1
Signal 2: parameters 3 4 1 3 OUTPUT2 MIN and 3 4 1 4 OUTPUT^ MAX CANCEL 00:00 E Z V r
Signal 3: parameters 3 4 2 0 OUTPUT3 MIN and 3 4 2 1 o u ~ p u r 3MAX. LOC P, PAR E D I T
I/
3 4 0 7 O U T P U T 1 MAX
500.0 HZ 1
Control panels
ACS550 Useis Manual 51
Assistants mode
When the drive is first powered up, the Start-up Assistant guides you through the
setup of the basic parameters. The Start-up Assistant is divided into assistants, each
of which guides you through the task of specifying a related parameter set, for
example Motor Set-up or PID Control. You can activate the assistants one after the
other as the Start-up Assistant suggests, or independently. The tasks of the
assistants are listed in the table on page 52.
In the Assistants mode, you can:
use assistants to guide you through the specification of a set of basic parameters
start, stop, change the direction and switch between local and remote control
How to use an assistant
The table below shows the basic operation sequence which leads you through
assistants. The Motor Set-up Assistant is used as an example.
Step Action Display
1. Go to the Main menu by pressing if you are in the Output mode, otherwise
by pressing @ repeatedly until you get to the Main menu.
ASSISTANTS
CHANGED PAR
If you select the Stahup Assistant, it activates the first assistant, which guides
you through the task of specification of its parameter set as shown in steps 4.
and 5. below. The Stahup Assistant then asks if you want to continue with the
next assistant or skip it - seiect the appropriate answer with keys a and
w, and press +. i f you choose to skip, the Start-up Assistant asks the
same question about the next assistant, and so on.
Control panels
52 ACS550 User's Manual
The table below lists the tasks of the assistants and the relevant drive parameters.
Depending on the selection made in the Application task (parameter 9902 APPLIC
MACRO), the Start-up Assistant decides, which consequent tasks it suggests.
1 Name 1 Description I Set ~arameters I
Language select I Selecting the language 9901
Motor set-up Setting the motor data 9904...9909
Performing the motor identification. (If the speed limits are not in 9910
I the allowed range: Setting the limits:)
Application I Selecting the application macro 1 9902, parameters associated to
the macro
Option modules Activating the option modules Group 35: MOTOR TEMP MEA S
Group 52: PANEL COMM
9802
Speed control Selecting the source for the speed reference 1103
EXTl (If A l l is used: Setting analog input A l l limits, scale, inversion) (1301... 1303, 3001)
Setting the reference limits 1104, 1105
Setting the speed (frequency) limits 2001, 2002, (2007, 2008)
Setting the acceleration and deceleration times 2202, 2203
Speed control Selecting the source for the speed reference 1106
EXT2 (If A l l is used: Setting analog input A l l limits, scale. inversion) (1301... 1303, 3001)
Setting the reference limits 1107. 1108
Torque control Selecting the source for the torque reference 1106
(If A l l is used: Setting analog input A l l limits, scale, inversion) (1301... 1303, 3001)
Setting the reference limits 1107, 1108
PID control I
Setting the torque ramp up and ramp down times
Selecting the source for the process reference
(If A l l is used: Setting analog input A l l limits. scale, inversion)
/
2401, 2402
1106
(1301... 1303, 3001)
1
Setting the reference limits 1107, 1108
Setting the speed (reference) limits 2001, 2002, (2007, 2008)
Setting
.the source and limits for the process actual value I
4016. 4018. 4019
Startistop control Selecting the source for start and stop signals of the two external 1001, 1002
control locations. EXTI and EXT2
Selecting between EXTl and EXTZ 1102
Defining the direction control 1003
Defining the start and stop modes 2101...2103
Selecting the use of Run Enable signal 1601
Timed functions Setting the timed functions Group 36: TIMED FUNCTIONS
Selecting the timed startlstop control for external control locations 1001, 1002
EXTI and EXT2
Selecting timed EXTIIEXTZ control
Activation of timed constant speed 1
Control oanels
ACS550 User's Manual 53
Control panels
ACS550 User's Manual
Go to the Main menu by pressing if you are in the Output mode, otherwise
by pressing @ repeatedly until you get to the Main menu.
ASSISTANTS
CHANGED PAR
9902 APPLIC-MACRO-
EXIT 00:oo m
Select the changed parameter on the list with keysa w. and The
value of the selected parameter is shown below it. Press to modify the
value. 10.0 H z
down changes the value faster Pressing the keys simultaneously replaces the
displayed value with the default value.
Control panels
ACS550 User's Manual
1. Go to the Main menu by pressing if you are in the Output mode, otherwise
by pressing @ repeatedly until you get to the Main menu.
ASSISTANTS
CHANGED PAR
2.
keys and and pressing
starting with the latest fault.
w.
Go to the Fault Logger mode by selecting FAULT LOGGER on the menu with
w, The display shows the fault log
The number on the row is the fault code according to which the causes and
corrective actions are listed in chapter Diagnostics.
3. To see the details of a fault, select it with keys rn and w,and press
"9. FAULT TIME 1
13:04:57
FAULT TIME 2
Control panels
ACS550 User's Manual
ICANCEL00:oo 1 1
and select a suitable format. Press
changes.
e to save or Ce +
T o specify the time format, select TlME FORMAT on the menu, press
to cancel your
ICANCEL~00:oo 1
1
T o set the time, select SET TIME on the menu and press +. Specify the
hours with keys and w, and press e . ~ h e specify
n the minutes.
Press
OK
to save orpCANCEL
to cancel your changes.
Control panels
ACS550 User's Manual 57
Pressing @ opens the help that shows the beginning and end dates of the
period during which daylight saving time is used in each country or area
whose daylight saving changes you can select to be followed.
To disable automatic clock transitions according to the daylight saving
changes, select Off and press +. On: Mar l a s t sunday
Off: o c t l a s t Sunday
Control panels
ACS550 User's Manual
Controlpanels
ACS550 User's Manual
After the upload is completed, the display shows a message about the
completion. Press to return to the Copy menu.
m00 :00 -1
1
.To perform downloads, select the appropriate operation (here DOWNLOAD
a .. - . .
w.and press e.
FULL SET is used as an example) on the Copy menu with keys and .-
I I
The display shows the transier status as a
percentage of completion. Press @ if you want stop the operation.
After the download is completed, the display shows a message about the LOC GMESSAGE
Parameter download
completion. press% to return to the Copy menu. successful ly
completed.
Control ~ a n e l s
60 ACS550 User's Manual
press m. The display shows the following information about the drive where
the backup was made:
type of the drive
DRIVE RATING: rating o i the drive in format XXXYZ, where
XXX: nominal current rating. If present, a n " A indicates
a decimal point, e.g. 4A6 means 4.6 A.
Y: 2 = 200 v
4 = 400V
6 = 600V
Z: i = European loading package
n = US loading package
firmware version of the drive.
Control panels
ACS550 User's Manual
-DI3-
4.
and press e.
Select the setting (line with a parameter number) with keys
1 0 0 1 E X T l COMMANDS
5. Specify a new value for the setting with keys and w. LOC &PAR EDIT
Pressing the key once increments or decrements the value. Holding the key
I I down changes the value faster. Pressing the keys simultaneously replaces the
displayed value with the default value.
Control panels
ACS550 User's Manual
Features
The Basic Control Panel features:
numeric control panel with an LCD display
copy function - parameters can be copied to the control panel memory for later
transfer to other drives or for backup of a particular system.
Overview
The following table summarizes the key functions and displays on the Basic Control
Panel.
No. Use
1 LCD display - Divided into five areas:
a. Upper left- Control location:
LOC: drive control is local, that is, from the control panel
REM: drive control is remote, such as the drive I10 or fieldbus.
b. Upper right - Unit of the displayed value.
c. Center-Variable: in general, shows parameter and signal values, menus or
lists. Shows also fault and alarm codes.
d. Lower left and center - Panel operation state:
OUTPUT. Outout mode
PAR: ~arameiermode
MENU: Main menu
mm:Fault mode.
e. Lower right - Indicators:
FWD (forward) / REV (reverse): direction of the motor rotation
Flashing slowly: stopped
Flashing rapidly: running, not at setpoint
Steady: running, at setpoint
HiW DisDlaved
. . value can be modified (in the Parameter and Reference
modes).
RESETIEXIT- Exits to the next higher menu level without saving changed
values. Resets faults in the Outout and Fault modes.
3 MENUIENTER - Enters deeper into menu level. In the Parameter mode,
saves the displayed value as the new setting.
4 Up-
Scrolls up through a menu or list.
Increases a value if a parameter is selected.
Increases the reference value in the Reference mode.
Holding the key down changes the value faster.
5 Down-
Scrolls down through a menu or list.
Decreases a value if a parameter is selected.
Decreases the reference value in the Reference mode.
Holding the key down changes the value faster.
6 LOCIREM - Changes between local and remote control of the drive.
, ~- .
1
~~ ~~
I ~~~
Control panels
ACS550 Useis Manual
Operation
You operate the control panel with menus and keys. You select an option, e.g.
operation mode or parameter, by scrolling the a
and i ~ arrow
/ keys until the
option is visible in the display and then pressing the key.
With the key, you return to the previous operation level without saving the made
changes.
The Basic Control Panel has five panel modes: Output, Reference, Parameter, Copy
and Fault. The operation in the first four modes is described in this chapter. When a
fault or alarm occurs, the panel goes automatically to the Fault mode showing the
fault or alarm code. You can reset the fault or alarm in the Output or Fault mode (see
chapter Diagnostics).
After the power is switched on, the panel is in the
Output mode, where you can start, stop, change the
direction, switch between local and remote control and OUTPUT
EFq
monitor up to three actual values (one at a time). To do
other tasks, go first to the Main menu and select the
appropriate mode.
How to do common tasks
The table below lists common tasks, the mode in which you can perform them and
the page number where the steps to do the task are described in detail.
Task Mode Page
How to switch between local and remote control l~nv 1, 64
How to start and stop the drive IA~Y
I '
1 64
How to change the direction of the motor rotation IA~Y 64
-
IHow to browse the monitored sipnals lout~ut 1I 65 1
How to set the speed, frequency or torque reference 1 Reference
I '
1 66
How to change the value of a parameter 1 Parameter 67
-
[How to select the monitored siqnals II Parameter 14 68 1
How to reset faults and alarms Output, Fault 1 249
How to copy parameters from the drive to the control panel COPY 70
IHow to restore parameters from the control ane el to the drive ~CODV 1 70 1
Control aanels
64 ACS550 User's Manual
t How to start, stop and switch between local and remote control
You can start, stop and switch between local and remote control in any mode. To be
able to start or stop the drive, the drive must be in local control.
Step Action Display
T o switch between remote control (REM shown on the left) and local
control (LOC shown on the lefl), press @.
Note: Switching to local control can be disabled with parameter 1606 OUTPUT
LOCAL LOCK.
Afler pressing the key, the display briefly shows message ' L o C or YE",
as appropriate, before returning to the previous display.
The vety first time the drive is powered up, it is in remote control (REM)
and controlled through the drive I10 terminals. To switch to local control
(LOC) and control the drive using the control panel, press @.The result
depends on how long you press the key:
If you release the key immediately (the display flashes 'LoC), the drive
stops. Set the local control reference as instructed on page 66.
If you press the key for about two seconds (release when the display
changes from "LoC to "LoC r"), the drive continues as before. The drive
copies the current remote values for the runistop status and the
reference, and uses them as the initial local control settings.
j
II II T o stop the dr~vein local control, press @
(
4 9.1 1
2. To change the direction from forward (FWD shown at the bottom) to LOC
reverse (REV shown at the bottom), or vice versa, press B. HZ
OUTPUT REV
Note: Parameter 1003 DIRECTION must be set to 3 (REQUEST).
Control panels
ACS550 Usefs Manual
Output mode
In the Output mode, you can:
- monitor actual values of up to three Group 01: OPERATING DATA signals, one
signal at a time
start, stop, change the direction and switch between local and remote control
You get to the Output mode by pressing puntil the display shows text OUTPUT at
the bottom.
The display shows the value of one Group 01:
OPERATING DATA signal. The unit is shown on the
right. Page 68 tells how to select up to three signals to
be monitored in the Output mode. The table below
shows how to view them one at a time.
How to browse the monitored signals
1.
I
If more than one signals have been selected to be monitored (see page
68),you can browse them in the Output mode.
To browse the s~gnalsforward, press keyarepeatedly To browse
I
REM
lou~~"'
. .
4 9.1
FWD
Hz I]
them backward, press key repeatedly
OUTPUT
1
OUTPUT
-
Control panels
ACS550 User's Manual
Reference mode
In the Reference mode, you can:
set the speed, frequency or torque reference
start, stop, change the direction and switch between local and remote control
How to set the speed, frequency or torque reference
Action Display
Go to the Main menu by pressing rn if you are in the Output mode,
otherwise by pressing repeatedly until you see MEN" at the bottom. /'EM PA r
I
m
MENU FWD
If the drive is in remote control (REM shown on the left), switch to local
control by pressing @.The display briefly shows 'LoC before switching
to local control.
Note: With Group 11: REFERENCE SELECT, you can allow the reference
modification in remote control (REM).
If the panel is not in the Reference mode ('rEF not visible), press key
a or until you see "rEF and then press W.Now the display
shows the current reference value with !Zi3 under the value.
5i FWD
Control panels
ACS5.50 Usefs Manual
Parameter mode
In the Parameter mode, you can:
view and change parameter values
select and modify the signals shown in the Output mode
start, stop, change the direction and switch between local and remote control
How to select a parameter and change its value
Step Action Display
If the panel is not in the Parameter mode ("PA< not visible), press key
/r7 or until you see "PA? and then press m. The display
shows the number of one of the parameter groups.
01
Use keys aand w to find the desired parameter group.
Press
group.
v. The display shows one of the parameters in the selected
aand
Use keys to find the desired parameter.
1103
Press and hold for about two seconds until the display shows the
value of the parameterwith rn underneath indicating that changing of the
LOC
1
I I 1
value is now possible. PAR nril FWD
Note: When is visible, pressing keys a and
simultaneously changes the displayed value to the default value of the
parameter.
7. Use keys and to select the parameter value. When you have
changed the parameter value. B3i starts flashing.
LOC
PAR
2FWD
m.
T o save the displayed parameter value, press
T o cancel the new value and keep the original, press v. 1103
Control panels
68 ACS550 User's Manual
2. Specib the decimal point location, or use the decimal point location and
unit of the source signal [setting (9 (DIRECT)]. Bar graphs are not available
for Basic Operation Panel. For details, see parameter 3 4 0 4 . PAR an FWD
Signal 1: parameter 3 4 0 4 OUTPUT^ DSP FORM
Signal 2: parameter 3 4 1 1 OUTPUT:! DSP FORM
Signal 3: parameter 3 4 1 8 OUTPUT^ OSP FORM.
3. Select the units to be displayed for the signals. This has no effect if
parameter 3404/341113418 is set to 9 (DIRECT). For details. see
parameter 3 4 0 5 .
Signal 1: parameter 3 4 0 5 OUTPUT^ UNIT
I"'/ PAR FWD
4. Select the scalings for the signals by specifying the minimum and
maximum display values. This has no effect if parameter 3404/341113418is
set to 9 (DIRECT). For details, see parameters 3406 and 3407.
Signal 1: parameters 3 4 0 6 OUTPUTI MIN and 3 4 0 7 OUTPUT^ MAX
1- PAR W FWD
Control panels
ACS550 User's Manual 69
Copy mode
The Basic Control Panel can store a full set of drive parameters and up to two user
sets of drive parameters to the control panel. The control panel memory is non-
volatile.
In the Copy mode, you can:
copy all parameters from the drive to the control panel (uL - Upload). This
includes all defined user sets of parameters and internal (not adjustable by the
user) parameters such as those created by the ID Run.
restore the full parameter set from the control panel to the drive (dL A - Download
All). This writes all parameters, including the internal non-user-adjustable motor
parameters, to the drive. It does not include the user sets of parameters.
Note: Only use this function to restore a drive, or to transfer parameters to
systems that are identical to the original system.
copy a partial parameter set from the control panel to a drive (dL P - Download
Partial). The partial set does not include user sets, internal motor parameters,
parameters 9905 ...9909, 1605, 1607,5201,nor any Group 51: EXT COMM
MODULE and Group 53: EFB PROTOCOL parameters.
The source and target drives and their motor sizes do not need to be the same.
- copy USER S1 parameters from the control panel to the drive (dL u l -Download
User Set 1). A user set includes Group 99: START-UP DATA parameters and the
internal motor parameters.
The function is only shown on the menu when User Set 1 has been first saved
using parameter 9902 APPLIC MACRO (see section Userparameter sets on page
81) and then uploaded to panel.
copy USER S2 parameters from the control panel to the drive (dL u2 - Download
User Set 2). As dL u l - Download User Set 1 above.
start, stop, change the direction and switch between local and remote control.
Confrol panels
ACS550 User's Manual
rn
1. Go to the Main menu by pressing
otherwise by pressing
if you are in the Output mode.
repeatedly until you see MENU at the bottom. ILoC PAT 1
I I
2. If the panel is not in the Copy mode ('COPY" not visible), press key
or until you see "COPY.
MENU FWD
3. - panel,
To upload all parameters (including user sets) from the drive to the control LOC
.
Press m. During the transfer, the display shows the transfer status as a LoC
percentage of completion.
FWD
-
T o perform downloads, step to the appropriate operation (here "dL A ,
Download All, is used as an example) with keys and v. 'OC dL A
MENU FWD
m.
Press During the transfer, the display shows the transfer status as a
dL 50
LOC
percentage of completion. %
I FWD
Controlpanels
ACS550 User's Manual
Application macros
The following sections describe each of the application macros and provide a
connection example for each macro.
The last section in this chapter, Macro default values for parameters, lists the
parameters that the macros change and the default values established by each
macro.
Application macros
72 ACS550 User's Manual
Application macros
ACS550 Useis Manual 73
3-wire macro
This macro is used when the drive is controlled using momentary push-buttons. It
provides three (3) constant speeds. To enable, set the value of parameter 9902 to
2 (3-WIRE).
Note: When the stop input ( ~ 1 2 is
) deactivated (no input), the control panel staNstop
buttons are disabled.
Connection example:
XI
Signal cable shield (screen)
External speed reference 1: 0...10 V
Analog input circuit common
Reference voltage 10 V DC
Not used
Analog input circuit common
Motor output speed: 0...20 mA
Output current: 0...20 mA
Analog output circuit common
Auxiliary voltage output +24 V DC
Auxiliary voltage output common
Digital input common for all
Start: Momentary activation with Dl2 activated starts the drive
Stop: Momentary deactivation stops the drive
FwdlRev: Activation reverses rotation direction
Constant speed selection'
Constant speed selection'
Not used
-
Input signals
Analog reference (All)
Start, stop and direction (DI1.2,3)
Constant speed selection (D14,5)
.
-
Output signals
Analog output A01: Speed
Analog output A02: Current
Relay output 1: Ready
Relay
. output 2: Running
~
~ A I I : O...lOV
A12: O(4). ..20 mA
A l l : O...lOV
Application macros
74 ACS550 Usefs Manual
Alternate macro
This macro provides an 110 configuration adopted to a sequence of Dl control
signals used when alternating the rotation direction of the motor. To enable, set the
value of parameter 9902 to 3 (ALTERNATE).
Connection example:
XI
Signal cable shield (screen)
External speed reference 1: 0...10 V
Analog input circuit common
Reference voltage 10 V DC
Not used
Analog input circuit common
Motor output speed: 0...20 mA
Output current: 0...20 mA
Analog output circuit common
-
Input signals
Analog reference (All)
Start, stop and direction (D11,2)
Constant speed selection (D13,4)
Ramp . .pair 112 selection (D15)
. .
-
Output signals
Analog output AOl: Speed
Analog output A02: Current
Relay output 1: Ready
Relav
. output
. 2: Runninq -
6
,,
",
nr
g
Jumper setting
Application macros
ACS550 User's Manual 75
Application macros
76 ACS550 User's Manual
I Hand-Auto macro
This macro provides an 110 configuration that is typically used in HVAC applications.
To enable, set the value of parameter 9902 to 5 (HANDIAUTO).
Note: Parameter 2108 START INHIBIT must remain in the default setting, 0 (OFF).
Connection example:
XI
Signal cable shield (screen)
External reference I: 0...10 V(Hand Control)
Analog input circuit common
Reference voltage 10 V DC
External reference 2: 0...20 mA (Auto Control)
Analog input circuit common
Motor output speed: 0...20 mA
Output current: 0...20 mA
Analog output circuit common
i
10 24V Auxiliary voltage output +24 V DC
11 GND Auxiliary voltage output common
12 DCOM Digital input common for all
13 Dl1 StartlStop (Hand): Activation starts the drive
14 Dl2 ForwardlReverse (Hand): Activation reverses rotation direction
15 Dl3 EXTIIEXTZ Selection: Activation selects auto control
16 014 Run enable: Deactivation always stops the drive
17 Dl5 ForwardlReverse (Auto): Activation reverses rotation direction
18 StaNStop (Auto): Activation starts the drive
Relay output 1, programmable
Default operation:
Readv =>I9 connected to 21
Relay output 2, programmable
Default operation:
Running =>22 connected to 24
Relay output 3, programmable
Default operation:
Fault (-1) =>25 connected to 27
(Fault => 25 connected to 26)
Application macros
ACS550 User's Manual 77
Note: Parameter 2108 START INHIBIT must remain in the default setting, 0 (OFF)
Connection example:
-- Input signals
Analog reierence (All)
Actual value (A12) .
Output signals
Analog output AOl: Speed
Analog output A02: Current
Jumper setting
- -
Startlstop hand1PID (DII. 6) .
.
Relay output 1: Ready
",
EXTllEXT2 selection (012)
. . Relay
. output 2: Running -.
Constant speed selection (013, 4) . ~
Application macros
78 ACS550 Use& Manual
PFC macro
This macro provides parameter settings for pump and fan control (PFC) applications.
To enable. set the value of parameter 9902 to 7 (PFC CONTROL).
Note: Parameter 2108 START INHIBIT must remain in the default setting, 0 (OFF).
Connection example:
XI
I i n rohm,ll ISCR I Signal cable shield (screen)
~'ternal ref. I( ~ a n u a lo;) Ext ref. 2 (PIDIPFC): O... 10 V'
Analog input circuit common
Reference voltage 10 V DC
7 ]A01
8 [A02
Actual signal (PID): 4...20 mA
- .
Analoa i n ~ ucircuit
t common
Output frequency: 0...20 mA
. - ---
m ~ 1 2O(4).
: ..20 mA
Note: Use the following switch-on order:
1. EXTlIEXT2
2. Run Enable
3. Start.
Application macros
ACS550 User's Manual 79
Input signals
- Two analog references (All, 2) . AnalogOutput signals
output A01: Speed
Jumper setting
Application macros
80 ACS550 User's Manual
Note: The sensor is supplied through its current output. Thus the output signal must
be 4...20 mA, not 0...20 m A.
Application macros
ACS550 User's Manual
The user parameter set can also be switched through digital inputs (see parameter
1605).
Note: Loading the user parameter set restores the parameter settings including
Group 99: START-UP DATA and the results of the motor identification. Check that
the settings correspond to the motor used.
Hint: The user can for example switch the drive between two motors without having
to adjust the motor parameters and to repeat the motor identification every time the
motor is changed. The user needs only to adjust the settings and perform the motor
identification once for each motor and then to save the data as two user parameter
sets. When the motor is changed, only the corresponding user parameter set needs
to be loaded, and the drive is ready to operate.
Application macros
82 ACS550 Useis Manual
Note: There are two sets of values because the defaults are configured for 50 Hz/
IEC compliance (ACS550-01) and 60 HzlNEMA compliance (ACS550-UI).
Parameter g<
E 2
-
m
m L;
20
L
m
u
?
0
3
-
2
*
c
o
-2
A.
g 23
et;
.$ g3 u
h 0
"
4:3
V)
m
4: 0 L
$0"
p a a
Application macros
ACS550 User's Manual
Parameter
E 2
m
2
E:
L
m
+
s..;o
0
5
7
-
2
*
L3
o
-
-2
c :YzE
qg
3
"7
;Z -
o
m
I Q
a
o
0
2
a
26
Application macros
ACS550 User's Manual
Application macros
ACS550 User's Manual
Parameters
Parameters
86 ACS550 Usefs Manual
Parameters
ACS550 User's Manual 87
-..-. -. -..-.
r n crc i n m a n 7
-
...... -.. -.-......-. .
o u t i o
1
I
0
--
, 7 7 1
--
.... .-.-- I
1104 IREFIMIN 10.0 ...500.0 HZ I0...30000 rpm 10.1 HZ /I rpm 10.0 Hz 10 rpm
1105 IREFIMAX 10.0...500.0 Hz I 0...30000 rpm 10.1 Hz1 1 rpm 101: 50.0 Hz/ 1500 rpml
~
p~~~~~~~~
Parameters
88 ACS550 User's Manual
r; pge
...
....
;Name - ..--... .. ...- ....
;CONSr S P C t u 5
--- .
1505 MAXIMUM A01 0.0 ...20.0 rnA 0.1 rnA 20.0 rnA
1506 FILTER A01 0.0 ...10.0 S 0.1 S 0.1 S
1507 A02 CONTENT SEL 99... 159 1 104 (parameter 0104
CURRENT)
1508 A02 CONTENT MIN - Defined by par. 0104
1509 A02 CONTENTMAX - Defined bv ~ a r0104
.
Parameters
ACS550 User's Manual 89
I , I I
2112 ZERO SPEED DELAY 10.0 = NOT SEL, 0.1 ...60.0 S 10.1 s 10.0 s (NOTSEL)
2113 START DELAY 10.00...60.00 s 10.01 S /O.OO S
Parameters
90 ACS550 Usefs Manual
Rangc
... .
Group 22:ACCEUDECEP
-
I--- -I:: ' '
,
._ ;
_... . .
2201 IACCIDEC 112 SEL 1-6 7
RAMP INPUT
U IOTJhE RUh 1
- I . - . I -
.... ....
Group 25: CRITICALSPEEDS . .'. . .
.-..-- --
2501 ICR - -- - SEI
. T SPEED .-. 10. :OFF
. ~ . ,1 : O h
~
I
1
'
- l\-.n. ,
I0 ~ ~ T-?-
I I
. 2502 ~CRITSPEED 1 LO 10 ...30000 r ~ /m0.0 ...500.0 HZ rom I0.1 Hz
/I 10 rDm 10.0 Hz
,I 2503 CRlT SPEED 1 HI 0...30000 rpm 10.0...500.0 HZ 1 rpm 10.1 HZ 0 rpm / 0.0 HZ
2504 CRlT SPEED 2 LO 0...30000 rpm / 0.0 ...500.0 HZ 1 rpm 10.1 HZ 0 rpm / 0.0 Hz
2505 CRlT SPEED 2 HI m ...500.0 HZ
0...30000 r ~ 10.0 1 r ~ 10.1
m HZ 0 r ~ 10.0
m Hz
I
2902 COOLING FAN ACT 0.0 ...6553.5 kh 0.1 kh 0.0 kh
2903 REVOLUTION TRIG 0...65535 Mrev, 0 disables 1 Mrev 0 Mrev
2904 REVOLUTION ACT 0...65535 Mrev 1 Mrev 0 Mrev
2905 RUN TIME TRIG 0.0 ...6553.5 k h , 0.0 disables 0.1 kh 0 0 kh
Parameters
ACS550 User's Manual 91
g:ode>? Naxe3<,:;$i;$::,:<%
::;,.5:. g.a$,ge%*;:z ;,*, &$:;,:>.;$ !:,,;::.,;;:$,;:;i?;;;~,~~~~~~~i!~~:2,,:~,,~~~~~~~~;>:~
2907 USER MWh TRIG 0.0 ...6553.5 MWh, 0.0 disables 0.1 MWh 10.0 MWh
2908 USER MWh ACT 0.0...6553.5 MWh 10.1 MWh 10.0 MWh 1 I
I I I \ - ---, I I
3002 [PANEL COMM ERR (I ...3 11 11 (FAULT)
3003 EXTERNAL FAULT 1 -6...6 1 0 (NOT SEL)
3004 EXTERNAL FAULT 2 -6...6 1 0 (NOT SEL)
3005 MOT THERM PROT 0 = NOT SEL, 1 = FAULT, 2 = ALARM 1 1 (FAULT)
3006 MOT THERM TIME 256...9999 s 1 500 s
3007 MOT LOAD CURVE 50... 150% 1 100%
3008 ZERO SPEED LOAD 25 ...150% 1 70%
j
3101 INUMBER OF TRIALS 10. . 5
3102 ITRIALTIME 11.0...600.0 s 10.1 s 30 s
3103 DELAY TIME 10.0 ... 120.0 s 10.1 s 10 s 1 I
--
I I I I ~ I I
3106 IAR UNDERVOLTAGE 10 = DISABLE. 1 = ENABLE lo (DISABLE)
Parameters
92 ACS550 User's Manual
-.-.-..-.
. . . . -. .--.
~ ~ ~ ' F FhexF F
-. -.. ....
I I I I
3413 OUTPUlZ MIN 1
3414 OUTPUT^ MAX
~~ ~ 1-I 11I '
1-I II II
3415 ISIGNAL~PARAM 1100 = NOT SELECTED. 101... 1 5 9 11 1105 (oarameter 0 1 0 5 1
3416 ISIGNAL~MIN 1- 1 1-, I 1
3417 SIGNAL3 MAX 1
3418 OUTPUT3 DSP FORM 0...9 1 9 (DIRECT)
3419 OUTPUT3 UNIT 0...127 1
3420 OUTPUT3 MIN 1
3421 OUTPUT3 MAX 1
I I I I I
3503 LIMIT
~ W R M IPar. 3 5 0 1 = 1...3: -10...200 " C I1 ~ 1 1 0 " ~ / 1 5 0 0 o h m / I0
r 3 5 0 1 = 4: 0...5000 ohm
Parameters
ACS550 Usefs Manual 93
Parameters
94 ACS550 User's Manual
-. -. .-. -
..-. . ..
Un t and sca e uefned by par 4006 arla - 1000%
4023 PI0 SLEEP LEVEL 10 ...30000 rpm 10.0...500.0 HZ 1 rpm 10.1 HZ 10 rpm / 0.0 HZ I
4102 [INTEGRATION TIME 10.0 = NOT SEL, 0.1 ...3600.0 s 10.1 S 160.0 s
I
4103 DERIVATION TIME 10.0... 10.0 s 10.1 s 10.0 s I
4104 PID DERIV FILTER 0.0 ... 10.0 S 0.1 S 1.0 s
4105 ERROR VALUE INV 0 = NO, 1 =YES 1 0 (NO)
4106 UNITS 0...127 1
'\
I
~.,'
Parameters
96 ACS550 User's Manual
5202 BAUD RATE 9.6, 19.2.38.4, 57.6, 115.2 kbitsls 9.6 kbitsls
5203 PARlN 0 = 8 NONE 1. 1 = 8 NONE 2, 1 0 (8 NONE 1)
2=8EVEN1,3=8ODDI
5204 OK MESSAGES 0...65535 1
, I I I
5302 ~EFBSTATION ID 0...65535 11 1 J
5303 EFB BAUD RATE 1.2, 2.4, 4.8, 9.6, 19.2. 38.4, 57.6, 76.8 - 9.6 kbitsls
.. . - -
khitsls
I I I I I I
8104 REFERENCE STEP 2 10.0 ... 100.0% /0.1% 10.0%
8105 REFERENCE STEP 3 10.0 ... 100.0% 10.1% 10.0%
Parameters
ACS550 Useis Manual 97
, I I I I
8119 IAUTOCHNGLEVEL 10.0.. 100.0% 10.1% 150%
8120 INTERLOCKS 0...5 1 4 (D14) J
8124 ACC IN AUX STOP 0.0=NOTSEL,O.1 ...1800.0s 0.1 S 0.0 s (NOT SEL)
,.. 8125 DEC IN AUX START 0.0 = NOT SEL, 0.1 ... 1800.0 S 0.1 s 0.0 s (NOT SEL)
8126 TMEDAUTOCHNG 0...4 1 o (NOT SEL)
8127 MOTORS 1...7 1 2 J
Parameters
ACS550 User's Manual
- e n t e r motor information.
-..
-..
.
Code Description
,9901 LANGUAGE
- - .. -.-.-.....-
-4
-- -- . . .-.- .- -.-
I I Se ecls tne d splay language Tnere are rwo a~lfereorAbslstant Conrro Panels eacn supporr iiy a a ffarent language
set (Parel ACS-CP-_ sLpponlng languages 0 2 11 15 -11 be integrateu lnro ACS-CP-A )
Assistant Control Panel ACS-CP-A:
o = ENGLISH 1 = ENGLISH (AM) 2 = DEUTSCH 3 = ITALIANO 4 = ESPA~OL
5 = PORTUGUES 6 = NEDERLANDS 7 = FRANCAIS 8 = DANSK 9 = SUOMI
10 = SVENSKA 11 = RUSSKI 12 = POLSKI 13 = TORKCE 14 = CZECH
15 = MAGYAR
Assistant Control Panel ACS-CP-D (Asia):
0 = ENGLISH 1 = CHINESE 2 = KOREAN 3 =JAPANESE
9902 IAPPLICMACRO
I I Selects an application macro. Application macros automatically edit parameters to configure the ACS550 for a
particular application. I
1 = ABB STANDARD 2 = 3-WIRE 3 = ALTERNATE 4 = MOTOR POT 5 = HANDIAUTO
6 = PID CONTROL 7 = PFC CONTROL
,:I 0 = USER S1 LOAD -1 =USER S1 SAVE
8 = TORQUE CTRL
-2 = USER $2 LOAD
31 = LOAD FD SET
-3 =USER $2 SAVE
31 = LOAD FD SET- FlashDrop parameter values as defined by the FlashDrop file. Parameter view is selected by
parameter 1611 PARAMETER VIEW.
FlashDrop is an optional device for fast copying of parameters to unpowered drives. FlashDrop allows easy
customization of the parameter list, e.g. selected parameters can be hidden. For more information, see MFDT-01
FlashDrop User's Manual [3AFE68591074 (English)].
-1 = USER s1 SAVE, -3 = USER s2 SAVE -With these it is possible to save two different user parameter sets into the
drive permanent memory for later use. Each set contains parameter settings, including Group 99: START-UP
DATA, and the results of the motor identification run.
0 = USER s1 LOAD,-2 = USER s2 LOAD - With these the user parameter sets can be taken back in use.
9904 MOTOR CTRL MODE
Reference 2 is speed reference in % (100% is absolute maximum speed, equal to the value of parameter 2002
MAXIMUM SPEED,or 2001 MINIMUM SPEED if the absolute value of the minimum speed is greater than the maximum
speed).
2 = VECT0R:TORQ.
Reference 1 is speed reference in rpm.
Reference 2 is torque reference in % (100% is nominal torque.)
3 = SCALAR:FREQ -scalar control mode.
Reference 1 is frequency reference in Hz.
Reference 2 is frequency reference in % (100% is absolute maximum frequency, equal to the value of parameter
2008 MAXIMUM FREQ, or 2007 MINIMUM FREQ if the absolute value of the minimum speed is greater than the
maximum speed).
9905 MOTOR NOM VOLT
Defines the nominal motor voltage.
Must equal the value on the motor rating plate.
The ACS550 cannot supply the motor with a voltage greater than the input power (mains) voltage.
i
ACS550 User's Manual 99
I I
I
T r i ~ sparameter contro s a se f callbrat on process called the Motor ID Run D-rlng I n s process trw drwe operates
me motor (motor rota1 ng, and makes nleasLrements in oraer lo den1 ty motor cnaractilr st~csand create a model
lused for internal calculations. An ID Run is esoeciallv effective when: I
-- vector control mode is used [parameter 9904 = 1 (VECTOR:SPEED)
operation point is near zero speed, and/or
or 2 (VECTOR:TORQ)], and/or
operation requires a torque range above the motor nominal torque, over a wide speed range, and without any
measured speed feedback (i.e. without a pulse encoder).
0 = OFFilDMAGN -The Motor ID Run process is not run. ldentification magnetization is performed, depending on
parameter 9904 and 2101 settinqs. In identification maqnetization. the motor model is calculated at first start bv
magnetizing the motor for 10 to 15 s at zero speed (mGor not rotating). The model is recalculated always at s&rt
3 after motor parameter changes.
1
'< Parameter 9904 = 1 (VECTOR:SPEED) or 2 (VECTOR:TORQ):ldentification magnetization is performed.
1 Parameter 9904 = 3 (SCALAR:FREQ)
magnetization is performed.
and parameter 2101 = 3 (SCALAR FLYST)or 5 (FLY+ BOOST):ldentification
Parameter 9904 = 3 (SCALAR:FREQ) and parameter 2101 has other value than 3 (SCALAR FLYST) or 5 (FLY +
BOOST):ldentification magnetization is not performed.
1 =ON - Enables the Motor ID Run, during which the motor is rotating, at the next start command. Afler run
completion, this value automatically changes to 0.
Note: The motor must be de-coupled from the driven equipment.
Note: If motor parameters are changed after ID Run, repeat the ID Run.
WARNING! The motorwill run at up to approximately 50 ...80% of the nominal speed during the ID Run. The
A motor will rotate in the forward direction.
Ensure that it is safe to run the motor before performing the ID Run1
See also section How to perform the ID Run on page 39.
Parameters
ACS550 User's Manual
The calculated signed speed of the motor (rpm). The absolute value of 0101 SPEED 8 DIR is the same as the value 01
0102 SPEED.
The value of 0101 SPEED 8 DIR is positive if the motor runs in the folward direction.
The value of 0101 SPEED 8 DIR is negative if the motor runs in the reverse direction.
0102 SPEED
The calculated speed of the motor (rpm). (Parameter 0102 or 0103 is shown by default in the control panel Output
mode.)
0103 OUTPUT FREQ
The frequency (Hz) applied to the motor. (Parameter 0102 or 0103 is shown by default in the control panel Output
mode.)
0104 CURRENT
The motor current, as measured by the ACS550. (Shown by default in the control panel Output mode.)
0105 TORQUE
Output torque. Calculated value of torque on motor shaft in % of motor nominal torque. (Shown by default in the
control panel Output mode.)
0106 POWER
The measured motor power in kW.
0107 DC BUS VOLTAGE
!
