Professional Documents
Culture Documents
Application Note
3 Phase Inverter Design with Rapid Control
Prototyping using PSIM and Typhoon-HIL
June 2017
1 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
2 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
3 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Figure 39 - Successfully connected DSP 'scope' displaying the 3 phase feedback signals ........... 28
Figure 40 - SCI out element implementation................................................................................ 29
Figure 41 - Unscaled analog input singals..................................................................................... 30
Figure 42 - Ia_fb with HIL 1 A per Vdac......................................................................................... 31
Figure 43 - Ia_fb with HIL 10 A per Vdac....................................................................................... 31
Figure 44 - ADC signal before software offset and scaling ........................................................... 32
Figure 45 - HIL simulation signal to be matched .......................................................................... 32
Figure 46 - Adjusting the DSP scale for sensitive adjustments ..................................................... 33
Figure 47 - Adjusting the offset with the DSP scope .................................................................... 33
Figure 48 - Analog feedback signal with proper gain and offset .................................................. 34
Figure 49 - 3 Properly scaled feedback signals ............................................................................. 35
Figure 50 - AC sweep simulation................................................................................................... 36
Figure 51 - AC Sweep control ........................................................................................................ 36
Figure 52 - AC probe element ....................................................................................................... 36
Figure 53 - Open loop frequency response .................................................................................. 37
Figure 54 - SmartCtrl Design space ............................................................................................... 38
Figure 55 - Closed loop dq control ................................................................................................ 39
Figure 56 - HIL Waveforms with closed loop simulation .............................................................. 40
Figure 57 - A01 & A02 channels probed with external oscilloscope ............................................ 40
Figure 58 - DSP scope waveforms of closed loop HIL simulation ................................................. 41
Figure 59 - Offline simulation step response in Iq_ref ................................................................. 41
Figure 60 - Real-time simulation of step response in Iq_ref ....................................................... 41
Figure 61 - Over/under voltage protection .................................................................................. 43
Figure 62 - C block being used to define the overcurrent fault response .................................... 44
Figure 63- Heatsink over temperature detection ......................................................................... 44
Figure 64 - ADC & HIL setup for DC bus detection and heatsink temperature ............................ 44
Figure 65 - Typhoon HIL three-phase inverter schematic with fault-testing elements............... 45
Figure 66 - Inverter View panel for fault and system simulation ................................................. 46
Figure 67 - Contactor control settings .......................................................................................... 46
Figure 68 - HIL simulation of line to line fault with control clearing ............................................ 46
Figure 69 - Control response to DC bus overvoltage .................................................................... 47
Figure 70 - Control response to heatsink over-temperature with Iq_ref reduction .................... 47
4 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Introduction
This application note will introduce how to implement a 3 phase voltage source inverter with dq
control and implement on a TI C2000 MCU (TMS320F28335). Verification of the control algorithm
will be performed with a Typhoon HIL real-time Hardware-In-the-Loop simulation. The concept of
rapid control prototyping, RCP, will be used to test and verify the operation of the inverter. Rapid
control prototyping is made possible by combining automated embedded code generation from
PSIM with a high fidelity real-time hardware simulation from Typhoon–HIL. A properly defined RCP
platform should allow the question “Does it work?” to be answered in real-time and if it does not
work a solution can be quickly implemented and tested again. The workflow for sequential
implementation and testing is as follows:
The open loop section will cover the initial PSIM schematic setup and open loop code generation.
The most important part of this section is the setup of the analog feedback signals while the
inverter is working in open loop.
The close loop section introduces a method for designing stable PI controllers for Id and Iq in the z-
domain. These controllers are then implemented with PSIM and tested with the HIL system
The final part of this document covers some preliminary fault handling and operational scenarios. In
this section the concepts and methods used can be applied to a broad range of test scenarios.
These methods should act as the starting point for continued analysis and design iteration of the
inverter from a proof of concept to a robust field ready design.
Offline simulation and embedded code PSIM Professional with Digital control,
generation platform (required): SimCoder & F28335 target
Control loop design software (optional): SmartCtrl Pro
Hardware-in-the-Loop simulation platform: HIL 402, 600, or 602*
*The HIL 602 is used in this document and was used to generate the files. All of the HIL simulations
performed can be done with the 402, 600, or 602 unit.
5 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
In this section an open loop 3 phase voltage source inverter will be simulated with PSIM. Once open
loop operation is confirmed the simulation will be setup to generate code to program an F28335
MCU from Texas Instruments. The operation of the open loop code will be confirmed with a real-
time Hardware-In-the-Loop simulation using Typhoon HIL.
