You are on page 1of 34

SmartLine

Technical Information

STR700 SmartLine Remote Diaphragm Seals


Specification 34-ST-03-104

Introduction

Part of the SmartLine® family of products, the STR700 is


suitable for monitoring, control and data acquisition.
STR700 products feature piezoresistive sensor
technology combining pressure sensing with on chip
temperature compensation capabilities providing high
accuracy, stability and performance over a wide range of
application pressures and temperatures.
The SmartLine family is also fully tested and compliant
with Experion ® PKS providing the highest level of
compatibility assurance and integration capabilities.
SmartLine easily meets the most demanding application
needs for pressure measurement applications

Best in Class Transmitter Features:


 Accuracies up to 0.075% Span standard Figure 1 – STR700 Remote Diaphragm Seal Unit
 Automatic static pressure & temperature
compensation
Typical Diaphragm Seal applications
 Rangeability up to 100:1
 High Process Temperatures
 Local display capabilities  Viscous or Suspended Solids
 External zero, span, & configuration capability  Highly Corrosive Process Materials
 Polarity insensitive electrical connections  Sanitary Applications
 Comprehensive on-board diagnostic capabilities  Applications with Hydrogen Permeation Possibilities
 Integral Dual Seal design for highest safety based on  Level Applications with Maintenance Intensive Wet
ANSI/NFPA 70-202 and ANSI/ISA 12.27.0 Legs
 World class overpressure protection  Applications requiring remote Transmitter Mounting
 Full compliance to SIL 2/3 requirements.  Tank Applications with Density or Interface
 Modular design characteristics Measurements

Remote Seal/Transmitter Span & Range Limits: Communications/Output Options:

Model URL LRL Max Span Min Span  Honeywell Digitally Enhanced (DE)
psid (bar) psid (bar) psid (bar) psid (bar)
 HART ® (version 7.0)
STR73D 100 (7.0) -100 (-7.0) 100 (7.0) 0.9 (0.062)
 FOUNDATION™ Fieldbus
Model psig (bar) psig (bar) psig (bar) psig (bar)
All transmitters are available with the above listed
STR74G 500 (35.0) -14.7 (-1.0) 500 (35.0) 5 (0.35)
communications protocols.
2 STR700 Smart Pressure Transmitter

