Power Breakers, Contactors & Fuses 13-1

December 2008

Power Breakers,
Contactors & Fuses
Contents
Description Page
Power Circuit Breakers
Low Voltage Power Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-2
Magnum Family . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-2
Magnum DS Low Voltage Power Circuit Breakers . . . . . . . . . . . . . . . . 13-6
Magnum SB Insulated Case Circuit Breakers . . . . . . . . . . . . . . . . . . . . 13-8
Magnum IEC Rated Air Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . 13-10
Series NRX Low Voltage Power Circuit Breakers . . . . . . . . . . . . . . . . . 13-17
Medium Voltage Power Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-24
Medium Voltage Power Contactors
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-33
Product Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-38
Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-39
7.2 kV SL Series (160 – 400 Amperes) . . . . . . . . . . . . . . . . . . . . . . . . . . 13-41
7.2 kV SL Series (800 Amperes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-43
15 kV SL Series (250 Amperes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-44
Lug Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-45
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-46
Expulsion Fuses
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-48
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-50
Type RBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-51
13
Type RDB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-55
Type DBU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-59
Type DBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-62
Current Limiting Fuses
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-64
Type CLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-65
Type HLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-69
Type BHLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-71
Types BHLE and HCL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-72
Type CLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-76
Type CLPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-80
Type CX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-83
Type CXN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-85
Type DSL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-86
Type CXF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-87
Typical Fuse Mounting for Current Limiting Fuses . . . . . . . . . . . . . . . 13-88
Pricing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-89

Power Breakers, Contactors and Fuses Family

CA08101001E For more information visit: www.eaton.com


13-2 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Magnum Low Voltage Power Circuit Breakers Magnum IEC Air Circuit Breakers for IEC Rated Switchboards
■ Up to 690 Vac.
for Global Application
■ 200 to 6300 A continuous.
Magnum Low Voltage Power Circuit Breakers enable ■ 40 to 100 kA Icu/Ics.
comprehensive solutions to meet and exceed the unique
and wide-ranging requirements of today’s global power
distribution systems. This powerful circuit breaker offering
is designed for ultimate custom configuration and applica-
tion flexibility, with the needs of the power distribution
equipment user and the electrical equipment manufacturer
in mind.

Three Product Families


Magnum consists of three product families; each provides
specific ratings features and approvals to optimize perfor-
mance when applied in power distribution equipment
and custom enclosures:
Magnum DS Low Voltage Power Circuit Breakers for ANSI Magnum IEC Low Voltage Air Circuit Breaker Family
Rated Switchgear Applications
■ Up to 635 Vac.
■ 200 to 6000 A continuous.
■ 42 to 200 kA interrupting.

13

Magnum DS Low Voltage Power Circuit Breaker Family ANSI Rated


for Switchgear Applications

Magnum SB Low Voltage Insulated Case Circuit Breakers for


Switchboard Applications
■ Up to 635 Vac.
■ 200 to 5000 A continuous.
■ 50 to 150 kA interrupting.

Magnum SB Low Voltage Insulated Case Circuit Breaker Family UL


Rated for Switchboard Applications

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-3
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Features, Benefits and Functions


■ 200 kA interruption ratings with current limiting perfor-
mance and low current let-through to reduce damaging
energy to downstream equipment at high fault levels.
■ Withstand ratings up to 100 kA to maximize system
coordination and selectivity.
■ Three physical frame sizes (Narrow, Standard and
Double) to promote breaker application in compact
modular enclosures.
■ Continuous current ratings from 800 to 6300 A with 100%
rating at 40ºC and no derating on most ratings up to 50ºC.
■ Fixed breaker mounting configurations with horizontal
and optional vertical and front connected terminal
connections.
■ Drawout breaker mounting configurations with cassette
and optional safety shutters.
■ 3- and 4-pole breaker configurations.
■ Through-the-door design for human interface with the
breaker compartment door closed.
■ Two-step stored energy mechanism for manually and
electrical operated breakers.
■ Digitrip RMS Trip Unit family with four models, each
providing increasing levels of features:
❑ Basic to advanced programmable overcurrent
protection with communications, power metering and
power quality 13
❑ New Arcflash Reduction Maintenance Switch 
setting (enabled locally or remotely) to reduce arc flash
potential on downstream circuits during maintenance
Through-the-Door Design for Human Interface with the Breaker
operations Compartment Door Closed
■ Field installable accessories (UL approved) common
across the breaker frames and designed to be easily
installed in the field to service or modify the breaker at
the point of use.
■ Secondary terminal contacts mounted at the top front of
the breaker and away from the primary voltage areas for
improved safety and access. Finger-proof terminal blocks
accommodate ring-tongue or spade type terminals as
standard.

High Technology Microprocessor-Based Digitrip RMS 1150+ Trip


Units are Available With Advanced Features Like Programmable
Overcurrent Settings, Power Metering, Power Quality and
Communications

CA08101001E For more information visit: www.eaton.com


13-4 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Breaker Features on   
Front Cover
The controls and indicators are func-
tionally grouped on the breaker face-
plate to optimize the human interface,
visibility, and ease of use. For maxi- 
mum safety, a modern, through-the- 
door design permits access to the

breaker levering system, trip unit,
controls and indicators with the 
door closed.
 Mechanical Trip Flag Pop-out

Indicator (Optional) — Red
 Accessory Viewing Windows for:

❑ Shunt Trip Attachment (STA)


❑ Spring Release Device (SR)

❑ Undervoltage Release (UVR)


Device or Second STA

 Digitrip RMS Trip Unit (Model 520M
Shown) Protected by Clear Cover
 Contact Status Indicators:

❑ OPEN — Green
13 ❑ CLOSED — Red Magnum DS Drawout Breaker
 Spring Status Indicators:

❑ Charged — Yellow
❑ Discharged — White
 Push OFF (Open) Pushbutton —Red
 Push ON (Close) Pushbutton —
Green
 Manual Spring Charging Handle for
Manually Charging the Stored
Energy Springs
Accessory Viewing Windows Visibly
Mechanical Operations Counter Confirm the Breaker Shunt Trip, Spring
(Optional) Release, and UVR Installation and Their
Control Voltage Rating

Key Off Lock (Optional)
Drawout Breaker Levering Can be
Padlockable Levering Device Accomplished With the Compartment
Shutter for Drawout Breakers Door Closed Without the Need for a
Special Levering Tool
Color-Coded Position Indicator
for Drawout Breakers:
❑ CONNECT — Red
❑ TEST — Yellow
❑ DISCONNECT — Green

Through-the-Door Design for Human


Interface with the Breaker Compartment
Door Closed, for Example, Manually
Charging the Stored Energy Springs

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-5
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Breaker Internal Features  

Magnum is designed for ease of


access for inspection, modification 
and maintenance at the point of use.
The breaker front cover is easily
removed with four captive bolts,
revealing the modular internal breaker
features.
 Secondary Terminal Points for
Internal Breaker Wiring
Connections
 Breaker Accessory Mounting Deck
with Three Positions for Mounting:
❑ Shunt Trip Attachment (STA)

❑ Spring Release Device (SR)
❑ Undervoltage Release (UVR)
Device or Second STA
 Digitrip RMS Trip Unit (Model
1150+ Shown) 
 Spring Charging Motor (Optional) 
for Electrically Charging the Stored

Energy Springs
 Manual Spring Charging Handle for
Manually Charging the Stored Magnum Drawout Breaker Front View With Front Cover Removed
13
Energy Springs Showing Easy Access to the Breaker Internal Devices
 Padlockable Levering Device
Shutter for Drawout Breakers 
 Color-Coded Position Indicator for
Drawout Breakers:
❑ CONNECT — Red
❑ TEST — Yellow
❑ DISCONNECT — Green

 Secondary Contact Blocks for
Connection to External Cell
Control Wiring
Removable Arc Chute Covers for
Easy Access to Breaker Main
Contacts

Primary Finger Cluster Disconnect-


ing Contacts for Drawout Breaker
are Mounted on the Breaker Ele-
ment (Not in the Breaker Compart-
ment) for Ease of Access for
Inspection and Maintenance
Current Sensor Viewing Windows
to View and Confirm Breaker
Sensor Rating
Rigid Frame Housing (Thermoset
Composite Resin) Providing
Increased Strength and Durability

Magnum Drawout Breaker Rear View Showing Primary Disconnecting


Finger Clusters Mounted on the Breaker for Ease of Inspection

CA08101001E For more information visit: www.eaton.com


13-6 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Magnum DS Low Voltage UL and ANSI Test Comprehensive Enclosure


Power Circuit Breakers Certifications Solutions
Magnum DS is a true UL 1066 listed Magnum DS meets or exceeds the Magnum DS has proven performance
low voltage power circuit breaker applicable ANSI, NEMA, UL and in Eaton manufactured switchgear and
family, designed for the highest perfor- CSA standards, including: switchboards with the following test
mance requirements of switchgear certifications:
and specialty enclosure applications. ■ ANSI C37.13 (Low Voltage ac Power
Circuit Breakers Used in Enclo- ■ UL 1558 (Certified Magnum DS Low
■ Magnum DS Low Voltage Power sures). Voltage Metal-Enclosed
Circuit Breakers have short time ■ ANSI C37.16 (Preferred Ratings, Switchgear).
withstand and interruption ratings Related Requirements, and ■ UL 891 (Certified Pow-R-Line C Low
up to 100 kA at 635 Vac with Application Recommendations for Voltage Switchboards).
continuous current ratings up to Low Voltage Power Circuit Breakers ■ UL 1008 Standard for Transfer
6000 amperes to maximize system and ac Power Circuit Breakers). Switch Equipment.
coordination and selectivity. ■ ANSI C37.17 (Trip Devices for ac and ■ UL, CSA 22.2.31 Low Voltage
■ Magnum MDSX Current Limiting General Purpose dc Low Assemblies.
Power Circuit Breakers have 200 kA Voltage Power Circuit Breakers).
interrupting ratings at 480 Vac with ■ ANSI C37.50 (Test Procedures for Approvals
continuous current ratings up to Low Voltage ac Power Circuit Break-
5000 amperes. ■ UL listed: Magnum DS Breaker UL
ers Used in Enclosures). File No. E52096 and Cassette UL File
■ Magnum MDSL Current Limiting
■ UL 1066 (Standard for Low Voltage No. E204565.
Power Circuit Breakers have 200 kA ac and dc Power Circuit Breakers
interrupting ratings at 600 Vac with ABS (American Bureau of Shipping)
Used in Enclosures). Type Listed Certificate Number
continuous current ratings up to
2000 amperes. ■ NEMA SG3 (This standard adopts 04-HS422844A-DUB.
ANSI C37.16 in its entirety).

13 Magnum DS, MDSL and MDSX Circuit Breakers

Magnum DS Low Voltage Power The new Magnum MDSL Current The new Magnum MDSX Current Lim-
Circuit Breakers have high withstand Limiting Power Circuit Breakers have iting Power Circuit Breakers have fast
ratings from 42 kA to 100 kA to integral current limiters to provide opening contacts to provide interrupt-
provide for maximum system interrupting ratings of 200 kA at ing ratings up to 200 kA at 480 Vac
coordination and selectivity. 600 Vac. without fuses.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-7
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Magnum DS Switchgear Class UL 1066

Magnum DS Low Voltage Power Circuit Breaker Family ANSI Rated for Switchgear Applications

Table 13-1. Magnum DS Switchgear Class UL 1066 Low Voltage Power Circuit Breakers
Frame Breaker Frame rms Symmetrical Current Ratings kA 50/60 Hz  Short Time Fixed Internal Available Current Sensor &
Amperes Type Type Interrupting at Interrupting at Interrupting at Withstand Instantaneous Rating Plugs for Digitrip
254 Vac 508 Vac 635 Vac Rating Trip RMS Trip Unit (Establishes
Breaker In rating)

800 MDN-408 Narrow 42 42 42 42 — 200, 250, 300, 400, 600, 800


MDN-508 Narrow 50 50 50 50 —
MDN-608 Narrow 65 65 65 65 —
MDN-C08 Narrow 100 100 65 20 18 x In
MDS-408 Standard 42 42 42 42 — 13
MDS-608 Standard 65 65 65 65 —
MDS-808 Standard 85 85 85 85 —
MDS-C08 Standard 100 100 100 85 85
MDS-L08  Standard 200 200 200 — —
MDS-X08  Standard 200 200  30 30
1600 MDN-416 Narrow 42 42 42 42 — 200, 250, 300, 400, 600, 800,
MDN-516 Narrow 50 50 50 50 — 1000, 1200, 1600
MDN-616 Narrow 65 65 65 65 —
MDN-C16 Narrow 100 100 65 30 18 x In
MDS-616 Standard 65 65 65 65 —
MDS-816 Standard 85 85 85 85 —
MDS-C16 Standard 100 100 100 85 85
MDS-L16  Standard 200 200 200 — —
MDS-X16  Standard 200 200  30 30
2000 MDN-620 Narrow 65 65 65 65 — 200, 250, 300, 400, 600, 800,
MDN-C20 Narrow 100 100 65 35 18 x In 1000, 1200, 1600, 2000
MDS-620 Standard 65 65 65 65 —
MDS-820 Standard 85 85 85 85 —
MDS-C20 Standard 100 100 100 85 85
MDS-L20  Standard 200 200 200 — —
MDS-X20  Standard 200 200  30 30
3200 MDS-632 Standard 65 65 65 65 — 200, 250, 300, 400, 600, 800,
MDS-832 Standard 85 85 85 85 — 1000, 1200, 1600, 2000, 2500,
MDS-C32 Standard 100 100 100 85 85 3000, 3200
MDS-X32  Double 200 200  50 50
4000 MDS-840 Double 85 85 85 85 — 2000, 2500, 3200, 4000
MDS-C40 Double 100 100 100 100 —
MDS-X40  Double 200 200  50 50
5000 MDS-850 Double 85 85 85 85 — 2500, 3200, 4000, 5000
MDS-C50 Double 100 100 100 100 —
MDS-X50  Double 200 200  50 50
6000 MDS-C60  Double 100 100 100 100 — 3200, 4000, 5000, 6000
 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are
equal to the published Short Time Withstand Rating. These interruption ratings are based on the standard duty cycle consisting of an open operation,
a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short
time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the
two periods.
 Magnum MDSL Current Limiting Power Circuit Breaker With Integral Current Limiters. Current Limiter selected determines short time and fixed instan-
taneous trip rating. Maximum voltage rating is 600 Vac.
 Magnum MDSX Current Limiting Power Circuit Breaker With Fast Opening Contacts.
 Product to be tested. Contact Eaton for product rating.
 Breaker applied in a tested fan-cooled enclosure.

CA08101001E For more information visit: www.eaton.com


13-8 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Magnum SB Magnum SB is a Low Voltage Insulated UL & ANSI Test Certifications


Case Circuit breaker family designed
Low Voltage Insulated Case for the performance and economic Magnum SB meets or exceeds the
Circuit Breakers requirements of UL 891 switchboards. applicable ANSI, NEMA, UL and CSA
standards, including:
■ Magnum SB Insulated Case
Circuit Breakers have Interruption ■ ANSI C37.13 (Low Voltage AC Power
ratings up to 100 kA at 635 Vac with Circuit Breakers Used in Enclosures)
continuous current ratings up to ■ ANSI C37.16 (Preferred Ratings,
5000 amperes. Related Requirements, and
■ Magnum SB Insulated Case Circuit Application Recommendations for
Breakers have lighter-duty Short Low Voltage Power Circuit Breakers
Time Withstand ratings and fixed and AC Power Circuit Breakers)
internal instantaneous trips on ■ ANSI C37.17 (Trip Devices for AC
most ratings, which is characteristic and General Purpose DC Low
of UL 489 molded case breakers Voltage Power Circuit Breakers)
commonly used in UL 891 switch-
■ ANSI C37.50 (Test Procedures for
boards. This provides for greater
Low Voltage AC Power Circuit
economy and excellent coordination
Breakers Used in Enclosures)
and selectivity for most commercial
applications. ■ UL 1066 (Standard for Low Voltage
AC and DC Power Circuit Breakers
■ Fixed internal instantaneous trips
Used in Enclosures)
Magnum SB Low Voltage Insulated Case
will be phased in on all SB Insulated
Case Circuit Breakers rated 3200 ■ NEMA SG3 (This standard adopts
Circuit Breakers are Designed for the
amperes and below to provide an ANSI C37.16 in its entirety)
Performance and Economic Requirements
of UL 891 Switchboards extra safety factor by reducing the
energy let-through to downstream Comprehensive Enclosure
circuits at the maximum instanta-
13 neous trip point and to facilitate Solutions
feeder circuit breaker protection
in UL 891 switchboards with Magnum DS has proven performance
3-cycle bus bracing. in Eaton manufactured switchgear and
switchboards with the following test
■ Magnum SBSE Current Limiting
certifications:
Power Circuit Breakers have 150 kA
Interrupting Ratings at 480 Vac ■ UL 1558 (Certified Magnum DS Low
with continuous current ratings up Voltage Metal-Enclosed switchgear)
to 5000 amperes. The Short Time ■ UL 891 (Certified Pow-R-Line C Low
Withstand Rating is 30 kA for Voltage Switchboards)
standard frame and 50 kA for ■ UL, CSA 22.2.31 Low Voltage
double frame breakers. Assemblies

Approvals
■ UL listed: Magnum DS Breaker
UL File E52096 and Cassette
UL File E204565.

Typical Magnum SB Low Voltage Insulated


Case Circuit Breaker Nameplate

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-9
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Magnum SB Switchboard Class UL 1066 Insulated Case

Magnum SB Low Voltage Insulated Case Circuit Breaker Family UL Rated for Switchboard Applications

Table 13-2. Magnum SB Switchboard Class UL 1066 Insulated Case Low Voltage Power Circuit Breaker
Frame Breaker Frame rms Symmetrical Current Ratings kA 50/60 Hz  Available Current Sensor & Rating
Amperes Type Type Interrupting Interrupting Interrupting Short Time Fixed Internal Plugs for Digitrip RMS Trip Unit
at 254 Vac at 508 Vac at 635 Vac Withstand Rating Inst Trip (Establishes Breaker In rating)

800 SBN-508 Narrow 50 50 35 20  200, 250, 300, 400, 600, 800


SBN-608 Narrow 65 65 42 20 
SBN-C08 Narrow 100 100 65 20 18 x In
SBS-608 Standard 65 65 65 20 
SBS-C08
SBS-E08 
Standard
Standard
100
200
100
150 
85 20
30

30
13
1200 SBN-512 Narrow 50 50 35 25  200, 250, 300, 400, 600, 800,
SBN-612 Narrow 65 65 42 25  1000, 1200
SBN-C12 Narrow 100 100 65 25 18 x In
SBS-612 Standard 65 65 65 25 
SBS-C12 Standard 100 100 85 25 
SBS-E12  Standard 200 150  30 30
1600 SBN-516 Narrow 50 50 35 30  200, 250, 300, 400, 600, 800,
SBN-616 Narrow 65 65 42 30  1000, 1200, 1600
SBN-C16 Narrow 100 100 65 30 18 x In
SBS-616 Standard 65 65 65 30 
SBS-C16 Standard 100 100 85 30 
SBS-E16  Standard 200 150  30 30
2000 SBN-620 Narrow 65 65 65 35  200, 250, 300, 400, 600, 800,
SBN-C20 Narrow 100 100 65 35 18 x In 1000, 1200, 1600, 2000
SBS-620 Standard 65 65 65 35 
SBS-C20 Standard 100 100 85 35 
SBS-E20  Standard 200 150  30 30
2500 SBS-625 Standard 65 65 65 45  200, 250, 300, 400, 600, 800,
SBS-C25 Standard 100 100 85 45  1000, 1200, 1600, 2000, 2500
SBS-E25  Double 200 150  50 50
3000 SBS-630 Standard 65 65 65 50  200, 250, 300, 400, 600, 800,
SBS-C30 Standard 100 100 85 50  1000, 1200, 1600, 2000, 2500, 3000
SBS-E30  Double 200 150  50 50
4000 SBS-840 Double 85 85 85 85 — 2000, 2500, 3000, 4000
SBS-C40 Double 100 100 100 100 —
SBS-E40  Double 200 150  50 50
5000 SBS-850 Double 85 85 85 85 — 2500, 3000, 4000, 5000
SBS-C50 Double 100 100 100 100 —
SBS-E50  Double 200 150  50 50
6000 SBS-C60  Double 100 100 100 100 — 3000, 4000, 5000, 6000
 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are
equal to the published Short Time Withstand Rating. These interruption ratings are based on the standard duty cycle consisting of an open operation,
a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short
time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the
two periods.
 Fixed Internal Instantaneous Trip set at approximately 18 x In symmetrical will be phased into the product.
 Product to be tested. Contact Eaton for product rating.
 Magnum SBSE Current Limiting Power Circuit Breaker With Fast Opening Contacts.
 Breaker applied in a tested fan-cooled enclosure.

CA08101001E For more information visit: www.eaton.com


13-10 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Magnum IEC Rated Magnum Air Circuit Breakers are Comprehensive


designed to enable global power
Air Circuit Breakers distribution solutions in IEC switch- Enclosure Solutions
boards and other custom enclosures.
Magnum Air Circuit Breakers have
■ Magnum IEC Air Circuit Breakers proven performance in IEC switch-
have interruption ratings up to boards and custom enclosures manu-
100 kA at 690 Vac with continuous factured by Eaton and Low Voltage
current ratings up to 6300 amperes. Systems Builders (OEMs) to the
■ Magnum IEC Air Circuit Breaker following standards:
continuous current frames are ■ EN/IEC 60947-1.
100% rated. No thermal de-rating
is required when applying the ■ EN/IEC 60439-1.
breaker in the low voltage systems ■ Eaton manufactured IEC Low Volt-
enclosure at ambient temperatures age Switchboard solutions include:
of 40°C. ❑ Eaton MEM M-Form (UK)
■ Magnum IEC Breakers carry the Low Voltage Switchboards
KEMA Keur Mark, which requires ❑ Eaton Holec Capitole 40 and
periodic follow-up testing, wit- Capitole 20 (Holland) Low Voltage
nessed by KEMA, to demonstrate Switchboards
our product performs to its pub- ❑ Eaton Tabula Low Voltage
lished nameplate ratings. This Switchboard Systems (Global) for
differentiates Magnum Air Circuit Low Voltage Systems Builders
Magnum Narrow Frame Drawout Breakers from competition, who
Air Circuit Breaker With Cassette generally self-tests their product ❑ Eaton Elatis (Germany) Low
when it is first introduced and is Voltage Switchboards
not bound to perform subsequent
follow-up third-party testing. Approvals and Marks
13 Magnum Air Circuit Breakers carry
IEC Test Certifications the following approvals and approval
marks:
Magnum Air Circuit Breakers meet or ■ CE.
exceed the applicable IEC standards,
including: ■ KEMA Keur mark.
■ ABS (American Bureau of Shipping)
The KEMA Keur Mark on the Magnum
■ EN/IEC 60947-2. Type Listed Certificate Number
ACB Label Confirms Third-Party Witness ■ KEMA third-party witness and 04-HS422844B-PDA-DUB.
and Follow-up Testing follow-up testing. ■ CCC (Certificate for China
Compulsory Product Certification)
to GB14048.2-2001, Certificate
Numbers:
❑ 2005010307139381
❑ 2003010307094561
❑ 2003010307094558

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-11
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Magnum IEC 60947-2 Rated

Magnum IEC Low Voltage Air Circuit Breaker Family

Table 13-3. Magnum IEC 60947-2 Rated Air Circuit Breakers


Frame Breaker Frame rms Symmetrical Current Ratings kA  Available Current Sensor & Rating
Amperes Type Type Interrupting Interrupting Interrupting Withstand Rating Fixed Plugs for Digitrip RMS Trip Unit
at 240 Vac at 440 Vac at 690 Vac Icw Internal (Establishes Breaker In Rating)
Icu = Ics Icu = Ics Icu = Ics 1-Sec / 3-Sec Inst. Trip

800 MWN-408 Narrow 40 40 40 40 / — — 200, 250, 300, 400, 630, 800


MWN-508 Narrow 50 50 50 50 / — —
MWN-608 Narrow 65 65 65 65 / 40 — 13
MWI-608 Standard 65 65 65 65 / — —
MWI-808 Standard 85 85 85 85 / 65 —
MWI-C08 Standard 100 100 85 85 / 65 85
1000 MWN-410 Narrow 40 40 40 40 / — — 200, 250, 300, 400, 630, 800, 1000
MWN-510 Narrow 50 50 50 50 / — —
MWN-610 Narrow 65 65 65 65 / 40 —
MWI-610 Standard 65 65 65 65 / — —
MWI-810 Standard 85 85 85 85 / 65 —
MWI-C10 Standard 100 100 85 85 / 65 85
1250 MWN-412 Narrow 40 40 40 40 / — — 200, 250, 300, 400, 630, 800,
MWN-512 Narrow 50 50 50 50 / — — 1000, 1250
MWN-612 Narrow 65 65 65 65 / 40 —
MWI-612 Standard 65 65 65 65 / — —
MWI-812 Standard 85 85 85 85 / 65 —
MWI-C12 Standard 100 100 85 85 / 65 85
1600 MWN-516 Narrow 50 50 50 50 / — — 200, 250, 300, 400, 630, 800,
MWN-616 Narrow 65 65 65 65 / 40 — 1000, 1250, 1600
MWI-616 Standard 65 65 65 65 / — —
MWI-816 Standard 85 85 85 85 / 65 —
MWI-C16 Standard 100 100 85 85 / 65 85
2000 MWN-520 Narrow 50 50 50 50 / 30 — 200, 250, 300, 400, 630, 800,
MWN-620 Narrow 65 65 65 65 / 40 — 1000, 1250, 1600, 2000
MWI-620 Standard 65 65 65 65 / 50 —
MWI-820 Standard 85 85 85 85 / 65 —
MWI-C20 Standard 100 100 85 85 / 65 85
2500 MWI-625 Standard 65 65 65 65 / — — 200, 250, 300, 400, 630, 800,
MWI-825 Standard 85 85 85 85 / 65 — 1000, 1250, 1600, 2000, 2500
MWI-C25 Standard 100 100 85 85 / 65 85
3200 MWI-632 Standard 65 65 65 65 / 50 — 200, 250, 300, 400, 630, 800,
MWI-832 Standard 85 85 85 85 / 65 — 1000, 1250, 1600, 2000, 2500, 3200
MWI-C32 Standard 100 100 85 85 / 65 85
4000 MWI-64N Double 65 65 65 65 / — — 2000, 2500, 3200, 4000
MWI-84N Double 85 85 85 85 / — —
MWI-C4N Double 100 100 100 100 / — —
5000 MWI-85N Double 85 85 85 85 / — — 2500, 3200, 4000, 5000
MWI-C5N Double 100 100 100 100 / — —
6300 MWI-86N Double 85 85 85 85 / — — 3200, 4000, 5000, 6300
MWI-C6N Double 100 100 100 100 / — —
 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS Trip Unit. Interruption ratings for non-automatic breakers are equal
to the published breaker Icw Rating.

CA08101001E For more information visit: www.eaton.com


13-12 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Table 13-4. Digitrip Trip Units for Magnum DS and SB ANSI/UL Rated Power Circuit Breakers

Trip Unit Type Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+ 

Ampere Range 200 A – 6000 A 200 A – 6000 A 200 A – 6000 A 200 A – 6000 A
Interrupting Rating at 480 V 42 through 200 kA 42 through 200 kA 42 through 200 kA 42 through 200 kA
rms Sensing Yes Yes Yes Yes
Protection and Coordination
Protection Ordering Options LI, LSI, LSIG LSI, LSIG, LSIA LSI, LSIG, LSIA LSI, LSIG, LSIA
Fixed Rating Plug (In) Yes Yes Yes Yes
Overtemperature Trip Yes Yes Yes Yes
Long Long Delay Pickup 0.4 – 1.0 x (In) 0.4 – 1.0 x (In) 0.4 – 1.0 x (In) 0.4 – 1.0 x (In)
Delay Long Delay Time I2t at 6 x Ir 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds
Protection Long Delay Time I4t No No No 1 – 5 Seconds
(L) IEEE Curves No No No Yes
Long Delay Thermal Memory Yes Yes Yes Yes
High Load Alarm No No No 0.5 – 1.0 x (Ir)
Short Short Delay Pickup 200 – 1000% x (Ir) & M1 200 – 1000% x (Ir) & M1 200 – 1000% x (Ir) & M1 200 – 1000% x (Ir) & M1
Delay Short Delay Time I2t at 8 x Ir 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
Protection Short Delay Time Flat 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
(S) Short Delay Time ZSI Yes Yes Yes Yes
Instanta- Instantaneous Pickup 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1
neous Making Current Release Yes Yes Yes Yes
13 Protection
(I)
Off Position LSI & LSIG Yes Yes Yes

Ground Ground Fault Alarm No Yes Yes Yes


Fault Ground Fault Pickup 25 – 100% x (In) 25 – 100% x (In) 25 – 100% x (In) 24 – 100% x (In)
Protection Ground Fault Delay I2t at .625 x In 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
(G)  Ground Fault Delay Flat 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
Ground Fault ZSI Yes Yes Yes Yes
Ground Fault Thermal Memory Yes Yes Yes Yes
Disable Ground Fault Protection No No No No
Neutral Protection (N) Model LSI Model LSI Model LSI Model LSI
System Diagnostics
Cause of Trip LEDs Yes Yes Yes Yes
Magnitude of Trip Information No Yes Yes Yes
Remote Signal Contacts No Yes Yes Yes
Programmable Contacts No No No Yes
System Monitoring
Digital Display No 4-Character LCD 4-Character LCD 24-Character LED
Current (%) Full Scale Sensor No Yes +/- 2% Yes +/- 2% Yes +/- 1%
Voltage (%) L to L No No No Yes +/- 1%
Power and Energy (%) No No No Yes +/- 2%
Apparent Power kVA and Demand No No No Yes
Reactive Power kvar No No No Yes
Power Factor No No No Yes
Crest Factor No No No Yes
Power Quality — Harmonics No No No Yes
% THD No No No Yes
System Communications
Type No No INCOM/PowerNet INCOM/PowerNet/TripLink
Power Supply in Breaker N/A Optional Standard Standard
Additional Features
Trip Log (3 Events) No No No Yes
Electronic Operations Counter No No No Yes
Testing Method  Test Set Test Set Test Set Integral and Test Set
Waveform Capture No No No Yes
ARMs (Arc Flash Reduction Mode) No No Yes Yes 
Breaker Health Monitor No No No Yes
Programmable Relay Functions No No No Yes 
 Over and Undervoltage Alarm or Trip, Over  1200 ampere maximum ground fault setting
and Underfrequency Alarm or Trip, Voltage per UL/NEC. Legend: In = Rating Plug and Sensor Rating.
Unbalance Alarm or Trip, Reverse Power  Test set for secondary injection. Ir = Long Delay Pickup setting.
Trip, and Phase Rotation Alarm are included.  Contact Eaton for availability.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-13
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Table 13-5. Digitrip Trip Units for Magnum IEC Rated Air Circuit Breakers

Trip Unit Type Digitrip 520i Digitrip 520Mi Digitrip 520MCi Digitrip 1150i+ 

Ampere Range 200 A – 6300 A 200 A – 6300 A 200 A – 6300 A 200 A – 6300 A
Interrupting Rating at 690 V 40 – 100 kA 40 – 100 kA 40 – 100 kA 40 – 100 kA
rms Sensing Yes Yes Yes Yes
Protection and Coordination
Protection Ordering Options LI, LSI, LSIG LSI, LSIG, LSIA LSI, LSIG, LSIA LSI, LSIG, LSIA
Fixed Rate Plug (In) Yes Yes Yes Yes
Overtemperature Trip Yes Yes Yes Yes
Long Long Delay Setting 0.4 – 1.0 x (In) 0.4 – 1.0 x (In) 0.4 – 1.0 x (In) 0.4 – 1.0 x (In)
Delay Long Delay Time I2t at 6 x Ir 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds
Protection Long Delay Time I4t No No No 1 – 5 Seconds
(L) IEC Type A, B, C Curves No No No Yes
Long Delay Thermal Memory Yes Yes Yes Yes
High Load Alarm No No No 0.7 – 1.0 x Ir
Short Short Delay Pickup 200 – 1000% x (Ir) & M1 200 – 1000% x (Ir) & M1 200 – 1000% x (Ir) & M1 150 – 1000% x (Ir) & M1
Delay Short Delay Time I2t at 8 x Ir 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
Protection Short Delay Time Flat 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
(S) Short Delay Time ZSI Yes Yes Yes Yes
Instanta- Instantaneous Pickup 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1 200 – 1000% x (In) & M1
neous Making Current Release Yes Yes Yes Yes
Protection Off Position Yes Yes Yes Yes
(I) 13
Earth Earth Fault Alarm No Yes Yes Yes
Fault Earth Fault Pickup 25 – 100% x (In) 25 – 100% x (In) 25 – 100% x (In) 24 – 100% x (In)
Protection Earth Fault Delay I2t at .625 x In 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
(G) Earth Fault Delay Flat 100 – 500 ms 100 – 500 ms 100 – 500 ms 100 – 500 ms
Earth Fault ZSI Yes Yes Yes Yes
Earth Fault Memory Yes Yes Yes Yes
Disable Ground Fault Protection No No No Yes
Neutral Protection (N) Model LSI Model LSI Model LSI Model LSI
System Diagnostics
Cause of Trip LEDs Yes Yes Yes Yes
Magnitude of Trip Information No No No Yes
Remote Signal Contacts No Yes Yes Yes
Programmable Contacts No No No 2
System Monitoring
Digital Display No 4 Character LCD 4 Character LCD 24 Character LED
Current (%) Full Scale Sensor No Yes +/- 2% Yes +/- 2% Yes +/- 1%
Voltage (%) L to L No No No Yes +/- 1%
Power and Energy (%) No No No Yes +/- 2%
Apparent Power kVA and Demand No No No Yes
Reactive Power kvar No No No Yes
Power Factor No No No Yes
Crest Factor No No No Yes
Power Quality — Harmonics No No No Yes
% THD No No No Yes
System Communications
Type No No INCOM/PowerNet INCOM/PowerNet/TripLink
Power Supply in Breaker N/A Optional Standard Standard
Additional Features
Trip Log (3 Events) No No No Yes
Electronic Operations Counter No No No Yes
Testing Method  Test Set Test Set Test Set Integral and Test Set
Waveform Capture No No No Yes
ARMs (Arc Flash Reduction Mode) No No Yes Yes 
Breaker Health Monitor No No No Yes
Programmable Relay Functions No No No Yes 
 Over and Undervoltage Alarm or Trip, Over  Test set for secondary injection.
and Underfrequency Alarm or Trip, Voltage  Contact Eaton for availability.
Legend: In = Rating plug rating.
Unbalance Alarm or Trip, Reverse Power Ir = LDPU setting.
Trip, and Phase Rotation Alarm are included.
Note: i Trip units are only used on IEC
breakers with earth fault.

CA08101001E For more information visit: www.eaton.com


13-14 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Breaker-Mounted Options ■ Auxiliary Switch. Up to 6a/6b


auxiliary individual dedicated con-
and Accessories tacts are available for customer use
to indicate if the breaker is in the
OPEN or CLOSE position.
■ Mechanical Trip Indicator Flag. The
red trip indicator flag pops out to
provide local visual indication when
the Digitrip RMS trip unit acts to trip
the breaker on an overcurrent
condition.
■ Bell Alarm/Overcurrent Trip Switch
(OTS). Provides 2 Form C
(changeover) contacts that change Auxiliary Switches Come in Modular 2a/2b
Contact Stages Providing up to 6a/6b
state when the Digitrip RMS trip unit
Dedicated Contacts
acts to trip the breaker on an over-
Arc Chutes are Easily Removable for current condition. The contacts are
Inspection and Access to Breaker Contacts available for external indication or
customer use and are manually
reset by the Mechanical Trip
Indicator.
■ Padlockable Pushbutton Cover.
Permits padlocking hinged cover
plates to block access to the PUSH
ON and PUSH OFF buttons on the
breaker faceplate.
■ Mechanical Operations Counter.
13 Heel-Toe Contact Design Provides
Demonstrated Long Life and Includes
Records mechanical operations of
the breaker over its installed life.
Wear Indicator for Visual Inspection ■ Key Off Lock Provisions. Enables
Magnum breakers are available with a mounting of a single cylinder Kirk,
comprehensive array of factory- Castell, or Ronis Key Lock to lock the
installed breaker options to enable breaker in the OPEN position.
configured-to-order solutions for spec- ■ Latch Check Switch. Provides 1
ified customer requirements. Field Form C (changeover contact) that
option kits are available to provide changes state when the breaker is
easy service, modification and ready to close. Can be wired to the Mechanical Trip Indicator With Bell Alarm
customization of the breaker at the Spring Release Device for fast (OTS) Switches Mounted
point of use. transfer applications or wired for
external ready-to-close indication.
■ Shunt Trip device (ST). Provides
for remote electrically controlled
breaker opening when energized
by a rated voltage input.
■ Spring Charge Motor (MOT).
Charges the breaker closing springs
automatically, facilitating remote or
local closing. The motor assembly
includes its own cut-off switch
that changes state at the end of the
charging cycle. This contact can be
wired out for external indication.
■ Spring Release device (SR).
Provides for remote electrically
controlled breaker closing when
its coils are energized by a rated
voltage input.
■ Undervoltage Release (UVR).
Trips the breaker when an existing Shunt Trip, Spring Release and
voltage signal is lost or falls Undervoltage Release Device Installed
below an established threshold. on Accessory Deck

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-15
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Table 13-6. Magnum Breaker Control Device Application Guide — Vdc


Breaker Control Device 24 Vdc 32 Vdc 48 Vdc 125 Vdc 250 Vdc
Nominal Voltage

Shunt Trip (ST) Trip Circuit —


Operational Voltage Range 70 to 110% 17 – 26 Vdc 34 – 53 Vdc 77 – 138 Vdc 154 – 275 Vdc
Power Consumption (Inrush) (Required for 35 ms) 250 Watts 250 Watts 450 Watts 450 Watts
Opening Time Seconds 35 ms 35 ms 35 ms 35 ms
Spring Release (SR) Close Circuit —
Operational Voltage Range 70 to 110% 17 – 26 Vdc 34 – 53 Vdc 77 – 138 Vdc 154 – 275 Vdc
Power Consumption (Inrush) (Required for 200 ms) 250 Watts 250 Watts 450 Watts 450 Watts
Closing Time Seconds 40 ms 40 ms 40 ms 40 ms
Spring Charge Motor (MOT) —
Operational Voltage Range 85 to 110% Voltage 20 – 26 Vdc 41 – 53 Vdc 94 – 138 Vdc 187 – 225 Vdc
Amps (Running) Running 12.0 Amps 5.0 Amps 2.0 Amps 1.0 Amp
Amps (Inrush) % of Running 300% 500% 600% 600%
Power Consumption 300 Watts 250 Watts 250 Watts 250 Watts
Charging Time Seconds 5 Sec 5 Sec 5 Sec 5 Sec
Undervoltage Release (UVR)
Operational Voltage Range 85 to 110% Voltage 20 – 26 Vdc 27 – 35 Vdc 41 – 53 Vdc 94 – 138 Vdc 187 – 275 Vdc
Drop-out Voltage Range 30 to 60% Voltage 7 – 14 Vdc 10 – 19 Vdc 14 – 29 Vdc 33 – 75 Vdc 66 – 150 Vdc
Power Consumption (Inrush) Required for 200 ms 250 Watts 275 Watts 275 Watts 450 Watts 450 Watts
Power Consumption (Continuous) Required for 400 ms 18 Watts 15 Watts 18 Watts 10 Watts 10 Watts
Opening Time Seconds 70 ms 70 ms 70 ms 70 ms 70 ms
Auxiliary Switches —
Minimum Load
Contact Rating Inductive Load 0.5 Amps 0.5 Amps 0.5 Amps 0.25 Amps

Table 13-7. Magnum Breaker Control Device Application Guide — Vac


Breaker Control Device 120 Vac 240 Vac 415 Vac 480 Vac 600 Vac
Nominal Voltage
13
Shunt Trip (ST) Trip Circuit — — —
Operational Voltage Range 70 to 110% 77 – 140 Vac 146 – 264 Vac
Power Consumption (Inrush) (Required for 35 ms) 450 VA 450 VA
Opening Time Seconds 35 ms 35 ms
Spring Release (SR) Close Circuit — — —
Operational Voltage Range 70 to 110% 77 – 140 Vac 146 – 264 Vac
Power Consumption (Inrush) (Required for 200 ms) 450 VA 450 VA
Closing Time Seconds 40 ms 40 ms
Spring Charge Motor (MOT) — — —
Operational Voltage Range 85 to 110% Voltage 93 – 140 Vdc 177 – 264 Vdc
Amps (Running) Running 2.0 Amps 1.0 Amp
Amps (Inrush) % of Running 600% 600%
Power Consumption 250 VA 250 VA
Charging Time Seconds 5 Sec 5 Sec
Undervoltage Release (UVR)
Operational Voltage Range 85 to 110% Voltage 94 – 140 Vac 177 – 264 Vac 323 – 457 Vac 408 – 528 Vac 510 – 660 Vac
Drop-out Voltage Range 30 to 60% Voltage 33 – 76 Vac 62 – 144 Vac 114 – 249 Vac 144 – 288 Vac 180 – 360 Vac
Power Consumption (Inrush) Required for 200ms 450 VA 400 VA 480 VA 400 VA 400 VA
Power Consumption (Continuous) Required for 400 ms 10 VA 10 VA 10 VA 10 VA 10 VA
Opening Time Seconds 70 ms 70 ms 70 ms 70 ms 70 ms
Auxiliary Switches — — —
Minimum Load
Contact Rating Inductive Load 10 Amps 10 Amps

CA08101001E For more information visit: www.eaton.com


13-16 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Legend:
LS Limit Switch for Closing Spring
MOT Motor for Spring Charging
ST Shunt Trip
SR Spring Release Close Open G Open R
UVR Undervoltage Release
OTS Overcurrent Trip Switch

Description of Operation: B12 B15 B26 B10 B24 A7 A1 A2 A3


1 — Motor is energized through
Lever
LS contact. in Door
2 — Motor runs and charges closing Switch
spring. (Draw- a.
3 — When closing spring is fully charged, Control out Only)
LS contacts change state. Power OTS 1*
4 — Close contacts energize SR coil. SR L.S. b. ST a. UVR OTS 2*
5 — When breaker closes, “b” opens.
6 — LS contacts change state and motor MOT
recharges closing springs.