6 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
6 ideal switches
Models an ideal switch the “MOSFET”
variant is being used which can model
an Rdson conduction loss. The ideal bi-
directional, ideal MOSFET, and ideal
IGBT are equivalent apart from how
conduction losses are modelled.
7 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
8 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Comparator element
Compares the modulation waveform
with the carrier waveform to get the
gating signals for the switches
1/(Fsw*100)
9 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Simulation results
Figure 6 - Open loop Carrier and modulation waveforms Figure 7 - Open loop carrier and modulation waveform (close
(wide view) view)
Figures 5 – 7, show the open loop PSIM simulation results. Figure 5 shows three balanced
currents compared with the modulation waveform for phase A. Figure 6 and 7 shows how the
modulation waveform, Vma, is being compared with the carrier waveform, V_car.
10 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
There are a few changes between the simple open loop simulation from the previous section
and the one that is code generation compatible. The way the device gating signals are
generated has changed and there are changes to be made in the simulation control element.
The gating waveforms are now generated by a 3-ph PWM (F28335) control block.
The 3-ph PWM control block is fed with the modulation waveform and has an internal carrier
waveform setup.
11 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
The default values of the 3-phase PWM block which defines a carrier waveform of Vmax = 1V
Vmin = 1V @ 10KHz with a duty cycle of 50% can be used. The PWM signals will output on:
A detailed discussion of the settings can be found in the SimCoder user manual and a brief
explanation can be read by clicking the components “Help”. This setting are important as the
output pins from the MCU will need to be mapped to the proper input pins of the HIL and
eventually the real hardware.
There is a setting to define the deadband; however, this block will not implement deadband
during simulation as this can impact simulation time-step requirements and can lead to slow
simulations and it is not necessary for a system level simulation. If you are interested in
simulating deadband, example circuits exist in the PSIM examples folder.
The “SimCoder” tab of simulation control is now setup to generate code for the F28335
processor, figure 11.
12 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
The only setting that needs to be selected is that the CPU version matches the hardware that
you will be programming, the Delfino F28335 is assumed. The F28335 is a floating point
processor and floating point code will be generated. If a fixed point processor is used fixed
point code will be generated. Fixed point code generation is covered in a separate application
note.
13 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
In the folder that the schematic is saved in a new folder will be created with the schematic file
name and (C code) appended.
This folder contains the generated code and associated files required to program the target
MCU.
The generated files define a full Code Composer Studio Project that can be imported into CCS.
The *.c file contains the converted code from the simulation, the other files are generated by
PSIM and are used by CCS when compiling the *.out file that will be loaded to the target MCU.
14 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Figure 15 - Import Legacy CCSv3.3 project menu option Figure 16 - Legacy CCS project import file selection screen
15 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Click “Finish”. In your Project Explorer view you will see the
project files imported.
A warning will likely pop up mentioning a
missing path to “xdias” this can be ignored.
Important note: once the project is imported you do not need to repeat the process.
Generating code from PSIM from the original schematic will update the associated “*.c” file in
the imported project.
Target Configurations
The target configuration defines the processor and the connection method used to program it.
Defining the correct target configuration is critical for a successful upload of the compiled *.out
file to the target MCU. Thankfully, defining the proper configuration is a relatively easy task
covered in this section. The target configuration is the *.ccxml file in your CCS project.
16 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Use these settings to program a TMS320F28335 processor with XDS100v2 JTAG interface. The
XDS100v2 debug probe is the most common type as it is built onto most development kits
and later generation controlCARDs. There is an option to test the connection on the right.
17 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
The project is now ready to build and load onto the MCU. The default action of the “Debug”
button is to build a new “.out” file and to load it to the MCU. There is no need to clean or
rebuild the project.
18 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
The HIL power stage, “HIL 600 3 phase inverter.tse”, will be identical to the PSIM power stage.
At the moment we are only interested in the inverter connected to the upper three-phase load.
Contactors for load switching and fault simulation as well as the heat sink circuit will be
discussed later. There are four main components:
The only settings that need to be adjusted from the schematic are which digital input ports drive
the switches.
Figure 24 - Three phase inverter component switch mapping Figure 25 - HIL docking station PWM pin mapping
From Table 2 of TI Docking Station User Guide, t-ug009.pdf, the PWM signals of interest are
19 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
This circles back to the 3 Phase PWM settings discussed in figure 10, from the PSIM embedded code
generation schematic, as the mapping needs to match what the code is setup to drive.
The model is ready to be compiled and loaded to the HIL as is. Once the model is loaded the HIL
SCADA screen will load.