Description Configuration Tools


The SmartLine family pressure transmitters are designed External Three Button Configuration Option
around a high performance piezo-resistive sensor. This Suitable for all electrical and environmental requirements,
one sensor actually integrates multiple sensors linking SmartLine offers the ability to configure the transmitter
process pressure measurement with on-board static and display via three externally accessible buttons when
pressure (DP Models) and temperature compensation a display option is selected. Zero/span capabilities are
measurements. This level of performance allows the ST also optionally available via these buttons with or without
700 to replace most competitive transmitters available selection of the display option.
today.
Internal Two Button Configuration Option
Indication/Display Option The Simple display has two buttons that can be used for
Basic configuration such as re ranging, PV Engineering
The ST 700 modular design accommodates a basic
unit setting, Zero/Span settings and Loop testing and
alphanumeric LCD display. calibration functions.
Basic Alphanumeric LCD Display Features Hand Held Configuration
o Modular (may be added or removed in the field)
SmartLine transmitters feature two-way communication and
o 0, 90,180, & 270 degree position adjustments
configuration capability between the operator and the
o Configurable (HART only) and standard (Pa, KPa,
transmitter. This is accomplished via Honeywell’s field-
MPa, KGcm2, Torr, ATM, inH2O, mH2O, bar,
rated Multiple Communication Configurator (MCT404).
mbar, inH2O, inHG, FTH2O, mmH2O, mm HG, &
The MCT404 is capable of field configuring DE and HART
psi) measurement units
Devices and can also be ordered for use in intrinsically safe
o 2 Lines 16 Characters (4.13H x 1.83W mm)
environments. All Honeywell transmitters are designed and
o Square root output indication (√) tested for compliance with the offered communication
protocols and are designed to operate with any properly
Simple LCD Display Features validated hand held configuration device.
o Modular (may be added or removed in the field)
o Supports HART protocol variant Personal Computer Configuration
o 0, 90,180, & 270 degree position adjustments Honeywell’s SCT 3000 Configuration Toolkit provides an
o Configurable (HART only) and standard (Pa, KPa, easy way to configure Digitally Enhanced (DE) instruments
MPa, KGcm2, Torr, ATM, inH2O, mH2O, bar, mbar, using a personal computer as the configuration interface.
inH2O, inHG, FTH2O, mmH2O, mm HG, & psi) Field Device Manager (FDM) Software and FDM Express
measurement units. are also available for managing HART & Fieldbus device
configurations.
o Supports Flow engineering units
o 2 Lines 6 digits PV (9.95H x 4.20W mm) 8 Modular Design
Characters
To help contain maintenance & inventory costs, all ST 700
o Square root output indication (√) and Write protect
transmitters are modular in design supporting the user’s
Indication
ability to replace meter bodies, add indicators or change
o Built in Basic Device Configuration through Internal
electronic modules without affecting overall performance or
Buttons – Range/Engineering Unit/Loop Test /Loop
Calibration/Zero /Span Setting approval body certifications. Each meter body is uniquely
characterized to provide in-tolerance performance over a wide
Diagnostics range of application variations in temperature and pressure
SmartLine transmitters all offer digitally accessible and due to the Honeywell advanced interface, electronic
diagnostics which aid in providing advanced warning of modules may be swapped with any electronics module
possible failure events minimizing unplanned shutdowns, without losing in-tolerance performance characteristics.
providing lower overall operational costs Modular Features
System Integration o Meter body replacement
o SmartLine communications protocols all meet the o Exchange/replace electronics/comms modules*
most current published standards for o Add or remove integral indicator*
HART/DE/Fieldbus. o Add or remove lightning protection (terminal
o Integration with Honeywell’s Experion PKS offers the connection)*
following unique advantages. * Field replaceable in all electrical environments (including
o Tamper reporting IS) except flameproof without violating agency approvals.
o FDM Plant Area Views with Health summaries With no performance effects, Honeywell’s unique
o All ST 700 units are Experion tested to provide modularity results in lower inventory needs and lower
the highest level of compatibility assurance overall operating costs.
STR700 Smart Pressure Transmitter 3

Performance Specifications

Reference Accuracy (conformance to +/-3 Sigma)

Maximum Reference
Turndown Accuracy1,2
Model URL LRL Min Span Ratio (% Span)
STR73D 100 psid/7.0 bar -100 psi/-7.0bar 0.9 psi/.062bar 100:1 0.075
STR74G 500 psi/35 bar -14.7 psi/-1.0 bar 5 psi/.035 bar 100:1 0.075
Zero and span may be set anywhere within the listed (URL/LRL) range limits

Accuracy1,2
(% of Span) Temperature Effect 3
o
(% Span/50 F)

Turn down C F
A B D E
Model URL greater than psi(bar) psi(bar)

STR73D 100 psi/7.0 bar 27.7:1 0.0250 0.050 3.61 (0.249) 0.028 1.200 7.2 (0.50)
STR74G 500 psig/35 bar 25:1 0.0250 0.050 20 (1.4)
Turn Down Effect Temp Effect
  C    F 
 A  B   D  E  
  Span    Span 
% Span % Span per 28oC (50oF)

Accuracy at Specified Span, Temperature and Static Pressure: (conformance to +/-3 Sigma)

Total Performance (% of Span):

Total Performance = +/- √( Accuracy)2 + (Temp Effect)2

Total Performance Examples: (5:1 Turndown, up to 50 oF shift)


STR73D @ 20 psid: 1.03% of span

Typical Calibration Frequency:


Calibration verification is recommended every four (4) years

Notes:
1.Terrninal Based Accuracy – Includes combined effects of linearity, hysteresis, and repeatability. Analog output adds 0.005% of span.
2. For zero based spans and reference conditions of 25oC (77oF), 0 psi static pressure for DP, >= 0 psia for GP, 10 to 55% R.H, and
316Stainless Steel barrier diaphragms
3. Specification applies to transmitter with 2 balanced remote seals. Apply a factor of 1.5 for temperature effect of capillary lengths greater
than 10 feet.
4 STR700 Smart Pressure Transmitter

Operating Conditions – All Models


Reference Rated Condition Operative Limits Transportation and
Parameter Condition (at Storage
zero static)
C F C F C F C F
Ambient Temperature1 25±1 77±2 - - - - -55 to 90 -67 to 194
Humidity %RH 10 to 55 0 to 100 0 to 100 0 to 100
Vacuum Region, Minimum
Pressure
mmHg absolute Atmospheric (See Figure 4 for vacuum limitation)

Supply Voltage, Current, and 10.8 to 42.4 Vdc at terminals (IS versions limited to 30 Vdc)
Load Resistance 0 to 1,440 ohms (as shown in Figure 2)
Maximum Allowable MAWP is minimum of Body Rating or Seal Rating (See Model Selection Guide for Seal
Working Pressure (MAWP)4 MAWP)
(ST 700 products are rated to Body MAWP
Maximum Allowable Working
Pressure. MAWP depends on
STR73D 750 psig (51.7 bar) Bolted Process Heads
Approval Agency and transmitter STR74G 500 psig (35 bar)
materials of construction.)

1
Ambient Temperature Limit is a function of Process Interface Temperature. (See Figures 3 & 4)
LCD Display operating temperature -20C to +70C . Storage temperature -30C to 80C
4
Consult factory for MAWP of ST 700 transmitters with CRN approval.

Figure 2- Supply voltage and loop resistance

200 185
180 165
160 140
Maximum Ambient 140
Temperature (°F)
120
100
80
60 Figure 3- Ambient temperature Limits
40
20
0
200 350 450
Process Interface Temperature (°F)
STR700 Smart Pressure Transmitter 5

Figure 4 - STR700 Remote Seals operable limits for pressure vs. temperature
6 STR700 Smart Pressure Transmitter

Performance Under Rated Conditions – All Models


Parameter Description
Analog Output Two-wire, 4 to 20 mA (HART & DE Transmitters only)
Digital Communications: Honeywell DE, HART 7 protocol or FOUNDATION Fieldbus ITK 6.0.1 compliant
All transmitters, irrespective of protocol have polarity insensitive connection.
HART & DE Output Failure Modes Honeywell Standard: NAMUR NE 43 Compliance:
(NAMUR for DE Units requires Normal Limits: 3.8 – 20.8 mA 3.8 – 20.5 mA
selecting display and configuration Failure Mode: ≤ 3.6 mA and ≥ 21.0 mA ≤ 3.6 mA and ≥ 21.0 mA
buttons or factory configuration)
Supply Voltage Effect 0.005% span per volt.

Transmitter Turn on Time HART or DE: 2.5 sec. Foundation Fieldbus: Host dependant
(includes power up & test algorithms)

Damping Time Constant HART: Adjustable from 0 to 32 seconds in 0.1 increments. Default: 0.50 seconds
DE: Discrete values 0, .16, .32, .48, 1, 2, 4, 8, 16, 32 seconds. Default: 0.48 seconds
Electromagnetic Compatibility IEC 61326-3-1
Lightning Protection Option Leakage Current: 10uA max @ 42.4VDC 93C
Impulse rating: 8/20uS 5000A (>10 strikes) 10000A (1 strike min.)
10/1000uS 200A (> 300 strikes)