B13 B14 B27 B11 B25 A8 A4 A5 A6

* Contacts shown for breaker open (not fully


charged), not tripped.

Dotted line denotes Magnum Breaker.

13 MDSEOBKR

Figure 13-1. Typical Magnum Breaker Control Circuit Diagram

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-17
Power Circuit Breakers
December 2008
Low Voltage Power Circuit Breakers

Series NRX Low Voltage Features, Benefits ■ Patented “Direct Drive” Mechanism
— symmetrically loaded forces of
Power Circuit Breakers and Functions the two-staged stored energy
mechanism improves robustness,
Series NRX utilizes several innovative reliability, and achieves improved
technologies: breaker life ratings.
■ Rogowski Coil — Does not saturate ■ Fold-up Cassette — With this
like iron core sensors, and one sen- “patent-pending” simple design, all
sor accommodates 200 – 1600 amp items in a cassette are replaceable
range. You NEVER have to change a without removing the cassette from
sensor and NO CTs are required. the cell.
■ Tension Clamp Secondary Terminals ■ Patented “arc chute” design.
— 10 A Continuous Rating at 600 V ■ Breaker Mounted Racking or
meets UL/CSA/RoHS and UL-94 V0. Levering-In Device — Racking
Mounted directly to fixed breaker or device is mounted on the breaker
drawout cassette they reduce wiring decreasing the width of the cassette,
throughout enclosure and provide because the cassette is not
clean, organized wiring schemes. burdened with the cost or parts
Series NRX Low Voltage Power ■ Breaker Mounted Communication of the lev-in.
Circuit Breaker Modules — Communication mod- ■ Plug-N-Play Accessories — No spe-
ules for INCOM and Modbus mount cial tools needed. Accessory comes
Product Description directly to the cassette, reducing the with plug and wires ready to install.
space and room required in gear for
Series NRX is a low voltage power communication capability. The use of these technologies allows
circuit breaker suitable for UL 1558, Series NRX to offer a life of 20,000
UL 891, and IEC switchgear and mechanical operations and 10,000
switchboards. The compact size and electrical operations with a high
degree of reliability.
weight of 3-pole drawout with cassette
Series NRX, 14.18" (360 mm) x 10.02"
13
Table 13-8. Mounting and Load Connection Configurations
(255 mm) x 10.68" (271 mm) at 85 lbs
Breaker Type Draw-out Breaker Cassette Fixed
(39 kg) allows for a 24" switchgear
enclosure.
The breaker ratings are:
■ 800 A for UL 1066.
■ 800 A, 1200 A for UL 489. Breaker Mechanism Stored Energy — Stored Energy
■ 630 – 1600 A IEC 60947-2 from a Standard Bus Finger Clusters Rear Connected Rear Connected
voltage range of 220 Vac – 725 Vac. Connection Provisions Pre-Drilled Bus Pads Pre-Drilled Bus Pads
Rear Connected —
Application Description Horizontal/Vertical
Adapter Kit With and
Without Cover (Kits
The Series NRX is a compact globally Shipped Unassembled)
certified low voltage power (air) circuit
breaker. It is rated for 800 amperes Front Connected —
Horizontal/Vertical
UL 1066, 800 and 1200 amperes Adapter Kit With and
UL 489, and 630 – 1600 amperes Without Cover (Kits
IEC 60947-2 with an interrupting Shipped Unassembled)
capacity of 65 kA with short time with-
Cable Connected Cable — —
stand at 42 kA at the 440/480 Vac level. Terminals With Cover
The Series NRX circuit breaker pro-
vides all the capabilities of a power
circuit breaker in the compact size of a
molded case breaker. It offers you the
same protection and performance —
along with increased flexibility — at
half the size of a typical power circuit
breaker. The dimensions and design of
Series NRX allows up to eight UL 1066
or UL 489 breakers in a 24-inch
(600 mm) wide structure. The one
frame size, regardless of ampere
rating, reduces drawing conversion,
structure integration time and parts
inventory for several board, gear and
machinery applications.

CA08101001E For more information visit: www.eaton.com


13-18 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
General Description

Standards and Certifications ■ ANSI C37.20.1 (Metal-enclosed Table 13-9. List of Manuals
low voltage power circuit breaker Description Publication
■ UL 1066 (Low voltage ac power switchgear). Number
circuit breakers used in enclosures). ■ ANSI C37.60 (Requirements for
Instruction Book for Fixed and MN01301001E
■ UL 489 (Molded-case circuit overhead, pad mounted dry-type Drawout Breaker/Cassette
breakers, molded case switches and submersible automatic
IL Drawout Circuit Breaker IL01301006E
and circuit breaker enclosures). reclosers and fault interrupters and Cassette Rejection
■ EN 45011. for ac systems). Interlocks
■ CEI EN 60947. ■ ANSI C37.50 (Low voltage ac power IL Auxiliary Switch in Right IL01301007E
circuit breakers used in enclosures Accessory Tray
■ BS EN 60439-1 Form 4b.
— test procedures). IL UVR/ST/OTS in Left IL01301008E
■ IEC 60439-1 (Low voltage switch- Accessory Tray
■ ANSI C37.17 (For trip devices for ac
gear and controlgear assemblies).
and general purpose dc low voltage IL Motor Operator IL01301010E
■ IEC 60947-1 (Low voltage switch- power circuit breakers). IL Spring Release Device IL01301010E
gear and controlgear — Part 1 and Latch Check Switch
■ ANSI C37.16 (Low voltage power
general rules). (Numbers 5 and 6 are Com-
circuit breakers and ac power circuit bining into one Document)
■ IEC 60947-2 (Low voltage switch- protectors — preferred ratings,
gear and controlgear — Part 2 IL Door Escutcheon and IL01301012E
related requirements, and applica- Gasket Kit
circuit breakers). tion recommendations).
IL Drawout Cassette Shutters IL01301013E
■ IEC 60947-3 (Switches, disconnec- ■ ANSI C37.13 (IEEE standard for low
tors, switch-disconnectors and IL Fixed Breaker Arc Hood Kit IL01301014E
voltage ac power circuit breakers
fuse-combination units). used in enclosures). IL Fixed Breaker Front/Rear/ IL01301015E
Cable Connectors
■ CSA 22.2 (Molded-case circuit ■ CCC — China.
breakers, molded case switches IL Drawout Cassette Front/ IL01301016E
■ Kema Keur (&CB). Rear/Cable Connectors
and circuit breaker enclosures).
■ UL 891 (Dead front switchboard). IL Racking Device IL01301018E
■ ANSI C37.51 (Metal-enclosed low Levering Device
voltage ac power circuit breaker ■ UL 1558 (Metal-enclosed low
13 switchgear assemblies — conform- voltage power circuit breaker IL Mechanical Pop-out
Indicator
IL01301019E

ance test procedures). switchgear).


IL Breaker and Cassette IL01301021E
Phase Barriers
IL Cassette Rails IL01301025E

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-19
Power Circuit Breakers
December 2008
Product Selection

Product Selection
Table 13-10. Series NRX Circuit Breakers Catalog Number Format (Exclusionary Rules Apply) — Positions 1 – 8

N S S6 08 3 W
Breaker Frame Size Mounting Configuration 
N = Type NF, 630 – 1600 Amperes, (70 mm Pole Spacing) W = Drawout
B = Fixed-Mount Rear-Connect, Mounting Bracket
With Secondary Terminal Row
Industry Standard, Mechanism Type & Device Description
R = Fixed-Mount Rear-Connect, Surface Mount
S = UL 1066, Stored Energy, Power Circuit Breaker With Secondary Terminal Row
X = UL 489, Stored Energy, Insulated Case Circuit Breaker C = Fixed-Mount Front Connect, Mounting Bracket,
E = IEC 60947-2, Stored Energy, Air Circuit Breaker Cable-Ct. With Secondary Terminal Row
T = Fixed-Mount Front Connect, Surface Mount,
Fault Current Rating Cable-Ct. With Secondary Terminal Row
F = Fixed-Mount Front Connect, Mounting Bracket,
S4 = Selective, 42 kA @ 480 Vac UL or 415 V IEC Bus-Ct. With Secondary Terminal Row
S5 = Selective, 50 kA @ 480 Vac UL or 415 V IEC S = Fixed-Mount Front Connect, Surface Mount,
S6 = Selective, 65 kA @ 480 Vac UL or 415 V IEC Bus-Ct. With Secondary Terminal Row

Poles & Phasing


3 = 3-Pole ABC
4 = 4-Pole NABC

Frame Rating in Amperes


07 = 630 Amperes, IEC Only
08 = 800 Amperes 13
10 = 1000 Amperes, IEC Only
12 = 1200 Amperes, UL Only
13 = 1250 Amperes, IEC Only
16 = 1600 Amperes, On NF: IEC Only

 See Page 13-20 for additional breaker options.

CA08101001E For more information visit: www.eaton.com


13-20 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Product Selection

Table 13-11. Series NRX Circuit Breakers Style Number Format — Positions 9 – 20

52 8 A A A N 4 X N D X

Trip Unit Rating Plug Reserved for Future Use


(Amperes)
52 = 520 LSI (No ZSI) X = All Products
53 = 520 LSI (With ZSI) 1 = 200
5G = 520 LSIG (No ZSI) 2 = 250
Drawout Breaker Shipping/Fixed Breaker Terminals
5H = 520 LSIG (With ZSI) 3 = 300
& Door Frame Kit
M2 = 520M LSI (No ZSI, 24 Vdc) 4 = 400
M3 = 520M LSI (With ZSI, 24 Vdc) 5 = 500 D = Drawout (or Parent) Breaker Shipping Alone,
MA = 520M LSIA (No ZSI, 24 Vdc) 6 = 600 without Door Frame Kit
MB = 520M LSIA (With ZSI, 24 Vdc) 7 = 630 C = Drawout Breaker in Cassette,
MG = 520M LSIG (No ZSI, 24 Vdc) 8 = 800 with Door Frame Kit
MH = 520M LSIG (With ZSI, 24 Vdc) A = 1000 N = Fixed Breaker, No Adapters (Rear-Connect) or Cable
R2 = 520M LSI (No ZSI, B = 1200 Lugs (Front Cable Connect), without Door Frame Kit
24 Vdc, with ARMS) C = 1250 K = Fixed Breaker, No Adapters (Rear-Connect) or Cable
R3 = 520M LSI (With ZSI, D = 1600 Lugs (Front Cable Connect), with Door Frame Kit
24 Vdc, with ARMS) A = Terminal Adapters for Rear-Connect,
RA = 520M LSIA (No ZSI, Short Vertical, with Door Frame Kit
Shunt Trip  B = Terminal Adapters for Rear-Connect,
24 Vdc, with ARMS)
RB = 520M LSIA (With ZSI, N = None Short Horizontal, with Door Frame Kit
24 Vdc, with ARMS) A = 110 – 127 Vac/Vdc V = Terminal Adapters for Rear-Connect,
RG = 520M LSIG (No ZSI, R = 208 – 250 Vac/Vdc Short Vertical, without Door Frame Kit
13 RH =
24 Vdc, with ARMS)
520M LSIG (With ZSI,
W = Terminal Adapters for Rear-Connect,
Short Horizontal, without Door Frame Kit
Motor Operator 
24 Vdc, with ARMS)
M = Manually Operated Operations Counter, Padlocking
B = 110 – 125 Vac
or Key Lock Provisions 
W = 110 – 125 Vdc
T = 208 – 240 Vac N = None
P = 220 – 250 Vdc
Trip Indicator & Bell Alarm/OTS,
Spring Release, Latch Check Switch  Secondary Terminal Blocks 
N = None (No LCS) N = No Indicator, No OTS, Secondary Terminal Blocks
A = 110 – 125 Vac/Vdc (No LCS) per Breaker Options
R = 208 – 250 Vac/Vdc (No LCS) X = Trip Indicator Provided, No OTS, Secondary
Terminal Blocks per Breaker Options
Z = Trip Indicator Provided, 2 Form-C OTS,
Undervoltage Release (UVR),
Secondary Terminal Blocks per Breaker Options
Second Shunt Trip 
1 = No Indicator, No OTS, Full-Complement of
N = None Secondary Terminal Blocks
A = 110 – 125 Vac/Vdc UVR 2 = Trip Indicator Provided, No OTS,
R = 220 – 250 Vac/Vdc UVR Full-Complement of Secondary Terminal Blocks
1 = 110 – 125 Vac/Vdc Second Shunt Trip 3 = Trip Indicator Provided, 2 Form-C OTS,
2 = 208 – 250 Vac/Vdc Second Shunt Trip Full-Complement of Secondary Terminal Blocks

Auxiliary Switches, Breaker Label Language 


E = No Auxiliary Switch, English
2 = 2 Form-C, English
4 = 4 Form-C, English

 Contact Eaton for available voltages. Not all voltages are currently available.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-21
Power Circuit Breakers
December 2008
Product Selection

Table 13-12. Series NRX Cassette Style Number Format

NX 12 3 F A D N S N N N C

Cassette Family & Breaker Frame Arc Hood Cassette Shipping


NS = UL 1066 N-Frame A = Arc Hood Installed C = Cassette Only
NX = UL 489 N-Frame (Default) B = Breaker Shipped in Cassette
NE = IEC N-Frame
Door Frame Gasket Kit Future
Continuous Ampere Range & Rejection Kit
N = None
08 = 800 Amperes (UL 1066) D = Door Kit Included (Default),
12 = 800 – 1200 Amperes (UL 489) No Rejection Kit
N = Not Included, Future
16 = 630 – 1600 Amperes (IEC)
No Rejection Kit N = None
B = Door Kit Included (Default),
Poles & Phasing
With Rejection Kit
(Facing Front of Breaker) Secondary Contact Terminals Installed
R = Not Included,
3 = 3-Pole ABC With Rejection Kit N = None
4 = 4-Pole NABC F = Full Complement
B = Defined by Breaker
Accessory Switches —
Load Terminal Connections TOC (Truck Operated Cell), Other
F = With Flat Tapped Pads Only N = Not Included (Default)
Shutters 13
G = With Vertical/Horizontal Bus Adapter Kit (Short Style) N = Not Included (Default)
H = With Front Connected Kit S = Included
N = No Cassette Stabs (Interunit Only)

CA08101001E For more information visit: www.eaton.com


13-22 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Technical Data

Technical Data
Table 13-13. UL 1066 Ratings Table 13-14. UL 489 Ratings
Description Rating Description Rating

Continuous Current Rating (Amps) 800 Continuous Current Rating (Amps) 800 1200
Short Circuit Rating (kA) Short Circuit Rating (kA)
254 Vac 85 240 Vac 85 85
508 Vac 65 480 Vac 65 65
635 Vac 42 600 Vac 42 42
Short Time Withstand (kA) 42 Short Time Withstand (kA) 42 42

Table 13-15. IEC 60947-2 Ratings


Description Rating

Continuous Current Rating (Amps) 630 & 800 1000 & 1250 1600
Short Circuit Rating (kA) Icu Ics Icu Ics Icu Ics
240/254 Vac 85 50 85 50 85 50
415/435 Vac 65 50 65 50 65 50
690/725 Vac 42 42 42 42 42 42
Short Time Withstand = Icw (kA) 42 42 42 42 42 42

Accessory Tables
Table 13-16. Shunt Trip
Control Frequency Operational Voltage Inrush/Continuous Power Opening Time
Voltages Range 70% – 110% Consumption (VA) (ms)
13 24 dc 17 – 26 500/5 25
48 dc 34 – 53 530/5 25
110 – 127 5 – 60 Hz 77 – 140 540/5 25
110 – 125 dc 77 – 138 540/5 25
208 – 240 50 – 60 Hz 146 – 264 500/5 25
220 – 250 dc 154 – 275 515/5 25

Table 13-17. UVR


Control Frequency Operational Voltage Dropout Volts Inrush/Continuous Power Opening Time
Voltages Range 85% – 110% 35% – 60% Consumption (VA) (ms)

24 dc 20 – 26 8 – 14 500/5 50
32 dc 27 – 35 11 – 19 620/5 50
48 dc 41 – 53 17 – 29 850/5 50
110 – 127 50 – 60 Hz 94 – 140 44 – 94 890/5 50
110 – 125 dc 94 – 138 44 – 94 890/5 50
208 – 240 50 – 60 Hz 177 – 264 84 – 125 910/5 50
220 – 250 dc 187 – 275 88 – 132 910/5 50
380 – 415 ac 323 – 457 145 – 228 960/5 50
480 ac 408 – 528 168 – 288 800/8 50
600 ac 510 – 660 210 – 360 800/12 50

Table 13-18. Spring Release


Control Frequency Operational Voltage Inrush Power Closing Time
Voltages Range 70% – 110% Consumption (VA) (ms)

24 dc 17 – 26 500 25
48 dc 34 – 53 530 25
110 – 127 50 – 60 Hz 77 – 140 540 25
110 – 125 dc 77 – 138 540 25
208 – 240 50 – 60 Hz 146 – 264 500 25
220 – 250 dc 154 – 275 515 25

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-23
Power Circuit Breakers
December 2008
Technical Data

Table 13-19. OCT/OTS Table 13-20. Auxiliary Switch Table 13-21. Breaker Position/Continuity
Control Frequency Contact Rating Control Frequency Contact Rating Breaker Continuity Continuity
Voltages (Amperes) Voltages (Amperes) Position Between Red Between Blue
and Black and Black
250 50 – 60 Hz 10 250 50 – 60 Hz 10 Lead Pairs Lead Pairs
125 dc 0.5 125 dc 0.5
Open NO 45 and 43
250 dc 0.25 250 dc 0.25
46 and 47
51 and 49
52 and 53
Closed 44 and 43 NO
48 and 47
50 and 49
54 and 53

Table 13-22. Motor Operator


Control Frequency Operational Running Current Typical Inrush Power Consumption Maximum
Voltages Voltage Range (A) Current (VA) Charging
85% – 110% Time (sec)

24 dc 20 – 26 5 500% 150 3
48 dc 41 – 53 3 500% 150 3
110 – 127 50 – 60 Hz 94 – 140 2 300% 280 3
110 – 125 dc 94 – 138 1 500% 150 3
208 – 240 50 – 60 Hz 177 – 264 1 1000% 280 4
220 – 250 dc 187 – 275 1 1000% 280 4

Table 13-23. Control Voltages and Currents


13
Control Voltages 24 Vdc 48 Vdc 110 – 125 Vdc 110 – 127 Vac 220 – 250 Vdc 208 – 240 Vac
Current
Close Current (inrush) 21 11 5 5 2 2
Shunt Trip Current (ST) — (inrush/continuous) 21 / .2 11 / .1 5 / .04 5 / .04 2 / .02 2 / .02
Charge Motor Current — (inrush/continuous) TBD TBD 5/1 6/2 10 / 1 10 / 1
Operating Voltage Rating
Close 17 – 26 34 – 53 77 – 138 77 – 140 154 – 275 146 – 264
Trip 17 – 26 34 – 53 77 – 138 77 – 140 154 – 275 146 – 264
Charge 20 – 26 41 – 53 94 – 138 94 – 140 187 – 275 177 – 264

CA08101001E For more information visit: www.eaton.com


13-24 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Medium Voltage Power Contactors

Medium Voltage Breakers VCP-W Standard Features VCP-T Standard Features


■ Eaton’s maintenance-free Cutler- ■ Grounded steel barrier between
Hammer vacuum interrupters with mechanism and primary conductors.
visual contact erosion indicator. ■ Spring loaded, silver-plated primary
■ Patented non-sliding/non-rolling disconnects (drawout breaker).
V-flex current transfer system. ■ Silver-plated primary connections
■ Glass polyester insulation. (fixed circuit breaker).
■ Cycloaliphatic Epoxy Insulation ■ Manual charging of closing springs
(optional with Type VCPW-SE (includes shunt trip).
breakers) for 27 kV and 38 kV ■ Integral spring charging handle.
breakers. ■ Auxiliary switch (5a and 5b contacts).
■ Front-accessible operating ■ Mechanical operations counter.
mechanism.
■ 24, 48, 125 and 250 Vdc, 120 and
■ Electrically operated trip-free, spring 240 Vac control.
stored energy mechanism.
Type VCP-W/VCP-T Medium Voltage ■ Shunt trip.
■ Interlocks which prevent moving
Vacuum Circuit Breaker ■ ON and OFF pushbuttons.
a closed circuit breaker into or out
of the connected position. ■ Integral lifting hooks.
Product Description
■ Closing springs automatically ■ Through or behind door operation.
Breakers and structures for switchgear discharge before moving the circuit ■ Identified/dedicated secondaries.
assemblies: breaker into or out of the enclosure. ■ Secondary umbilical cord
■ ANSI 4.76 kV, 8.25 kV, 15 kV, 27 kV ■ Provisions for manual charging of (drawout circuit breaker).
and 38 kV: closing springs. ■ Secondary disconnect block
❑ 250 to 1500 MVA ■ Manual close and trip pushbuttons. (fixed circuit breaker).
❑ IEC 3.6 kV thru 17.5 kV ■ Operations counter. ■ Two-step stored energy mechanism.
13 ❑ 16 kA to 63 kA ■ Closing spring charged/discharged ■ O – 0.3s – CO – 15s – CO.
indicator. ■ Anti-pump.
■ Metal-clad, compartmented design.
■ Circuit breaker Open/Closed ■ Trip free.
■ Power modules. indicator.
■ Mini modules. ■ Latch check switch.
■ Auxiliary switch with 2A/3B for dc
■ Breaker compartment kits. ■ Visible contact erosion indicator.
and 1A/3B for ac spare contacts.
■ Visible contact wipe indicator.
■ Spring charging motor, close coil,
Application Description trip coil, latch check switch, and ■ Disconnect, Test and Connect
Eaton’s Cutler-Hammer Type VCP-W, anti-pump relay. (drawout circuit breaker).
VCP-T, T-VAC and W-VAC vacuum ■ Integral levering mechanism
breakers provide centralized control (drawout circuit breaker).
and protection of medium voltage ■ Field installable accessories.
power equipment and circuits in
industrial, commercial and utility Standards and Certifications
installations involving generators,
■ Designed, tested and certified
motors, feeder circuits, and transmis-
in accordance with ANSI and IEC
sion and distribution lines.
standards.
■ Applicable ANSI standards
C37.04-1979 or 1999, C37.09-1979
or 1999, C37.06-2000 and C37.013.
■ Internal arc resistance tested
to IEC 298, Appendix AA, 25 kA
for 1 second.
■ Drawout circuit breaker fully
qualified to IEC 56 by testing inside
the IEC 298 switchgear cubicle.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-25
Power Circuit Breakers
December 2008
Medium Voltage Power Contactors

ANSI Standards
Table 13-24. ANSI Standard Ratings  — VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis
Identification Rated Values Weight
Circuit Voltage Insulation Current Current Values
Breaker Level

Permissible Tripping Delay


Nominal 3-Phase MVA Class
Type

Voltage Range Factor 


Withstand Contin- Short Maximum Closing Closing and
Test uous Circuit Symmetrical and Latching
Nominal Voltage Class

Voltage Current Current Interrupting Latching Momentary

Maximum Voltage

Maximum Voltage
at 60 Hz (at Rated Capability Capability Capability

Divided by K 
Power Frequency

Interrupting Time
Max. kV)
Short Time
Current 

Impulse
E K (1 Min.) I Y E/K Kx1
kV MVA kV kV kV Amperes kA Cycles Seconds kV kA rms kA Peak kA rms Total Lbs. (kg)
rms rms Peak rms rms

50 VCP-WND250 4.16 250 4.76 1.24 19 60 1200 29 5 2 3.85 36 97 58 345 (157)


50 VCP-W250 4.16 250 4.76 1.24 19 60 1200 29 5 2 3.85 36 97 58 350 (159)
2000 410 (186)
3000 525 (238)
50 VCP-W350 4.16 350 4.76 1.19 19 60 1200 41 5 2 4.0 49 132 78 460 (209)
2000 490 (223)
3000 525 (238)
50 VCP-W500 4.16 — 4.76 1.00 19 60 1200 63 5 2 4.76 63 170 101 525 (238)
(63 kA) 2000 530 (241)
3000 550 (250)
75 VCP-W500 7.2 500 8.25 1.25 36 95 1200 33 5 2 6.6 41 111 66 375 (170)
2000 410 (186) 13
3000 525 (238)
150 VCP-W500 13.8 500 15 1.30 36 95 1200 18 5 2 11.5 23 62 37 350 (159)
2000 97 58 410 (186)
Standard Circuit Breakers 

3000 525 (238)


150 VCP-W750 13.8 750 15 1.30 36 95 1200 28 5 2 11.5 36 97 58 350 (159)
2000 130 77 410 (186)
3000 525 (238)
150 VCP-W1000 13.8 1000 15 1.30 36 95 1200 37 5 2 11.5 48 130 77 460 (209)
2000 490 (223)
3000 525 (238)
150 VCP-W1500 13.8 — 15 1.00 36 95 1200 63 5 2 15.0 63 170 101 525 (238)
(63 kA) 2000 530 (241)
3000 550 (250)
50 VCP-W25C 4.16 — 5.95 1.00 24 75 1200 25 3 2 5.95 25 97 58 350 (159)
2000 410 (186)
3000 525 (238)
50 VCP-W40C 4.16 — 5.95 1.00 24 75 1200 40 3 2 5.95 40 139 83 460 (209)
2000 490 (223)
3000 525 (238)
50 VCP-W50C 4.16 — 5.95 1.00 24 75 1200 50 3 2 5.95 50 139 83 525 (238)
2000 530 (241)
3000 550 (250)
50 VCP-W63C 4.16 — 5.95 1.00 24 75 1200 63 3 2 5.95 63 175 104 350 (159)
2000 410 (186)
3000 525 (238)
75 VCP-W50C 7.2 — 10.3 1.00 42 95 1200 50 3 2 10.3 50 139 83 460 (209)
2000 490 (223)
3000 525 (238)
150 VCP-W25C 13.8 — 17.5 1.00 42 95 1200 25 3 2 17.5 25 97 58 350 (159)
2000 410 (186)
Extra Capability Breakers 

3000 525 (238)


150 VCP-W40C 13.8 — 17.5 1.00 42 95 1200 40 3 2 17.5 40 139 83 350 (159)
2000 410 (186)
Tested for 3 Seconds

3000 525 (238)


150 VCP-W50C 13.8 — 17.5 1.00 42 95 1200 50 3 2 17.5 50 139 83 460 (209)
2000 490 (223)
3000 525 (238)
150 VCP-W63C 13.8 — 15.0 1.00 42 95 1200 63 3 2 15.0 63 175 104 525 (238)
2000 530 (241)
3000 550 (250)
 Applicable ANSI Standards C37.04-1999, C37.06-2000 (including both K >1 and K =1 ratings) and C37.09-1999.
 See Consulting Application Guide for further information.

CA08101001E For more information visit: www.eaton.com


13-26 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Medium Voltage Power Contactors

Table 13-24. ANSI Standards  — VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis (Continued)
Identification Rated Values Weight
Circuit Voltage Insulation Current Current Values
Breaker Level

Permissible Tripping Delay


Nominal 3-Phase MVA Class
Type Withstand Contin- Short Maximum Closing Closing and

Voltage Range Factor


Test uous Circuit

Maximum Voltage 
Symmetrical and Latching
Nominal Voltage Class

Maximum Voltage
Voltage Current Current Interrupting Latching Momentary
at 60 Hz (at Rated Capability Capability Capability

Power Frequency

Interrupting Time
Max. kV)

Divided by K
Short Time
Current 

Impulse
(1 Min.)
E K I Y E/K Kx1
kV MVA kV kV kV Amperes kA Cycles Seconds kV kA rms kA Peak kA rms Total Lbs. (kg)
rms rms Peak rms rms
Generator Breakers (to ANSI C37.013)

50 VCP-WG50 4.16 — 4.76 1.00 19 60 1200 50 3 1 4.76 50 137 82 525 (238)


2000 530 (241)
3000 550 (250

50 VCP-WG63 4.16 — 4.76 1.00 19 60 1200 63 3 1 4.76 63 173 103 525 (238)
2000 530 (241)
3000 550 (250

Tested for 3 Seconds


150 VCP-WG50 13.8 — 15.0 1.00 36 95 1200 50 3 1 15.0 50 137 82 525 (238)
2000 530 (241)
3000 550 (250)

150 VCP-WG63 13.8 — 15.0 1.00 36 95 1200 63 3 1 15.0 63 173 103 525 (238)
2000 530 (241)
13 
3000 550 (250)
Applicable ANSI Standards C37.04-1999, C37.06-2000 (including both K >1 and K =1 ratings), and C37.09-1999.
 See Consulting Application Guide for further information.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-27
Power Circuit Breakers
December 2008
Medium Voltage Power Contactors

Table 13-25. VCP-W Vacuum Breaker Types rated on Symmetrical Current Rating Basis 
Identification Rated Values Weight
Circuit Voltage Insulation Current Transient Current
Breaker Level Recovery Values
Type Voltage

Maximum Permissible
Short Circuit Current
Withstand E2 T2

Capacitor Switching
Continuous Current

(at Rated max. kV) I

Latching Capability

Rated Short Circuit


Test Voltage
Nominal 3-Phase

Tripping Delay Y

Cable Charging
Voltage Range
Voltage Class

(2.6 K Times
Interrupting

Closing and
MVA Class

Frequency
Maximum
Nominal

Factor 

Current)
at 60 Hz
Impulse
Voltage

(1 min.)
Power

Time

K
E

kV MVA kV rms kV rms kV Peak Amperes kA rms ms (Cy) Seconds kV Peak µs kA Peak Amperes lbs.

270 VCP-W750 27 750 27  1.0 60 125 600 16 83 (5)  2 51 105 ¥43 31.5 460
1200 480
2000 500
270 VCP-W1000 27 1000 27  1.0 60 125 600 22 83 (5)  2 51 105 60 31.5 460
1200 480
2000 500
270 VCP-W1250 27 1250 27  1.0 60 125 600 25 83 (5)  2 51 105 68 31.5 460
1200 480
2000 500
270 VCP-W1600 27 1600 27  1.0 60 125 1200 25 83 (5)  2 51 105 85 31.5 545
2000 560
270 VCP-W2000 27 2000 27  1.0 60 125 1200 40 83 (5)  2 51 105 106 31.5 545
2000 600
270 VCP-W25C 27 — 27 1.0 60 125 1200 25 50 (3) 2.5 50 50 85 31.5 545
1600 560 13
270 VCP-W32C 27 — 27 1.0 60 125 1200 31.5 50 (3) 1.6 50 50 100 31.5 545
1600 560
270 VCP-W40C 27 — 27 1.0 60 125 1200 40 50 (3) 1.0 50 50 112 31.5 545
1600 560
 CESI tested to applicable ANSI standards C37.04, C37.09 and C37.06. Consult Eaton for CESI copies of test reports on file. Operating duty cycle CO-15
seconds-CO. Operating time values: Opening 33 – 55 ms, closing 50 – 60 ms and reclosing 18 cycles (300 ms).
 Tested at 28.5 kV.
 K = 1.0, therefore E = E/K and I = KI.
 Also maximum interrupting rating and short-time current rating.
 Duration of short-time current = 3 seconds, except as noted in
 Optional interrupting time of 50 ms (3 cycles) is available.

CA08101001E For more information visit: www.eaton.com


13-28 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Medium Voltage Power Contactors

IEC Standards
Table 13-26. IEC Standards  — VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis
Identification Rated Values Weight
Circuit Voltage Insulation Level Normal Short Circuit Short Cable
Breaker Power Impulse Current Breaking Circuit Charging
Type Frequency Withstand Current and Making Breaking
3-Second Current Current
Short Time
Current
kV rms kV rms Peak kV Peak Amperes kA rms kV Peak Amperes Lbs. (kg)

36 VCP-WND25 3.6 10 40 630 25 65 10 350 (159)


1250
36 VCP-WND32 3.6 10 40 630 31.5 82 10 350 (159)
1250
72 VCP-WND25 7.2 20 60 630 25 65 10 350 (159)
1250
72 VCP-WND32 7.2 20 60 630 31.5 82 10 350 (159)
1250
36 VCP-W25 3.6 10 40 630 25 65 10 414 (188)
1250 430 (195)
2000 496 (225)
36 VCP-W32 3.6 10 40 1250 31.5 82 10 414 (188)
2000 496 (225)
36 VCP-W40 3.6 10 40 1250 40 104 10 496 (225)
2000 550 (250)
72 VCP-W25 7.2 20 60 630 25 65 10 414 (188)
1250 414 (188)
2000 496 (225)
13 72 VCP-W32 7.2 20 60 1250 31.5 82 10 414 (188)
2000 430 (195)
72 VCP-W40 7.2 20 60 1250 40 104 10 430 (195)
2000 496 (225)
120 VCP-W25 12.0 28 75 630 25 65 25 430 (195)
1250 496 (225)
2000 496 (225)
120 VCP-W32 12.0 28 75 1250 31.5 82 25 430 (195)
2000 496 (225)
120 VCP-W40 12.0 28 75 1250 40 104 25 496 (225)
2000 550 (250)
175 VCP-W25 17.5 38 95 630 25 65 — 430 (195)
1250 496 (225)
2000 496 (225)
175 VCP-W32 17.5 38 95 1250 31.5 82 — 430 (195)
2000 496 (225)
175 VCP-W40 17.5 38 95 1250 40 104 — 496 (225)
2000 550 (250)
175 VCP-W50 17.5 38 95 1250 50 130 — 1013 (460)
2000 1079 (490)
3150 1156 (525)
 IEC Standards 60056 and 60694 apply.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-29
Power Circuit Breakers
December 2008
Medium Voltage Power Contactors

Type VCP-W Vacuum Circuit Breaker Ratings


Table 13-27. Type VCP-W Ratings on Symmetrical Current Rating Basis 
Identification Rated Values
Circuit Voltage Insulation Current Interr-
Breaker Level upting
Type Withstand Test Short Circuit Current Time


Max. Asym. Interrupting

Max. Asym. Interrupting

Mechanical Endurance
Maximum Permissible
Sym. Interrupting at V

Asym. Interrupting (It)


% dc Component (Idc)

Withstand Capability
Closing and Latching

Momentary Current
Continuous Current

Short Time Current

Short Time Current

Transient Recovery
at V/K (SxKxlsc) 
Lightning Impulse
Power Frequency

Rated Reclosing
at V/K (Kxlsc) 

Voltage (RRRV)
Tripping Delay
Voltage Class

Asym. Factor S (Ref.)

Duration of
Maximum

(1 Minute)

at 60 Hz 

Capability
Voltage V

Factor (R)
Range Factor K 

1.2x50 
Nominal

Operating Duty
(Isc)
V/K

(Duty Cycle)

Voltage

kV kV kV kV kV Amps kA % kA kA kA kA kA kA s % Sec. kV/ 

Cyc.
rms rms rms rms Peak rms rms rms rms rms Peak rms rms µs

rms
Total Total Total

380 VCP-W 6 34.5 38 1 38 80 170 600 16 47 1.2 19.2 16 19.3 43 26 16 3


100 83 5 2 0.6
and 1200

2000
380 VCP-WR 16 1600
2000
380 VCP-W 25 34.5 38 1 38 80 170 600 25 47 1.2 30.0 25 30.0 68 40 25 3
100 83 5 2 0.6
and 1200

2000
380 VCP-WR 25 1600
2000
380 VCP-W 32 34.5 38 1 38 80 170 600 31.5 47 1.2 37.8 31.5 37.8 85 50 31.5 3
100 83 5 2 0.6
and 1200
380 VCP-WR 32 1600
2000
13
3000FC

2000
2500 —
380 VCP-W 21 34.5 38 1.65 23 80 170 1200 21 47 1.2 39.5 35 42.0 95 56 35 3
100 83 5 2 0.6
and   2000 
380 VCP-WR 21 3000FC

2000
2500 —
380 VCP-W 40 34.5 38 1 38 80 170 1200 40 47 1.2 48.0 40 48.0 107 63 40 3 100 83 5 2 0.6
and 2000

2000
380 VCP-WR 40 3000FC
2500
 KEMA tested to applicable ANSI standards C37.04-1979, C37.09-1979 and C37.06-1979 (operating duty sequence CO - 15s - CO). Typical operating time
values: operating 45 ms, closing 75 ms and reclosing 300 ms (18 cycles).
 The standard breaker is not rated for capacitor switching. If you require capacitor switching, please refer to the “C” breakers.
 K = 1.0, therefore E = E/K and I = KI. Refer to the Consulting Application Guide for more information.
 The ANSI C37.06 standard requires 150 kV BIL. If higher BIL levels are required, please refer to the “C” breakers.
 For force air cooled fixed breaker applications, consult Eaton.
 If you require 50 ms (3 cycle) interrupting time, please refer to the “C” breakers.
 No-load operations.
 At 23 kV rms (rated maximum voltage/K). Rated maximum symmetrical interrupting capability = 35kA rms (K x 1).
CO – 15s – CO.