The DC bus voltage in V DC, as measured by the ACS550.
) 0109 OUTPUT VOLTAGE
The voltage applied to the motor.
0110 DRIVE TEMP
The temperature of the drive power transistors in degrees Celsius.
0111 EXTERNAL REF 1
External reference, REFI, in rpm or Hz - units determined by parameter 9904.
0112 EXTERNAL REF 2
External reference, REF^, in %.
0113 CTRL LOCATION
Active control location. Alternatives are:
0 = LOCAL
1 = EXTl
2 = EXT2
0114 RUN TIME (R)
The drive's accumulated running time in hours (h).
Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0115 KWH COUNTER (R)
The drive's accumulated power consumption in kilowatt hours.
-
Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0116 APPL BLK OUTPUT
Application block output signal. Value is from either:
PFC control, if PFC Control is active, or
Parameter 0112 EXTERNAL REF 2.
Parameters
ACS550 Usefs Manual 101
I
i 'cOas
#**>.<<a
osrddiigm;;;"i<
a..: ,>,. .**.*~:,*>
,,$s, ,: ~,:..,,,,.~,;,*~",
>,. 'dZt3
,", &@;z
","w
, ?"Tp:*"-.,'
>$*s.4d..~>: :
%r i;;>
.-*.'
-" bTxt%
I,;:~,.'
'--
.Z.\'.; : ? : g @ ; ~
-; 3 y...
:r.,.+, 2 .:..; $ . ~ ; ~%wa:,>s .,s. .:
. ~ ; 2 : ~ ; : ' : ;:,: < :.:;:~
.,.e,s. a
,
. ,:,.~.,~
,-.,*~ ~ , : ,,.,,
y ; ;/.*: ;.,..,*
: : :':.~:
; ~.,< ;,,.~ ; ; : ~ $ ~ 5 " ~ y ~
0118 Dl 1-3 STATUS
Status of the three digital inputs.
-
The PID 2 controller setpoint signal.
Units and scale defined by PI0 parameters.
0130 PI0 1 FBK
The pi0 1 controller feedback signal.
Units and scale defined by PID parameters.
0131 PID2 FBK
The PID 2 controller feedback signal.
Units and scale defined by PID parameters.
0132 PID 1 DEVIATION
The difference between the PID 1 controller reference value and actual value.
Units and scale defined by PID parameters.
0133 PID 2 DEVIATION
The difference between the PID 2 controller reference value and actual value.
Units and scale defined by PID parameters.
0134 COMM RO WORD
Free data location that can be written from serial link.
-
Used for relay output control.
See parameter 1401.
0135 COMM VALUE 1
Free data location that can be written from serial link.
j
Parameters
102 ACS550 Useis Manual
G %rde
**A*
ps$>E8iFp5"
>*<me<,
;ty$<+*:~:
*,v*ea,
~ *,%
,,
e?y*c5?>,. .".,,.,.>,ir"".
*..-:
* ',*.L.,:<,:~..~::"**~>,~.:.;~&;::>.,~J~!
$,;$:>:
,:
-. ,....:: *:,3::,!*
<z:*:.s.> "W.. , ,....v~.2*,.
!.;<.*, *,r >?#><.,,.ass,: ...- ,,:,<:,y..<,z.,.,,;,,..;":'##.*#.!".:..
<,~*><>
~?.#"73.z."": >J,O~
%
' *.
., a,.:- . ,.-,,,,. .-v,*ii-,.:-<.-.*- .*,*:.,.e~.$<,.:*,.,.A*,<
#2,> ?
. , ~ ,,
#"%
.~ <
.$
' .'&,'. <a*.
~ ..,, .,p2..! ..#.;>:y<;2;yt$7~i,~<~:Bp,* :,;
-,<
., ,...~'::>6>* ' ..,
, ,',
%>:;:*.,>:>..:;::.,,,
< ~, ., . ,. ".*'
<..s..
,:, ~ .>5?7:
'
-
a 2-pulse input, if parameter 5010 z PLS ENABLE = 1 (ENABLE)
parameter 5011 POSITION RESET, if parameter 5010 z PLS ENABLE = 2 (DISABLE)
any status change of parameter 5002 ENCODER ENABLE.
0147 MECH REVS
A signed integer that counts full revolutions of the motor shaft. The value:
increments when parameter 0146 MECH ANGLE changes from 32767 to 0
decrements when parameter 0146 MECH ANGLE changes from 0 to 32767.
0148 Z PLS DETECTED
Encoder zero pulse detector. When a 2-pulse defines the zero position, the shaft must pass through the zero position
to trigger a Z-pulse. Until then, the shaft position is unknown (the drive uses the shaft position at power up as zero).
This parameter signals when parameter 0146 MECH ANGLE is valid. The parameter starts at 0 = NOT DETECTED on
power-up and changes to 1 = DETECTED only it
parameter 5010 z PLS ENABLE = 1 (ENABLE) and
an encoder 2-pulse has been detected.
0150 CBTEMP
Temperature of the drive control board in degrees Celsius.
Note: Some drives have a control board (OMIO) that does not support this feature. These drives always show the
constant value of 25.0 "C.
Parameters
ACS550 Useis Manual 103
Parameters
104 ACS550 User's Manual
Parameters
ACS550 User's Manual 105
- -
Code I~escriptlon--
--. ..- -T w
- - IFAIII
n?n5 .
..-n. .-
~ <n
. r -- -
Read-only copy of the Fault Word 1
When a fault is active, the
corresponding bit for the active fault is
set in the Fault Words.
Each fault has a dedicated bit
allocated within Fault Words.
See section Fault listing on page 244
for a description of the faults.
-
The control panel displays the word in
hex. For example, all zeros and a 1 in
Bit 0 displays as 0001. All zeros and a
1 in Bit 15 displays as 8000.
0306 FAULT WORD 2
Read-only copy of the Fault Word 2.
See parameter 0305.
0307 FAULT WORD 3
Read-only copy of the Fault Word 3.
.
See parameter 0305.
I
14 ~ E X TFAULT 2 MOTOR PHASE [System error
15 ]EARTH FAULT IOUTPWIRING I ~ a r a msetting
. fault
0308
-.ALARM WORD - ~-1
-.
-
~ ~~ ~~~~ ~ ~
-
the word.)
The control panel displays the word in
hex. For example, all zeros and a 1 in
Bit 0 displays as 0001. All zeros and a
7 PANELLOSS ENCODER ERROR
8 DEVICE OVERTEMP FIRST START
See parameter 0308.
9 MOTORTEMP Reserved
I I I/ 10 I~eserved
I
USER LOAD CURVE I
11
12
13
MOTOR STALL
AUTOR RESET
PFC AUTOCHANGE
[START DELAY
l~eserved
Reserved
1
14 PFC ILOCK Reserved
15 Reserved Reserved
Parameters
106 ACS550 U s e i s Manual
Paranieters
ACS550 User's Manual
Ilefines exlerna control locat,on 1 ( c x r t j - tlic coniyural on of start, stop and o rsct or) conlmanos
I1 = NO1 SEL - NOexternal Slan stop and d rec: on comm3no source
1 = 011 - Two-wire StarVStop.
- StaNStop is through digital input Dl1 (011 activated = Start; 011de-activated = Stop).
Parameter 1003 defines the direction. Selecting 1003 = 3 (REQUEST) is the same as 1003 = 1 (FORWARD)
2 = ~11.2-Two-wire StarVStop, Direction.
I -. StarVSt0~is throuah diaital inout Dl1 (Dl1 activated = Start: Dl1 de-activated = Stool.
~irectioncontrol [GquiFes pa~ameter'1003= 3 (REQUEST)]'
(Dl2 activated = Reverse; de-activated = Forward).
is through digital 1nput'd~2
SlarVStop commands are through momentary push-o .hons (!he P stands for pulse',
Start 1s through a norma i y open psn-outton connecred to 01q.talmpLt 011 In order lo stan tnc ar ve the d qltal
i n ~ u012
t must be activated orior to the Dulse in DII
Connect m-It ple Stan P ~ ~ h : o L ! tint ~bar21
n~ e
Stop 1s through a norma. y c oseo p~sh-outton connected to o glta nput o 2
- Connect multioie Stoo oush-buttons in series.
Parameter 1003 defines the direction. Selecting 1003 = 3 (REQUEST) is the same as 1003 = I(FORWARD).
1= o l l ~ , 2 ~-, 3
Three-wire StarVStop, Direction.
StaNStop commands are through momentary push-buttons, as described for D I ~ P , ~ P .
Direction control [requires parameter 1003 = 3 (REQUEST)]is through digital input 013
(013 activated = Reverse; de-activated = Forward).
5 = DllP,2P,3P - Start Forward. Start Reverse and Stop.
Start and Direction commands are given simultaneously with two separate momentary push-buttons (the P stands
for "pulse").
Start Forward command is through a normally open push-button connected to digital input DII. In order to start the
drive, the digital input 013 must be activated prior to the pulse in o l l
Start Reverse command is through a normally open push-button connected to digital input 012. In order to start
the drive, the digital input 013 must be activated during the pulse in 012.
Connect multiple Start push-buttons in parallel.
Stop is through a normally closed push-button connected to digital input D13.
Connect multiple Stop push-buttons in series.
Reauires oarameter 1003 = 3 (REQUEST).
'
6 = Dl6 1~wd-wireStartlStop.
StaNStop is through digital input Dl6 (016 activated = Start; 016 de-activated = Stop).
Parameter 1003 defines the direction. Selecting 1003 = 3 (REQUEST) is the same as 1003 = 1 (FORWARD).
7 = 016,5 - Two-wire StaNStopIDirection.
StaNStop is throuah diaital input 016 (016 activated =Start: Dl6 de-activated = Stop).
control [requires parameter1003 = 3 REQUEST)^ is through digital input'd15.
= Reverse; de-activated = Forward).
I 18 = KEYPAD - Control Panel
SlarlJStop and D~recuoncommanos are rnrough me control pane when EXTI is actwe
Olrecl on con:rol reqL res parameter 1003 = 3 (REOJFST,
9 :D l l F 2R - StarllStoplO recllon commands tnrougl>U 1 an0 D 2 comulnat.ons
- Start forward = D 1 ac~~vated and o 2 ae-activated
Start reverse = o Ide-act~vateuand u12 act vatea
I --
I Stoo = both DII and Dl2 activated, or both de-activated
~equiresparameter 1003 = 3 (RMUEST).
10 = COMM -Assigns the fieldbus Command Word as the source for the stafflstop and direction commands.
Bits 0,1, 2 of Command Word 1 (parameter 0301) activates the startfstop and direction commands.
See Fieldbus user's manual for detailed instructions.
Parameters
108 ACS550 User's Manual
, . .......-...<<. r,.*+sn
,>q
,, i.-isiz. wm*;<w."..- ' &,?, ;.,- ""
,,' ,,,,-,< ,:*.- ,'.<.,*.:.-<*-;,>
I-'2!'B:,...)~*>:L,.- '-"".~&,~,s'~,-.-., ::-
g ,' ,*, ~&<* *d$>a&4b;2;:>'.<>.,
\,.*,.,,.~.. ,-:,.,':J.c,.2.,.;.:l,,,z
$
..,' %
+, '
;.,>.#.-
3.:.:";:zkc;
' nJxfp" i<g$j:$p;"2;~,,;$~,;::~~;,,>::;;*g$~g&$~;~l;~;~<~e~*,,"
11 =TIMEDFUNC I. - Assigns StaNStop control to Timed Function 1 (Xmed Function activated = START; Timed
Function de-activated = STOP). See Group 36: TIMED FUNCTIONS.
-
12... 14 = TlMED FUNC 2...4 - Assians StaNStoo control to Timed Function 2...4. See TlMED FUNC 1 above^ ~ ~~ ~~~~
I I
/
Defines the s ynal tnal act bares me,ogg ng Idncrlon Joyylny Jses Consranr Speed 7 (parameter 1206) for speed
reference and ramp patr 2 (paranicrers 2205 ano 2206) for acce eratlng ana decelerarlnq When the .oqqlnq
lactivation sianal is lost. the drive uses ram0 s t o to
.. .
~ decelerate to zero soeed. even if coast stoo is used in normal
I
i
1
I I operation (parameter 2102). The jogging status can be parameterized to'relay outputs (paiameier 1401). The jogging
status -1s also seen .in DCU Profile status bit 21.
0 = NOT SEL - Disables the jogging function.
1 = 011-Activates/de-activates jogging based on the state of DII (011 activated = jogging active; DII de-activated =
jogging inactive).
2L.6 = 012...016 - Activates jogging based on the state of the selected digital input. See ~ labove.
l
-1 = DII(INV) -Activates jogging based on the state of 011 (oil activated = jogging inactive; DII de-activated =jogging
nrtivel
1 1 - 2 ~ - 6 ~ 1 2 (...1016(1Nv)
~ ~ ) -Activates iowinq based on the state of the selected diaital inout. See DII(INVIabove. 1
Parameters
ACS550 Use& Manual
- = ..-. - .- ,
7 a~67
\ 1 ~ / ~ \
I I-
I
7 = EXIZ - Selecls extirna control location 2 ( E X T ~ ,
See psratneter 1002 ~ x i cor,iMANDS
2 for EXT2's StarVS~op/Dtroef~nito~is
I See Darameter 1106 REF2 SELECT for EXT2.s reference definitions
I I ..
I
8 = C O ~ I A-~Assigns control of the dr ye v a external conlrol local on E X T ~or Fxi2 oaseo on the fta db-s contro woro
61t 5 of !he Command Woru 1 (parameter 0301) defnes me act ve external contro oca1,on (FxTl or ixT2)
I See Fieldbus user's manual for detailed instructions. I
I I 9 = TIMED FUNC 1 -Assigns control to EXTI Or EXT2 based on the state of the Timed Function (Timed Function
activated = EXT2; Timed Function de-activated = EXTI).See Group 36: TlMED FUNCTIONS.
FUNC 1 above.
-1 = DI~(INV) - Assigns control to EXTI
-
10... 12 =TIMED FUNC 2...4 - Assians control to EXTI or EXT2 based on the State of the Timed Function. See TIMED
Parameters
110 ACS550 User's Manual
. Ii , , . .
,.; ,,,. . .-
' , ; > * ,
" '<.? ,
, . , L .;
,
;;
, ,
; .., :.:, , I,
15 = 013U,4O(R) - Defines diaital inputs as the soeed reference source (motor ~otentiometercontrol).
I .
I Diaital inout 013 increases the'soeed (the u stands for"uoS')
~~ ~~
Changing the control source (EXTI to E k , E X T to ~ EXTI. LOC to REM) does not copy the reference
13 = DISU,~D(NC) - Same as o15u,6D above, except that:
-Changing the control source (EXTI to EXT2, EXT2 to EXTI,LOC to REM)does not copy the reference.
14 = All+Al2 - Defines an analog input 1 (All) and analog input 2 (A12) combination as the reference source. See
Analog input reference correction below.
15 = AIi*AI2 - Defines an analog input 1 (All) and analog input 2 (A12) combination as the reference source. See
Analog input reference correction below.
16 = Ali-Al2 - Defines an analog Input 1 (~11)and analog input 2 (A12) combination as the reference source. See
Analoa inout reference correction below.
17 = ~ 1 1 ~ ~ 1Defines
2'- an analog input 1 (All) and analog input 2 (A12) combination as the reference source. See
Analog input reference correction below.
20 = KEYPAD(RNC) - Defines the control oanel as the reference source.
I .A St00 command resets the reference to zero (the R stands for reset.)
I I . ~ ~
chan&ng me conlrol source (ExTl to ExT2 EX;^ lo LXII) 0085 no1 COP) me reference
) Defines the contro panel as tne reference soLrce
21 = K E Y P A D ( ~ C -
A Stop command does not reset the reference to zero. The reference is stored.
-Changing the control source (EXTIto E X T ~EXT2 , to EXTI) does not copy the reference.
l ~ n a l o uinout reference correction
I I~aramete;values 9. 10 and 14...17 use the formula in the following table
Parameters
ACS550 User's Manual 111
---
Values must be positive (No negative speed values for constant speeds).
- Constant speed selections are ignored if:
-the torque control is active, or
- the process PID reference is followed, or
- the drive is in local control mode, or
- PFC (Pump-Fan Control) is active.
Note: Parameter 1208 CONST SPEED 7 acts also as a so-called fault speed which
may be activated if the control signal is lost. For example, see parameters 3001
AI<MIN FUNCTION, 3002 PANEL COMM ERR and 3018 COMM FAULT FUNC.
-
Code Description
-- -.-.... .- .- - . ... -.
1201 CONST
~- SPEED SEL
~ ~ ---
~~
Defines the digital inputs used to select Constant Speeds. See general comments in introduction
0 = NOT SEL- Disables the constant speed function.
1 = DII -Selects Constant Speed 1 with digital input DII
Digital input activated = Constant Speed 1 activated.
2...6 = 012...016 - Selects Constant Speed 1 with digital input 012...Dl6 See above.
7 = 011,2 - Selects one of three Constant Speeds (1... 3) using DII and 012.
Uses two digital inputs, as defined below (0 = Dl de-activated. 1 = 01activated):
Parameters
ACS550 User's Manual 113
,' i,a> Ja
%' ,:.\-:..;
.
...,3,v,6e
,
?+zh::*:<
,.
u>,,.* .,,, , ".?~.<,.,":,'
113 = 013.4.5 -Selects one of seven Constant Speeds (1...7) usino
, .
, .,*:*>:,~.., :: Z.,.'..
-
See above (011,2,3) for code.
- 013.
,
14 = 014.5.6 -Selects one of seven Constant Speeds (1...7) using 014, Dl5 and D16.
See above (011,2,3) for code.
15... 16 =TIMEDFUNC 1...4 - Selects Constant Speed 1 when Timed Function is active. See Group 36: TIMED
FI INCTIONS
. . - . .- .
19 =TIMEDFUN1&2 - Selects a constant speed depending on the state of Timed Functions 1 & 2. See parameter
-13 = 013,4,5(INV) - Selects one of seven Constant Speeds (1... 7) using 013, 014 and 015.
See above (oI1,2,3(INv)) for code.
-14 = D14,5,6(INV)- Selects one of seven Constant Speeds (1...7) using 014, 015 and 016.
See above (011,2,3(1~v)) for code.
1202 CONST SPEED I
Sets value for Constant Soeed 1
The range and m t s debend on parameter 9904 MOTOR CTR. MODE
Range 0 30000 rpm wnen 9904 = 1 (VECTOR s i ' c ~ v )or 2 (VECTOR
191<o,
I -
Ranae 0 500 h z wnen 9904 = 3 ISCALAR FREO) \ -
1..
1 Each sets a va Le for a Constant Speea See cohsr srEEn 1 aoove
1208 Constant Speeo 7 s ~ s e a d so as logging Speed See parameter 1004 .OGG hs SE-
- ....... -.. . .. - -. . .. .-
Parameters
114 ACS550 User's Manual
-
I~efinestimed function activated, constant speed mode. Timed function can be used to chanae between external
~ ~~ ~~~
reierence and a maximum of three constanispeeds, or to change between a maximum of 4 selectable speeds, i.e.
~
I
constant speeds 1, 2, 3 and 4.
1 = ExTlcs1/2/3 - Selects an external speed when no timed function is active, selects Constant speed 1 when only
Timed function 1 is active, Selects Constant speed 2 when only Timed function 2 is active and selects Constant
speed 3 when both Timed functions 1 and 2 are active.
External reference
Parameters
ACS550 User's Manual
..
M N '8 JM A cannot be greater Inan ~AXlrnL'IA
These paramelers trefere~icean0 analoq
reference.
- mln ano rnax sell nos)
" . ,orob de scale and offset ao ustrncni for the
I /
1303 FILTER A l l
Defines the filter time constant for analog input 1 (~11) /
Unfiltered signal
I I The filtered signal reaches 63% of a step change within the time
specified.
J
Time constant
1304 MINIMUM A12
Defines the minimum value of the analog input.
See MINIMUM A l l above.
1305 MAXIMUM A12
Defines the maximum value of the analog input.
See MAXIMUM A I ~above.
1306 FILTER A12
Defines the filter time constant for analog input 2 (~12).
See FILTER All above.
Parameters
116 ACS550 U s e i s Manual
ssa
, ' *A. , : :
.. ..:,x,.;'2.:*,.$;,.: ,--.
#,,.,., ,%,# ,.., ",
No faults exist.
-.
Supply voltage is within range.
Emergency Stop command is not on.
2 =RUN - Energize relay when the drive is running.
3 = FAULT(-I)- Energize relay when power is applied. De-energizes when a fault occurs
4 = FAULT- Energize relay when a fault is active.
5 = A U R M - Eneroize relav when an alarm is active.
I I
d
9 = SUPRVI
-
See Group 32: SUPERVISION starting on page 144.
-
UNDER Eneroize relav when first suoervised oarameter 13201). droos . below the limit (3202).
-
I I. See Group 3 2 S U P E ~ V I S I O N ' S ~ ~ ~ ~on
12 = suPRv3 o\rER - Enero ze reav rvnen tn rd suoervised oara~neter13207, exceeos the lim113209).
See Group 32: ~ ~ ~ ~ < ~ l ~ l on ~ page
~ ~ 144.
s t a r t i n ~
13 = S U P R V ~UNDER - Energize relay when third supervised parameter (3207) drops below the limit (3208).
I
.
See Group 32: SUPERVISION starting on page 144.
14 = A TSET POINT- Energize relay when the output frequency is equal to the reference frequency.
15 = FAULT(RST) - Energize relay when the drive is in a fault condition and will reset after the programmed auto-
delay.
See parameter 3103 DEN TIME.
16 = FLT~ALARM- Energize reiay when fault or alarm occurs.
17 = EXT CTRL- Energize reiay when external control is selected.
-
18 = REF 2 SEL - Eneroize relav when EXT2 is selected.
19 = CONST FREQ - Energ~zerelay when a constant speed 1s selected
20 = REF LOSS - Enerqize relav when reference or actlve control oiace 1s lost
121 = OVERCURRENT -Eneroize < relav when an overcurrent aiarm or fault occurs.
22 = O / F I ( ~ O ~ T A G E- Energze relay *hen all odergotage alarm or fa^ t occLrs
23 = oRlVE TEMP - Enerq~zere av wrlen a or ve or coltrol board overterncerature a arrn or fault occurs
124 = UNDERVOLTAGE - Geraize u Felav
~
, when an undervoitaoe
~
u alarm or fault occurs.
25 = n l l Loss - Energize relay when nll signal is lost.
~~
Parameters
ACS550 Useis Manual 117
--
- ..---.. -- ...- - .
ze relay oased on 1np.J f l u , I l'r; diius comm-ntcal on
Fie dous writes binary code n p~rameter0134 that can energ ze relay 1 re ay 6 accorolng lo tne 1ollov.ng
I.
Defines the switch-on delay for relay 3.
See RO 1 ON DELAY.
Parameters
118 ACS550 User's Manual
-
. . ... .
~ ~ i
-.
1409 RO 3 OFF DELAY
~~
p t
.--- -.
...
i o n
--. -I1
-
Switch-of delay for relay 3.
See RO 1 OFF DELAY.
1410 RELAY OUTPUT 4...6
-.. Defines the event or condition that activates relay 4...6 - what relay output 4...6 means.
1412 See 1401 REtAY OUTPUT 1.
1413 RO 4 ON DELAY
.
Defines the switch-on delay for relay 4.
See RO 1 ON DELAY.
1414 RO 4 OFF DELAY
Defines the switch-off delay for relay 4.
See RO 1 OFF DELAY.
1425 RO 5 ON DELAY
Defines the switch-on delay for relay 5.
See RO 1 ON DELAY.
1416 RO 5 OFF DELAY
Defines the switch-off delay for relay 5.
See RO 1 OFF DELAY.
1417 RO 6 ON DELAY
Defines the switch-on delay for relay 6.
See RO 1 ON DELAY.
1418 RO 6 OFF DELAY
Defines the switch-off delay for relay 6.
See RO 1 OFF DELAY.
1
Parameters
ACS550 User's Manual 119
k-
Parameter defined by value (value 102 = parameter 0102)
1502 A 0 1 CONTENT MIN 4AO (mA)
Sets the minimum content value. p $505I - - - - - -- -- --
.-
Content is the parameter selected by parameter 1501
Minimum value refers to the minimum content value that will be
P 1511
converted to an analog output.
.
These parameters (content and current min. and max. settings)
,
provide scale and offset adjustment for the output. See the
figure. P 1504 I
1503 A01 CONTENT MAX P 1510 1 A 0 CONTENT
P 1502 I1508
P 1503 1 1509
See the figure in parameter 1303.
1507 A 0 2 CONTENT SEL
Defines the content for analog output ~ 0 2 See
. AOI
CONTENT SEL above.
1508 1 ~ 0 CONTENT
2 MIN
Sets the minimum content value. See AOI
CONTENT MIN above.
1509 1 ~ 0 2CONTENT MAX
CONTENT MAX above.
Sets the maximum content value. See AOI
1510 MINIMUM A 0 2
Sets the minimum output current. See MINIMUM A01 above.
Parameters
120 ACS550 Usefs Manual
-
"-*"".-r
'""" >.,.r )! i;,i
.d>.,#$*; *.%_
-,-.... . . .";.,. ;. .
,.....*.~,,; .-,:....,:.z,
..**? , .. ,,.
.
g e n, , , , , . ,, ,; ;..,:, ::>!::>..,*:<:~ .
,,; ;p34
,,,..,,. ,,,,.,$....*,,. ;;,.8i: ,f*, .,..?. ?:,,,;
~%>,,,
,. . ,?:,:
:.:;;'/;?'!:;ly,,,:. ~ ,z.#".
~>.,, J,.(:!:;~ ~ ~ : , ~ , v ~ , ~ ~ ~ ~ * z ~ ~ :
?;<3:,?.;:%
1511 MAXIMUM A 0 2
Sets the maximum output current. See MAXIMUM AOI above.
1512 FILTER A 0 2
Defines the filter time constant for ~ 0 2 See
. FILTER AOI
above.
Parameters
ACS550 User's Manual
Parameters
122 ACS550 Useis Manual
I
1 = u l i - Dcfiries d gl:a input D I ~as a conlrol for cnanglng U5er Parameter Sels
The drlve loaos User Parameler Set 1 on the fa ng edge of tne d glla Input
- The
- - orlve oaas User Paramcler Set 2 on the ris ng edge of the olgita npLt
T h e User Parameter Set changes only when the drive is stopped.
2...6 = 012...016 - Defines digital input 012...016 as a control for changing User Parameter Sets.
See 011above.
-1 = oll(1NV) - Defines an inverted digital input o l l as a control for changing User Parameter Sets.
T h e drive loads User Parameter Set 1 on the rising edge of the digital input.
T h e drive loads User Parameter Set 2 on the falling edge of the digital input.
The User Parameter Set changes only when the drive is stopped.
2 . - 6 = DIZ(1NV)...DI~(INV) - Defines an inverted digital input Dl2...Dl6 as a control for changing User Parameter Sets
See 011(INV) above.
1606 LOCAL LOCK
Defines control for the use of the LOG mode. The LOC mode allows drive control from the control panel.
W h e n LOCAL LOCK is active, the control panel cannot change to LOG mode.
0 = NOT SEL- Disables the lock. The control panel can select LOC and control the drive.
1 = 011 -Defines digital i n ~ uDII
t as the control for settina- the local lock.
Ac18va1ng the dcgital inp-t lords 0-1 loca conrro
De-ac1,valng the o gital input enable ine -0C he ecllon
2 6 = 0 2 olb - Defines ala la1 nD,l ~ 1 2 D 6 as !he contro for settlna lne oc3 ock
1 See 011above.
I I 7 = Oh - Sets lne locn h e conlro panel cannot select ILOC and cannot contro the d r ~ / e
8 = coMh4 - Defnes bit 13 of the Command Word 1 as In? control lor settinq
The Command Word is supplied through fieldbus communication.
- the ocal low
T h e Command Word is 0301.
-1 = DIl(1NV) - Defines an inverted digital input Dl1 as the control for setting the local lock.
De-activating the digital input locks out local control.
Activating the digital input enable the LOG selection.
-2...-6 = D12(1NV)...DI~(INV)- Defines an inverted digital input Dl2...Dl6 as the control for setting the local lock.
S e e DI~(INV)above.
1607 PARAM SAVE
Saves all altered parameters to permanent memory.
Parameters altered through a fieldbus are not automatically saved to permanent memory To save, you must use
this parameter.
If 1602 PARAMETER LOCK = 2 (NOTSAVED),parameters altered from the control panel are not saved. To save, you
must use this parameter.
If 1602 PARAMETER LOCK = 1 (OPEN), parameters altered from the control panel are stored immediately to
permanent memory
0 = DONE - Value changes automatically when all parameters are saved.
1 =SAVE... -Saves altered oarameters to Dermanent memorv.
Parameters
ACS550 User's Manual 123
time to stop
(Par 2202)
Parameters
124 ACS550 User's Manual
----. --.
. -. .- .-- -
Code ~ e s c r i p l i o n
E k N A B L E2
Selects the source of the start enable 2 signal.
---...-......--.-.-. . -
--.
I
..-
Note: Start enable functionality differs from the run enable functionality.
0 = NOT SEL -Allows the drive to start without an external start enable signal.
1 = Dl1 -Defines digital input Dl1 as the start enable 2 signal.
This digital input must be activated for start enable 2 signal.
If the voltage drops and de-activates this digital input, the drive will coast to stop and show alarm 2022 on panel
display. The drive will not start until stalt enable 2 signal resumes.
2...6 = 012...016 - Defines digital input Dl2 ... Di6 as the start enable 2 signal.
See Dl1 above.
7 = COMM - Assigns the fieldbus Command Word as the source for the start enable 2 signal. Bit 3 of the Command
word 2 (parameter 0302) activates the start disable 2 signal.
-
See fieldbus user's manual for detailed instructions.
-1 = o l l ( l ~ v-) Defines an inverted digital input Dl1 as the start enable 2 signal.
-2...-6 = 012(1NV)... DI~(INV) - Defines an inverted digital input Dl2...Dl6 as the start enable 2 signal.
See 011 (INV) above.
1610 DISPLAY ALARMS
Controls the visibility of the following alarms:
.
2001, Overcurrent alarm
2002. Overvoitage alarm
2003, Undervoltage alarm
2009. Device overtemperature alarm.
For more information, see section Alarm 11stingon page 250.
0 =NO - The above alarms are suppressed.
1 =YES -All of the above alarms are enabled.
1611 PARAMETER VIEW
Selects the parameter view, i.e. which parameters are shown.
Note: This parameter is visible Only when it is activated by the optional FlashDrop device. FlashDrop is designed fo
fast copying of parameters to unpowered drives. It allows easy customization of the parameter list, e.g. selected
parameters can be hidden. For more information, see MFDT-Of FlashDrop User's Manual [3AFE68591074
(English)].
FlashDrop parameter values are activated by setting parameter 9902 to 31 (LOADFD SET).
0 = DEFAULT- Complete long and short parameter lists are shown.
1 = FLASHDROP - FlashDrop parameter list is shown. Does not include short parameter list. Parameters that are
hidden by the FlashDroP device are not visible.
Parameters
ACS550 Useis Manual 125
2002 IMINIMUM
SPEED I S.,OD~I ,
2001 value is < 0
I l~efinestheminimum speed (rpm) allowed.
A oosltlve for zero) mlnlmum meed value defines two ranaes.
I .1
and a'ne negative.'
speed value defines one speed range.
" '1 Time
See the figure
I
P 2001
Defines the maximum output current (A) supplied by the drive to the motor.
2005 OVERV VOLT CTRL
1 /Sets the DC overvoltaae controller on or off.
I I Fast orakmg of a h j h Inen a load cadses tne DC o-s vo tage lo rise to me overvoltage control I rn I lo pre,ent tne
DC vo taae from exceed~rigthe tr p m,t the ouervo lago controller automat.ca1 y oecreases the oranlng~.torque by.
increasing output frequency.
0 = DISABLE - Disables controller.
1 = ENABLE - Enables controller
Note: If a braking chopper or a braking resistor is connected to the drive, this parameter value must be set to
0 (DISABLE)to ensure proper operation of the chopper.
UNDERVOLT CTRL
Sets the DC undervoltage controller on or off. When on:
If the DC bus voltage drops due to loss of input power, the undervoltage controller decreases the motor speed in
order to keep the DC bus voltage above the lower limit.
When the motor weed decreases, the inertia of the load causes reaeneration back into the drive. keeDina - the DC
I I o-s cnargea and prevent ng an unde~voltage1r.p
The DC -ndarvoltage control cr incrsases povrer loss r ae-tnro-gh on systems w lh a h~gniccrtla sucn as a
centrifuge or a fan.
I
0 = DISABLE - Disables controller.
1 = ENAaLE(TIME) - Enables controller with 500 rns time limit for operation.
2 = ENABLE - Enables controller without maximum time limit for ooeration.
Parameters
126 ACS550 User's Manual
.**. .- .....~.~
""'.. .....* .
, Cddz *.&$
s*-'*m,..'-
&*.." .,,,.,.,.;<,'::~'2:"":":'"'i".:'i-
-,, DeScrlptlpn*-,*%;<;7Gs?>*a<;*~&
>>.,
,:<#&>?;.!>:$<&,~t:~&.;>:, *:$
;~
;' ;s,." ,%,,, .,,,-.:. " - '":., ,>%d*>?...A'v,:$. :.:?:,{'-*r:": -:."'-c.,<*
. ,, .>: .,::<~:4' $: ,,,:. :s<".7"J,~
;Z4:,
~s.$",,~::!
:'.:I-- ;::.,
:; :,.,<:.,: ;, : ; , ,.., ..<,<..
.,.A,,,
'
-
. ,,
P 2008
2007 value is 2 0 I
P 2007
n Time
-(P 2007) ---
Frequency range allowed
-(P 2008, .. - .-
I I 7 = CQMM - Defines bit 1 5 of the Command Word Ias the control for selecting the maximum limit used
T h e Command Word is supolied throuah fieldbus communication.
The Command Word is parameter 0301.
-1 = DII(1NV) - Defines an inverted digital input dil as the control for selecting the maximum limit used.
.Activating the digital input selects MAX TORQUE 1 value.
De-activating the digital input selects MAX TORQUE 2 value.
-2...-6 = D12(1NV) ... DI~(INV)- Defines an inverted digital input Dl2...Dl6 as the control for selecting the maximum limit
used.
See DI~(INV) above.
2015 MIN TORQUE 1
Sets the first minimum limit for torque (%). Value is a percent of the motor nominal torque.
2 0 1 6 MIN TORQUE 2
Sets the second minimum limit for torque (%). Value is a percent of the motor nominal torque.
Parameters
ACS550 User's Manual 127
Sets the first maximum limit for torque (%). Value is a percent of the motor nominal torque.
2018 MAX TORQUE 2
Sets the second maximum limit for torque (%). Value is a Dercent of the motor nominal toroue.
Parameters
128 ACS.550 Use& Manual
1Selects the motor start method. The valid options depend on the value of parameter 9904 MOTOR CTRL MODE.
1 =AUTO- Selects the automatic start mode.
Vector control modes: Optimal start in most cases. The drive automatically selects the correct output frequency to
I start a rotatina motor.
SChlAH rRLO mooe l~nrneolatestan from zero freqdency
2 = Dc ~ ~ A G-NSe ects the DC Magnet zlng stan mode
Note Tne DC Maonet ztnu slan mode cannot start a rotat na motor
Note: The drive siarts when the set pre-magnetizing time (parameter 2103 DC MAGN TIME)has passed, even if motoi
magnetization is not complete.
Vector control modes: Magnetizes the motor within the time determined by the parameter 2103 DC MAGN TIME
using DC current. The normal control is released exactly alter the magnetizing time. This selection guarantees
the highest possible break-away torque.
SCALAR:FREa mode: Maqnetizes the motor within the time determined bV the Darameter 2103 DC MAGN TIME usinc
DC current. The norma~controlis released exactly alter the magnetizing time.
13 =SCALAR FLYST - Selects the Rying start mode.
I .Vector control modes: Not aoolicable. I
.
1 1 SCAAR FrlFQ mooe The dr&e a-tomatica y se ecls the correct OJI[,LI
Torque boost is only applied at start, ending when output frequency exceeds 20 Hz or when output frequency is
equal to reference.
In the beginning the motor magnetizes within the time determined by the parameter 2103 DC MAGN TIME using DC
current.
-See parameter 2110 TORQ BOOST CURR.
5 =FLY + BOOST - Selects both the flying start and the torque boost mode (SCALAR:FREQ mode only).
Flying start routine is performed first and the motor is magnetized. If the speed is found to be zero, the torque
boost is done.
8 = RAMP -Immediate start from zero frequency.
!I02 STOP FUNCTION
Selects the motor stop method.
1 = COAST - Selects cutting off the motor power as the stop method. The motor coasts to stop.
2 = RAMP - Selects using a deceleration ramp.
Deceleration ramp is defined by 2203 DECELER TlME 1 Or 2206 DECELER TlME 2 (whichever is active).
!I03 DC MAGN TlME
Defines the pre-magnetizing time for the DC Magnetizing start mode.
Use parameter 2101 to select the start mode.
After the start command, the drive pre-magnetizes the motor for the time defined here and then starts the motor.
Set the pre-magnetizing time just long enough to allow full motor magnetization. Too long a time heats the motor
excessively.
!I04 DC HOLD CTL Motor
DC hold
Selects whether DC current is used for braking or DC Hold.
0 = NOT 5EL- Disables the DC current operation.
1 = DC HOLD - Enables the DC Hold function. See the diagram.
Requires parameter 9904 MOTOR CTRL MODE = 1 (VECTOR:SPEED) speed b I 7
Stops generating sinusoidal current and injects DC into the motor when
both the reference and the motor speed drop below the value of parameter
I
7105
Ref+ I 1 .
When Ule reference rises above the level of parameter 2105 the drive
resumes normal operation. T
2 = DC BRAKING - Enables the DC Injection Braking alter modulation has speed
stopped.
-
If parameter 2102 STOP FUNCTION is 1 (COAST),braking is applied after start is removed.
If parameter 2102 STOP FUNCTION is 2 (RAMP),braking is applied alter ramp.
ACS550 User's Manual 129
-..--.
n --
..
. ..
Code Description
.-.-..... .-
. - ..-. - ..- - .-- .--
. -.