Materials Specifications (see model selection guide for availability/restrictions with various models)
Parameter Description
Process Interface See Model Selection Guide for Material Options for desired seal type.
Seal Barrier Diaphragm 316L Stainless Steel, Monel®, Hastelloy® C, Tantalum
Seal Gasket Materials Klinger C-4401 (non-asbestos) Grafoil®, Teflon®, Gylon 3510®
Mounting Bracket Carbon Steel (Zinc-Chromate plated) or 304 Stainless Steel or 316 Stainless Steel.
Silicone 200 S.G. @ 25°C = 0.94
CTFE (Chlorotrifluoroethylene) S.G. @ 25°C = 1.89
Fill Fluid (Meter Body)
Silicone 704 S.G. @ 25°C = 1.07
NEOBEE M-20® S.G. @ 25°C = 0.93
Silicone 200 S.G. @ 25°C = 0.94
CTFE (Chlorotrifluoroethylene) S.G. @ 25°C = 1.89
Fill Fluid (Secondary) Silicone 704 S.G. @ 25°C = 1.07
Syltherm 800® S.G. @ 25°C = 0.90
NEOBEE M-20® S.G. @ 25°C = 0.93
Pure Polyester Powder Coated Low Copper (<0.4%)-Aluminum. Meets NEMA 4X, IP66, & P67.
Electronic Housing
All stainless steel housing is optional.
Material: Armored Stainless Steel or PVC Coated Armored Stainless Steel.
Length: 5, 10, 15, 20, 25, and 35 feet (1.5, 3, 4.6, 6.1, 7.5, and 10.7 meters).
A 2 inch (51 millimeter) S.S. close-coupled nipple is also available. See Model Selection Guide.
Refer to Figure 5 for guide to maximum capillary length vs. diaphragm diameter.Note: The
Capillary Tubing
minimum span is the higher of the higher of the value from the table above or the value
defined under the Performance Conditions for the range transmitter.

Figure 5
Wiring Accepts up to 16 AWG (1.5 mm diameter)
Mounting See Figure 6
Dimensions Transmitter: See Figures 7a and 7b. Seal: See Figure 8 through Figure 15
Net Weight Transmitter: 8.3 pounds (3.8 Kg). With Aluminum Housing. Total weight is dependent on seal

NOTE: Pressure transmitters that are part of safety equipment for the protection of piping (systems) or vessel(s) from exceeding allowable
pressure limits, (equipment with safety functions in accordance with Pressure Equipment Directive 97/23/EC article 1, 2.1.3), require
separate examination.
STR700 Smart Pressure Transmitter 7

Minimum recommended span for STR73D Transmitter with two Seals


Diaphragm Capillary Length (Feet) Maximum Capillary
Size (Inch) 5 10 15 20 25 35 Length (Feet)
1.9 15 psi 20 psi 25 psi - - - 15
2.4 5.4 psi 7.2 psi 9.0 psi 10.8 psi 12.6 psi 14.4 psi 35
2.9 1.8 psi 2.7 psi 3.6 psi 4.5 psi 5.4 psi 7.2 psi 35
3.5 0.9 psi 0.9 psi 0.9 psi 1.0 psi 1.2 psi 1.4 psi 35
4.1 0.9 psi 0.9 psi 0.9 psi 0.9 psi 0.9 psi 1.1 psi 35

Minimum recommended span for STR74G and STR73D Transmitter with one Remote Seal
Diaphragm Direct Capillary Length (Feet) Maximum
Size (Inch) Mount 5 10 15 20 25 35 Capillary
Length (Feet)
1.9 25 psi 30 psi 40 psi 50 psi - - - Maximum
15
2.4 10 psi 15 psi 20 psi 25 psi 30 psi 35 psi 50 psi 35
2.9 8 psi 9 psi 10 psi 11 psi 12 psi 13 psi 15 psi 35
3.5 2 psi 2 psi 3 psi 4 psi 5 psi 6 psi 8 psi 35
4.1 0.9 psi 0.9 psi 1 psi 2 psi 3 psi 3.5 psi 5 psi 35
Note: The minimum span is the higher of the higher of the value from the table above or the value defined under the
Performance Conditions for the range transmitter.

