You are on page 1of 10

A brand of the

FP100 ®

THE FIRE RESISTANT SOLUTION FOR STEEL CONDUIT

Certificate No 077c, 077p

CABLE DESCRIPTION

Conductor Performance Standards


Plain annealed copper stranded (class 2) conductor.
> 450/750 V and 600/1000 V
> BS 6387:1994 Cat C (950±40°C for 180 mins)
> BS 6387:1994 Cat W (650±40°C for 30 mins)
Insulation > BS 6387:1994 Cat Z (950±40°C for 15 mins)
> EN 50267-2-2:1999
Mineral ceramic (Mica/Glass) fire resistant tape. 90°C high performance > EN 61034-2:2005
cross linked mineral filled insulation. > IEC 60331-21:1999
> Use in screwed steel conduit to achieve f ire rating
Key Applications > LPCB Approved
> Low smoke, zero halogen, flame retardant
> Essential safety circuits where the cable is protected by metal
conduit.
> May be used for emergency lighting, fire alarm systems not requiring
Core identification
a twisted cable or other essential services.
FIRE RESISTANT CABLES o red
o grey
o brown
o blue
o black o yellow
green/yellow
LOW
o orange VOLTAGE

Other core colours available on request


600/1000 V l *

FP100®
Ref:FP100/12/2017

Tem peratureRange
Tempreture Range Bending Radi
Bending us
Radius M echanicalimpact
Mechanical im pact Fi
re Per
Fire form ance
performance Flexibility
Flexibility HalogenFree
Halogen Free LowSmoke
Low Sm okeEmissions
Em issions FireResistant
Fire Resistant
-25
-25 tto
o +90ºC≠
+90°C up to
up to 8mm
8m m di am eterrr=4D
diameter =4D Requires pr
Requires otection
rotection BSEN60332-1-2
BS EN 60332-1-2 Sem i-flexible
Semi-flexible BSEN50267-2-1
BS EN 50267-2-1 BSEN61034-2
BS EN 61034-2 IEC 60331-21
IEC 60331-21
above 9mm
above 8m m di am eterrr=6D
diameter =6D BS6387
BS CategoryCWZ
6387 Category CW Z*
EN50200PH120*
EN50200 PH120*
BS8434-2 120m in*
*W hen tested in SteelConduit
Nominal Approximate Approximate Maximum Short Current Current Volt drop Volt drop Volt drop
cross overall cable conductor circuit rating rating DC Single Three
sectional diameter weight resistance rating DC or single Three phase AC phase AC
area at 20°C (1 sec) phase AC phase AC

mm2 mm kg/km Ω/km Amps Amps Amps mV/A/m mV/A/m mV/A/m

Single Core
1 .5* 3.5 26 12.1 215 23 20 31 31 27
2.5* 4.1 38 7.41 360 31 28 19 19 16
4* 4.6 54 4.61 570 42 37 12 12 10
6* 5.2 75 3.08 860 54 48 7.9 7.9 6.8
10* 6.6 120 1.83 1425 75 66 4.7 4.7 4
16 7.7 180 1.15 2275 100 88 2.9 2.9 2.5
25 9.0 270 0.727 3375 133 117 1.85 1.9 1.65
35 10.0 360 0.524 5000 164 144 1.35 1.35 1.15
50 11.7 490 0.387 7150 198 175 0.99 1.05 0.9
70 13.2 680 0.268 10000 253 222 0.68 0.75 0.65
95 15.3 940 0.193 13575 306 269 0.49 0.58 0.5
120 16.8 1160 0.153 17150 354 312 0.39 0.48 0.42
150 18.7 1440 0.124 21450 393 342 0.32 0.43 0.37
185 20.8 1800 0.0991 26450 449 384 0.25 0.37 0.32
240 23.5 2350 0.0754 34325 528 450 0.19 0.33 0.29
300 27.3 3000 0.0601 42925 603 514 0.155 0.31 0.27
400 32.5 3970 0.0470 57225 683 584 0.120 0.29 0.25
500 36.0 4980 0.0366 71525 783 666 0.093 0.28 0.24
630 40.0 6340 0.0283 90125 900 764 0.072 0.27 0.23

Notes to table
> * Sizes 1.5 - 10mm2 are rated at 450/750V.
> Installation methods for current rating “Enclosed in conduit on a wall or in trunking” in accordance with BS7671/IEE Wiring Regulations.
> Minimum recommended installation temperature -5°C.
> The tabulated ratings are based upon a 30°C ambient temperature at 90°C operating temperature.
> For other ambient temperatures or where several circuits are grouped together, the following rating factors should be applied.