Figure 26 – HIL SCADA screen with voltage source setting for open loop simulation
Load the model settings file, “simple settings_inverter.runx”. This file sets the source as a DC source
with a value of 100V, and also it maps current signals IA, IB, and IC to analog outputs A01, A02, and
A03 respectively.
Additionally, for simulation visualization and providing stimulus in runtime, you need to load the
SCADA panel file, “3 Phase Inverter SCADA”.
To run the open loop simulation on the HIL, you will need to have successfully compiled and loaded
the three-phase inverter schematic, as well as the model and HIL SCADA settings. You will also need
to have successfully built the generated code project.
20 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
The figure 27 shows the test setup. An F28335 controlCARD is loaded in the TI docking station. A
JTAG XDS100v2 debug probe is visible at the bottom right connected via a ribbon cable to the JTAG
header. The TI docking station is interfaced with the Typhoon HIL 600 unit.
From CCS clicking the ‘debug’ button will build and load the .out file onto the DSP using the defined
target configuration parameters. Once loaded the debug session starts in the “pause” state.
Figure 28 - Shows the CCS Debug screen after a successful launch into pause state
21 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Figure 30 – Typhoon HIL phase current signals coming from Capture/Scope widget
22 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Figures 30 & 31 compare the HIL real-time simulation results with the PSIM simulation results. The
current ripple in both sense is comparable and the peak to peak values are both +/- 7.5 Amps.
23 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
24 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
The power stage has remained constant but the control stage has now changed drastically from the
simple open loop simulations. The most significant change being that the modulation waveform
that drive the inverter are being generated from dq reference frame values.
The theory behind the dq frame will not be covered in this document.
The F28335 ADC element setups the analog input channels. The side labeled A0, A1..B7 defines the
input side to the DSP from the analog conditioning circuits of the hardware. The side labelled D0,
D1… D15 represents the sampled and converted signal. On the hardware side an offset is being
applied of 1.65 volts as the raw current feedback signals are AC and the ADC will not accept
negative input signals. This offset is removed by individual offsets, offset_A, offset_B, & offset_C,
for each channel on the code side of the ADC element. The gain of the current feedback signals can
be adjusted individually with the Gain_A, Gain_B, & Gain_C control blocks. The real-time offset and
gain adjustment of the ADC channels is a critical debugging procedure that will be covered later in
this section.
25 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
In this circuit the ADC conversion is being triggered by the 3-phase PWM element. Figure 35 shows
the ADC setting, and figure 36 shows the settings from the PWM element.
Figure 35- ADC sampling settings Figure 36 - PWM settings for ADC conversion
The PWM settings show that the PWM timer will trigger the ADC group A with a trigger position at
the beginning of the period. The carrier wave starting low corresponds with the bottom side switch
switching on at the beginning of the period. More information about these settings can be found in
the PSIM SimCoder user manual.
This project makes use of the Serial Communications Interface, SCI, and the controlCARD has
jumper settings that need be properly configured. ‘SW1’ on the controlCARD needs be toggled
depending on your controlCARD rev and connection method. Please refer to the PSIM Tutorial –
“Using SCI for waveform monitoring” for further details.
Generate the code for this project and “legacy import” into CCS following the method describe
earlier you will have two projects defined in CCS now.
3_phase_inverter_open_lopp_code_gen_sci_comms.pjt is the file name that you will be looking for
during import.
As before the program will launch in the pause state you will need to hit the “Resume”
26 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
With 3_phase_inverter_open_lopp_code_gen_sci_comms running on the MCU and with the HIL 600
3 phase inverter running on the HIL unit the DSP oscilloscope utility will be used to monitor the
signals that the ADC has converted.
27 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Figure 39 - Successfully connected DSP 'scope' displaying the 3 phase feedback signals
28 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
freq Offset_C
Id_ref Gain_A
Iq_ref Gain_B
Offset_B Gain_C
Offset_A
29 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
The initial settings also define that 1 Amp = 1 Volt and that there is no offset applied to the signal.
With these initial settings we should observer the 3 phase feedback signals below with the DSP
Scope.
The waveforms should appear clipped at top and bottom and un-evenly offset with a negative peak
of -1.5V and a positive peak of 1.25V. It doesn’t matter if your waveforms match the figure 41, just
as long as there are three sinusoidal signals present. In the next few steps the signals will be
30 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Looking at phase A (Ia_fb) first we can see that the output signal is clipped, this means that the HIL
output scaling needs to be increased changing the scaling to 10 A per 1 Vdac will address this issue.
The difference can be seen in figures 42 & 43.
Changing the
Scaling from 1.0 A
per Vdac to 10 A
per Vdac.