Figure 5– Typical Maximum capillary length and diaphragm size chart

Figure 6 - STR700 transmitter with remote diaphragm seals shown mounted on a tank
8 STR700 Smart Pressure Transmitter

Reference Dimensions Horizontal Mounting


STR700 Smart Pressure Transmitter 9

Reference Dimensions Horizontal Mounting (cont’d)

Figure 7 — Approximate horizontal mounting dimensions for Remote Seal Transmitter

Reference Dimensions Vertical Mounting


10 STR700 Smart Pressure Transmitter

Reference Dimensions Vertical Mounting (cont’d)

Figure 8 — Approximate vertical mounting dimensions for Remote Seal Transmitter


STR700 Smart Pressure Transmitter 11

Reference Dimensions (cont’d)

Flush Flanged Seal Dimensions

Figure A

Figure B

Figure C Figure D

Figure 9 - Seal Dimensions (Flush Flanged)


12 STR700 Smart Pressure Transmitter

Reference Dimensions (cont’d)

Flush Flanged Seal with Lower

Flush Flanged Seal with Lower


Flush Flanged Seal with Lower Note: 0.90 dimension is 0.70 for 4.1” Dia Diaphragm

Figure 10- Seal Dimension (Flush Flanged)


STR700 Smart Pressure Transmitter 13

Reference Dimensions (cont’d)


Flanged Seal with Extended Diaphragm

Figure 11 — Seal Dimensions (Extended Diaphragms)

Pancake Seal

Figure 12 — Seal Dimensions (Pancake)


Chemical Tee “Taylor Wedge” Seal

Figure 13 — Seal Dimensions (Chemical TEE “Taylor Wedge” Seals


14 STR700 Smart Pressure Transmitter

Seal with Threaded Process Connection

Figure 14— Seal Dimensions (Threaded Process Connection Seals)

Sanitary Seal

Figure 15— Seal Dimensions (Sanitary Seals)


STR700 Smart Pressure Transmitter 15

Saddle Seal

Figure 16— Seal Dimensions (3” Saddle Seal)

Figure 17— Seal Dimensions (4” Saddle Seal)

Calibration Ring

Figure 18— Calibration Ring


16 STR700 Smart Pressure Transmitter

Communications Protocols & Diagnostics

HART Protocol Software Download


Version: Utilizes Class-3 of the Common Software Download
HART 7 procedure as per FF-883 which allows the field devices of
any manufacturer to receive software upgrades from any
Power Supply
host.
Voltage: 10.8 to 42.4Vdc at terminals
Load: Maximum 1440 ohms. See Figure 2. Honeywell Digitally Enhanced (DE)
Minimum Load: 0 ohms. (For handheld communications a DE is a Honeywell proprietary protocol which provides
minimum load of 250 ohms is required) digital communications between Honeywell DE enabled
Foundation Fieldbus (FF) field devices and Hosts.