2105 DC HOLD SPEED
Sets the speed for DC Hold. Requires that parameter 2104 oc HOLD CTL = 1 (DCHOLD).
2106 IDCCURR REF
Defines the DC current control reference as a percentage of parameter 9906 MOTOR NOM CURR.
2107 IDCBRAKE TIME
I~efinesthe DC brake time after modulation has stopped, if parameter 2104 is 2 (oc BRAKING).
2108 [START INHIBIT
Sets the Start inhibit function on or off. The Start inhibit function ignores a pending start command in any of the
following situations (a new start command is required):
A fault is reset.
Run Enable (parameter 1601) activates while start command is active.
Mode changes from local to remote.
Control switches from EXTI to E X T ~ .
Control switches from EXT2 to EXTI.
0 =OFF- Disables the Start inhibit function.
1 = ON - Enables the Start inhibit function.
2109 EMERG STOP SEL
Defines control of the Emergency stop command. When activated:
Emergency stop decelerates the motor using the emergency stop ramp (parameter 2208 EMERG OEC TIME).
Requires an external stop command and removal of the emergency stop command before drive can restart.
0 = NOT SEL - Disables the Emergency stop function through digital inputs.
1 = DII -Defines digital input DII as the control for Emergency stop command.
Activating the digital input issues an Emergency stop command.
De-activating the digital input removes the Emergency stop command.
2...6 = Dl2...016- Defines digital input 012...016 as the control for Emergency stop command.
See 011 above.
-1 = DI~(INV) - Defines an inverted digital input 011 as the control for Emergency stop command.
De-activating the digital input issues an Emergency stop command.
Activating the digital input removes the Emergency stop command.
2 . - 6 = D12(1NV)... 016(INv) - Defines an inverted digital input 012 ... 016 as the control for Emergency stop command.
See DI~(INV) above.
2110 TORQ BOOST CURR
-
Sets the maximum supplied current during torque boost.
See parameter 2101 START FUNCTION.
Parameters
130 ACS550 User's Manual
F?
Code Description
.- -....
2112 ZERO SPEED DELAY
....-... . -.-. .. -- . . -. .-. ...-. . -. .- ---
Defines the delay for the Zero Speed Delay function. If parameter value is set to zero, the Zero Speed Delay functior
is disabled.
The function is useful in applications where a smooth and quick restarting is essential. During the delay the drive
knows accurately the rotor position.
No Zero Speed Delay With Zero Speed Delay
Speed Speed
Speed controller switched off: Speed controller remains live.
Motor coasts to stop. Motor is decelerated to true 0 speed.
Zero Speed
Delay
Zero speed delay can be used e.g. with jogging function or mechanical brake.
No Zero Speed Delay
The drive receives a stop command and decelerates along a ramp. When the motor actual speed falls below an
internal limit (called Zero Speed), the speed controller is switched off. The drive modulation is stopped and the mot01
coasts to standstill.
With Zero S ~ e e d Delav
I l ~ h drive
e receives a st& command and decelerates alona a ramo. When the motor actual soeed falls below an I
II I nlernal i mil (called Zero Speeo) Ihe zero speed de ay funct on acthates Dur ng tna oela, tAe f-ncl on$ keeps lne
speed conlro ler ve The dr ve niod I ate5 moror ,s magnel zed arla dr ve is reaov for a qu c< restart
I ~ o t e Parameter
: 2102STOP FUNCTION must be 2 = RAMP for zero speed delay to bperate: I
10.0 = NOT SEL- Disables the Zero Speed Delay function.
2113 [START DELAY
,) Deiines the Start delay. After the conditions for start have been fulfilled, the drive waits until the delay has elapsed
and then starts the motor. Start delay can be used with all start modes.
If START DELAY =zero, the delay is disabled.
Durina the Start deiav. alarm 2028 START DELAY is shown.
Parameters
ACS550 User's Manual 131
/..Ramps are defned in palls one each for acce era1 on and aece erallon
See be on, for ihe ran p dafinlton parameters
0 = NOT SEL - Disables selection, the first ramp pair is used.
1 = o l l -Defines digital input o l l as the control for ramp pair selection.
Activating the digital input selects ramp pair 2.
De-activating the digital input selects ramp pair 1
2...6 = Dl2...016 - Defines digital input 012 ...016 as the control for ramp pair selection.
S e e oll above.
7 = COMM - Defines bit 10 of the Command Word 1 as the control for ramp pair selection.
T h e Command Word is supplied through fieldbus communication.
The Command Word is parameter 0301.
-1 = DII(INv) - Defines an inverted digital input 011as the control for ramp pair selection.
-
De-activating the diaital inwut selects ramo oair 2
Activating t& digitiinput'selects ramp pei; 1.
2...-6 = 012(1NV)...DI6(INV) - Defines an inverted diqital
. input 012 ... Dl6 as the control for ramp
. .pair selection
See ~ 1 1 ( l ~ v ) a b o v e .
!202 ACCELER TIME 1
Sets the acceleration time for zero to maximum frequency for ramp pair 1. See A in :goi ~ i n e a r
y;
the fiaure. - 7"-
~ c c u aacceleration
l time also depends on 2204 RAMP SHAPE 1.
See 2008 MAXIMUM FRED.
i
2203 DECELER TIME 1
Sets the deceleration time for maximum frequency to zero for ramp pair 1
++ B
+
(=O)
,('
.Actual deceleration time also depends on 2204 RAMP SHAPE 1
7
See 2008 MAXIMUM FREO.
2204 RAMP SHAPE 1
Selects the shape of the accelerationldeceleration ramp for ramp pair 1. See B in
FREQ 1 S-curve!
- -r
1
I I
ihe fg-re
Shape 1s defned as a ramp, n.. ess aad t ona Ime s spec f.ed here ro reacn tne
max mum frequency A longer Ime prov des a soRer lranslllon at each ena of the
slope. The shape becomes an s-curve.
Rule of thumb: 115 is a suitable relation between the ramp shape time and the 1
acceleration ramp time.
0.0 = LINEAR - Specifies linear accelerationldecelerationramps for ramp pair 1.
0.1 ... 1000.0 = s-CURVE- Specifies s-curve accelerationldeceleration ramps for
A = 2202 ACCELER
B = 2204 RAMP SHAPE 1
,
ramp pair 1.
2205 ACCELER TIME 2
I 1 Sets the acceleration time for zero to maxlmum frequency for ramp pair 2
See 2202 ACCELER TIME I
-- - acceleration time. See 1004 JOGGING SEL.
Used also as .ioqain~
2206 DECELER TlME 2
Sets the deceleration time for maximum frequency to zero for ramp pair 2.
See 2203 DECELER TlME 1
Used also as jogging deceleration time. See 1004 JOGGING SEL.
2207 IRAMP SHAPE 2
Selects the shape of the accelerationldeceleration ramp for ramp pair 2.
See 2204 RAMP SHAPE I.
Parameters
132 ACS550 User's Manual
.
I I1. Sets the deceleration time for maximum frequency to zero for an emergency
See parameter 2109 EMERG STOP SEL.
~ a m is
b linear.
2209 RAMP INPUT 0
Defines control for forcing the ramp input to 0.
0 = NOT SEL - Not selected.
1 = 011- Defines digital input 011as the control for forcing the ramp input to 0.
Activating the digital input forces ramp input to 0. Ramp output will ramp to 0 according to the currently used ramp
time, after which it will stay at 0.
- De-activating the digital input: ramp resumes normal operation.
2...6 2 012...Dl6 - Defines digital input Dl2...Dl6 as the control for forcing the ramp input to 0.
See DII above.
I I .- 7 = comm - Defnes o ~ 13 t of ine Coninlarid Woro 1 as rne conlro for iorc ng tne ramb nput lo 0
Ttle Command Wora IS s-ppl ea lnroLqh fle abLs communlcar on
I Tne Command Word is oarameter 0301
1 = ~ I ~ ( I N-VDefnes
) an Avertea dlgltal ~ulpurn l as me control for furclng the ramp I ~ P lo J ~0
. D2-aclvatlng the o q tal 1np.t forces ramp Input to O
Activating the digitaiinput: ramp resumes normal operation.
-2...-6 = 012(1NV)...DI6(INV) - Defines an inverted digital input 012 ...016 as the control for forcing the ramp function
generator input to 0.
S e e D I ~ ~ I N Vabove.
)
Parameters
ACS550 User's Manual
.
This group defines variables used for speed control operation.
. ".'.'",;" :;.. I.<>..:'<,';:,., : ,, :: - ,.,. . ,,,, .., .,'
co"dS.
, : ,,.,.,' "".:;'":~".',,
, .,.' ~.,.
, , .
. ,...
, ,, .
,.
,~,,,i,
Controller output
KP . TD . -
Error value
- - - A-4-
Gain = Kp =,I
T, = lntegratlon time > 0 K,-e' e = Error value
To= Derivation time > 0 t
T,= Sample time period = 2 ms
Ae = Error value change between two samples
. -- -,
Ti
Parameters
134 ACS550 Use& Manual
-.
Code Description
l i x A T l O N
-. -.-- .- .. ...-. ..-- - ...-. ..... .- -.. . - ....
I
1 I Sets the derivation time for acceleration compensation.
Adding a derivative of the reference to the output of the speed controller compensates for inertia during
acceleration.
2303 DERIVATION TIME describes the principle of derivative action.
Rule of thumb: Set this parameter between 50 and 100% of the sum of the mechanical time constants for the motoi
and the driven machine.
The figure shows the speed responses when a high inertia load is accelerated along a ramp.
I I ' No acceleration compensation Acceleration compensation
Actual speed
*Note: You can use parameter 2305 AUTOTUNE RUN to automatically set acceleration compensation.
2305 AUTOT TUNE RUN
Starts automatic tuning of the speed controller.
0 =OFF - Disables the Autotune creation process. (Does not disable the operation of Autotune settings.)
1 = ON - Activates speed controller autotuning. Automatically reverts to OFF.
Procedure:
I ~ o t e The
: motor load must be connected
..
Run the motor at a constant speed of 20 to 40% of the rated speed
Change the autotuning parameter 2305 to ON.
I ..The drive:
Accelerates the motor.
.
II I - Calcu atcs va es for propo,tlonal ga n lnlegrai on 1 me and sccc erarlon compensai!on
Chanqes parameters 2301 2302 ariu 2304 to these va "es
I ~ e s e i s2305 to OFF
Parameters
ACS550 User3 Manual
R
Code Description
2101 Td.<6 .. ..-. . .. . .. ..... ... ....- ..
Defines the torque reference ramp up tlme -The mlnlmum tlme for the reierence to Increase from zero to the
nominal motor torque
2402 ITORQ RAMP DOWN
Defines the torque reference ramp down tlme -The minimum time for the reference to decrease from the nominal
motor torque to zero.
Parameters
136 ACS550 User's Manual
I I
Set 2503 CRIT SPEED I HI = 23 HZ.
Set 2504 CRIT SPEED 2 LO = 46 Hz
Set 2505 CRT l SPEED 2 HI = 52 Hz.
Parameters
ACS550 U s e i s Manual
Changes the magnitude of the flux depending on the actual load. Flux Optimization can reduce the total energy
consumption and noise, and it should be enabled for drives that usually operate below nominal load.
0 = OFF - Disables the feature.
1 = ON - Enables the feature.
2602 FLUX BRAKING
Braking
Provides faster deceleration by raising the level of torque (%) Rated motor power
magnetization in the motor when needed, instead of
limiting the deceleration ramp. By increasing the flux in
the motor, the energy of the mechanical system is
changed to thermal energy in the motor.
Requires parameter 9904 MOTOR CTRL MODE =
1 (VECTOR:SPEED) OR 2 (VECTOR:TORO).
0 =OFF- Disables the feature.
1 = O N- Enables the feature.
5 10 20 30 40 50
A = IR compensated
B = No compensation
P 2603
IR COMP FREQ
Sets the frequency at which IR compensation is 0 V (in
% of motor frequency).
I
2605 UIF RATIO
Selects the form for the Ulf (voltage to frequency) ratio below field weakening point.
1 = LINEAR - Preferred for constant torque applications.
2 = SQUARED - Preferred for centrifugal pump and fan applications. (Square is more silent for most operating
frequencies.)
Parameters
138 ACS5.50 User's Manual
..-. ..-
;=I --....-
, E,-....
R ----.-. .-..-. . .
4
-- .... ..-.
Sets the switching irequency for the drive. Also see parameter 2607 SWITCH FREO CTRL and section Switching
frequency derating on page 262.
Higher switching frequencies mean less noise.
- The 1. 4 and 8 kHz switching frequencies are available i0r all types, except for ACS550-01-246.4-4 only 1 and
4 kHz are available.
The 12 kHz switching irequency is available only if parameter 9904 MOTOR CTRL MODE = 3 (SCALAR:FREO).
The 12 kHz switching frequency is available for 200 V and 400 V irame sizes R1...R4 (except for the R4 types
ACS550-01-O87A-4 and ACS550-U1-097A-4) and for 600 V frame sizes R2 ...R4.
SWITCH FREQ CTRL
The switching frequency may be reduced if the ACS550 R1...R4 drives, see par 2606
limit
internal temperature rises above a limit. See the figure.
This function allows the highest possible switching 12 kHz R5...R6 drives, see par 2606
frequency to be used based on operating conditions.
8kHz Drive
Higher switching frequency results in lower acoustic
temperature
noise.
0 = OFF - The function is disabled. 4 kHz ...'... ...7' . - - - - -
I I
~equiresparameter 9904 MOTOR CTRL MODE = 3 (SCALAR:FREQ).
0 - No slip compensation.
1...200 - Increasing - slip
. comuensation. 100% means full sliw comoensation
2609 NOISE SMOOTHING
+I This parameter introduces a random component to the switching frequency. Noise smoothing distributes the acoustic
,,.
motor noise over a range of frequencies instead of a single tonal frequency resulting in lower peak noise intensity.
The random component has an average of 0 Hz. It is added to the switching frequency set by parameter 2606
SWITCHING FREQ. This parameter has no effect if parameter 2606 = 12 kHz.
0 = DISABLE
1 = ENABLE.
2619 DC STABILIZER
Enables or disables the DC voltage stabilizer. The DC stabilizer is used in scalar control mode to prevent possible
voltage oscillations in the drive DC bus caused by motor load orweak supply network. In case of voltage variation the
drive tunes the frequency reference to stabilize the DC bus voltage and therefore the load torque oscillation.
0 =DISABLE- Disables DC stabilizer.
1 = ENABLE - Enables DC stabilizer.
Parameters
ACS550 User's Manual 139
Sets the trigger point for the drive's cooling fan counter.
.0.0
Value is compared to parameter 2902 value.
- Disables the trigger.
2902 COOLING FAN ACT
Defines tho actual value of the drive's cooling fan counter.
When parameter 2901 has been set to a non-zero value, the counter starts.
When the actual value of the counter exceeds the value defined by parameter 2901, a maintenance notice is
displayed on the panel.
0.0 - Resets the parameter.
2903 REVOLUTION TRlG
I I When the actual value of the counter exceeds the valuedefined by parameter 2905, a maintenance notice is
displayed on the panel.
0.0 - Resets the parameter.
2907 USER MWh TRlG
Sets the trigger point for the drive's accumulated power consumption (in megawatt hours) counter.
-Value is compared to parameter 2908 value.
0.0 - Disables the trigger.
2908 USER MWh ACT
Defines the actual value of the drive's accumulated Dower consumotion (in meaawatt hours) counter.
I I-- Wnen parameter 2907 has oeen set to a non-zero value the counter starts -
When the actua value of the coJnter exceeds tne bal-e defined oy parameter 2907 a ma nlenance not ce 1s
displayed on the panel.
0.0 -Resets the parameter.
Parameters
140 ACS550 User's Manual
I I Defines the drive response if the analog input (AI) signal drops below the fault limits and AI is used in reference chain.
3021 All FAULT LIMIT and 3022 A12 FAULT LIMIT Set
0 = NOT SEL - NOresponse.
~ ~
the fault limits
~~~~-~~~ ~-
/i\ WARNING! If you select CoNsT SP 7 Or LAST SPEED, make sure that continued operation is safe when the
analog input signal is lost.
3002 PANEL COMM ERR
Defines the drive response to a control panel communication error.
1 = FAULT - Disolavs a fault (10. PANEL LOSS) and the drive coasts to stoo. .~
2 = CONST SP 7 - disp ays a" alarm ,2008, PANE. I.OSS, and sets speed .*my 1208 cohsr SPrlio 7
II I
~
3 = LAST SPFEI) - D splays an a arm ,2008 PAhm - 0 s ) ano sets spoea s n o- rhe last ooerarina
" lebel Tn s ,a ue 1
s
1 the average
- meed
. over the last 10 seconds. I
WARNING! If you select CONST SP 7 or LAST SPEED, make sure that continued operation is safe when the
control panel communication is lost.
3003 IEXTERNAL FAULT I
Defines the External Fault 1 signal input and the drive response to an external fault.
0 = NOT SEL - External fault signal is not used.
1 = 011-Defines digital input 011as the external fault input.
Activating the digital input indicates a fault. The drive displays a fault (14, ExT FAULT 1) and the drive coasts to
stoo.
1 12...6 ='Dl2...016- Defines digital input Dl2...Dl6 as the external fault input. I
I I
S e e 011above.
-1 = DII(INv)- Defines an inverted digital input Dl1 as the external fault input.
De-activating the digital input indicates a fault. The drive displays a fault (14, EXT FAULT I) and the drive coasts to
stop.
-2...-6 = D12(1NV) ...DI~(INV)- Defines an inverted digital input 012...016 as the external fault input.
See DI~(INV) above.
3004 EXTERNAL FAULT 2
Defines the External Fault 2 signal input and the drive response to an external fault.
See parameter 3003 above.
3005 MOT THERM PROT
Defines the drive response to motor overheating.
0 =NOT SEL - NOresponse andlor motor thermal protection not set up.
1 =FAULT- When the calculated motor temperature exceeds 90 "C, displays an alarm (2010, MOTOR TEMP). When
the calculated motor temperature exceeds 110 "C, displays a fault (9. MOT OVERTEMP)
and the drive coasts to st01
2 = ALARM - When the calculated motor temperature exceeds 90 "C, displays an alarm (2010, MOTOR TEMP).
MOT THERM TlME
n
3006
Sets the motor thermal time constant for the motor temperature
. . ..- - ..
rnnrini load/
This is the time required for the motor to reach 63% of the final
temperature with steady load. I
For thermal protection according to UL requirements for NEMA
class motors, use the rule Of thumb: MOTOR THERM TIME equals
35 times t6, where t6 (in seconds) is specified by the motor
manufacturer as the time that the motor can safely. operate
. at six
I I-
times its rated current.
The thermal time for a Class 10 trip curve is 350 s, for a Class
20 trip cutve 700 s, and for a Class 30 trip curve 1050 s.
Parameters
ACS550 User's Manual 141
Cb' . , i'. .
. : '":,'.':
. d,cU~~E'iip;tioE'n"""""(tk~35~~12c~~,ii:I~;>*:~""""~~
,,
,
,; , ,,
; , , ,
%,
<,
<,:-':. ,,.-.
.
" ,,;:--
, :, : >,~,
. :. ' . .
%.,.
, ,
,,.,
:
..:<.:,~
, ,.,:,;: <->.
. , ,
:',8...:;.:;,,..,
- -- ,,.
:*,:.
3007 MOT LOAD CURVE
Output current (%) relative
Sets the maximum allowable operating load of the motor. to 9906 MOTOR NOM CURR
When set to loo%, the maximum allowable load is equal to the value
of parameter 9906 MOTOR NOM CURR.
-
Adjust the load curve level if the ambient temperature differs from
nominal.
3008 ZERO SPEED LOAD
Sets the maximum allowable current at zero speed.
Value is relative to 9906 MOTOR NOM CURR. P 3008 50
3009 BREAK POINT FREQ Frequency
Sets the break point frequency for the motor load curve.
P 3009
Example: Thermal protection trip times when parameters 3006 MOT THERM TIME, 3007 MOT LOAD CURVE and 3008
ZERO SPEED LOAD have default values.
3.0
I
0.5
0
' folfg~~
F
0 0.2 0.4 0.6 0.8 1.0 1.2
3010 STALL FUNCTION
This parameter defines the operation of the Stall function. This
protection is active if the drive operates in the stall region (see the
figure) for the time defined by 3012 STALL TIME. The "User LimiY' is
defined in Group 20: LIMITS by 2017 MAX TORQUE 1.2018 MAX TORQUE
2, or the limit on the COMM input. Torque1
0 = NOT SEL - Stall protection is not used. Current
1 = FAULT- When the drive operates in the stall region for the time set
by 3012 STALL TIME: Stall region
The drive coasts to stop.
A fault indication is displayed. 95%
2 =ALARM-When the drive operates in the stall region for the time set
by 3012 STALL TIME: limit
A n alarm indication is dis~laved.
T h e alarm disappears when'the drive is out of the stall region for
half the time set by parameter 3012 STALL TIME.
3011 ISTALL FREQUENCY P 3011
This parameter sets the frequency value for the Stall function. Refer to Stall frequency
the figure.
3012 ISTALLTIME
h his parameter sets the time value for the Stall function.
3017 IEARTH
FAULT
I I1 Defines the drive response if the drive detects a ground fault in the motor or motor cables. The drive monitors for
ground faults while the drive is running, and while the drive is not running. Also see parameter 3023 WRING FAULT.
0 = DISABLE - NOdrive response to around faults.
= ENABLE - Ground faults display Lult 16 (EARTHFAULT),and (if running) the drive coasts to stop.
Parameters
142 ACS550 User's Manual
.- -- ...-- --.
H
Code Description
3018 COMM FAULT FUNC
-. - . -. . -.- -..
1 = FAULT - Displays a fault (28, SERIAL 1 ERR) and the drive coasts to stop.
2 = CONST SP 7 -Displays an alarm (2005. VO COMM) and sets speed using 1208 C o N s T SPEED 7. This "alarm speed'
remains active until the fieldbus writes a new reference value.
3 = LAST SPEED - Displays an alarm (2005. I10 COMM) and sets speed using the last operating level. This value is t h ~
average speed over the last 10 seconds. This "alarm speed remains active until the fieldbus writes a new
reference value.
A WARNING! If you select CONST SP 7. or LAST SPEED, make sure that continued operation is safe when
fieldbus communication is lost.
3019 COMM FAULT TIME
Sets the communication fault time used with 3018 COMM FAULT FUNC.
Brief interruptions in the fieldbus communication are not treated as faults if they are less than the COMM FAULT TIME
value.
3021 A l l FAULT LIMIT
Sets a fault level for analog input 1
See 3001 AI<MIN FUNCTION.
3022 A12 FAULT LIMIT
Sets a fault level for analog input 2.
See 3001 AI<MIN FUNCTION.
3023 WIRING FAULT
Defines the drive response to cross wiring faults and to ground faults detected when the drive is NOT running. When
the drive is not running it monitors for:
Improper connections of input power to the drive output (the drive can display fault 35, OUTPUT WRING if improper
connections are detected).
Ground faults (the drive can display fault 16, EARTH FAULT if a ground fault is detected). Also, see parameter 3017
EARTH FAULT.
0 = DISABLE - No drive response to either of the above monitoring results.
1 = ENABLE- The drive displays faults when this monitoring detects problems.
3024 CB TEMP FAULT
Defines the drive response to control board overheating. Not for drives with an OM10 control board.
0 = DISABLE - NOresponse.
1 =ENABLE- Displays fault 37 (CB OVERTEMP) and the drive coasts to stop.
Parameters
ACS550 Useis Manual 143
A WARNING! When the analog input signal is restored, the drive may restart, even after a long stop. Make
sure that automatic, long delayed starts will not cause physical injury and/or damage equipment.
108 AR EXTERNAL FLT
Sets the automatic reset for external faults function on or off.
--~
Parameters
ACS5.50 User's Manual
1-tl ti
Energized ( I )
~GhlL
OJTPJT 2 ClC ) Vallle IS SLPRd1 O\ ER 01 S JPRV2 OVER USE 0
I for monitorina whenlif the su~ervisedsional exceeds a
gwen Ifm t r i e relay rema ns act1.e "nil tne s-pen~seo Case B
va ue drops be ow tne ow Ihm t Energized ( I )
Case R = Parameter 1401 RE.AY O J ~ P L1~for 1402 REnv
OUTPUT 2, etc.) value is SUPRVI UNDER or S U P R V ~UNDER. 0
Use for monitoring whenlif the supervised signal falls
below a given limit. The relay remains active until the LO > HI
supervised value rises above the high limit. Note: Case LO>HI represents a special hysteresis witt
LO >HI two separate supervision limits.
Operating data supervision using relay outputs, when LO>HI Active limit
Value of supervised parameter
@J
Tne louest llni I(1113203) 1s act ve fnlt a ly and renafns a c t ~ ~ e
A \4
.nt I tne sLperv sea parameter goes a o o ~ etne h ghest I mlt LO (3202)-- - - - -
( - 0 3202) ,nanlna that l ~ m t the 3ct ve Ifm I That llm 1 renialtis
active u&l the slpervised parameter goes below the lowest +
HI ( 3 2 0 3 ) - ~ 1 , - 4-C
t
u
limit (HI 3203). making that limit active. I I / / I I L
Case A = Parameter 1401 RELAY OUTPUT 1 (or 1402 RELAY
OUTPUT 2, etc.) value is ~UPRVI OVER or S U P R V ~OVER. Case A
Initially the relay is de-energized. It is energized whenever Energized (1)
the supervised parameter goes above the active limit.
Case B = Parameter 1401 RELAY OUTPUT 1 (or 1402 REIAY 0
OUTPUT 2, etC.) Value is SUPRVl UNDER Or SUPRV2 UNDER. Case B
Initially the relay is energized. It is de-energized whenever
the supervised parameter goes below the active limit. Energized (1)
3202 ISUPERV ILIM LO 0
Sets the low limit for the first supervised parameter. See
3201 SUPERV 1 PARAM above.
3203 ~SUPERV1 LIM HI
Sets the high limit for the first supervised parameter. See
3201 SUPERV 1 PARAM above.
3204 ~SUPERV2 PARAM
Selects the second supervised parameter. See 3201 SUPERV 1 PARAM above.
3205 ~SUPERV2 LIM LO
Sets the low limit for the second supervised parameter. See 3204 SUPERV 2 PARAM above.
3206 SUPERV 2 LIM HI
Sets the high limit for the second supervised parameter See 3204 SUPERV 2 PARAM above.
Parameters
ACS550 User's M a n u a l 145
-- ..---
&
Code Description
3r
-- - --.. .
PARAM
---. .-.... .
Selects the third supervised parameter. See 3201 SUPERV 1 PARAM above.
-- ...... . - - .---. .-.
1
-..
...
~~~~
p~~
Parameters
146 ACS550 User's Manual
Parameters
ACS550 U s e i s Manual 147
P 3404 P 3405
,. .,.....:. ,:; ,.~,
,??.*",.?><$;>>?:,' ,zc>:<z,<.:,.:...,,.
,:3:5..;~:\>>:;$;>,;.::;
j:<;,,'
' ,
:>
.5 ;<:;~
Parameters
148 ACS550 User's Manual
Parameters
ACS550 User's Manual 149
,. ..,..
" .
.i.*.liv.
,
.
.$.
,.
6*;_-
" , " :.,, .
,, ., , ,
;:-, ;,
,,, .. ,.
:,,,.,",::,, i ,;-,: ;,. l:,:s.,,.,>:',".
,..>.. :,' .:,<' #*+*:#<::!;< ,~>;';?!3t2-,;?,>*tR
<A
e
: ,,
.
6
,;, %G.-,
..,,, ..*.:.,*.*'...,,.,*, 2
,v:.;,:
. <,< ...
,.s . . ,: ~:.<;:
. :,: ?,> ,.,; ..:;:,..! ,;
.,,.'~
~,.
...<:x:;
,.*;
.
3421 OUTPUT^ MAX
1 /Sets the maximum value displayed for the third display parameter See parameter 3407. I
Parameters
ACS550 User3 Manual
Motor
, , , ,
, , ,
, , ,
A01
I ,
, .
,
AGND
10 n~
WARNING! IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either non-
conductive or conductive but not connected to the protective earth.
To fulfil this requirement, connect a thermistor (and other similar components) to the
drive's control terminals using any of these alternatives:
Separate the thermistor from live parts of the motor with double reinforced
insulation.
Protect all circuits connected to the drive's digital and analog inputs. Protect
against contact, and insulate from other low voltage circuits with basic insulation
(rated for the same voltage level as the drive's main circuit).
Use an external thermistor relay. The relay insulation must be rated for the same
voltage level as the drive's main circuit.
The figure below shows alternate thermistor connections. At the motor end the cable
shield should be earthed through a 10 nF capacitor. If this is not possible, leave the
shield unconnected.
Thermistor relay: THERM(O) or THERM(~) THERM(O)
+24 V DC
Parameters
ACS550 User's Manual 151
For other faults, or for anticipating m o t o r overheating using a model, see Group 30:
F A U L T FUNCTIONS.
-. ....- ..-
F:F--
Code Description
3501 SENSOR
-~~~ - - TYPE
~ - ~
~~~
.. - ... - -.. . . ..- - ..-
Identifies the type of motor temperature sensor used, PT100 ("C), PTC (ohm) or thermistor.
- .- . -
.
See parameters 1501 A01 CONTENT SEL and 1507 A02 CONTENTSEL.
0 = NONE
1 = 1 x PTIOO - Sensor configuration uses one PT 100 sensor.
Analog output AOI or ~ 0 feeds
2 constant current through the sensor.
The sensor resistance increases as the motor temperature rises, as does the voltage over the sensor.
T h e temperature measurement function reads the voltage through analog input A l i or A12 and converts it to
degrees Celsius.
2 = 2 x PT100 - Sensor configuration uses two PT100 sensors.
Operation is the same as for above 1 x PT100.
3 = 3 x PTIOO - Sensor configuration uses three PTlOO sensors. ohm
Operation is the same as for above 1 x PT100.
A = PTC - Sensor configuration uses PTC.
T h e analog output feeds a constant current through the sensor.
T h e resistance of the sensor increases sharply as the motor
temperature rises over the PTC reference temperature (T,) as does
the voltage over the resistor. The temperature measurement function 550 . -1.. . :. . .I. . . .
reads the voltage through analog input A IIconverts it into ohms.
and
~
Parameters
ACS550 User's Manual
Time Period 2
3606 START TlME 2 I
3607 crno r, 8, , kv a- Lc c 7 3626 TIMED FUNC 1 SRC
3606 START DAY 2
3609s~vru~r~ ?,
Parameters
ACS550 User's Manual 153
12:oo:oo
Time period 3 a
09:OO:OO
Parameters
154 ACS550 User's Manual
~
See parameter 3602
~~~
-
I
Defines the booster ON time. Time is started when booster sel
signal is released. If parameter value is 01:30:00, booster is I
B~~~~~~active
active for 1 hour and 30 minutes after activation Dl is released. I I
I I
I I Activation Dl
I
I
I Booster time I
Parameters
ACS550 U s e f s Manual 155
r1---- -
--. .-
1
Code Description
21 = ~l + T ~ +-BBooster sna- -
Time Per ods 1 ano 3 selecteu in tne Imer
122 = T2+T3+B - Booster and Time Periods 2 and 3 selected in the timer.
1 I
23 = TI+TZ+T~+B - Booster and Time Periods 1, 2 and 3 selected in the timer.
24 = T4+B - Booster and Time Period 4 selected in the timer.
25 = TI+T4+B- Booster and Time Periods 1 and 4 selected in the timer,
26 = T ~ + T ~ + B Booster
- and Time Periods 2 and 4 selected in the timer.
27 = TI+R+T4+B - Booster and Time Periods 1, 2 and 4 selected in the timer.
28 = T ~ + T ~ -+ Booster
B and Time Periods 3 and 4 selected in the timer.
29 = T I + T ~ + T ~ -
+BBooster and Time Periods 1, 3 and 4 selected in the timer.
30 = T2+T3+T4+B - Booster and Time Periods 2, 3 and 4 selected in the timer.
31 = ~1+2+3+4+B- Booster and Time Periods I,2, 3 and 4 selected in the timer.
3627 TIMED FUNC 2 SRC
See parameter 3626.
3628 TIMED FUNC 3 SRC
See parameter 3626.
3629 TIMED FUNC 4 SRC
-See Darameter 3626.
Parameters
156 ACS550 User's Manual
-
Defines the frequency value of the first load curve definition point.
Must be smaller than 3707 LOAD FRED 2.
3705 LOAD TORQ LOW 1
Defines the torque value of the first underload curve definition point.
Must be smaller than 3706 LOAD TOR0 HlGH I.
3706 LOAD TORQ HlGH I
Defines the torque value of the first overload curve definition point.
3707 LOAD FREQ 2
Defines the frequency value of the second load curve definition point.
Must be smaller than 3710 LOAD FREa 3.
3708 LOAD TORQ LOW 2
-
Defines the torque value of the second underload curve definition point.
Must be smaller than 3709 LOAD TORQ HlGH 2.
3709 LOAD TORQ HlGH 2
Defines the torque value of the second overload curve definition point.
3710 LOAD FREQ 3
Defines the frequency value of the third load curve definition point.
Must be smaller than 3713 LOAD FREa 4.
3711 LOAD TORQ LOW 3
Defines the toroue value of the third underload curve definition Doint.
1.
Must be smalier than 3712 LOAD TOR0 HIGH 3.
3712 LOAD TORQ HlGH 3
I Def~nesthe torque value of the thlrd overload curve defin~t~on
polnt
Parameters
ACS550 User's Manual 157
R- .- .-
Code Description
3713 LOAD FREQ 4
- ...--
. -...
-
....--
.
--.-
--..
.
-. --
.-. .
Defines the frequency value of the fourth load curve definition point.
Must be Smaller than 3716 LOAD FREO 5
3714 LOAD TORQ LOW 4
I I. Defnes tne torque va "0 of me f o ~ n hJnoer oaa cJnc de1.n Iton potnr
M.sI be srna ler tnan 3i15
3715 LOAD TORQ HIGH 4
rof.0 d.Gh 4
Defines the torque value of the fourth overload curve definition point.
3716 LOAD FREQ 5
Defines the frequency value of fifth load curve definition point.
3717 LOAD TORQ LOW 5
I I- Dcf~nesthe rorqJe value of tnc f frh Lnder oao curie aef n ltori po nr
Must oe srna. er Inan 3718 .o~oTORQ htGi 5
Defines the torque value of the fifth overload curve definition point.
1
curves shown in the figure. The parameter characteristics were as described below.
If the load drops below the T..
,"I
set curve for longer than
(%) Underload curve types
the time set by parameter 80
3014 UNDERLOAD TIME 70%
(obsolete), the underload
protection is activated.
Curves 1... 3 reach
60
Bq
maximum at the motor
rated frequency set by
parameter 9907 MOTOR 20
.
_
. ..
NOM FREQ.
-
TM= nominal torque of the
motor
,1 I
I 8 f
f~ 24 IN
f N = nominal frequency of
the motor.
If you want to emulate the behavior of an old underload curve with parameters as in
the shaded columns, set the new parameters as in the white columns in the two
tables below:
Parameters
ACS550 User's Manual
New parameters
-
3705
LOAD
TORQ
LOW 1
(%)
EU US EU US
32 38 41 50
31 37 30 42 50 40
Parameters
ACS550 User's Manual 159
PANEL
Torque - LOCIREM
Power-- selection
- LOC
REM
Power-
Panel REF 1 -m
Dl -
Al -
Comm REF 1 --L___
Const
Comm REF 2
P4013
Comm
Internal
plDl out
Current
Torque
Power P4014 P4015
c u r r $ \ m PID Act Value
Power
Torque Li-
Note: In order to activate and use the PID controller, parameter 1106 must be set to
value 19.
Parameters
ACS550 Useis Manual
-
Initially, set:
4001 GAIN = 0.1.
.4002 INTEGRATION TlME = 20 seconds.
Stan the system and see 11I reacnes tne setpolnl q.1 ck y wn le mainta n.ng stable opera! on If not, ncrease GA N
(4001) "nt I tne actLal slgnal (or orwe speed) osc llales constantl, It may be necessarv to stan and s t o ~
ine dr~veto
induce this oscillation.
Reduce GAlN (4001) Until the oscillation stops.
Set GAIN (4001) to 0.4 to 0.6 times the above value.
- Decrease the INTEGRATION TIME (4002) until the feedback signal (or drive speed) oscillates constantly. It may be
necessary to start and stop the drive to induce this oscillation.
- Increase INTEGRATION TIME (4002) until the oscillation stops.
Set INTEGRATION TlME (4002) to 1.15 to 1.5 times the above Value.
If the feedback signal contains high frequency noise, increase the value of parameter 1303 FILTER AII or 1306
FILTER ~ 1 until
2 the noise is filtered from the sianal.
Parameters
Bv
ACS550 Useis Manual 161
I -
l~efinesthe PID controller's intearation time. I
lntegration time is, by definition, the time required to increase the
.-
output by the error value:
Error value is constant and 100%.
Gain= I.
D(P4001 = I 0
C(P4001=1)
lntegration time of 1 second denotes that a 100% change is
achieved in 1 second.
0.0 = NOT SEL - Disables integration (I-part of controller).
0.1 ...3600.0 - lntegration time (seconds). ,
P 4002 -,
See 4001 for adjustment procedure. A = Error
B = Error value step
PID output
D-part of controller 01
P 4001
0314 3.14
3142 3.142
Parameters
162 ACS550 Use& Manual
*"-,
$&$z
-'-.-..".#."-,'
.'* * ,-.,.,,..,,. .:--.,,.
*,;,'.."..
~~~3~#~&~s~x:;;>2,;$J.,;,:t
*-,\,;:,,,, <,--^,.p,. . ::
, ' -,.-..l:j, r;".a,
<.?* "~
;*.?>:&$~>;r.;;$~?:,.. ,>..~.,
~;:$<
r r;. .,,
:<:., ,<
,,-.< ,-.'
,,> .:
t:-,,? A.<:, :'.:,
,. ,,,.'.,,
, , : ,%:. :,,
,
.'., . ' ',
,,..
$. ,.
,. ,,,., *..,:.-
,?& ' ."':~':
..,,
-, ..>,5!$:.-?:.;.:+(.-l
?::,a :,.'?
~ <
,?
.i;,..ri,
;',:;, . .
. :s?:;F;:
- ,' -.:..---.>; -r.i.