Rated and tested also for rapid reclosing capability O - 0.3s - CO.
Not rated for rapid reclosing.

CA08101001E For more information visit: www.eaton.com


13-30 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Medium Voltage Power Contactors

T-VAC and T-VACR Vacuum Breaker Ratings Table 13-29. T-VAC and T-VACR Ratings (Certified to IEC62271-100)
Table 13-28. VCP-T and VCP-TR Ratings (ANSI C37.04 and C37.09) Identification Rated Values
Circuit Insulation Level
Identification Rated Values Breaker

Withstand Voltage

Withstand Voltage
Lightning Impulse
Circuit Insulation Level Type

Power Frequency
Breaking Current

Breaking Current
Making Current

Making Current
Short Circuit 
Breaker

Short Circuit 
Short Circuit
Type

Short Circuit
Continuous

Mechanical

Current (In)

Mechanical
Endurance
Frequency

Withstand

Endurance
Impulse
Voltage

Current

Voltage

Normal
Power
Class

Class
C–0

(Uw)

C–0
(Isc)
kV kV kV Amp- kA kA Oper- kV kV kV Amp- kA kA Oper-
rms rms Peak eres rms Peak ations rms rms Peak eres rms Peak ations

50 VCP-T16 4.76 19 60 600 16 42 20,000 72 T-VAC16 7.2 20 60 630 16 40 20,000


and 800 20,000 and 800 20,000
50 VCP-TR16 1200 10,000 72 T-VACR16 1250 10,000
1600  10,000 1600  10,000
50 VCP-T20 4.6 19 60 600 16 52 10,000 72 T-VAC20 7.2 20 60 630 20 50 10,000
and 800 10,000 and 800 10,000
50 VCP-TR20 1200 10,000 72 T-VACR20 1250 10,000
1600  10,000 1600  10,000
50 VCP-T25 4.76 19 60 600 25 65 10,000 72 T-VAC25 7.2 20 60 630 25 63 10,000
and 800 10,000 and 800 10,000
50 VCP-TR25 1200 10,000 72 T-VACR25 1250 10,000
1600  10,000 1600  10,000
75 VCP-T16 8.25 20 60  600 16 42 20,000 120 T-VAC16 12 28 75  630 16 40 20,000
and 800 20,000 and 800 20,000
75 VCP-TR16 1200 10,000 120 T-VACR16 1250 10,000
1600  10,000 1600  10,000
75 VCP-T20 8.25 20 60  600 20 52 10,000 120 T-VAC20 12 28 75  630 20 50 10,000
13 and
75 VCP-TR20
800
1200
10,000
10,000
and
120 T-VACR20
800
1250
10,000
10,000
1600  10,000 1600  10,000
75 VCP-T25 8.25 20 60  600 25 65 10,000 120 T-VAC25 12 28 75  630 25 63 10,000
and 800 10,000 and 800 10,000
75 VCP-TR25 1200 10,000 120 T-VAC25 1250 10,000
1600  10,000 1600  10,000
150 VCP-T16 15 36 95 600 16 42 10,000 175 T-VAC16 17.5 38 95 630 16 40 10,000
and 800 10,000 and 800 10,000
150 VCP-TR16 1200 10,000 175 T-VACR16 1250 10,000
1600  10,000 1600  10,000
150 VCP-T20 15 36 95 600 20 52 10,000 175 T-VAC20 17.5 38 95 630 20 50 10,000
and 800 10,000 and 800 10,000
150 VCP-TR20 1200 10,000 175 T-VACR20 1250 10,000
1600  10,000 1600  10,000
150 VCP-T25 15 36 95 600 25 65 10,000 175 T-VAC25 17.5 38 95 630 25 63 10,000
and 800 10,000 and 800 10,000
150 VCP-TR25 1200 10,000 175 T-VACR25 1250 10,000
1600  10,000 1600  10,000
 Use 15 kV breaker and cassette when 95 kV impulse withstand required.  Use 17.5 kV breaker and cassette when 95 kV impulse withstand required.
 1600 A VCP-T breaker available.  1600 A T-VAC breaker available.
 Also 2 second short time current rating.  Also 3 second short time current rating.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-31
Power Circuit Breakers
December 2008
Medium Voltage Power Contactors

Technical Data and Specifications

Mini Module Type VCP-W Circuit Breaker VCP-W Circuit Breaker with Deadfront
Shown from Rear Panel Removed

5/15 kV VCPW-ND and VCP-W Power Modules — Dimensions in Inches (mm)

13

Figure 13-2. Power Module, 5/15 kV VCPW-ND 26.00 (660) Wide, VCP-W 36.00 (914) Wide
 VCPW-ND Dimensions of Breaker Travel 15.00 (381.0 mm).

CA08101001E For more information visit: www.eaton.com


13-32 Power Breakers, Contactors & Fuses
Power Circuit Breakers
December 2008
Medium Voltage Power Contactors

5/15 kV VCPW-ND and VCP-W Mini Modules — Dimensions in Inches (mm)

13
Figure 13-3. 5 kV VCPW-ND Mini Module 25.88 (657) Wide
 Current transformers not supplied.

5/15 kV VCP-W Mini Module — Dimensions in Inches (mm)

Figure 13-4. 5/15 kV VCP-W Mini-Module 35.88 (911) Wide


 Current transformers not supplied.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-33
Medium Voltage Power Contactors
December 2008
Product Description

SL MV Power Contactor Fully applicable to: Options and Accessories


■ Full voltage starting.
7.2 kV/160 – 400 Amperes
■ Reduced voltage starting. SL Series — Accessory Kits
The perfect choice for harsh duty Mechanical Latch Kit — SL Vacuum
applications: Contactor Sizes 7.2 kV/160 – 400 Amperes
■ Mining. Field Mount to 7.2 kV/60 – 400 amperes
■ Pulp and paper. SL Vacuum Contactor. Coil voltages
■ HVAC. available in a wide range of ac and dc
■ Petrochemical. selections. Easy to install on new and
existing units.
■ Automotive.
■ Many others.

Features, Benefits
and Functions
SL Medium Voltage Contactor The SL Contactor Ratings
■ Voltages of 2200 – 7200 volts.
Product Description ■ Amperages from 160 – 400 amperes.
■ Interrupting ratings as high as
■ A single family of contactors for any 8500 amperes.
medium voltage control application.
Mechanical Latch Kit
Voltage range of 2200 to 7200 volts. Control Voltages (Field Adjustable)
■ Ampere ratings from 160 through ■ 110, 220 Vac 50 Hz. Auxiliary Contact Kit — SL Vacuum
400 amperes with Induction Motor ■ 120, 240 Vac 60 Hz. Contactor Sizes 7.2 kV/160 – 400 Amperes
Horsepower ranges from 600 to
5500 hp.
■ 125 Vdc. Field Mount auxiliary contact kits for 13
7.2 kV/160 – 400 amperes SL Vacuum
■ Three different altitude versions. Drop-out Time (Field Adjustable) Contactor. Contact kits are available in
■ Leading-edge vacuum technology. ■ 30 ms many configurations of NO-NC.
■ Fully complies with global ■ 50 ms
standards. ■ 130 ms
■ Third-party qualified by UL, ■ 250 ms
CSA, KEMA. ■ 330 ms
■ Long life — 300,000 electrical
and over 2 million mechanical. Global Acceptability
■ Mounting flexibility — panel or ■ NEMA
pedestal mounting provisions are ■ ANSI
standard. Unit can be mounted in ■ IEC
horizontal or vertical position.
■ Field-selectable settings for Third-Party Verification
coil voltage, ac/dc, and coil ■ UL
dropout time. ■ CSA
■ Field kits available for auxiliary ■ KEMA Auxiliary Contact Kit
contacts and mechanical latch.
Accessories are common for Easy-to-Install Option Kits (Field Addition) Mechanical Interlock Kit
all sizes. ■ Up to 6 extra auxiliary contacts. Field Mount mechanical interlock
■ Special ordering allows unit to ■ Mechanical latch — many coil kits for 7.2 kV/160 – 400 amperes SL
be factory pre-set to customer voltages. Vacuum Contactor.
specification, including field kit
installation. Long Life Guarantees High Quality
■ Highest quality available — all ■ 300,000 electrical operations.
contactors manufactured within ■ 2.5 million mechanical operations.
state-of-the-art “ISO-Certified”
facilities. 100% made in America.
Standards and Certifications
Application Description Design and Test Standards
Eaton’s Cutler-Hammer SL Medium Voltage ■ UL 347, File No. E63257.
Contactor starting applications: ■ CSA T.I.L. D-21, File No. LR28548.
■ Squirrel-cage induction motors. ■ IEC No. 60470.
■ Synchronous motors. ■ ANSI/NEMA ICS 3 – 1993 (R2000)
■ Wound-rotor. Mechanical Interlock Kit

CA08101001E For more information visit: www.eaton.com


13-34 Power Breakers, Contactors & Fuses
Medium Voltage Power Contactors
December 2008
Product Description

SL MV Power Contactor Application Description Standards and Certifications


7.2 kV/800 Amperes Eaton’s Cutler-Hammer SL Medium Voltage Design and Test Standards
Contactors starting applications:
■ UL 347, File No. E63257.
■ Squirrel-cage induction motors.
■ CSA T.I.L. D-21, File No. LR28548.
■ Synchronous motors.
■ ANSI/NEMA ICS 3 – 1993 (R2000)
■ Wound-rotor.
■ IEC 60470
Fully applicable to:
■ Full voltage starting. SL Series — Accessory
■ Reduced voltage starting. Options 800 Amperes
The perfect choice for harsh duty
applications:
■ Mining.
■ Pulp and paper.
■ HVAC.
SL Medium Voltage Contactor ■ Petrochemical.
■ Automotive.
Product Description ■ Many others.
■ A single family of contactors for
any medium voltage control appli- Features, Benefits
cation. Voltage range of 2200 to and Functions
7200 volts.
■ Ampere rating of 800 amperes with The SL Contactor Ratings
13 Induction Motor Horsepower ranges
from 3000 to 10,000 hp.
■ Voltages of 2200 – 7200 volts.
■ 800 amperes (720 amperes
■ Two different altitude versions. enclosed).
■ Leading-edge vacuum technology. ■ Interrupting rating of
■ Third-party qualified by UL, 12,500 amperes.
CSA, KEMA.
Control Voltages
■ Long life — 100,000 electrical
and 300,000 mechanical. ■ 110, 220 Vac 50 Hz.
■ Special ordering allows unit to ■ 120, 240 Vac 60 Hz.
be factory pre-set to customer ■ 125 Vdc.
specification, including field kit
installation. Drop-out Time
Mechanical Latch Assembly 800 Amperes
■ Highest quality available — all ■ 130 – 330 ms
contactors manufactured within Mechanical Latch Option — SL
Acceptability Vacuum Contactor Size 800 Ampere
state-of-the-art “ISO-Certified”
■ NEMA Factory installed for 800 ampere
facilities. 100% made in America.
■ ANSI SL Vacuum Contactor. Coil voltages
■ IEC available in a wide range of ac and
dc selections.
Third-Party Verification
■ UL
■ CSA
■ KEMA

Factory Installed Option Kit


■ Mechanical latch — many coil
voltages.
Long Life Guarantees High Quality
■ 100,000 electrical operations.
■ 300,000 mechanical operations.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-35
Medium Voltage Power Contactors
December 2008
Product Description

SL MV Power Contactor Application Description Standards and Certifications


15 kV/250 Amperes Eaton’s Cutler-Hammer SL Medium Voltage Design and Test Standards
Contactors starting applications:
■ UL 347, File No. E63257.
■ Squirrel-cage induction motors.
■ CSA T.I.L. D-21, File No. LR28548.
■ Synchronous motors.
■ ANSI/NEMA ICS 3 – 1993 (R2000)
■ Wound-rotor.
■ IEC 60470
Fully applicable to:
■ Full voltage starting. SL Series — Accessory
■ Reduced voltage starting. Options 15 kV/250 Amperes
The perfect choice for harsh duty
applications:
■ Mining.
■ Pulp and paper.
■ HVAC.
■ Petrochemical.
SL 15 kV/250 Ampere Medium Voltage ■ Automotive.
Contactor ■ Many others.

Product Description Features, Benefits


■ A single family of contactors for and Functions
any medium voltage control appli-
The SL Contactor Ratings
cation. Voltage range of 7200 to
15,000 volts. ■ Voltages to 15,000 volts. 13
■ Ampere rating of 250 amperes with ■ 250 amperes.
Induction Motor Horsepower ranges ■ Interrupting rating of 5000 amperes.
from 500 to 5000 hp.
Control Voltages
■ Two different altitude versions.
■ 110, 220 Vac 50 Hz.
■ Leading-edge vacuum technology.
■ 120, 240 Vac 60 Hz.
■ Third-party qualified by UL,
■ 125 Vdc.
CSA, KEMA.
■ Long life — 250,000 electrical Drop-out Time
and mechanical. ■ 50 – 330 ms
■ Special ordering allows unit to ■ Field Selectable
be factory pre-set to customer Mechanical Latch Assembly
specification, including field kit Acceptability 15 kV/250 Amperes
installation. ■ NEMA Mechanical Latch Option —
■ Highest quality available — all ■ ANSI SL Vacuum Contactor
contactors manufactured within ■ IEC Factory installed for 15 kV/250 ampere
state-of-the-art “ISO-Certified” SL Vacuum Contactor. Coil voltages
facilities. 100% made in America. Third-Party Verification available in a wide range of ac and
■ UL dc selections.
■ CSA
■ KEMA

Factory Installed Option Kit


■ Mechanical latch — many coil
voltages.
Long Life Guarantees High Quality
■ 250,000 electrical operations.
■ 250,000 mechanical operations.

CA08101001E For more information visit: www.eaton.com


13-36 Power Breakers, Contactors & Fuses
Medium Voltage Power Contactors
December 2008
SL Series Fuses

SL Series Fuses
Table 13-30. Fuse Application Table for SL Contactors Table 13-30. Fuse Application Table for SL Contactors (Continued)
Motor Voltage Suggested Rating Minimum Motor Voltage Suggested Rating Minimum
FLA Cutler-Hammer Opening FLA Cutler-Hammer Opening
Fuse Time Fuse Time
7.2 kV/SL-160 7.2 kV/SL-360
11 – 18 2400 – 4800 5BCLS-30 30 – 1R 30 11 – 18 2400 – 4800 5BCLS-30 30 – 1R 30
18 – 31 5BCLS-2R 70 – 2R 30 18 – 31 5BCLS-2R 70 – 2R 30
31 – 46 5BCLS-3R 100 – 3R 30 31 – 46 5BCLS-3R 100 – 3R 30
46 – 62 5BCLS-4R 130 – 4R 30 46 – 62 5BCLS-4R 130 – 4R 30
62 – 74 5BCLS-5R 150 – 5R 30 62 – 74 5BCLS-5R 150 – 5R 30
74 – 93 5BCLS-6R 170 – 6R 30 74 – 93 5BCLS-6R 170 – 6R 30
93 – 137 5BCLS-9R 200 – 9R 130 93 – 137 5BCLS-9R 200 – 9R 130
137 – 160 5BCLS-12R 230 – 12R 130 137 – 187 5BCLS-12R 230 – 12R 130
11 – 34 5500 – 6600 7BCLS-2R 70 – 2R 30 187 – 200 5BCLS-12R 230 – 12R 130
34 – 46 7BCLS-3R 100 – 3R 30 200 – 360 N/A — —
46 – 56 7BCLS-4R 130 – 4R 30 11 – 34 5500 – 6600 7BCLS-2R 70 – 2R 30
56 – 68 7BCLS-5R 150 – 5R 30 34 – 46 7BCLS-3R 100 – 3R 30
68 – 85 7BCLS-6R 170 – 6R 30 46 – 56 7BCLS-4R 130 – 4R 30
85 – 137 7BCLS-9R 200 – 9R 50 56 – 68 7BCLS-5R 150 – 5R 30
137 – 160 7BCLS-12R 230 – 12R 250 68 – 85 7BCLS-6R 170 – 6R 30
7.2 kV/SL-200 85 – 137 7BCLS-9R 200 – 9R 50
137 – 200 7BCLS-12R 230 – 12R 250
11 – 18 2400 – 4800 5BCLS-30 30 – 1R 30 187 – 200 7BCLS-12R 230 – 12R 250
18 – 31 5BCLS-2R 70 – 2R 30 200 – 360 N/A — —
31 – 46 5BCLS-3R 100 – 3R 30
46 – 62 5BCLS-4R 130 – 4R 30 7.2 kV/SL-400
62 – 74 5BCLS-5R 150 – 5R 30 11 – 18 2400 – 4800 5BCLS-30 30 – 1R 30
74 – 93 5BCLS-6R 170 – 6R 30 18 – 31 5BCLS-2R 70 – 2R 30
93 – 137 5BCLS-9R 200 – 9R 130 31 – 46 5BCLS-3R 100 – 3R 30
137 – 200  5BCLS-12R 230 – 12R 130 46 – 62 5BCLS-4R 130 – 4R 30
13 11 – 34 5500 – 6600 7BCLS-2R 70 – 2R 30 62 – 74 5BCLS-5R 150 – 5R 30
34 – 46 7BCLS-3R 100 – 3R 30 74 – 93 5BCLS-6R 170 – 6R 30
46 – 56 7BCLS-4R 130 – 4R 30 93 – 137 5BCLS-9R 200 – 9R 30
56 – 68 7BCLS-5R 150 – 5R 30 137 – 187 5BCLS-12R 230 – 12R 30
68 – 85 7BCLS-6R 170 – 6R 30 187 – 273 5BCLS-18R 390 – 18R 50
85 – 137 7BCLS-9R 200 – 9R 50 273 – 400  5BCLS-24R 450 – 24R 130
137 – 200  7BCLS-12R 230 – 12R 250 11 – 34 5500 – 6600 7BCLS-2R 70 – 2R 30
 For FLA > 180, maximum acceleration time = 4.5 seconds. 34 – 46 7BCLS-3R 100 – 3R 30
46 – 56 7BCLS-4R 130 – 4R 30
56 – 68 7BCLS-5R 150 – 5R 30
68 – 85 7BCLS-6R 170 – 6R 30
85 – 137 7BCLS-9R 200 – 9R 30
137 – 187 7BCLS-12R 230 – 12R 30
187 – 273 7BCLS-18R 390 – 18R 50
273 – 400  7BCLS-24R 450 – 24R 250
7.2 kV/SL-800
225 – 360 2400 – 4800 5BCLS-24R 450 – 24R 50
360 – 449 5BCLS-36R 650 – 36R 130
450 – 720 5BCLS-44R 800 – 44R 250
225 – 400 5500 – 6600 7BCLS-24R 450 – 24R 50
400 – 449 7BCLS-36R 650 – 36R 130
450 – 720 7BCLS-44R 800 – 44R 250
15 kV/SL-250
50 – 200  10,000 – 13,800 15HLE-250E 250E 130
 For FLA > 360, maximum acceleration time = 6 seconds.
 For FLA > 150, contact factory for maximum acceleration time.
Note: Fuse selections based on LRC = FLA x 6 with acceleration time
of 10 seconds except where otherwise noted.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-37
Medium Voltage Power Contactors
December 2008
SL Series Ratings

SL Series Ratings
Table 13-31. Type SL Vacuum Contactor Ratings
Rated Interrupting Rating Application Table Transformer Capacitor Maximum
Utilization NEMA NEMA Induction Synchronous Motor kVA kvar Insulation
Voltage Unfused (E1) Fused (E2) Motor Horsepower Voltage
kA kA Horsepower (0.8 PF) (1.0 PF)
7.2 kV/160 Ampere Frame
2200 – 2500 4.5 50 600 600 800 600 480 7200
3000 – 3600 4.5 50 900 900 1000 800 640
3800 – 4800 4.5 50 1200 1200 1400 1000 960
6000 – 6900 4.5 50 1800 1800 2200 1600 1320
7.2 kV/200 Ampere Frame
2200 – 2500 4.5 50 800 800 1000 750 600 7200
3000 – 3600 4.5 50 1100 1100 1250 1000 800
3800 – 4800 4.5 50 1500 1500 1750 1250 1200
6000 – 6900 4.5 50 2250 2250 2750 2000 1650
7.2 kV/360 Ampere Frame
2200 – 2500 4.5 50 1500 1500 1750 1200 1000 7200
3000 – 3600 4.5 50 2000 2000 2500 1600 1475
3800 – 4800 4.5 50 2500 2500 3000 2000 2150
6000 – 6900 4.5 50 4000 4000 5000 3200 2950
7.2 kV/400 Ampere Frame
2200 – 2500 8.5 50 1750 1750 2000 1500 1200 7200
3000 – 3600 8.5 50 2250 2250 2500 2000 1650
3800 – 4800 8.5 50 3000 3000 3500 2500 2400
6000 – 6900 8.5 50 4500 4500 5500 4000 3300
7.2 kV/800 Ampere Frame
2200 – 2500
3000 – 3600
12.5 (50 MVA)
12.5 (50 MVA)
50 (200 MVA at 2300 V)
50 (285 MVA at 3300 V)
3000
4000
3000
4000
3500
5000
2500
3500
2400
3200
7200 13
3800 – 5000 12.5 (75 MVA) 50 (400 MVA at 4600 V) 5000 5000 6000 4500 4000
6000 – 7200 12.5 (100 MVA) 50 (570 MVA at 6600 V) 8000 8000 10,000 6000 4800
15 kV/250 Ampere Frame
10,000 – 11,000 5 50 (950 MVA at 11,000 V) 4000 4000 4500 3800 Consult Factory 15,000
12,400 – 13,800 5 50 (1190 MVA at 13,800 V) 5000 5000 5500 4750 Consult Factory

Table 13-32. Rating Specifications


Ampere Rating 7.2 kV/160 A 7.2 kV/200 A 7.2 kV/60 A 7.2 kV/400 A 7.2 kV/800 A 15 kV/250 A

Maximum Interrupting Current 4500 4500 4500 8500 12,500 5000


(3 Operations — Amperes)
Rated Current 160 200 360 400 800 250
(720 Enclosed)
IEC Make-Break Capability — AC4 (Amperes)
Make 1600 2000 3600 4000 8000 2500
Break 1280 1600 2880 3200 6400 2000

CA08101001E For more information visit: www.eaton.com


13-38 Power Breakers, Contactors & Fuses
Medium Voltage Power Contactors
December 2008
Product Specifications

Product Specifications 7.2 kV/160 – 400 Amperes ■ Latch (when specified)


❑ Mechanical life:
■ Short-time current:
Voltage Class 250,000 operations
❑ 30 seconds: 2400 amperes
❑ Trip voltage
Eaton’s Cutler-Hammer SL Medium Volt- ❑ 1 second: 6000 amperes
age Vacuum Contactors are designed to – dc: 24 volts
❑ 8.7 ms: 63 kA Peak
operate at voltages from 2200 to 15,000 (0.5 cycle) – dc: 125 volts
volts, depending on contactor type.
■ Normal service altitude: -3281 to – ac: 110/120 volts
Typical system voltages are 2400, 3300,
4160 and 6600 volts for 7.2 kV contactors +6562 ft. (-1000 to +2000 meters). ❑ Minimum trip voltage:
and 10,000, 11,000, 13,200 and 13,800 ■ Mechanical life: 2.5 million. 80% rated coil voltage
volts for 15 kV contactors. ■ Electrical life: ❑ Trip burden
❑ 6 x Rated Make/ – 24 Vdc: 400 VA
Altitude 1x Rated Break:
– 48 and 125 Vdc: 400 VA
7.2 kV/160 – 400 ampere SL Contactors 300,000 operations
are capable of operating in virtually ❑ 6 x Rated Make/
– 110 and 120 Vac: 400 VA
any altitude range. Three versions are 6 x Rated Break: – 220 and 240 Vac: 400 VA
offered in Standard, High and Low 300,000 operations ❑ Trip Time (2 cycles): 30 ms
altitude configurations. No de-rating ■ BIL (impulse withstand): ■ Weight
is necessary for proper operation. 60 kV (1.2 x 50 microseconds)
Altitude designations are listed in the ❑ 150 – 360 A: 47 Lbs. (21.3 kg)
■ Dielectric strength:
table below. ❑ 400 A: 49 Lbs. (22.2 kg)
20 kV rms (1 minute)
Table 13-33. Altitude ■ Closing time: 80 milliseconds
(energization to contact touch).
7.2 kV/800 Amperes
Altitude Low Standard High
■ Selectable opening times: ■ Short-time current
7.2 kV/160 – 400 A
❑ 30 milliseconds (2 cycles) ❑ 30 seconds: 4320 amperes
Feet -11,500 to -3300 to +6600 to
-3300 +6600 +13,100 ❑ 50 milliseconds (3 cycles) ❑ 1 second: 10,800 amperes
13 Meters -3500 to -1000 to +2000 to ❑ 8.7 ms (0.5 cycle) 86 kA peak
❑ 130 milliseconds (8 cycles)
-1000 +2000 +4000
❑ 250 milliseconds (15 cycles) ■ Normal service altitude: -3281 to
7.2 kV/800 A and 15 kV/250 A
+6562 ft. (-1000 to +2000 meters).
Feet N/A -3300 to +11,800 to ❑ 330 milliseconds (20 cycles)
+11,800 +16,000
■ Mechanical life: 1 million.
■ Arcing time:
Meters N/A -1000 to +3600 to 12 ms (0.75 cycle) or less. ■ Electrical life: 100,000 operations.
+3600 +4900
■ Pickup voltage: ■ BIL (impulse withstand):
80% rated coil voltage. 60 kV (1.2 x 50 microseconds).
Control Voltage ■ Dropout voltage: ■ Dielectric strength:
Control coil voltage should be select- 60% rated coil voltage. 18.2 kV rms (1 minute).
able in the field. Standard voltages ■ Control voltages: ■ Closing time (energization
available should be 120/60, 110/50, to contact touch):
❑ ac/Hz: 110/50, 120/60, 220/50,
240/60, 220/50 and 125 Vdc. Coil 240/60 80 milliseconds.
should pickup at 80% of rated coil ■ Opening times (deenergization
voltage and dropout not sooner ❑ dc: 125
to full open):
than 60% of rated coil voltage. Open- ■ Control circuit burden: ❑ 130 ms (8 cycles)
ing time should be field selectable ❑ Closing: (200 milliseconds)
within the range of 30 ms – 330 ms ❑ 200 ms (12 cycles)
– 110/120 ac, 125 dc 1 kVA
for 7.2 kV/160 – 400 A and 50 ms – ❑ 330 ms (20 cycles)
330 ms for 15 kV/250 A. Opening time – 220/240 ac 1.8 kVA
for 7.2 kV 800 A must be specified at ❑ Holding:
■ Arcing time:
order entry and can be either 130 ms, 12 ms (0.75 cycle) or less.
– 110/120 ac 125 dc 40 VA
250 ms or 330 ms. ■ Pickup voltage:
– 220/240 ac 50 VA 80% rated coil voltage.
■ Auxiliary contact rating: ■ Dropout voltage:
❑ 600 volts (maximum) 60% rated coil voltage.
❑ 10 amperes continuous current ■ Control voltages:
❑ Making capacity ❑ ac/Hz: 110/50, 120/60 Vac, 220/50,
240/60
– ac: 7200 VA
❑ dc: 125 Vdc
– dc: 125 VA
■ Control circuit burden:
❑ Breaking capacity
❑ Closing (120/240): 2600 VA
– ac: 720 VA
❑ Holding (120/240): 50 VA
– dc: 125 VA

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-39
Medium Voltage Power Contactors
December 2008
Product Specifications

7.2 kV/800 Amperes (Continued) 15kV/250 Amperes ■ Control circuit burden:


❑ Closing (120/240): 1700/2600 VA
■ Auxiliary contact rating: ■ Short-time current.
❑ 600 volts (maximum) ❑ 30 seconds: 1500 amperes ❑ Holding (120/240): 80 VA

❑ 10 amperes continuous current ❑ 1 second: 3750 amperes ■ Auxiliary contact rating:

❑ Making capacity ❑ 8.7 ms (0.5 cycle) 25 kA peak ❑ 600 volts (maximum)


❑ 10 amperes continuous current
– ac: 7200 VA ■ Normal service altitude: -3281 to
+6562 ft. (-1000 to +2000 meters). ❑ Making capacity
– dc: 200 VA
❑ Breaking capacity
■ Mechanical life: 250,000. – ac: 7200 VA
■ Electrical life: 250,000 operations – dc: 200 VA
– ac: 720 VA
■ BIL (impulse withstand): ❑ Breaking capacity
– dc: 200 VA 75 kV (1.2 x 50 microseconds)
■ Latch (when specified): – ac: 720 VA
■ Dielectric strength:
❑ Mechanical life: 36 kV rms (1 minute) – dc: 200 VA
250,000 operations ■ Closing time (energization to ■ Latch (when specified):
❑ Trip voltage contact touch): 80 milliseconds. ❑ Mechanical life:
– dc: 24, 48, 96 volts ■ Selectable opening times 250,000 operations
(de-energization to full open): ❑ Trip voltage
– ac: 110/120, 220/240 volts
50/60 Hz ❑ 50 ms (3 cycles) – dc: 24, 48, 96 volts
❑ Minimum trip voltage: ❑ 130 ms (8 cycles) – ac: 110/120, 220/240 volts
80% rated coil voltage ❑ 250 ms (12 cycles) 50/60 Hz
❑ Trip burden ❑ 330 ms (20 cycles) ❑ Minimum trip voltage: 80% rated
– 24 Vdc: 1200 VA ■ Arcing time: coil voltage
12 ms (0.75 cycle) or less. ❑ Trip burden
– 48 and 96 Vdc: 400 VA
– 110 and 220 Vac: 500 VA ■ Pickup voltage: – 24 Vdc: 1200 VA 13
80% rated coil voltage. – 48 and 96 Vdc: 400 VA
❑ Trip time (2 cycles):
■ Dropout voltage: – 110 and 220 Vac: 500 VA
30 milliseconds
60% rated coil voltage.
■ Weight: 95 Lbs. (43.1 kg). ❑ Trip time (2 cycles):
■ Control voltages:
30 milliseconds
❑ ac/Hz: 110/50, 120/60 Vac,
■ Weight: 95 Lbs. (43.1 kg).
220/50, 240/60
❑ dc: 125 Vdc

CA08101001E For more information visit: www.eaton.com


13-40 Power Breakers, Contactors & Fuses
Medium Voltage Power Contactors
December 2008
Technical Data and Specifications

Technical Data and Specifications


Electrical Connections Diagrams (7.2 kV/160 – 400 Amperes)

7
White
6 Black
dc dc
Coil 1 Coil 2
5 White
4 Black

Control 2
Voltage
(On/Off) 1

Figure 13-5. Connection for Magnetically Held Contactor

(+)

M  (–)
dc Latch
M Coil
Control 8
Voltage
13 (Open) 7
White
6 Black
dc dc
Coil 1 Coil 2
5 White
4 Black

Control 2
Voltage
(Close) 1

Figure 13-6. Connections for Mechanically Latched Contactor


 M contacts are connected in parallel for ≤ 48 V. M contacts are connected in series for > 48 V.

Table 13-34. Control Voltage Settings


Setting SW1 SW2 SW3

110 Vac 50 Hz Off Off Off


120 Vac 60 Hz On Off Off
220 Vac 50 Hz Off On Off
240 Vac 60 Hz On On Off
125 Vdc Off Off On

Note: Stock units pre-set to 120/60 Vac.

Table 13-35. Dropout Time Settings


Delay Setting SW4 SW5 SW6

30 ms Off Off Off


50 ms On Off Off
130 ms Off On Off
250 ms On On Off
330 ms Off Off On

Table 13-36. Altitude Designations


Altitude Low Standard High

Feet -11,483 to -3281 -3281 to +6562 +6562 to +13,123


Meters -3500 to -1000 -1000 to +2000 +2000 to +4000

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-41
Medium Voltage Power Contactors
December 2008
SL Series (7.2 kV/160 – 400 Amperes)

SL Series (7.2 kV/160 – 400 Amperes)

Panel-Mount Panel-Mount
Provisions Provisions

Vacuum Interrupters

Panel-Mount
Provisions

Actuator Assembly

Control Contactor Nameplate


Terminal Strip

Auxiliary Auxiliary
Contact Blocks Contact Blocks

13
Pedestal-Mount Pedestal-Mount
Provisions Provisions

Coil Control Board Magnet Mechanical Latch


(Behind Control Terminal Strip) Coil Provision

SL Series Features

Control Settings

Coil Control Board DIP Switches


Note: Refer to Table 13-34
for Control Voltage Settings
and Table 13-35 for
Control Terminal Strip Dropout Time Settings.

CA08101001E For more information visit: www.eaton.com


13-42 Power Breakers, Contactors & Fuses
Medium Voltage Power Contactors
December 2008
SL Series (7.2 kV/160 – 400 Amperes)

Front and Rear View (7.2 kV/160 – 400 Amperes)

Front View 7.2 kV/160 – 400 Amperes Rear View 7.2 kV/160 – 400 Amperes

Dimensional Drawings (7.2 kV/160 – 400 Amperes) in Inches (mm)

14.00 4.38 4.38


(355.6) Upper (111.3) (111.3)
4.38 4.38 Te
erminals
(111.3) (111.3)

15.50
13 Lower
(393.7)
Terminalss
6.85 15.06
(174.0)
174.0 (382.5) 16.00
(406.4)
16.00
0 8.75
(406.4)
406.4 (222.2))

7.36 15 25
15.25
(186.9)
186.9 (387.4)
(387 4)
16 25
16.25
(412.8)
(412 8)

Figure 13-9. Rear Dimensions 7.2 kV/160 – 400 Amperes


15.25
(387.4)
16.25
(412.8)

Figure 13-7. Front Dimensions 7.2 kV/160 – 400 Amperes Rear Mounting
.328 (8.3) DIA
15.50
.406
406 (10
(10.3)
3) .78 Front Mounting (393.7)
DIA (6) (19.8) 6.85 .328 (8.3) DIA
(174.0)

16.00
8.70
(221.0)
221.0 (406.4)

7.70
(195.6)
195.6 7.36
(186.9)
186.9
.313 (8.0) DIA .27
(6.9)
1.77
Front (45.0)
.83
83 13.60 .83
83 4.44
(21.1)) (345.4) (21.1)
(21 1) 8.70
15.25
Front 9.09 (112.8) (221.0)
(387.4) (230.9)

Figure 13-8. Base Plate Dimensions 7.2 kV/160 – 400 Amperes Figure 13-10. Side Dimensions 7.2 kV/160 – 400 Amperes

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-43
Medium Voltage Power Contactors
December 2008
SL Series (7.2 kV/800 Amperes)

Front and Rear View 7.2 kV/800 Amperes

Front View 7.2 kV/800 Amperes Rear View 7.2 kV/800 Amperes

Dimensional Drawings 7.2 kV/800 Amperes in Inches (mm)

3 70
3.70 4 38
4.38 4 38
4.38 .50
50 (12.7) DIA Bolt Hole
2.75 (6) Places
(69.9) Latch Trip Target (94.0)
(94 0) (111.3)
111 3 (111.3)
111 3
(When Used) .50 (12.7) DIA
Mounting Hole
(4) Places

I l’k
Intl’ Intl’k
.625 (15.9) square
shaft with the axis 13
vertical when the
14.89 10.25 contactor is closed.
(378.2) (260.4) Rotates 3.8
counterclockwise
Optional to open.
12 Point Plug 11.25
8.50 (2
285.8)
(216.0)
216.0 2.35
5 (59.7)
4.01 4.34
(101.9) (110.2)
.39 (9.9)
(
5.01 6.12 .80 (20.3)
(127.3) (155.4) 16 93
16.93
8.07 (430.0)
(430 0)
(205.0) 16.15
(410.2)

Figure 13-11. Front Dimensions 7.2 kV/800 Amperes Figure 13-13. Top Dimensions 7.2 kV/800 Amperes

Latch
(When Used) 16.41
(416.8)
1.30 (33.0) 4.50
Plug
Line
(When Used)
Terminals
1.15 (29.2)
Latch Trip 17.12
when Used (434.8)
0.3 (7.62) Load
Travel 11.36
Terminals (288.5)
Required to
Trip when 10.70
Latch is Used (271.8)
Optional
12 Point Plug
4.06
(103.1) 2.69
13.94
(68.3)
(354.0)

Figure 13-12. Side Dimensions 7.2 kV/800 Amperes

CA08101001E For more information visit: www.eaton.com


13-44 Power Breakers, Contactors & Fuses
Medium Voltage Power Contactors
December 2008
SL Series (15 kV/250 Amperes)

Front and Rear View 15 kV/250 Amperes

Front View 15 kV/250 Amperes Rear View 15 kV/250 Amperes

Dimensional Drawings 15 kV/250 Amperes in Inches (mm)

16.18
(410.9) 4.65
Line Terminals (118.1)

13 Intl'k

21.40
(543.4) 17.77
(451.4)

12.29
(312.1) 18.58
8 7 6 5 4 3 2 2 (471.9)
LATCH COIL AUX POWER
Load
3.50 Terminals 5.60
(88.9) (142.2)
7.95
(202.0) 15.88
(403.4) 5.60
Front View (142.2)

Figure 13-14. Front Dimensions 15 kV/250 Amperes 13.25


(336.6)
3.55 4.40 4.40 RH Side View
(90.1) (111.7) (111.7) ø 0.31
(7.9) Figure 13-16. Top Dimensions 15 kV/250 Amperes
ø 0.34
(8.7)

13.00
(330.2)
11.50
(292.1)

4.60
(116.8)

0.38 0.80
15.88 (9.5) (20.3)
(403.4)
16.63
(422.4)

Top View

Figure 13-15. Side Dimensions 15 kV/250 Amperes

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-45
Medium Voltage Power Contactors
December 2008
Lug Terminal

Lug Terminal
Table 13-37. Lug Terminal Dimensions
in Inches (mm)
Contactor Width Depth Hardware
Ampere (Bolt
Rating Diameter)
Upper Terminal
7.2 kV/160 0.75 (19.1) 1.31 (33.3) 10
7.2 kV/200 1.00 (25.4) 1.31 (33.3) 10
7.2 kV/360 1.00 (25.4) 1.31 (33.3) 10
7.2 kV/400 1.00 (25.4) 1.31 (33.3) 10
7.2 kV/800 1.75 (44.5) 2.00 (50.8) 10
15 kV/250 1.25 (31.8) 1.25 (31.8) 10
Lower Terminal
Width De 7.2 kV/160 1.25 (31.8) 1.10 (27.9) 10
pt 7.2 kV/200 1.25 (31.8) 1.10 (27.9) 10
h
7.2 kV/360 1.25 (31.8) 1.10 (27.9) 10
Hardware 7.2 kV/400 1.25 (31.8) 1.10 (27.9) 10
Diameter 7.2 kV/800 1.50 (38.1) 1.50 (38.1) 10
15 kV/250 1.50 (38.1) 1.25 (38.1) 10

Lug Terminal

13

CA08101001E For more information visit: www.eaton.com


13-46 Power Breakers, Contactors & Fuses
Medium Voltage Power Contactors
December 2008
Product Selection

Product Selection
Table 13-38. Power Contactors Catalog Numbering System

SL N 01 2 S 5 A - 22 0

SL Mechanical Latch
Contactor
7.2 kV/160 – 400 Amperes 7.2 kV/800 Amperes
Series
(Coil Voltage) 15 kV/250 Amperes
(Coil Voltage)
Design 0= None 0 = None
N = NEMA 1= 24 Vdc 1 = 24 Vdc
C = IEC 2= 32 Vdc 3 = 48 Vdc
3= 48 Vdc 4 = 110 (50/60)
4= 110/50,120/60, 5 = 220 (50/60)
Type or 125 Vdc 6 = 96 – 125 Vdc
01 = 7.2 kV Contactor 5 = 220/50, 240/60
03 = 15 kV Contactor
Auxiliary Contacts
Ampere Rating 7.2 kV/160 – 400 Amperes 7.2 kV/800 Amperes
1 = 160 15 kV/250 Amperes
2 = 7.2 kV/200, 22 = 2 NO, 2 NC 22 = 2 NO, 2 NC
15 kV/250 28 = 2 NO, 8 NC
3 = 360 37 = 3 NO, 7 NC
4 = 400 46 = 4 NO, 6 NC
8 = 800 55 = 5 NO, 5 NC
13 64 = 6 NO, 4 NC
73 = 7 NO, 3 NC
Altitude
82 = 8 NO, 2 NC
7.2 kV/160 – 400 Amperes 7.2 kV/800 Amperes
15 kV/250 Amperes
Coil Voltage
S = Standard -3281 to +6562 ft. S = Standard -3281 to +11,811 ft.
(-1000 to +2000 m) (-1000 to +3600 m) A = 120/60
L = Low -11,483 to -3281 ft. H = High +11,811 to +16,076 ft. B = 240/60
(-3500 to -1000 m) (+3600 to +4900 m) S = 125 Vdc
H = High +6562 to +13,123 ft. U = 110/50
(+2000 to +4000 m) W = 220/50

Coil Dropout Time


7.2 kV/160 – 400 Amperes 7.2 kV/800 Amperes
15 kV/250 Amperes
5 = 30 ms 6 = 50 ms (15 kV/250 A only)
6 = 50 ms 7 = 130 ms
7 = 130 ms 8 = 250 ms (250 A); 200 ms (800 A)
8 = 250 ms 9 = 330 ms
9 = 330 ms

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-47
Medium Voltage Power Contactors
December 2008
Accessory Kits

SL Vacuum Contactor Series — Auxiliary Contact Kit Mechanical Interlock Kit


Accessory Kits (7.2 kV/160 – Field Mount auxiliary contact kits for Field Mount mechanical interlock
7.2 kV/160 – 400 amperes SL Vacuum kits for 7.2 kV/160 – 400 amperes SL
400 Amperes) Contactor. Contact kits are available in Vacuum Contactor.
many configurations of NO-NC.
Mechanical Latch Kit
Field Mount to 7.2 kV/160 –
400 amperes SL Vacuum Contactor.
Coil voltages available in a wide range
of ac and dc selections. Easy to install
on new and existing units.