Power Supply Requirements Power Supply


Voltage: 9.0 to 32.0Vdc at terminals Voltage: 10.8 to 42.4Vdc at terminals
Steady State Current: 17.6mAdc Load: Maximum 1440 ohms See .
Software Download Current: 27.4mAdc Standard Diagnostics
Available Function Blocks ST 700 top level diagnostics are reported as either critical
or non-critical and readable via the DD/DTM tools or
Block Type Qty Execution Time
integral display as shown below.
Resource 1 n/a Critical Diagnostics
Transducer 1 n/a HART DD/DTM Tools Basic Display Simple Display
Electronic Module Electronics module fault Fault Comm El
Diagnostic 1 n/a DAC Failure
Analog Input 1* 30 ms Meter Body NVM Meter Body fault Fault Mtrbody
Corrupt
PID w/Autotune 1 45 ms Config. Data Corrupt Electronics module fault Fault Comm El
Integrator 1 30 ms Electronic Module Electronics module fault Fault Comm El
Diag Failure
Signal Char (SC) 1 30 ms
Meter Body Critical Meter Body fault Fault Mtrbody
LCD Display 1 n/a Failure
Sensor Comms Meter Body Comm fault Fault Mbd Com
Flow Block 1 30 ms Timeout
Input Selector 1 30 ms Non-Critical Diagnostics
Arithmetic 1 30 ms HART DD/DTM Tools
* AI block may have two (2) additional instantiations. Display Failure
All available function blocks adhere to FOUNDATION Electronic Module Comm Failure
Fieldbus standards. PID blocks support ideal & robust PID Meter Body Excess Correct
algorithms with full implementation of Auto-tuning. Sensor Over Temperature
Fixed Current Mode
Link Active Scheduler
PV Out of Range
Transmitters can perform as a backup Link Active
No Factory Calibration
Scheduler and take over when the host is disconnected.
No DAC Compensation
Acting as a LAS, the device ensures scheduled data
LRV Set Error – Zero Config. Button
transfers typically used for the regular, cyclic transfer of
URV Set Error – Zero Config. Button
control loop data between devices on the Fieldbus.
AO Out of Range
Number of Devices/Segment Loop Current Noise
Entity IS model: 6 devices/segment Meter Body Unreliable Comm

Schedule Entries Tamper Alarm,

18 maximum schedule entries No DAC Calibration


Sensor Supply Voltage Low
Number of VCR’s: 24 max
Refer to ST 700 manuals for additional level diagnostic
Compliance Testing: Tested according to ITK 6.0.1
information.
STR700 Smart Pressure Transmitter 17

Approval Certifications:

COMM. FIELD AMBIENT TEMP


AGENCY TYPE OF PROTECTION
OPTION PARAMETERS (Ta)

Explosionproof:
Class I, Division 1, Groups A, B, C, D;
Dust Ignition Proof:
T5: -50 ºC to 85ºC
Class II, III, Division 1, Groups E, F, G; T4 All Note 1
T6: -50 ºC to 65ºC
Class l, Zone 0/1, AEx d IIC Ga/Gb
Class ll, Zone 21, AEx tb IIIC Db T 95oC
Intrinsically Safe: 4-20 mA / DE/
Class I, II, III, Division 1, Groups A, B, C, Note 2a -50 ºC to 70ºC
HART
D, E, F, G: T4
FM ApprovalsTM
Class l, Zone 0, AEx ia IIC Ga T4
Foundation
Note 2b -50 ºC to 70ºC
Fieldbus
FISCO Field Device (Only for FF Option)
Ex ia IIC T4
Nonincendive:
Class I, Division 2, Groups A, B, C, D 4-20 mA / DE/
locations, HART/ Foundation Note 1 -50 ºC to 85ºC
Fieldbus
Class l, Zone 2, AEx nA IIC Gc T4
Enclosure: Type 4X/ IP66/ IP67 All All -
Explosion Proof:
Class I, Division 1, Groups A, B, C, D;
Dust Ignition Proof:
T5: -50 ºC to 85ºC
Class II, III, Division 1, Groups E, F, G; All Note 1
T6: -50 ºC to 65ºC
Ex d IIC Ga
Ex tb IIIC Db T 95oC
Intrinsically Safe:
Class I, II, III, Division 1, Groups A, B, C, 4-20 mA / DE/
Canadian Note 2a -50 ºC to 70ºC
Standards D, E, F, G; T4 HART
Association
(CSA) Ex ia IIC Ga T4
Foundation
Note 2b -50 ºC to 70ºC
FISCO Field Device (Only for FF Option) Fieldbus
Ex ia IIC T4
Nonincendive:
Class I, Division 2, Groups A, B, C, D; T4 4-20 mA / DE/
HART/ Foundation Note 1 -50 ºC to 85ºC
Fieldbus
Ex nA IIC Gc T4
Enclosure: Type 4X/ IP66/ IP67 All All -
18 STR700 Smart Pressure Transmitter