P 4009
-
to the PID controller's actual values.
Units and scale are defined by parameters 4006 and 4007.
P 4008
8 -
0%
-1000.0%
Internal scale (%)
I I
$010 SET POINT SEL
Defines the reference siqnal source for the PID controller.
.
Parameter has no s f i n f~canceNhen tho PID reg-lator s by-passe0 (see 8121 REG BYPASS CIR.,
/O = t(wPAD - Contra panel prov~desreference
1 = AII -Atlalog input 1 provides reference.
2 = ~ 1 -Analog
2 input 2 provides reference.
8 = COMM - Fieldbus provides reference.
9 = COMM+AI~ -Defines a fieldbus and analog input 1 (All) combination as the reference source. See Analog input
reference correction below.
10 = COMM+AII -Defines a fieldbus and analog input 1 (All) combination as the reference source. See Analog input
reference correction below.
11 = D13U,4D(RNC) - Digital inputs, acting as a motor potentiometer control, provide reference.
--
013 increases the speed (the U stands for ''up")
014 decreases the reference (the D stands for "down").
--
Parameter 2205 ACCELER TIME 2 controls the reference signal's rate of change.
R = Stop command resets the reference to zero.
NC = Reference value is not copied.
12 = 013U,40(NC)- Same as D13,40(RNC) above, except:
Stop command does not reset reference to zero. At restart the motor ramps up, at the selected acceleration rate
to the stored reference.
I 3 = DI5U,6D(NC) - Same as D I ~ U , ~ D ( N
above,
C ) except:
.
Uses digital inputs Dl5 and 016.
14 = All+A12 - Defines an analog input 1 (~11)and analog input 2 (A12) combination as the reference source. See
Analog input reference correction below.
15 = ~11.~12 -Defines an analog input 1 (AII) and analog input 2 (~12)combination as the reference source. See
Analog input reference correction below.
16 = All-A12 - Defines an analog input 1 (~11)and analog input 2 (A12) combination as the reference source. See
Analog input reference correction below.
17 = ~ 1 1 1 ~-Defines
12 an analog input 1 (AII) and analog input 2 (~12)combination as the reference source. See
Analoa input reference correction below.
19 = INT~RNAL- A constant value set using parameter4011 provides reference.
20 = PID20UT - Defines PID controller 2 output (parameter 0127 PlD 2 OUTPUT) as the reference source.
Parameters
ACS550 Usefs Manual 163
Where:
C = Main reference value 120A
( = COMM for values 9. 10 and
= AII forvalues 14...17)
- B = Correcting reference
( = AII for values 9. 10 and
2 values 14...17).
= ~ 1 for
Example:
The figure shows the reference source curves for
value settings 9. 10 and 14... 17. where:
. C = 25%.
P 4012 SETPOINT MIN = 0.
P 4013 SETPOINT MAX = 0.
8 varies along the horizontal axis.
0 100% 6
4011 INTERNAL SETPNT
Sets a constant value used for the process reference.
Units and scale are defined by parameters 4006 and 4007.
4012 SETPOINT MIN
Sets the minimum value for the reference signal source.
See parameter 4010.
4013 SETPOINT MAX
Sets the maximum value for the reference signal source.
See parameter 4010.
4014 FBK SEL
Defines the PID controller feedback (actual signal).
You can define a combination of two actual values (ACTIand ACTZ) as the feedback signal.
Use parameter 4016 to define the source for actual value 1 ACT^).
Use parameter 4017 to define the source for actual value 2 (ACTZ).
1 = ACTl -Actual value 1 (Acrl) provides the feedback signal.
2 = ACTI-ACT;! -ACT? minus ACT^ provides the feedback signal.
3 = ACTI+ACT;! - A C T l plus ACT2 provides the feedback signal.
4 = ACTI'ACTZ-ACT% times ACT;!provides the feedback signal.
5 = ACTIIACTZ ACT^ divided by ACT;!provides the feedback signal.
6 = MIN(ACT1,2) -The smaller of ACT$ or ACT^ provides the feedback signal.
7 = MAX(ACT~ ,2) -The greater of ACTI or ACT;!provides the feedback signal.
8 = sqrt(~c~1-2) - Square root of the value for ACTI minus ACT^ provides the feedback signal.
9=sq~l+sq~ - 2Square root of ACTIplus the square root of ACT^ provides the feedback signal.
10 = s q r t ( ~ c ~-
1 )Square root of ACTI provides the feedback signal.
11 COMM FBK 1 -Signal 0158 PlD COMM VALUE 1 provides the feedback signal.
12 = COMM FBK 2 - Signal 0159 PI0 COMM VALUE 2 provides the feedback signal.
13 = AVE(ACT1,Z) -The average of ACTl and ACT2 provides the feedback signal.
4015 FBK MULTIPLIER
Defines an extra multiplier for the PID feedback value FBK defined by parameter 4014.
Used mainly in applications where the flow is calculated from the pressure difference.
0.000 = NOT SEL - The parameter has no effect (1.000 used as the multiplier).
-32.768...32.767 - Multiplier applied to the signal defined by parameter 4014 FBK SEL.
Parameters
164 ACS550 User's Manual
.- . .
'~odel~escri~tion
-- - .. . -.....--
14016 IACTI INPUT
Defines the source for actual value 1 (ACT?).See also parameter 4018 ACTI
MINIMUM.
1 = AII - Uses analog input 1 for ACTI
2 = A12 - Uses analog input 2 for ACTI.
3 =CURRENT-Uses current for ACTI
4 =TORQUE - Uses torque for ACT?
5 = POWER - Uses power for ACTI
6 = COMM ACT 1 - Uses Value Of signal 0158 PlD COMM VALUE 1 for ACT1
7 = COMM ACT 2 - Uses value of signal 0159 PIU COMM VALUE 2 forAcT1.
1017 ACT2 INPUT
Defines the source for actual value 2 (AcR). See also parameter 4020 ACR
MINIMUM.
1 = AII-Uses analog input 1 for ACT^.
2 =~ 1-2 Uses analog input 2 for ACT^.
3 =CURRENT-Uses current for ACT^.
4 = TORQUE - Uses torque for ACT^.
5 = POWER - Uses power for ACQ.
6 = COMM ACT 1 - Uses value of signal 0158 PID COMM VALUE 1 for ACT^.
7 = COMM ACT 2 - USeS Value of Signal 0159 PlD COMM VALUE 2 for ACT2.
4018 ACT1 MINIMUM
ACT1 (%)
t
Sets the minimum value for ACT? A
Scales the source signal used as the actual value ACT1 (defined p 4019 -- -- -----
I
bv ~arameter4016 ACTI INPUT). For ~arameter4016 values
I
~'(COMM ACT I) and 7 (COMM ACT2) ;caling is not done. I I /
7
I I
Par401,6 ,2::$Source$2.,i
1
2
3
Analog input 1
Analog input 2
Current
5:SQurcemin.::.
1301 MINIMUM AII
0
.,. ' . Source max!
1302 MAXIMUM AII
1304 MINIMUM ~ 1 2 1305 MAXIMUM~ 1 2
2 . nominal current
P 4018
'-t i *
Source min. Source max.
- Source signal
4 7 - 2 nominal torque 2 . nominal torque
5 Power -2. nominal power 2 - nominal power
ACT1 (%I A R
See the figure: A= Normal: B = Inversion (ACT?MINIMUM > ACTI P 4018
MAXIMUM)
4019 ~ACTI MAXIMUM
Sets the maximum value for ACTI
See 4018 ACT1 MINIMUM.
4020 ACT2 MINIMUM
Sets the minimum value for ACT^.
See 4018 ACTl MINIMUM.
Source signal
4021 ACT2 MAXIMUM
Sets the maximum value for ACT^.
See 4018 ACT1 MINIMUM.
4022 SLEEP SELECTION
Defines the control for the PID sleep function.
0 =NOT SEL- Disables the PID sleep control function.
1 = 011- Defines digital input DII as the control for the PID sleep function.
Activating the digital input activates the sleep function.
-
De-activating the digital input restores PID control.
2...6 = 012... 016 - Defines digital input 012 ...016 as the control for the PID sleep function.
See DII above.
7 = INTERNAL - Defines the output rpmlfrequency, process reference and process actual value as the control for the
PID sleep function. Refer to parameters 4025 WAKE-UP DEV and 4023 PID SLEEP LEVEL.
-1 = DII(INV) - Defines an inverted digital input Dl1 as the control for the PID sleep function.
De-activating the digital input activates the sleep function.
Activating the digital input restores PID control.
-2...-6 = D12(lNV)...DI6(INV) - Defines an inverted digital input 012 ...Dl6 as the control for the PID sleep function.
-
-
See DI~(INV)above.
Parameters
ACS550 User's Manual 165
--
I I I
function istopping the drive).
Requires 4022 = 7 (INTERNAL).
Sets the time delay for the PID sleep function - a motor speed I
freauencv below 4023 PID SLEEP LEVEL for at least this time oeriod
I IIWAKE-UP
.'
enables the PID sleep function (stopping the drive).
See 4023 PlD SLEEP LEVEL above.
4025 DEV
Defines lne wane.up der~aton -- a dev~aton from thc sctpo nt
stop :
I I greater lnan rhls va.uc. for at leas1 the t me per~od4026 WAKE-JP
DELAY, re-starts the PID controller.
Parameters 4006 and 4007 define the units and scale.
- Parameter 4005 = 0,
Wake-up level = Setpoint - Wake-up deviation. Setpoint
. Parameter 4005 = 1. P 4025
-----
4005 = 0
Parameters
166 ACS550 User's Manual
Process PID (PIDI) has two separate sets of parameters, PID set 1 and PID set 2
PID set 1 uses parameters 4001 ...4026.
PID set 2 uses parameters 4101 ...4126.
PID 1 PARAM SET defines which set is selected.
0 = SET 1 - PID Set 1 (parameters 4001 ...4026) is active.
1 = Dl1 -Defines digital input DII as the control'for PID Set selection.
Activating the digital input selects PID Set 2.
De-activating the digital input selects PID Set 1.
2...6 = Dl2...Dl6 - Defines digital input Dl2...Dl6 as the control for PID Set selection
- See DII above.
7 =SET 2 - PID Set 2 (parameters 4101 ...4126) is active.
8... 11 =TIMEDFUNC 1.:'.4 - Defines the Timed Gnction as the control for the PID Set selection (Timed function de-
activated = PID Set 1: Timed function activated = PID Set 2)
See Grow 36: TIMED FUNCTIONS.
12 = 2-ZONEMIN - The drive calculates the difference between setpoint 1 and feedback 1 as well as setpoint 2 and
feedback 2. The drive will control the zone (and select the set) that has a larger difference.
A positive difference (a setpoint higher than the feedback) is always larger than a negative difference. This keep:
feedback values at or above the setpoint.
Controller does not react to the situation of feedback above setpoint if another zone's feedback is closer to its
setpoint.
13 = 2-ZONE MAX - The drive calculates the difference between setpoint 1 and feedback 1 as well as setpoint 2 and
feedback 2. The drive will control the zone (and select the set) that has a smaller difference.
A negative difference (a setpoint lower than the feedback) is always smaller than a positive difference. This keep:
feedback values at or below the setpoint.
Controller does not react to the situation of feedback below setpoint if another zone's feedback is closer to its
setpoint.
14 =?.-ZONE AVE - The drive calculates the difference between setpoint 1 and feedback 1 as well as setpoint 2 and
feedback 2. In addition, it calculates the average of the deviations and uses it to control zone 1. Therefore one
feedback is kept above its setpoint and another is kept as much below its setpoint.
-1 = DI~(INV) - Defines an inverted digital input DII as the control for PID Set selection.
Activating the digital input selects PID Set 1
De-activating the digital input selects PID Set 2.
-2...-6 = DIZ(1NV)...DI6(INV) - Defines an inverted digital input Dl2... Dl6 as the control for PID Set selection.
See DI~(INV)above.
Parameters
ACS550 Usets Manual
Parameters
ACS550 User's Manual
4228 ACTIVATE
Defines the source for enabling the external PID function.
Requires 4230 TRIM MODE = 0 (NOT SEL).
0 = NOT SEL - Disables external PID control.
1 = Dl1 -Defines digital input DII as the control for enabling external PID control.
Activating the digital input enables external PID control.
De-activating the digital input disables external PID control.
2...6 = Dl2...Dl6 - Defines digital input 012... 016 as the control for enabling external PID control.
See 011above.
7 = DRIVE RUN- Defines the start command as the control for enabling external PID control.
Activating the start command (drive is running) enables external PID control.
8 = ON - Definesthe power-on as the control for enabling external PID control.
Activating power to the drive enables external PID control.
9...12 =TIMED FUNC 1...4 - Defines the Timed function as the Control for enabling external PID control (Timed
function active enables external PID control).
See Group 36: TIMED FUNCTIONS.
-1 = DI~(INV) - Defines an inverted digital input DII as the control for enabling external PID control.
i Activating the digital input disables external PID control.
De-activating the digital input enables external PID control.
-2...-6 = D12(1NV)...DI~(INV)- Defines an inverted digital input Dl2...Dl6 as the control for enabling external PID control.
S e e DI~(INV)above.
4229 OFFSET
Defines the offset for the PID output.
When PID is activated, output starts from this value.
When PID is deactivated, output resets to this value.
Parameter is active when 4230 TRIM MODE = 0 (trim mode is not active).
4230 TRlM MODE
I I Selects the type of trim, if any. Using the trim it is possible to combine a corrective factor to the drive reference.
0 =NOTSEL- Disables the trim function.
1 = PROPORTIONAL -Adds a trim factor that is ~ r o ~ o r t i o nto
a lthe romlHz reference.
12 = DIRECT-Addsa trim factor based on the doniro~loop's maximum limit.
I
4231 ITRIM SCALE
I l~efinesthe multiplier (as a percent. plus or minus) used in the trim mode. I
Parameters
ACS550 Useis Manual 169
I Ramped ref .W
I Switch I Select - - Trimmed ref
-
(par. 4230) Trim scale Mul. + C
+-
Ext ref Imax (A) ,
off
t
,- X X "
Ext ref 2 max (6) proportional
Abs max speed1 direct Select
freq (C) (par 4232)
Parameters
ACS550 User's Manual
Sets the number of pulses provided by an optional encoder for each full motor shaft revolution (ppr).
102 IENCODER
ENABLE
l~nablesidisablesan optional encoder
0 = DISABLE- Drive uses speed feedback derived from the internal motor model (applies for any setting of paramete
9904 MOTOR CTRL MODE).
1 = ENABLE- Drive uses feedback from an oDtional encoder. This function reauires the Pulse Encoder
~ ~~~- Interface
~- ~ - -
Moable ro~~c.01, an0 an encoder operaton depends on the sell ng of parame~er5904 rnoron C T I ~MODE.
.9901 = 1 (VECTORSPEED) Tne encooer provldes mprovfd speeo feeabacn and Improved low speed torque
accuracy.
- 9904 = 2 (VECT0R:TORO): The encoder provides improved speed feedback and improved low speed torque
accuracy.
9904 = 3 (SCALAR:SPEED): The encoder provides speed feedback. (This is not closed loop speed regulation.
However, using parameter 2608 SLIP COMP RATIO and an encoder improves steady state speed accuracy.)
103 ENCODER FAULT
Defines the drive operation if a failure is detected in communication between the encoder and the encoder interface
module, or between the module and the drive.
1 = FAULT - The drive generates fault ENCODER ERR, and the motor coasts to a stop.
2 =ALARM- The drive generates alarm ENCODER ERR and operates as if parameter 5002 ENCODER ENABLE =
0 (DISABLE), that is, speed feedback is derived from the internal motor model.
I10 Z PLS ENABLE
Enablesldisables the use of an encoder's Z-pulse to define the motor shaft's zero position. When enabled, a Z-pulse
input resets parameter 0146 MECH ANGLE to zero to define the shaft's zero position. This function requires an encode
that provides Z-pulse signals.
0 = DISABLE - Z-pulse input is not present or ignored if present.
1 = ENABLE - A Z-pulse input resets parameter 0146 MECH ANGLE to zero.
I11 POSITION RESET
Resets the encoder's position feedback. This parameter is self-clearing.
0 = DISABLE - Inactive.
1 = ENABLE - Resets the encoder position feedback. Parameters reset depends on the state of parameter 5010 z PL!
.....
5010 = 0 (D SARLE, - Reset appl~esto parameters 0147 M E C I REVS anu 0146 rnrcn A ~ G - E
= 1 (ENABLE) - Reset apples on y to parameter 0147 h:f!cd ntbs
. -...... --. .. --
Parameters
ACS550 User's Manual 171
I I- 32 = CANopen
37 = DEVICENET
I
5102 FB PAR 2...FB PAR 26
... Refer to communication module documentation for more information on these parameters.
5126
~ -~
..
y = minor revision number
z = correction number
Example: 107 =revision 1.07
5129 FlLE CONFIG ID
Displays the revision of the drive's fieldbus adapter module's configuration file identification.
File configuration information is drive application program-dependent.
5130 FlLE CONFIG REV
Contains the revision of the drive's fieldbus adapter module configuration file.
Example: I = revision 1
5131 FBA STATUS
Contains the status of the adapter module.
0 = IDLE - Adapter not configured.
1 = EXECUT INIT- Adapter is initializing.
2 = TIME OUT - A timeout has occurred in the communication between the adapter and the drive.
3 = CONFIG ERROR - Adapter configuration error.
T h e revision code of the adapter's CPI firmware revision is older than required CPI firmware version defined in
the drive's configuration file (parameter 5132 c 5128).
4 = OFF-LINE - Ada~teris off-line.
5 = ON-LINE- ~ d a p t e ris on-line.
6 = RESET- Adapter is performing a hardware reset.
5132 ]FBA CPI FW REV
Contains the revision of the module's CPI program. Format is xyz where:
x = major revision number
.
y = minor revision number
z = correction number
I~xarnple:107 = revision 1.07
5133 ~FBAAPPL FW REV
I hontains the revision of the module's aoalication orooram. Format is xvz (see oarametrer 5132)
Parameters
ACS550 Usefs Manual
I I- Contains a count of the characters received that cannot be placed in the buffer.
Longest possible message length for the drive is 128 bytes.
Received messaqes exceedinq 128 bvtes overtlow the buffer. The excess characters are counted
I I1.- Contams a count of the messages with a CRC error that the drive receives. For high counts, check:
- noise levels qenerate
Ambient electro-maqnetic noise levels - hiqh
CRC calculations f& possible errors.
- errors.
Parameters
ACS550 User's Manual
1
1 '0 = 4oQ DRV .LI - operalo" of Corllrol ~let..sVJoroi conforms lo ABB Drlves Proh e as used In ACS4OO
Parameters
174 ACS550 Useis Manual
j
QTd'E ~-e~ijjr~8g&~~~~~saw<~~~~~~~z:.~:L~
~w-.I~~&.*.dy-.dy-.dy-
# ,, *&~&>~w~4,&5~~&>a*~;$2{$~~&&5i *#A-j
.A.
..-'''....,,,.,.. ,.;<[i8g;;;
;;e<j2:*;;~;~~~~;~~~~~~~~~;$:~2;p.;.-.~~*:i#~ '$7:
rd3*-i;b$r%?:$*%2a>x:s:$:(3<z+::;5.;i.::~;$< $gj;$
,...
:=r;.?*,.-
:
: %.- :.-<' ' .-7- ",,"
5311 ~EFBPAR 11
Specifies the parameter mapped to Modbus Register 40006.
5312 ~EFBPAR 12
Specifies the parameter mapped to Modbus Register 40007.
5313 EFB PAR 13
Specifies the parameter mapped to Modbus Register 40008.
5314 EFB PAR 14
Specifies the parameter mapped to Modbus Register 40009.
5315 ~EFBPAR 15
Specifies the parameter mapped to Modbus Register 40010.
5316 ~EFBPAR 16
Specifies the parameter mapped to Modbus Register 40011
5317 EFB PAR 17
Specifies the parameter mapped to Modbus Register 40012.
5318 EFB PAR 18
For Modbus: Sets additional delay in milliseconds before the ACS550 begins transmitting response to the master
request.
5319 EFB PAR 19
ABB Drives profile (Ass DRv LIM or AEE ORV FULL) Control Word. Read only copy of the Fieldbus Control Word.
5320 EFB PAR 20
ABB Drives profile IABB ORV LIM or ABB DRV FULL) Status Word. Read onlv copy of the Fieldbus Status Word.
Parameters
ACS550 User's Manual
Parameters
176 ACS550 User's Manual
.
Sets the frequency limit used to star? the first auxiliary motor. The first auxiliary motor starts if
No auxiliary motors are running.
f (Hz)
ACS550 output frequency exceeds the limit:
8109 + 1 Hz.
Output frequency stays above a relaxed limit
4
fMAX - - - -
P8ll5 --1: :-
(8109 - 1 Hz) for at least the time: 8115 AUX MOT START D.
.( P 8109
810!3)+~#
After
Output
the first
frequency
auxiliary
decreases
motor starts:
by the value =
Parameters
ACS550 User's Manual 177
Sets the frequency limit used to stop the first auxiliary motor. The first auxiliary motor stops if:
Only one (the first) auxiliary motor is running. f (HZ)
ACS550 output frequency drops below the limit:
8112 - 1.
Output frequency stays below the relaxed limit P 8109
(8112 + 1 Hz) for at least the time: 8116 nux MOT STOP 0.
After the first auxiliary motor stops:
Output frequency increases by the value =
(8109 START FREQ 1) - (8112 LOWFREQ 1). P 8112
. In effect. the output of the speed regulated motor increases to
compensate for the loss of the auxiliary motor.
('
I
Sets the frequency limit used to stop the second auxiliary motor
See 8112 LOW FREO 1 for a complete description of the operation
The second auxiliary motor stops if:
-
Two auxiliary motors are running.
ACS550 outout freauencv droas below the limit: 8113 - 1
1-
Output freqiency siays delow'the relaxed limit (8113 + 1 Hz) for at least the time: 8116 AUX MOT STOP D.
8114 LOW FREQ 3
Sets the frequency limit used to stop the third auxiliary motor.
See 8112 Low FREQ 1 for a complete description of the operation.
The third auxiliary motor stops if:
--
Three auxiliary motors are running.
ACS550 output frequency drops below the limit: 8114 - 1
Output frequency stays below the relaxed limit (8114 + 1 Hz) for at least the time: 8116 AUX MOT STOP D.
8115 AUX MOT START D
Sets the Start Delay for the auxiliary motors.
The output frequency must remain above the start frequency limit (parameter 8109, 8110, or 8111) for this time
period before the auxiliary motor starts.
-
See 8109 START FREQ 1 for a complete description of the operation.
8116 AUX MOT STOP D
Sets the Stop Delay for the auxiliary motors.
-
The output frequency must remain below the low frequency limit (parameter 8112, 8113, or 8114) for this time
period before the auxiliary motor stops.
See 8112 Low FREQ 1 for a complete description of the operation.
Parameters
178 ACS550 Usefs Manual
-.An external digital output module can be added to provide relay outputs R 0 4 . . R06.
Parameters 1401... 1403 and 1410... 1412 define, respectively, how relays R 0 1... R 0 6 are used - the parameter
value 31 PFC defines the relay as used for PFC.
The ACS550 assigns auxiliary motors to relays in ascending order. If the Autochange function is disabled, the firs
auxiliary motor is the one connected to the first relay with a parameter setting = 31 PFC, and so on. If the
Autochange function is used, the assignments rotate. Initially, the speed regulated motor is the one connected to
the first relay with a parameter setting = 31 PFc, the first auxiliary motor is the one connected to the second relay
with a parameter setting = 31 PFC, and so on.
I I
Standard PFC mode PFC with Autochange mode
The fourth auxiliary motor uses the same reference step, low frequency and start frequency values as the third
auxiliarv motor.
Parameters
ACS550 User's Manual 179
---
1.1... 336-The operating time interval (the time when the start
signal is on) between automatic motdr changes. I+
11 - 11
A WARNING! h h e n enabled, tne A~lochangefunct~on
requtres the inter ocks (8120 II.TERIOCKS = value > 0
enabled. During autochange the power output is
1 'I
interrupted and the drive coasts to stop, preventing
damage to the contacts. PFC with Autochanae mode
Parameters
180 ACS550 User's Manual
Sets an upper limit, as a percent of output capacity, for the autochange logic. When the output from the PIDIPFC
control block exceeds this limit, autochange is prevented. For example, use this parameter to deny autochange when
the Pump-Fan system is operating near maximum capacity.
Autochange - overview
The purpose of the autochange operation is to equalize duty time between multiple motors used in a system. At each
autochange operation:
A different motor takes a turn connected to the ACS550 output - the speed regulated motor.
The starting order of the other motors rotates.
The Autochanae function rewires:
Externa snlicngear for chang ng tne dr (e s OL~PLIpower connections
Parameter 8120 INTFRI OCKS = value > 0
l~utochan~ iseperformed when:
I. The running time since the previous autochanae reaches the time set bv 8118 AUTOCHNG INTERV,
The PFC np-t is oeo*, t h c l e ~ eset by th s pa-rameler. 8119 ALTOCIING'LEIIE.
Notc: The ACS55O alnays coasts to stcp when aLtocnange s performeo
In an autochange, the Autochange function does all of the PID output
following (see the figure):
Initiates a change when the running time, since the last
autochange, reaches 8118 AUTOCHNG INTERV, and PFC
input is below limit 8119 AUTOCHNG LEVEL.
- Stops the speed regulated motor.
Switches off the contactor of the speed regulated motor,
Increments the starting order counter, to change the
starting order for the motors.
ldentifies the next motor in line to be the speed regulated
motor.
Switches off the above motor's contactor, if the motor was I 1"P8122
running. Any other running motors are not interrupted. I
Switches on the contactor of the new speed regulated rc P 8118- I-- P8118-
motor. The autochanae switchaear connects this motor to B
the ACS550 power oltp-I - A =Area aoove 8119 A - T O C ~ ~L ~E G
~EL -
Delays molor stan for trle tlme 8122 PI c STAR r DELAY a-tochange rlol a loueo
Starts the speed regulated motor. B = Autochange occurs.
ldentifies the next constant speed motor in the rotation. IPFC, etc. = PID output associated with each motor.
Switches the above motor on, but only if the new speed
regulated motor had been runnina (as a constant s ~ e e d
molor) - Th s step deeps an e q i numoer of motors running oefore and aher aLtochange
Con1 nues w th norma PFC operat on
Starting order counter Output
The operation of the starting-order counter:
The relay output parameter definitions (1401...1403 and
1410... 1412) establish the initial motor sequence. (The lowest MAX
parameter number with a value 31 (PFC) identifies the relay
connected to IPFC, the first motor, and so on.)
Initially, IPFC = speed regulated motor, 2PFC = 1st auxiliary
motor, etc.
The first autochange shifts the sequence to: 2PFC =speed
regulated motor, 3PFC = 1st auxiliary motor, ..., IPFC =last
auxiliary motor.
The next autochange shifts the sequence again, and so on.
If the autochange cannot start a needed motor because all
inactive motors are interlocked, the drive displays an alarm
(2015, PFC I LOCK). P 8119 100%
When ACS550 power supply is switched off, the counter
preselves the current Autochange rotation positions in permanent memory When power is restored, the
Autochange rotation starts at the position stored in memory.
- If the PFC relay configuration is changed (or if the PFC enable value is changed), the rotation is reset. (See the firs
bullet above.)
Parameters
ACS550 User's Manual 181
Defines operation of the lnterlock function. When the lnterlock function is enabled:
--An interlock is active when its command signal is absent.
An interlock is inactive when its command sianal is wresent.
. .-
The ACS550 vr tI not start f a start c o m m a n ~ o c c ~when
control pane. olsplays an alarm (2015, PFC LOCO
r i tne speea reg.. ate0 inoror's fnterlock is act.,e - the
.
Wire each lnterlock circuit as follows:
Wire a contact of the motor's OnIOff switch to the lnterlock circuit - the drive's PFC loaic can then recoanize that
the niolor is s.v~tcnedoff aria stan the next avai ab.e motor
-W,re a contact of tne motor thermal re ay (or otner protect ve uevlce in tne motor clrcL 1) to tne lnterloc~np-t - tne
drive's PFC logic can then recognize that a motor fault is activated and stop the motor.
0 = NOT SEL - Disables the lnterlock function. All digital inputs are available for other purposes.
.
Requires 8118 AUTOCHNG INTERV = 0 (The Autochange function must be disabled if lnterlock function is disabled.)
1 = 011-Enables the lnterlock function and assians a diaital input (startino with 011) to the interlock sianal for each
"
PFC relay Tnese assignments are oerned in ihe follow rlq table and debend on
the n-mber of PFC relays [number of parameters 1401 1403 anu 1410 1412 w m va Le = 31 (PI c)]
-
the A.llocliange f-nction stat~s(d sab ed if 8118 AUTOCt~riGI h T E R V = 0 an0 olncW se enab ed)
012...016: Free
1013...016: Free
2 011: Speed Reg Motor Dt1: First PFC Relay
012: First PFC Relav 012: Second PFC Relav
I 1013: Second PFC delay
1014...016: Free
1013...~ 1 6Free
I
: I
3 011: Speed Reg Motor 011: First PFC Relay
012: First PFC Relay 012: Second PFC Relay
I I012: ~ / r sPFC
t ?Way
013: Second PFC Relay
014: Third PFC Relav
015: Fourth PFC ~ e i a y
016: Fifth PFC Relay
012: Second PFC ~ e l a y
013: Third PFC Relay
D14: Fourth PFC Relav
015: Fifth PFC Relay
016: Free
1
6 Not allowed 011: First PFC Relay
~ 1 2Second
: PFC Relav
013: Third PFC Relay
014: Fourth PFC Relay
D15: Fifth PFC Relay
016: Sixth PFC Relay
Parameters
182 ACS550 User's Manual
.....--
-. -.
enaolea) 1
2 = ~2 - Enao es the lllterlocn fdnctlon and sssigns a dlglta. np-t (stari~nghllh u 2) to trle Interlock signal for each
PFC relay Toese ass gnrnents are defined in lhc fol owing laole ana aepend on
tne n-mbor 01 PFC re a)s [number of parameters 1401 1403 and 1410.. 1412 .v th valLe = 31 (PFC)]
lne A-tochange f-ncl on sta1.s (dsablea f 8118 AJTOClihti hTChV = 0, arid o t h e ~ l s e
013...616: ~ r e e -
1 011: Free oll: Free
012: Speed Reg Motor 012: First PFC Relay
013: First PFC Relay Dl3...016: Free
1014...016: Free
2 1011: Free 1~11:Free
Free
DII:
Parameters
ACS550 Usei-s Manual 183
. -..
... L -- -..-- .
.-
3 = 013 - Enaoles tne Inter ocks funcl'on and asslgns a oglla input (slart ng w i n D 3) to the
I I PFC relav- ~ -These
, - - assianments are defined in the followina table and d e ~ e n don: I
. <
I I I
~ ~~ ~~
th; nunber of PFC reays [numoer of parameters 1401 1403 and 14i0 . 1412 wiln value = 31 (PFc)]
.
F:,,[
Ine A~lochangef ~ n c r o nstatus (d sab ed 118118 ALTOC~NC:
No. Br.c-
.----. - .
n11 0 % Free
I~IER
Autochange e n a b l T -
(P 8118) -. --
lhoi a ov~eo 1
= 0V and otnerv~lseenao ed)
4 = 014 - Enables the Interlock function and assigns a digital input (starting with 014) to the interlock signal for each
PI-C relay .I ncsc asslgnrnei,ts are deinea n the fo low;ng la0 e and aepenu on
-
t h e numoer of PFC relays [nulnoer of parameters 1401. 1403 and 1410 1412 wtn bal-e 31 ( v F c . ]
. the Aulochangc f~ncllonsratus ,d sab ed if 0118 AJroct~hGhTiRd = 0 ano olnerv,lSe e13aOle0,
Parameters
184 ACS550 User's Manual
$.5f,3 t i ~'$*a.ev<.,h"
3 ~ ~ ~ ~'*i,7F.,~
at.>ey*,
~.4;*d6* ~ " .* ~ ~ ~ i ;ect
,**
~M
~r>&..
$q&
tpp*"&
"' ~ ~.:*,~ : ~ ~ ~ ~ *~
>
<>i.-i.i.i.i.i.i.i.-i.i.i.i.
k$i;&a
i ~ ; ~ ~ ~ B ~ ~ ~ y.; ..7,x~ g*,.,,.: *.,<a
.,: + ~ ~.?'>~
i. v.5M
..,f,,,
:,;:~*:@~+~~~;j,~[~;<;g$;,~~,2,$~~::::::;~;;
-",Ua- #
.' ,pa.. ~ !<?+":z'
5 = Dl5 - Enables the Interlock function and assigns a digital input (starting with 015) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
I
t h e number of PFC relavs [number of ~arameters1401... 1403 and 1410... 1412 with value = 31 ~PFCII . ~,.
I -the Autochange function siatus (disabied if 8118AUTOCHNG INTERV = 0, and othelwise enabled).
I
6 = 016- Enables the Interlock function and assigns digital input Dl6 to the interlock signal for the speed regulated
motor.
Requires 8118 AUTOCHNG INTERV = 0.
NP,;;,"range disabled Autochange e n a b l e d -
Parameters
ACS550 Usefs Manual 185
,elects Regulator by-pass control. When enabled. Regulator by-pass control provides a simple control mechanism
rithout a PID reauiator.
Use ~egulatoFby-passcontrol only in special
applications. four
= NO - Disables Regulator by-pass control. The drive
uses the normal PFC reference: 1106 REF:! SELECT.
= YES - Enables Regulator by-pass control.
T h e Process PiD reauiator is bv~assed.
~ c t i avalue
l of P I D ~ Sused asihe PFC reierence
(input). Normally D(T REF2 is used as the PFC
reference.
T h e drive uses the feedback signal defined by 4014
FBK SEL (or 4114) ior the PFC frequency reierence.
T h e figure shows the relation between the control P 8113
signal 4014 FBK SEL (OR4114) and the speed
regulated motor's frequency in a three-motor
system. I
:xample: in the diagram below, the pumping station's
utiet flow is controlled by the measured inlet flow (A). P-A-WB-C- (Yo)
A = No auxiliary motors running
B = One auxiliary motor running
Contactors C = Two auxiliary motors running
Outlet pipe1
+A Sewage
I tank
I P2 \ Outlet pipe2
Inlet pipe
Outlet pipe3
Aiter the ACS550 relay output switches a motor on, the star-delta starter must switch to the star-connection and
then back to the delta-connection before the drive applies power.
So, the PFC Start Delay must be longer than the time setting of the star-delta starter.
-- -. . . - -
F C ENABLE
elects PFC control. When enabled, PFC control:
Switches in, or out, auxiliary constant speed motors as output demand increases or decreases. Parameters 8109
START FREO 1 to 8114 LOW FREQ 3 define the switch points in terms of the drive output frequency.
Adjusts the speed regulated motor output down, as auxiliary motors are added, and adjusts the speed regulated
motor output up, as auxiliary motors are taken off line.
Provides Interlock functions. if enabled.
Requires 9904 MOTOR CTRL'MOOE = 3 (SCALAKFREQ).
= NOT SEL - Disables PFC control.
=ACTIVE - Enables PFC control
Parameters
186 ACS550 User's Manual
- -
Code/~escription
....
8124 ~ A C CIN AUX STOP I.
I I.1 Sets the PFC acceleration time for a zero-to-maximum
frequency ramp. This PFC acceleration ramo:
I I1 0 = NOT SEL.
0.1 ... 1800 -Activates this function usina
~ ~
I I-
I
Sets rhe PFC deceleration t me for a maxlm~m-to-zero
freqJency ramp Tn s PFC dece erallon ramp
A = speed regulated motor accelerating using Group 22:
ACCEUDECEL parameters (2202 or 2205).
Appl~esto tne speed requlatea motor. v.han an auxl ary 8 = speed regulated motor decelerating using Group
1 motor is switched on. -
. - 1 22: ACCEUDECEL parameters (2203 or 2206\.
-
and 3 spare motors).
This value includes also the speed regulated motor.
This value must be compatible with the number of relays allocated to PFC if the Autochange function is used.
If Autochange function is not used, the speed regulated motor does not need to have a relay output allocated to
PFC but it needs to be included in this value.
-
128 AUX START ORDER
Sets the start order of the auxiliary motors.
1 =EVENRUNTIME - Time sharing is active. The start order depends on the run times.
2 =RELAY ORDER - The start order is fixed to be the order of the relays.
ACS550 Useis Manual 187
Parameters
ACS550 Usets Manual
Parameters
ACS550 Useis Manual
Overview
The ACS550 can be set up to accept control from an external system using standard
serial communication protocols. When using serial communication, the ACS550 can
either:
receive all of its control information from the fieldbus, or
be controlled from some combination of fieldbus control and other available
control locations, such as digital or analog inputs and the control panel.
Fieldbus
Control interface
In general, the basic control interface between Modbus and the drive consists of:
Output words
- Control Word
- Reference1
- Reference2
Input words
- Status Word
- Actual value 1
- Actual value 2
Embedded fieldbus
AGS5.50 User's Manual
- Actual value 3
- Actual value 4
- Actual value 5
- Actual value 6
Actual value 7
-
- Actual value 8
The content of these words is defined by profiles. For details on the profiles used,
sees section ABB controlprofi/es technical data on page 209.
Note: The words "output" and "input" are used as seen from the fieldbus controller
point of view. For example an output describes data flow from the fieldbus controller
to the drive and appears as an input from the drive point of view.
Planning
Network planning should address the following questions:
What types and quantities of devices must be connected to the network?
- What control information must be sent down to the drives?
What feedback ~nformat~on
must be sent from the drives to the controlling
system?
1
Mechanical and electrical installation - EFB
WARNING! Connections should be made only while the drive is disconnected from
the power source.
Embedded fieldbus
AGS550 User's Manual 191
To reduce noise on the network, terminate the RS485 network using 120 !2
resistors at both ends of the network. Use the DIP switch to connect or disconnect
the termination resistors. See following diagram and table.
Terminated Terminated
station Station Station station
m m
\ A A - 2
Connect the shield at each end of the cable to a drive. On one end, connect the
shield to terminal 28, and on the other end connect to terminal 32. Do not connect
the incoming and outgoing cable shields to the same terminals, as that would
make the shielding continuous.