Auxiliary Contact Kit

Table 13-40. Ordering Information —


Auxiliary Contact Kit
Description Catalog Price
Mechanical Latch Kit Number U.S. $
Table 13-39. Ordering Information —
Mechanical Latch Kit
3NO – 3NC Additional
6NO Additional
SLA-AS33
SLA-AS60
13
Coil Voltage Catalog Price 6NC Additional SLA-AS06
Number U.S. $ 5NO – 1NC Additional SLA-AS51
4NO – 2NC Additional SLA-AS42
24 Vdc SLA-ML24 2NO – 4NC Additional SLA-AS24
32 Vdc SLA-ML32 1NO – 5NC Additional SLA-AS15
48 Vdc SLA-ML48
110/50, 120/60, SLA-ML120
125 Vdc Selectable
220/50, 240/60 Selectable SLA-ML240

Mechanical Interlock Kit

Table 13-41. Ordering Information —


Mechanical Interlock Kit
Description Catalog Price
Number U.S. $

Vertical or Horizontal SLA-MI


Arrangement

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . N/A

CA08101001E For more information visit: www.eaton.com


13-48 Power Breakers, Contactors & Fuses
Expulsion Fuses
December 2008
Product Description

Power Fuse Overview A better understanding of some fuse ■ Low voltage — 1000 volts and below.
terminology will help you understand ■ Medium voltage — Greater than
Eaton’s Cutler-Hammer roots in and select the correct fuse. The follow- 1000 to 69,000 volts.
the power fuse business began over ing is a brief overview of those terms. ■ High voltage — Greater than
60 years ago under Westinghouse 69,000 volts.
Electric. In 1935, Westinghouse Power vs. Distribution
introduced the medium voltage boric The differentiation is intended to Expulsion vs. Current Limiting
acid expulsion fuse followed by the indicate the test conditions and where
medium voltage current limiting fuse. (Definitions per ANSI C47.40-1993)
fuses are normally applied on an
Even today, medium voltage fuses electrical system, based on specific An expulsion fuse is a vented fuse in
continue to use the core Westinghouse requirements for generating sources, which the expulsion effect of the gases
technology. Eaton continues to build substations and distribution lines. produced by internal arcing, either
on the Westinghouse technology leg- Each class has its own unique set alone or aided by other mechanisms,
acy by engineering higher performance, of voltage, current and construction results in current interruption.
cost-effective power fuse products. requirements (see ANSI C37.42, An expulsion fuse is not current limit-
Westinghouse and Cutler-Hammer .44, .46 and .47). ing and as a result limits the duration
medium voltage fuses are manufac- of a fault on the electrical system, not
tured and tested to the requirements Low vs. Medium vs. High Voltage the magnitude.
of the C37.4X series of standards. While fuses are defined in the ANSI
These standards are: standards as either low or high A current limiting fuse is a fuse that,
voltage, Eaton has elected to name when its current responsive element
IEEE Std. C37.40-1933 – IEEE Standard is melted by a current within the
their fuses to correspond with the
Service Conditions and Definitions for fuse’s specified current limiting range,
equipment in which they are installed.
High Voltage Fuses, Distribution abruptly introduces a high resistance
Therefore, per ANSI C84, our fuses are
Enclosed Single-Pole Air Switches, to reduce current magnitude and dura-
named as follows:
Fuse Disconnecting Switches, and tion, resulting in subsequent current
Accessories (ANSI) interruption. Refer to Figure 13-17 for
a features comparison.
13 IEEE Std. C37.41-2000 – IEEE Standard
Design Tests for High Voltage Fuses, Table 13-42. General High Voltage Fuse Comparison
Distribution Enclosed Single-Pole Air Expulsion Current Limiting
Switches, Fuse Disconnecting
Switches, and Accessories (ANSI) Vented Sealed
Electromechanical Static
ANSI C37.42-1996 – American National Interrupts at Current Zero Limits Fault Current
Standard Specifications for High Volt- Generally Higher Voltage & Current Application Capabilities Generally Higher Interrupting Ratings
age Expulsion Type Distribution Class Different Time/Current Characteristics Different Time/Current Characteristics
Fuses, Cutouts, Fuse Disconnecting
Switches and Fuse Links
ANSI C37.46-2000 – American National
Standard for High Voltage Expulsion i max. — maximum rated interrupting current
and Current Limiting Type Power Class i min. — minimum rated interrupting current
Fuses and Fuse Disconnecting i hr. — current causing element melting in 1 hour
Switches
i — any current melting element with no time limit
ANSI C37.47-2000 – American National
Standard for High Voltage Current
Limiting Type Distribution Class Fuses
and Fuse Disconnecting Switches BACKUP
Current Limiting Type

The following IEEE standards are


also applicable to the fuse products
covered in this publication: GENERAL PURPOSE
IEEE Std. C37.48-1997 – IEEE Guide
for Application, Operation and FULL RANGE
Maintenance of High Voltage Fuses,
Distribution Enclosed Single-Pole
Air Switches, Fuse Disconnecting
Switches, and Accessories (ANSI) i i hr. i min. i max.
IEEE Std. C37.48-1-2001 – IEEE Guide Interrupting Current
for the Operation, Classification,
Application and Coordination of Figure 13-17. Fuse Types Protection Range
Current Limiting Fuses with Rated
Voltages 1 – 38 kV

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-49
Expulsion Fuses
December 2008
Product Description

Fuse Types General Fuse Component Terms Disconnect Mounting: The disconnect
mounting allows the fuse unit to be
There are three current limiting fuse Replaceable Fuse Unit: A replaceable removed (off load) using an insulated
types: Backup, General Purpose and fuse unit is a phrase used to describe hook stick. The hookstick grabs a pull
Full Range. It is important that the user a fuse that does not have a separate ring and disconnects the fuse unit, which
have an understanding of these defini- holder and refill assembly. In a may then be lifted out of its mounting.
tions to ensure proper application of replaceable fuse unit, the fuse is
the fuse (Figure 13-17). its own holder and is completely Live Parts: Live parts were briefly
replaced after interruption. discussed as part of the “Mounting”
Backup Fuses: A fuse capable of inter- definition. Everything above the insula-
rupting all currents from the maximum Mounting: A mounting provides all the tors on the mounting excluding the fuse
rated interrupting current down to the necessary parts to safely mount unit, fuse holder, and the fuse end fit-
rated minimum interrupting current. a fuse in its intended piece of equip- tings (if required) are considered the live
ment. The base is the metal support parts. Fuse end fittings are discussed
Backup fuses are always used in a to which all other pieces attach. Insula-
series with another interrupting device next and are not required with non-dis-
tors attach to the base and insulate the connect live parts, but are required and
capable of interrupting currents below live fuse unit from the base and every-
the fuse’s minimum interrupting current. included with disconnect live parts. Live
thing beyond the base. Live parts are parts may be sold separately as replace-
General Purpose Fuses: A fuse capable the parts of the mounting that are ment parts or for new OEM applications.
of interrupting all currents from the energized once electricity is flowing.
rated interrupting current down to the The live parts provide the means to End Fittings: End fittings are metal
current that causes melting of the fus- hold the fuse unit in place, electrical parts that attach to each end of a fuse
ible element in no less than one hour. contact, and a place to make line unit’s ferrules (end caps). As previ-
and load connections. ously mentioned, they are used solely
General Purpose fuses are typically with disconnect fuse applications or
used to protect feeders and compo- Non-Disconnect Mounting: A non- when converting a non-disconnect to a
nents such as transformers. disconnect mounting does not provide disconnect fuse configuration.
a means for removing the fuse unit
Full Range Fuses: A fuse capable until the circuit is dead and the fuse When end fittings are ordered, a fitting
of interrupting all currents from the
rated interrupting current down to the
unit can be removed manually. The
fuse unit is held in place by friction
for each end of the fuse is included. 13
Keep in mind that end fittings can
minimum continuous current that through the use of fuse clips or by become damaged in use and, therefore,
causes melting of the fusible element, a cross bar. are sold separately from the live parts
with the fuse applied at the maximum when necessary. It is not necessary to
ambient temperature specified by the purchase an entire set of live parts when
manufacturer. only the end fittings are required.

CA08101001E For more information visit: www.eaton.com


13-50 Power Breakers, Contactors & Fuses
Expulsion Fuses
December 2008
Product Selection

Expulsion Fuse Table 13-43. Expulsion Fuse Units Catalog Numbering System

Easy to Use, Easy to Order! DBU 17 - 100 E


Eaton’s Cutler-Hammer fuse catalog
numbering system makes it easy to
order the right fuse. The catalog num- Type Maximum kV Amperes Speed
bers are easy to remember, unique to RBA 8 .5 50 E
each fuse, and are broken down in DBU 15 3 65 K
three descriptive segments: Fuse Type, DBA 17 5 80 SE
RDB 25 7 100
Voltage Rating and Current Rating. RBT 27 10 125
These Catalog Numbers can be BA 38 15 150
48 20 200
entered directly and easily: 72 25 250
92 30 300
■ No change in order processing 121 40 400
will occur if you use either a style 145
number or its corresponding catalog
number. You will get the same fuse.
■ In the back of this ordering guide is Table 13-44. Expulsion Fuse Accessories Catalog Numbering System
a style number to catalog number
cross-reference chart.
15 RBA2 - P NM C
Examples:
8RBA2-10E 8.3 max. kV,
RBA-200 refill, Maximum kV Type Diameter Size
10E amperes
8 RBA A = 1-5/8 Inch 0.5E – 1.5E,
DBU17-30K 17.1 max. kV, 15 DBU Single Barrel
13 DBU fuse unit, 17
25
DBA
RDB
B = 1-5/8 Inch 3E – 10E,
Single Barrel
30 amperes 27 RBT C = 2-Inch Single Barrel
38 BA D = 3-Inch Single Barrel
15RBA8-INH 15.5 max. kV, 48 E = 3-Inch Double Barrel
RBA-800, 72 F = 4-Inch Double Barrel
indicating 92 G = 5/8 Inch Ferrule
Insulator
nondisconnect 121
holder 145 G = Glass Polyester
P = Porcelain
RBA4-FLTR RBA-400 filter H = High BIL Hardware
UM = Underhung Mounting
VM = Vertical Mounting
DL = Disconnect Live Parts
NL = Nondisconnect Live Parts
DH = Disconnect Holder
NH = Nondisconnect Holder
NM = Nondisconnect Mounting
UL = Underhung Live Parts
VL = Vertical Live Parts
I = Indicating
O = Outdoor
V = Vented
M = Muffled
VO = Vented Outdoor
MO = Muffled Outdoor
FLTR = Filter
COND = Condenser
MFLR = Muffler
SHNT = Shunt and Spring Assembly

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-51
Expulsion Fuses
December 2008
Type RBA

Table 13-45. Type RBA Expulsion Fuses for Use Indoors or in an Enclosure

Approximate Shipping Weight. in Lbs. (kg)


Standard Speed Time Lag Fuse- Voltage Mounting (including Live Live Fuse Filters and Spring
(Fuse Refills) (Fuse Refills) holder (kV) Parts less Holder) Parts Condensers and
Porcelain Glass Shunt
Insulator Polyester Assy.

Non-Indicating Catalog Number


Catalog Catalog Catalog Catalog Catalog Catalog
Number Number Number Number Number Number

Indicating Catalog Number

Catalog Number
Curve Reference

Curve Reference
Ampere Rating

Ampere Rating

Maximum
Nominal
36-635

36-635

Style

BIL
RBA/RBT Refill Units RBA Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders for
Indoor or Enclosure Applications)
8.3 kV Maximum (7.2 kV Nominal) 8.3 kV Maximum (7.2 kV Nominal)
200 Ampere 200 Ampere (For Use with 8RBA2 Fuseholders)
10E 8RBA2-10E (1,2) — — 4.8 5.5 60 5RBA2-PNM 5RBA2-GNM 15RBA2-NL RBA2-FLTR
Non-Disconnect

15E 8RBA2-15E (1,2) — — 7.2 8.3 75 8RBA2-PNM 8RBA2-GNM RBA2-COND


8RBA2-INH
8RBA2-NH

20E 8RBA2-20E (1,2) 8RBT2-20E (3,4)


25E 8RBA2-25E (1,2) 8RBT2-25E (3,4)

8RBA2-SHNT
30E 8RBA2-30E (1,2) 8RBT2-30E (3,4)
10E to 200E
1.0 (.45)

40E 8RBA2-40E (1,2) 8RBT2-40E (3,4)


50E 8RBA2-50E (1,2) 8RBT2-50E (3,4)
65E 8RBA2-65E (1,2) 8RBT2-65E (3,4) 4.8 5.5 60 5RBA2-PDM 5RBA2-GDM 14RBA2-DL
13
BRBA2-IDH
Disconnect
8RBA2-DH

80E 8RBA2-80E (1,2) 8RBT2-80E (3,4) 7.2 8.3 75 8RBA2-PDM 8RBA2-GDM


100E 8RBA2-100E (1,2) 8RBT2-100E (3,4)
125E 8RBA2-125E (1,2) 8RBT2-125E (3,4)
150E 8RBA2-150E (1,2) 8RBT2-150E (3,4)
200E 8RBA2-200E (1,2) 8RBT2-200E (3,4)
8.3 kV Maximum (7.2 kV Nominal) 8.3 kV Maximum (7.2 kV Nominal)
400 Ampere 400 Ampere (For Use with 8RBA4 Fuseholders)
.5E 8RBA4-.5E (5,6) — — 4.8 5.5 60 5RBA4-PNM 5RBA4-GNM 15RBA4-NL RBA4-FLTR
3E 8RBA4-3E (5,6) — — 7.2 8.3 75 8RBA4-PNM 8RBA4-GNM RBA4-COND
Non-Disconnect

5E 8RBA4-5E (5,6) — —
8RBA4-INH
8RBA4-NH

7E 8RBA4-7E (5,6) — —
10E 8RBA4-10E (5,6) — —
15E 8RBA4-15E (5,6) — —
20E 8RBA4-20E (5,6) 8RBT4-20E (7,8)
25E 8RBA4-25E (5,6) 8RBT4-25E (7,8)

8RBA4-SHNT
.5E to 400E

30E 8RBA4-30E (5,6) 8RBT4-30E (7,8)


2.1 (.95)

40E 8RBA4-40E (5,6) 8RBT4-40E (7,8) 4.8 5.5 60 5RBA4-PDM 5RBA4-GDM 14RBA4-DL
50E 8RBA4-50E (5,6) 8RBT4-50E (7,8) 7.2 8.3 75 8RBA4-PDM 8RBA4-GDM
65E 8RBA4-65E (5,6) 8RBT4-65E (7,8)
BRBA2-IDH

80E 8RBA4-80E (5,6) 8RBT4-80E (7,8)


Disconnect
8RBA4-DH

100E 8RBA4-100E (5,6) 8RBT4-100E (7,8)


125E 8RBA4-125E (5,6) 8RBT4-125E (7,8)
150E 8RBA4-150E (5,6) 8RBT4-150E (7,8)
200E 8RBA4-200E (5,6) 8RBT4-200E (7,8)
250E 8RBA4-250E (5,6) 8RBT4-250E (10,11)
300E 8RBA4-300E (5,6) 8RBT4-300E (10,11)
400E 8RBA4-400E (5,6) 8RBT4-400E (10,11)
8.3 kV Maximum (7.2 kV Nominal) 8.3 kV Maximum (7.2 kV Nominal)
800 Ampere 800 Ampere (For Use with 8RBA8 Fuseholders)
 4.8 5.5 60 5RBA8-PNM 5RBA8-GNM 15RBA8-NL (2)RBA4-FLTR 
Non-Disconnect

450E (2)8RBA4-250E (9) (2)8RBT4-250E (12)


8RBA8-SHNT
450E to 720E

 (2)RBA4-COND 
8RBA8-INH
8RBA8-NH

540E (2)8RBA4-300E (9) (2)8RBT4-300E (12) 7.2 8.3 75 8RBA8-PNM 8RBA8-GNM


720E (2)8RBA4-400E (9) (2)8RBT4-400E (12) 

 Requires two fuse refills as shown. Price each refill individually. Example: To order refill units for a 720E, 8.3 kV fuse, order 2 pieces of an 8RBA4-400E.
 Two filters or condensers required.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder, one mounting, and one filter or condenser per phase.
Live parts can be substituted for the mounting if the user is supplying base support and insulators.

CA08101001E For more information visit: www.eaton.com


13-52 Power Breakers, Contactors & Fuses
Expulsion Fuses
December 2008
Type RBA

Table 13-46. Type RBA Expulsion Fuses for Use Outdoors

Approximate Shipping Weight. in Lbs. (kg)


Standard Speed Time Lag Fuse- Voltage (kV) Mounting (including Live Live Fuse Filters and Spring
(Fuse Refills) (Fuse Refills) holder Parts less Holder) Parts Condensers and
Porcelain Glass Shunt
Insulator Polyester Assy.

Non-Indicating Catalog Number


Catalog Catalog Catalog Catalog Catalog
Number Number Number Number Number

Indicating Catalog Number

Catalog Number

Catalog Number
Curve Reference

Curve Reference
Ampere Rating

Ampere Rating

Maximum
Nominal
36-635

36-635

Style

BIL
RBA/RBT Refill Units RBA Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders
for Indoor or Enclosure Applications)
15.5 kV Maximum (14.4 kV Nominal) 15.5 kV Maximum (14.4 kV Nominal)
200 Ampere 200 Ampere (For Use with 15RBA2 Fuseholders)
10E 15RBA2-10E (1,2) — — 13.8 15.5 95 14RBA2-PNM RBA2-FLTR
Non-Disconnect

14RBA2-GNM
15RBA2-INH
15RBA2-NH

15RBA2-NL
15E 15RBA2-15E (1,2) — — 13.8 15.5 110 15RBA2-PNM RBA2-COND
20E 15RBA2-20E (1,2) 15RBT2-20E (3,4)
25E 15RBA2-25E (1,2) 15RBT2-25E (3,4)

15RBA2-SHNT
30E 15RBA2-30E (1,2) 15RBT2-30E (3,4)
10E to 200E

40E 15RBA2-40E (1,2) 15RBT2-40E (3,4)


1.1 (.5)

50E 15RBA2-50E (1,2) 15RBT2-50E (3,4)

14RBA2-GDM
65E 15RBA2-65E (1,2) 15RBT2-65E (3,4) 13.8 15.5 95 14RBA2-PDM
15RBA2-IDH

13
15RBA2-DH

38RBA2-DL
Disconnect

80E 15RBA2-80E (1,2) 15RBT2-80E (3,4) 13.8 15.5 110 15RBA2-PDM


100E 15RBA2-100E (1,2) 15RBT2-100E (3,4)
125E 15RBA2-125E (1,2) 15RBT2-125E (3,4)
150E 15RBA2-150E (1,2) 15RBT2-150E (3,4)
200E 15RBA2-200E (1,2) 15RBT2-200E (3,4)
15.5 kV Maximum (14.4 kV Nominal) 15.5 kV Maximum (14.4 kV Nominal)
400 Ampere 400 Ampere (For Use with 15RBA4 Fuseholders)
.5E 15RBA4-.5E (5,6) — — 13.8 15.5 95 14RBA4-PNM RBA4-FLTR
3E 15RBA4-3E (5,6) — — 13.8 15.5 110 15RBA4-PNM RBA4-COND
Non-Disconnect

14RBA4-GNM
15RBA4-INH
15RBA4-NH

5E 15RBA4-5E (5,6) — — 15RBA4-NL


7E 15RBA4-7E (5,6) — —
10E 15RBA4-10E (5,6) — —
15E 15RBA4-15E (5,6) — —
20E 15RBA4-20E (5,6) 15RBT4-20E (7,8)
25E 15RBA4-25E (5,6) 15RBT4-25E (7,8)

15RBA4-SHNT
.5E to 400E

30E 15RBA4-30E (5,6) 15RBT4-30E (7,8)


2.3 (1.0)

40E 15RBA4-40E (5,6) 15RBT4-40E (7,8) 13.8 15.5 95 14RBA4-PDM


50E 15RBA4-50E (5,6) 15RBT4-50E (7,8) 13.8 15.5 110 15RBA4-PDM
65E 15RBA4-65E (5,6) 15RBT4-65E (7,8)
14RBA4-GDM
15RBA4-IDH
15RBA4-DH

15RBA4-DL

80E 15RBA4-80E (5,6) 15RBT4-80E (7,8)


Disconnect

100E 15RBA4-100E (5,6) 15RBT4-100E (7,8)


125E 15RBA4-125E (5,6) 15RBT4-125E (7,8)
150E 15RBA4-150E (5,6) 15RBT4-150E (7,8)
200E 15RBA4-200E (5,6) 15RBT4-200E (7,8)
250E 15RBA4-250E (5,6) 15RBT4-250E (10,11)
300E 15RBA4-300E (5,6) 15RBT4-300E (10,11)
400E 15RBA4-400E (5,6) 15RBT4-400E (10,11)
15.5 kV Maximum (14.4 kV Nominal) 15.5 kV Maximum (14.4 kV Nominal)
800 Ampere 800 Ampere (For Use with 15RBA8 Fuseholders)
 (2)RBA4-FLTR 
Non-Disconnect

450E (2)15RBA4-250E (9) (2)15RBT4-250E (12) 13.8 15.5 95 14RBA8-PNM


15RBA8-SHNT
14RBA8-GNM
450E to 720E

15RBA8-INH
15RBA8-NH

 (2)RBA4-COND 
15RBA8-NL

540E (2)15RBA4-300E (9) (2)15RBT4-300E (12) 13.8 15.5 110 15RBA8-PNM


720E (2)15RBA4-400E (9) (2)15RBT4-400E (12) 

 Requires two fuse refills as shown. Price each refill individually. Example: To order refill units for a 720E, 15 kV fuse, order 2 pieces of an 8RBA4-400E.
 Two filters or condensers required.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder, one mounting, and one filter or condenser per phase.
Live parts can be substituted for the mounting if the user is supplying base support and insulators.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-53
Expulsion Fuses
December 2008
Type RBA

Table 13-47. Type RBA Expulsion Fuses for Use Indoors or in an Enclosure

Approximate Shipping Weight. in Lbs (kg)


Standard Speed Time Lag Fuse- Voltage (kV) Mounting (including Live Live Fuse Filters and Spring
(Fuse Refills) (Fuse Refills) holder Parts less Holder) Parts Condensers and
Porcelain Glass Shunt
Insulator Polyester Assy.

Non-Indicating Catalog Number


Catalog Catalog Catalog Catalog Catalog
Number Number Number Number Number

Indicating Catalog Number

Catalog Number

Catalog Number
Curve Reference

Curve Reference
Ampere Rating

Ampere Rating

Maximum
Nominal
36-635

36-635

Style

BIL
RBA/RBT Refill Units RBA Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders
for Indoor or Enclosure Applications)
25.5 kV Maximum (23.0 kV Nominal) 25.5 kV Maximum (23.0 kV Nominal)
200 Ampere 200 Ampere (For Use with 25RBA2 Fuseholders)
10E 25RBA2-10E (1,2) — — 23.0 25.5 150 25RBA2-PNM — RBA2-FLTR
Non-Disconnect

25RBA2-INH
25RBA2-NH

38RBA2-NL
15E 25RBA2-15E (1,2) — — RBA2-COND
20E 25RBA2-20E (1,2) 25RBT2-20E (3,4)
25E 25RBA2-25E (1,2) 25RBT2-25E (3,4)

25RBA2-SHNT
30E 25RBA2-30E (1,2) 25RBT2-30E (3,4)
10E to 200E

40E 25RBA2-40E (1,2) 25RBT2-40E (3,4)


1.3 (.6)

50E 25RBA2-50E (1,2) 25RBT2-50E (3,4)


65E 25RBA2-65E (1,2) 25RBT2-65E (3,4) 23.0 25.5 150 25RBA2-PDM —
25RBA2-IDH
25RBA2-DH

38RBA2-DL
Disconnect

80E
100E
25RBA2-80E
25RBA2-100E
(1,2)
(1,2)
25RBT2-80E
25RBT2-100E
(3,4)
(3,4)
13
125E 25RBA2-125E (1,2) 25RBT2-125E (3,4)
150E 25RBA2-150E (1,2) 25RBT2-150E (3,4)
200E 25RBA2-200E (1,2) 25RBT2-200E (3,4)
25.5 kV Maximum (23.0 kV Nominal) 25.5 kV Maximum (23.0 kV Nominal)
400 Ampere 400 Ampere (For Use with 25RBA4 Fuseholders)
.5E 25RBA4-.5E (5,6) — — 23.0 25.5 150 25RBA4-PNM — RBA4-FLTR
3E 25RBA4-3E (5,6) — — RBA4-COND
Non-Disconnect

25RBA4-SHNT
25RBA4-INH
25RBA4-NH

38RBA4-NL
5E 25RBA4-5E (5,6) — —
.5E to 300E
2.7 (1.2)

7E 25RBA4-7E (5,6) — —
10E 25RBA4-10E (5,6) — —
15E 25RBA4-15E (5,6) — —
20E 25RBA4-20E (5,6) 25RBT4-20E (7,8)
25E 25RBA4-25E (5,6) 25RBT4-25E (7,8)
30E 25RBA4-30E (5,6) 25RBT4-30E (7,8)
40E 25RBA4-40E (5,6) 25RBT4-40E (7,8) 23.0 25.5 150 25RBA4-PDM —
50E 25RBA4-50E (5,6) 25RBT4-50E (7,8)
65E 25RBA4-65E (5,6) 25RBT4-65E (7,8)
25RBA4-IDH
25RBA4-DH

38RBA4-DL
Disconnect

80E 25RBA4-80E (5,6) 25RBT4-80E (7,8)


100E 25RBA4-100E (5,6) 25RBT4-100E (7,8)
125E 25RBA4-125E (5,6) 25RBT4-125E (7,8)
150E 25RBA4-150E (5,6) 25RBT4-150E (7,8)
200E 25RBA4-200E (5,6) 25RBT4-200E (7,8)
250E 25RBA4-250E (5,6) 25RBT4-250E (10,11)
300E 25RBA4-300E (5,6) 25RBT4-300E (10,11)
25.5 kV Maximum (23.0 kV Nominal) 25.5 kV Maximum (23.0 kV Nominal)
800 Ampere 800 Ampere (For Use with 25RBA8 Fuseholders)
 (2)RBA4-FLTR 
Non-Disconnect

450E (2)25RBA4-250E (9) (2)25RBT4-250E (12) 23.0 25.5 150 25RBA8-PNM —


25RBA8-SHNT
450E to 540E

25RBA8-INH
25RBA8-NH

 (2)RBA4-COND 
38RBA8-NL

540E (2)25RBA4-300E (9) (2)25RBT4-300E (12)

 Requires two fuse refills as shown. Price each refill individually. Example: To order refill units for a 720E, 25 kV fuse, order 2 pieces of an 8RBA4-400E.
 Two filters or condensers required.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder, one mounting, and one filter or condenser per phase.
Live parts can be substituted for the mounting if the user is supplying base support and insulators.

CA08101001E For more information visit: www.eaton.com


13-54 Power Breakers, Contactors & Fuses
Expulsion Fuses
December 2008
Type RBA

Table 13-47. Type RBA Expulsion Fuses for Use Indoors or in an Enclosure (Continued)

Approximate Shipping Weight. in Lbs (kg)


Standard Speed Time Lag Fuse- Voltage (kV) Mounting (including Live Live Fuse Filters and Spring
(Fuse Refills) (Fuse Refills) holder Parts less Holder) Parts Condensers and
Porcelain Glass Shunt
Insulator Polyester Assy.

Non-Indicating Catalog Number


Catalog Catalog Catalog Catalog Catalog
Number Number Number Number Number

Indicating Catalog Number

Catalog Number

Catalog Number
Curve Reference

Curve Reference
Ampere Rating

Ampere Rating

Maximum
Nominal
36-635

36-635

Style

BIL
RBA/RBT Refill Units RBA Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders
for Indoor or Enclosure Applications)
38.0 kV Maximum (34.5 kV Nominal) 38.0 kV Maximum (34.5 kV Nominal)
200 Ampere 200 Ampere (For Use with 38RBA2 Fuseholders)
10E 38RBA2-10E (1,2) — — 34.5 38.0 150 38RBA2-PNM — RBA2-FLTR
Non-Disconnect

38RBA2-INH
38RBA2-NH

38RBA2-NL
15E 38RBA2-15E (1,2) — — RBA2-COND
20E 38RBA2-20E (1,2) 38RBT2-20E (3,4)
25E 38RBA2-25E (1,2) 38RBT2-25E (3,4)

38RBA2-SHNT
30E 38RBA2-30E (1,2) 38RBT2-30E (3,4)
10E to 200E

40E 38RBA2-40E (1,2) 38RBT2-40E (3,4)


1.4 (.6)

50E 38RBA2-50E (1,2) 38RBT2-50E (3,4)


65E 38RBA2-65E (1,2) 38RBT2-65E (3,4) 34.5 38.0 150 38RBA2-PDM —
38RBA2-IDH
38RBA2-DH

38RBA2-DL
Disconnect

13 80E
100E
38RBA2-80E
38RBA2-100E
(1,2)
(1,2)
38RBT2-80E
38RBT2-100E
(3,4)
(3,4)
125E 38RBA2-125E (1,2) 38RBT2-125E (3,4)
150E 38RBA2-150E (1,2) 38RBT2-150E (3,4)
200E 38RBA2-200E (1,2) 38RBT2-200E (3,4)
38.0 kV Maximum (34.5 kV Nominal) 38.0 kV Maximum (34.5 kV Nominal)
400 Ampere 400 Ampere (For Use with 38RBA4 Fuseholders)
.5E 38RBA4-.5E (5,6) — — 34.5 38.0 150 38RBA4-PNM — RBA4-FLTR
3E 38RBA4-3E (5,6) — — RBA4-COND
Non-Disconnect

38RBA4-INH
38RBA4-NH

38RBA4-NL
5E 38RBA4-5E (5,6) — —
7E 38RBA4-7E (5,6) — —
10E 38RBA4-10E (5,6) — —
15E 38RBA4-15E (5,6) — —
20E 38RBA4-20E (5,6) 38RBT4-20E (7,8)

38RBA4-SHNT
25E 38RBA4-25E (5,6) 38RBT4-25E (7,8)
.5E to 300E
3.1 (1.4)

30E 38RBA4-30E (5,6) 38RBT4-30E (7,8)


40E 38RBA4-40E (5,6) 38RBT4-40E (7,8) 34.5 38.0 150 38RBA4-PDM —
50E 38RBA4-50E (5,6) 38RBT4-50E (7,8)
65E 38RBA4-65E (5,6) 38RBT4-65E (7,8)
38RBA4-IDH
38RBA4-DH

38RBA4-DL
Disconnect

80E 38RBA4-80E (5,6) 38RBT4-80E (7,8)


100E 38RBA4-100E (5,6) 38RBT4-100E (7,8)
125E 38RBA4-125E (5,6) 38RBT4-125E (7,8)
150E 38RBA4-150E (5,6) 38RBT4-150E (7,8)
200E 38RBA4-200E (5,6) 38RBT4-200E (7,8)
250E 38RBA4-250E (5,6) 38RBT4-250E (10,11)
300E 38RBA4-300E (5,6) 38RBT4-300E (10,11)
38.0 kV Maximum (34.5 kV Nominal) 38.0 kV Maximum (34.5 kV Nominal)
800 Ampere 800 Ampere (For Use with 38RBA8 Fuseholders)
 (2)RBA4-FLTR 
Non-Disconnect

450E (2)38RBA4-250E (9) (2)38RBT4-250E (12) 34.5 38.0 150 38RBA8-PNM —


38RBA8-SHNT
450E to 540E

38RBA8-INH
38RBA8-NH

 (2)RBA4-COND 
38RBA8-NL

540E (2)38RBA4-300E (9) (2)38RBT4-300E (12)

 Requires two fuse refills as shown. Price each refill individually. Example: To order refill units for a 720E, 38 kV fuse, order 2 pieces of an 8RBA4-400E.
 Two filters or condensers required.
Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder, one mounting, and one filter or condenser per phase.
Live parts can be substituted for the mounting if the user is supplying base support and insulators.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-55
Expulsion Fuses
December 2008
Types RBA and RDB

Table 13-48. Type RDB Expulsion Fuses for Use Outdoors

Approximate Shipping Weight. in Lbs (kg)


Standard Speed Time Lag Fuse- Voltage (kV) Mounting (including Live Live Spring
(Fuse Refills) (Fuse Refills) holder Parts less Holder) Parts and
Catalog Catalog Catalog Catalog Shunt
Number Number Number Number Assy.
Vertical Underhung Vertical Under- Catalog
(180°) (90°) hung Number
Mounting Mounting

Catalog Number
Curve Reference

Curve Reference
Ampere Rating

Ampere Rating

Maximum
Nominal
36-635

36-635

Style

BIL
RBA/RBT Refill Units RBD Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders
for Outdoor Applications)
8.3 kV Maximum (7.2 kV Nominal) 8.3 kV Maximum (7.2 kV Nominal)
200 Ampere 200 Ampere
10E 8RBA2-10E (1,2) — — 7.2 8.3 95 8RDB2-VM 8RDB2-UM RDB2-VL RDB2-UL
15E 8RBA2-15E (1,2) — —
20E 8RBA2-20E (1,2) 8RBT2-20E (3,4)
25E 8RBA2-25E (1,2) 8RBT2-25E (3,4)

8RDB2-SHNT
30E 8RBA2-30E (1,2) 8RBT2-30E (3,4)
10E to 200E
Disconnect
8RDB2-DH
1.0 (.45)

40E 8RBA2-40E (1,2) 8RBT2-40E (3,4)


50E 8RBA2-50E (1,2) 8RBT2-50E (3,4)
65E 8RBA2-65E (1,2) 8RBT2-65E (3,4) 7.2 8.3 95 8RDB2-HVM 8RDB2-HUM
80E
100E
8RBA2-80E
8RBA2-100E
(1,2)
(1,2)
8RBT2-80E
8RBT2-100E
(3,4)
(3,4)
13
125E 8RBA2-125E (1,2) 8RBT2-125E (3,4)
150E 8RBA2-150E (1,2) 8RBT2-150E (3,4)
200E 8RBA2-200E (1,2) 8RBT2-200E (3,4)
8.3 kV Maximum (7.2 kV Nominal) 8.3 kV Maximum (7.2 kV Nominal)
400 Ampere 400 Ampere
.5E 8RBA4-.5E (5,6) — — 7.2 8.3 95 8RDB4-VM 8RDB4-UM RDB4-VL RDB4-UL
3E 8RBA4-3E (5,6) — —
5E 8RBA4-5E (5,6) — —
7E 8RBA4-7E (5,6) — —
10E 8RBA4-10E (5,6) — —
15E 8RBA4-15E (5,6) — —
20E 8RBA4-20E (5,6) 8RBT4-20E (7,8)
25E 8RBA4-25E (5,6) 8RBT4-25E (7,8)

8RDB4-SHNT
Disconnect
.5E to 400E

8RDB4-DH

30E 8RBA4-30E (5,6) 8RBT4-30E (7,8)


2.1 (.95)

40E 8RBA4-40E (5,6) 8RBT4-40E (7,8) 7.2 8.3 95 8RDB4-HVM 8RDB4-HUM


50E 8RBA4-50E (5,6) 8RBT4-50E (7,8)
65E 8RBA4-65E (5,6) 8RBT4-65E (7,8)
80E 8RBA4-80E (5,6) 8RBT4-80E (7,8)
100E 8RBA4-100E (5,6) 8RBT4-100E (7,8)
125E 8RBA4-125E (5,6) 8RBT4-125E (7,8)
150E 8RBA4-150E (5,6) 8RBT4-150E (7,8)
200E 8RBA4-200E (5,6) 8RBT4-200E (7,8)
250E 8RBA4-250E (5,6) 8RBT4-250E (10,11)
300E 8RBA4-300E (5,6) 8RBT4-300E (10,11)
400E 8RBA4-400E (5,6) 8RBT4-400E (10,11)
8.3 kV Maximum (7.2 kV Nominal) 8.3 kV Maximum (7.2 kV Nominal)
800 Ampere 800 Ampere

8RDB8-SHNT

450E (2)8RBA4-250E (9) (2)8RBT4-250E (12) 7.2 8.3 95 8RDB8-VM 8RDB8-UM RDB8-VL RDB8-UL
450E to 720E
Disconnect
8RDB8-NH

540E (2)8RBA4-300E (9) (2)8RBT4-300E (12) 


720E (2)8RBA4-400E (9) (2)8RBT4-400E (12)
7.2 8.3 95 8RDB8-HVM 8RDB8-HUM

 Requires two fuse refills as shown. Price each refill individually.


Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder and one mounting per phase. Live parts can be
substituted for the mounting if the user is supplying base support and insulators.

CA08101001E For more information visit: www.eaton.com


13-56 Power Breakers, Contactors & Fuses
Expulsion Fuses
December 2008
Types RBA and RDB

Table 13-48. Type RDB Expulsion Fuses for Use Outdoors (Continued)

Approximate Shipping Weight. in Lbs (kg)


Standard Speed Time Lag Fuse- Voltage (kV) Mounting (including Live Live Spring
(Fuse Refills) (Fuse Refills) holder Parts less Holder) Parts and
Catalog Catalog Catalog Catalog Shunt
Number Number Number Number Assy.
Vertical Underhung Vertical Under- Catalog
(180°) (90°) hung Number
Mounting Mounting

Catalog Number
Curve Reference

Curve Reference
Ampere Rating

Ampere Rating

Maximum
Nominal
36-635

36-635

Style

BIL
RBA/RBT Refill Units RDB Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders
for Outdoor Applications)
15.5 kV Maximum (14.4 kV Nominal) 15.5 kV Maximum (14.4 kV Nominal)
200 Ampere 200 Ampere
10E 15RBA2-10E (1,2) — — 13.8 15.5 110 15RDB2-VM 15RDB2-UM RDB2-VL RDB2-UL
15E 15RBA2-15E (1,2) — —
20E 15RBA2-20E (1,2) 15RBT2-20E (3,4)
25E 15RBA2-25E (1,2) 15RBT2-25E (3,4)

15RDB2-SHNT
30E 15RBA2-30E (1,2) 15RBT2-30E (3,4)
15RDB2-DH
10E to 200E
Disconnect
1.1 (.50)

40E 15RBA2-40E (1,2) 15RBT2-40E (3,4)


50E 15RBA2-50E (1,2) 15RBT2-50E (3,4)
65E 15RBA2-65E (1,2) 15RBT2-65E (3,4) 13.8 15.5 150 15RDB2-HVM 15RDB2-HUM
13 80E
100E
15RBA2-80E
15RBA2-100E
(1,2)
(1,2)
15RBT2-80E
15RBT2-100E
(3,4)
(3,4)
125E 15RBA2-125E (1,2) 15RBT2-125E (3,4)
150E 15RBA2-150E (1,2) 15RBT2-150E (3,4)
200E 15RBA2-200E (1,2) 15RBT2-200E (3,4)
15.5 kV Maximum (14.4 kV Nominal) 15.5 kV Maximum (14.4 kV Nominal)
400 Ampere 400 Ampere
.5E 15RBA4-.5E (5,6) — — 13.8 15.5 110 15RDB4-VM 15RDB4-UM RDB4-VL RDB4-UL
3E 15RBA4-3E (5,6) — —
5E 15RBA4-5E (5,6) — —
7E 15RBA4-7E (5,6) — —
10E 15RBA4-10E (5,6) — —
15E 15RBA4-15E (5,6) — —
20E 15RBA4-20E (5,6) 15RBT4-20E (7,8)
25E 15RBA4-25E (5,6) 15RBT4-25E (7,8)

15RDB4-SHNT
15RDB4-DH
Disconnect
.5E to 400E

30E 15RBA4-30E (5,6) 15RBT4-30E (7,8)


2.3 (1.0)

40E 15RBA4-40E (5,6) 15RBT4-40E (7,8) 13.8 15.5 150 15RDB4-HVM 15RDB4-HUM
50E 15RBA4-50E (5,6) 15RBT4-50E (7,8)
65E 15RBA4-65E (5,6) 15RBT4-65E (7,8)
80E 15RBA4-80E (5,6) 15RBT4-80E (7,8)
100E 15RBA4-100E (5,6) 15RBT4-100E (7,8)
125E 15RBA4-125E (5,6) 15RBT4-125E (7,8)
150E 15RBA4-150E (5,6) 15RBT4-150E (7,8)
200E 15RBA4-200E (5,6) 15RBT4-200E (7,8)
250E 15RBA4-250E (5,6) 15RBT4-250E (10,11)
300E 15RBA4-300E (5,6) 15RBT4-300E (10,11)
400E 15RBA4-400E (5,6) 15RBT4-400E (10,11)
15.5 kV Maximum (14.4 kV Nominal) 15.5 kV Maximum (14.4 kV Nominal)
800 Ampere 800 Ampere

15RDB8-SHNT

450E (2)15RBA4-250E (9) (2)15RBT4-250E (12) 13.8 15.5 110 15RDB8-VM 15RDB8-UM RDB8-VL RDB8-UL
450E to 720E

15RDB8-NH
Disconnect

540E (2)15RBA4-300E (9) (2)15RBT4-300E (12) 


720E (2)15RBA4-400E (9) (2)15RBT4-400E (12) 13.8 15.5 150 15RDB8-HVM 15RDB8-HUM

 Requires two fuse refills as shown. Price each refill individually.


Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder and one mounting per phase. Live parts can be
substituted for the mounting if the user is supplying base support and insulators.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-57
Expulsion Fuses
December 2008
Types RBA and RDB

Table 13-48. Type RDB Expulsion Fuses for Use Outdoors (Continued)

Approximate Shipping Weight. in Lbs (kg)


Standard Speed Time Lag Fuse- Voltage (kV) Mounting (including Live Live Spring
(Fuse Refills) (Fuse Refills) holder Parts less Holder) Parts and
Catalog Catalog Catalog Catalog Shunt
Number Number Number Number Assy.
Vertical Underhung Vertical Under- Catalog
(180°) (90°) hung Number
Mounting Mounting

Catalog Number
Curve Reference

Curve Reference
Ampere Rating

Ampere Rating

Maximum
Nominal
36-635

36-635

Style

BIL
RBA/RBT Refill Units RDB Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders for
Outdoor Applications)
25.5 kV Maximum (23.0 kV Nominal) 25.5 kV Maximum (23.0 kV Nominal)
200 Ampere 200 Ampere
10E 25RBA2-10E (1,2) — — 23.0 25.5 150 25RDB2-VM 25RDB2-UM RDB2-VL RDB2-UL
15E 25RBA2-15E (1,2) — —
20E 25RBA2-20E (1,2) 25RBT2-20E (3,4)
25E 25RBA2-25E (1,2) 25RBT2-25E (3,4)

25RDB2-SHNT
30E 25RBA2-30E (1,2) 25RBT2-30E (3,4)
25RDB2-DH
10E to 200E
Disconnect

40E 25RBA2-40E (1,2) 25RBT2-40E (3,4)


1.3 (.6)

50E 25RBA2-50E (1,2) 25RBT2-50E (3,4)


65E 25RBA2-65E (1,2) 25RBT2-65E (3,4) 23.0 25.5 200 25RDB2-HVM 25RDB2-HUM
80E
100E
25RBA2-80E
25RBA2-100E
(1,2)
(1,2)
25RBT2-80E
25RBT2-100E
(3,4)
(3,4)
13
125E 25RBA2-125E (1,2) 25RBT2-125E (3,4)
150E 25RBA2-150E (1,2) 25RBT2-150E (3,4)
200E 25RBA2-200E (1,2) 25RBT2-200E (3,4)
25.5 kV Maximum (23.0 kV Nominal) 25.5 kV Maximum (23.0 kV Nominal)
400 Ampere 400 Ampere
.5E 25RBA4-.5E (5,6) — — 23.0 25.5 150 25RDB4-VM 25RDB4-UM RDB4-VL RDB4-UL
3E 25RBA4-3E (5,6) — —
5E 25RBA4-5E (5,6) — —
7E 25RBA4-7E (5,6) — —
10E 25RBA4-10E (5,6) — —
15E 25RBA4-15E (5,6) — —
20E 25RBA4-20E (5,6) 25RBT4-20E (7,8)

25RDB4-SHNT
25E 25RBA4-25E (5,6) 25RBT4-25E (7,8)
25RDB4-DH
Disconnect
.5E to 300E
2.7 (1.2)

30E 25RBA4-30E (5,6) 25RBT4-30E (7,8)


40E 25RBA4-40E (5,6) 25RBT4-40E (7,8) 23.0 25.5 200 25RDB4-HVM 25RDB4-HUM
50E 25RBA4-50E (5,6) 25RBT4-50E (7,8)
65E 25RBA4-65E (5,6) 25RBT4-65E (7,8)
80E 25RBA4-80E (5,6) 25RBT4-80E (7,8)
100E 25RBA4-100E (5,6) 25RBT4-100E (7,8)
125E 25RBA4-125E (5,6) 25RBT4-125E (7,8)
150E 25RBA4-150E (5,6) 25RBT4-150E (7,8)
200E 25RBA4-200E (5,6) 25RBT4-200E (7,8)
250E 25RBA4-250E (5,6) 25RBT4-250E (10,11)
300E 25RBA4-300E (5,6) 25RBT4-300E (10,11)
25.5 kV Maximum (23.0 kV Nominal) 25.5 kV Maximum (23.0 kV Nominal)
800 Ampere 800 Ampere

25RDB8-SHNT

450E (2)25RBA4-250E (9) (2)25RBT4-250E (12) 23.0 25.5 150 25RDB8-VM 25RDB8-UM RDB8-VL RDB8-UL
450E to 540E

25RDB8-NH
Disconnect

540E (2)25RBA4-300E (9) (2)25RBT4-300E (12) 

23.0 25.5 200 25RDB8-HVM 25RDB8-HUM

 Requires two fuse refills as shown. Price each refill individually.


Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder and one mounting per phase. Live parts can be
substituted for the mounting if the user is supplying base support and insulators.

CA08101001E For more information visit: www.eaton.com


13-58 Power Breakers, Contactors & Fuses
Expulsion Fuses
December 2008
Types RBA and RDB

Table 13-49. Type RBA Expulsion Fuses for Use Indoors or in an Enclosure

Approximate Shipping Weight. in Lbs (kg)


Standard Speed Time Lag Fuse- Voltage (kV) Mounting (including Live Live Spring
(Fuse Refills) (Fuse Refills) holder Parts less Holder) Parts and
Catalog Catalog Catalog Catalog Shunt
Number Number Number Number Assy.
Vertical Underhung Vertical Under- Catalog
(180°) (90°) hung Number
Mounting Mounting

Catalog Number
Curve Reference

Curve Reference
Ampere Rating

Ampere Rating

Maximum
Nominal
36-635

36-635

Style

BIL
RBA/RBT Refill Units RDB Fuseholders, Mountings and Hardware (For Use with RBA/RBT Refills/Holders for
Outdoor Applications)
38.0 kV Maximum (34.5 kV Nominal) 38.0 kV Maximum (34.5 kV Nominal)
200 Ampere 200 Ampere
10E 38RBA2-10E (1,2) — — 34.5 38.0 200 38RDB2-VM 38RDB2-UM RDB2-VL RDB2-UL
15E 38RBA2-15E (1,2) — —
20E 38RBA2-20E (1,2) 38RBT2-20E (3,4)
25E 38RBA2-25E (1,2) 38RBT2-25E (3,4)

38RDB2-SHNT
30E 38RBA2-30E (1,2) 38RBT2-30E (3,4)
38RDB2-DH
10E to 200E
Disconnect

40E 38RBA2-40E (1,2) 38RBT2-40E (3,4)


1.4 (.6)

50E 38RBA2-50E (1,2) 38RBT2-50E (3,4)


65E 38RBA2-65E (1,2) 38RBT2-65E (3,4) 34.5 38.0 250 38RDB2-HVM 38RDB2-HUM
13 80E
100E
38RBA2-80E
38RBA2-100E
(1,2)
(1,2)
38RBT2-80E
38RBT2-100E
(3,4)
(3,4)
125E 38RBA2-125E (1,2) 38RBT2-125E (3,4)
150E 38RBA2-150E (1,2) 38RBT2-150E (3,4)
200E 38RBA2-200E (1,2) 38RBT2-200E (3,4)
38.0 kV Maximum (34.5 kV Nominal) 38.0 kV Maximum (34.5 kV Nominal)
400 Ampere 400 Ampere
.5E 38RBA4-.5E (5,6) — — 34.5 38.0 150 38RDB4-VM 38RDB4-UM RDB4-VL RDB4-UL
3E 38RBA4-3E (5,6) — —
5E 38RBA4-5E (5,6) — —
7E 38RBA4-7E (5,6) — —
10E 38RBA4-10E (5,6) — —
15E 38RBA4-15E (5,6) — —
20E 38RBA4-20E (5,6) 38RBT4-20E (7,8)

38RDB4-SHNT
25E 38RBA4-25E (5,6) 38RBT4-25E (7,8)
38RDB4-DH
Disconnect
.5E to 300E
3.1 (1.4)

30E 38RBA4-30E (5,6) 38RBT4-30E (7,8)


40E 38RBA4-40E (5,6) 38RBT4-40E (7,8) 34.5 38.0 200 38RDB4-HVM 38RDB4-HUM
50E 38RBA4-50E (5,6) 38RBT4-50E (7,8)
65E 38RBA4-65E (5,6) 38RBT4-65E (7,8)
80E 38RBA4-80E (5,6) 38RBT4-80E (7,8)
100E 38RBA4-100E (5,6) 38RBT4-100E (7,8)
125E 38RBA4-125E (5,6) 38RBT4-125E (7,8)
150E 38RBA4-150E (5,6) 38RBT4-150E (7,8)
200E 38RBA4-200E (5,6) 38RBT4-200E (7,8)
250E 38RBA4-250E (5,6) 38RBT4-250E (10,11)
300E 38RBA4-300E (5,6) 38RBT4-300E (10,11)
38.0 kV Maximum (34.5 kV Nominal) 38.0 kV Maximum (34.5 kV Nominal)
800 Ampere 800 Ampere

38RDB8-SHNT

450E (2)38RBA4-250E (9) (2)38RBT4-250E (12) 34.5 38.0 150 38RDB8-VM 38RDB8-UM RDB8-VL RDB8-UL
450E to 540E

38RDB8-NH
Disconnect

540E (2)38RBA4-300E (9) (2)38RBT4-300E (12) 

34.5 38.0 200 38RDB8-HVM 38RDB8-HUM

 Requires two fuse refills as shown. Price each refill individually.


Note: For new installation, order one refill (Standard Speed or Time Lag), one fuseholder and one mounting per phase. Live parts can be
substituted for the mounting if the user is supplying base support and insulators.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-59
Expulsion Fuses
December 2008
Type DBU

Table 13-50. Type DBU Expulsion Fuses for Use Indoors or Outdoors

Approximate Shipping Weight. in Lbs (kg)


Ampere Catalog Indoor Outdoor

Maximum Interrupting Rating (kA Symm)


Rating Number Voltage Catalog Voltage
Number

Mounting (Includes Live Parts)


Catalog Number

Catalog Number

Catalog Number
Curve Reference

Disconnect Fuse
Ampere Rating

Ampere Rating
Fuse Mounting
Live Parts Only
End Fittings

End Fittings
Maximum

Maximum
Mounting

Nominal

Nominal
36-643

Style

Style
BIL

BIL
3K DBU17-3K 12, 15 14 14.4 17.0 95

Non-Loadbreak
6K DBU17-6K

DBU17-GNM

DBU17-NL
8K DBU17-8K
10K DBU17-10K
12K DBU17-12K
15K DBU17-15K

DBU-EFOD
3K to 200K

3K to 200K
DBU-EFID

20K DBU17-20K
2.1 (.95)

25K DBU17-25K
30K DBU17-30K 14.4 17.0 95

DBU17-GDM 
40K DBU17-40K

DBU17-DL 
Loadbreak
50K DBU17-50K
65K DBU17-65K
80K DBU17-80K
100K
140K
DBU17-100K
DBU17-140K
13
200K DBU17-200K
5E DBU17-5E 11, 14 14 14.4 17.0 95
Non-Loadbreak

7E DBU17-7E
DBU17-GNM

DBU17-NL
10E DBU17-10E
13E DBU17-13E
15E DBU17-15E
20E DBU17-20E
25E DBU17-25E

DBU-EFOD
5E to 200E

5E to 200E
DBU-EFID
2.1 (.95)

30E DBU17-30E
40E DBU17-40E 14.4 17.0 95
50E DBU17-50E
DBU17-GDM 

DBU17-DL 

65E DBU17-65E
Loadbreak

80E DBU17-80E
100E DBU17-100E
125E DBU17-125E
150E DBU17-150E
175E DBU17-175E
200E DBU17-200E
15E DBU17-15SE 10, 13 14 14.4 17.0 95
Non-Loadbreak

DBU17-GNM

20E DBU17-20SE
DBU17-NL

25E DBU17-25SE
30E DBU17-30SE
40E DBU17-40SE
15SE to 200SE

15SE to 200SE
DBU-EFOD

50E DBU17-50SE
DBU-EFID
2.1 (.95)

65E DBU17-65SE
80E DBU17-80SE 14.4 17.0 95
DBU17-GDM 

DBU17-DL 

100E DBU17-100SE
Loadbreak

125E DBU17-125SE
150E DBU17-150SE
175E DBU17-175SE
200E DBU17-200SE

 To complete the Catalog Number, specify “-R” for right side cable termination or “-L” for left side cable termination.
Note: Muffler can be ordered separately. Order Catalog Number DBU-MFLR.

CA08101001E For more information visit: www.eaton.com


13-60 Power Breakers, Contactors & Fuses
Expulsion Fuses
December 2008
Type DBU

Table 13-50. Type DBU Expulsion Fuses for Use Indoors or Outdoors (Continued)

Approximate Shipping Weight. in Lbs (kg)


Ampere Catalog Indoor Outdoor

Maximum Interrupting Rating (kA Symm)


Rating Number Voltage Catalog Voltage
Number

Mounting (Includes Live Parts)


Catalog Number

Catalog Number

Catalog Number
Curve Reference

Disconnect Fuse
Ampere Rating

Ampere Rating
Fuse Mounting
Live Parts Only
End Fittings

End Fittings
Maximum

Maximum
Mounting

Nominal

Nominal
36-643

Style

Style
BIL

BIL
3K DBU27-3K 12, 18 12.5 25 27.0 125
6K DBU27-6K

Non-Loadbreak

DBU27-GNM
8K DBU27-8K

DBU27-NL
10K DBU27-10K
12K DBU27-12K
15K DBU27-15K

DBU-EFOD
3K to 200K

3K to 200K
DBU-EFID

20K DBU27-20K
2.1 (.95)

25K DBU27-25K
30K DBU27-30K
40K DBU27-40K 25 27.0 125

DBU27-GDM 

DBU27-DL 
50K DBU27-50K
Loadbreak

65K DBU27-65K
80K DBU27-80K
13 100K
140K
DBU27-100K
DBU27-140K
200K DBU27-200K
5E DBU27-5E 11, 17 12.5 25 27.0 125
7E DBU27-7E
Non-Loadbreak

10E DBU27-10E
DBU27-GNM

DBU27-NL
13E DBU27-13E
15E DBU27-15E
20E DBU27-20E
25E DBU27-25E

DBU-EFOD
5E to 200E

5E to 200E
DBU-EFID
2.1 (.95)

30E DBU27-30E
40E DBU27-40E
50E DBU27-50E
65E DBU27-65E 25 27.0 125
DBU27-GDM 

DBU27-DL 

80E DBU27-80E
Loadbreak

100E DBU27-100E
125E DBU27-125E
150E DBU27-150E
175E DBU27-175E
200E DBU27-200E
15E DBU27-15SE 10, 16 12.5 25 27.0 125
Non-Loadbreak

20E DBU27-20SE
DBU27-GNM

DBU27-NL

25E DBU27-25SE
30E DBU27-30SE
40E DBU27-40SE
15SE to 200SE

15SE to 200SE

50E DBU27-50SE
DBU-EFOD
DBU-EFID

65E DBU27-65SE
2.1 (.95)

80E DBU27-80SE
100E DBU27-100SE 25 27.0 125
DBU27-GDM 

DBU27-DL 

125E DBU27-125SE
Loadbreak

150E DBU27-150SE
175E DBU27-175SE
200E DBU27-200SE

 To complete the Catalog Number, specify “-R” for right side cable termination or “-L” for left side cable termination.
Note: Muffler can be ordered separately. Order Catalog Number DBU-MFLR.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-61
Expulsion Fuses
December 2008
Type DBU

Table 13-50. Type DBU Expulsion Fuses for Use Indoors or Outdoors (Continued)

Approximate Shipping Weight. in Lbs (kg)


Ampere Catalog Indoor Outdoor
Rating Number

Maximum Interrupting Rating kA Sym.


Voltage Catalog Voltage
Number

Mounting (Include Live Parts)


Catalog Number

Catalog Number

Catalog Number
Curve Reference

Disconnect Fuse
Ampere Rating

Ampere Rating
Fuse Mounting
Live Parts Only
End Fittings

End Fittings
Maximum

Maximum
Mounting

Nominal

Nominal
36-643

Style

Style
BIL

BIL
3K DBU38-3K 12, 18 10 34.5 38.0 150

Non-Loadbreak
6K DBU38-6K

DBU38-GNM

DBU38-NL
8K DBU38-8K
10K DBU38-10K
12K DBU38-12K
15K DBU38-15K

DBU-EFOD
3K to 200K

3K to 200K
DBU-EFID

20K DBU38-20K
2.8 (1.3)

25K DBU38-25K
30K DBU38-30K 34.5 38.0 150
40K DBU38-40K Loadbreak
50K DBU38-50K
65K DBU38-65K
80K DBU38-80K
100K
140K
DBU38-100K
DBU38-140K
13
200K DBU38-200K
5E DBU38-5E 11, 17 10 34.5 38.0 150
7E DBU38-7E
Non-Loadbreak

10E DBU38-10E
DBU38-GNM

DBU38-NL
13E DBU38-13E
15E DBU38-15E
20E DBU38-20E
25E DBU38-25E

DBU-EFOD
5E to 200E

5E to 200E
DBU-EFID

30E DBU38-30E
2.8 (1.3)

40E DBU38-40E
50E DBU38-50E
65E DBU38-65E 34.5 38.0 150
80E DBU38-80E
Loadbreak

100E DBU38-100E
125E DBU38-125E
150E DBU38-150E
175E DBU38-175E
200E DBU38-200E

15E DBU38-15SE 10, 16 10 34.5 38.0 150


Non-Loadbreak

20E DBU38-20SE
DBU38-GNM

DBU38-NL

25E DBU38-25SE
30E DBU38-30SE
40E DBU38-40SE
15SE to 200SE

15SE to 200SE

50E DBU38-50SE
DBU-EFOD
DBU-EFID

65E DBU38-65SE
2.1 (.95)

80E DBU38-80SE
100E DBU38-100SE 34.5 38.0 150
125E DBU38-125SE
Loadbreak

150E DBU38-150SE
175E DBU38-175SE
200E DBU38-200SE

Note: Muffler can be ordered separately. Order Catalog Number DBU-MFLR.

CA08101001E For more information visit: www.eaton.com


13-62 Power Breakers, Contactors & Fuses
Expulsion Fuses
December 2008
Type DBA

Type DBA Expulsion Fuses for Use Indoors or Outdoors


Table 13-51. Type DBA Expulsion Fuses for Use Indoors or Outdoors Type DBA Expulsion Fuses for Use Indoors or Outdoors (Continued)
Ampere DBA-1 Fuse Units Approximate Ampere DBA-1 Fuse Units Approximate
Rating Catalog Curve Reference Shipping Weight Rating Catalog Curve Reference Shipping Weight
Number 36-623 Lbs. (kg) Number 36-623 Lbs. (kg)

Type DBA-1 Fuse Refills Type DBA-1 Fuse Refills


8.3 kV Maximum (7.2 kV Nominal) 38 kV Maximum (34.5 kV Nominal)
0.5E 8DBA1-.5E (10, 11) 2.1 (.95) 0.5E 38DBA1-.5E (10, 12) 4.2 (1.9)
3E 8DBA1-3E 3E 38DBA1-3E
5E 8DBA1-5E 5E 38DBA1-5E
7E 8DBA1-7E 7E 38DBA1-7E
10E 8DBA1-10E 10E 38DBA1-10E
15E 8DBA1-15E 15E 38DBA1-15E
20E 8DBA1-20E 20E 38DBA1-20E
25E 8DBA1-25E 25E 38DBA1-25E
30E 8DBA1-30E 30E 38DBA1-30E
40E 8DBA1-40E 40E 38DBA1-40E
50E 8DBA1-50E 50E 38DBA1-50E
65E 8DBA1-65E 65E 38DBA1-65E
80E 8DBA1-80E 80E 38DBA1-80E
100E 8DBA1-100E 100E 38DBA1-100E
125E 8DBA1-125E 125E 38DBA1-125E
150E 8DBA1-150E 150E 38DBA1-150E
200E 8DBA1-200E 200E 38DBA1-200E
15.5 kV Maximum (14.4 kV Nominal) 48 kV Maximum (46 kV Nominal)
0.5E 15DBA1-.5E (10, 11) 2.1 (.95) 0.5E 48DBA1-.5E (10, 12) 4.2 (1.9)
3E 15DBA1-3E 3E 48DBA1-3E
5E 15DBA1-5E 5E 48DBA1-5E
7E 15DBA1-7E 7E 48DBA1-7E
13 10E
15E
15DBA1-10E
15DBA1-15E
10E
15E
48DBA1-10E
48DBA1-15E
20E 15DBA1-20E 20E 48DBA1-20E
25E 15DBA1-25E 25E 48DBA1-25E
30E 15DBA1-30E 30E 48DBA1-30E
40E 15DBA1-40E 40E 48DBA1-40E
50E 15DBA1-50E 50E 48DBA1-50E
65E 15DBA1-65E 65E 48DBA1-65E
80E 15DBA1-80E 80E 48DBA1-80E
100E 15DBA1-100E 100E 48DBA1-100E
125E 15DBA1-125E 125E 48DBA1-125E
150E 15DBA1-150E 150E 48DBA1-150E
200E 15DBA1-200E 200E 48DBA1-200E
25 kV Maximum (23 kV Nominal) 72 kV Maximum (69 kV Nominal)
0.5E 25DBA1-.5E (10, 11) 2.1 (.95) 0.5E 72DBA1-.5E (10, 12) 7.1 (3.2)
3E 25DBA1-3E 3E 72DBA1-3E
5E 25DBA1-5E 5E 72DBA1-5E
7E 25DBA1-7E 7E 72DBA1-7E
10E 25DBA1-10E 10E 72DBA1-10E
15E 25DBA1-15E 15E 72DBA1-15E
20E 25DBA1-20E 20E 72DBA1-20E
25E 25DBA1-25E 25E 72DBA1-25E
30E 25DBA1-30E 30E 72DBA1-30E
40E 25DBA1-40E 40E 72DBA1-40E
50E 25DBA1-50E 50E 72DBA1-50E
65E 25DBA1-65E 65E 72DBA1-65E
80E 25DBA1-80E 80E 72DBA1-80E
100E 25DBA1-100E 100E 72DBA1-100E
125E 25DBA1-125E 125E 72DBA1-125E
150E 25DBA1-150E 150E 72DBA1-150E
200E 25DBA1-200E 200E 72DBA1-200E

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-63
Expulsion Fuses
December 2008
Type DBA

Table 13-51. Type DBA Expulsion Fuses for Use Table 13-51. Type DBA Expulsion Fuses for Use
Indoors or Outdoors (Continued) Indoors or Outdoors (Continued)
Ampere DBA-2 Fuse Units Approximate Ampere DBA-2 Fuse Units Approximate
Rating Catalog Curve Reference Shipping Weight Rating Catalog Curve Reference Shipping Weight
Number 36-623 Lbs. (kg) Number 36-623 Lbs. (kg)

Type DBA-2 Fuse Refills Type DBA-2 Fuse Refills


38 kV Maximum (34.5 kV Nominal) 92 kV Maximum (92 kV Nominal)
0.5E 38DBA2-.5E (10, 12) 8 (3.6) 0.5E 92DBA2-.5E (10, 13) 16 (7.3)
3E 38DBA2-3E 3E 92DBA2-3E
5E 38DBA2-5E 5E 92DBA2-5E
7E 38DBA2-7E 7E 92DBA2-7E
10E 38DBA2-10E 10E 92DBA2-10E
15E 38DBA2-15E 15E 92DBA2-15E
20E 38DBA2-20E 20E 92DBA2-20E
25E 38DBA2-25E 25E 92DBA2-25E
30E 38DBA2-30E 30E 92DBA2-30E
40E 38DBA2-40E 40E 92DBA2-40E
50E 38DBA2-50E 50E 92DBA2-50E
65E 38DBA2-65E 65E 92DBA2-65E
80E 38DBA2-80E 80E 92DBA2-80E
100E 38DBA2-100E 100E 92DBA2-100E
125E 38DBA2-125E 125E 92DBA2-125E
150E 38DBA2-150E 150E 92DBA2-150E
200E 38DBA2-200E 200E 92DBA2-200E
48 kV Maximum (46 kV Nominal) 121 kV Maximum (115 kV Nominal)
0.5E 48DBA2-.5E (10, 12) 8 (3.6) 0.5E 121DBA2-.5E (10, 13) 15 (6.8)
3E 48DBA2-3E 3E 121DBA2-3E
5E 48DBA2-5E 5E 121DBA2-5E
7E 48DBA2-7E 7E 121DBA2-7E
10E 48DBA2-10E 10E 121DBA2-10E
15E
20E
48DBA2-15E
48DBA2-20E
15E
20E
121DBA2-15E
121DBA2-20E
13
25E 48DBA2-25E 25E 121DBA2-25E
30E 48DBA2-30E 30E 121DBA2-30E
40E 48DBA2-40E 40E 121DBA2-40E
50E 48DBA2-50E 50E 121DBA2-50E
65E 48DBA2-65E 65E 121DBA2-65E
80E 48DBA2-80E 80E 121DBA2-80E
100E 48DBA2-100E 100E 121DBA2-100E
125E 48DBA2-125E 125E 121DBA2-125E
150E 48DBA2-150E 150E 121DBA2-150E
200E 48DBA2-200E 200E 121DBA2-200E
72 kV Maximum (69 kV Nominal) 145 kV Maximum (138 kV Nominal)
0.5E 72DBA2-.5E (10, 12) 16 (7.3) 0.5E 145DBA2-.5E (10, 13) 14 (6.4)
3E 72DBA2-3E 3E 145DBA2-3E
5E 72DBA2-5E 5E 145DBA2-5E
7E 72DBA2-7E 7E 145DBA2-7E
10E 72DBA2-10E 10E 145DBA2-10E
15E 72DBA2-15E 15E 145DBA2-15E
20E 72DBA2-20E 20E 145DBA2-20E
25E 72DBA2-25E 25E 145DBA2-25E
30E 72DBA2-30E 30E 145DBA2-30E
40E 72DBA2-40E 40E 145DBA2-40E
50E 72DBA2-50E 50E 145DBA2-50E
65E 72DBA2-65E 65E 145DBA2-65E
80E 72DBA2-80E 80E 145DBA2-80E
100E 72DBA2-100E 100E 145DBA2-100E
125E 72DBA2-125E 125E 145DBA2-125E
150E 72DBA2-150E 150E 145DBA2-150E
200E 72DBA2-200E 200E 145DBA2-200E

CA08101001E For more information visit: www.eaton.com


13-64 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Product Selection

Current Limiting Fuse Table 13-52. Current Limiting Fuses Catalog Numbering System

Easy to Use, Easy to Order! 15 CLE – 100 E – D


Eaton’s Cutler-Hammer fuse catalog
numbering system makes it easy to
order the right fuse. The catalog num- Maximum kV Type Size
bers are easy to remember, unique to
2 = (2.4, 2.5, 2.75) CLE HCLS Amperes Class A
each fuse, and are broken down in
4 = (4.3, 4.8) HLE LCLS 0.5 – 1350 E D
three descriptive segments: Fuse Type, 5 = (5.08, 5.5) BHLE CX
Voltage Rating and Current Rating. R
7 = (7.2) CLPT CXN C
8 = (8.3) NCLPT CLT X
These Catalog Numbers can be 15 = (15.5) CLS AHLE
entered directly and easily: 25 = (25.5) BCLS CXF
38 = (38.0) CLS70 ACLS
■ No change in order processing will CLS75
occur if you use either a style num-
ber or its corresponding catalog
number. You will get the same fuse. Table 13-53. Current Limiting Fuse Accessories Catalog Numbering System
■ In the back of this ordering guide is
a style number to catalog number
cross reference chart. 15 CLE – P NM – C
Examples:
5CLE-30E 5.5 max. kV, Maximum kV Type Diameter Size
CLE fuse unit, 2 = (2.4, 2.5, 2.75) CLE HCLS Hardware A = 1-5/8 inches
30E amperes 4 = (4.3, 4.8) HLE LCLS DM = Disconnect (41.3 mm)
5 = (5.08, 5.5) CLPT CX Mounting 0.53E – 1.5E
15CXN-45C 15.5 max. kV,
13 CXN fuse unit,
7 = (7.2)
8 = (8.3)
NCLPT
CLS
CXN
CLT
NM = Nondisconnect
Mounting
Single Barrel
B = 1-5/8 inches
45C amperes 15 = (15.5) CLS75 DL = Disconnect (41.3 mm) 3E
25 = (25.5) Live Parts – 10E Single
5CLS-GDM-E 5.5 max. kV, 38 = (38.0) NL = Nondisconnect Barrel
CLS fuse unit, Live Parts C = 2-inch (50.8
Glass Polyester DF = Disconnect mm) Single
End Fittings Barrel
Nondisconnect D = 3-inch (76.2
Mounting mm) Single
Insulator Barrel
CLE-DL-D CLE, E = 3-inch (76.2
Disconnect Live Parts G = Glass Polyester mm) Double
Size D P = Porcelain Barrel
H = High BIL F = 4-inch (101.6
mm) Double
Barrel
G = 5/8-inch (15.9
mm) Ferrule
(CX/CXN
Only)

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-65
Current Limiting Fuses
December 2008
Type CLE

Table 13-54. Type CLE Current Limiting Fuses


Catalog Mounting Catalog Performance

Interrupting Rating rms


Number (Includes Live Parts, End Fittings) Number Curves

Clip Center (Inches)


Type Catalog Number Live End

Peak Let-Through
Maximum Design

Diameter (Inches)

Approx. Shipping

Heritage Product
Parts  Fittings 

Voltage (BIL) kV
Indoor/Outdoor
Length (Inches)
Porcelain Glass-
Current Rating

Barrel Number

Total Clearing
Melting Time
Polyester

Weight (lbs.)
Voltage (kV)

(Amperes)

(kA Sym.)

Minimum

Current
Time
2.75 kV Maximum (2.4 kV Nominal)
15E 2CLE-15E 1 50 2 8.13 9.5 2 H I Non- 60 2CLE-PNM-C 2CLE-GNM-C CLE-NL-C —

56353202

56353302

63931702
20E 2CLE-20E 1 50 2 8.13 9.5 2 H I Disconnect
25E 2CLE-25E 1 50 2 8.13 9.5 2 H I Disconnect 60 2CLE-PDM-C 2CLE-GDM-C CLE-DL-C CLE-DF-C

10E 2CLE-10E 1 50 3 7 10.9 7 H I Non- 60 2CLE-PNM-D 2CLE-GNM-D CLE-NL-D —


30E 2CLE-30E 1 50 3 7 10.9 7 H I Disconnect
40E 2CLE-40E 1 50 3 7 10.9 7 H I Disconnect 60 2CLE-PDM-D 2CLE-GDM-D CLE-DL-D CLE-DF-D
50E 2CLE-50E 1 50 3 7 10.9 7 H I
65E 2CLE-65E 1 50 3 7 10.9 7 H I
80E 2CLE-80E 1 50 3 7 10.9 7 H I
100E 2CLE-100E 1 50 3 7 10.9 7 H I

53686104

53686204

63931704
125E 2CLE-125E 1 50 3 7 10.9 7 H I
150E 2CLE-150E 1 50 3 7 10.9 7 H I
200E 2CLE-200E 1 50 3 7 10.9 7 H I
225E 2CLE-225E 1 50 3 7 10.9 7 H I
250E 2CLE-250E 2 50 3 7 10.9 15 H I Non- 60 2CLE-PND-E 2CLE-GNM-E CLE-NL-E —

53690002

53690102

63931802
300E 2CLE-300E 2 50 3 7 10.9 15 H I Disconnect
350X 2CLE-350X 2 50 3 7 10.9 15 H I Disconnect 60 2CLE-PDM-E 2CLE-PDM-E CLE-DL-E CLE-DF-E
400X 2CLE-400X 2 50 3 7 10.9 15 H I
450X 2CLE-450X 2 50 3 7 10.9 15 H I 13
5.5 kV Maximum (4.8 kV Nominal)
15E 5CLE-15E 1 50 2 11.5 12.9 3 H I Non- 60 5CLE-PNM-C 5CLE-GNM-C CLE-NL-C —

56353204

56353304

63931702
20E 5CLE-20E 1 50 2 11.5 12.9 3 H I Disconnect
25E 5CLE-25E 1 50 2 11.5 12.9 3 H I Disconnect 60 5CLE-PDM-C 5CLE-GDM-C CLE-DL-C CLE-DF-C

10E 5CLE-10E-D 1 63 3 14 17.9 9 — I/O Non- 60 5CLE-PNM-D 5CLE-GNM-D CLE-NL-D —

70548501

70548601

70548701
15E 5CLE-15E-D 1 63 3 14 17.9 9 — I/O Disconnect
20E 5CLE-20E-D 1 63 3 14 17.9 9 — I/O Disconnect 60 5CLE-PDM-D 5CLE-GDM-D CLE-DL-D CLE-DF-D
25E 5CLE-25E-D 1 63 3 14 17.9 9 — I/O
30E 5CLE-30E-D 1 63 3 14 17.9 9 — I/O
40E 5CLE1-40E 1 50 3 14 17.9 9 H I Non- 60 5CLE-PNM-D 5CLE-GNM-D CLE-NL-D —
50E 5CLE1-50E 1 50 3 14 17.9 9 H I Disconnect

62908902 70546001 70545801 53686104

62908903 70546101 70545901 53686204

62908904 70547601 70547601 63931704


65E 5CLE1-65E 1 50 3 14 17.9 9 H I Disconnect 60 5CLE-PDM-D 5CLE-GDM-D CLE-DL-D CLE-DF-D
80E 5CLE1-80E 1 50 3 14 17.9 9 H I
100E 5CLE1-100E 1 50 3 14 17.9 9 H I
125E 5CLE1-125E 1 50 3 14 17.9 9 H I
150E 5CLE-150E 1 63 3 14 17.9 9 — I/O Non- 60 5CLE-PNM-D 5CLE-GNM-D CLE-NL-D —
175E 5CLE-175E 1 63 3 14 17.9 9 — I/O Disconnect
200E 5CLE-200E 1 63 3 14 17.9 9 — I/O Disconnect 60 5CLE-PDM-D 5CLE-GDM-D CLE-DL-D CLE-DF-D
250E 5CLE-250E 1 63 3 14 17.9 9 — I/O
300E 5CLE-300E 2 63 3 14 17.9 19 — I/O Non- 60 5CLE-PNM-E 5CLE-GNM-E CLE-NL-E —
350E 5CLE-350E 2 63 3 14 17.9 19 — I/O Disconnect
400E 5CLE-400E 2 63 3 14 17.9 19 — I/O Disconnect 60 5CLE-PDM-E 5CLE-GDM-E CLE-DL-E CLE-DF-E
450E 5CLE-450E 2 63 3 14 17.9 19 — I/O
600E 5CLE-600E 2 40 4 N/A N/A 40 — I Non- 60 Refer to Factory.
750E 5CLE-750E 2 40 4 40 — I Disconnect
1100E 5CLE-1100E 4 31 4 80 — I
1350E 5CLE-1350E 4 31 4 80 — I
 Includes end fittings.
 Disconnect only.