Temperature ratings factor


Ambient Temperature°C 25 30 35 40 45 50 55 60

Rating factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71
Rating Factors for Groupings
Number of circuits 2 3 4 5 6 7 8 9
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50

Sales enquiries Overseas sales enquiries


Tel: 0845 767 8345 Tel: +44 (0) 23 8029 5481
Fax: 023 8029 5465 Fax: +44 (0) 23 8029 5465

UK Technical helpline Overseas technical


Tel: 0845 767 8345 Tel: +44 (0) 23 8029 5481
Fax: 023 8029 5002 Fax: +44 (0) 23 8029 5002

Prysmian Cables & Systems Limited Information hotline


Chickenhall Lane Tel: +44 (0) 23 8029 5029
Eastleigh Fax: +44 (0) 23 8029 5437
Hampshire
SO50 6YU
United Kingdom
www.prysmiangroup.co.uk
Ref: FP100/12/2017

For further information please


see our dedicated FP Cables website:
www.fpcables.co.uk A brand of the
Certificate No:

017/004/343
Issue No: 1

Certificate of Product Approval

Licensee:
Prysmian Cables & Systems Ltd
Chickenhall Lane, Eastleigh, SO50 6YU, Hampshire, United Kingdom

Factory:
Chickenhall Lane, Eastleigh, SO50 6YU, Hampshire, United Kingdom

Standard:
BS 8592:2016

Description:
Single core non-sheathed fire resistant cables with thermosetting insulation and having low
emission of smoke and corrosive gases when affected by fire

Details:
These cables conform to BS 8592, and by reference, conform to the appropriate
requirements of BS EN 60228, BS EN 60332-1-2, BS EN61034-2, BS EN 60754-1 and IEC
60331-3. Additionally tested to BS 8434-2:2003+A2:2009 and BS EN 50200:2015 PH120
(tests conducted in steel conduit). These cables have a rated voltage of 450/750V

Materials:
Insulation EI 5, Sheath None

Brand Name:
FP100

Origin Mark:
PRYSMIAN (B) OR (B) PRYSMIAN

Permissible Approval Marks:

Signed for and on behalf of the British Approvals


Service for Cables

Date: 17/11/2020

Date of original issue: 04/11/2020 0004

Check BASEC website to verify validity.


Page 1 of 2
BASEC, Presley House, Presley Way, Milton Keynes, MK8 0ES,
Expiry date:
Registered in England No. 1150237, Tel: +44(0)1908267300
Email: mail@basec.org.uk, Web: www.basec.org.uk 11/08/2023
Certificate No:

017/004/343
Issue No: 1

Type(s) and Range(s) of Approval

Table / Code Conductor Range of Min Nominal Max Nominal


Clause Designation Class Cores Size -sqmm Size - sqmm
2 N/A Class 2 1 1.5 70

Signed for and on behalf of the British Approvals


Service for Cables

Date: 17/11/2020

Date of original issue: 04/11/2020 0004

Check BASEC website to verify validity.


Page 2 of 2
BASEC, Presley House, Presley Way, Milton Keynes, MK8 0ES,
Expiry date:
Registered in England No. 1150237, Tel: +44(0)1908267300
Email: mail@basec.org.uk, Web: www.basec.org.uk 11/08/2023
Certificate of Product Approval
Certificate Number: 077p Issue: 04

PRYSMIAN CABLE & SYSTEMS LIMITED


Chickenhall Lane
Bishopstoke
Eastleigh
Hants
SO50 6YU
United Kingdom

is authorised to use the LPCB mark in association with the product(s) listed in this certificate and appendix
having complied with the requirements of the standard(s) detailed below:

Product(s) Standard(s) (see Appendix for details)


Cable Types as listed below: BS 6387:2013 (Category CWZ)
FP100 LSOH EN 50267-2-1:1999
See Certificate Appendix for details EN 61034-2:2005
IEC 60331-21:1999

This Certificate is maintained and held in force through regular surveillance activities and subject to the
corresponding ISO 9001 Certificate being maintained.