For configuration information see the following sections:
- Communication set-up - EFB on page 191
- Activate drive control functions - EFS on page 193
- The appropriate EFB protocol specific technical data. For example, Modbus
protocol technical data on page 201.
Note: If you cannot see the desired selection on the panel, your drive does not have
that protocol software in the application memory.
Embedded fieldbus
ACS550 User's Manual
Note: Afler any changes to the communication settings, the protocol must be
reactivated by either cycling the drive power, or by clearing and then restoring the
station Id (5302).
Embedded fieldbus
ACS550 User's Manual
1001 EXTl COMMANDS 10 (COMM) StartlStop by fieldbus 40001 bits 0...3 40031 bits 0, 1
with Extl selected.
1002 EXT2 COMMANDS 10 (COMM) StartlStop by fieldbus 40001 bits 0...3 40031 bits 0, 1
with Ex12 selected.
I I I I I
I
1003 1I DIRECTION 11 3 ,(REQUEST) II Direction bv fieldbus. 1I 400214003~ 1I 40031 bit 3 I
' tables
For Modbus, the protocol reference can depend on the profile used, hence two columns in these
One column refers to the ABB Drives profile, selected when parameter 5305 = 0 (ABB DRV
LIM)or 5305 = 2 (ABB DRV FULL). The other coiumn refers to the DCU orofile selected when
parameter 5305 1 (Ocu PRO~ILE). See section ABB controlprohles iechnical data on page 209
The reference provides direction control - a negative reference provides reverse rotation.
Embedded fieldbus
ACS550 User's Manual
1102 EXTIIEXTZ SEL 8 (COMM) Reference set selection by fieldbus. 40001 bit 11 40031 bit 5
1103 REF1 SELECT 8 (COMM) Input reference 1 by fieldbus. 40002
1106 REF2 SELECT 8 (COMM) Input reference 2 by fieldbus. 40003
Reference Scaling
Where required, REFERENCES can be scaled. See the following, as appropriate:
Modbus Register 40002 in section Modbus protocol technical data on page 201
Reference scaling in section ABB control profiles technical data on page 209.
I
Modbus protocol
Drive parameter Value Description reference
ABB DRV DCU PROFILE
1
1601 RUN ENABLE Run enable bv fieldbus. 40001 bit 3 140031 bit 6
1
1604 FAULT RESET SEL 1 8 (COMM) I Fault reset by fieldbus.
I (inverted)
140001 bit 7 140031 bit 4
I I I I
1
1606 LOCAL LOCK 1 8 (COMM) I Source for local lock selection is I Does not 140031 bit 14
the fieldbus. / apply
1
1607 PARAM SAVE I I(SAVE) I saves altered parameters to I 41607
I I8 II I memorv. (then
I . value returns to 0). Ii 1
1608 START ENABLE 1 7 (COMM) Source for Start enable 1 is the Does not 40032 bit 2
fieldbus Command word. apply.
1609 START ENABLE 2 7 (COMM) Source for start enable 2 is the
fieldbus Command word.
2013 MIN TORQUE SEL 7 (coMM) Source for minimum torque
selection is the fieldbus.
i
2014
lI
lnAx TORQJE SE.
L
2201 ACC/DEC 112 SEL
i I
7 (COMA) Source for max:m~mtorque
e c1 t on 1s h e fie1d.u
7 (COMM) Source for ramp pair selection is
the fieldbus. H 40031 bit 10
Embeddedfieldbus
ACS550 Usefs Manual
Modbus protocol
Drive parameter Description reference
ABB DRV DCU PROFILE
Embeddedfieldbus
ACS550 User's Manual
(Set 2)
(ExVTrim)
Communication fault
When using fieldbus control, specify the drive's action if serial communication is lost.
I Drive warameter II Value 1I Descri~tion I
3018 COMM FAULT FUNC 0 (NOT sEL)
I(FAULT)
Set for appropriate drive response.
1
I3 [LAST SPEED)
3019 1 COMM FAULT TIME I Set time delay before acting on a communication loss.
Embedded fieldbus
ACS550 User's Manual
I I
0107 DC BUS VOLTAGE 40107
0109 1 OUTPUT VOLTAGE 40 109
0301 1I FB CMD WORD1 -bit 0 (STOP) II 40301 bit 0
0301 FB CMD WORol 1 - bit 2 (REV) 40301 bit 2
0118 I Dl 1-3 STATUS- bit 0 (D13) 40118
Note: W~thModbus, any parameter can be accessed using the format "4" followed
by the parameter number
Embeddedfieldbus
ACS550 Useis Manual
For example:
Value o f the
Feedback Parameter
parameter that
(Feedback integer). (Parameter resolution) -
integer resolution (Value of 100% ref.) 1100% =Scaled value
, defines 100%
,
10
I
0.1% 1 1500 rpm' 1 0 - 0.1%. 1500RPM / 100%=15rpm
100 0.1% / 500 HZ' 100. 0.1% - 500 Hz 1 100% = 50 Hz
' Assuming, for the sake ofthis example, that the Actual Value uses parameter9908
as the 100% reference and that 9908 = 1500 rwm.
MOT NOM SPEED
' Assuming, for the sake of this example, that the Actual Value uses parameter9907
as the 100% reference and that 9907 = 500 Hz.
MOT NOM FREO
Diagnostics - EFB
Embedded fieldbus
ACS550 User's Manual
Diagnostic situations
The sub-sections below describe various diagnostic situations -the problem
symptoms and corrective actions.
Normal operation
During normal network operation, 5306 ...5309 parameter values act as follows at
each drive:
5306 EFB OK MESSAGES advances (advances for each message properly received
and addressed to this drive).
5307 EFB CRC ERRORS does not advance at all (advances when an invalid
message CRC is received).
5308 EFB UART ERRORS does not advance at all (advances when character format
errors are detected, such as parity or framing errors).
- 5309 EFB STATUS value varies depending on network traffic
Loss of communication
The ACS550 behavior, if communication is lost, was configured earlier in section
Communication fault on page 196. The parameters are 3018 COMM FAULT FUNC and
3019 COMM FAULT TIME. Section Complete parameter descriptions on page 98
describes these parameters in detail.
No master station on line
If no master station is on line: Neither the EFB OK MESSAGES nor the errors (5307 EFB
CRC ERRORS and 5308 EFB UART ERRORS) increase on any of the stations.
To correct:
Check that a network master is connected and properly programmed on the
network.
Verify that the cable is connected and that it is not cut or short circuited.
Duplicate stations
If two or more stations have duplicate numbers:
Two or more drives cannot be addressed.
Every time there is a read or write to one particular station, the value for 5307 EFB
CRCERRORSO~~~~~EFBUARTERRORS~~V~~~C~S.
To correct: Verify the station numbers of all stations. Change conflicting station
numbers.
Swapped wires
If the communication wires are swapped (terminal A on one drive is connected to
terminal B on another):
The value of 5306 EFB OK MESSAGES does not advance.
The values of 5307 EFB CRC ERRORS and 5308 EFB UART ERRORS are advancing.
To correct: Check that the RS-485 lines are not swapped
Embedded fieldbus
ACS550 User's Manual
Embedded fieldbus
ACS550 U s e i s Manual
Overview
The ModbusB protocol was introduced by Modicon, Inc. for use in control
environments featuring Modicon programmable controllers. Due to its ease of use
and implementation, this common PLC language was quickly adopted as a de-facto
standard for integration of a wide variety of master controllers and slave devices.
Modbus is a serial, asynchronous protocol. Transactions are half-duplex, featuring a
single Master controlling one or more Slaves. While RS232 can be used for point-to-
point communication between a single Master and a single Slave, a more common
implementation features a multi-drop RS485 network with a single Master controlling
multiple Slaves. The ACS550 features RS485 for its Modbus physical interface.
RTU
The Modbus specification defines two distinct transmission modes: ASCII and RTU.
The ACS550 supports RTU only.
Feature summary
The following Modbus function codes are supported by the ACS550
Function I Code (Hex) I Description
Read Coil Status 0x01 Read discrete output status. For the ACS550, the individual bits
of the control word are mapped to Coils 1... 16. Relay outputs are
mapped sequentially beginning with Coil 33 (e.g ROI=Coil 33).
Read Discrete Input 0x02 Read discrete inputs status. For the ACS550, the individual bits
Status of the status word are mapped to Inputs 1...16 or 1...32.
depending on the active profile. Terminal inputs are mapped
sequentially beginning with lnput 33 (e.g. DIl=lnput 33).
Read Multiple 0x03 Read multiple holding registers. For the ACS550, the entire
Holding Registers parameter set is mapped as holding registers, as well as
command, status and reference values.
Read Multiple Input 0x04 Read multiple input registers. For the ACS550, the 2 analog input
Registers channels are mapped as input registers 1 & 2.
Force Single Coil 0x05 Write a single discrete output. For the ACS550, the individual bits
of the control word are maoDed to Coils 1...16. Relav outouts are
mapped sequentially beginning with Coil 33 (e.g. ~ 0 1 = d o i33).
l
Write Single 0x06 Write single holding register. For the ACS550, the entire
Holding Register parameter set is mapped as holding registers, as well as
command, status and reference values.
Diagnostics 0x08 Perform Modbus diagnostics. Subcodes for Query (0x00).
Restart (0x01) & Listen Only (0x04) are supported.
Force Multiple Coils OxOF Write multiple discrete outputs. For the ACS550, the individual
bits of the control word are mapped to Coils I...
16. Relay outputs
are mapped sequentially beginning with Coil 33 (e.g. ROI=Coil
33).
Write Multiple 0x10 Write multiple holding registers. For the ACS550, the entire
Holding Registers parameter set is mapped as holding registers, as well as
command, status and reference values.
ReadlWrite Multiple 0x17 This function combines functions 0x03 and 0x10 into a single
Holding Registers command.
Embedded fieldbus
ACS550 User's Manual
Mapping summaty
The following table summarizes the mapping between the ACS550 (parameters and
110) and Modbus reference space. For details, see Modbus addressing below.
ACS550 Modbus reference Supported function codes
- Control Bits
Relay Outputs
Coils(0xxxx)
-
01 - Read Coil Status
05 - Force Single Coil
15 Force Multiple Coils
-
. Status Bits . 02 -Read Input Status
- Discrete Inputs
Discrete Inputs(1xxxx)
Communication profiles
When communicating by Modbus, the ACS550 supports multiple profiles for control
and status information. Parameter 5305 EFB CTRL PROFILE selects the profile used.
A08 DRV LIM - The primary (and default) profile is the ABB DRV LIM profile. This
implementation of the ABB Drives profile standardizes the control interface with
ACS400 drives. The ABB Drives profile is based on the PROFIBUS interface. It is
discussed in detail in the following sections.
D c u PROFILE - The D c u PROFILE profile extends the control and status interface to
32 bits. It is the internal interface between the main drive application and the
embedded fieldbus environment.
ABB DRV FULL - ABB DRV FULL is the implementation of the ABB Drives profile that
standardizes the control interface with ACSGOO and ACS800 drives. This
implementation supports two control word bits not supported by the ABB DRV LIM
implementation.
Modbus addressing
With Modbus, each function code implies access to a specific Modbus reference set.
Thus, the leading digit is not included in the address field of a Modbus message.
Refer again to the Mapping summary above. The following sections describe, in
detail, the mapping to each Modbus reference set.
Oxxxx Mapping - Modbus coils. The drive maps the following information to the
Oxxxx Modbus set called Modbus Coils:
bit-wise map of the CONTROL WORD (selected using parameter 5305 EFB CTRL
PROFILE). The first 32 coils are reserved for this purpose.
Embedded fieldbus
ACS550 Users Manual
Embedded fieldbus
ACS550 User's Manual
The ACS550 supports the following Modbus function codes for coils:
I Function code I Description I
01 Read coil status
05 I Force single coil
15 (OXOF Hex) I Force rnulti~lecoils
I x x x x Mapping - Modbus discrete inputs. The drive maps the following
information to the l x x x x Modbus set called Modbus Discrete Inputs:
bit-wise map of the STATUS WORD (selected using parameter 5305 EFB CTRL
PROFILE). The first 32 inputs are reserved for this purpose.
Embedded fieldbus
ACS550 User's Manual 205
Embedded fieldbus
ACS550 Usefs Manual
The following table summarizes the 4xxxx drive control registers 40001 ...40099 (for
4xxxx registers above 40099, see the drive parameter list, e.g. 40102 is parameter
0102):
Modbus register Access Remarks
40001 CONTROL WORD RM, Maps directly to the profile's CONTROL WORD.Supported only
if 5305 = 0 or 2 (ABB Drives profile). Parameter 5319 holds
a copy in hex format.
40002 Reference 1 RM, Range = 0...+20000 (scaled to 0...1105 REFIMAX),or
-20000...0 (scaled to 1105 REFI MAX...^).
40003 Reference 2 RIW Range = 0...+10000 (scaled to O...1108 REF^ MAX).or
40004 i
..................................
slnTLi nonn
iI I
-'f0000...0 (scaled to 1108 REF2 MA,...O).
-
Maps o rect y to tne prof .e s STATUS .vonrj Supported on y 11
5305 = 0 or 2 (ABB Dr.bes pr0l.e) Parameter 5320 nods a
1 I CODY in hex format. I
~ ...
By O e f a t~ Stores a Copy O f 0103 OLTPJT FREO. Use
(select uslng 5310) parameter 5310 to se ect a d~fferenlact-a \ a LE for th s
I I l register. I
40006 Actual 2
(select "s ng 5311,
40007 Actual 3
lR I R
By defa~lt,stores a c?p{ of 0104 CJI~RENT Use parameter
5311 to select a alfierent act.~alva uc for this rcglster
By default, stores nothing. Use parameter 5312 to select an
(select using 5312) actual value for this register.
40008 Actual 4 R By default, stores nothing. Use parameter 5313 to select an
(select using 5313) actual value for this register.
40009 Actual 5 R By default, stores nothing. Use parameter 5314 to select an
(select using 5314) actual value for this register.
40010 Actual 6 R By default, stores nothing. Use parameter 5325 lo select an
(select using 5315) actual value for this register.
40011 Actual 7 R By default. stores nothing. Use parameter 5316 to select an
(select using 5316) actual value for this register.
40012 Actual 8 R By default, stores nothing. Use parameter 5317 to select an
(select using 5317) actual value for this register.
40031 ACS550 CONTROL RM, Maps directly to the Least Significant Word of the DCU
WORD LSW profile's CONTROL WORD. Supported only if 5305 = 1
See parameter 0301
40032 ACS550 CONTROL R Maps directly to the Most Significant Word of the DCU
WORD MSW profile's CONTROL WORD. Supported only if 5305 = 1.
See parameter 0302.
40033 ACS550 STATUS R Maps directly to the Least Significant Word of the DCU
WORD LSW profile's STATUS WORD. Supported only if 5305 = 1
See parameter 0303.
40034 ACS550 STATUS R Maps directly to the Most Significant Word of the DCU
WORD MSW profile's STATUS WORD. Supported Only if5305 = I.
See parameter 0304.
Embedded fieldbus
ACS550 User's Manual 207
For the Modbus protocol, drive parameters in Group 53: EFB PROTOCOL report the
parameter mapping to 4xxxx Registers.
Code Description
5310 EFB PAR 10
Specifies the parameter mapped to Modbus register 40005.
5311 EFB PAR 11
Specifies the parameter mapped to Modbus register 40006.
5312 EFB PAR 12
Specifies the parameter mapped to Modbus register 40007.
5313 EFB PAR 13
Soecifies the Darameter maDDed to Modbus reaister 40008.
5314 EFB PAR 14
Specifies the parameter mapped to Modbus register 40009.
5315 EFB PAR 15
Specifies the parameter mapped to Modbus register 40010.
5316 1 EFB PAR 16
Specifies the parameter mapped to Modbus register 40011
5317 EFB PAR 17
Specifies the parameter mapped to Modbus register 40012.
5318 EFB PAR 18
Sets additional delay in milliseconds before the ACS550 begins
transmitting response to the master request.
5319 EFB PAR 19
Holds a copy (in hex) of the CONTROL WORD, Modbus register 40001.
5320 EFB PAR 20
Holds a copy (in hex) o i the STATUS WoRo. Modbus register 40004.
Except where restricted by the drive, all parameters are available for both reading
and writing. The parameter writes are verified for the correct value and for a valid
register addresses.
Note: Parameter writes through standard Modbus are always volatile i.e. modified
values are not automatically stored to permanent memory. Use parameter 1607
PARAM SAVE to save all altered values.
The ACS550 supports the following Modbus function codes for 4xxxx registers:
Function code Description
03 Read holding 4mxx registers
06 Preset sinale
" 4xxxx reaister
I
16 (0x10 Hex) ) Preset multiple 4xmx registers
123 (0x17 Hex) I Readlwrite 4xxxx registers
Embedded fieldbus
ACS550 User's Manual
Actual values
The contents of the register addresses 40005 ... 40012 are ACTUAL VALUES and are:
- specified using parameters 5310 ... 5317
Read-only values containing information on the operation of the drive
16-bit words containing a sign bit and a 15-bit integer
when negative values, written as the two's complement of the corresponding
positive value
scaled as described earlier in section Actual value scaling on page 197.
Exception codes
Exception codes are serial communication responses from the drive. The ACS550
supports the standard Modbus exception codes defined below.
Exception
Name Meaning
code
I I
01 I ILLEGAL FUNCTION I Unsuooorted
,. Command
ILLEGAL DATA ADDRESS Thedata address received in the quely is not allowable. It is not
a defined parameterlproup.
A value contained in the query data field is not an allowable
value for the ACS550, because it is one of the following:
. Outside min. or max, limits.
. Parameter is read-only.
Message is too long.
. Parameter write not allowed when start is active.
- Parameter write not allowed when factow macro is selected.
Embedded fieldbus
ACS550 User's Manual
Overview
ABB Drives profile
The ABB Drives profile provides a standard profile that can be used on multiple
protocols, including Modbus and the protocols available on the FBA module. Two
implementations of the ABB Drives profile are available:
ABB DRV FULL - This
implementation standardizes the control interface with
ACSGOO and ACS800 drives.
ABB DRV LIM - Thisimplementation standardizes the control interface with
ACS400 drives. This implementation does not support two control word bits
SU~~O~~~~~~ABBDRVFULL.
Except as noted, the following "ABB Drives Profile" descriptions apply to both
implementations.
DCU profile
The DCU profile extends the control and status interface to 32 bits. It is the internal
interface between the main drive application and the embedded fieldbus
environment.
Control Word
The CONTROL WORD is the principal means for controlling the drive from a fieldbus
system. The fieldbus master station sends the CONTROL WORD to the drive. The drive
switches between states according to the bit-coded instructions in the CONTROL
WORD. Using the CONTROL WORD requires that:
Embedded fieldbus
ACS550 User's Manual
A BB D r i v e s profile
The following table and the state diagram later in this sub-section d e s c r i b e the
CONTROL WORD c o n t e n t for the ABB Drives profile.
I ABB Drives ~ r o f i l e
CONTROL WORD (See . .
parameter 53191
Commanded
Bit Name Value Comments
state
-Enter
READY TO OPERATE READY TO OPERATE
CONTROL - - . .-
EMERGENCY OFF Dr~veramps to stop accord rig to c.rrently
acllve decelerat~onramp ~.(2203 or 22051
Normal command sequence:
Enter OFFI ACTIVE
Proceed to READY TO SWITCH ON, unless
other interlocks (OFF2, OFF^) are active.
OPERATING Continue operation (OFF2 inactive)
CONTROL
EMERGENCY OFF Drive coasts to stop.
Normal command sequence:
Enter OFF2 ACTIVE
Proceed to SWITCHON INHIBITED
1 OPERATING Continue operation (OFF3 inactive)
0 EMERGENCY STOP Drive stops within time specified by parameter
2208.
Normal command sequence:
enable slana
-. ... .-.
Enrer OPEPA~IOII 'NAULED (Note the Rur~
- - - must oe a c t ~ ~See
e 1601 if
1601 is set to COMM, this bit also actives the
Run Enable signal.)
0 OPERATION Inhibit operation. Enter OPERATION INHIBITED
INHIBITED
Embedded fieldbus
ACS550 Usei-s Manual 211
Comments
DCU Profile
The following tables describe the CONTROL WORD content for the DCU profile.
Embedded fieldbus
ACS550 User's Manual
I 31
I
I
OFF-INTERLOCK
I
0
1
I
Start inhibit request
is OFF
Panel OFF button
I
For the control panel (or PC tool) this is
oressed the OFF button interlock.
Status Word
The contents of the STATUS WORD is status information, sent by t h e drive to the
master station.
Embedded fieldbus
ACS550 Useis Manual
A BB Drives profile
The following table and the state diagram later in this sub-section describe the
STATUS WORD content for the ABB Drives profile.
Embeddedfieldbus
ACS550 User's Manual
DCU profile
The following tables describe the STATUS WORD content for the DCU profile.
I
0 Drive has not reached zero speed.
5 1 ACCELERATE /1 I Drive is accelerating.
0 Drive is not accelerating.
6 DECELERATE 1 Drive is decelerating.
0 Drive is not decelerating.
7 AT-SETPOINT 1 Drive is at setpoint.
Embedded fieldbus
ACS550 User's Manual 215
17 I REQ-MAINT
- / 1 II A maintenance reauest is pendina.
-
1 1
I I
0 I1 No maintenance reauest is uendino. d
I I
0 II Drive is in scalar control mode.
21 ...25 1 Reserved
o (no OP)
1 Reference 1 requested in this channel.
0 Reference 1 is not requested in this channel.
1 Reference 2 requested in this channel.
0
1
0
I Reference 2 s not req-es~ean t h s channel
Externa, PID reference 2 requested n tnts cnanrte
External PID reference 2 is not requested in this channel.
1 A start inhibit from this channel is granted.
0 A staii inhibit from this channel is not granted.
31 I ACK-OFF-ILCK
~- - 1I II Start inhibit due to OFF button
I I 0 I Normal oueration
Embedded fieldbus
ACS550 Useis Manual
State diagram
ABB Drives profile
To illustrate the operation of the state diagram, the following example (ABBDRV LIM
implementation of the ABB Drives profile) uses the control word to start the drive:
First, the requirements for using the CONTROL WORD must be met. See above.
When the power is first connected, the state of the drive is not ready to switch on.
See dotted lined path (-) in the state diagram below.
Use the CONTROL WORD to step through the state machine states until the
OPERATING state is reached, meaning that the drive is running and follows the
given reference. See the table below.
Embedded fieldbus
ACS550 User's Manual 217
The state diagram below describes the start-stop function of CONTROL WORD (CVV)
and STATUS WORD (SW) bits for the ABB Drives profile.
From any state From any state From any state
Emergency Off
OFF2 (CW Bitl=O)
(SW Bit3=1)
(SW Bit4=0)
ACTIVE
(CW Bit7=1)'*
Ih I L=
From any state
9',7 P / NOT Y D Y
TO SWITCH ON
b(w Bito=o)
(CW Bit3=0) P+ a
+
,. (CW xxxx xlxx xxxx x110)
OPERATION
(SW BitZ=O)
INHIBITED SWITCH ON
C D 1 ENABLED
OpERAT'ON b ( S W Bit2=1)
-
I
.. State change
Path described in example
CW = CONTROL WORD
(CW Bit6=0)
xlxx xx11' 1111
Embedded fieldbus
ACS550 Useis Manual
Reference scaling
ABB Drives and DCU profiles
The following table describes REFERENCE scaling for the ABB Drives and DCU
profiles.
ABB Drives and DCU profiles
When parameter 1103 REFI SELECT or 1106 REF^ SELECT is set to COMM+AI~or
COMM*AI~,the reference is scaled as follows:
REF1 COMM+AII COMM (%) +(At (%) - 0.5. REF1 MAX (%))
Fieldbus reference
correction coefficient
(100 + 0.5 . (par. 1Io5)%
- - - - - - - - - -.
Embedded fieldbus
ACS550 User's Manual 219
Reference Value
setting Al reference scaling
REF1 COMM*All COMM (%) . (A1 (%) / 0.5. REF1 MAX (%))
Fieldbus reference
correction coefficient
I
I
I I A l l input signal
(100- 0.5. (par. 1105))%
0% 50% lob%
REF2 COMM+All COMM (%) + (A1 (%) - 0.5 - REF2 MAX (%))
I/
Fieldbus reference
correction coefficient
(100 + 0.5 - (Par. 1108)% - - - - - ,- - - - -
----- - -.
'-
- - - - - - - - - -.
I
I
I
I
I
O%osb 50%
I
10'0% ,
Allinput signal
Embedded fieldbus
__
220 ACS550 Usets Manual
Reference handling
Use Group 10: START/STOP/DIR parameters to configure for control of rotation
direction for each control location (EXTI
and EXT2). The following diagrams illustrate
how group 10 parameters and the sign of the fieldbus reference interact to produce
REFERENCE values (REFI and REF^). Note, fieldbus references are bipolar, that is
they can be positive or negative.
ABB Drives profile
Parameter Value setting Al reference scaling
1003 DIRECTION 1 (FORWARD)
Fieldbus I I I I
reference -163% -loo%
100% 163%
-(Max. ref.) .- - - - - - - - - .
1003 DIRECTION 2 (REVERSE)
ax, ref .- - - - - - - - - -
Resultant ret
-(Max. ref.) --
1003 DIRECTION 3 (REQUEST)
Resultant ref.
Embedded fieldbus
ACS550 User's Manual
Fieldbus adapter
Overview
The ACS550 can be set up to accept control from an external system using standard
serial communication protocols. When using serial communication, the ACS550 can
either:
receive all of its control information from the fieldbus, 01
Fieldbus
Fieldbus adapter
ACS550 User3 Manual
Control interface
In general, the basic control interface between the fieldbus system and the drive
consists of.
Output Words:
- CONTROL WORD
- REFERENCE (speed Or frequency)
- Others: The drive supports a maximum of 15 output words. Protocols limits
may further restrict the total.
Input Words:
- STATUS WORD
- Actual Value (speed or frequency)
- Others: The drive supports a maximum of 15 input words. Protocols limits may
further restrict the total.
Note: The words "output" and "input" are used as seen from the fieldbus controller
point of view. For example an output describes data flow from the fieldbus controller
to the drive and appears as an input from the drive point of view.
The meanings of the controller interface words are not restricted by the ACS550.
However, the profile used may set particular meanings.
Fieldbus controller
I Fieldbus
Process I10
(cyclic)
L
Control Word (CW)
References
Control Word
The CONTROL WORD is the principal means for controlling the drive from a fieldbus
system. The fieldbus controller sends the CONTROL WORD to the drive. The drive
switches between states according to the bit-coded instructions in the CONTROL
WORD. Using the CONTROL WORD requires that:
Fieldbus adapter
ACS550 Useis Manual
Actual Values
Actual Values are 16-bit words containing information on selected operations of the
drive. Drive Actual Values (for example, Group 10: SJARJ/STOP/DIR parameters)
can be mapped to Input Words using Group 51: EXT COMM MODULE parameters
(protocol-dependent, but typically parameters 5104 ... 5126).
Planning
Network planning should address the following questions:
What types and quantities of devices must be connected to the network?
What control information must be sent down to the drives?
What feedback information must be sent from the drives to the controlling
system?
Fieldbus adapter
224 ACS550 Useis Manual
WARNING! Connections should be made only while the drive is disconnected from
the power source.
Overview
The FBA (fieldbus adapter) is a plug-in module that fits in the drive's expansion slot
2. The module is held in place with plastic retaining clips and two screws. The
screws also ground the shield for the module cable and connect the module GND
signals to the drive control board.
On installation of the module, electrical connection to the drive is automatically
established through the 34-pin connector.
Mounting procedure
1
Note: Install the input power and motor cables first.
2
1. Insert the module carefully into the drive expansion slot 2
until the retaining clips lock the module into position.
2. Fasten the two screws (included) to the stand-offs.
~~
Fieldbus adaptel
ACS550 User's Manual
Fieldbus adapter
ACS550 Useis Manual
Note: Multiple references are supported only when using the ABB Drives profile.
Scaling
Where required, REFERENCES can be scaled. See the following sections, as
appropriate:
Reference scaling on page 236 (ABB Drives profile technical data)
Reference scaling on page 240 (Generic profile technical data).
System control
Using the fieldbus for miscellaneous drive control requires:
drive parameter values set as defined below
fieldbus controller command(s) in the appropriate location. (The location is
defined by the Protocol Reference, which is protocol dependent.)
Fieldbus adapter
ACS550 User's Manual
/ I I
1:z 1
Drive parameter value Description
I I
RELAY OUTPUT 1 35 (COMM) I Relay output Icontrolled by fieldbus I
RELAY OUTPUT 2 I
36 (CoMM(-l)) Relay Output 2 controlled by fieldbus. It
1403 / RELAY OUTPUT 3 Relay Output 3 controlled by fieldbus.
Relay Output 4 controlled by fieldbus. /
Relay Output 5 controlled by fieldbus.
Relay O u t ~ u6t controlled bv fieldbus, 1
' More than 3 relays requires the addition of a relay extension module.
Note: Relay status feedback occurs without configuration as defined below.
I Drive parameter I
I
value
I
I
Description I
I
Protocol
reference I
1501 A01 CONTENT SEL 135 (COMM VALUE 1) Analog Output 1 controlled by -
writing to parameter 0135.
0135 1 COMM VALUE 1 I
-
I I
1502 AOI
CONTENT MIN Set appropriate Used for scaling -
... ... values.
1505 MAXIMUM A 0 1
Fieldbus adapter
ACS550 Usefs Manual
Communication fault
When using fieldbus control, specify the drive's action if serial communication is lost.
Drive parameter Value Description
3018 COMM FAULT FUNC 0 (NOT SEL) Set for appropriate drive
1 (FAULT) response.
2 (CONST SP7)
3 (LAST SPEED)
3019 COMM FAULT TIME Set time delay before acting on a communication loss.
Scaling
To scale the drive parameter values see the following sections, as appropriate:
Actual Value scaling on page 239 (ABB Drives profile technical data)
Actual Value scaling on page 241 (Generic profile technical data).
Fieldbus adapter
ACS550 User's Manual
Diagnostics - FBA
Fault handling
The ACS550 provides fault information as follows:
The control panel display shows a fault code and text. See chapter Diagnostics
on page 243 for a complete description.
Parameters 0401 LAST FAULT, 0412 PREV~OUSFAULTI
and 0413 PREVIOUS FAULT:!
store the most recent faults.
For fieldbus access, the drive reports faults as a hexadecimal value, assigned
and coded according to the DRIVECOM specification. See the table below. Not all
profiles support requesting fault codes using this specification. For profiles that
support this specification, the profile documentation defines the proper fault
request process.
Fieldbus fault code
Drive fault code (DRIVECOM
specification)
1 / OVERCURRENT I2310h
2 DC OVERVOLT 3210h
3 DEVOVERTEMP 4210h
4 SHORT ClRC 2340h
5 Reserved FF6Bh
6 I DC UNDERVOLT 13220h
7 A l l LOSS 8110h
-
8 A12 LOSS 8110h
9 MOT OVERTEMP 4310h
I I
10 PANEL LOSS 5300h
I1 I ID RUN FAIL
I
I FF84h
I
12 1I MOTOR STALL 17121h
I
14 EXT FAULT 1 9000h
15 1 EXT FAULT 2 1 9001h
16 EARTH FAULT 2330h
17 Obsolete FF6Ah
18 THERM FAIL 5210h
I I
19 1I OPEX LINK /t 7500h
20 OPEX PWR 5414h
21 1 CURRMEAS 12211h
22 SUPPLY PHASE 3130h
23 1 ENCODER ERR
I
1 7301h
24 1I OVERSPEED (7310h
I
25 Reserved FF80h
26 1 DRIVE 10 / 5400h
Fieldbus adapter
ACS550 Useis Manual
I I
103 SERF MACRO FF55h
104 / Reserved / FF55h
105 Reserved FF55h
201 DSP T I OVERLOAD 6100h
202 DSP T2 OVERLOAD 6100h
203 DSP T3 OVERLOAD 6100h
204 DSP STACK ERROR 6100h
205 Reserved (obsolete) 5000h
206 CB ID ERROR 5000h
207 EFB LOAD ERR 6100h
1000 PAR HZRPM 6320h
-
1001 PAR PFC REF NEG 6320h
I I
1002 Reserved (obsolete) 6320h
1003 1 PAR A1 SCALE 16320h
,
1004 1I PAR A 0 SCALE 16320h
I
1005 1I PAR PCU 2
~~ - l6370h
1006 1 PAR EXT RO 16320h
I
1007 /I PAR FIELDBUS MISSING 16320h
I
1008 PAR PFC MODE 6320h
1009 1 PAR PCU 1 16320h
1012 PARPFCIOI 6320h
1013 PAR PFC 10 2 6320h
1014 PAR PFC 10 3 6320h
I I
1016 PARUSERLOADC 6320h
ACS550 Usefs Manual 23 1
Fieldbus adapter
ACS5.50 User's Manual
The ABB Drives profile provides a standard profile that c a n b e used on multiple
protocols, including protocols available on t h e FBA module. This section describes
t h e A B B Drives profile implemented for FBA modules.
Control Word
As described earlier in section Control interface on p a g e 222, t h e CONTROL WORD is
t h e principal means for controlling the drive from a fieldbus system.
Fieldbus adapter
ACS550 User's Manual 233
Status Word
As described earlier in section Control interface on page 222, the contents of the
STATUS WORD is status information, sent by the drive to the master station. The
following table and the state diagram later in this sub-section describe the status
word content.
I . . STATUS WORD
ABB Drives Drofile IFBA) I
Bit Name / 1 Description
ValUe (Correspond to stateslboxes in the state diagram)
READY TO SWITCH ON
0 OFF1 ACTIVE
I I I
2 I RDY-REF II OPERATION ENABLED
I ITRIPPED
OL.1
o
FAULT
I NO fault
Fieldbus adapter
ACS550 User's Manual
Fieldbus adapter
ACS550 User's Manual 235
The state diagram below describes the start-stop function of CONTROL WORD (CVV)
and STATUS WORD (SW) bits.
From any state From any state From any state
Emergency Stop
OFF2 (CW Bitl=O)
(SW Bitl=O)
(CW BitO=O)
A B C D
TO SWITCH ON
(swB~~~=o)----/
OPERATION
I I SWITCH ON b ( S W BitO=l)
B C D
OPERATE
(CW Bit4=0) it3=1 and
it12=1)
(CW Bit6=O)
KEY (CW=xxxx x l x x x x l l 1111)
0 State
I. State change RFG: ACCELERATOR
C W = CONTROL WORD
SW = STATUS WORD
RFG = Ramp Function Generator (CW=XXxxxlxx x l l l 1111)
I = Param. 0104 CURRENT
f = Param. 0103 OUTPUT FREQ
n = Soeed
Fieldbus adapter
ACS550 User's Manual
Reference
As described earlier in section Confrolinterface on page 222, the REFERENCE word is
a speed or frequency reference.
Reference scaling
The following table describes REFERENCE scaling for the ABB Drives profile.
ABB Drives Profile (FBA)
Reference
Reference Range Scaling Remarks
type
REF1 -32767... Speed or -20000 =-(par. 1105) Final reference limited by
+32767 frequency 0=0 110411105. Actual motor
+20000 = (par. 1105) speed limited by 200112002
(20000 corresponds to 100%) (Speed) or 200712008
(frequency).
REF2 -32767.. Speed or -10000 =-(par. 1108) Final reference limited by
+32767 frequency 0 =0 110711108. Actual motor
+I0000 = (par. 1108) speed limited by 200112002
(10000 corresponds to 100%) (Weed) Or 2007/2008
(frequency).
Torque -10000 =-(par. 1108) Final reference limited by
0=0 2015/2017 (torquel) or
+I0000 = (par. 1108) 2016/2018 (torque2).
(10000 corresponds to 100%)
PI0 -10000 = -(par. 1108) Final reference limited by
Reference 0 =0 4012/4013 (PID setl) or
110000 = (par. 1108) 411214113 (PID set2).
(10000 corresponds to 100%)
When parameter 1103 REFI SELECT or 1106 REF^ SELECT is set to COMM+AI? or
COMM*AI~,the reference is scaled as follows:
%.----, -- - J
50%
I
100%
,
A l l input signal
Fieldbus adapter
ACS550 Useis Manual 23 7
100% -- -- ---J
I
/
(100 - 0.5 . (par. 1108)%
0% 50% 100%
,
A l l input signal
REF2 COMMfAll COMM (%) - (Al (%) 10.5 - REF2 MAX (%))
Fieldbus reierence
correction coefficient
0%
I , A l l input signal
0% 50% 100%
Fieldbus adapter
ACS550 Usefs Manual
Reference handling
Use Group 10: START/STOP/DIR parameters to configure for control of rotation
direction for each control location (EXTIand EXT2). The following diagrams illustrate
how group 10 parameters and the sign of the fieldbus reference interact to produce
REFERENCE values (REFIand REF^). Note, fieldbus references are bipolar, that is
they can be positive or negative.
I ABB Drives ~rofile I
Parameter Value setting A l reference scaling
1003 DlRECnoN 1 (FORWARD) Resultant ref.
Max. ref - - -
Fieldbus
100% 163%
-(Max. ref.) .- - - - - - - - - .
reference
-(Max, ref.) - -
1003 DIRECTION 3 (REQUEST) Resultant ref.
Fieldbus adapter
ACS550 User's Manual 239
Actual Value
As described earlier in section Control interface on page 222, Actual Values are
words containing drive values.
Actual Value scaling
The scaling of the integers sent to the fieldbus as Actual Values depends on the
resolution of the selected drive parameter. Except as noted for ACTI and ACT^ below,
scale the feedback integer using the resolution listed for the parameter in section
Complete parameter list on page 85. For example:
Feedback integer Parameter resolution Scaled Value
1 10.1 mA I 1 . O . l mA=O.lmA
Fieldbus adapter
ACS550 User's Manual
Overview
The generic profile aims to fulfill the industry-standard drive profile for each protocol
(e.g. PROFIdrive for PROFIBUS, AClDC Drive for DeviceNet).
Control Word
As described earlier in section Control interface on page 222, the CONTROL WORD is
the principal means for controlling the drive from a fieldbus system. For specific
CONTROL WORD content, see the user's manual provided with the FBA module.
Status Word
As described earlier in section Control interface on page 222, the contents of the
STATUS WORD is status information, sent by the drive to the master station. For
specific STATUS WORD content, see the user's manual provided with the FBA module.