Approval Certifications: (Continued)

Flameproof:
T5: -50 ºC to 85ºC
II 1/2 G Ex d IIC Ga/Gb All Note 1
T6: -50 ºC to 65ºC
II 2 D Ex tb IIIC Db T 95oC
Intrinsically Safe: 4-20 mA / DE/
Note 2a -50 ºC to 70ºC
II 1 G Ex ia IIC Ga T4 HART

ATEX FISCO Field Device (Only for FF Option) Foundation -50 ºC to 70ºC
Note 2b
Fieldbus
Ex ia IIC T4
4-20 mA / DE/
Nonincendive: HART/
Foundation Note 1 -50 ºC to 85ºC
II 3 G Ex nA IIC Gc T4
Fieldbus

Enclosure: IP66/ IP67 All All -


Flameproof :
T5: -50 ºC to 85ºC
Ex d IIC Ga/Gb T4 All Note 1
T6: -50 ºC to 65ºC
Ex tb IIIC Db T 95oC
Intrinsically Safe: 4-20 mA / DE/
Note 2a -50 ºC to 70ºC
Ex ia IIC Ga T4 HART
IECEx
(World) FISCO Field Device (Only for FF Option) Foundation
Note 2b -50 ºC to 70ºC
Fieldbus
Ex ia IIC T4
Nonincendive: 4-20 mA / DE/
HART/
Ex nA IIC Gc T4 Foundation Note 1 -50 ºC to 85ºC
Fieldbus
Enclosure: IP66/ IP67 All All -
Flameproof :
Ex d IIC Ga/Gb T4 All Note 1 -50 ºC to 85ºC
Ex tb IIIC Db T 95oC
Intrinsically Safe: 4-20 mA / DE/
Note 2a -50 ºC to 70ºC
Ex ia IIC Ga T4 HART
SAEx
(South Africa) FISCO Field Device (Only for FF Option) Foundation
Note 2b -50 ºC to 70ºC
Fieldbus
Ex ia IIC T4
Nonincendive: 4-20 mA / DE/
HART/
Ex nA IIC Gc T4 Foundation Note 1 -50 ºC to 85ºC
Fieldbus

Enclosure: IP66/ IP67 All All -


Flameproof:
Ex d IIC Ga/ Gb T4 All Note 1 -50 ºC to 85ºC
Ex tb IIIC Db T 95oC
Intrinsically Safe: 4-20 mA / DE/
Note 2a -50 ºC to 70ºC
INMETRO Ex ia IIC Ga T4 HART

(Brazil) FISCO Field Device (Only for FF Option) Foundation


Fieldbus
Note 2b -50 ºC to 70ºC
Ex ia IIC T4
Nonincendive: 4-20 mA / DE/
HART/
Ex nA IIC Gc T4 Foundation Note 1 -50 ºC to 85ºC
Fieldbus

Enclosure : IP 66/67 All All -


STR700 Smart Pressure Transmitter 19

Approval Certifications: (Continued)


Flameproof:
Ex d IIC Ga/Gb T4 All Note 1 -50 ºC to 85ºC
Ex tb IIIC Db T 85oC
Intrinsically Safe: 4-20 mA / DE/
Note 2a -50 ºC to 70ºC
Ex ia IIC Ga T4 HART
NEPSI
(China) FISCO Field Device (Only for FF Option) Foundation
Note 2b -50 ºC to 70ºC
Fieldbus
Ex ia IIC T4
Nonincendive: 4-20 mA / DE/
HART/
Ex nA IIC Gc T4 Foundation Note 1 -50 ºC to 85ºC
Fieldbus