CA08101001E For more information visit: www.eaton.com


13-66 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Type CLE

Table 13-55. Type CLE Current Limiting Fuses


Ampere Fuse Mounting Voltage Mounting Live Parts End Fittings
Rating Type  BIL (kV) (Including Live Parts, (Including (Disconnect
End Fittings)  End Fittings)  Only)
Porcelain Glass-Polyester Catalog Catalog
Insulator Insulator Number Number
Catalog Catalog
Number Number
CLE Mountings and Hardware
2.75 kV Maximum (2.4 kV Nominal)
10E Non-Disconnect 60 2CLE-PNM-D 2CLE-GNM-D CLE-NL-D —
Disconnect 60 2CLE-PDM-D 2CLE-GDM-D CLE-DL-D CLE-DF-D
15E to 30E Non-Disconnect 60 2CLE-PNM-C 2CLE-GNM-C CLE-NL-C —
Disconnect 60 2CLE-PDM-C 2CLE-GDM-C CLE-DL-C CLE-DF-C
30E to 225E Non-Disconnect 60 2CLE-PNM-D 2CLE-GNM-D CLE-NL-D —
Disconnect 60 2CLE-PDM-D 2CLE-GDM-D CLE-DL-D CLE-DF-D
250E to 450E Non-Disconnect 60 2CLE-PNM-E 2CLE-GNM-E CLE-NL-E —
Disconnect 60 2CLE-PDM-E 2CLE-GDM-E CLE-DL-E CLE-DF-E
CLE Mountings and Hardware
5.5 kV Maximum (4.8 kV Nominal)
10E Non-Disconnect 60 5CLE-PNM-D 5CLE-GNM-D CLE-NL-D —
Disconnect 60 5CLE-PDM-D 5CLE-GDM-D CLE-DL-D CLE-DF-D
15E to 25E Non-Disconnect 60 5CLE-PNM-C 5CLE-GNM-C CLE-NL-C —
Disconnect 60 5CLE-PDM-C 5CLE-GDM-C CLE-DL-C CLE-DF-C
40E to 250E Non-Disconnect 60 5CLE-PNM-D 5CLE-GNM-D CLE-NL-D —
Disconnect 60 5CLE-PDM-D 5CLE-GDM-D CLE-DL-D CLE-DF-D
300E to 450E Non-Disconnect 60 5CLE-PNM-E 5CLE-GNM-E CLE-NL-E —
Disconnect 60 5CLE-PDM-E 5CLE-GDM-E CLE-DL-E CLE-DF-E
13 600E and 750E Non-Disconnect 60 9078A70G01 9078A70G02 — —
1100 and 1350 (Consult Factory)
 See Page 13-88 for diagram of typical mounting.
 End fittings supplied only when required.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-67
Current Limiting Fuses
December 2008
Type CLE

Table 13-56. Type CLE Current Limiting Fuses


Catalog Mounting Catalog Performance

Interrupting Rating rms


Number (Includes Live Parts, End Fittings) Number Curves

Clip Center (Inches)


Type Catalog Number Live End

Peak Let-Through
Maximum Design

Diameter (Inches)

Approx. Shipping

Heritage Product
Parts  Fittings 

Voltage (BIL) kV
Indoor/Outdoor
Length (Inches)
Porcelain Glass-
Current Rating

Barrel Number

Total Clearing
Melting Time
Polyester

Weight (lbs.)
Voltage (kV)

(Amperes)

(kA Sym.)

Minimum

Current
Time
8.3 kV Maximum (7.2 kV Nominal)
15E 8CLE-15E 1 50 2 14 15.5 3 H I Non- 75 8CLE-PNM-C 8CLE-GNM-C CLE-NL-C —

56353204

56353304

63931703
20E 8CLE-20E 1 50 2 14 15.5 3 H I Disconnect
25E 8CLE-25E 1 50 2 14 15.5 3 H I Disconnect 75 8CLE-PDM-C 8CLE-GDM-C CLE-DL-C CLE-DF-C

10E 8CLE-10E-D 1 50 3 14 17.9 9 — I/O Non- 75 8CLE-PNM-D 8CLE-GNM-D CLE-NL-D —

70548501

70548601

70548801
15E 8CLE-15E-D 1 50 3 14 17.9 9 — I/O Disconnect
20E 8CLE-20E-D 1 50 3 14 17.9 9 — I/O Disconnect 75 8CLE-PDM-D 8CLE-GDM-D CLE-DL-D CLE-DF-D
25E 8CLE-25E-D 1 50 3 14 17.9 9 — I/O
30E 8CLE-30E-D 1 50 3 14 17.9 9 — I/O
40E 8CLE-40E 1 50 3 14 17.9 9 — I/O Non- 75 8CLE-PNM-D 8CLE-GNM-D CLE-NL-D —
50E 8CLE-50E 1 50 3 14 17.9 9 — I/O Disconnect
65E 8CLE-65E 1 50 3 14 17.9 9 — I/O Disconnect 75 8CLE-PDM-D 8CLE-GDM-D CLE-DL-D CLE-DF-D
80E 8CLE-80E 1 50 3 14 17.9 9 — I/O

70546401 70546201

70546501 70546301

70547301 70547301
100E 8CLE-100E 1 50 3 14 17.9 9 — I/O
125E 8CLE-125E 1 50 3 14 17.9 9 — I/O
150E 8CLE-150E 1 50 3 14 17.9 9 — I/O
175E 8CLE-175E 1 50 3 14 17.9 9 — I/O
200E 8CLE-200E 2 50 3 14 17.9 19 — I/O Non- 75 8CLE-PNM-E 8CLE-GNM-E CLE-NL-E —
250E
300E
8CLE-250E
8CLE-300E
2
2
50
50
3
3
14
14
17.9
17.9
19
19


I/O Disconnect
I/O Disconnect 75
13
8CLE-PDM-E 8CLE-GDM-E CLE-DL-E CLE-DF-E
350E 8CLE-350E 2 50 3 14 17.9 19 — I/O
15.5 kV Maximum (4.8 kV Nominal)
15E 15CLE-15E 1 31.5 2 20 21.5 4.5 H I Non- 95 15CLE-PNM-C 15CLE-GNM-C CLE-NL-C —
20E 15CLE-20E 1 31.5 2 20 21.5 4.5 H I Disconnect 110 15CLE-HPNM-C —

56353204

56353304

63931703
25E 15CLE-25E 1 31.5 2 20 21.5 4.5 H I
Disconnect 95 15CLE-PDM-C 15CLE-GDM-C CLE-DL-C CLE-DF-C
110 15CLE-HPDM-C —
10E 15CLE-10E-D 1 63 3 20 23.9 11 — I/O Non- 95 15CLE-PNM-D 15CLE-GNM-D CLE-NL-D —
15E 15CLE-15E-D 1 63 3 20 23.9 11 — I/O Disconnect 110 15CLE-HPNM- —
20E 15CLE-20E-D 1 63 3 20 23.9 11 — I/O

70548501

70548601

70548802
D
25E 15CLE-25E-D 1 63 3 20 23.9 11 — I/O
30E 15CLE-30E-D 1 63 3 20 23.9 11 — I/O Disconnect 95 15CLE-PDM-D 15CLE-GDM-D CLE-DL-D CLE-DF-D
110 15CLE-HPDM-D —
40E 15CLE-40E 1 63 3 20 23.9 11 — I/O Non- 95 15CLE-PNM-D 15CLE-GNM-D CLE-NL-D —
50E 15CLE-50E 1 63 3 20 23.9 11 — I/O Disconnect 110 15CLE-HPNM- —
65E 15CLE-65E 1 63 3 20 23.9 11 — I/O D
70546801

70546901

70547501
80E 15CLE-80E 1 63 3 20 23.9 11 — I/O
100E 15CLE-100E 1 63 3 20 23.9 11 — I/O Disconnect 95 15CLE-PDM-D 15CLE-GDM-D CLE-DL-D CLE-DF-D
125E 15CLE-125E 1 63 3 20 23.9 11 — I/O 110 15CLE-HPDM-D —
150E 15CLE-150E 1 63 3 20 23.9 11 — I/O
175E 15CLE-175E 2 63 3 20 23.9 23 — I/O Non- 95 15CLE-PNM-E 15CLE-GNM-E CLE-NL-E —
200E 15CLE-200E 2 63 3 20 23.9 23 — I/O Disconnect 110 15CLE-HPNM-E
70547001

70547101

70547501

250E 15CLE-250E 2 63 3 20 23.9 23 — I/O
300E 15CLE-300E 2 63 3 20 23.9 23 — I/O Disconnect 95 15CLE-PDM-E 15CLE-GDM-E CLE-DL-E CLE-DF-E
110 15CLE-HPDM-E —
80E 15CLE2-80E 2 85 3 20 23.9 23 H I For Replacement Only
100E 15CLE2-100E 2 85 3 20 23.9 23 H I
125X 15CLE2-125X 2 85 3 20 23.9 23 H I
59878302

59878402

63931604

150E 15CLE3-150E 3 50 3 20 23.9 36 H I For Replacement Only


175E/ 15CLE3-175E/ 3 50 3 20 23.9 36 H I
200X 200X
 Includes end fittings.
 Disconnect only.

CA08101001E For more information visit: www.eaton.com


13-68 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Type CLE

Table 13-57. Type CLE Current Limiting Fuses


Ampere Fuse Mounting Voltage Mounting Live Parts End Fittings
Rating Type  BIL (kV) (Including Live Parts, (Including (Disconnect
End Fittings)  End Fittings)  Only)
Porcelain Glass-Polyester Catalog Catalog
Insulator Insulator Number Number
Catalog Catalog
Number Number
CLE Mountings and Hardware
8.3 kV Maximum (7.2 kV Nominal)
15E to 25E Non-Disconnect 75 8CLE-PNM-C 8CLE-GNM-C CLE-NL-C —
Disconnect 75 8CLE-PDM-C 8CLE-GDM-C CLE-DL-C CLE-DF-C
30E to 200E Non-Disconnect 75 8CLE-PNM-D 8CLE-GNM-D CLE-NL-D —
Disconnect 75 8CLE-PDM-D 8CLE-GDM-D CLE-DL-D CLE-DF-D
CLE Mountings and Hardware
15.5 kV Maximum (14.4 kV Nominal)
15E to 25E Non-Disconnect 95 15CLE-PNM-C 15CLE-GNM-C CLE-NL-D —
110 15CLE-HPNM-C — — —
Disconnect 95 15CLE-PDM-C 15CLE-GDM-C CLE-DL-C CLE-DF-C
110 15CLE-HPDM-C — — —
30E to 150E Non-Disconnect 95 15CLE-PNM-D 15CLE-GNM-D CLE-NL-D —
110 15CLE-HPM-D — — —
Disconnect 95 15CLE-PDM-D 15CLE-GNM-D CLE-DL-D CLE-DF-D
110 15CLE-HPDM-D — — —
150E to 300E Non-Disconnect 110 15CLE-PNM-E — CLE-DL-E CLE-DF-E
Disconnect 110 15CLE-PDM-E — — —
 See Page 13-88 for diagram of typical mounting.
 End fittings supplied only when required.
13

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-69
Current Limiting Fuses
December 2008
Type HLE

Table 13-58. Type HLE Current Limiting Fuses


Catalog Mounting Catalog Performance

Interrupting Rating rms


Number (Includes Live Parts, End Fittings) Number Curves

Clip Center (Inches)


Type Catalog Number Live End

Peak Let-Through
Maximum Design

Diameter (Inches)

Approx. Shipping

Heritage Product
Parts  Fittings 

Indoor/Outdoor

Voltage (BIL) kV
Length (Inches)
Porcelain Glass-
Current Rating

Barrel Number

Total Clearing
Melting Time
Polyester

Weight (lbs.)
Voltage (kV)

(Amperes)

(kA Sym.)

Minimum

Current
Time
5.5 kV Maximum (4.8 kV Nominal)
10E 5HLE-10E 1 63 3 12 15.9 8 — I/O Non- 60 5HLE-PNM-D 5HLE-GNM-D CLE-NL-D —

70548507

70548607

70548703
15E 5HLE-15E 1 63 3 12 15.9 8 — I/O Disconnect
20E 5HLE-20E 1 63 3 12 15.9 8 — I/O Disconnect 60 5HLE-PDM-D 5HLE-GDM-D CLE-DL-D CLE-DF-D
25E 5HLE-25E 1 63 3 12 15.9 8 — I/O
30E 5HLE-30E 1 63 3 12 15.9 8 — I/O
40E 5HLE-40E 1 63 3 12 15.9 8 — I/O Non- 60 5HLE-PNM-D 5HLE-GNM-D CLE-NL-D —
50E 5HLE-50E 1 63 3 12 15.9 8 — I/O Disconnect
65E 5HLE-65E 1 63 3 12 15.9 8 — I/O Disconnect 60 5HLE-PDM-D 5HLE-GDM-D CLE-DL-D CLE-DF-D
80E 5HLE-80E 1 63 3 12 15.9 8 — I/O
100E 5HLE-100E 1 63 3 12 15.9 8 — I/O
125E 5HLE-125E 1 63 3 12 15.9 8 — I/O

70546005 70545805

70546105 70545905

70547603 70547603
150E 5HLE-150E 1 63 3 12 15.9 8 — I/O
175E 5HLE-175E 1 63 3 12 15.9 8 — I/O
200E 5HLE-200E 1 63 3 12 15.9 8 — I/O
250E 5HLE-250E 1 63 3 12 15.9 8 — I/O
300E 5HLE-300E 2 63 3 12 15.9 17 — I/O Non- 60 5HLE-PNM-E 5HLE-GNM-E CLE-NL-E —
350E 5HLE-350E 2 63 3 12 15.9 17 — I/O Disconnect
400E 5HLE-400E 2 63 3 12 15.9 17 — I/O Disconnect 60 5HLE-PDM-E 5HLE-GDM-E CLE-DL-E CLE-DF-E
450E 5HLE-450E 2 63 3 12 15.9 17 — I/O
 Includes end fittings.
13
 Disconnect only.

Table 13-59. Type HLE Current Limiting Fuses


Ampere Fuse Mounting Voltage Mounting Live Parts End Fittings
Rating Type  BIL (kV) (Including Live Parts, (Including (Disconnect
End Fittings)  End Fittings)  Only)
Porcelain Glass-Polyester Catalog Catalog
Insulator Insulator Number Number
Catalog Catalog
Number Number
SCLE Mountings and Hardware
5.5 kV Maximum (4.8 kV Nominal)
30E to 225E Non-Disconnect 60 5HLE-PNM-D 5HLE-GNM-D CLE-NL-D —
Non-Disconnect 60 5HLE-PDM-D 5HLE-GDM-D CLE-DL-D CLE-DF-D
250E to 400X Non-Disconnect 60 5HLE-PNM-E 5HLE-GNM-E CLE-NL-E —
Disconnect 60 5HLE-PDM-E 5HLE-GDM-E CLE-DL-E CLE-DF-E
HLE Mountings and Hardware
5.5 kV Maximum (4.8 kV Nominal)
30E to 450E Non-Disconnect 60 5HLE-PNM-D 5HLE-GNM-D CLE-NL-D —
Disconnect 60 5HLE-PDM-D 5HLE-GDM-D CLE-DL-D CLE-DF-D
300E to 450E Non-Disconnect 60 5HLE-PNM-E 5HLE-GNM-E CLE-NL-E —
Disconnect 60 5HLE-PDM-E 5HLE-GDM-E CLE-DL-E CLE-DF-D
 See Page 13-88 for diagram of typical mounting.
 End fittings supplied only when required.

CA08101001E For more information visit: www.eaton.com


13-70 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Type HLE

Table 13-60. Type HLE Current Limiting Fuses


Catalog Mounting Catalog Performance

Interrupting Rating rms


Number (Includes Live Parts, End Fittings) Number Curves

Clip Center (Inches)


Type Catalog Number Live End

Peak Let-Through
Maximum Design

Diameter (Inches)

Approx. Shipping

Heritage Product
Parts  Fittings 

Indoor/Outdoor

Voltage (BIL) kV
Length (Inches)
Porcelain Glass-
Current Rating

Barrel Number

Total Clearing
Melting Time
Polyester

Weight (lbs.)
Voltage (kV)

(Amperes)

(kA Sym.)

Minimum

Current
Time
8.3 kV Maximum (7.2 kV Nominal)
10E 8HLE-10E 1 50 3 12 15.9 8 — I/O Non- 75 8HLE-PNM-D 8HLE-GNM-D CLE-NL-D —

70548507

70548607

70548804
15E 8HLE-15E 1 50 3 12 15.9 8 — I/O Disconnect
20E 8HLE-20E 1 50 3 12 15.9 8 — I/O Disconnect 75 8HLE-PDM-D 8HLE-GDM-D CLE-DL-D CLE-DF-D
25E 8HLE-25E 1 50 3 12 15.9 8 — I/O
30E 8HLE-30E 1 50 3 12 15.9 8 — I/O
40E 8HLE-40E 1 50 3 12 15.9 8 — I/O Non- 75 8HLE-PNM-D 8HLE-GNM-D CLE-NL-D —
50E 8HLE-50E 1 50 3 12 15.9 8 — I/O Disconnect
65E 8HLE-65E 1 50 3 12 15.9 8 — I/O Disconnect 75 8HLE-PDM-D 8HLE-GDM-D CLE-DL-D CLE-DF-D
80E 8HLE-80E 1 50 3 12 15.9 8 — I/O

70546403 70546203

70546503 70546303

70547201 70547201
100E 8HLE-100E 1 50 3 12 15.9 8 — I/O
125E 8HLE-125E 1 50 3 12 15.9 8 — I/O
150E 8HLE-150E 1 50 3 12 15.9 8 — I/O
175E 8HLE-175E 1 50 3 12 15.9 8 — I/O
200E 8HLE-200E 2 50 3 12 15.9 8 — I/O Non- 75 5HLE-PNM-E 5HLE-GNM-E CLE-NL-E —
250E 8HLE-250E 2 50 3 12 15.9 8 — I/O Disconnect
300E 8HLE-300E 2 50 3 12 15.9 8 — I/O Disconnect 75 5HLE-PDM-E 5HLE-GDM-E CLE-DL-E CLE-DF-E
350E 8HLE-350E 2 50 3 12 15.9 8 — I/O
15.5 kV Maximum (14.4 kV Nominal)
13 10E 15HLE-10E 1 63 3 15 18.9 10 — I/O Non- 95 15HLE-PNM-D 15HLE-GNM-D CLE-NL-D —

70548507

70548607

70548805
15E 15HLE-15E 1 63 3 15 18.9 10 — I/O Disconnect
20E 15HLE-20E 1 63 3 15 18.9 10 — I/O Disconnect 95 15HLE-PDM-D 15HLE-GDM-D CLE-DL-D CLE-DF-D
25E 15HLE-25E 1 63 3 15 18.9 10 — I/O
30E 15HLE-30E 1 63 3 15 18.9 10 — I/O
40E 15HLE-40E 1 63 3 15 18.9 10 — I/O Non- 95 15HLE-PNM-D 15HLE-GNM-D CLE-NL-D —
50E 15HLE-50E 1 63 3 15 18.9 10 — I/O Disconnect

70546601 70546601

70546701 70546701

70547401 70547401
65E 15HLE-65E 1 63 3 15 18.9 10 — I/O Disconnect 95 15HLE-PDM-D 15HLE-GDM-D CLE-DL-D CLE-DF-D
80E 15HLE-80E 1 63 3 15 18.9 10 — I/O
100E 15HLE-100E 1 63 3 15 18.9 10 — I/O
125E 15HLE-125E 1 63 3 15 18.9 10 — I/O
150E 15HLE-150E 2 63 3 15 18.9 21 — I/O Non- 95 15HLE-PNM-E 15HLE-GNM-E CLE-NL-E —
175E 15HLE-175E 2 63 3 15 18.9 21 — I/O Disconnect
200E 15HLE-200E 2 63 3 15 18.9 21 — I/O Disconnect 95 15HLE-PDM-E 15HLE-GDM-E CLE-DL-E CLE-DF-E
250E 15HLE-250E 2 63 3 15 18.9 21 — I/O
 Includes end fittings.
 Disconnect only.

Table 13-61. Type HLE Current Limiting Fuses


Ampere Fuse Mounting Voltage Mounting Live Parts End Fittings
Rating Type  BIL (kV) (Including Live Parts, (Including (Disconnect
End Fittings)  End Fittings)  Only)
Porcelain Glass-Polyester Catalog Catalog
Insulator Insulator Number Number
Catalog Catalog
Number Number
HLE Mountings and Hardware
8.3 kV Maximum (7.2 kV Nominal)
20E to 180E Non-Disconnect 75 8HLE-PNM-D 8HLE-GNM-D CLE-NL-D —
Disconnect 75 8HLE-PDM-D 8HLE-GDM-D CLE-DL-D CLE-DF-D
200E to 350E Non-Disconnect 75 8HLE-PNM-E 8HLE-GNM-E CLE-NL-E —
Disconnect 75 8HLE-PDM-E 8HLE-GDM-E CLE-DL-E CLE-DF-E
HLE Mountings and Hardware
15.5 kV Maximum (14.4 kV Nominal)
20E to 125E Non-Disconnect 95 15HLE-PNM-D 15HLE-GNM-D CLE-NL-D —
Disconnect 95 15HLE-PDM-D 15HLE-GDM-D CLE-DL-D CLE-DF-D
150E to 250E Non-Disconnect 95 15HLE-PNM-E — CLE-NL-E —
Disconnect 95 15HLE-PDM-E — CLE-DL-E CLE-DF-E
 See Page 13-88 for diagram of typical mounting.
 End fittings supplied only when required.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-71
Current Limiting Fuses
December 2008
Type BHLE

Table 13-62. Type BHLE Current Limiting Fuses (5.5 kV Maximum, 4.8 kV Nominal)
Catalog Mounting Catalog Performance

Interrupting Rating rms


Number (Includes Live Parts, Number Curves
End Fittings)

Clip Center (Inches)

Peak Let-Through
Maximum Design

Diameter (Inches)

Approx. Shipping
Type Catalog Number Live End

Heritage Product

Voltage (BIL) kV
Indoor/Outdoor
Parts  Fittings 

Length (Inches)
Barrel Number
Current Rating

Porcelain Glass-

Total Clearing
Weight (Lbs.)

Melting Time
Voltage (kV)

Polyester
(Amperes)

(kA Sym.)

Minimum

Current
Time
5.5 10E 5BHLE-10E 1 63 3  15.9 8 — I Non- Bolt-on. Not applicable.


70548507

70548607

70548703
15E 5BHLE-15E 1 63 3 15.9 8 — I Disconnect
20E 5BHLE-20E 1 63 3  15.9 8 — I

Disconnect
25E 5BHLE-25E 1 63 3 15.9 8 — I
30E 5BHLE-30E 1 63 3  15.9 8 — I
40E 5BHLE-40E 1 63 3  15.9 8 — I Non-
50E 5BHLE-50E 1 63 3  15.9 8 — I Disconnect
65E 5BHLE-65E 1 63 3  15.9 8 — I

Disconnect
80E 5BHLE-80E 1 63 3 15.9 8 — I
100E 5BHLE-100E 1 63 3  15.9 8 — I
125E 5BHLE-125E 1 63 3  15.9 8 — I


70546005 70545805

70546105 70545905

70547603 70547603
150E 5BHLE-150E 1 63 3 15.9 8 — I
175E 5BHLE-175E 1 63 3  15.9 8 — I
200E 5BHLE-200E 1 63 3  15.9 8 — I
250E 5BHLE-250E 1 63 3  15.9 8 — I
300E 5BHLE-300E 1 63 3  15.9 8 — I Non-
350E 5BHLE-350E 1 63 3  15.9 8 — I Disconnect
400E 5BHLE-400E 1 63 3  15.9 8 — I

Disconnect
450E 5BHLE-450E 1 63 3 15.9 8 — I
 Includes end fittings. 13
 Disconnect only.
 Bolt-in.

Table 13-63. Type BHLE Current Limiting Fuses (8.3 kV Maximum, 7.2 kV Nominal)
Catalog Mounting Catalog Performance
Interrupting Rating rms

Number (Includes Live Parts, Number Curves


End Fittings)
Clip Center (Inches)

Peak Let-Through
Maximum Design

Diameter (Inches)

Approx. Shipping

Type Catalog Number Live End


Heritage Product

Voltage (BIL) kV
Indoor/Outdoor

Parts  Fittings 
Length (Inches)
Barrel Number
Current Rating

Porcelain Glass-

Total Clearing
Weight (Lbs.)

Melting Time
Voltage (kV)

Polyester
(Amperes)

(kA Sym.)

Minimum

Current
Time
8.3 10E 8BHLE-10E 1 50 3  15.9 8 — I Bolt-on. Not applicable.

70548507

70548607

70548804
15E 8BHLE-15E 1 50 3 15.9 8 — I
20E 8BHLE-20E 1 50 3  15.9 8 — I
25E 8BHLE-25E 1 50 3  15.9 8 — I
30E 8BHLE-30E 1 50 3  15.9 8 — I
40E 8BHLE-40E 1 50 3  15.9 8 — I
50E 8BHLE-50E 1 50 3  15.9 8 — I
65E 8BHLE-65E 1 50 3  15.9 8 — I
80E 8BHLE-80E 1 50 3  15.9 8 — I

70546403 70546203

70546503 70546303

70547201 70547201

100E 8BHLE-100E 1 50 3 15.9 8 — I


125E 8BHLE-125E 1 50 3  15.9 8 — I
150E 8BHLE-150E 1 50 3  15.9 8 — I
175E 8BHLE-175E 1 50 3  15.9 8 — I
200E 8BHLE-200E 1 50 3  15.9 17 — I
250E 8BHLE-250E 1 50 3  15.9 17 — I
300E 8BHLE-300E 1 50 3  15.9 17 — I
350E 8BHLE-350E 1 50 3  15.9 17 — I
 Includes end fittings.
 Disconnect only.
 Bolt-in.

CA08101001E For more information visit: www.eaton.com


13-72 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Types BHLE and HCL

Table 13-64. Type BHLE Current Limiting Fuses (15.5 kV Maximum, 14.4 kV Nominal)
Catalog Mounting Catalog Performance

Interrupting Rating rms


Number (Includes Live Parts, Number Curves
End Fittings)

Clip Center (Inches)

Peak Let-Through
Maximum Design

Diameter (Inches)

Approx. Shipping
Type Catalog Number Live End

Heritage Product

Voltage (BIL) kV
Indoor/Outdoor
Parts  Fittings 

Length (Inches)
Barrel Number
Current Rating

Porcelain Glass-

Total Clearing
Melting Time
Weight (lbs.)
Voltage (kV)

Polyester
(Amperes)

(kA Sym.)

Minimum

Current
Time
15.5 10E 15BHLE-10E 1 63 3  18.9 10 — I/O Bolt-on. Not applicable.


70548507

70548607

70548805
15E 15BHLE-15E 1 63 3 18.9 10 — I/O
20E 15BHLE-20E 1 63 3  18.9 10 — I/O
25E 15BHLE-25E 1 63 3  18.9 10 — I/O
30E 15BHLE-30E 1 63 3  18.9 10 — I/O
40E 15BHLE-40E 1 63 3  18.9 10 — I/O
50E 15BHLE-50E 1 63 3  18.9 10 — I/O
65E 15BHLE-65E 1 63 3  18.9 10 — I/O
80E 15BHLE-80E 1 63 3  18.9 10 — I/O
100E 15BHLE-100E 1 63 3  18.9 10 — I/O
125E 15BHLE-125E 1 63 3  18.9 10 — I/O


70546601

70546701

70547401
150E 15BHLE-150E 2 63 3 18.9 21 — I/O
175E 15BHLE-175E 2 63 3  18.9 21 — I/O
200E 15BHLE-200E 2 63 3  18.9 21 — I/O
250E 15BHLE-250E 2 63 3  18.9 21 — I/O
 Includes end fittings.
 Disconnect only.
 Bolt-in.
13 Table 13-65. Type HCL Current Limiting Fuses (5.5 kV Maximum, 4.8 kV Nominal)
Maximum Current Catalog Clip Mounting Catalog Performance
Interrupting Rating rms

Design Rating Number Center Type Number Curves


Voltage (Amperes) Live Parts Minimum Total Peak
Diameter (Inches)

Approx. Shipping

Heritage Product

(kV) (Includes
Indoor/Outdoor

Melting Clearing Let-Through


Barrel Number

End Fittings) Time Time Current


Weight (lbs.)
(kA Sym.)

5.5 10E 5HCL-10E 1 63 3 Clip-Lock 9 — I Non- HCL-NL-1 70548505 70548605 70548702


15E 5HCL-15E 1 63 3 Clip-Lock 9 — I Disconnect
20E 5HCL-20E 1 63 3 Clip-Lock 9 — I
25E 5HCL-25E 1 63 3 Clip-Lock 9 — I
30E 5HCL-30E 1 63 3 Clip-Lock 9 — I
40E 5HCL-40E 1 63 3 Clip-Lock 9 — I Non- HCL-NL-1 70545803 70545903 70547602
50E 5HCL-50E 1 63 3 Clip-Lock 9 — I Disconnect
65E 5HCL-65E 1 63 3 Clip-Lock 9 — I
80E 5HCL-80E 1 63 3 Clip-Lock 9 — I
100E 5HCL-100E 1 63 3 Clip-Lock 9 — I
125E 5HCL-125E 1 63 3 Clip-Lock 9 — I
150E 5HCL-150E 1 63 3 Clip-Lock 9 — I
200E 5HCL-200E 1 63 3 Clip-Lock 10 — I Non- HCL-NL-1
250E 5HCL-250E 1 63 3 Clip-Lock 10 — I Disconnect
300E 5HCL-300E 2 63 3 Clip-Lock 20 — I Non- HCL-NL-1 70546003 70516103 70547602
400E 5HCL-400E 2 63 3 Clip-Lock 20 — I Disconnect
450E 5HCL-450E 2 63 3 Clip-Lock 20 — I
500E 5HCL-500E 2 63 3 Clip-Lock 20 — I Non- HCL-NL-1 66703401 66703501 66703701
600E 5HCL-600E 2 63 3 Clip-Lock 20 — I Disconnect
750E 5HCL-750E 3 63 3 Bolt-in 30 — I
900E 5HCL-900E 3 63 3 Bolt-in 30 — I

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-73
Current Limiting Fuses
December 2008
Type HCL

Table 13-66. Type HCL Current Limiting Fuses (15.5 kV Maximum, 14.4 kV Nominal)
Maximum Current Catalog Clip Mounting Catalog Performance

Interrupting Rating rms


Design Rating Number Center Type Number Curves
Voltage (Amperes) Live Parts Minimum Total Peak

Diameter (Inches)

Approx. Shipping

Heritage Product
(kV) (Includes

Indoor/Outdoor
Melting Clearing Let-Through

Barrel Number
End Fittings) Time Time Current

Weight (lbs.)
(kA Sym.)
15.5 10E 15HCL-10E 1 63 3 Clip-Lock 10 — I Non- HCL-NL-1 70548503 70548603 70548803
15E 15HCL-15E 1 63 3 Clip-Lock 10 — I Disconnect
20E 15HCL-20E 1 63 3 Clip-Lock 10 — I
25E 15HCL-25E 1 63 3 Clip-Lock 10 — I
30E 15HCL-30E 1 63 3 Clip-Lock 10 — I
40E 15HCL-40E 1 63 3 Clip-Lock 10 — I Non- HCL-NL-1 66703201 66703301 70547402
50E 15HCL-50E 1 63 3 Clip-Lock 10 — I Disconnect
65E 15HCL-65E 1 50 3 Clip-Lock 12 — I Non- HCL-NL-1
80E 15HCL-80E 1 50 3 Clip-Lock 12 — I Disconnect
100E 15HCL-100E 1 50 3 Clip-Lock 12 — I
125E 15HCL-125E 1 50 3 Clip-Lock 12 — I
150E 15HCL-150E 2 50 3 Clip-Lock 24 — I Non- HCL-NL-1 66703201 66703301 70547402
200E 15HCL-200E 2 50 3 Clip-Lock 24 — I Disconnect
250E 15HCL-250E 2 50 3 Clip-Lock 24 — I
300E 15HCL-300E 2 50 3 Clip-Lock 24 — I

13

CA08101001E For more information visit: www.eaton.com


13-74 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Types CLE, HLE and BHLE

Fuse Dimensional Details Table 13-67. CLE Fuse Dimensional Details


CLE kV “L” “B” Dia.

2.75 9.50 ± .06 2.00


5.50 17.88 ± .03 3.00
"B" Dia. 8.30 17.88 ± .03 3.00
15.50 23.88 ± .03 3.00
1.56 Ref.
"L" Table 13-68. HLE Fuse Dimensional Details
HLE kV L ± 0.03
17.88
5.50 15.88
8.30 15.88
Figure 13-18. CLE Fuse Dimensional Details — Inches 15.50 18.88
25.80 23.88

3.00 Dia.
3.56

L ± .03 L ± .03

Figure 13-19. HLE Fuse Dimensional Details — Inches

13 Indicator to be
Located Here

3.31

2.12

3.00 17.88 ± .06 17.88 ± .06 3.00


Ref. 19.25 Ref. 19.25 Ref. Ref.
Single Barrel Double Barrel
Type 5BHLE & 8BHLE Fuses

3.00

1.53 3.56 3.56

3.00 20.88 ± .06 20.88 ± .06


Ref.
22.25 Ref. 22.25 Ref.
Single Barrel Double Barrel
Type 15BHLE Fuses

Figure 13-20. BHLE Fuse Dimensional Details — Inches

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-75
Current Limiting Fuses
December 2008
Type HCL

Table 13-69. 15.5 kV Clip Lock Mounted


Ampere Number Figure Dimensions in Inches Interrupting
Type HCL-14 Fuses Rating of Number A B C Rating
Barrels rms Sym.
Indicator Flush with Surface Amperes
in Untripped Position
15.5 kV Maximum — Clip Lock Style — 21.25-Inch Clip Centers —
3-Inch Barrel Diameter
A
B Indicator 65E 1 A 22.81 22.12 0.5 63,000
80E Tripped
.25 100E Force
125E 2 Lb.
1.25 3.00
C 150E 2 B 50,000
Figure A 200E
250E
300E
Indicator Flush with Surface
in Untripped Position Table 13-70. 5.5 and 15.5 kV Clip Lock Mounted
A Ampere Number Figure Dimensions in Inches Interrupting
B Rating of Number A B C Rating
Barrels rms Sym.
Amperes
5 5.5 kV Maximum — Clip Lock Style — 15.25-Inch Clip Centers —
3-Inch Barrel Diameter
1.25 1.25 C 3.00 10E 1 A 16.81 16.12 0.5 63,000
Figure B 15E Tripped
20E Force
25E 2 Lb.
Indicator Flush with Surface 30E
in Untripped Position 40E
50E
B 65E 13
80E
100E
125E
150E
.38
5.5 kV Maximum — Clip Lock Style — 21.25-Inch Clip Centers —
A 3-Inch Barrel Diameter
Blown Fuse 200E 1 A 22.81 22.12 0.5 63,000
1.50 .44 x .91 Slots Indicator 250E Tripped
300E Force
C .44 Dia. Hole
400E 2 Lb.
Figure C 450E 2 B
500E
600E
Type HCL Fuses 15.5 kV Maximum — Clip Lock Style-18.25-Inch Clip Centers —
3-Inch Barrel Diameter
16.38 ± .06 for HCL-8 10E 1 A 19.81 19.12 0.5 63,000
19.38 ± .06 FOR HCL-15 15E Tripped
20E Force
25E 2 Lb.
30E
40E
50E
Figure 13-21. HCL Fuse Dimensional Details — Inches
Table 13-71. Bolt-in-Series — 5.5 kV
Ampere Number Figure Dimensions in Inches Interrupting
Rating of Number A B C D Rating
Barrels rms Sym.
Amperes
5.5 kV Maximum — Bolt-in Style — 23.73-Inch Hole Centers —
3-Inch Barrel Diameter
750E 3 C 25.11 22.37 23.73 0.5 63,000
900E Tripped
Force
2 Lb.

CA08101001E For more information visit: www.eaton.com


13-76 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Type CLS

Table 13-72. CLS Type Current Limiting Fuses


Catalog Mounting Catalog Performance

Interrupting Rating rms


Number (Includes Live Parts, End Fittings) Number Curves

Clip Center (Inches)


Type Catalog Number Live End

Peak Let-Through
Maximum Design

Diameter (Inches)

Approx. Shipping
“R” Designation

Parts  Fittings 

Voltage (BIL) kV
Length (Inches)
Porcelain Glass-

Barrel Number
Current Rating

Total Clearing
Weight (Lbs.)