Reference
As described earlier in section Control interface on page 222, the REFERENCE word is
a speed or frequency reference.
Reference scaling
REFERENCE scaling is fieldbus type specific. However, at the drive, the meaning of a
100% REFERENCE value is fixed as described in the table below. For a detailed
description on the range and scaling of the REFERENCE, see the user's manual
supplied with the FBA module.
Generic profile
Reference
Reference Range Scaling Remarks
type
REF Fieldbus Speed -100% =-(par. 9908) Final reference limited by
specific O=O 1104/1105.
+ I 0 0 = (par. 9908) Actual motor speed limited by 20011
2002 (soeed).
,. ,
I
Frequency -100% = -(par. 9907) Final reference limited by
o=o 110411105.
+I00 = (par. 9907) Actual motor speed limited by 20071
2008 (frequency).
Actual Values
As described earlier in section Control interface on page 222, Actual Values are
words containing drive values.
Fieldbus adapter
ACS550 User's Manual
/ Feedback
inte~er
I Parameter resolution / (Feedback integer). (Parameter resolution) =
Scaled Value
Fieldbus adapter
ACS550 User's Manual
Fieldbus adapter
ACS550 Usets Manual
Diagnostics
WARNING! All electrical installation and maintenance work described in this chapter
should only be undertaken by qualified service personnel. The safety instructions in
chapter Safety on page 5 must be followed.
Diagnostic displays
The drive detects error situations and reports them using:
the green and red LED on the body of the drive
the status LED on the control panel (if an Assistant Control Panel is attached to
the drive)
the control panel display (if a control panel is attached to the drive)
the Fault Word and Alarm Word parameter bits (parameters 0305 to 0309). See
Group 03: FB ACTUAL SIGNALS on page 104 for the bit definitions.
The form of the display depends on the severity of the error. You can specify the
severity for many errors by directing the drive to:
ignore the error situation
- report the situation as an alarm
report the situation as a fault.
Red - Faults
The drive signals that it has detected a severe error, or fault, by:
enabling the red LED on the drive (LED is either steady on or blinking)
showing the steady red status LED on the control panel (if attached to the drive)
setting an appropriate bit in a Fault Word parameter (0305 to 0307)
overriding the control panel display with the display
of a fault code in the Fault mode (figures on the
FAULT 8
right)
A 1 1 LO55
stopping the motor (if it was on).
The fault code on the control panel display is
temporary. Pressing any of the following keys removes
the fault message: MENU, ENTER, UP, or DOWN key.
ACS550 Useis Manual
The message reappears after a few seconds if the control panel is not touched and
the fault is still active.
1 o o : o o 1
I
display afler a few seconds. The message returns
periodically as long as the alarm condition exists.
I Correcting faults
The recommended corrective action for faults is.
Use the table in section Fault listing below to find and address the root cause of
the problem.
Reset the drive. See section Fault resetting on page 249.
Fault listing
The following table lists the faults by code number and describes each. The fault
name is the long form shown in the Fault mode of the Assistant Control Panel when
the fault occurs. The fault names shown (for Assistant Control Panel only) in the
Fault Logger mode (see page 55) and the fault names for parameter 0401 LAST
FAULT may be shorter.
Fault Fault name in
Description and recommended corrective action
code panel
1 OVERCURRENT Output current is excessive. Check for and correct:
. Excessive motor load.
insufficient acceleration time (parameters 2202 ACCELER TIME 1 and
2205 ACCELER TIME 2).
Faulty motor, motor cables or connections.
Diagnostics
ACS550 User's Manual 245
I
OC UNDERVOLT Intermediate circuit DC voltage is not sufficient. Check for and correct:
- Missing phase in the input power supply.
- Blown fuse.
- Undervoltage on mains.
7 AII
LOSS FAULT LIMIT (3021).
Analog input 1 loss. Analog input value is less than AII
Check for and correct:
Source and connection for analog input.
Parameter settings for AII FAULT LIMIT (3021) and 3001 AI<MIN FUNCTION.
8 ~ 1 LOSS
2 Analog input 2 loss. Analog input value is less than A12 FAULT LIMIT (3022).
Check for and correct:
Source and connection for analog input.
Parameter settings for A12 FAULT LIMIT (3022) and 3001 A I ~ M I NFUNCTION.
9 MOT OVERTEMP Motor is too hot, based on either the drive's estimate or on temperature
feedback.
. Check for overloaded motor.
. Adjust the parameters used for the estimate (3005...3009).
Check the temperature sensors and Group 35: MOTOR TEMP MEAS
parameters.
PANEL LOSS Panel communication is lost and either:
Drive is in local control mode (the control panel displays LOC), or
. Drive is in remote control mode (REM) and is parameterizedto accept
start/stop, direction or reference from the control panel.
To correct check:
- Communication lines and connections.
Parameter 3002 PANEL COMM ERR.
. Parameters in Group 10: START/STOP/DIR and Group 11:
REFERENCE SELECT (if drive operation is REM).
Diagnostics
ACS550 User's Manual
11 ID RUN FAIL The Motor ID Run was not completed successfully. Check for and correct:
- Motor connections.
Motor parameters 9905 ...9909.
12 MOTOR STALL Motor or process stall. Motor is operating in the stall region. Check for and
correct:
- Excessive load.
Insufficient motor power.
Parameters 3010 ...3012.
RESERVED Not used.
EXT FAULT 1 Digital input defined to report first external fault is active. See parameter
3003 EXTERNAL FAULT 1.
M T FAULT 2 Digital input defined to report second external fault is active. See parameter
3004 EXTERNAL FAULT 2.
- ........ .. -. ..... -..
EARTH FAULT Poss ble g r o ~ r ~
f ad~ loetected
t in the motor or motor cab es Tne ar:\e
mon.tors for gro..nd fa^ ts whlle tne d r ~ r eIS rbnnlrlq ana nhile the arive is
not runnina. Detection is more sensitive when the drive is not runnina and
can produce false positives.
Possible corrections:
Check forlcorrect faults in the input wiring.
Verify that motor cable does not exceed maximum specified length.
A delta grounded input power supply and motor cables with high
capacitance may result in erroneous error reports durina non-runnino
tests. To disabliresponse to fault monitoring' when the :rive is not
running, use parameter 3023 WRING FAULT. TO disable response to all
-
ground fault monitorinq, use parameter 3017 EARTH FAULT:
1 17 /
/ /' _
OBSOLETE
TI-ERI.I FA .
Not used.
.._ .. .- ..- ....- -.
Internal fau,t The thcrm~storineas-rng the interr~altemperature of the
I
1 l9 I OPEX L'Nd
Interna fa- t A commun~catlon-reated proolem has oeen detected on tne
f ber optic irik oetween the contro and OlNT boards Contact your oca
ABB representative.
Internal fault. Low voltage condition detected on OlNT power supply.
Contact your local ABB representative.
CURR MEAS Internal fault. Current measurement is out of range. Contact your local ABB
representative.
SUPPLY PHASE Ripple voltage in the DC link is too high. Check for and correct:
Missing mains phase.
Blown fuse.
ENCODERERR The drive is not detecting a valid encoder signal. Check for and correct:
Encoder presence and proper connection (reverse wired, loose
connection or short circuit).
Voltage logic levels are outside of the specified range.
A working and properly connected Pulse Encoder Interface Module,
OTAC-01
Wrong value entered in parameter 5001 PULSE NR. A wrong value will
only be detected if the error is such that the calculated slip is greater
than 4 times the rated slip of the motor.
Encoder is not being used, but parameter 5002 ENCODER ENABLE =
1 (ENABLE).
Diagnostics
ACS550 User's Manual 24 7
28 SERIAL 1 ERR Fieldbus communication has timed out. Check for and correct:
Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME).
Communication settings (Group 51: EXTCOMM MODULEor Group 53:
EFB PROTOCOL as appropriate).
Poor connections and/or noise on line.
29 EFB CON FILE Error in reading the configuration file for the embedded fieldbus.
-
30 FORCE TRIP Fault trio forced bv the fieldbus. See the fieldbus User's Manual.
-
...... ...- .
Fault code reservea for !lie e~noedaedr e d b ~ s(EFB) protoco appl cat~on
Tne meanlng IS protoco. dependent
EFB 2
Fault in the motor circuit. One of the motor phases is lost. Check for and
correct:
. Motor fault.
. Motor cable fault.
Thermal relay fault (if used)
lnternal fault.
OUTP WIRING Posslole poher uYlrlfig error delected h n e n the ar ve IS not runn~ngI
monltors for an improper connect on between the dr ve npdt power anu me
drive output. Check for and correct:
Proper input wiring - line voltage is NOT connected to drive output.
The fault can be erroneously declared if the input power is a delta
grounded system and motor cable capacitance is large. This fault can be
disabled using parameter 3023 WRING FAULT.
INCOMPATIBLE The drive cannot use the soitware.
SW lnternal fault.
The loaded software is not compatible with the drive.
Call support representative.
CBOVERTEMP Drive control board is overheated. The fault trip limit is 88 "C. Check for and
correct:
. Excessive ambient temperature.
. Fan failure.
Obstructions in the air flow.
Not for drives with an OM10 control board.
Diagnostics
ACS550 User's Manual
SYSTEM ERROR Error internal to the drive. Contact your locai ABB representativeand report
the error number.
201 ... SYSTEM ERROR Error in the system. Contact your local A B B representative and report the
299 error number.
UNKNOWN Wrong type of panel, ie. panel that supports drive X but not the A C S 5 5 0 ,
DRIVE ~ Y P E : has been connected to the A C S 5 5 0 .
ACS550
SUPPORTED
DRIVES' X
Faults that indicate conflicts in the parameter settings are listed below.
-
Fault
code
1000
panel
Fault
name in
PAR HZRPM
I Description and recommended corrective action
1
II .Parameter values for power control are inconsistent: Improper mot01
nomlnai kVA or motor nominal power. Check for the following:
1 .I<
- ( 9 9 0 6 MOTOR NOM CURR - 9905 MOTOR NOM VOLT. 1.73 / PN)5 3.0
where Ph = 1 0 0 0 9909 M O T U hot4 ~ POWER ( f ~n ts are kVV)
or Ph = 7 4 6 9 9 0 9 E.IOTOR r.o:n P O ~ L R( f untts are hp e g in IJS)
1006 PAR EXT RO Parameter values are inconsistent. Check for the following:
Extension relay module not connected and
1410...1412 RELAY OUTPUTS 4...6 have non-zero values.
1007 PAR FIELDBUS Parameter values are inconsistent. Check for and correct:
MISSING A parameter is set for fieidbus control (e.g 1001 EXTICOMMANDS = 10
(COMM)), but 9802 COMM PROT SEL = 0.
I I
1008 PAR PFC MODE Parameter values are inconsistent - 9 9 0 4 MOTOR CTRL MODE must be = 3
(SCALAR:FREQ), when 8123 PFC ENABLE is activated.
Diagnostics
ACS550 Useis Manual 249
1 I0O9 I Parameter values for power control are inconsistent: Improper motor
nom~nalfrequency or speed. Check for both of the following:
1 5 (60.9907 MOTOR NOM FREO / 9908 MOTOR NOM SPEED 5 16
0.8 5 9908 MOTOR NOM SPEED /
(120 - 9907 MOTOR NOM FREO / Motor Poles) 50.992
RESERVED Not used.
I I
PAR PFC 101
I/ 10 cnnrguration IS not complea - not eiiouyn relays ate parameterized to
PFC Or, a conflict exists oetwden tiro.,p 1.1 RELAY OUlPUTS paranteter
8117 NR OF AUX MOT and Parameter 8118 AUTOCHNG INTERV, I
I I PAR PFC 10 2 10 cnnfg~ration1s not corllp.ele - In.? actc.al nunlter ol PFC motors
(parameter 8127. IAOTOUS) does not malcr. lne PFC nlulors in G r w p :4
H E W Y OU TPdTS arid parameler 0118 A~TOCHEIG 1~1Crw
I I loin
PAR PFC 103
RESERVED
10 configuration is not complete - the drive is unable to allocate a digital
input (interlock) for each PFC motor (parameters 8120 INTERLOCKS and
8127 MOTORS).
Not used.
PAR USER LOAD C Parameter values for the user load curve are inconsistent. Check that the
following conditions are met:
- 3704LOADFREO 153707 L O A D F R E O ~ ~ ~ ~ ~ L O A D F R E O ~ ~
3713LOAOFREO453716LOADFREO5.
- 3705LOADTOR4LOW1~37~6LOADTOROHlGH1.
3708 LOAD TOR4 LOW 2 5 3709 LOAD TORO HlGH 2.
3711 LOAD TORO LOW353712 LOAD TORQ HlGH 3.
3714 LOADTORO LOW4 53715 LOAD TOR4 HlGH4.
- 3717 LOAD TORO L O W 5 53718 LOAD TORO HlGH 5.
Fault resetting
The ACS550 can be configured to automatically reset certain faults. Refer to
parameter Group 31: AUTOMATIC RESET.
~~~~~~ - ~ -
A WARNING! If an external source for start command is selected and it is active, the
ACS550 may start immediately after fault reset.
- digital input
serial communication.
When the fault has been corrected, the motor can be started
History
For reference, the last three fault codes are stored into parameters 0401, 0412,
0413. For the most recent fault (identified by parameter 0401), the drive stores
additional data (in parameters 0402 ... 0411) to aid in troubleshooting a problem. For
example, parameter 0404 stores the motor speed at the time of the fault.
The Assistant Control Panel provides additional information about the fault history.
See section Fault Logger mode on page 55 for more information.
To clear the fault history (all of the Group 04: FAULT HISTORY parameters):
1. Using the control panel in the Parameters mode, select parameter 0401
2. Press EDIT (or ENTER on the Basic Control Panel)
3. Press UP and DOWN at the same time.
4. Press SAVE.
Correcting alarms
The recommended corrective action for alarms is:
- Determine if the alarm requires any corrective action (action is not always
required).
Use the table in section Alarm listing below to find and address the root cause of
the problem.
Alarm listing
The following table lists the alarms by code number and describes each
Alarm
Display Description
code
2001 OVERCURRENT Current limiting controller is active. Check for and correct:
. Excessive motor load.
Insufficientacceleration time (parameters 2202 ACCELER TIME 1 and
2205 ACCELER TlME 2).
- Faulty motor, motor cables or connections.
2002 OVERVOLTAGE Overvoltage controller is active. Check for and correct:
- Static or transient overvoltages in the input power supply.
Insufficientdeceleration time (parameters 2203 DECELER TIME 1 and
2206 DECELER TlME 2).
2003 UNDERVOLTAGE Undervoltage controller is active. Check for and correct:
Undervoltage on mains.
Diagnostics
ACS550 User's Manual 25 1
Alarm Description
Display
code
2004 OIR LOCK The change in direction being attempted is not allowed. Either:
Do not attempt to change the direction of motor rotation, or
Change parameter 1003 DIRECTION to allow direction change (if
reverse operation is safe).
2005 10 COMM Fieldbus communication has timed out. Check for and correct:
Fault Setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME).
Communication settings (Group 51: EXT COMM MODULE or
Group 53: EFB PROTOCOL as appropriate).
Poor connections and/or noise on line.
2006 A l l LOSS Analog input 1 is lost, or value is less than the minimum setting.
Check:
- lnput source and connections.
- Parameter that sets the minimum (3021).
Pardrneler lhal szls ina a armifaUlropnratlon (3001)
2007 A12 LOSS Analog i n p ~2l is osl or value? 1s ICSS1ha11!he inililmum setllllg
Check:
- lnput source and connections.
Parameter that sets the minimum (3022).
Parameter that sets the alarmlfault operation (3001).
2008 PANEL LOSS Panel communication is lost and either:
Drive is in local control mode (the control panel displays LOC), or
Drive is in remote control mode (REM) and is parameterizedto
accept startistop, direction or reference from the control panel.
To correct check:
- Communication lines and connections.
Parameter 3002 PANEL COMM ERR.
Parameters in Group 10: START/STOP/DlR and Group i f :
REFERENCE SELECT (if drive operation is REM).
2009 DEVICE Drive heatsink is hot. This alarm warns that a DEVICE OVERTEMP
fault
OVERTEMP may be near.
R1... R4 & R71RB: 100°C (212 "F)
R5iR6: 110 "C (230 "F)
Che& for and correct:
Fan failure.
Obstructions in the air now.
Dirt or dust coating on the heat sink.
- Excessive ambient temperature.
. Excessive motor load.
Diagnostics
ACS550 User's Manual
Alarm
code
1 Display
I Description
2013 AUTORESET This alarm warns that the drive is about to perform an automatic fault
(Note 1) reset, which may start the motor.
To control automatic reset, use Group 31: AUTOMATIC RESET.
2014 AUTOCHANGE - function is active.
This alarm warns that the PFC autochanqe
(Note 1) . To control PFC, use Group 81: PFC CONTROL and the PFC macro
on page 78.
PFC I LOCK This alarm warns that the PFC interlocks are active. which means that
the drive cannot start the following:
Any motor (when Autochange is used).
- The speed regulated motor (when Autochange is not used).
20161 RESERVED Not used
2017
2018 PI0 SLEEP This alarm warns that the PID sleep function is active, which means
(Note 1) that the motor could accelerate when the PID s l e e ~
function ends.
'To co~~troi
PI[) sleep \.se parameters 4022 . 4026 or 4122 4126
-. - -. . .. . ..- .- . . .-....-- . .. -
ID RUN Perlofroiny ln Run
RESERVED Not used.
START ENABLE 1 This alarm warns that the Start Enable 1 signal is missing.
MISSING To control Start Enable 1 function, use parameter 1608.
To correct, check:
Digital input configuration.
. Communication settings.
START ENABLE 2 This alarm warns that the Start Enable 2 signal is missing.
MISSING To control Start Enable 2 function, use parameter 1609.
To correct, check:
Digital input configuration.
Communication settings.
EMERGENCY Emergency stop activated.
STOP
ENCODERERROR The drive is not detecting a valid encoder signal. Check for and
correct
Encoder presence and proper connection (reverse wired, loose
connection.or short circuit).
Voltage logic levels are outside of the specified range.
A working and properly connected Pulse Encoder Interface Module.
OTAC-01
-
Wrong value entered in parameter 5001 PU-SE NR A wrong value
w I1 on y oe detecteo 11the error is sucli that the calc~latc?d
slip is
greatefthan 4 times the rated slip of the motor.
Encoder is not being used, but parameter 5002 ENCODER ENABLE =
1 (ENABLE).
FIRST START Slgnals tnat a the dr VP IS perlorniing a F ~ r sSran
l e~aluat011of motor
character st cs This IS nornial the Irst time tlie motor 1s run after motor
parameters are entered or changed. See parameter 9910 ID RUN for a
description of motor models.
RESERVED Not used
Diagnostics
ACS550 User's Manual 253
Alarm Description
Display
code
2027 USER LOAD This alarm warns that the condition defined by parameter 3701 USER
CURVE LOAD c MODE has been valid longer than half of the time defined by
3703 USER LOAD C TIME.
2028 START DELAY Shown durina the Start delav. See parameter 21 13 START DELAY.
Note 1. Even wncn the relay o u t p ~ is care a arm connitions ( e g. paranleter
t configbred to i ~ r d
I401 IUAY ours~r1 = 5 (A-ARL~)or 16 (F.1IA.ARI.I)) rhs alann s not tn3:cared oy a relay
output
Diagnostics
ACS550 User's Manual
I Code II Description I
5050 1I Parameter unload was aborted.
5051 ( File error was detected.
5052 Parameter upload attempt has failed.
5060 1 Parameter download was aborted. ~p
Diagnostics
ACS550 User's Manual
Maintenance
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Maintenance Interval instruction
Heatsink temperature check Depends on the dustiness of the See Heatsink on page 255.
and cleaning environment (every 6 . . 12
months)
Main cooling fan replacement Every six years See Main fan replacement on
page 256.
Internal enclosure cooling fan Every three years. See lnlernal enclosure fan
replacement replacement on 257.
(IPS4 iUL type 12 drives)
Capacitor reforming Every year when stored See Reforming on page 258.
Capacitor replacement Every nine to ten years See Replacement on page 258.
(frame sizes R5 and R6)
Replace battery in the Assistant Every ten years See Bafleryon page 258.
Control Panel
Heatsink
The heatsink fins accumulate dust from the cooling air. Since a dusty heatsink is less
efficient at cooling the drive, overtemperature faults become more likely. In a
"normal" environment (not dusty, not clean) check the heatsink annually, in a dusty
environment check more often.
Clean the heatsink as follows (when necessary):
1. Remove power from drive.
2. Remove the cooling fan (see section Main fan replacement on page 256).
3. Blow clean compressed air (not humid) from bottom to top and simultaneously use a
vacuum cleaner at the air outlet to trap the dust.
Note: If there is a risk of the dust entering adjoining equipment, perform the cleaning
in another room.
Maintenance
ACS550 User's Manual
Maintenance
ACS550 Usefs Manual
Maintenance
ACS550 User's Manual
Capacitors
Reforming
The drive DC link capacitors need to be reformed (re-aged) if the drive has been
non-operational for more than one year. W~thoutreforming, capacitors may be
damaged when the drive starts to operate. It is therefore recommended to reform the
capacitors once a year. See section Serial number on page 13 for how to check the
date of manufacture from the serial number shown on the drive labels.
For information on reforming the capacitors, refer to Guide for Capacitor Reforming
in ACS50/150/350/550 [3AFE68735190 (English)], available on the Internet (go to
www.abb.com and enter the code in the Search field).
Replacement
The drive intermediate circuit employs several electrolytic capacitors. Their life span
is from 35 000 ... 90 000 hours depending on drive loading and ambient temperature.
Capacitor life can be prolonged by lowering the ambient temperature.
It is not possible to predict a capacitor failure. Capacitor failure is usually followed by
a input power fuse failure or a fault trip. Contact ABB if capacitor failure is suspected.
Replacements for frame size R5 and R6 are available from ABB. Do not use other
than ABB specified spare parts.
Control panel
I
Cleaning
Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could
scratch the display window.
Battery
A battery is only used in Assistant Control Panels that have the clock function
available and enabled. The battery keeps the clock operating in memory during
power interruptions.
The expected life for the battery is greater than ten years. To remove the battery, use
a coin to rotate the battery holder on the back of the control panel. Replace the
battery with type CR2032.
Note: The battery is NOT required for any control panel or drive function, except the
clock.
Maintenance
ACS550 Usefs Manual 259
Technical data
Ratings
By type code, the table below provides ratings for the ACS550 adjustable speed AC
drive, including:
- IEC ratings
NEMA ratings (shaded columns)
frame size.
Technical data
ACS550 User's Manual
Technical data
ACS550 User3 Manual
Symbols
Typical ratings:
Normal use (10% overload capability)
. N continuous rms current. 10% overload is allowed for one minute in ten minutes
I-.~
PN typical motor power in normal use. The kilowatt power ratings apply to most IEC. Cpole
motors. The horsepower ratinqs apply
. . to most 4-pole NEMA motors.
Heavy-duty use (50% overload capability)
/2hd continuous rms current. 50% overload is allowed for one minute in ten minutes.
phd typical motor power in heavy duty use. The kilowatt power ratings apply to most IEC. 4-pole
motors. The horsepower ratings apply to most 4-pole NEMA motors.
Sizing
The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current. Also note that:
the ratings apply for ambient temperature of 40 "C (104 "F)
the maximum allowed motor shaft power is limited to 1.5 . Phd.If the limit is
exceeded, motor torque and current are automatically restricted. The function
protects the input bridge of the drive against overload.
Technical data
ACS550 User's Manual
Derating
The load capacity (current and power) decreases for certain situations, as defined
below. In such situations, where full motor power is required, oversize the drive so
that the derated value provides sufficient capacity.
For example, if your application requires 15.4 A of motor current and a 8 kHz
switching frequency, calculate the appropriate drive size requirement as follows:
The minimum size required = 15.4 A 10.80 = 19.25 A
Where: 0.80 is the derating for 8 kHz switching frequency (see section Switching frequency derating
on page 262).
Referring to JZN in the ratings tables (starting from page 259), the following drives
exceed the IzN requirement of 19.25 A: ACS550-XI-023A-4, or ACS550-XI-024A-2.
Temperature derating
In the temperature range +40 "C ...50 "C (+I04 "F... 122 OF), the rated output current
is decreased 1% for every 1 "C (I .8 "F) above +40 "C (+I04 OF). Calculate the
output current by multiplying the current given in the rating table by the derating
factor.
Examale If the ambient temperature is 50 "C (+I22 "F), the derating factor is
100% - I0hI"C x 10 "C = 90% or 0.90.
The output current is then 0.90 x IZN
or 0.90 x lzhd.
Altitude derating
In altitudes 1000... 4000 m (3300... 13,200 ft) above sea level, the derating is 1% for
every 100 m (330 ft). If the installation site is higher than 2000 m (6600 ft) above sea
level, please contact your local ABB distributor or office for further information.
Technical data
ACS550 User's Manual
WARNING! Do not operate the drive outside the nominal input line voltage range.
Overvoltage can result in permanent damage to the drive.
Fuses
Branch circuit protection must be provided by the end user and sized per national
and local electric codes. The following tables provide fuse recommendations for
short circuit protection on the drive's input power.
Technical data
ACS550 User's Manual
00467918 XISB
Technical data
ACS550 User's Manual 265
00467918 XISB
Technical data
ACS550 Uset-s Manual
Size wiring according to local safety regulations, appropriate input voltage and the
drive's load current. In any case, the conductor must be less than the maximum limit
defined by the terminal size (see section Drive's powerconnection terminals on page
268).
The table below lists copper and aluminium cable types for different load currents.
These recommendations apply only for the conditions listed at the top of the table.
Ground connections
For personnel safety, proper operation and reduction of electromagnetic emissionl
pick-up, the drive and the motor must be grounded at the installation site.
Conductors must be adequately sized as required by safety regulations.
Power cable shields must be connected to the drive PE terminal in order to meet
safety regulations.
Technical data
ACS550 User's Manual 267
Power cable shields are suitable for use as equipment grounding conductors only
when the shield conductors are adequately sized as required by safety
regulations.
- In multiple drive installations, do not connect drive terminals in series.
Corner grounded TN systems
Corner grounded TN systems are defined in the following table. In such systems,
disconnect the internal ground connection by removing the screws (do this also if the
grounding configuration of the system is unknown):
ACS550-01, frame sizes R1 ...R4: Remove both the EM1 and EM3 screws (see
section Power connection diagrams on page 20).
ACS550-Ul, frame sizes R1... R4: Remove the EM1 screw -drive is shipped with
EM3 removed (see section Power connection diagrams on page 20).
Frame sizes R5 ... R6: Remove both the F1 and F2 screws (see section Power
connection diagrams, page 21).
Technical data
A CS.550 Usets Manual
I T systems
00467918.xls B
' Aluminium cable cannot be used with frame sizes R1 ... R5 because of its lower capacity.
Technical data
ACS550 Usefs Manual
WARNING! For R6 power terminals, if screw-on terminal lugs are supplied, they can
only be used for wire sizes that are 95 mm2 (310 AWG) or larger. Smaller wires will
loosen and may damage the drive. They require crimp-on ring lugs as described
below.
Technical data
ACS550 User's Manual
larger.
1. Attach the supplied screw-on lugs to the
drive end of the cables.
2. Attach screw-on lugs to the drive.
Technical data
ACS550 User's Manual
Motor connections
- -
A WARNING! Never connect line power to the drive output terminals: U2,V2 or W2.
Line voltage applied to the output can result in permanent damage to the drive. If
frequent bypassing is required, use mechanically interlocked switches or contactors.
A WARNING! Do not connect any motor with a nominal voltage less than one half of
the drive's nominal input voltage.
WARNING! Disconnect the drive before conducting any voltage tolerance (Hi-Pot)
test or insulation resistance (Megger) test on the motor or motor cables. Do not
conduct these tests on the drive.
Technical data
ACS550 User3 Manual
1 I
EMC limits Operational limits
Second environ ent First environmpnt
(category C37') (category C2 ) Basic unit With
' See the new terms in section IEC/EN 61800-3 (2004) Definitions on page 292.
12 kHz switching frequency is not available.
Not tested.
Sine filters further extend the cable lengths.
i WARNING! Using a motor cable longer than spec~fiedin the table above may cause
permanent damage to the drive
---- -. .. I Check EMC limits -> EMC requirements for Category C3 are met
with a 300 m (980 ft) cable.
..
R5 frame size.
8 kHz fsw,
Category C3.
t i t sR5 and 8 kHz -> for a 150 m (490 ft)
~ n e c k i ~ e r a t i o n a i i ~ mfor
cable the basic unit is sufficient.
150 (490 ft) cable Check EMC limits -> EMC requirements for Category C3 cannot be
met with a 300 m (980 ft) cable. The installation configuration is not
~ossible.An EMC olan is recommended to overcome the situation.
R6 frame size.
4 kHz fsw.
EMC limits not
EMC limits do not need to be checked as there are no EMC
1
applicable.
150 m (490 ft) cable
Technical data
ACS550 U s e f s Manual
R6 300 980 1
I
150' 1
I
4902
12 kHz switching frequency is not available.
WARNING! Using a motor cable longer than specified in the table above may cause
permanent damage to the drive.
Technical data
ACS550 Useis Manual
Grounding
See section Ground connections on page 266
For CE compliant installations and installations where EMC emissions must be
minimized, see section Effective motor cable screens on page 275.
Technical data
ACS550 User's Manual
! I
Recommended (CE & C-Tick) Allowed (CE & C-Tick)
Symmetrical shielded cable: three phase A separate PE conductor is required if the
conductors and a concentric or otherwise conductivity of the cable shield is < 50% of the
symmetrically constructed PE conductor, and a conductivity of the phase conductor.
Shield
I Not allowed for motor cables (CE & C-Tick) II
I A four-conductor system: three ~ h a s e
1 conductors and a protective conductor, without a
shield.
II @
'J
Allowed for motor cables with phase
conductor cross section up to 10 mm2.
,
Braided metallic screen '3L
Technical data
276 ACS550 User's Manual
Technical data
ACS550 User's Manual
Brake components
Availability
Braking availability for ACS550 drives, by frame size is:
R1 and R2 - a built-in brake chopper is standard equipment. Add appropriate
resistor, as determined using the following section. Resistors are available from
ABB.
- R3 ... R6 -does not include an internal brake chopper. Connect a chopper and a
resistor, or a brake unit to the DC link terminals on the drive. Contact your ABB
representative for appropriate parts.
Time
k-
OFF time
4 Li
I ON tim'
I Cvcle time I Duty cycle = -
- the peak braking power requirement
- type of braking (deceleration to zero vs. overhauling load) - During
deceleration to zero, the generated power steadily decreases, averaging half
of the peak power. For an overhauling load, the braking is countering an
external force (gravity for example) and the braking power is constant. The
total heat generated from an overhauling load is double the heat generated
from deceleration to zero speed (for the same peak torque and ON time).
Technical data
ACS550 User's Manual
Power*
Avg. braking power -
overhauling load - -
Avg. braking power - -
during deceleration
-
- -
--
-1- Decelerationcurve
- - -
Overhauling load
curve
Time
r
to zero I
I I I
Temperature
4 I I I
The many variables in the last requirement above are most easily dealt with using
the following tables.
First, determine your maximum braking time ON (ONMAx), minimum braking time
OFF (OFFMIN)and load type (deceleration or overhauling load).
Calculate duty cycle:
ONMAX
Duty cycle = 100%
(ONMAX OFFMINI
+
In the appropriate table, find the column that best matches your data:
- ONMAX5 column specification and
- Duty cycle 5 column specification
Find the row that matches your drive
The minimum power rating for deceleration to zero is the value in the selected
row/column.
For overhauling loads, double the rating in the selected rowlcolumn, or use the
"Continuous O N column.
208 ...240 V drives
Continuous ON
-
-012A-2 80 44 125 235 345 570 3000
-017A-2 48 44 210 390 575 950 4000
-024A-2 32 30 315 590 860 1425 5500
-031A-2 23 22 430 800 1175 1940 7500
' Resistor time constant specification must be 2 85 seconds.
Technical data
ACS550 User's Manual 279
380...480 V drives
. ... -
- -- .- --.. ...- -... --. .--
. ----.--- .--. ..-
: :1
i..i~-~ I Resista~ice
....
~ e s i s t o r 'minimum continuous power rating
..- .- ..... ... - -.. .
Deceleration-to-zero rating
...... - .. . .. .. . . .. . . .
Type code
Continuous ON
ACS550- >60sON
see below > 25% Duty
500...600 V drive
I
-09AO-6 149 80 342 643 943 1560 5359
-011A-6 110 60 467 877 1286 2127 7308
-017A-6 75 60 685 1286 1886 3119 10718
Resistor time constant specification must be, 85 seconds.
WARNING! Never use a brake resistor with a resistance below the minimum value
specified for the particular drive. The drive and the internal chopper are not able to
handle the overcurrent caused by the low resistance.
Symbols
RMIN- Minimum allowed resistance of the braking resistor.
RMAX- Maximum resistance allowed if maximum braking torque is necessary.
Technical data
ACS550 Usefs Manual
P,- Duty-cycle based resistor power rating in deceleration braking, where "x" is
ONMAxtime.
WARNING! The surface temperature of the resistor is very high, and air flowing from
the resistor is very hot. Materials near the brake resistor must be non-flammable.
Provide protection from accidental contact with the resistor.
To ensure that the input fuses protect the resistor cable, use resistor cables with the
same rating as used for the power input to the drive.
The maximum length of the resistor cable(s) is 10 m (33 ft). See section Power
connection diagrams on page 20 for the resistor cable connection points.
Parameter set-up
To enable dynamic braking, switch off the drive's o v e ~ o l t a g econtrol [Set parameter
2005 = 0 (DISABLE)].
Technical data
ACS550 User's Manual
Control c o n n e c t i o n s
Control connection specifications
Control connection specifications
Analog inputs and See section Control terminals table on page 22.
~- -, l-tr"- .l -l t- S
I
Digital input impedance 1.5 kohm. Maximum voltage for digital inputs is
Digital inputs 30 V.
Max. contact voltage: 30 V DC. 250 VAC
- Max. contact current Ipower: A. 30 V DC; 1500 VA, 250 V AC
6
Relays - Max. continuous current: 2 A rms (cos q = A rms (cos q = 0.4)
1). 1
(digital outputs) - Minimum load: 500 m W 10 mA)
(12 V.
. Contact material: Silver-nickel (AgN)
. Isolation between relay digital outputs, test voltage: 2.5 kV rms. 1 minute
Cable soecifications See section Control terminals table on page 22.
Control cables
General recommendations
Use multi-core cables with a braided copper wire screen, temperature rated at 60 " C
(140 "F) or above:
At the drive end, twist the screen together into a bundle not longer than five times its
width and connected to terminal XI-! (for digital and analog 110 cables) or to either
XI-28 or XI-32 (for RS485 cables). Leave the other end of the cable shield
unconnected.
Route control cables to minimize radiation to the cable:
- Route as far away as possible from the input power and motor cables [at least
20 cm (8 in)].
Where control cables must cross power cables, make sure they are at an angle
as near 90" as possible.
Stay at least 20 cm (8 in) from the sides of the drive
Use care in mixing signal types on the same cable:
Do not mix relay-controlled signals using more than 30 V and other control
signals in the same cable.
Run relay-controlled signals as twisted pairs (especially if voltage > 48 V). Relay-
controlled signals using less than 48 V can be run in the same cables as digital
input signals.
Technical data
ACS550 User's Manual
Analog cables
Recommendations for analog signal runs:
Use double shielded, twisted pair cable
Use one individually shielded pair for each signal.
Do not use a common return for different analog signals.
Digital cables
Recommendation for digital signal runs: A double shielded cable is the best
alternative, but single-shielded, twisted, multi-pair cable is also usable.
Efficiency
Approximately 98% at nominal power level
Technical data
ACS550 User's Manual 283
Cooling
I Cooling specifications
Method Internal fan. flow direction from bottom to top.
Free space above and below the ACS550 drive: 200 mm (8 in).
Requirement Free space is not required on the drive's sides - ACS550 drives can be mounted
side-bv-side.
~~~
Technical data
ACS550 User's Manual
Technical data
ACS550 User's Manual
Technical data
ACS550 User's Manual
Mounting dimensions
F W 1 1
See detail A
See detail B
Detail A Detail B
IP21 I UL type 1 and IPS4 I UL type 12 -Dimensions for each frame size I
Technical data
ACS550 Usefs Manual
Outside dimensions
Drives with IP21/ UL type I enclosures
Technical data
ACS550 User's Manual
C w 2 - 4
Weight
The following table lists typical maximum weights for each frame size. Variations
within each frame size (due to components associated with voltagelcurrent ratings
and options) are minor.
Weight
Enclosure R1 I R2 I R3 I R4 I R5 I R6
Technical data
ACS550 User's Manual
Degrees of protection
Available enclosures:
IP21 IUL type 1 enclosure. The site must be free of airborne dust, corrosive
gases or liquids, and conductive contaminants such as condensation, carbon
dust and metallic particles.
IP54 IUL type 12 enclosure. This enclosure provides protection from airborne
dust and light sprays or splashing water from all directions.
Compared to the IP21 1 UL type 1 enclosure, the IP54 IUL type 12 enclosure has:
the same internal plastic shell as the IP21 enclosure
a different outer plastic cover
- an additional internal fan to improve cooling
larger dimensions
the same rating (does not require a derating).
Ambient conditions
The following table lists the ACS550 environmental requirements.
Ambient environment requirements I
Installation site Storage and transportation in the
protective package
0...1000 m (0 ...3 300 A)
Altitude 1000...2000 m (3 300. . 6 600 ft) if
PNand IZNderated 1% every 100 m
above 1000 m (300 ft above 3 300 ft)
Min. -15 'C (5 "F) - no frost allowed 4 0 ...70 "C ( 4 0... 158 "F)
Max. (fsw = 1 or4) 40 "C (104 'F);
50 "C (122 "F) if
The following table lists the standard stress testing that the ACS550 passes.
