Name Plate Details of 220 KV Uravakonda Twin MooseFeeder-1(Circuit Breaker):-

DOC:-21-03-2017
Make:- Crompton Greaves Limited
SR.No:- 47002C
Type:- 200-SFM-50AA
Rated Lightning Impulse withstand voltage:- 1050 KVP
Rated Short Circuit Breaking Current:- 50 KA
First Pole to clear Factor:- 1.5
Motor Voltage:- 230 V Ac
Rated duration of short circuit current:- 50 KA/3 Sec
Rated Line Charging Breaking current:- 125 A
Gas Weight:- 18 Kg
Rated short circuit making current:- 125 KA
Rated Voltage:- 245 KV
Rated Frequency:- 50 HZ
Rated Normal Current:- 3150 A
Rated Closing Voltage:- 220 V,DC
Rated Opening Voltage:- 220 V,DC
Rated Sf6 Gas Pressure:- 6.5 kg/cm^2g(at 20^c)
Rated voltage& frequency for Aux. Circuit:- 1-ph 240V AC,50HZ
Total weight with gas:- 3750 kg
Rated Operating Sequence:- 0-0.3s-CO-3Min-CO
Year of MFG:- 2016
STD.IEC:- 62271-100
Customer:- M/S SPR Constructions
PO.No:- SPR/APTRANSCO/APT-19/14-15/13,Date: 28-09-2015
Name Plate Details of 220 KV Uravakonda Twin Moose Feeder-1 (Current Transformer)R-Phase:-
Make:-
S.No:-
Standard:-
Frequency:-
Rated STC:-
Idy:-
Quantity of oil:- 315 Lts+_15%(Appx), Wt of CT:- 900 kg+_15%(Appx), Rated Thermal Current:- 1920 A
Highest system voltage:-
Rated System Voltage:-
Type Designation:-
Insulation Level:-
Year of MFG:-
Client:-
PO.No:-

CORE
Ratio:-

Rated Burden(VA)
Accuracy Class:-
ISF-ALF

Knee Point Voltage:-

Resistance aat 75^C (Ohms)

MAG> Current (MA) at VK

Ratio:-

1600/1
1200/1
800/1
ate Details of 220 KV Uravakonda Twin Moose Feeder-1 (Current Transformer)R-Phase:-
TOSHIBA
511330
IS:2705:1992
50 HZ
40KA rms/1 Sec
100 Kap
ts+_15%(Appx), Wt of CT:- 900 kg+_15%(Appx), Rated Thermal Current:- 1920 A
245 KV
220 KV
DT 245
460/1050 KV/kvp
2015
APTRANSCO
185/CPT 150/SE-PM/APT-e-19/2014/Borampalli SS/RM.No:- 4283/D.No; 23-12-2014

CORE
Primary(A)
Secondary(A)
Rated Burden(VA)
Accuracy Class:-
ISF-ALF

Knee Point Voltage:-

Resistance aat 75^C (Ohms)

MAG> Current (MA) at VK

Primary Connection:-

P1-P2
P1-P2
P1-P2
CORE-1,2,4 & 5 CORE-3
1600-1200-800 1600-1200-800
1 1
- 20
PS 0.2
- <5/-
>_1200 AT 1200/1A -
>_800 AT 800/1A -
>_6 at 1200/1A -
<_4at 800/1A -
<_ 30 at 1200/1A -
<_45 at 800/1A -

Secondary Connection:-
CORE-1 CORE-2 CORE-3 CORE-4 CORE-5
1S1-1S4 2S1-2S4 3S1-3S4 4S1-4S4 5S1-5S4
1S1-1S3 2S1-2S3 3S1-3S3 4S1-4S3 5S1-5S3
1S1-1S2 2S1-2S2 3S1-3S2 4S1-4S2 5S1-5S2
Name Plate Details of 220 KV Uravakonda Twin Moose Feeder-1 (Current Transformer)Y-Phase:-
Make:-
S.No:-
Standard:-
Frequency:-
Rated STC:-
Idy:-
Quantity of oil:- 315 Lts+_15%(Appx), Wt of CT:- 900 kg+_15%(Appx), Rated Thermal Current:- 1920 A
Highest system voltage:-
Rated System Voltage:-
Type Designation:-
Insulation Level:-
Year of MFG:-
Client:-
PO.No:-

CORE
Ratio:-

Rated Burden(VA)
Accuracy Class:-
ISF-ALF

Knee Point Voltage:-

Resistance aat 75^C (Ohms)

MAG> Current (MA) at VK

Ratio:-

1600/1
1200/1
800/1
te Details of 220 KV Uravakonda Twin Moose Feeder-1 (Current Transformer)Y-Phase:-
TOSHIBA
511318
IS:2705:1992
50 HZ
40KA rms/1 Sec
100 Kap
+_15%(Appx), Wt of CT:- 900 kg+_15%(Appx), Rated Thermal Current:- 1920 A
245 KV
220 KV
DT 245
460/1050 KV/kvp
2015
APTRANSCO
185/CPT 150/SE-PM/APT-e-19/2014/Borampalli SS/RM.No:- 4283/D.No; 23-12-2014

CORE
Primary(A)
Secondary(A)
Rated Burden(VA)
Accuracy Class:-
ISF-ALF

Knee Point Voltage:-

Resistance aat 75^C (Ohms)

MAG> Current (MA) at VK

Primary Connection:-

P1-P2
P1-P2
P1-P2
CORE-1,2,4 & 5 CORE-3
1600-1200-800 1600-1200-800
1 1
- 20
PS 0.2
- <5/-
>_1200 AT 1200/1A -
>_800 AT 800/1A -
>_6 at 1200/1A -
<_4at 800/1A -
<_ 30 at 1200/1A -
<_45 at 800/1A -