David Hoare 16 September 2014 13 May 2013


Signed for LPCB Certification Scheme Manager Date of Issue Date of First issue

This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX
T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: enquiries@breglobal.com

BF1345 Rev. 0.2 Page 1 of 3 © BRE Global Ltd, 2014


Appendix to Certificate No: 077p Issue: 04
PRYSMIAN CABLE & SYSTEMS LIMITED

LPCB Ref.
Product name
No.

FP100 LSOH 077p/01

Nominal csa of
Core Construction BS 6387 EN 50267-2-1 EN 61034-2 IEC 60331-21
conductor (mm2)

1.5 One(1) C,W,Z(2,3) <0.5% HCI >60% Complies(4)

2.5 One(1) C,W,Z(2,3) <0.5% HCI >60% Complies(4)

4.0 One(1) C,W,Z(2,3) <0.5% HCI >60% Complies(4)

6.0 One(1) C,W,Z(2,3) <0.5% HCI >60% Complies(4)

10 One(1) C,W,Z(2,3) <0.5% HCI >60% Complies(4)

Uo/U 600/1000 V
Notes:
1. Stranded conductor only.
2. Where a single cable is fitted in a conduit, only phase to earth voltage was applied.
3. To satisfy the requirements of BS 6387:2013, for Categories C,W,Z testing was conducted using a 20mm
stainless steel conduit as the other metallic element.
4. The FP100 LSOH cables met the requirements of IEC 60331-21:1999 when tested at a temperature of 950ºC
for a duration of 90mins + 15mins cool down, at a voltage rating of 600V.

Cross-Listed products and alternative branding are detailed on page 3.

This Certificate is maintained and held in force through regular surveillance activities and subject to the
corresponding ISO 9001 Certificate being maintained.

David Hoare 16 September 2014 13 May 2013


Signed for LPCB Certification Scheme Manager Date of Issue Date of First issue

This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX
T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: enquiries@breglobal.com

BF1345 Rev. 0.2 Page 2 of 3 © BRE Global Ltd, 2014


Appendix to Certificate No: 077p Issue: 04
PRYSMIAN CABLE & SYSTEMS LIMITED

LPCB Ref No. Model No. Alternative Model No. Labelled Distributors Cert/Ref No.

FP100 LSOH FT SIFER 950i OHLS


077p/01 Draka UK Ltd 1134g/01
1.5mm2 - 10mm2 1.5mm2 - 10mm2

This Certificate is maintained and held in force through regular surveillance activities and subject to the
corresponding ISO 9001 Certificate being maintained.

David Hoare 16 September 2014 13 May 2013


Signed for LPCB Certification Scheme Manager Date of Issue Date of First issue

This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX
T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: enquiries@breglobal.com

BF1345 Rev. 0.2 Page 3 of 3 © BRE Global Ltd, 2014


TO WHOM IT MAY CONCERN

For FP100 077p issue we received the response letter by FSD, we could
use on-line certificate to convince FSD officer.
 
 
 
http://www.redbooklive.com/search/displaycompany.jsp?sectiontype=1&
companyid=352&productgroupid=3074&sectionid=24&searchgrouptypei
d=13&searchgroupid=0&id=677 
3rd June, 2009

TO WHOM IT MAY CONCERN

Dear Customers,

Approval for Single Core Fire Resistant Cable – BS6387 C,W,Z


(FP100, FP300)

This letter is to advise you that our single core fire resistant cable, FP100 (insulated only)
and FP300 (insulated and sheathed) is accredited to BS6387 C,W,Z with LPCB certificate
077c and 077e respectively. This is also recognised by the Hong Kong Fire Services
Department.

Since single core fire resistant cable is not published with BS standard, both FP100 and
FP300 could not be type tested with BASEC. Therefore, there is no BASEC product
certificate available for single core fire resistant cable.

Both of the FP100 and FP300 are under the guarantee policy of Prysmian.

Yours sincerely,

Stephen Lam
Area Manager

Prysmian Hong Kong Holding Limited


Room 1010-11, Lu Plaza T (852) 2311 1554
2 Wing Yip Street F (852) 2366 1227
Kwun Tong
HONG KONG