1 Stress tests I
Without shipping package Inside shipping package
Mechanical conditions: In accordance in accordance with ISTA 1A and 1 6
Sinusoidal with IEC 60721-3-3, Class 3M4 specifications.
vibration 2...9 Hz3.0mm (0.12 in)
9...200 Hz 10 m/s2 (33 WS')
I
Not allowed In accordance with IEC 68-2-29:
Shock
max. 100 m/sZ(330 ftIs2). l l m s
Not allowed 76 cm (30 in), frame size R1
61cm (24 in), frame size R2
Free fall
- 46 cm (18 in), frame size R3
31 cm (12 in), frame size R4
25 cm (10 in), frame size R5
15 cm (6 in), frame size R6
Materials
Material specifications
PClABS 2.5 mm, color NCS 1502-Y or NCS 7000-N
Hot-dip zinc coated steel sheet 1.5...2 mm, thickness of coating 20
micrometers. If the surface is painted, the total thickness of the coating (zinc
Drive enclosure and paint) is 80... 100 micrometers.
Cast aluminium AlSi
Extruded aluminium AlSi
I
Corrugated board, expanded uolystvrene.
. . . plywood. raw wood (heat dried).
Package package wrap consisis of one or more of the following: ~ ~ - ~ ~ b l wrap.
a s t i PP
c
or steel bands.
The drive contains raw materials that should be recycled to preserve energy
and natural resources. The package materials are environmentally compatible
and recyclable. All metal parts can be recycled. The plastic parts can either be
recycled or burned under controlled circumstances, according to local
regulations. Most recyclable parts are marked with recycling marks.
I Disposal
I
If recychng is in01 leasble, al. parts excl~oingelectrolyuc capacitors and pr~nled
circut buaros can be laridlilled. The DC capac.tors conta:n electrolvte ano. ifthe
-
- ~
~~~
boards
~ - contain
~
lead, both df which will be classified as ha&rdous waste within the EU. They
- to local reaulations.
~
I
- I
Technical data
ACS550 Useis Manual
Applicable standards
Drive compliance with the following standards is identified by the standard "marks"
on the type code label.
Mark Applicable standards
a* C22.2 No. 14 CSA Standard for Industrial Control Equipment (for ACS550-U1
drives only)
CE marking
cc $ A C Emark is attached to the drive to verify that the drive follows the provisions of the
'European Low Voltage and EMC Directives (Directive 73123lEEC, as amended by
931681EEC, and Directive 8913361EEC, as amended by 931681EEC).
Note: The 600 V ACS550-U1 drives are not CE approved
C-Tick marking
The drive carries C-Tick marking.
C-Tick marking is required in Australia and New Zealand. A C-Tick mark is attached
to the drive to verify compliance with the relevant standard (IEC 61800-3 (2004) -
Technical data
ACS550 User's Manual
Adjustable speed electrical power drive systems - Part 3: EMC product standard
including specific test methods), mandated by the Trans-Tasman Electromagnetic
Compatibility Scheme.
The Trans-Tasman Electromagnetic Compatibility Scheme (EMCS) was introduced
by the Australian Communication Authority (ACA) and the Radio Spectrum
Management Group (RSM) of the New Zealand Ministry of Economic Development
(NZMED) in November 2001. The aim of the scheme is to protect the radio
frequency spectrum by introducing technical limits for emission from electrical1
electronic products.
ULlCSA m a r k i n g s
An UL mark is attached to ACS550 drives to verify that the drive follows the
of UL 508C.
LlSTEO
A CSA mark is attached to ACS550-U1 type drives to verify that the drive follows the
@* provisions of C22.2 NO. 14.
The ACS550 is suitable for use on a circuit capable of delivering not more than
100.000 RMS symmetrical amperes, 480 V maximum.
Branch circuit protection must be provided in accordance with local codes.
The ACS550 has an electronic motor protection feature that complies with the
requirements of UL 508C and, for ACS550-Ul, C22.2 No. 14. When this feature is
selected and properly adjusted, additional overload protection is not required unless
more than one motor is connected to the drive or unless additional protection is
required by applicable safety regulations. See parameters 3005 (MOT THERM PROT)
and 3006 (MOT THERM RATE).
The drives are to be used in a controlled environment. See section Ambient
conditions on page 289 for specific limits.
Note: For open type enclosures, i.e. drives without the conduit box and/or cover for
IP21 1 UL type 1 drives, or without the conduit plate andlor hood for IP54 I
UL type 12 drives, the drive must be mounted inside an enclosure in accordance
with National Electric Code and local electrical codes.
Brake choppers, when applied with appropriately sized brake resistors, will allow the
drive to dissipate regenerative energy (normally associated with quickly decelerating
a motor). Frame sizes R1 and R2 have a built-in brake chopper a s standard
equipment. For frame sizes R3...R6, contact your ABB representative for
appropriate parts. See section Brake components on page 277.
Technical data
ACS550 User's Manual
Likewise, the equipment must not disturb or interfere with any other product or
system within its locality.
First environment includes establishments connected to a low-voltage network which
supplies buildings used for domestic purposes.
Second environment includes establishments connected to a network not directly
supplying domestic premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be
installed and commissioned only by a professional when used in the first
environment.
Note: A professional is a person or organisation having necessary skills in installing
andlor commissioning power drive systems, including their EMC aspects.
Category C2 has the same EMC emission limits as the earlier class first environment
restricted distribufion. EMC standard IECIEN 61800-3 does not any more restrict the
distribution of the drive, but the using, installation and commissioning are defined.
Drive of category C3: drive of rated voltage less than 1000 V, intended for use in the
second environment and not intended for use in the first environment.
Category C3 has the same EMC emission limits as the earlier class second
environment unrestricted distribution.
Technical data
ACS550 Useis Manual
Note: It is not allowed to install a drive with the internal EMC filter connected on IT
(ungrounded) systems. The supply network becomes connected to ground potential
through the EMC filter capacitors, which may cause danger or damage the drive.
Note: It is not allowed to install a drive with the internal EMC filter connected to a
corner grounded TN system as this would damage the drive.
Liability limits
The manufacturer is not responsible for:
Any costs resulting from a failure if the installation, commissioning, repair,
alteration, or ambient conditions of the drive do not fulfil the requirements
specified in the documentation delivered with the unit and other relevant
documentation.
Units subjected to misuse, negligence or accident.
Units comprised of materials provided or designs stipulated by the purchaser.
In no event shall the manufacturer, its suppliers or subcontractors be liable for
special, indirect, incidental or consequential damages, losses or penalties.
This is the sole and exclusive warranty given by the manufacturer with respect to the
equipment and is in lieu of and excludes all other warranties, express or implied,
arising by operation of law or othenvise, including, but not limited to, any implied
warranties of merchantability or fitness for a particular purpose.
If you have any questions concerning your ABB drive, please contact the local
distributor or ABB office. The technical data, information and specifications are valid
at the time of printing. The manufacturer reserves the right to make modifications
without prior notice.
Technical data
ACS550 User's Manual
Technical data
ACS550 User's Manual
Technical data
ACS550 Usefs Manual
lndex
lndex
298 ACS550 User's Manual
Index
ACS550 User's Manual
.
airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
EFB comm . . . . . . . . . . . . . . . . . . . . . . . . . . 198
fan maintenance triggers. . . . . . . . . . . . . . 139 FBAcomm . . . . . . . . . . . . . . . . . . . . . . . . . . 229
heatloss . . . . . . . . . . . . . . . . . . . . . . . . . . . 283 digital cable requirements . . . . . . . . . . . . . . . . . . 282
space requirement . . . . . . . . . . . . . . . . . . . 283 digital input
copy mode (Basic Control Panel) . . . . . . . . . . . . 69 at fault. history parameters . . . . . . . . . . . . . . 106
corner grounded TN system . . . . . . . . . . . . . . . 267 connections . . . . . . . . . . . . . . . . . . . . . . . . . . 22
warning about filters . . . . . . . . . . . . . . . . . . . . 6 specifications . . . . . . . . . . . . . . . . . . . . . . . . . 23
warning about screws at EMI. EM3 . . . . . . . 20 status. data parameter . . . . . . . . . . . _ . 101
.
warning about screws at F1 F2 . . . . . . . . . . 21
correction source (PID). parameter . . . . . . . . . . 169
. output
diaital
connections . . . . . . . . . . . . . . . . . . . . . . . . . . 22
cover specifications . . . . . . . . . . . . . . . . . . . . . . . . 281
remove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 dimensions
replace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 drive. mounting . . . . . . . . . . .
cover. top. see hood drive. outside . . . . . . . . . . . .
CRC errors (count). parameter . . . . . . . . . . . . . 172 DIP switches . . . . . . . . . . . . . . . .
crimp-on ring lugs . . . . . . . . . . . . . . . . . . . . . . . 269 direction control. parameter . . . .
critical soeeds iavoidina) -.
parameter group . . . . . . . . . . . . . . . . . . . . . 136
direction of rotation
Assistant Control Panel . . . .
high. parameters . . . . . . . . . . . . . . . . . . . . . 136 Basic Control Panel . . . . . . .
low.. .oarameters . . . . . . . . . . . . . . . . . . . . . . 136 display format (PID). parameter .
select. parameter . . . . . . . . . . . . . . . . . . . . 136 disposal. . . . . . . . . . . . . . . . . . . .
C-Tick markina .. . . . . . . . . . . . . . . . . . . . . . . . . 291 download parameter sets
current application . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
at fault. history parameter . . . . . . . . . . . . . . 106 full set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
data parameter . . . . . . . . . . . . . . . . . . . . . . 100 usersets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
max. limit. parameter. . . . . . . . . . . . . . . . . . 125 drive
measurement. fault code. . . . . . . . . . . . . . . 246 EFB comm installation . . . . . . . . . . . . . . . . . 190
ratingcode . . . . . . . . . . . . . . . . . . . . . . . . . . 13 FBA module installation . . . . . . . . . . . . . . . . 224
id. fault code . . . . . . . . . . . . . . . . . . . . . . . . . 247
mountina . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
..
brake time . oarameter . . . . . . . . . . . . . . . . . 129
bus voltage: data parameter . . . . . . . . . . . . 100 rating. parameter . . . . . . . . . . . . . . . . . . . . . 146
current ref.. parameter . . . . . . . . . . . . . . . . 129 temperature. data parameter . . . . . . . . . . . . 100
rnaanetizina time . oarameter. . . . . . . . . . . . 128 weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
ov&oltag& fault bode . . . . . 245 drive on time. data parameters . . . . . . . . . . . . . . 102
.
dndervoltage fault code . . . . . . . . . . .
voltaae stabilizer.. ~arameter
.
245
E
. ............ 138
deceleraGon earth fault
parameter group . . . . . . . . . . . . . . . . . . . . . 131 fault code . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
at aux. start (PFC). parameter . . . . . . . . . . 186 parameter . : . . . . . . . . . . . . . . . . . . . . . . . . . 141
emergency time. parameter . . . . . . . . . . . . 132 earthing
ram~select . oarameter . . . . . . . . . . . . . . . . 131 see ground
ramb shape'. parameter. . . . . . . . . . . . . . . . 131
ramp time (PFC). parameter . . . . . . . . . . . . 186
.
rarno zero select.. barameter . . . . . . . . . . . .
time. parameter. . . . . . . . . . . . . . . . . . . . . .
132
131
default values
listing for macros . . . . . . . . . . . . . . . . . . . . . . 82
. for. parameters. . . . . . . . . . . . . . . . . . .
listinn 85
derating
adiustment example
altitude. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
single phase supply. . . . . . . . . . . . . . . . . . . 262
sw~tchina . freauencv
. ................... 262
temperature . . . . . . . . . . . . . . . . . . . . . . . . . 262
derivation time (PID). parameter . . . . . . . . . . . . 161
derivation time. parameter. . . . . . . . . . . . . . . . . 133
device overtemperature. fault code . . . . . . . . . . 245
Index
ACS550 Usefs Manual
current at. history parameter . . . . . . . . . . . . 106 config file revision. p$ameter . . . . . . . . . . . 171
digital input status at. history parameter . . . 106 fault function. parameter. . . . . . . . . . . . . . . . 142
FBA comm . . . . . . . . . . . . . . . . . . . . . . . . . 228 fault time . parameter . . . . . . . . . . . . 142
frequency at. history parameter . . . . . . . . . 106 fie dous appl program revlslon. parameter 17 1
history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250 fieldbds CPI firmware revlslon. parameter 17 1
last. historv . .parameter. . . . . . . . . . . . . . . . . 106 f~eldbusparameter refresh. uarameter 171
listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244 fieldbus barameters . . . . . . . . . . . . . . . . . . . . 171
logging (Assistant Control Panel) . . . . . . . . . 55 fieldbus status. parameter . . . . . . . . . . . . . . 171
mode (Assistant Control Panel) . . 43 243 244
mode (Basic Control Panel) . . . . . 63 . 243 . 244
. . fieldbus type. parameter . . . . . . . . . . _ . 171
protocol select. parameter . . . . . . . . . . . . . . 187
previo;s. history paramete; . . . . . . . . . . . . . . ' 106 relay output word. data parameter . . . . . . . . 101
reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249 status words. data parameters . . . . . . . . . . . 104
reset select. parameter . . . . . . . . . . . . . . . . 121 values. data parameter . . . . . . . . . . . . . . . . . 101
speed at. history parameter . . . . . . . . . . . . 106 feedback
status at. history parameter. . . . . . . . . . . . . 106 multiplier (PID). parameter . . . . . . . . . . . . . . 163
time of. history parameters . . . . . . . . . . . . . 106 on ABB manuals. . . . . . . . . . . . . . . . . . . . . . 309
torque at. history parameter . . . . . . . . . . . . 106 select (PID). parameter . . . . . . . . . . . . . . . . 163
voltage at. history parameter. . . . . . . . . . . . 106 field weakening point . . . . . . . . . . . . . . . . . . . . . 271
words. data parameters . . . . . . . . . . . . . . . 105
fault display
..- .,".,
fin~rlhllc
see EFB (embedded fieldbus)
alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . see EFB. drive parameters
fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . see FBA (fieldbus adapter)
fauknames . . . . . . . . . . . . . . . . . . . . . . see FBA. drive parameters
FB actual signals. parameter group. . . . . . . fieldbus adapter
FBA see FBA
protocol listing . . . . . . . . . . . . . . . . . . . . see FBA. drive parameters
FBA (fieldbus adapter). . . . . . . . . . . . . . . . . fieldbus. embedded
actual values . . . . . . . . . . . . . . . . . . . . . see EFB
analog output control. activate . . . . . . . see EFB. drive parameters
comm fault response. . . . . . . . . . . . . . . firmware
.
confiauration . . . . . . . . . . . . . . . . . . . . . panel. version . . . . . . . . . . . . .
control word . . . . . . . . . . . . . . . . . . . . . . version. parameter . . . . . . . . .
.
control word ABB drives . . . . . . . . . . . . first environment
.
diaanostics (C2). compliance with IECIEN 61800-3 . . . . 293
drive feedback . . . . . . . . . . . . . . . . . . . . (C2)..motor cable length . . . . . . . . . . . . . . . . 272
fieldbus control. activate . . . . . . . . . . . . definit~on. . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
input reference sel.. activate FlashDrop
installation . . . . . . . . . . . . . . . . . . . . . . . application macro. parameter . . . . . . . . . . . . . 98
PID control setpoint source. activate. . . connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
.
reference. . . . . . . . . . . . . . . . . . . . . . . .
parameter view. parameter . . . . . . . . . . . . . 124
floating network
relay output control. activate . . . . . . . . . see IT system
set-uu . : flux braking. parameter . . . . . . . . . . . . . . . . . . . . 137
startlitop /direction control. activate . . .
flux optimization. parameter . . . . . . . . . . . . . . . . 137
state diaaram
. . . ABB drives . . . . . . . . . . .
status word . . . . . . . . . . . . . . . . . . . . . . force trip. fault code . . . . . . . . . . . . . . . . . . . . . . 247
status word. ABB drives . . . . . . . . . . . . frame errors (count). parameter . . . . . . . . . . . . . 172
frame size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
free fall. stress testing . . . . . . . . . . . . . . . . . . . . . 290
frequency
at fault. history parameter. . . . . . . . . . . . . . . 106
max. limit. parameter . . . . . . . . . . . . . . . . . . 126
min. limit. parameter . . . . . . . . . . . . . . . . . . . 126
motor. resolution . . . . . . . . . . . . . . . . . . . . . . 271
moJor. specification . . . . . . . . . . . . . . . . . . . 271
sw~tching.parameter . . . . . . . . . . . . . . . . . . 138
Index
302 ACS550 User's Manual
M
macros checking insulation . . . . . . . . . . . . . . .
3-wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 compatibility . . . . . . . . . . . . . . . . . . . .
id run. parameter . . . . . . .
ABB standard (default) . . . . . . . . . . . . . . . . . 72 loao c u v e break point frequency . . .
alternate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
hand-auto . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 load curve max.. fault parameter . . .
motor potentiometer . . . . . . . . . . . . . . . . . . . 75 load culve zero speedload . . . . . . . .
PFC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 maintenance triggers . . . . . . . . . . . . .
PID control . . . . . . . . . . . . . . . . . . . . . . . . . . 77 nominal current. parameter . . . . . . . .
torque control . . . . . . . . . . . . . . . . . . . . . . . . 79 nominal freauencv . ~arameter. . . . . .
user parameter sets . . . . . . . . . . . . . . . . . . . 81 nominal power. perameter . . . .
narameter default values . . . . . . . . . . . . . . . . 82 nominal speed. parameter . . . . .
parameters not changed . . . . . . . . . . . . . . . . 71 nominal voltage . . .. narameter . . . . .
phase. fault code . . . . . . . . . . . . . . . .
maanetization. identification . . . . . . . . . . . . . . . . 99 requirements . . . . . . . . . . . . . . . . . . .
main menu stall. fault code . . . . . . . . . . . . . . . . . .
Ass!stant Control Panel . . . . . . . . . . . . . . . . . 44 thermal nrotection . . . . . . . . . . . . . . . .
Baslc Control Panel. . . . . . . . . . . . . . . . . . . . 63 motor cable
mains
see input power
checking .insulation . . . . . . . . . . . . . . . . . . . . . 24
length
mainteoance 400Vdrives . . . . . . . . . . . . . . . . . . . . . . 272
capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . 258 600Vdrives . . . . . . . . . . . . . . . . . . . . . . 273
control panel . . . . . . . . . . . . . . . . . . . . . . . . 258
heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . 255 max. length . . . . . . . . . . . . . . . . . . . . . . . . . . 271
requjrements . . . . . . . . . . . . . . . . . . . . . . . . 274
internal enclosure fan . . . . . . . . . . . . . . . . .
intervals . . . . . . . . . . . . . .
257
.
requirements EMC . . . . . . . . . . . . . . . . . 274
motor connection
main fan . . . . . . . . . . . . .
triggers. parameter group lugs for R6 . . . . . . . . . . . . . . . . . . . . . . . . . . 269
manuals termlnal size . . . . . . . . . . . . . . . . . . . . . . . . . 268
list of ACS550 manuals . torque . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
providing feedback . . . . . motor control
mapping parameter group . . . . . . . . . . . . . . . . . . . . . . 137
actual value. FBA. generic profile . . . . . . . . 241 control mode. parameter . . . . . . . . . . . . . . . . 98
EFBmodbus . . . . . . . . . . . . . . . . . . . . . . . . IR compensation. parameters . . . . . . . . . . . 137
202
motor potentiometer macro . . . . . . . . . . . . . . . . . . 15
-.
materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
maximum motor temperature '
freqdency. parameter . . . . . . 126 measure. parameter group . . . . . . . . . . . . . . 150
torque limit. parameters . . . . . . . . . 127 alarm limit. parameter . . . . . . . . . . . . . . . . . . 151
torque select. paranierer . . . . . . . . . . 126 data parameter . . . . . . . . . . . . . . . . . . . . . . . 102
mechanical fault limit. parameter . . . . . . . . . . . . . . . . . . . 151
angle. data parameter . . . . . . . . . . . . . . . . . 102 overtemperature. fault code . . . . . . . . . . . . . 245
revolutions. data parameter . . . . . . . . . . . . 102 sensorselection. parameter . . . . . . . . . . . . .
minimum . . . naraineter
sensor tvne . ................ .
.
.
N
NEMA ratings
see ratings
noise
random sw. freq . parameter
Index
ACS550 User's Manual
NPN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 parity
(RS.232). parameter . . . . . . . . . . . . . . . . . . 172
0 errors (count). . .parameter . . . . . . . . . . . . . . . 172
patents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
offset (PID). parameter . . . . . . . . . . . . . . . . . . . 168
PE earth
ok messages (count). parameter. . . . . . . . . . . . 172 earth fault. parameter. . . . . . . . . . . . . . . . . . 141
operating data. parameter group . . . . . . . . . . . . 100
PE earth connection
operation terminal size . . . . . . . . . . . . . . . . . . . . . . . . . 268
Assistant Control Panel . . . . . . . . . . . . . . . . 43 torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
Basic Control Panel . . . . . . . . . . . . . . . . . . . 63 PELV (Protective Extra Low Voltage) . . . . . . . . . . 23
OPEX link. fault code . . . . . . . . . . . . . . . . . . . . 246
PFC
OPEX oower. fault code . . . . . . . . . . . . . . . . . . 246 control. parameter group . . . . . 175
options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 acceleration !.me. parameler . . . . . . . 186
parameter group . . . . . . . . . . . . . . . . . . . . . 187 aux start order. parameter . . . . . . . . . . . . . . 186
code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 aux . motor start delay. parameter . . . . . . . . 177
output aux . motor stop delay. parameter . . . . . . . . 177
frequency. data parameter . . . . . . . . . . . . . 100 deceleration time. parameter . . . . . . . . . . . . 186
voltage. data parameter . . . . . . . . . . . . . . . 100 enable. parameter . . . . . . . . . . . . . . . . . . . . 185
wirinq. fault code . . . . . . . . . . . . . . . . . . . . . 247 low frequency. parameters . . . . . . . . . . . . . . 177
output mode macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Assistant Control Panel . . . . . . . . . . . . . . . . 47 number of aux. motors. ~arameter . . . . . . . . 178
Basic Control Panel . . . . . . . . . . . . . . . . . . . 65 number of motors pararneler . . 1 8 6
overcurrent reference step. parameters . . 175
automatic reset. parameter. . . . . . . . . . . . . 143 start delav . ~aramerer . . . . 185
faultcode . . . . . . . . . . . . . . . . . . . . . . . . . . 244 start freqjehcy. parameters . . . . . . . . . . . . . 176
overload curve
see user load curve
oversoeed. fault code . . . . . . . . . . . . . . . . . . . . 247
overvb~ta~e
control enable. parameter
) P
panel communication. parameter group . . . . . . 172
panel display variables. parameter group . . . . . 147
panel firmware version . . . . . . . . . . . . . . . . . 41. 45
panel loss. fault code . . . . . . . . . . . . . . . . . . . . . 245
parameter
analog input scale. fault code . . . . . . . . . . . 248
analog output scale. fault code . . . . . . . . . . 248
chanaelock
Y
......................... 121
descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . 98
external relay output. fault code . . . . . . . . . 248
fieldbus. fault code . . . . . . . . . . . . . . . . . . . 248
hz rpm.fault code . . . . . . . . . . .
list~nq(ranges. resolutions. defaults)
D "'P U-I(oower
8
, control unit). fault code
PCU 2 bower control unit\; fault code
PFC 10. fault code . . . . . . . . . . . . . . .
PFC mode. fault code
PFC ref. k g . , fault code . . . .
savechanges . . . . . . . . . . . .
table version. parameter . . . .
user load curve. fault code . .
view. parameter . . . . . . . . . .
parameter mode
Assistant Control Panel . . . .
Basic Control Panel . . . . . . .
parameter restore
Assistant Control Panel . . . .
Basic Control Panel . . . . . . .
Index
ACS550 User's Manual
PID protection
process sets. parameter groups . . . . . . . . . circuit. required wl chopper . . . . . . . . . . . . . 280
external I trimming. parameter group . . . . . disconnecting device (disconnecting means) 263
0% (actual signal). parameter . . . . . . . . . . . enclosure standard . . . . . . . . . . . . . . . . . . . . 291
100% (actual signal). parameter . . . . . . . . . environmental . . . . . . . . . . . . . . . . . . . . . . . . 289
actual input select. parameters . . . . . . . . . . motor thermal . . . . . . . . . . . . . . . . . . . . . . . . 273
actual value max.. parameters . . . . . . . . . . PT100 temperature sensor . . . . . . . . . . . . . . . . . 151
actual value min.. oarameters . . . . . . . . . . . PTC temperature sensor. . . . . . . . . . . . . . . . . . 151
adjustment procedure
comm v a l ~ e1. data parameter
comm value 2 . data barameter
control macro . . . . . . . . . . . . . . . . . . . . . . . radiation limits. conducted
correction source. parameter . . . . . . . . . . . EN 61800-3 . . . . . . . . .......
decimal point (actual signal). parameter . . . ramp pair (accelldecel). parameter . . . . _ . . . 131
derivation filter. parameter . . . . . . . . . . . . . range listing for parameters . . . . . . . . . . . . . . . . . 85
derivation time. parameter . . . . . . . . . . . . . ratinas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
.
deviation data ~arameter. . . . . . . . . . . . . . reference
error feedoack inversion. parameter . . . . . select. parameter group . . . . . . . . . . . . . . . . 109
external soJrce activate. parameter . . . corrections for parameter values . . . . . . . . . 110
.
feedback mult.pler ~arameter. . . . keypad control. parameter . . . . . . . . . . . . . . 109
feedback select. paiameter . . . . . . . . . . . . . maxlmum. parameters . . . . . . . . . . . . . . . . . 111
feedback. data parameter . . . . . . . . . . . . . . minimum. parameters. . . . . . . . . . . . . . . . . . I 1 1
gain. parameter . . . . . . . . . . . . . . . . . . . . . . mode (Basic Control Panel) . . . . . . . . . . . . . . 66
integration time. parameter . . . . . . . . . . . . . select source. parameter . . . . . . . . . . . . . . . 109
internal setpoint. parameter . . . . . . . . . . . . step (PFC). parameters . . . . . . . . . . . . . . . . 175
offset. parameter . . . . . . . . . . . . . . . . . . . . . reference scaling
o u t ~ u.tdata ~arameter. . . . . . . . . . . . . . . . EFB. ABB drives profile . . . . . . . . . . . . . . 218
parameter sel select. parameter . . . . FBA. ABB drives profile . . . . . . . . . . . . . . . . 236
.
scaing (0. 100%) parameters . . . . . . FBA. generic profile . . . . . . . . . . . . . . . . . . . 240
setpoint maximum. parameter. . . . . . . . . . . reference settino "
setpoint minimum. parameter . . . . . . . . . . . Assistant Control Panel . . . . . . . . . . . . . . . . .
setpoint select. parameter. . . . . . . . . . . . . .
.
setpoint source EFB comm activate. . . . . .
setpoint source. FBA comm. activate . . . . .
Basic Control Panel . . . . . . . . . . . . . . . . . . . . .
regulator by-pass control. parameter . . . . . . . . . 185
' setpoint. data parameter . . . . . . . . . . . . . . . .
relative humiditv
sleep delay. parameter . . . . . . . . . . . . . . . . . environment limit . . . . . . . . . . . . . . . . . . . . .
sleep level. parameter. . . . . . . . . j . . . . . . . . shipping limit . . . . . . . . . . . . . . . . . . . . . . . . .
sleep selection. parameter . . . . . . . . . ;. . . relay output
tnm mode. parameter . . . . . . . . . . . . . . . . . parameter group . . . . . . . . . . . . . . . . . . . . . . 116
trim scale. parameter . . . . . . . . . . . . . . . . . . activation condition oarameters . . . . . . . . . . 116
units (actual signal). parameter. . . . . . . . . . off-delay. parameters . . . . . . . . . . . . . . . . . .
wake-up delay. parameter. . . . . . . . . . . . . owdelay. parameters . . . . . . . . . . . . . . . . . .
wake-up deviation. parameter. : . . . . . . . . . . status. data oarameter . . . . . . . . . . . . . . . . . 101
PID controller relays. specifications . . . . . . . . . . . : . . . . . . . . . . 281
advanced set-up . . . . . . . . . . . . . . . . . ;. . . REM. . (remote control)
basic set-up . . . . . . . . . . . . . . . . . . . . . . . . . ~ndicationon Assistant Control Panel . . . . . . . 43
planning indication on Basic Control Panel. . . . . . . . . . . 62
. EFB comm . :. . . . . . . . . . . . . . . . . . . . . . . . removecover . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
FBA comm . . . . . . . . . :. . . . . . . . . . . . . . . reset. automatic
PNP . . . . . . . . . . . . . . . . . . . . .. . : parameter group . . . . . . . . . . . . . . . . . . . . . . 143
. ........... analog input less than min.. parameter . . . . 143
power
consumption ( M W ~ maintenance ) trigger . . delay time. parameter. . . . . . . . . . . . . . . . . . 143
data parameter . . . . . . . . . . . . . . . . . . . . . . external fault. ~arameter. . . . . . . . . . . . . . . 143
previous faults. history parameters . . . . . . . . . . number of triais. parameter . . . . . . . . . . . . . 143
process PID sets. parameter groups . . . . . . . . . overcurrent. parameter . . . . . . . . . . . . . . . . . 143
trial time . ~arameter. . . . . . . . . . . . . . . . . . . 143
process variables. data parameter . . . . . . . . . . undelvokage. parameter . . . . . . . . . . . . . . . 143
product
. . . resolution listing for parameters . . . . . . . . . . . . . . 85
. . ............................
inqulrles
resonance (avoiding)
tralnlng . . . . . . . . . . . . . . . . . . . . . . . . . . . .
select. parameter . . . . . . . . . . . . . . . . . . . . . 136
profiles. EFB comm . . . . . . . . . . . . . . . . . . . . . .
revolution counter. data parameter . . . . . . . . . . . 102
proportional gain. parameter
revolutions. mechanical. data parameter . . . . . . 102
ring lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
Index
306 ACS550 User's Manual
speed
baud rate. parameter . . . . . . . . . . . . . . . . . 172 and direction (sianed). data parameter
parity. parameter. . . . . . . . . . . . . . . . . . . . . 172 at fault. histor); Grameter . . . . . . . . .
station id. parameter . . . . . . . . . . . . . . . . . . 172 data parameter. . . . . . . . . . . . . . . . . . .
RS-232 counts max. limit. parameter . . . . . . . . . . . . . .
buffer overruns. parameter . . . . . . . . . . . . . 172 min. limit.parameter. . . . . . . . . . . . . . .
CRC errors. parameter . . . . . . . . . . . . . . . . 172 speed control
frame errors. parameter . . . . . . . . . . . . . . . 172 parameter group. . . . . . . . . . . . . . . . . . . . . . 133
ok messages.. parameter . . . . . . . . . . . . . . 172 acceleration compensation. parameter . . . . 134
parity errors. parameter . . . . . . . . . . . . . . . 172 automatic tuning. parameter . . . . . . . . 133. 134
RS485comm . . . . . . . . . . . . . . . . . . . . . . . . . . .
run enable source select. parameter. . . . . . . . .
run time
190
121 integration time. parameter . . . . . . . . .
proportional gain. parameter . . . . . . . . . . . 133
_
derivation time. parameter . . . . . . . . . . . . . . 133
. . 133
data parameter . . . . . . . . . . . . . . . . . 100. 102 vector:speed mode. . . . . . . . . . . . . . . . 98
maintenance trigger . . . . . . . . . . . . . . . . . . 139 speed. constant
parameter group . . . . . . . . . . . . . . . . . . . 112
S digital input selection parameter . . . . . . . 112
parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 113
safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 stall
save changes parameter. . . . . . . . . . . . . . . . . . 122 frequency. fault parameter . . . . . . . . . . . 141
sca1ar:frequency mode . . . . . . . . . . . . . . . . . . . . 98 function. fault parameter . . . . . . . . . . . . . 141
scaling region . . . . . . . . . . . . . . . . . . . . . . . . 141
.
actual value. FBA ABB drives profile . . . . . 239
actual value. FBA. generic profile . . . . . . . . 241
time. fault parameter . . . . . . . . . . . . . . I41
standards . . . . . . . . . . . . . . . . . . . .
actual values. EFB comm . . . . . . . . . . . . . . 197
. ..
reference EFB ABB drives profile . . . . . . . 218
reference. FBA ABB drives.profile . . . . . . . 236
C22.2 No. 14 . . . . . . . . . . . . . .
CE marking . . . . . . . . . . . . . . .
CSA marking . . . . . . . . . . . . . .
reference. FBA. generic profile . . . . . . . . . . 240 C-Tick marking . . . . . . . . . . . . .
screw-on terminal lugs . . . . . . . . . . . . . . . . . . 270 EN 50178 . . . . . . . . . . . . . . . . .
s-curve ramp. parameter . . . . . . . . . . . . . . . 131 IEC 60664.1 . . . . . . . . . . . . . . .
second environment IECIEN 60204.1 . . . . . . . . . . . .
(C3). compliance with IEClEN 61800-3 . . . . 293 IECIEN 60529 . . . . . . . . . . . . .
(C3). motor cable lenqth . . . . . . . . . . . . . . . . 272 IEClEN 61800-3 . . . . . . . . . . . .
definition . . . . . . . . . . . . . . . . . . . . . . 293 IECIEN 61 800-5-1 . . . . . . . . . .
sensor type. parameter . :: . . . . . . . . . . . . . . . . . 151 UL 508C . . . . . . . . . . . . . . . . . .
sensorless vector control mode. . . . . . . . . . . . . . 98 UL marking. . . . . . . . . . . . . . . .
serial 1 error (fault code 28)". . . . . . . . . . . . 200 start
serial 1 error. fault code . . . . . . . . . . . . . . . . . . . 247 parameter group . . . . . . . . . . . .
serial communication aux. motor (PFC), parameters .
see EFB (embedded fieldbus) aux. motor delay . . . . . . . . . . . .
see EFB. drive parameters control. EFB comm. . . . . . . . . .
see FBA (fieldbus adapter) control; FBA comm. . . . . . . . . . . . . . . . . . . .
see FBA. drive parameters DC magnetizing time. parameter . . . . . . . . .
delay (PFC). parameter . . . . . . . . . . . . . . . .
serialnumber . . . . . . . . . . . . . . . . . . . . . . . . . 12. 13 delay. parameter . . . . . . . . . . . . . . . . . . . . .
service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309 frequency (PFC). parameters . . . . . . . . . . . .
setpoint maximum (PID). parameter . . . . . . . . . 163 function. parameter . . . . . . . . . . . . . . . . . . .
setpoint minimum (PID). parameter . . . . . . . . . 163 inhibit. parameter . . . . . . . . . . . . . . . . . . . . .
setpoint select (PID). parameter . . . . . . . . . . . . 162 .
select enable source parameter . . . . . . . . .
shock. stress testing . . . . . . . . . . . . . . . . . . . 290 torque boost current.parameter . . . . . . . . . . 129
short circuit. fault code . . . . . . . . . . . . . . . . . 245 start mode
single phase supply automatic . . . . . . . . . . . . . . . . . . . . . . . 128
connection . . . automatic torque boost. . . . . . . . . . . . . . . . . 128
derating . . . . . . . . . . . . . . . . . . . . . . . 262 DC magnet~zlng. . . . . . . . . . . . . . . . . . . . . . 128
sleep selection (PID). parameter. . . . . . . . . . . . 164 flying start . . . . . . . . . . . . . . . . . . . . . . . . . . 128
slip compensation ratio. parameter . . . . . . . . . . 138 startlstop
soft keys (Assistant Control Panel) . . . . . . . . . . . 42 parameter group. . . . . . . . . . . . . . . . . . . . . . 128
specifications with Assistant Control Panel . . . . . . . . . . . . . 46
control connections . . . . . . . . . . . . . . . . . . . 281 with Basic Control Panel . . . . . . . . . . . . . . . . 64
Input power . . . . . . . . . . . . . . . . . . . . . . . . 263 startlstopldir. parameter qroup . . . . . . . . . . . . . . . . 107
mains . . . . . . . . . . . . . . . . . . . . . . . . 263 starting order counter . . . . . . . . . . . . . . . . . . . . . 180
Index
ACS550 User's Manual 307
startq tools . . . . . . . . . . . .
assistant . . . . . . . . . . . . . . . . . . . . . . . . . 36.51 top cover. see hood
data. parameter group. . . . . . . . . . . . . . . . . . 98 torque
guided. Assistant Control Panel . . . . . . . . . . 36 at fault. history parameter. . . . . . . . . . . . . . . 106
limited. Assistant or Basic Control Panel . . . 31 boost current. parameter . . . . . . . . . . . . . . . 129
state diagram data parameter . . . . . . . . . . . . . . . . . . . . . 100
comm (EFB) . . . . . . . . . . . . . .
comm. ABB drives . . . . . . . . . .
.
max..l]mjt select parameter . . . . . . . . . . . . . 126
max. Ilmlt. parameter . . . . . . . . . . . . . 127
station id (RS-232) parameter . . . min. limit select. parameter . . . . . . . . . . . . 126
status at fault. history parameter . . min. limit. parameters . . . . . . . . . . . . . . . . . 126
status word ramp down. parameter . . . . . . . . . . . . . . . . . 135
ABB drives. FBA. description . ramp up. parameter . . . . . . . . . . . . . . . . 135
EFB comm. definition . . . . . . . torque control
FBA . . . . . . . . . . . . . . . . . . . . . parameter group . . . . . . . . . . . . . . . . . 135
FBA aeneric ~ r o f i l e. . . . . . . . . macro . . . . . . . . . . . . . . . . . . . . . . . . . . 7 9
stop ramp down. parameter . . . . . . . . . . . . . . . . . 135
parameter group . . . . . . . . . . . ramp up. parameter . . . . . . . . . . . . . . . . . . . 135
aux. motor (PFC). parameters vect0r:torque mode . . . . . . . . . . . . . . . . . . . . 98
aux. motor delay . . . . . . . . . . . training . . . . .
DC brake time. parameter . . . . trim
DC current control. parameter. mode (PID). parameter. . . . . . . . . . . . . . . . .