Melting Time
Polyester
Voltage (kV)

(Amperes)

(kA Sym.)

Minimum

Current
Time
2.54 25 — 2CLS-25 1 50 3 7 10.8 7 Non- 60 2CLE-PNM-D 2CLE-GNM-D CLE-NL-D —
70 2R 2CLS-2R 1 50 3 7 10.8 7 Disconnect
100 3R 2CLS-3R 1 50 3 7 10.8 7 Disconnect 60 2CLE-PDM-D 2CLE-GDM-E CLE-DL-D CLE-DF-D
130 4R 2CLS-4R 1 50 3 7 10.8 7
150 5R 2CLS-5R 1 50 3 7 10.8 7
170 6R 2CLS-6R 1 50 3 7 10.8 7
200 9R 2CLS-9R 1 50 3 7 10.8 7
230 12R 2CLS-12R 1 50 3 7 10.8 7
390 18R 2CLS-18R 2 50 3 7 10.8 16 Non- 60 2CLE-PNM-E 2CLE-GNM-E CLE-NL-E —

66664702

66664704

66700202
450 24R 2CLS-24R 2 50 3 7 10.8 16 Disconnect
Disconnect 60 2CLE-PDME 2CLE-GDM-E CLE-DL-E CLE-DF-E

25 — 2ACLS-25 1 50 3  10.8 7 For use with AMPGARD 400 A Motor Starters


70 2R 2ACLS-2R 1 50 3  10.8 7
100 3R 2ACLS-3R 1 50 3  10.8 7
130 4R 2ACLS-4R 1 50 3  10.8 7
150 5R 2ACLS-5R 1 50 3  10.8 7
170 6R 2ACLS-6R 1 50 3  10.8 7
200 9R 2ACLS-9R 1 50 3  10.8 7

66664702

66664704

66700202
230 12R 2ACLS-12R 1 50 3  10.8 7
13 390 18R 2ACLS-18R 2 50 3  10.8 16
450 24R 2ACLS-24R 2 50 3  10.8 16
25 — 2BCLS-25 1 50 3  10.8 8 Bolt-in
70 2R 2BCLS-2R 1 50 3  10.8 8
100 3R 2BCLS-3R 1 50 3  10.8 8
130 4R 2BCLS-4R 1 50 3  10.8 8
150 5R 2BCLS-5R 1 50 3  10.8 8
170 6R 2BCLS-6R 1 50 3  10.8 8
200 9R 2BCLS-9R 1 50 3  10.8 8

66664702

66664704

66700202
230 12R 2BCLS-12R 1 50 3  10.8 8
390 18R 2BCLS-18R 2 50 3  10.8 17
450 24R 2BCLS-24R 2 50 3  10.8 17
25 — 2HCLS-25 1 50 3  10.8 7 Hermetically Sealed Fuses for use with AMPGARD 400 A Motor Starters
70 2R 2HCLS-2R 1 50 3  10.8 7
100 3R 2HCLS-3R 1 50 3  10.8 7
130 4R 2HCLS-4R 1 50 3  10.8 7
150 5R 2HCLS-5R 1 50 3  10.8 7
170 6R 2HCLS-6R 1 50 3  10.8 7
200 9R 2HCLS-9R 1 50 3  10.8 7
66664702

66664704

66700202
230 12R 2HCLS-12R 1 50 3  10.8 7
390 18R 2HCLS-18R 2 50 3  10.8 16
450 24R 2HCLS-24R 2 50 3  10.8 16
5.5 30 — 5CLS-30 1 50 3 12 15.9 8 Non- 60 5HLE-PNM-D 5HLE-GNM-D CLE-NL-D —
70 2R 5CLS-2R 1 50 3 12 15.9 8 Disconnect
100 3R 5CLS-3R 1 50 3 12 15.9 8 Disconnect 60 5HLE-PDM-D 5HLE-GDM-E CLE-DL-D CLE-DF-D
130 4R 5CLS-4R 1 50 3 12 15.9 8
150 5R 5CLS-5R 1 50 3 12 15.9 8
170 6R 5CLS-6R 1 50 3 12 15.9 8
200 9R 5CLS-9R 1 50 3 12 15.9 8
230 12R 5CLS-12R 1 50 3 12 15.9 8
390 18R 5CLS-18R 2 50 3 12 15.9 17 Non- 60 5HLE-PNM-E 5HLE-GNM-E CLE-NL-E —
66690602

66690702

66700203

450 24R 5CLS-24R 2 50 3 12 15.9 17 Disconnect


Disconnect 60 5HLE-PDME 5HLE-GDM-E CLE-DL-E CLE-DF-E

 Includes end fittings.


 Disconnect only.
 Not applicable.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-77
Current Limiting Fuses
December 2008
Type CLS

Table 13-72. CLS Type Current Limiting Fuses (Continued)


Catalog Mounting Catalog Performance

Interrupting Rating rms


Number (Includes Live Parts, End Fittings) Number Curves

Clip Center (Inches)


Type Catalog Number Live End

Peak Let-Through
Maximum Design

Diameter (Inches)

Approx. Shipping
“R” Designation

Parts  Fittings 

Voltage (BIL) kV
Length (Inches)
Porcelain Glass-

Barrel Number
Current Rating

Total Clearing
Weight (Lbs.)

Melting Time
Polyester
Voltage (kV)

(Amperes)

(kA Sym.)

Minimum

Current
Time
5.08 30 — 5ACLS-30 1 50 3  15.9 8 For use with AMPGARD 400 A Motor Starters
70 2R 5ACLS-2R 1 50 3  15.9 8
100 3R 5ACLS-3R 1 50 3  15.9 8
130 4R 5ACLS-4R 1 50 3  15.9 8
150 5R 5ACLS-5R 1 50 3  15.9 8
170 6R 5ACLS-6R 1 50 3  15.9 8
200 9R 5ACLS-9R 1 50 3  15.9 8
230 12R 5ACLS-12R 1 50 3  15.9 8

66690602

66690702

66700203
390 18R 5ACLS-18R 2 50 3  15.9 17
450 24R 5ACLS-24R 2 50 3  15.9 17
4.3 480 26R 4ACLS-26R 2 50 3  15.9 17
5.08 30 — 5BCLS-30 1 50 3  15.9 8 Bolt-in
70 2R 5BCLS-2R 1 50 3  15.9 8
100 3R 5BCLS-3R 1 50 3  15.9 8
130 4R 5BCLS-4R 1 50 3  15.9 8
150 5R 5BCLS-5R 1 50 3  15.9 8
170 6R 5BCLS-6R 1 50 3  15.9 8
200 9R 5BCLS-9R 1 50 3  15.9 8
230 12R 5BCLS-12R 1 50 3  15.9 8

66690602

66690702

66700203
390 18R 5BCLS-18R 2 50 3  15.9 17
450 24R 5BCLS-24R 2 50 3  15.9 17 13
4.3 480 26R 4BCLS-26R 2 50 3  15.9 17
5.08 30 — 5HCLS-30 1 50 3  15.9 8 Hermetically Sealed for use with AMPGARD 400 A Motor Starters
70 2R 5HCLS-2R 1 50 3  15.9 8
100 3R 5HCLS-3R 1 50 3  15.9 8
130 4R 5HCLS-4R 1 50 3  15.9 8
150 5R 5HCLS-5R 1 50 3  15.9 8
170 6R 5HCLS-6R 1 50 3  15.9 8


66690602

66690702

66700203
200 9R 5HCLS-9R 1 50 3 15.9 8
230 12R 5HCLS-12R 1 50 3  15.9 8
390 18R 5HCLS-18R 2 50 3  15.9 17
450 24R 5HCLS-24R 2 50 3  15.9 17
5.08 70 2R 5CLS70-2R 2 50 3  15.9 20 For use with AMPGARD 800 A Motor Starters
100 3R 5CLS70-3R 2 50 3  15.9 20
130 4R 5CLS70-4R 2 50 3  15.9 20
150 5R 5CLS70-5R 2 50 3  15.9 20
170 6R 5CLS70-6R 2 50 3  15.9 20
200 9R 5CLS70-9R 2 50 3  15.9 20
230 12R 5CLS70-12R 2 50 4  15.9 40
390 18R 5CLS70-18R 2 50 4  15.9 40

66690602

66690702

66700203
450 24R 5CLS70-24R 2 50 4 15.9 40
600 32R 5CLS70-32R 2 50 4  15.9 40
650 36R 5CLS70-36R 2 50 4  15.9 40
700 44R 5CLS70-44R 2 50 4  15.9 40
5.5 70 2R 5LCLS-2R 1 50 3 14 17.9 11 Non- 60 5CLE-PNM-D 5CLE-GNM-D CLE-NL-D —
100 3R 5LCLS-3R 1 50 3 14 17.9 11 Disconnect
130 4R 5LCLS-4R 1 50 3 14 17.9 11 Disconnect 60 5CLE-PDM-D 5CLE-GDM-D CLE-DL-D CLE-DF-D
150 5R 5LCLS-5R 1 50 3 14 17.9 11
170 6R 5LCLS-6R 1 50 3 14 17.9 11 Disconnect 75 8CLE-PDM-D 8CLE-GDM-D
200 9R 5LCLS-9R 1 50 3 14 17.9 11
230 12R 5LCLS-12R 1 50 3 14 17.9 11
390 18R 5LCLS-18R 2 50 3 14 17.9 22 Non- 60 5CLE-PNM-E 5CLE-GNM-E CLE-NL-E —
51285302

51285402

66700204

450 24R 5LCLS-24R 2 50 3 14 17.9 22 Disconnect


Disconnect 60 5CLE-PDM-E 5CLE-GDM-E CLE-DL-E CLE-DF-E
Disconnect 75 8CLE-PDM-E 8CLE-PDM-E
 Includes end fittings.
 Disconnect only.
 Not applicable.

CA08101001E For more information visit: www.eaton.com


13-78 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Type CLS

Table 13-72. CLS Type Current Limiting Fuses (Continued)


Catalog Mounting Catalog Performance

Interrupting Rating rms


Number (Includes Live Parts, End Fittings) Number Curves

Clip Center (Inches)


Type Catalog Number Live End

Peak Let-Through
Maximum Design

Diameter (Inches)

Approx. Shipping
“R” Designation

Parts  Fittings 

Voltage (BIL) kV
Length (Inches)
Porcelain Glass-

Barrel Number
Current Rating

Total Clearing
Weight (Lbs.)

Melting Time
Polyester
Voltage (kV)

(Amperes)

(kA Sym.)

Minimum

Current
Time
8.3 70 2R 8CLS-2R 1 50 3 12 15.9 7 Non- 75 8HLE-PNM-D 8HLE-GNM-D CLE-NL-D —
100 3R 8CLS-3R 1 50 3 12 15.9 7 Disconnect
130 4R 8CLS-4R 1 50 3 12 15.9 7 Disconnect 75 8HLE-PDM-D 8HLE-GDM-D CLE-DL-D CLE-DF-D
150 5R 8CLS-5R 1 50 3 12 15.9 7
170 6R 8CLS-6R 1 50 3 12 15.9 7
200 9R 7CLS-9R 1 50 3 12 15.9 7
230 12R 7CLS-12R 1 50 3 12 15.9 7

66700602

66700702

66700205
7.2 390 18R 7CLS-18R 2 50 3 12 15.9 16 Non- 75 8HLE-PDM-E 8HLE-GNM-E CLE-NL-E —
450 24R 7CLS-24R 2 50 3 12 15.9 16 Disconnect
Disconnect 75 8HLE-PDM-E 8HLE-GDM-E CLE-DL-E CLE-DF-E
8.3 70 2R 7BCLS-2R 1 50 3  15.9 7 Bolt-in
100 3R 7BCLS-3R 1 50 3  15.9 7
130 4R 7BCLS-4R 1 50 3  15.9 7
150 5R 7BCLS-5R 1 50 3  15.9 7
170 6R 7BCLS-6R 1 50 3  15.9 7
200 9R 7BCLS-9R 1 50 3  15.9 7

66700602

66700702

66740205
230 12R 7BCLS-12R 1 50 3  15.9 7
7.2 390 18R 7BCLS-18R 2 50 3  15.9 16
450 24R 7BCLS-24R 2 50 3  15.9 16
13 8.3 70 2R 8ACLS-2R 1 50 3  15.9 8 For use with AMPGARD 400 A Motor Starters
100 3R 8ACLS-3R 1 50 3  15.9 8
130 4R 8ACLS-4R 1 50 3  15.9 8
150 5R 8ACLS-5R 1 50 3  15.9 8
170 6R 8ACLS-6R 1 50 3  15.9 8
7.2 200 9R 7ACLS-9R 1 50 3  15.9 8
230 12R 7ACLS-12R 1 50 3  15.9 8
390 18R 7ACLS-18R 2 50 3  15.9 17
450 24R 7ACLS-24R 2 50 3  15.9 17

66700602

66700702

66740205
450 24R 7CLS70-24R 2 50 3  15.9 20 For use with AMPGARD 800 A Motor Starters
650 36R 7CLS70-36R 3 50 3  15.9 30
700 44R 7CLS70-44R 2 50 4  15.9 40
8.3 15  8CLS-15 1 50 3 14 17.9 11 Non- 75 8CLE-PNM-D 8CLE-GNM-D CLE-NL-D —
30  8CLS-30 1 50 3 14 17.9 11 Disconnect
60  8CLS-60 1 50 3 14 17.9 11

Disconnect 75 8CLE-PDM-D 8CLE-GDM-D CLE-DL-D CLS-DF-D
70 8CLS-70 1 50 3 14 17.9 11
90  8CLS-90 1 50 3 14 17.9 11
110  8CLS-110 1 50 3 14 17.9 11
125  8CLS-125 1 50 3 14 17.9 11
66664202

66664302

66679802
150  8CLS-150 2 50 3 14 17.9 22 Non- 75 8CLE-PNM-E 8CLE-GNM-E CLE-NL-E —
200  8CLS-200 2 50 3 14 17.9 22 Disconnect
225  8CLS-225 2 50 3 14 17.9 22 Disconnect 75 8CLE-PDM-E 8CLE-GDM-E CLE-DL-E CLE-DF-E
 Includes end fittings.
 Disconnect only.
 Not applicable.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-79
Current Limiting Fuses
December 2008
Types CLS and BCLS

Fuse Dimensional Details — Inches

3.56 Ref.

± .06 for 2CLS


15.85 ±

10.81 ± .06 for 2CLS


15.85 ± .06 for 5, 7 & 8CLS

Figure 13-22. CLS Fuse

.455 Dia. x .91 Slot (4)

1.53

3.31 13
2.12

3.00 17.88 17.88 ± .06 3.00


Ref. 19.25 19.25 Ref. Ref.
Type 5BCLS & 7BCLS Fuses

1.53

3.00 12.81 ± .06 12.81 ± .06 3.00


Ref. 14.18 ± .06 14.18 ± .06 Ref.
Type 2BCLS Fuse

Figure 13-23. BCLS Fuse

CA08101001E For more information visit: www.eaton.com


13-80 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Type CLPT

Table 13-73. Type CLPT Current Limiting Fuses


Catalog Mounting Catalog Number Performance

Interrupting Rating rms


Number (Includes Live Parts, End Fittings) Curves

Clip Center (Inches)


Type Catalog Number Live End

Peak Let-Through
Diameter (Inches)
Maximum Design

Approx. Shipping
Parts  Fittings 

Voltage (BIL) kV
Length (Inches)
Porcelain Glass-
Current Rating

Total Clearing
Melting Time
Weight (lbs.)
Polyester
Voltage (kV)

(Amperes)

Minimum

Current
Time
2.475 kV Maximum (2.4 kV Nominal)
Indicating 0.25E 2NCLPT-.25E 63 0.81 — 4.5 0.25 Not applicable.
0.5E 2NCLPT-.5E 63 0.81 — 4.5 0.25
1E 2NCLPT-1E 40 0.81 — 4.5 0.25
2E 2NCLPT-2E 40 0.81 — 4.5 0.25
5E 2NCLPT-5E 25 0.81 — 4.5 0.25

56357202

59883702

63933702
5.5 kV Maximum (4.8 kV Nominal)
Non-Indicating 0.5E 5NCLPT-.5E 63 0.81 — 5.63 0.25 Not applicable.
1E 5NCLPT-1E 63 0.81 — 5.63 0.25
2E 5NCLPT-2E 63 0.81 — 5.63 0.25
3E 5NCLPT-3E 63 0.81 — 5.63 0.25
4E 5NCLPT-4E 63 0.81 — 5.63 0.25
5E 5NCLPT-5E 63 0.81 — 5.63 0.25
0.5E 317B487H02 50 1 — 5.63 0.25

66702402

66702502

66704101
1E 317B487H06 50 1 — 5.63 0.25
2E 317B487H03 50 1 — 5.63 0.25
13 3E
5E
317B487H04
317B487H05
50
50
1
1


5.63
5.63
0.25
0.25
Indicating 0.5E 5CLPT-.5E 80 1.6 8.1 9.5 1.2 Non- 60 5CLPT-PNM-A 5CLPT-GNM-A CLPT-NL —
1E 5CLPT-1E 80 1.6 8.1 9.5 1.2 Disconnect

56353206

56353306

63934001
1.5E 5CLPT-1.5E 80 1.6 8.1 9.5 1.2 Disconnect 60 5CLPT-PDM-A 5CLPT-GDM-A CLPT-DL CLPT-DF
3E 5CLPT-3E 80 1.6 8.1 9.5 1.2
5E 5CLPT-5E 80 1.6 8.1 9.5 1.2
10E 5CLPT-10E 80 1.6 8.1 9.5 1.2
0.5E 5NCLPT-.5E-A 63 1.6 8.1 9.5 1.2 Non- 60 5CLPT-PNM-A 5CLPT-GNM-A CLPT-NL —
1E 5NCLPT-1E-A 63 1.6 8.1 9.5 1.2 Disconnect

70548302

70548402

63934002
2E 5NCLPT-2E-A 63 1.6 8.1 9.5 1.2 Disconnect 60 5CLPT-PDM-A 5CLPT-GDM-A CLPT-DL CLPT-DF
3E 5NCLPT-3E-A 63 1.6 8.1 9.5 1.2
5E 5NCLPT-5E-A 63 1.6 8.1 9.5 1.2
10E 5NCLPT-10E-A 63 1.6 8.1 9.5 1.2
8.3 kV Maximum (7.2 kV Nominal)
2E 8NCLPT-2E 25 0.81 8 0.25 Not applicable.
56357206

59883706

63933704
4E 8NCLPT-4E 25 0.81 8 0.25
1E 8NCLPT-1E 50 1.1 5 0.5
5E 8NCLPT-5E 50 1.1 5 0.5
10E 8NCLPT-0E 50 1.1 5 0.5
.5E 8CLPT-.5E 80 1.6 8.1 9.5 1.5 Non- 75 8CLPT-PNM-A 8CLPT-GNM-A CLPT-NL —
Disconnect
Disconnect 75 8CLPT-PDM-A 8CLPT-GDM-A CLPT-DL CLPT-DF
56353206

56353306

63934001

3E 8CLPT-3E 80 1.6 11.5 12.9 1.5 Non- 75 8CLPT-PNM-B 8CLPT-GNM-B CLPT-NL —


5E 8CLPT-5E 50 1.6 11.5 12.9 1.5 Disconnect
10E 8CLPT-10E 50 1.6 11.5 12.9 1.5 Disconnect 75 8CLPT-PDM-B 8CLPR-GDM-B CLPT-DL CLPT-DF
0.5E 8NCLPT-.5E-A 50 1.6 8.1 9.5 1.5 Non- 75 8CLPT-PNM-A 8CLPT-GNM-A CLPT-NL —
1E 8NCLPT-1E-A 50 1.6 8.1 9.5 1.5 Disconnect
2E 8NCLPT-2E-A 50 1.6 8.1 9.5 1.5 Disconnect 75 8CLPT-PDM-A 8CLPT-GDM-A CLPT-DL CLPT-DF
70548303

70548403

63934002

3E 8NCLPT-3E-A 50 1.6 11.5 12.9 1.6 Non- 75 8CLPT-PNM-B 8CLPT-GNM-B CLPT-NL —


5E 8NCLPT-5E-A 50 1.6 11.5 12.9 1.6 Disconnect
10E 8NCLPT-10E-A 50 1.6 11.5 12.9 1.6 Disconnect 75 8CLPT-PDM-B 8CLPT-GDM-B CLPT-DL CLPT-DF
 Includes end fittings.
 Disconnect only.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-81
Current Limiting Fuses
December 2008
Type CLPT

Table 13-73. Type CLPT Current Limiting Fuses (Continued)


Catalog Mounting Catalog Number Performance

Interrupting Rating rms


Number (Includes Live Parts, End Fittings) Curves

Clip Center (Inches)


Type Catalog Number Live End

Peak Let-Through
Diameter (Inches)
Maximum Design

Approx. Shipping
Parts  Fittings 

Voltage (BIL) kV
Length (Inches)
Porcelain Glass-
Current Rating

Total Clearing
Melting Time
Weight (lbs.)
Polyester
Voltage (kV)

(Amperes)

Minimum

Current
Time
15.5 kV Maximum (7.2 kV Nominal)
0.5E 15CLPT-.5E 80 1.6 11.5 12.9 1.6 Non- 95 15CLPT-PNM-A 15CLPT-GNM-A CLPT-NL —
1E 15CLPT-1E 80 1.6 11.5 12.9 1.6 Disconnect
2E 15CLPT-1.5E 80 1.6 11.5 12.9 1.6 Disconnect 95 15CLPT-PDM-A 15CLPT-GDM-A CLPT-DL CLPT-DF

56353206

56353306

63934001
3E 15CLPT-3E 80 1.6 16.1 17.6 1.6 Non- 95 15CLPT-PNM-B 15CLPT-GNM-B CLPT-NL —
5E 15CLPT-5E 80 1.6 16.1 17.6 1.6 Disconnect
10E 15CLPT-10E 50 1.6 16.1 17.6 1.6 Disconnect 95 15CLPT-PDM-B 15CLPT-GDM-B CLPT-DL CLPT-DF
0.5E 15NCLPT-.5E 63 1.6 11.5 12.9 1.6 Non- 95 15CLPT-PNM-A 15CLPT-GNM-A CLPT-NL —
1E 15NCLPT-1E 63 1.6 11.5 12.9 1.6 Disconnect
2E 15NCLPT-1.5E 63 1.6 11.5 12.9 1.6 Disconnect 95 15CLPT-PDM-A 15CLPT-GDM-A CLPT-DL CLPT-DF

70548303

70548403

63934002
3E 15NCLPT-3E 63 1.6 16.1 17.6 1.6 Non- 95 15CLPT-PNM-B 15CLPT-GNM-B CLPT-NL —
5E 15NCLPT-5E 63 1.6 16.1 17.6 1.6 Disconnect
10E 15NCLPT-10E 63 1.6 16.1 17.6 1.6 Disconnect 95 15CLPT-PDM-B 15CLPT-GDM-B CLPT-DL CLPT-DF
25.5 kV Maximum (14.4 kV Nominal)
0.5E 25CLPT-.5E 44 1.6 16.1 17.6 2 Non- Not applicable. 25CLPT-NL —

56353208

56353308

63933901
1E 25CLPT-1E 44 1.6 16.1 17.6 2 Disconnect
Disconnect 25CLPT-DL CLPT-DF
13
38.0 kV Maximum (34.5 kV Nominal)
0.5E 38CLPT-.5E 44 1.6 17.1 18.6 2 Non- Not applicable. 25CLPT-NL —

56353208

56353308

63933901
Disconnect
Disconnect 25CLPT-DL CLPT-DF

 Includes end fittings.


 Disconnect only.

CA08101001E For more information visit: www.eaton.com


13-82 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Type CLPT

Table 13-74. Type CLPT Current Limiting Fuses


Ampere Fuse Mounting Voltage Mounting (Including Live Parts, Live Parts End Fittings
Rating Type  BIL (kV) End Fittings)  (Including (Disconnect
End Fittings)  Only)
Porcelain Glass-Polyester Catalog Catalog
Insulator Insulator Number Number
Catalog Catalog
Number Number
CLPT Mountings and Hardware
2.475 kV Maximum (2.4 kV Nominal)
Consult Factory
CLPT Mountings and Hardware
5.5 kV Maximum (4.8 kV Nominal)
0.5 to 1.5 Non-Disconnect 60 5CLPT-PNM-A 5CLPT-GNM-A CLPT-NL —
Disconnect 60 5CLPT-PDM-A 5CLPT-GDM-A — —
3 to 10 Non-Disconnect 60 5CLPT-PNM-B 5CLPT-GNM-B CLPT-NL —
Disconnect 60 5CLPT-PDM-B 5CLPT-GDM-B — —
CLPT Mountings and Hardware
8.3 kV Maximum (7.2 kV Nominal)
0.5 Non-Disconnect 75 8CLPT-PNM-A 8CLPT-GNM-A CLPT-NL —
Disconnect 75 8CLPT-PDM-A 8CLPT-GDM-A CLPT-DL CLPT-DF
3 to 10 Non-Disconnect 75 8CLPT-PNM-B 8CLPT-GNM-B CLPT-NL —
Disconnect 75 8CLPT-PDM-B 8CLPT-GDM-B CLPT-DL CLPT-DF
CLPT Mountings and Hardware
15.5 kV Maximum (14.4 kV Nominal)
0.5 to 1.5 Non-Disconnect 95 15CLPT-PNM-A 15CLPT-GNM-A CLPT-NL —
Disconnect 95 15CLPT-PDM-A 15CLPT-GDM-A CLPT-DL CLPT-DF

13 3 to 10 Non-Disconnect
Disconnect
95
95
15CLPT-PNM-B
15CLPT-PDM-B
15CLPT-GNM-B
15CLPT-GDM-B




CLPT Mountings and Hardware
25.5 kV Maximum (23.0 kV Nominal)
0.5 to 1.5 Non-Disconnect 150 25CLPT-PNM-A — 25CLPT-NL —
Disconnect 150 25CLPT-PDM-A — 25CLPT-DL —
CLPT Mountings and Hardware
38.0 kV Maximum (34.5 kV Nominal)
Consult Factory
 See Page 13-88 for diagram of typical mounting.
 End fittings supplied only when required.

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-83
Current Limiting Fuses
December 2008
Type CX

Table 13-75. Type CX Current Limiting Fuses


Catalog Mounting (Includes Live Parts, Catalog Number Performance Curves

Interrupting Rating rms


Number End Fittings)
Type Catalog Live End Minimum Total Peak I2t
Maximum Design

Diameter (Inches)

Approx. Shipping
Parts  Fittings  Melting

Voltage (BIL) kV
Number Clearing Let-

Length (Inches)
Barrel Number
Current Rating

Glass- Time Time Through

Weight (lbs.)
Voltage (kV)

Polyester Current
(Amperes)

(kA Sym.)
4.3 kV Maximum (2.4 kV Nominal)
18C 4CX-18C 1 50 1.13 10 1 Non- 60 5CX-GNM-G CX-NL — 70544101 70544501 70544901 70545101
25C 4CX-25C 1 50 1.13 10 1 Disconnect
35C 4CX-35C 1 50 2 10 1 Disconnect 60 5CX-GDM-G CX-DL CX-DF 70544102 70544502
45C 4CX-45C 1 50 2 10 2
50C 4CX-50C 1 50 2 10 2 70544101 70544501
60C 4CX-60C 1 50 2 10 2 70544102 70544502
65C 4CX-65C 1 50 2 10 2
70544101 70544501
75C 4CX-75C 1 50 2 10 2
80C 4CX-80C 1 50 2 10 2
100C 4CX-100C 1 50 2 10 2
5.5 kV Maximum (4.8 kV Nominal)
10C 5CX-10C 1 50 1.13 10 1 Non- 60 5CX-GNM-G CX-NL — 70544201 70544601 70544902 70545201
12C 5CX-12C 1 50 1.13 10 1 Disconnect 70544202 70544602
18C 5CX-18C 1 50 1.13 10 1
20C 5CX-20C 1 50 1.13 10 1 70544201 70544602
21C 5CX-21C 1 50 2 10 2 Disconnect 60 5CX-GDM-G CX-DL CX-DF 70544202 70544602
25C 5CX-25C 1 50 2 10 2
70544201 70544602
30C 5CX-30C 1 50 1.13 10 1
35C 5CX-35C 1 50 2 10 2 70544202 70544602
40C
50C
5CX-40C
5CX-50C
1
1
50
50
2
2
10
10
2
2
70544201 70544601 13
60C 5CX-60C 1 50 2 10 2
65C 5CX-65C 1 50 2 10 2
75C 5CX-75C 1 50 2 10 2
8.3 kV Maximum (7.2 kV Nominal)
3.5C 8CX-3.5C 1 50 1.13 10 2 Non- 75 8CX-GNM-G CX-NL — 70544302 70544702 70545001 70545301
4C 8CX-4C 1 50 1.13 10 2 Disconnect 70544301 70544701
4.5C 8CX-4.5C 1 50 1.13 10 2
6C 8CX-6C 1 50 1.13 10 2 70544302 70544702
7C 8CX-7C 1 50 1.13 10 2 70544301 70544701
8C 8CX-8C 1 50 1.13 10 2
Disconnect 75 8CX-GDM-G CX-DL CX-DF 70544302 70544702
10C 8CX-10C 1 50 1.13 10 2
12C 8CX-12C 1 50 1.13 10 2 70544301 70544701
15C 8CX-15C 1 50 1.13 10 2 70544302 70544702
18C 8CX-18C 1 50 2 10 2
20C 8CX-20C 1 50 2 10 2 70544301 70544701
25C 8CX-25C 1 50 2 10 2
30C 8CX-30C 1 50 2 10 2
35C 8CX-35C 1 50 2 10 2
40C 8CX-40C 1 50 2 10 2
15.5 kV Maximum (14.4 kV Nominal)
4C 15CX- 4C 1 50 2 14.3 2 Non- 95 15CX-GNM-G CX-NL — 70544401 70544801 70545002 40545401
6C 15CX- 6C 1 50 2 14.3 2 Disconnect 70544402 70544802
7C 15CX- 7C 1 50 2 14.3 2
8C 15CX- 8C 1 50 2 14.3 2 70544101 70544801
10C 15CX- 10C 1 50 2 14.3 2 Disconnect 95 15CX-GDM-G CX-DL CX-DF 70544402 70544802
12C 15CX- 12C 1 50 2 14.3 2
15C 15CX- 15C 1 50 2 14.3 2
18C 15CX- 18C 1 50 2 14.3 2
20C 15CX- 20C 1 50 2 14.3 2
25C 15CX- 25C 1 50 2 14.3 2
30C 15CX- 30C 1 50 2 14.3 2
40C 15CX- 40C 1 50 2 14.3 2
 Includes end fittings.
 Disconnect only.

CA08101001E For more information visit: www.eaton.com


13-84 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Type CX

Table 13-76. Type CX Current Limiting Fuses


Ampere Fuse Mounting Size Voltage Mounting (Including Live Parts, Live Parts End Fittings
Rating Type  BIL (kV) End Fittings)  (Including (Disconnect
End Fittings)  Only)
Porcelain Glass-Polyester Catalog Catalog
Insulator Insulator Number Number
Catalog Catalog
Number Number
CX Mountings and Hardware
4.3 kV Maximum (2.4 kV Nominal)
18C to 100C Non-Disconnect A 60 — 5CX-GNM-G CX-NL —
Disconnect 60 — 5CX-GDM-G CX-DL CX-DF
CX Mountings and Hardware
5.5 kV Maximum (4.8 kV Nominal)
10C to 75C Non-Disconnect A 60 — 5CX-GNM-G CX-NL —
Disconnect 60 — 5CX-GDM-G CX-DL CX-DF
CX Mountings and Hardware
8.3 kV Maximum (7.2 kV Nominal)
3.5C to 40C Non-Disconnect B 75 — 8CX-GNM-G CX-NL —
Disconnect 75 — 8CX-GDM-G CX-DL CX-DF
CX Mountings and Hardware
15.5 kV Maximum (14.4 kV Nominal)
4C to 40C Non-Disconnect C 95 — 15CX-GNM-G CX-NL —
Disconnect 95 — 15CX-GDM-G CX-DL CX-DF
 See Page 13-88 for diagram of typical mounting.
 End fittings supplied only when required.

13

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-85
Current Limiting Fuses
December 2008
Type CXN

Table 13-77. Type CXN Current Limiting Fuses


Mounting (Includes Live Parts, Catalog Number Performance Curves
End Fittings)

Interrupting Rating
Maximum Design

Diameter (Inches)

Approx. Shipping
Type Catalog Live End Minimum Total Peak I2t

Voltage (BIL) kV
Length (Inches)
Current Rating

Barrel Number
Parts  Fittings 

rms (kA Sym.)


Number Melting Clearing Let-

Weight (lbs.)
Voltage (kV)

Glass- Time Time Through


(Amperes)

Polyester Current
Number
Catalog

8.3 kV Maximum
60C 8CXN-60C 1 50 3 18.8 8 Non- 95 15CXN-GNM-D 15CXN-NL-D — 66675102 66675202 66664902
100C 8CXN-100C 1 50 3 18.8 8 Disconnect
125C 8CXN-125C 1 50 4 18.8 14
150C 1 50 4 18.8 14 Disconnect 95 15CXN-GDM-G 15CXN-DL-G 15CXN-DF-G
8CXN-150C
200C 1 50 4 18.8 14 Non- 95 15CXN-GNM-F 15CXN-NL-F —
250C 8CXN-200C 1 50 4 18.8 14 Disconnect
8CXN-250C
Non- 95 15CXN-GNM-G 15CXN- NL-G
Disconnect
Disconnect 95 15CXN-GDM-F 15CXN-DL-F
120C 8CXN-120C 2 50 3 18.8 16 Non- 95 15CXN-GNM-D 15CXN-NL-D — 66675104 66675204 2 X 60C
200C 8CXN-200C 2 50 3 18.8 16 Disconnect
250C 2 50 3 18.8 16 2 X 100C
8CXN-250C
300C 8CXN-300C 2 50 4 18.8 28 2 X 125C
Disconnect 95 15CXN-GNM-F 15CXN-NL-F 2 X 150C
15.5 kV Maximum
45C 15CXN-45C 1 50 3 18.8 8 Non- 95 15CXN-GNM-F 15CXN-NL-F — 66674802 66675002 66665002
60C 15CXN-60C 1 50 3 18.8 Disconnect
75C 15CXN-75C 1 50 4 18.8
85C 1 50 4 18.8 Non- 95 15CXN-GNM-G 15CXN-NL-G
15CXN-85C Disconnect
100C 1 50 4 18.8
15CXN-100C
8 Disconnect 95 15CXN-GDM-G 15CXN-DL-G 15CXN-DF-G 13
14
14 Non- 95 15CXN-GNM-F 15CXN-NL-F —
14 Disconnect
Non- 95 15CXN-GNM-G 15CXN-NL-G
Disconnect
Disconnect 95 15CXN-GDM-F 15CXN-DL-F — 66674804 66675004
90C 15CXN-90C 2 50 3 18.8 16 Non- 95 15CXN-GNM-D 15CXN-NL-D 2 X 45C
120C 15CXN-120C 2 50 3 18.8 16 Disconnect
2 X 60C
150C 15CXN-150C 2 50 4 18.8 28 Non- 95 15CXN-GNM-F 15CXN-NL-F 2 X 75C
175C 15CXN-175C 2 50 4 18.8 28 Disconnect
2 X 85C
 Includes end fittings.
 Disconnect only.

Table 13-78. Type CXN Current Limiting Fuses


Ampere Fuse Mounting Voltage Mounting (Including Live Parts, Live Parts (Including End Fittings
Rating Type  BIL (kV) End Fittings)  End Fittings)  (Disconnect Only)
Porcelain Insulator Glass-Polyester Insulator Catalog Catalog
Number Number
Catalog Number Catalog Number
CXN Mountings and Hardware
8.3 kV Maximum (7.2 kV Nominal)
60C to 100C Non-Disconnect 95 — 15CXN-GNM-D 15CXN-NL-D —
Non-Disconnect 95 — 15CXN-GNM-G 15CXN-NL-G —
Disconnect 95 — 15CXN-GDM-G 15CXN-DL-G 15CXN-DF-G
125C to 250C Non-Disconnect 95 — 15CXN-GNM-F 15CXN-NL-F —
Non-Disconnect 95 — 15CXN-GNM-G 15CXN-NL-G —
Disconnect 95 — 15CXN-GDM-F 15CXN-DL-F 15CXN-DF-G
300C Non-Disconnect 95 — 15CXN-GNM-F 15CXN-NL-F —
CXN Mountings and Hardware
15.5 kV Maximum (14.4 kV Nominal)
45C to 60C Non-Disconnect 95 — 15CXN-GNM-D 15CXN-NL-D —
Non-Disconnect 95 — 15CXN-GNM-G 15CXN-NL-G —
Disconnect 95 — 15CXN-GDM-G 15CXN-DL-G 15CXN-DF-G
75C to 100C Non-Disconnect 95 — 15CXN-GNM-F 15CXN-NL-F —
Non-Disconnect 95 — 15CXN-GNM-G 15CXN-NL-G —
Disconnect 95 — 15CXN-GDM-F 15CXN-DL-F 15CXN-DF-G
120C Non-Disconnect 95 — 15CXN-GNM-D 15CXN-NL-D —
150C and 175C Non-Disconnect 95 — 15CXN-GNM-F 15CXN-NL-F —
 See Page 13-88 for diagram of typical mounting.
 End fittings supplied only when required.

CA08101001E For more information visit: www.eaton.com


13-86 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Type DSL

Table 13-79. Type DSL Low Voltage Current Limiting Fuse


Fuse Catalog Diameter Length Interrupting Application Data Approximate
Type/Voltage Number Inches Inches Rating Amperes, (Time Current Curves) Ship Wt.
(mm) (mm) rms (Symmetrical) Lbs. (kg)
Type DSL Fuse Units
600 Volts Nominal
6DSL-A150 — — 200,000 33 – 792 (2) 3.00 (1.4)
6DSL-A200 — — 200,000 33 – 792 (2) 3.00 (1.4)
6DSL-A250 — — 200,000 33 – 792 (2) 3.00 (1.4)
6DSL-A300 — — 200,000 33 – 792 (2) 3.00 (1.4)
6DSL-A400 — — 200,000 33 – 792 (2) 3.00 (1.4)
6DSL-A600 — — 200,000 33 – 792 (2) 3.00 (1.4)
6DSL-A800 — — 200,000 33 – 792 (2) 3.00 (1.4)
6DSL-B1200 — — 200,000 33 – 792 (2) 4.00 (1.8)
6DSL-B1600 — — 200,000 33 – 792 (2) 4.00 (1.8)
6DSL-B2000 — — 200,000 33 – 792 (2) 4.00 (1.8)
6DSL-C800 — — 200,000 33 – 792 (3) 5.50 (2.5)
6DSL-C1000 — — 200,000 33 – 792 (3) 5.50 (2.5)
6DSL-C1200 — — 200,000 33 – 792 (3) 5.50 (2.5)
6DSL-C1600 — — 200,000 33 – 792 (3) 5.50 (2.5)
6DSL-C2000 — — 200,000 33 – 792 (3) 5.50 (2.5)
6DSL-D2500 — — 200,000 33 – 792 (3) 8.50 (3.9)
6DSL-D3000 — — 200,000 33 – 792 (3) 8.50 (3.9)
6DSL-E2500 — — 200,000 33 – 792 20.00 (9.1)
6DSL-E3000 — — 200,000 33 – 792 20.00 (9.1)
6DSL-E4000 — — 200,000 33 – 792 20.00 (9.1)
6DSL-F5000 — — 200,000 33 – 792 24.00 (10.9)

13

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-87
Current Limiting Fuses
December 2008
Type CXF

Table 13-80. Type CXF Indicated Full-Range Current-Limiting Fuses


Catalog Mounting Catalog Number Performance I2t

Approximate Shipping
Number Curves

Interrupting Rating

Peak Let-Through
Type Catalog Live End
Maximum Design

Voltage (BIL) kV

Maximum Total
Number Parts Fittings

Minimum Melt
Current Rating

Tube Diameter
(rms kA Sym.)