Figure 42 - Ia_fb with HIL 1 A per Vdac Figure 43 - Ia_fb with HIL 10 A per Vdac
Increasing the scaling of the HIL outputs has addressed the signal clipping. The same change is
applied to all three HIL output settings These settings are saved as “scaled run settings.runx”.
31 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
This is a critical step, with real hardware the analog feedback of simple DC signals is usually
accomplished with a simple voltage divider circuit. AC signals need to be scaled and offset which is
typically accomplished with Op. Amp circuits. Each one of these Op. Amp circuits can exhibit slightly
different gains and offsets from the theoretical calculations as real components with tolerances
need to be used.
As observed in the example the ADC is currently displaying a sinusoidal signal with a negative offset.
The negative offset needs to be corrected so that the signal is centered on ‘0’ and the gain will be
adjusted so that the real “current” value is observed. The MCU needs to provide a signal that
matches what the HIL waveforms are.
Figure 44 - ADC signal before software offset and Figure 45 - HIL simulation signal to be matched
scaling
The raw MCU feedback signal shows a The HIL waveforms show a peak value of 7.44A
peak to peak ~500mA and a negative centered on 0. The DSP scope waveforms will be
offset. scaled to match the HIL waveforms.
Increase the scale of the DSP scope waveform to allow for more sensitive adjustments.
32 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
In the figure below the offset_A has been changed to 1.525 from 1.65 and the feedback signal is
33 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
now centered on ‘0’. The change required by your hardware will likely be slightly different.
With Gain_A adjusted the feedback signal now mirrors what the HIL simulation waveform is an
easy way to check if you have applied proper gain and offset is to insert the peak value into the
display offset and see if the waveform touches ‘0’.
34 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Use the ‘A’ parameters as the starting point for ‘B’ & ‘C’ and adjust as needed.
Figure 49 shows the three properly scaled feedback signals. The new offset and gain values are not
‘saved’ as the default values and you will need to replace the offset values in the schematic for the
next code generation cycle.
35 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
This simulation is setup to generate a frequency response for the open loop converter. A
perturbation is introduced into the open loop Iq reference with vsin1, the impact of the
perturbation is observed on the feedback value of Iq. PSIM will compare the gain and phase of the
open loop perturbation with the value observed at the ‘ac’ probe element, figure 52.
36 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
The parameters for the AC sweep are defined by AC Sweep m-sine element, figure 51. During the
AC sweep the m-sine element drives the vsin1 voltage source through the specified frequency
range. More information about the setup of the AC sweep is covered in the PSIM user manual in
and through various tutorial videos available online.
A critical part of the simulation setup for control design is the modelling of digital delay. The delay is
modelled with the addition of two elements the ZOH and the 1/Z blocks. The Zero Order Hold, ZOH,
is inserted after the current sense element, it is modelling the sampling impact of converting a
continuous time signal into a discrete time signal. The 1/Z or unit delay element is delaying the
input to the element by one sampling period which represents the delay of implementing a
controller on an MCU or DSP as the new PWM duty cycle can only be updated at the beginning of
the next timing pulse.
SmartCtrl is a graphical control loop tuning program, it works by combing the transfer function
of the plant, sensor, and controller together. The plant can be defined with a pre-defined
topology, a set of equations, or as in this case with a frequency response waveform file. With
SmartCtrl the control options are PI, Type 2, or a Type 3 controller.
37 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Once the initial design parameters have been input into SmartCtrl and design space resembling
Figure 54 should appear. The bode plots at left of figure 54 show the control to output or loop
gain plot (pink) and the open loop plant response (green). As the phase margin vs cross
frequency is manipulated in the solution space all of the plots will update.
A robust control design will have a large DC gain, adequate phase margin at the cross over
frequency, and strong attenuation of the switching frequency. All of these control parameters
are observed from the control to output (pink) bode plots. A large DC gain will ensure a fast
response, a phase margin of >40 degrees will ensure stability, and attenuation of the switching
>-20 dB will provide good noise immunity.
From SmartCtrl the control parameters for a cross frequency of 500Hz with a phase margin of
40 degrees for a PI controller are below:
Kp 238.716m
Ti 498.313u
The control parameters from above describe an s-domain transfer function and will need to be
converted to the z-domain with backwards Euler, bilinear, or some other conversion method. The
PSIM element “Digital PI Controller” takes s-domain coefficients and automatically converts to z-
domain with backwards Euler.