DC current ref.. parameter . . . scale (PID). parameter . . . . . . . . . . . . . . . . .
emergency devices . . . . . . . . . two-wire sensor..connection example . . . . . . . . . . 80
emergency select. parameter . type code . . . . . . . . . . . . . . . . . . . . . . . . . . . 12. 13
flux braking. parameter . . . . . .
function. parameter . . . . . . . . . u
stress tests . . . . . . . . . . . . . . . . . .
su~ervision Ulf ratio. parameter . . . . . . . . . . . . . . . . . . . . . . . 137
parameter group . . . . . . . . . . . . . . . . . . . . . 144 ULlCSA markings . . . . . . . . . . . . . . . . . . . . . . . . 292
parameter low limit. parameters . . . . . . . . . 144 underload curve
parameter selection. .oarameters . . . . . . . . 144 see user load curve
supply phase. fault code . . . . . . . . . . . . . . . . . . 246 undervoltage
switching frequency . . . . . . . . . . . . . . . . . . . . . . 271 automatic reset. parameter . . . . . . . . . . . . . 143
control. parameter . . . . . . . . . . . . . . . . . . . . 138 control enable. parameter . . . . . . . . . . . . . . 125
deratinn.. . . . . . . . . . . . . . . . . . . . . . . . . . . . 262 ungrounded network
parameter . . . . . . . . . . . . . . . . . . . . . . . . . . 138 see IT system
symmetrically grounded network units (PID). parameter. . . . . . . . . . . . . . . . . . . . . 161
see corner grounded TN system unknown drive type. fault code . . . . . . . . . . . . . . 248
system controls. parameter group . . . . . . . . . . . 121 unpacking drive . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
unsymmetrically grounded networks
see corner grounded TN system
temperature derating . . . . . . . . . . . . . . . . . . . . . 262 user load curve
parameter group . . . . . . . . . . . . . . . . . . . . . . 156
template. mounting . . . . . . . . . . . . . . . . . . . . . . . 16 fault code . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
terminal lugs. ........................... 270 frequency. parameters . . . . . . . . . . . . . 156. 157
terminals fundlon. parameter . . . . . . . . . . . . . . . . . . . 156
control. descriotion mode. parameter . . . . . . . . . . . . . . . . . . . . . 156
control; specifkations . . . . . . . . . . . . . . . . . 282 time. parameter . . . . . . . . . . . . . . . . . . . . . . 156
location diagram. R1... R4 . . . . . . . . . . . . . . . 20 torque. parameters . . . . . . . . . . . . . . . . 156 157 .
location . .
. . diaaram. R5IR6 . . . . . . . . . . . . . . . . 21 user parameter set . . . . . . . . . . . . . . . . . . . . . . . . 81
termlnat~on. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191 change control. parameter . . . . . . . . . . . . . . 122
test date. parameter . . . . . . . . . . . . . . . . . . . . . 146 download . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
thermal fail. fault code . . . . . . . . . . . . . . . . . . . . 246
timed functions
parameter group . . . . . . . . . . . . . . . . . . . . . 152 vector:
autochange. parameter . . . . . . . . . . . . . . . . 186 speedmode . . . . . . . . . . . . . . . . . . . . . . . . . . 98
booster. parameter . . . . . . . . . . . . . . . . . . . 154 torquemode . . . . . . . . . . . . . . . . . . . . . . . . . . 98
enable. parameter . . . . . . . . . . . . . . . . . . . . 153
source. parameter . . . . . . . . . . . . . . . . . . . . 154 version
speedcontrol . . . . . . . . . . . . . . . . . . . . . . . . 114 firmware. parameter . . . . . . . . . . . . . . . . 60. 146
start time. parameter . . . . . . . . . . . . . . . . . . 153 loading package. parameter . . . . . . . . . . . . . 146
stop time. parameter . . . . . . . . . . . . . . . . . . 153 panel firmware . . . . . . . . . . . . . . . . . . . . . 41.45
timed mode. parameter . . . . . . . . . . . . . . . . . . . 114 parameter table. parameter . . . . . . . . . . . . . 146
Index
ACS550 User's Manual
.
vibration . stress testina . . . . . . . . . . . . . . . . . . . 290
voltage
.
at fault . historv .oarameter . .
ratingcode . . . . . . . . . . . . . . . . . . . . . . . . . . 13
voltagelfrequency ratio. parameter . . . . . . . . . . 137
wake-up
delay (PID). parameter . . . . . . . . . . . . . . . . 165
deviation (PID). parameter . . . . . . . . . . . . . 165
warnina
aufomatic start uo . . . . . . . . . . . . . . . . . . . . . . 6
~ ~~~ ~
dangerous voltages . . . . . . . . . . . . . . . . . . . . 5
disconnecting device (disconnecting means) . 6
ELV (Extra Low Voltage) . . . . . . . . . . . . . . . 23
.
EM?. EM3 F1 and F2 screws. . . . . . . . . . . . . 6
filter on corner grounded TN system. . . . . . . . 6
filter on IT svstem . . . . . . . . . . . . . . . . . . . . . . 6
high temperatures . . . . . . . . . . . . . . . . . . . . . . 6
listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
not field repairable . . . . . . . . . . . . . . . . . . . . . 6
parallel control connections . . . . . . . . . . . . . . 5
qualified installer . . . . . . . . . . . . . . . . . . . . . . . 5
weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
wiring
control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
fault. parameter. . . . . . . . . . . . . . . . . . . . . . 142
~nstallation. . . . . . . . . . . . . . . . . . . . . . . . . . . 24
.
installation steps IP21lcables . . . . . . . . . . . 25
installation steps. IP2llconduit . . . . . . . . . . . 26
installation steps. IP541cables . . . . . . . . . . . 27
installation steos . .. IP54lconduit . . . . . . . . . . . 28
overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
requirements. general . . . . . . . . . . . . . . . . . . 18
XYZ
zero pulse
detected. data parameter . . . . . . . . . . . . . . 102
enable. parameter. . . . . . . . . . . . . . . . . . . . 170
zero speed
delay. parameter . . . . . . . . . . . . . . . . . . . . . 130
load. fault parameter . . . . . . . . . . . . . . . . . . 141
Index
Contact ABB
Product training
For information on ABB product training, navigate to www.abb.comldrives and select Drives - Train-
ing courses on the right pane.
Safety instructions
Eleaiical installalion planning
- Mechanical and electrical installation
Molar conliol and 110 board (RMIO)
Maintenance
Technical dala
Dimensionaldrawings
Resistor braking
Hardware Manual
3AFE68372984 Rev E EN
EFFECTIVE: 31.03.2008
Safety instructions
Installation and maintenance work
These warnings are intended for all who work on the drive, motor cable or motor.
WARNING! Ignoring the following instructions can cause physical injury or death, or
damage to the equipment:
. Only qualified electricians are allowed t o install and maintain the drive.
. Never work on the drive, the motor cable or the motor when main power is
applied. After switching off the input power, always wait for 5 min to let the
intermediate circuit capacitors discharge before you start working on the drive,
the motor or the motor cable.
Always ensure by measuring with a multimeter (impedance at least 1 Mohm)
that:
I . voltage between drive input phases U1. V1 and W1 and the frame is close to
0v
2. voltage between terminals UDC+ and UDC- and the frame is close to 0 V.
Do not work on the control cables when power isapplied to the drive or to the
external control circuits. Externally supplied control circuits may cause
dangerous voltages inside the drive even when the main power on the drive is
switched off.
. Do not make any insulation or voltage withstand tests on the drive or drive
modules.
When reconnecting the motor cable, always check that the phase order is
correct.
Note:
. The motor cable terminals on the drive are at a dangerously high voltage when
the input power is on, regardless of whether the motor is running or not.
The brake control terminals (UDC+, UDC-, R+ and R- terminals) carry a
dangerous DC voltage (over 500 V).
Depending on the external wiring, dangerous voltages (115 V, 220 V or 230 V)
may be present on the terminals of relay outputs R 0 1 to R 0 3 or on the optional
AGPS board (Prevention of Unexpected Start).
. The Prevention of Unexpected Start function does not remove the voltage from
the main and auxiliary circuits.
* At installation sites above 2000 m (6562 ft), the terminals of the RMlO board
and optional modules attached to the board do not fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 50178.
Safety instructions
Grounding
These instructions are intended for all who are responsible for the grounding of the
drive.
WARNING! Ignoring the following instructions can cause physical injury, death,
increased electromagnetic interference and equipment malfunction:
A
Ground the drive, motor and adjoining equipment to ensure personnel safety in
all circumstances, and to reduce electromagnetic emission and interference.
. .
Make sure that grounding conductors are adequately sized as required by
safety regulations.
. In a multiple-drive installation, connect each drive separately to protective
earth (PE).
. In first environment (EU EMC Directive): make a 360" high frequency
grounding of the motor cable entry at the cabinet lead-through.
Do not install a drive with EMC filter option +E202 or +€ZOO on an ungrounded
power system or a high resistance-grounded (over 30 ohms) power system.
Note:
. Power cable shields are suitable for equipment grounding conductors only
when adequately sized to meet safety regulations.
. As the normal leakage current of the drive is higher than 3.5 mA AC or 10 mA
DC (stated by EN 50178, 5.2.11.1), a fixed protective earth connection is
required.
Safety inst~clions
Mechanical installation and maintenance
These instructions are intended for all who install and service the drive.
WARNING! Ignoring the following instructions can cause physical injury or death,
or damage to the equipment:
.
a
. The drive is heavy. Do not lift it alone. Place the unit only on its back
WARNING! Ignoring the following instructions can cause damage to the printed
1 ,A circuit boards:
The printed circuit boards contain components sensitive to electrostatic
discharge. Wear a grounding wrist band when handling the boards. Do not
touch the boards unnecessarilv.
Safetv instructions
Operation
These warnings are intended for all who plan the operation of the drive or operate
the drive.
WARNING! Ignoring the following instructions can cause physical injury or death.
or damage to the equipment:
. Before adjusting the drive and putting it into service, make sure that the motor
and all driven equipment are suitable for operation throughout the speed range
provided by the drive. The drive can be adjusted to operate the motor at
speeds above and below the speed provided by connecting the motor directly
to the power line.
. Do not activate automatic fault reset functions of the Control Program if
dangerous situations can occur. When activated, these functions will reset the
drive and resume operation after a fault.
Do not control the motor with the disconnecting device (means); instead, use
the control panel keys @ and 0, or commands via the 1{0board of the drive.
The maximum allowed number of charging cycles of the DC capacitors (i.e.
power-ups by applying power) is five in ten minutes.
Note:
Ifan external source for start command is selected and it is ON, the drive (with
Standard I Motion Control Program) will start immediately after fault reset
unless the drive is configured for 3-wire (a pulse) start/stop.
When the control location is not set to Local (L not shown in the status row of
the display), the stop key on the control panel will not stop the drive. To stop
the drive using the control panel, press the LOCIREM key and then the stop
key @.
Safety inst~ctions
Permanent magnet motor
These are additional warnings concerning permanent magnet motor drives. Ignoring
the instructions can cause physical injury or death, or damage to the equipment.
WARNING! Do not work on the drive when the permanent magnet motor is rotating.
Also, when the supply power is switched off and the inverter is stopped, a rotating
permanent magnet motor feeds power to the intermediate circuit of the drive and the
supply connections become live.
Before installation and maintenance work on the drive:
Stop the motor.
Ensure that the motor cannot rotate during work. Prevent the start-up of any
drives in the same mechanical group by opening the "prevention of unexpected
start" switch and padlocking it. Make sure that no other system, like hydraulic
crawling drives, are able to rotate the motor directly or through any. mechanical
connection like felt, nip, rope, etc.
Ensure that there is no voltage on the drive power terminals:
Alternative I ) Disconnect the motor from the drive with a safety switch or by other
means. Measure that there is no voltage present on the drive input or output
terminals (UI. V1, W1, U2, V2, W2, UDC+, UDC-).
Alternative 2) Measure that there is no voltage present on the drive input or output
terminals (UI, V1, W1, U2, V2. W2, UDC+. UDC-). Ground the drive output
terminals temporarily by connecting them together as well as to the PE.
Alternative 3) If possible, both of the above.
WARNING! Do not run the motor over the rated speed. Motor overspeed leads to
overvoltage which may damage or explode the capacitors in the intermediate circuit
of the drive.
Controlling a permanent magnet motor is only allowed using the ACSBOO Permanent
Magnet Synchronous Motor Drive Control Program, or other control programs in
scalar control mode.
Safety instructions
Table o f contents
..
Safety instructions
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Useofwarningsandnotes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mechanical installation and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Printed circuit boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fibreopticcables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Permanentmagnetmotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Start-up and operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table o f contents
Whatthischaptercontains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Typecode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Main circuit and control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Printedcircuitboards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Motorcontrol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table of contents
Whatthischaptercontains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Cabinetconstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Dispositionofthedevices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Grounding of mounting structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 7
Freespacearoundtheunit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Cooling and degrees of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Preventing the recirculation of hot air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Outsidethecabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Inside the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Cabinet layout example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1
Cabinetheaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Mounting the optional control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Installing the control panel directly on the cabinet door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Control panel mounting platform kit (RPMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
EMCrequirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Mechanical installation
Unpackingtheunit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Deliverycheck . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Before installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : . . . . . . . . . . . . . . . . . . . . . 36
Requirements for the installation site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
lnstallationprocedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Flangemounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Table of contents
Motorcableshield . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Additional US requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Armored cable Ishielded power cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Power factor compensation capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Equipment connected to the motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Installation of safety switches. contactors. connection boxes. etc . . . . . . . . . . . . . . . . . . . . . 54
Bypassconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Before opening a contactor (DTC control mode selected) . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Protecting the relay output contacts and attenuating disturbances in case of inductive loads . . . . 55
Selecting the control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Relaycable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Controlpanelcable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Connection of a motor temperature sensor to the drive 110 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Installation sites above 2000 metres (6562 feet) . . . . . . . . : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Routingthecables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Controlcableducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Checking the insulation of the assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Inputcable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Motor and motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
IT(ungrounded)systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Powercableconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Connecting the power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Grounding the motor cable shield at the motor end . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Frame sizes R2 to R4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
FramesizeR5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Frame size R6: Cable lug installation [ I 6 to 70 mm2 (6 to 210 AWG) cables] . . . . . . . 64
Power cable protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
FramesizeR5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
FramesizeR6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Warningsticker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Connectingthecontrolcables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
360degreesgrounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
When the outer surface of the shield is covered with non-conductive material . . . . . . 69
Connecting the shield wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Cabling of 110 and fieldbus modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Pulseencodermodulecabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Installation of optional modules and PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Fibreopticlink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
External +24 V power supply for the RMlO board via terminal X34 . . . . . . . . . . . . . . . . . . . . . . . . 71
Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Connecting +24 V external power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Prevention of Unexpected Start, AGPS board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Table of contents
Motor control and 110 b o a r d (RMIO)
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7
Note on terminal labelling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7
Note on external power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7
External control connections (non-US) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
External control connections (US) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
RMlOboardspecifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Analogueinputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Constant
..
voltage output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -80
Auxiliary power output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Analogueoutputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Digitalinputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Relayoutputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
DDCSfibreopticlink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
24 V DC power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Installation checklist
Checltlist . . . . . . . . . .
Maintenance
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Maintenanceintervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
j Heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
..' Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Fan replacement (R2, R3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Fanreplacement(R4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Fanreplacernent(R5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Fanreplacement(R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Additionalfan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Replacement(R2, R3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Replacement(R4, R5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Replacement(R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Reforming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Technical data
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
IECdata . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Table of contents
Altitudederating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Cooling characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Cooling requirements for flange mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
FramesizesR2toR4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
FramesizesR5andR6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Calculation example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
gGfuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Ultrarapid (aR) fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Quick guide for selecting between gG and aR fuses . . . . . . . . . . . . . . . . . . . . . . . . . 100
Cabletypes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Cableentries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Dimensions. weights and noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
NEMAdata . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Fuses . . . . . . . . . . . . . . 105
Cabletypes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Cableentries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Dimensions, weights and noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : . . . . . . . 107
Input power connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 .
Motorconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Degreesofprotection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
AGPS-11C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Ambientconditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Applicablestandards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
CEmarking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
..
Defin~t~ons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Compliance with the EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Compliance with the EN 61800-3 (2004) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
First environment (drive of category C2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Second environment (drive of category C3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Second environment (drive of category C4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
. . .......................................................
MachineryD~rect~ve 112
"C-tickWmarking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : . . . . . . . . . 113
..
Defin~tlons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Compliance with IEC 61800-3 . . . . . . . . . . . . I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
First environment (drive of category C2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Second environment (drive of category C3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Second environment (drive of category C4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Marinetypeapprovals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
UUCSAmarkings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
UL 115
Equipment warranty and liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Product protection in the US . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
. .
...
. . . re&,? of contents
. .
Dimensional drawings
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Frame size R2 (with optional control panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Frame size R3 (with optional control panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Frame size R4 (with optional control panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 0
Frame size R5 (with optional control panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Frame size R6 (with optional control panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Flangemountingkits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Flange mounting kit for frame size R2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Ftange mounting kit for frame size R3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 5
Flange mounting kit for frame size R4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Flange mounting kit for frame size R5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 7
Flange mounting kit for frame size R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
AGPSboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Resistor braking
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . .
Availability of brake choppers and resistors . . . . . . . . . . . . . .
How to select the correct driveichopperlresistor combination
Optional brake chopper and resistor(s) . . . . . . . . . . . . . . . . .
Resistor installation and wiring . . . . . . . . . . . . . . . . . . . . . . . .
Protection of frame sizes R2 to R5 . . . . . . . . . . . . . . . . . . . . .
Protection of frame size R6 . . . . . . . . . . . . . . . . . . . . . . . . . .
Brake circuit commissioning . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of contents
About this manual
Compatibility
The manual is compatible with ACS800-04lU4 (frame sizes R2... R6).
Intended audience
This manual is intended for people who plan the installation, install, commission, use
and service the drive. Read the manual before working on the drive. The reader is
expected to know the fundamentals of electricity, wiring, electrical components and
electrical schematic symbols.
This manual is written for readers worldwide. Both SI and imperial units are shown.
Special US instructions for installations within the United States that must be
installed per the National Electrical Code and local codes are marked with (US).
Task See
Identify the frame size of your drive: R2,R3. R4. R5 Technical data: IEC data or NEMA dala
or R6.
4
Route the cables. Planning the eleclrical installation: Routing the
cables
4
Check the insulalian of the motor and the motor Electricalhstalla!im: Checking the insulalion of
cable. the assembly
Connect the power cables. Electrical installalion, Motor control and I/O
board (RMIO). Resislor braking (optional) and
the optional module manual delivered with the
module.
Operabng of the dnve start, stop, speed control etc Appropr~aleFfrmware Manual
Product training
For information on ABB product training, navigate to www.abb.corn/drives and select
Drives - Training courses on the right pane.
Size of the frame into which the drive module is assembled. Several
supply modules with different nominal powers may have the same frame
size. The term refers to modules that have a similar mechanical
construction.
To determine the frame size of a drive module, refer lo the rating tables in
chapter Technical data.
Input/Output
Gate driver Power Supply board. An optional board used to implement lhe
Prevention of Unexpected Start function.
Motor conlrol and 110 board. The external 110 control signals are
connected to RMIO.
Layout
The ACS800-041U4 (frame sizes R2 to R6) is an IP20 drive module for controlling
AC motors. It is to be installed into a cabinet by the customer with wall fastening.
Option slots
Power cable
terminal
Heatsink
\Selection 1 Alternatives I
Product series ACSBOO product series
Type 04 Drive module. When no options are selected: IP20, no control panel, no
EMC filter, Standard Control Program, brake chopper in frame sizes R2,
R3, and R4 (only 690 V), boards without coating, one set of manuals.
IUe I
Drive module (USA). When no options are selected: UL open lype, no
control panel. no EMC filter. Standard Control Program, brake chopper in
frame sizes R2, R3, and R4 (only 690 V), boards without coating, one set
I lof manuals.
Size /See Technical data: IEC data or NEMA data.
Voltage range 12 ~208/220/2301240V AC
(nominal rating in bold) 3 38014001415 V AC
5 380140014151440146014801500V AC
7 525/575/600/690 V AC
+options
Control panel J400 Control panel CDP312R assembled on the drive module
J414 Control panel holder for frame sizes R2. R3 and R4 (not to be used with
option J400)
Construction C132 Marine drive (coaled boards included)
C135 Flange mounting. Flange mounting plate assembled. IP55 for heal sink
side and IP20 for drive front side.
Filter E200 EMCIRFI filter for second environment TN (grounded) system, drive
category C3
E202 EMCIRFI filter for first environment TN (grounded) system, drive category
C2. (Not available for 690 V units.)
E210 EMCIRFI filter for second environment TNllT (groundedlungrounded)
system, drive category C3 (frame size R6 only)
Resistor braking Dl50 Brake chopper. Included as standard in frame sizes R2, R3 and R4 (only
690 V).
Safety Q950 Prevention of Unexpected Start: AGPS board and 3 m connection wire.
Fieldbus K... Refer to ACS800 Ordering Infomation 13AFE64556568 (English)].
110 L...
Control program N...
Manual language R...
Specialities P901 Coated boards
Diagram
This diagram shows the control interfaces and the main circuit of the drive. Location
of terminals vary depending on the drive frame size.
1 Drive
Input power 1
.
T
- ,
;-,?y 1 1
J
R- UDC+ UDC-
R+
output power
I Component / Description 1
1 Six-pulse rectifier 1 Converts the three-phase AC voltage to DC voltage. I
I Capacitor bank 1 Energy storage which stabilizes the intermediate circuit DC voltage. 1
I IGBT
inve*er I Converts the DC voltage to AC voltage and vice versa. The motor
. 1s controlied by switching the IGBTs.
operation
Note: The installation examples in this manual are provided only to help the installer
in designing the installation. The installation m u s t always be designed and made
according t o applicable local laws and regulations. ABB does not assume any
liability whatsoever for any installation which breaches the local laws andlor other
regulations.
Cabinet construction
The cabinet frame must be sturdy enough to carry the weight of the drive
components, control circuitry and other equipment installed in it.
The cabinet must protect the drive module against contact and meet the
requirements for dust and humidity (see chapter Technical data).
Note: Ensure that the modules are properly grounded through their fastening points
to the installation base.
Arrange the cooling air flow through the modules so that the requirements given in
chapter Technical data are met:
cooling air flow
Note: The values in Technical data apply to continuous nominal load. If the load is cyclic or less
than nominal, less cooling air is required.
Vertical mounting
AC fuse bases
Hot area
Coal area
..Mounting
plates
Modules
EMC requirements
Generally, the fewer and smaller the holes in the cabinet, the better the interference
attenuation. The maximum recommended diameter of a hole in galvanic metal
contact in the covering cabinet structure is 100 mm. Special attention must be paid
to the cooling air inlet and outlet gratings.
The best galvanic connection between the steel panels is achieved by welding them
together as no holes are necessary. If welding is not possible, the seams between
the panels are recommended t o be left unpainted and equipped with special
conductive EMC strips to provide adequate galvanic connection. Usually, reliable
strips are made of flexible silicon mass covered with a metal mesh. The non-
tightened touch-contact of the metal surfaces is not sufficient, so a conductive
gasket between the surfaces is required. The maximum recommended distance
between assembly screws is 100 mm.
Sufticient high-frequency grounding network must be constructed in the cabinet to
avoid voltage differences and forming of high-impedance radiator structures. A good
high-frequency grounding is made with short flat copper braids for low inductance.
One-point high-frequency grounding cannot be used due to the long distances inside
the cabinet.
First environment EMC compliance ') of the drive requires 360" high frequency
grounding of the motor cable shields at their entries. The grounding can be
implemented by a knitted wire mesh screening as shown below.
Lead-through plate
/ +----Cable
Cabinet bottom plate
') First environment EMC compliance is defined in section CE marking in chapter Technical daia.
Mechanical installation
Delivery check
Check that there are no signs of damage. Before attempting installation and
operation, check the information on the type designation label of the drive to verify
that the unit is of the correct type. The label includes IEC rating, C-UL US. CSA,
C-tick and CE markings, a type code and a serial number, which allow individual
recognition of each unit. The first digit of the serial number refers to the
manufacturing plant. The next four digits refer to the unit's manufacturing year and
week, respectively. The remaining digits complete the serial number so that there
are no two units with the same serial number.
The type designation label is attached to the heat sink and the serial number label to
the upper part of the back plate of the unit.
Before installation
Check the installation site according to the requirements below. See Dimensional
drawings for frame details.
Mechanicalinstallation
Installation procedure
1. Mark the locations for the four holes. The mounting points are shown in
Dimensional drawings. With frame sizes R2...R5, use the mounting template cut
from the package.
2. Fix the screws or bolts to the marked locations.
3. Position the drive onto the screws on the cabinet wall. Note: Lifl the drive by its
chassis (R6: by its lifting holes).
4. Tighten the screws in the cabinet wall securely.
Mechanical installation
Flange mounting
The flange mounting plate is factory assembled on the drive. With flange mounting,
the degree of protection is IP55 for the heat sink side and IP20 for the drive front
side. The drive front side must always be housed in a cabinet.
Mechanical
..
iqtallation
. . .
. . . . . .
. . .... .
. ..
. ..
R6 flange mounting
Mechanical insfallation
Planning the electrical installation
If frequent or long term brake cycles will be used, the motor voltage rating is
U~~eq.
= UDC/?.35
UACeq
where
UACeqis the equivalent AC power source voltage of the drive in VAC.
1
PN< 100 kW
and
Requirement for
ABB duldt filter, insulated N-end bearing and ABB common
134HPzPN< PN>469HP
and frame size < 469 HP or frame size >
NEMA 500 or frame size 2 NEMA 580
NEMA 500
Standard: (jlL= - +NorCMF +N+CMF
wound and 1300V
420 V < UN5 500 V Standard: qL= + duldt + duldt + N + duldt + N + CMF
1300 V or
+ duldt + CMF
or
Reinforced: - + N o r CMF +N+CMF
oLL = 1600 V.
0.2
microsecond
rise time
500 V < UN5600 V Reinforced: OLL t duldt + duldt + N + duldt + N c CMF
= 1600 V or
+ duldt + CMF
-.
nr
Abbreviation Definition
UN nominal voltage of the supply network
ljl~ peak line-lo-line voltage at motor terminals which the motor insulalion must withstand
~~~ ~
~ l h o udu/dl
f filler
Note 8: Sine filters protect the motor insulation system. Therefore, duldt filter can be replaced with
a sine filter. The peak phase-to-phase voltage with the sine filter is approximately 1.5 r UN.
Note 9: Common mode filter is available as a separate kit (one box including three rings for one cable)
Supply connection
Main contactor
If used, dimension the contactor according to the nominal voltage and current of the
drive. The utilization category (IEC 947-4) is AC-1.
Fuses
See section Thermal overload and short-circuit protection
Thermal overload protection of the drive and the input and motor cables
The drive protects itself and the input and motor cables against thermal overload
when the cables are dimensioned according to the nominal current of the drive. No
n'
additional thermal protection devices are needed.
41
8-d
1) Size the fuses according lo instructions given in chapter Technical dala. The fuses will protect the input
cable in short-circuit situations, restrict drive damage and prevent damage to adjoining equipment in
case of a short-circuit inside the drive.
WARNING! Due to the inherent operating principle and construction of circuit breakers
A ~ndeoendentof the manufacturer. hot ionized aases " mav escaoe from the breaker
c n c o s ~ r ei r j cssc of a shon-ctrc~il ro ccnsLre safe ube SIIEC 3 atlenllon rn )st be pa a to
/$\ It!@ ins~a..altonrind placement of lne breakers f ~ o l l lnc o ~ ~nan.laclurer's inslr~cuons
Note: Circuit breakers must not be used without fuses in the USA.
Emergency s t o p devices
For safety reasons, install the emergency stop devices at each operator control
station and at other operating stations where emergency stop may be needed.
Note: Pressing the stop key (a)
on the control panel of the drive does not generate
an emergency stop of the motor or separate the drive from dangerous potential.
WARNING! The Prevention of Unexpected Start function does not disconnect the
voltage of the main and auxiliary circuits from the drive. Therefore maintenance work
on electrical parts of the drive or the motor can only be carried out afler isolating the
drive system from the main supply.
Note: The Prevention of Unexpected Start function is not intended for stopping the
drive. If a running drive is stopped by using the Prevention of Unexpected Start
function, the drive will cut off the motor supply voltage and the motor will coast to
stop.
-- --
General rules
Dimension the mains (input power) and motor cables according t o local
regulations:
The cable must be able to carly the drive load current. See chapter Technical
data for the rated currents.
The cable must be rated for at least 70 "C maximum permissible temperature of
conductor in continuous use. For US, see section Additional US requiremenls.
The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
600 V AC cable is accepted for up to 500 V AC. 750 V A C cable is accepted for
up to 600 VAC. For 690 V A C rated equipment, the rated voltage between the
conductors of the cable should be minimum 1 kV.
For drive frame size R5 and larger, or motors larger than 30 kW (40 HP).
symmetrical shielded motor cable must be used (figure below). A four-conductor
system can be used up to frame size R4 with up to 30 kW (40 HP) motors, but
shielded symmetrical motor cable is always recommended. The shield(s) of motor
cable(s) must have 360" bonding at both ends.
Note: When continuous metal conduit is employed, shielded cable is not required
The conduit must have bonding at both ends as with cable shield.
A four-conductor system is allowed for input cabling, but shielded symmetrical cable
is recommended. To operate as a protective conductor, the shield conductivity must
be as follows when the protective conductor is made o f the same metal as the phase
conductors:
Cross-sectional area of the phase Minimum cross-sectional area of the corresponding
conductors protective conductor
s (rnrn2) S, (mm2)
S < 16 S
16<S535 16
35 < S 512
Recommended
Symmetrical shielded cable: lhree phase conductors Aseparate PE conductor is required if the conductivity
and a concenlric or otherwise symmetrically of the cable shield is < 50% of the conductivity of the
constructed PE conductor, and a shield phase conductor.
PE conductor
Shield
0 PE
lnsu,ation jacket Copper wire screen Helix of copper tape Inner insulation
\ \ or copper wire
\
,-Cable core
Note: Do not run motor wiring from more than one drive in the same conduit.
p~ ~~
If there are power factor compensation capacitors in parallel with the three phase
input of the drive:
1. Do not connect a high-power capacitor to the power line while the drive is
connected. The connection will cause voltage transients that may trip or even
damage the drive.
2. If capacitor load is increasedldecreased step by step when the AC-drive is
connected to the power line: Ensure that the connection steps are low enough not
to cause voltage transients that would trip the drive.
3. Check that the power factor compensation unit is suitable for use in systems with
AC drives i.e. harmonic generating loads. In such systems, the compensation unit
should typically b e equipped with a blocking reactor or harmonic filter.
WARNING! Never connect the supply power to the drive output terminals U2, V2
and W2. If frequent bypassing is required, employ mechanically connected switches
or contactors. Mains (line) voltage applied to thebutput can result in permanent
damage to the unit.
RMlO
I Relay outputs
Varistor
230 VAC
3 R01
RC filter , x7fi
a b
A double-shieldedtwisted A single-shielded twisted
pair cable multipair cable
Relay cable
The cable type with braided metallic screen (e.g. OLFLEX by LAPPKABEL,
Germany) has been tested and approved by ABB.
WARNING! IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either non-
conductive or conductive but not connected to the protective earth.
To fulfil this requirement, the connection of a thermistor (and other similar
components) to the digital inputs of the drive can be implemented in three alternate
ways:
1. There is double or reinforced insulation between the thermistor and live parts of
the motor.
2. Circuits connected to all digital and analogue inputs of the drive are protected
against contact and insulated with basic insulation (the same voltage level as the
drive main circuit) from other low voltage circuits.
3. An external thermistor relay is used. The insulation of the relay must be rated for
the same voltage level as the main circuit of the drive. For connection, see
ACSBOO Firmware Manual.
WARNING! Protect against direct contact when installing, operating and servicing
the RMlO board wiring and optional modules attached to the board. The Protective
Extra Low Voltage (PELV) requirements stated in EN 50178 are not fulfilled at
altitudes above 2000 m (6562 ft).
Motor cable
Drive
Control cables
Control c a b l e d u c t s
Not alloweu Jnless tllc 24 V cab0 IS Lead 21 V and 730 V (120 V j conlrol
InsJlaleU for 230 V (120 VI or illsulaled cables I>seDarate ducts Insme lllc
with an insulation sleevin&for cabinet
230 V (120 V).
WARNING! The work described in this chapter may only be carried out by a qualified
electrician. Follow the Safety instruclions on the first pages o f this manual. Ignoring
the safety instructions can cause injury or death.
Make sure that the drive i s disconnected from the mains (input power) during
installation. IF the drive i s already connected t o the mains, wait for 5 min after
disconnecting mains power.
Input cable
Checlc the insulation of the input cable according to local regulations before
connecting it to the drive.
Electrical installation
IT (ungrounded) systems
Ensure that the drive is not equipped with optional EMC filter, i.e. type code does not
include selections +E200 or +E202.
However if EMC filters exist, disconnect the EMC filter capacitors of selections
+E202 and +E200 before connecting the drive to an ungrounded system. For
detailed instructions on how to do this, please contact your local ABB distributor
Electrical installation
Power cable connection
t -1
I
--
&;
External brake
For alternatives, see
Planning!he e l e c t r i c a l 1
instal
Motor cable aroundinq: Use a separate grounding cable (3) if the conductivity of
the cable shield is < 50% of the conductivity of the phase conductor and there is
no symmetrically constructed grounding conductor in the cable (see Planning the
electrical installation: Selecting the power cables).
360 degrees grounding is required at the cabinet entry in first environment
installations. First environment EMC compliance is defined in chapter Technical
data.
Note: If there is a symmetrically constructed grounding conductor in the motor
cable in addition to the conductive shield, connect the grounding conductor to the
grounding terminal at the drive and motor ends.
Note: Do not use an asymmetrically constructed motor cable. Connecting its
fourth conductor at the motor end increases bearing currents and causes extra
wear.
Electrical installation
Connect the phase conductors of the mains cable to the U1, V1 and W1 terminals
and the phase conductors of the motor cable to the U2, V2 and W2 terminals.
Strip the conductor ends as follows to fit them inside the power cable connection
terminals.
Note: Lead the unstripped cable as close to the terminals as possible. All
unstripped parts must be protected against contact.
Frame size Stripping length
rnm I rn~
donductLe gaskets
or ground the cable by twisting the shield as follows: flattened width > 115 - length.
Electricalinstallation
Frame sizes R2 to R4
.-
U1 v1 W1 UDC+
R- R+ UDC- U2 V2 W2
PE
Frame size R5
Electrical installation
Frame size R6: Cable lug installation [I6 to 70 mm2 (6 lo 2/0 AWG) cables]
- . .
UDC+
U1 V1 W1 R- R+ UDC- U2 V2 W2 Remove the screw terminals.
Faslen the cable lugs to the
remaining bolts with M10
nuts.
Electrical installation
Frame size R6: Cable terminal installation 195 to 185 mm2 (310 to 2x410 AWG)
cables]
UDC+
Electrical installation
Removal of the shroud with a screw driver:
Frame size R6
Cover the power cable terminals as follows:
1. Cut holes for the installed cables into the clear plastic shroud in cable lug
installations.
2. Press the shroud onto the terminals.
Removal of the shroud by lifting up with a screw driver from the corner:
Warning sticker
There are warning stickers in different languages inside the packing box of the drive
Attach a warning sticker in the language of your choice onto the plastic skeleton
above the power cable terminals.
Electrical jnsfaRation
Connecting the control cables
Connect the control cables as described b e l o k Connect the conductors to the
appropriate detachable terminals of the RMIO board [see chapter Motor control and
I/O board (RMIO)]. Tighten the screws to secure the connection.
Terminals
Location of terminals vary depending on the drive frame size
Frame sizes R2 to R4
The control cable connection terminals are
exposed when the control panel mounling platiorm
is turned aside by pulling lhis knob. Be careful, do Oelachable connectian terminals (pull up)
not use excess force when pulling.
39 for conlrol panel cable
(control panel is an option)
Electrical instaffation
Frame sizes R5 and R6
./- -.
7
Control cable
- DDCS communication option module 3: RDCO
grounding: see
Section 360 A Place the warning sticker here
degrees
grounding l ~ e l a c h a b l connection
e terminals (pull up)
Electrical installation
360 degrees grounding
Electricalinsfallalion
C a b l i n g of 110 a n d f i e l d b u s m o d u l e s
As short as possible
Electrical installation
Installation of optional modules and PC
The optional module (such as fieldbus adapter, 110 extension module and the pulse
encoder interface) is inserted in the optional module slot of the RMlO board (see
section Connecting the control cables) and fixed with two screws. See the
appropriate optional module manual for cable connections.
External +24 V power supply for the RMlO board via terminal X34
This section describes how to connect an external +24 V power supply for the RMlO
board via terminal X34. For the current consumption of the RMlO board, see chapter
Motor control and I/O board (RMIO).
Note: External power is easier to supply to the RMlO board via terminal X23, see
chapter Motor control and I/O board (RMIO).
Parameter settings
In Standard Control program, set parameter 16.09 CTRL BOARD SUPPLY to
EXTERNAL 24V if the RMlO board is powered from an external supply.
Electricalinstallation
Frame sizes R2 lo R4 Frame sizes R5 and R6
Electrical installabon
'-RMlOboard. 7 r 'Rm-board - 1
1 2 3 ,
L i + - A
Electrical installation
Prevention of Unexpected Start, AGPS board
- -
WARNING! Dangerous voltages can be present on the AGPS board even when the
115...230 V supply is switched off. Follow the Safety instructions on the first pages of
this manual and the instruction in this section when working on the AGPS board.
Make sure that the drive i s disconnected from the mains (input power) and the
115...230 V source for the AGPS board i s switched off during installation and
maintenance. If the drive i s already connected t o the mains, wait for 5 m i n after
disconnecting mains power.
Electricalinstallation : . . . ..
.i :.
Note: Location of the X41 terminal block varies according to the drive frame size.
see page 67.
Note: Maximum cable length between AGPS terminal block X2 and drive terminal
block is restricted to 10 m.
For technical data see section AGPS-11C in chapter Technical data.
Electrical installation
Electrical installation
Motor control and 110 board (RMIO)
WARNING! If the RMIO board is supplied from an external power source via
terminal X34, the loose end of the cable removed from the RMlO board terminal
must be secured mechanically to a location where it cannot come into contact with
electrical parts. If the screw terminal plug of the cable is removed, the wire ends
must be individually insulated.
Parameter settings
In Standard Control Program, set parameter 16.09 CTRL BOARD SUPPLY to
EXTERNAL 24V if the RMlO board is powered from an external supply.
Constant speed 3