Clearing Time
Weight (Lbs.)

Melting Time
Tube Length
Voltage (kV)

(Amp2Sec)

(Amp2Sec)
(Amperes)

Minimum
(Inches)

(Inches)

Current
Total
70541102

70541202

70541902
5.5 80 5CXF-80 50 3.32 11.85 6.5 Non- — — CXN-NL-G — 22,100 110,000
100 5CXF-100 Disconnect 56,700 280,000
125 5CXF-125 Disconnect — — CXN-GL-G CXN-DF-G 78,300 380,000
150 5CXF-150 176,000 860,000
200 5CXF-200 259,000 1,270,000

70541702

70541802

70541902
10 6 8CXF-6 50 2.25 7.93 2 Non- 75 8CX-GNM-G CX-NL — 620 2,700
8 8CXF-8 Disconnect 800 4,000
10 8CXF-10 800 4,000
12 8CXF-12 920 8,000
18 8CXF-18 1,310 9,500
20 8CXF-20 Disconnect 75 8CX-GDM-G CX-DL CX-DF 1,620 11,000
25 8CXF-25 3,660 22,000
30 8CXF-30 5,250 30,000
40 8CXF-40 8,700 50,000
50 8CXF-50 12,800 70,000

70541302

70541402

70541902
8.3 65 8CXF-65 50 3.32 11.85 6.5 Non- — — CXN-NL-G — 25,200 100,000
80 8CXF-80 Disconnect 47,200 185,000
100 8CXF-100 Disconnect — — CXN-DL-G CXN-DF-G 78,300 330,000
125 8CXF-125 115,150 480,000
13

70541702

70541802

70541902
17.2 6 15CXF-6 50 2.25 12.24 2 Non- 95 15CX-GNM-G CX-NL — 620 2,600
8 15CXF-8 Disconnect 800 3,700
10 15CXF-10 800 3,700
12 15CXF-12 920 6,500
18 15CXF-18 1,310 8,000
20 15CXF-20 Disconnect 95 15CX-GDM-G CX-DL CX-DF 1,620 10,000
25 15CXF-25 3,660 22,000
30 15CXF-30 5,250 30,000
40 15CXF-40 8,700 50,000
50 15CXF-50 12,800 70,000
70541702 66704202

70541802 66704602

70541902 70541902
15.5 65 15CXF-65 50 3.32 14.66 8 Non- — — CXN-NL-G — 25,200 110,000
80 15CXF-80 Disconnect 39,400 185,000
100 15CXF-100 Disconnect — — CXN-DL-G CXN-DF-G 80,000 380,000

23 6 23CXF-6 50 2.25 15.05 4 Non- — — CX-NL — 620 3,100


8 23CXF-8 Disconnect 800 4,800
10 23CXF-10 800 4,800
12 23CXF-12 920 8,300
18 23CXF-18 1,310 11,200
20 23CXF-20 Disconnect — — CX-DL CX-DF 1,620 13,000
25 23CXF-25 3,660 28,000
30 23CXF-30 5,250 38,000
40 23CXF-40 8,700 61,000
50 23CXF-50 12,800 82,000

CA08101001E For more information visit: www.eaton.com


13-88 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Typical Fuse Mounting

Typical Fuse Mounting for Current Limiting Fuses

Figure 13-24. Single Barrel Disconnect with


2-Inch (50.8 mm) Diameter CLE Fuses Figure 13-28. Disconnect (CX) Figure 13-32. Disconnect (15CXN-GNM-G)

13

Figure 13-25. Single Barrel Disconnect Figure 13-29. Single-Barrel Non-Disconnect


All 3-Inch (76.2 mm) Diameter CLE Fuses All 2-Inch (50.8 mm) and 3-Inch (76.2 mm) Figure 13-33. Non-Disconnect
Diameter CL Fuses (15CXN-GNM-F and 15CXN-GNM-D)

Figure 13-26. Double Barrel Disconnect Figure 13-30. Double-Barrel Non-Disconnect Figure 13-34. Disconnect (15CXN-GNM-F)
All 3-Inch (76.2 mm) Diameter CLE Fuses All 2-Inch (50.8 mm) and 3-Inch (76.2 mm)
Diameter CL Fuses

Figure 13-27. Non-Disconnect (CX) Figure 13-31. Non-Disconnect (15CXN-GNM-G)

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-89
Current Limiting Fuses
December 2008
Pricing

Table 13-81. Pricing Pricing (Continued) Pricing (Continued)


Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $

121DBA2-100E 15CLE3-150E 15CX-4C


121DBA2-10E 15CLE3-175E/200X 15CX-6C
121DBA2-125E 15CLE-40E 15CX-7C
121DBA2-150E 15HLE-40E 15CX-8C
121DBA2-15E 15CLE-50E 15CX-GDM-G
121DBA2-200E 15HLE-50E 15CX-GNM-G
121DBA2-20E 15CLE-65E
121DBA2-25E 15HLE-65E 15CXN-100C
121DBA2-30E 15CLE-80E 15CXN-45C
121DBA2-3E 15HLE-80E 15CXN-60C
121DBA2-40E 15CXN-75C
15CLE-GDM-C 15CXN-85C
121DBA2-50E 15CLE-GDM-D
121DBA2-5E 15CLE-GNM-C 15CXN-DF-G
121DBA2-65E 15CLE-GNM-D 15CXN-DL-F
121DBA2-7E 15CXN-DL-G
121DBA2-80E 15CLE-HPDM-C
15CLE-HPDM-D 15CXN-GDM-F
145DBA2-100E 15CLE-HPNM-C 15CXN-GDM-G
145DBA2-10E 15CLE-HPNM-D 15CXN-GNM-D
145DBA2-125E 15CXN-GNM-F
145DBA2-150E 15CLE-PDM-C 15CXN-GNM-G
145DBA2-15E 15CLE-PDM-D
15CLE-PDM-E 15CXN-NL-D
145DBA2-200E
15CLE-PNM-C 15CXN-NL-F
145DBA2-20E
15CLE-PNM-D 15CXN-NL-G
145DBA2-25E
145DBA2-30E 15CLE-PNM-E 15DBA1-.5E
145DBA2-3E 15CLE-100E 15DBA1-100E
145DBA2-40E 15CLE2-125X 15DBA1-10E
145DBA2-50E 15CLE-50E 15DBA1-125E
145DBA2-5E 15CLE-65E 15DBA1-150E
145DBA2-65E 15DBA1-15E
145DBA2-7E
15CLE-80E
15CLPT-.5E
15DBA1-200E 13
145DBA2-80E 15DBA1-20E
15CLPT-1.5E
14RBA2-DL 15CLPT-10E 15DBA1-25E
14RBA2-GDM 15CLPT-1E 15DBA1-30E
14RBA2-GNM 15CLPT-3E 15DBA1-3E
14RBA2-PDM 15CLPT-5E 15DBA1-40E
14RBA2-PNM 15DBA1-50E
15CLPT-GDM-A 15DBA1-5E
14RBA4-GDM 15CLPT-GDM-B 15DBA1-65E
14RBA4-GNM 15CLPT-GNM-A 15DBA1-7E
14RBA4-PDM 15CLPT-GNM-B 15DBA1-80E
14RBA4-PNM
15CLPT-HPDM-A 15HLE-100E
14RBA8-GNM 15CLPT-HPDM-B 15HLE-10E
14RBA8-PNM 15CLPT-HPNM-A 15HLE-125E
15CLE-100E 15CLPT-HPNM-B 15HLE-150E
15CLE-10E-D 15CLPT-PDM-A 15HLE-15E
15HLE-10E 15CLPT-PDM-B 15HLE-175E
15CLE-125E 15CLPT-PNM-A 15HLE-200E
15CLE2-125X 15CLPT-PNM-B 15HLE-20E
15CLE-40E 15CLT-12 15HLE-250E
15CLE-150E 15CLT-18 15HLE-25E
15CLE-50E 15CLT-30 15HLE-30E
15CLE-15E 15CLT-4 15HLE-40E
15CLE-15E-D 15CLT-5 15HLE-50E
15HLE-15E 15CLT-8 15HLE-65E
15CLE-65E 15HLE-80E
15CX-10C
15CLE-175E 15HLE-GDM-D
15CX-12C
15CLE-200E 15HLE-GDM-E
15CX-15C
15CLE-20E 15HLE-GNM-D
15CX-18C
15CLE-20E-D 15HLE-GNM-E
15CX-20C
15HLE-20E
15CX-25C 15HLE-PDM-D
15CLE2-100E 15CX-30C 15HLE-PDM-E
15CLE2-125X 15CX-40C 15HLE-PNM-D
15CLE-250E 15HLE-PNM-E
15CLE-25E
15NCLPT-.5E-A
15CLE-25E-D
15NCLPT-1E-A
15HLE-25E
15CLE2-80E
15CLE-300E
15HLE-30E

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F

CA08101001E For more information visit: www.eaton.com


13-90 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Pricing

Table 13-81. Pricing (Continued) Pricing (Continued) Pricing (Continued)


Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $

15RBA2-100E 15RBT4-100E 25RBA2-DH


15RBA2-10E 15RBT4-125E 25RBA2-IDH
15RBA2-125E 15RBT4-150E 25RBA2-INH
15RBA2-150E 15RBT4-200E 25RBA2-ISHNT
15RBA2-15E 15RBT4-20E 25RBA2-LBDH
15RBA2-200E 15RBT4-250E 25RBA2-NH
15RBA2-20E 15RBT4-25E 25RBA2-PDM
15RBA2-25E 15RBT4-300E 25RBA2-PNM
15RBA2-30E 15RBT4-30E 25RBA2-SHNT
15RBA2-40E 15RBT4-400E 25RBA4-.5E
15RBA2-50E 15RBT4-40E 25RBA4-100E
15RBA2-65E 15RBT4-50E 25RBA4-10E
15RBA2-80E 15RBT4-65E 25RBA4-125E
15RBT4-80E 25RBA4-150E
15RBA2-DH
15RBA2-IDH 15RDB2-DH 25RBA4-15E
15RBA2-INH 15RDB2-HUM 25RBA4-200E
15RBA2-ISHNT 15RDB2-HVM 25RBA4-20E
15RBA2-LBDH 15RDB2-SHNT 25RBA4-250E
15RBA2-NH 15RDB2-UM 25RBA4-25E
15RBA2-NL 15RDB2-VM 25RBA4-300E
15RBA2-PDM 15RDB4-DH 25RBA4-30E
15RBA2-PNM 15RDB4-HUM 25RBA4-3E
15RBA2-SHNT 15RDB4-SHNT 25RBA4-40E
15RDB4-UM 25RBA4-50E
15RBA4-.5E 25RBA4-5E
15RBA4-100E 15RDB4-VM
25RBA4-65E
15RBA4-10E 15RDB8-HUM 25RBA4-7E
15RBA4-125E 15RDB8-HVM 25RBA4-80E
15RBA4-150E 15RDB8-UM
15RBA4-15E 15RDB8-VM 25RBA4-DH
13 15RBA4-200E 25CLPT-.5E
25RBA4-IDH
25RBA4-INH
15RBA4-20E 25CLPT-1E
15RBA4-250E 25RBA4-ISHNT
25CLPT-DL 25RBA4-LBDH
15RBA4-25E 25CLPT-NL
15RBA4-300E 25RBA4-NH
25CLPT-PDM-A 25RBA4-PDM
15RBA4-30E 25CLPT-PNM-A
15RBA4-3E 25RBA4-PNM
15RBA4-400E 25DBA1-.5E 25RBA4-SHNT
15RBA4-40E 25DBA1-100E 25RBA8-INH
15RBA4-50E 25DBA1-10E 25RBA8-NH
15RBA4-5E 25DBA1-125E 25RBA8-PNM
15RBA4-65E 25DBA1-150E
25DBA1-15E 25RBT2-100E
15RBA4-7E 25RBT2-125E
15RBA4-80E 25DBA1-200E
25DBA1-20E 25RBT2-150E
15RBA4-DH 25DBA1-25E 25RBT2-200E
15RBA4-DL 25DBA1-30E 25RBT2-20E
15RBA4-IDH 25DBA1-3E 25RBT2-25E
15RBA4-INH 25DBA1-40E 25RBT2-30E
15RBA4-ISHNT 25DBA1-50E 25RBT2-40E
15RBA4-LBDH 25DBA1-5E 25RBT2-50E
15RBA4-LBDL 25DBA1-65E 25RBT2-65E
15RBA4-NH 25DBA1-7E 25RBT2-80E
15RBA4-NL 25DBA1-80E 25RBT4-100E
15RBA4-PDM 25RBT4-125E
15RBA4-PNM 25RBA2-100E
25RBA2-10E 25RBT4-150E
15RBA4-SHNT 25RBT4-200E
25RBA2-125E
15RBA8-INH 25RBA2-150E 25RBT4-20E
15RBA8-NH 25RBA2-15E 25RBT4-250E
15RBA8-NL 25RBA2-200E 25RBT4-25E
15RBA8-PNM 25RBA2-20E 25RBT4-300E
15RBT2-100E 25RBA2-25E 25RBT4-30E
15RBT2-125E 25RBA2-30E 25RBT4-40E
15RBT2-150E 25RBA2-40E 25RBT4-50E
15RBT2-200E 25RBA2-50E 25RBT4-65E
15RBT2-20E 25RBA2-65E 25RBT4-80E
15RBT2-25E 25RBA2-80E 25RDB2-DH
15RBT2-30E 25RDB2-HUM
15RBT2-40E 25RDB2-HVM
15RBT2-50E 25RDB2-SHNT
15RBT2-65E 25RDB2-UM
15RBT2-80E 25RDB2-VM

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-91
Current Limiting Fuses
December 2008
Pricing

Table 13-81. Pricing (Continued) Pricing (Continued) Pricing (Continued)


Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $

2HCLS-200 38RBA2-SHNT
25RDB4-DH 2HCLS-230 38RBA4-.5E
25RDB4-HUM 2HCLS-24R 38RBA4-100E
25RDB4-HVM 2HCLS-25 38RBA4-10E
25RDB4-SHNT 2HCLS-2R 38RBA4-125E
25RDB4-UM 2HCLS-390 38RBA4-150E
25RDB4-VM 2HCLS-3R 38RBA4-15E
25RDB8-HUM 2HCLS-4R 38RBA4-200E
25RDB8-HVM 2HCLS-5R 38RBA4-20E
25RDB8-UM 2HCLS-6R 38RBA4-250E
25RDB8-VM 2NCLPT-.25E 38RBA4-25E
2ACLS-12R 2NCLPT-.5E 38RBA4-300E
2ACLS-18R 2NCLPT-1E 38RBA4-30E
2ACLS-24R 2NCLPT-2E 38RBA4-3E
2ACLS-25 2NCLPT-5E 38RBA4-40E
2ACLS-2R 38RBA4-50E
38CLPT-.5E
2ACLS-3R 38RBA4-5E
38CLPT-PNM-A
2ACLS-4L 38RBA4-65E
38DBA1-.5E 38RBA4-7E
2ACLS-4R
38DBA1-100E 38RBA4-80E
2ACLS-5R
38DBA1-10E
2ACLS-6R 38RBA4-DH
38DBA1-125E
2ACLS-9R 38RBA4-DL
38DBA1-150E
2CLE-100E 38RBA4-IDH
38DBA1-15E
2CLE-10E 38RBA4-INH
38DBA1-200E
2CLE-125E 38RBA4-ISHNT
38DBA1-20E
2CLE-150E 38RBA4-NH
38DBA1-25E
2CLE-15E 38RBA4-NL
38DBA1-30E
2CLE-200E 38RBA4-PDM
38DBA1-3E
2CLE-20E 38RBA4-PNM
38DBA1-40E
2CLE-225E 38RBA4-SHNT
38DBA1-50E
2CLE-250E
2CLE-25E
38DBA1-5E
38DBA1-65E
38RBA8-INH
38RBA8-NH 13
2CLE-300E 38DBA1-7E 38RBA8-NL
2CLE-30E 38DBA1-80E 38RBA8-PNM
2CLE-350X
38DBA2-.5E 38RBT2-100E
2CLE-400X
38DBA2-100E 38RBT2-125E
2CLE-40E
38DBA2-10E 38RBT2-150E
2CLE-450X
38DBA2-125E 38RBT2-200E
2CLE-50E
38DBA2-150E 38RBT2-20E
2CLE-65E
38DBA2-15E 38RBT2-25E
2CLE-80E
38DBA2-200E 38RBT2-30E
2CLE-GDM-C 38DBA2-20E 38RBT2-40E
2CLE-GDM-D 38DBA2-25E 38RBT2-50E
2CLE-GDM-E 38DBA2-30E 38RBT2-65E
2CLE-GNM-C 38DBA2-3E 38RBT2-80E
2CLE-GNM-D 38DBA2-40E 38RBT4-100E
2CLE-GNM-E 38DBA2-50E 38RBT4-125E
2CLE-PDM-C 38DBA2-5E 38RBT4-150E
2CLE-PDM-D 38DBA2-65E 38RBT4-200E
2CLE-PDM-E 38DBA2-7E 38RBT4-20E
2CLE-PNM-C 38DBA2-80E 38RBT4-250E
2CLE-PNM-D 38RBA2-100E 38RBT4-25E
2CLE-PNM-E 38RBA2-10E 38RBT4-300E
2CLS-200 38RBA2-125E 38RBT4-30E
2CLS-230 38RBA2-150E 38RBT4-40E
2CLS-24R 38RBA2-15E 38RBT4-50E
2CLS-25 38RBA2-200E 38RBT4-65E
2CLS-2R 38RBA2-20E 38RBT4-80E
2CLS-390 38RBA2-25E 38RDB2-DH
2CLS-3R 38RBA2-30E 38RDB2-HUM
2CLS-4R 38RBA2-40E 38RDB2-HVM
2CLS-5R 38RBA2-50E 38RDB2-SHNT
2CLS-6R 38RBA2-65E 38RDB2-UM
38RBA2-80E
2CLS-GDM-D 38RDB2-VM
2CLS-GDM-E 38RBA2-DH 38RDB4-DH
2CLS-PDM-D 38RBA2-DL 38RDB4-HUM
2CLS-PDM-E 38RBA2-IDH 38RDB4-HVM
38RBA2-INH
2CLT-12 38RDB4-SHNT
38RBA2-ISHNT
2CLT-150 38RDB4-UM
2CLT-18 38RBA2-NH 38RDB4-VM
2CLT-25 38RBA2-NL
2CLT-30 38RBA2-PDM
2CLT-5 38RBA2-PNM
2CLT-75
2CLT-90

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F

CA08101001E For more information visit: www.eaton.com


13-92 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Pricing

Table 13-81. Pricing (Continued) Pricing (Continued) Pricing (Continued)


Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $

38RDB8-HUM 5AHLE-50E 5CLE-GDM-C


38RDB8-HVM 5ACLE-65E 5CLE-GDM-D
38RDB8-UM 5AHLE-65E 5CLE-GDM-E
38RDB8-VM 5ACLE-80E 5CLE-GNM-C
48DBA1-.5E 5AHLE-80E 5CLE-GNM-D
48DBA1-100E 5ACLS-12R 5CLE-GNM-E
48DBA1-10E 5ACLS-18R 5CLE-PDM-C
48DBA1-125E 5ACLS-24R 5CLE-PDM-D
48DBA1-150E 5ACLS-2R 5CLE-PDM-E
48DBA1-15E 5ACLS-30 5CLE-PNM-C
48DBA1-200E 5ACLS-3R 5CLE-PNM-D
48DBA1-20E 5ACLS-4R 5CLE-PNM-E
48DBA1-25E 5ACLS-5R 5CLPT-.5E
48DBA1-30E 5ACLS-6R 5CLPT-1.5E
48DBA1-3E 5ACLS-9R 5CLPT-10E
48DBA1-40E 5AHLE-100E 5CLPT-1E
48DBA1-50E 5AHLE-10E 5CLPT-3E
48DBA1-5E 5AHLE-125E 5CLPT-5E
48DBA1-65E 5AHLE-150E
48DBA1-7E 5CLPT-GDM-A
5AHLE-15E 5CLPT-GDM-B
48DBA1-80E 5AHLE-175E 5CLPT-GNM-A
48DBA2-.5E 5AHLE-200E 5CLPT-GNM-B
48DBA2-100E 5AHLE-20E
48DBA2-10E 5AHLE-250E 5CLPT-PDM-A
48DBA2-125E 5AHLE-25E 5CLPT-PDM-B
48DBA2-150E 5AHLE-300E 5CLPT-PNM-A
48DBA2-15E 5AHLE-30E 5CLPT-PNM-B
48DBA2-200E 5AHLE-350E 5CLS-12R
48DBA2-20E 5AHLE-400E 5CLS-18R
13 48DBA2-25E
48DBA2-30E
5AHLE-40E
5AHLE-450E
5CLS-24R
5CLS-2R
48DBA2-3E 5AHLE-50E 5CLS-30
48DBA2-40E 5AHLE-65E 5CLS-3R
48DBA2-50E 5AHLE-80E 5CLS-4R
48DBA2-5E 5HLE-100E 5CLS-5R
48DBA2-65E 5CLE-10E-D 5CLS-6R
48DBA2-7E 5HLE-10E 5CLS70-100E
48DBA2-80E 5CLE1-100E 5CLS70-125E
4ACLS-26R 5CLE1-10E 5CLS70-12R
4CX-100C 5CLE1-125E 5CLS70-150E
4CX-18C 5CLE1-225E 5CLS70-200E
4CX-25C 5CLE-30E 5CLS70-24R
4CX-35C 5CLE1-40E 5CLS70-250E
4CX-45C 5CLE1-50E 5CLS70-2R
4CX-50C 5CLE-15E 5CLS70-32R
4CX-60C 5CLE-15E-D 5CLS70-36R
4CX-65C 5HLE-15E 5CLS70-3R
4CX-75C 5CLE1-65E 5CLS70-44R
4CX-80C 5CLE-175E 5CLS70-4R
5ACLE-100E 5CLE1-80E 5CLS70-5R
5AHLE-100E 5CLE-20E 5CLS70-600E
5AHLE-10E 5CLE-20E-D 5CLS70-6R
5ACLE-125E 5HLE-20E 5CLS70-750E
5ACLE-150E 5CLE2-250E/280X 5CLS70-80E
5AHLE-15E 5CLE2-350X 5CLS70-9R
5ACLE-200E 5CLE2-365X 5CLS75-24R
5AHLE-20E 5CLE2-400X 5CLS75-32R
5ACLE-225E 5CLE2-450X 5CLS75-36R
5ACLE-250E 5CLE-25E 5CLS-9R
5ACLE-25E 5CLE-25E-D 5CLS-GDM-D
5AHLE-25E 5CLE-300E 5CLS-GDM-E
5ACLE-300E 5CLE-30E
5ACLE-30E 5CLS-HGDM-D
5HLE-30E
5AHLE-30E 5CLS-HGDM-E
5CLE-350E
5ACLE-400X 5CLS-HPDM-D
5CLE-400E
5AHLE-40E 5CLS-HPDM-E
5HLE-40E
5ACLE-50E 5CLE-450E 5CLS-PDM-D
5HLE-50E 5CLS-PDM-E
5CLE-600E
5HLE-65E
5CLE-750E
5HLE-80E

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-93
Current Limiting Fuses
December 2008
Pricing

Table 13-81. Pricing (Continued) Pricing (Continued) Pricing (Continued)


Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $

5CLT-12 5NCLPT-2E 72DBA2-.5E


5CLT-18 5NCLPT-3E 72DBA2-100E
5CLT-25 5NCLPT-4E 72DBA2-10E
5CLT-30 5NCLPT-5E 72DBA2-125E
5CLT-45 72DBA2-150E
5RBA2-GDM
5CLT-60 72DBA2-15E
5RBA2-GNM
5CLT-8 72DBA2-200E
5RBA2-PDM
72DBA2-20E
5CX-10C 5RBA2-PNM
72DBA2-25E
5CX-12C 5RBA4-GDM
72DBA2-30E
5CX-18C 5RBA4-GNM
72DBA2-3E
5CX-20C 5RBA4-PDM
72DBA2-40E
5CX-21C 5RBA4-PNM
72DBA2-50E
5CX-25C 5RBA8-GNM
72DBA2-5E
5CX-30C 5RBA8-PNM
72DBA2-65E
5CX-35C 5SCLE-100E 72DBA2-7E
5CX-40C 5SCLE-125E 72DBA2-80E
5CX-50C 5SCLE-150E
5CX-60C 7ACLS-12R
5SCLE-200E
5CX-65C 7ACLS-18R
5SCLE-225E
5CX-75C 7ACLS-24R
5SCLE-250E
7ACLS-9R
5CX-GDM-G 5SCLE-300E
5CX-GNM-G 5SCLE-400X 7CLS-24R
5SCLE-50E 7CLS-36R
5HCLS-12R
5SCLE-65E 7CLS-44R
5HCLS-18R
5SCLE-80E
5HCLS-24R 8AHLE-100E
5HCLS-2R 6DSL-A150 8AHLE-10E
5HCLS-30 6DSL-A200 8AHLE-15E
5HCLS-3R 6DSL-A250 8AHLE-20E
5HCLS-4R 6DSL-A300 8AHLE-25E
5HCLS-5R 6DSL-A400 8AHLE-30E
5HCLS-6R
5HCLS-9R
6DSL-A600
6DSL-A800
8AHLE-40E
8AHLE-50E 13
8AHLE-65E
5HLE-100E 6DSL-B1200
8AHLE-80E
5HLE-10E 6DSL-B1600
5HLE-125E 6DSL-B2000 8ACLS-2R
5HLE-150E 8ACLS-3R
6DSL-C1000
5HLE-15E 8ACLS-4L
6DSL-C1200
5HLE-175E 8ACLS-4R
6DSL-C1600
5HLE-200E 8ACLS-5R
6DSL-C2000
5HLE-20E 8ACLS-6R
6DSL-C800
5HLE-250E 8AHLE-100E
5HLE-25E 6DSL-D2500
8AHLE-10E
5HLE-300E 6DSL-D3000
8AHLE-125E
5HLE-30E 6DSL-E2500 8AHLE-150E
5HLE-350E 6DSL-E3000 8AHLE-15E
5HLE-400E 6DSL-E4000 8AHLE-175E
5HLE-40E 6DSL-F5000 8AHLE-200E
5HLE-450E
72DBA1-.5E 8AHLE-20E
5HLE-50E
72DBA1-100E 8AHLE-250E
5HLE-65E
72DBA1-10E 8AHLE-25E
5HLE-80E
72DBA1-125E 8AHLE-300E
5HLE-GDM-D 72DBA1-150E 8AHLE-30E
5HLE-GDM-E 72DBA1-15E 8AHLE-350E
5HLE-GNM-D 72DBA1-200E 8AHLE-40E
5HLE-GNM-E 72DBA1-20E 8AHLE-50E
72DBA1-25E 8AHLE-65E
5HLE-PDM-D
72DBA1-30E 8AHLE-80E
5HLE-PDM-E
5HLE-PNM-D 72DBA1-3E 8CLE-100E
5HLE-PNM-E 72DBA1-40E 8HLE-100E
72DBA1-50E 8CLE-10E-D
5LCLS-12R
72DBA1-5E 8CLE-100E
5LCLS-18R
72DBA1-65E 8CLE-125E
5LCLS-24R
72DBA1-7E 8CLE-30E
5LCLS-2R
72DBA1-80E 8CLE-40E
5LCLS-3R
8CLE-150E
5LCLS-4R
8CLE-50E
5LCLS-5R
5LCLS-6R
5LCLS-9R
5NCLPT-.25E
5NCLPT-.5E
5NCLPT-.5E-A
5NCLPT-1E
5NCLPT-1E-A

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F

CA08101001E For more information visit: www.eaton.com


13-94 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Pricing

Table 13-81. Pricing (Continued) Pricing (Continued) Pricing (Continued)


Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $

8CLE-15E 8CX-10C 8HLE-PDM-D


8CLE-15E-D 8CX-12C 8HLE-PDM-D
8HLE-15E 8CX-15C 8HLE-PDM-E
8CLE-65E 8CX-18C 8HLE-PNM-E
8CLE-175E 8CX-20C 8NCLPT-1E
8CLE-80E 8CX-25C 8NCLPT-2E
8CLE-200E 8CX-3.5C 8NCLPT-4E
8CLE-20E 8CX-30C 8NCLPT-5E
8CLE-20E-D 8CX-35C 8NCLPT-8E
8HLE-20E 8CX-4.5C
8CX-40C 8RBA2-100E
8CLE2-100E 8RBA2-10E
8CLE2-150E 8CX-4C
8CX-6C 8RBA2-125E
8CLE-250E 8RBA2-150E
8CLE-25E 8CX-7C
8CX-8C 8RBA2-15E
8CLE-25E-D 8RBA2-200E
8HLE-25E 8CX-GDM-G 8RBA2-20E
8CLE-300E 8CX-GNM-G 8RBA2-25E
8CLE-30E 8CXN-100C 8RBA2-30E
8HLE-30E 8CXN-125C 8RBA2-40E
8CLE-350E 8CXN-150C 8RBA2-50E
8CLE-40E 8CXN-200C 8RBA2-65E
8HLE-40E 8CXN-250C 8RBA2-80E
8CXN-60C 8RBA2-DH
8CLE-50E
8HLE-50E 8DBA1-.5E 8RBA2-GDM
8DBA1-100E 8RBA2-GNM
8CLE-65E 8DBA1-10E 8RBA2-IDH
8HLE-65E 8DBA1-125E 8RBA2-INH
8CLE-80E 8DBA1-150E 8RBA2-ISHNT
8HLE-80E 8DBA1-15E 8RBA2-LBDH
13 8CLE-GDM-C
8DBA1-200E 8RBA2-NH
8DBA1-20E 8RBA2-PDM
8CLE-GDM-D
8DBA1-25E 8RBA2-PNM
8CLE-GDM-E
8DBA1-30E 8RBA2-SHNT
8CLE-GNM-C
8DBA1-3E 8RBA4-.5E
8CLE-GNM-D
8DBA1-40E 8RBA4-100E
8CLE-GNM-E
8DBA1-50E 8RBA4-10E
8CLE-PDM-C 8DBA1-5E 8RBA4-125E
8CLE-PDM-D 8DBA1-65E 8RBA4-150E
8CLE-PDM-E 8DBA1-7E 8RBA4-15E
8CLE-PNM-C 8DBA1-80E 8RBA4-200E
8CLE-PNM-D
8HLE-100E 8RBA4-20E
8CLE-PNM-E
8HLE-10E 8RBA4-250E
8CLPT-.5E 8HLE-125E 8RBA4-25E
8CLPT-10E 8HLE-150E 8RBA4-300E
8CLPT-3E 8HLE-15E 8RBA4-30E
8CLPT-5E 8HLE-175E 8RBA4-3E
8CLPT-GDM-A 8HLE-200E 8RBA4-400E
8CLPT-GDM-B 8HLE-20E 8RBA4-40E
8CLPT-GNM-A 8HLE-250E 8RBA4-50E
8CLPT-GNM-B 8HLE-25E 8RBA4-5E
8HLE-300E 8RBA4-65E
8CLPT-PDM-A 8HLE-30E 8RBA4-7E
8CLPT-PDM-B 8HLE-350E 8RBA4-80E
8CLPT-PNM-A 8HLE-40E
8CLPT-PNM-B 8RBA4-DH
8HLE-50E 8RBA4-GDM
8CLS-110 8HLE-65E 8RBA4-GNM
8CLS-125 8HLE-80E 8RBA4-IDH
8CLS-15 8HLE-GDM-D 8RBA4-INH
8CLS-150 8HLE-GDM-E 8RBA4-ISHNT
8CLS-200 8HLE-GNM-D 8RBA4-LBDH
8CLS-225 8HLE-GNM-E 8RBA4-NH
8CLS-30 8RBA4-PDM
8CLS-60 8RBA4-PNM
8CLS-70 8RBA4-SHNT
8CLS-90
8RBA8-GNM
8CLT-12 8RBA8-INH
8CLT-18 8RBA8-NH
8CLT-25 8RBA8-PNM
8CLT-30CL
8CLT-30CS
8CLT-45
8CLT-5
8CLT-8

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F

For more information visit: www.eaton.com CA08101001E


Power Breakers, Contactors & Fuses 13-95
Current Limiting Fuses
December 2008
Pricing

Table 13-81. Pricing (Continued) Pricing (Continued) Pricing (Continued)


Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $

8RBT2-100E CLS700-DUMMY DBU27-200E 


8RBT2-125E CLS-BAND DBU27-200K 
8RBT2-150E CX-DF DBU27-200SE 
8RBT2-200E CX-DL DBU27-20E 
8RBT2-20E CXN-CLMP DBU27-20K 
8RBT2-25E CX-NL DBU27-20SE 
8RBT2-30E DBU27-25E 
8RBT2-40E DBU17-100E  DBU27-25K 
8RBT2-50E DBU17-100K  DBU27-25SE 
8RBT2-65E DBU17-100SE 
DBU17-10E  DBU27-30E 
8RBT2-80E DBU27-30K 
DBU17-10K 
8RBT4-100E DBU17-125E  DBU27-30SE 
8RBT4-125E DBU17-125SE  DBU27-3K 
8RBT4-150E DBU17-12K  DBU27-40E 
8RBT4-200E DBU17-13E  DBU27-40K 
8RBT4-20E DBU17-140K  DBU27-40SE 
8RBT4-250E DBU17-150E  DBU27-50E 
8RBT4-25E DBU17-150SE  DBU27-50K 
8RBT4-300E DBU17-15E  DBU27-50SE 
8RBT4-30E DBU17-15K  DBU27-5E 
8RBT4-400E DBU17-15SE  DBU27-65E 
8RBT4-40E DBU17-175E  DBU27-65K 
8RBT4-50E DBU17-175SE  DBU27-65SE 
8RBT4-65E DBU27-6K 
8RBT4-80E DBU17-200E 
DBU17-200K  DBU27-7E 
8RDB2-DH DBU17-200SE  DBU27-80E 
8RDB2-HUM DBU17-20E  DBU27-80K 
8RDB2-HVM DBU17-20K  DBU27-80SE 
8RDB2-SHNT DBU17-20SE  DBU27-8K 
8RDB2-UM
8RDB2-VM
DBU17-25E  DBU38-100E 
13
DBU17-25K  DBU38-100K 
8RDB4-DH DBU17-25SE  DBU38-100SE 
8RDB4-HUM DBU17-30E  DBU38-10E 
8RDB4-HVM DBU17-30K  DBU38-10K 
8RDB4-SHNT DBU17-30SE  DBU38-125E 
8RDB4-UM DBU17-3K  DBU38-125SE 
8RDB4-VM DBU17-40E  DBU38-12K 
8RDB8-HUM DBU17-40K  DBU38-13E 
8RDB8-HVM DBU17-40SE  DBU38-140K 
8RDB8-UM DBU17-50E  DBU38-150E 
8RDB8-VM DBU17-50K  DBU38-150SE 
92DBA2-100E DBU17-50SE  DBU38-15E 
92DBA2-10E DBU17-5E  DBU38-15K 
92DBA2-125E DBU17-65E  DBU38-15SE 
92DBA2-150E DBU17-65K  DBU38-175E 
92DBA2-15E DBU17-65SE  DBU38-175SE 
92DBA2-200E DBU17-6K   Discount Symbol for DBU fuses is Y1-FE.
92DBA2-20E DBU17-7E 
92DBA2-25E DBU17-80E 
92DBA2-30E DBU17-80K 
92DBA2-3E DBU17-80SE 
92DBA2-40E DBU17-8K 
92DBA2-50E
92DBA2-5E DBU27-100E 
92DBA2-65E DBU27-100K 
92DBA2-7E DBU27-100SE 
92DBA2-80E DBU27-10E 
DBU27-10K 
CLE-DF-C DBU27-125E 
CLE-DF-D DBU27-125SE 
CLE-DF-E DBU27-12K 
CLE-DL-C DBU27-13E 
CLE-DL-D DBU27-140K 
CLE-DL-E DBU27-150E 
CLE-NL-C DBU27-150SE 
CLE-NLC-C DBU27-15E 
CLE-NLC-D DBU27-15K 
CLE-NLC-E DBU27-15SE 
CLE-NL-D DBU27-175E 
CLE-NL-E DBU27-175SE 
CLPT-DF
CLPT-DL
CLPT-NL
CLPT-NLC
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . Y1-F

CA08101001E For more information visit: www.eaton.com


13-96 Power Breakers, Contactors & Fuses
Current Limiting Fuses
December 2008
Pricing

Table 13-81. Pricing (Continued)


Catalog Number Price U.S. $

DBU38-200E 
DBU38-200K 
DBU38-200SE 
DBU38-20E 
DBU38-20K 
DBU38-20SE 
DBU38-25E 
DBU38-25K 
DBU38-25SE 
DBU38-30E 
DBU38-30K 
DBU38-30SE 
DBU38-3K 
DBU38-40E 
DBU38-40K 
DBU38-40SE 
DBU38-50E 
DBU38-50K 
DBU38-50SE 
DBU38-5E 
DBU38-65E 
DBU38-65K 
DBU38-65SE 
DBU38-6K 
DBU38-7E 
DBU38-80E 
DBU38-80K 
DBU38-80SE 
DBU38-8K 
13 DBU-EFID 
DBU-EFOD 
DBU-MFLR 
RBA2-COND
RBA2-FLTR
RBA2-IND
RBA4-COND
RBA4-FLTR
RBA4-FLTR-HC
RBA4-IND
RDB2-UL
RDB2-VL
RDB4-UL
RDB4-VL
RDB8-UL
RDB8-VL
 Discount Symbol for DBU fuses is Y1-FE.

CSA is a registered trademark of the Canadian Stan-


dards Association. ISO is the registered trademark and
sole property of the International Organization for
Standardization. NEMA is the registered trademark and
service mark of the National Electrical Manufacturers
Association. UL is a registered trademark of Underwrit-
ers Laboratories Inc. Cutler-Hammer is a federally
registered trademark of Eaton Corporation. Kirk is
a registered trademark of the Kirk Key Interlock
Company LLC.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . Y1-F

For more information visit: www.eaton.com CA08101001E