38 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Open the schematic, ‘3 phase inverter close loop code.psimsch’. This schematic features a
parameter file which is defining simulation vs code generation parameters with conditional
logic to define which set of parameters to use based on the user’s needs. The control
coefficient will be uniform for all use cases. The code generation coefficients might be different
based on your Hardware/HIL systems, adjust the “gain” and “offset” settings for the code gen
based on the numbers that were determined in section “Tuning the ADC feedback”
Generate the code and import to CCS using the steps outlined previously. In the parameter file
ensure that gen_flag = 0, as the state of this flag determines if offsets and gains for code
generation or for simulation will be used. The reason for the difference between the two sets of
parameters is dependent on the scaling of analog outputs from the HIL and how they are
interpreted and scaled by the hardware for the MCU analog inputs. This scaling is covered in
the HIL user guides.
With the HIL power stage running simply start the debug of the MCU, the three phase currents
39 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
should be equal and balanced as observed in the Capture/Scope widget, figure 56. The current
values can also be externally observed by probing the analog feedback test points for A01, A02, &
A03, figure 57.
Using an external oscilloscope channels A01 & A02 are probed and the analog feedback waveforms
generated by the HIL can be observed. In figure 57, we can see that the HIL scaling output is
showing +/- 0.8V which corresponds with the output being scaled 10A per 1 V in the initial settings.
40 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
In figures 59 & 60, the offline simulation of a step response is compared with the real-time
simulation of the same step. In both instances the Iq_ref is changed to 8 Amps and the observing
Iq_fb signal is monitored.
41 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
To recreate this real-time simulation, you will need to use the trigger options in the DSP
oscilloscope interface, the settings are in the bottom right of figure 60.
Trigger on Iq_fb
Select trigger ‘on’
Rising edge mode
Check box “Once” is enabled
Level = 5
With the trigger setup, simply change the Iq_ref from ‘4’ to ‘8’ and the scope will trigger on the
rising edge.
42 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
This section covers the PSIM schematic “3 phase inverter close loop code_protection.psimch”. This
simulation starts to implement some rudimentary protection and fault response for the inverter.
There are three operating conditions that prompt the protections to activate.
In figure 61 the DC bus feedback voltage is compared with pre-defined voltage thresholds, if the
limit is exceed it stops the PWM timer. The stop/start PWM blocks are active high.
43 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
In figure 62, a simplified c block is being used to define the over current latch state. The
overcurrent state is reset on the rising edge of ‘cur_rst’.
In figure 63, the heatsink over temperature detection is defined with a simplified c block. In this
case, when the heatsink cross a pre-defined threshold the Iq_ref is reduced by 25%.
For simulation purposes, the DC bus and heatsink analog signals are routed to pins B0 and B1 of
the ADC. When the code is generated and run in a real-time simulation with the HIL assigning
control signals to AO9 and AO10 will correspond with these two analog feedback signals.
Figure 64 - ADC & HIL setup for DC bus detection and heatsink temperature
44 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
The HIL model HIL 600 3 phase inverter.tse needs to be loaded and compiled. This HIL model
has contactors setup to switch between loads, introduce line faults, & has an external source
defining the heatsink temperature.
As shown in figure 65, both line-to-line and line-to-ground faults are implemented. The “Load
Select” is a triple pole double throw contactor that switches between two three-phase RL loads.
The voltage source labelled ‘heatsink_temp’ will serve as a proxy for the heatsink temperature
feedback circuit. These components will create the over current and over temperature faults
that will be cleared by the code created by the elements in figure 62 and 63.
Compile and load the schematic to your HIL system, once loaded open the SCADA panel ‘3
Phase Inverter SCADA.cus’. Figure 66, has built in widgets to introduce the faults, switching
loads, and monitoring the system status easier to perform.
45 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Generate code for “3 phase inverter close loop code_protection.psimch” and load it to the
MCU. Also ensure that the proper HIL simulation is loaded.
Overcurrent fault
The line-to-line fault is simulated by closing contactor “Fault A to B”. It is important that the
contactor has the “SW Control” enabled as in figure 67. This checkbox ensures that HIL SCADA
is in charge of controlling the contactor.
46 www.powersimtech.com
3 Phase Inverter Design and verification with RCP
Overvoltage/Undervoltage fault
Figure 69 shows the response to an overvoltage condition, to trigger this condition the source
Vs1 was set to 155V which exceeds the 150V limit defined in figure 61.
Figure 70, shows the response to the heatsink temperature hitting 150 dC. This achieved by
changing the source heatsink_temp to 150.
The fault scenarios presented are just a few of the various scenarios that could be encountered
by a product in the field. Other scenarios could include maximum power limits, frequency
operating range, etc. for each scenario introducing the fault in PSIM or with the Typhoon HIL
allows the designer to understand the characteristics of the fault and then the best method to
respond. The solution can then be implemented and tested.
47 www.powersimtech.com