Secondary Connection:-
CORE-1 CORE-2 CORE-3 CORE-4 CORE-5
1S1-1S4 2S1-2S4 3S1-3S4 4S1-4S4 5S1-5S4
1S1-1S3 2S1-2S3 3S1-3S3 4S1-4S3 5S1-5S3
1S1-1S2 2S1-2S2 3S1-3S2 4S1-4S2 5S1-5S2
Name Plate Details of 220 KV Uravakonda Twin Moose Feeder-1 (Current Transformer)B-Phase:-
Make:-
S.No:-
Standard:-
Frequency:-
Rated STC:-
Idy:-
Quantity of oil:- 315 Lts+_15%(Appx), Wt of CT:- 900 kg+_15%(Appx), Rated Thermal Current:- 1920 A
Highest system voltage:-
Rated System Voltage:-
Type Designation:-
Insulation Level:-
Year of MFG:-
Client:-
PO.No:-

CORE
Ratio:-

Rated Burden(VA)
Accuracy Class:-
ISF-ALF

Knee Point Voltage:-

Resistance aat 75^C (Ohms)

MAG> Current (MA) at VK

Ratio:-

1600/1
1200/1
800/1
Plate Details of 220 KV Uravakonda Twin Moose Feeder-1 (Current Transformer)B-Phase:-
TOSHIBA
511322
IS:2705:1992
50 HZ
40KA rms/1 Sec
100 Kap
15 Lts+_15%(Appx), Wt of CT:- 900 kg+_15%(Appx), Rated Thermal Current:- 1920 A
245 KV
220 KV
DT 245
460/1050 KV/kvp
2015
APTRANSCO
185/CPT 150/SE-PM/APT-e-19/2014/Borampalli SS/RM.No:- 4283/D.No; 23-12-2014

CORE
Primary(A)
Secondary(A)
Rated Burden(VA)
Accuracy Class:-
ISF-ALF

Knee Point Voltage:-

Resistance aat 75^C (Ohms)

MAG> Current (MA) at VK

Primary Connection:-

P1-P2
P1-P2
P1-P2
CORE-1,2,4 & 5 CORE-3
1600-1200-800 1600-1200-800
1 1
- 20
PS 0.2
- <5/-
>_1200 AT 1200/1A -
>_800 AT 800/1A -
>_6 at 1200/1A -
<_4at 800/1A -
<_ 30 at 1200/1A -
<_45 at 800/1A -

Secondary Connection:-
CORE-1 CORE-2 CORE-3 CORE-4 CORE-5
1S1-1S4 2S1-2S4 3S1-3S4 4S1-4S4 5S1-5S4
1S1-1S3 2S1-2S3 3S1-3S3 4S1-4S3 5S1-5S3
1S1-1S2 2S1-2S2 3S1-3S2 4S1-4S2 5S1-5S2
Name Plate Details of 220 KV Uravakonda Twin Moose-1 (Capacitive Voltage Transformer)R-Phase:-
DOC:-21-03-2017
Make:- Crompton Greaves Limited
SR.NO:- SH-60043
Type:- CVE: 245/1050/50
STD:- IS:3156-92, IS: 9348-98, IEC: 186-87,IEC:358-90
S.O:- SPRB 2190/10
Year:- 2016
HSV:- 245 KV
Frequency:- 50 HZ
Insulation Level:- 460 KV/1050 kvp
VF:- 1.2 CoNT/1.5-30 Sec
Equi.Capacitance:- 4400+1C%,-5% PF
Total SIM. Burden/Class:- 50VA/0.2
Thermal Output:- 300 VA
Capacitor Oil:- 30+_10% Kg
EMU. Oil:- 65+_10%Kg
Total Weight:- 575+_10Kg
Customer:- SPR Constructions. A/C APTRANSCO
Name Plate Details of 220 KV Uravakonda Twin Moose-1 (Capacitive Voltage Transformer)Y-Phase:-
DOC:-21-03-2017
Make:- Crompton Greaves Limited
SR.NO:- SH-60044
Type:- CVE: 245/1050/50
STD:- IS:3156-92, IS: 9348-98, IEC: 186-87,IEC:358-90
S.O:- SPRB 2190/10
Year:- 2016
HSV:- 245 KV
Frequency:- 50 HZ
Insulation Level:- 460 KV/1050 kvp
VF:- 1.2 CoNT/1.5-30 Sec
Equi.Capacitance:- 4400+1C%,-5% PF
Total SIM. Burden/Class:- 50VA/0.2
Thermal Output:- 300 VA
Capacitor Oil:- 30+_10% Kg
EMU. Oil:- 65+_10%Kg
Total Weight:- 575+_10Kg
Customer:- SPR Constructions. A/C APTRANSCO
Name Plate Details of 220 KV Uravakonda Twin Moose-1 (Capacitive Voltage Transformer)B-Phase:-
DOC:-21-03-2017
Make:- Crompton Greaves Limited
SR.NO:- SH-60045
Type:- CVE: 245/1050/50
STD:- IS:3156-92, IS: 9348-98, IEC: 186-87,IEC:358-90
S.O:- SPRB 2190/10
Year:- 2016
HSV:- 245 KV
Frequency:- 50 HZ
Insulation Level:- 460 KV/1050 kvp
VF:- 1.2 CoNT/1.5-30 Sec
Equi.Capacitance:- 4400+1C%,-5% PF
Total SIM. Burden/Class:- 50VA/0.2
Thermal Output:- 300 VA
Capacitor Oil:- 30+_10% Kg
EMU. Oil:- 65+_10%Kg
Total Weight:- 575+_10Kg
Customer:- SPR Constructions. A/C APTRANSCO