Enclosure : IP 66/67 All All -


Flameproof:
1 Ex d IIC Ga/Gb T4 All Note 1 -50 ºC to 85ºC
Ex tb IIIC Db T 85oC
Intrinsically Safe: 4-20 mA / DE/
GOST Note 2a -50 ºC to 70ºC
0 Ex ia IIC Ga T4 HART

FISCO Field Device (Only for FF Option) Foundation


Note 2b -50 ºC to 70ºC
Fieldbus
Ex ia IIC T4
Enclosure : IP 66/67 All All
Notes:
1. Operating Parameters:
Voltage= 11 to 42 V DC Current= 4-20 mA Normal
= 10 to 30 V (FF) = 30 mA (FF)
2. Intrinsically Safe Entity Parameters
a. Analog/ DE/ HART Entity Values:
Vmax= Ui = 30V Imax= Ii= 105mA Ci = 4.2nF Li =984 uH Pi =0.9W
Transmitter with Terminal Block Revision E or Later
Vmax= Ui = 30V Imax= Ii= 225mA Ci = 4.2nF Li = 0 Pi =0.9W
Note : Transmitter with Terminal Block Revision E or later
The revision is on the label that is on the module. There will be two lines of text on the label:
 First is the Module Part #: 50049839-001 or 50049839-002
 Second line has the supplier information, along with the REVISION:
XXXXXXX-EXXXX, THE “X” is production related, THE POSITION of the “E” IS THE REVISION.

b. Foundation Fieldbus- Entity Values


Vmax= Ui = 30V Imax= Ii= 180mA Ci = 0nF Li = 984 uH Pi =1W

Transmitter with Terminal Block Revision F or Later


Vmax= Ui = 30V Imax= Ii= 225mA Ci =0nF Li = 0 Pi =1 W

FISCO Field Device Imax= Ii= 380 mA Ci = 0nF Li = 0 Pi =5.32 W


Vmax= Ui = 17.5V
Note : Transmitter with Terminal Block Revision F or later
The revision is on the label that is on the module. There will be two lines of text on the label:
 First is the Module Part #: 50049839-003 or 50049839-004
 Second line has the supplier information, along with the REVISION:
XXXXXXX-EXXXX, THE “X” is production related, THE POSITION of the “E” IS THE REVISION.
20 STR700 Smart Pressure Transmitter

Approval Certifications: (Continued)


This certificate defines the certifications covered for the SmartLine Pressure Transmitter family of
products, including the SMV SmartLine Multivariable Transmitter. It represents the compilation of
the five certificates Honeywell currently has covering the certification of these products into marine
applications.

American Bureau of Shipping (ABS) - 2009 Steel Vessel Rules 1-1-4/3.7, 4-6-2/5.15, 4-8-3/13 &
13.5, 4-8-4/27.5.1, 4-9-7/13. Certificate number: 04-HS417416-PDA

Marine Certificates Bureau Veritas (BV) - Product Code: 389:1H. Certificate number: 12660/B0 BV

Det Norske Veritas (DNV) - Location Classes: Temperature D, Humidity B, Vibration A, EMC B,
Enclosure C. For salt spray exposure; enclosure of 316 SST or 2-part epoxy protection with 316
SST bolts to be applied. Certificate number: A-11476

Korean Register of Shipping (KR) - Certificate number: LOX17743-AE001

Lloyd's Register (LR) - Certificate number: 02/60001(E1) & (E2)

SIL 2/3 Certification IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use according to EXIDA and TÜV
Nord Sys Tec GmbH & Co. KG under the following standards: IEC61508-1: 2010; IEC 61508-2:
2010; IEC61508-3: 2010.

Other Certification Options


Materials
o NACE MRO175, MRO103, ISO15156
STR700 Smart Pressure Transmitter 21

Application Data

Liquid Level: Closed Tank

Determine the minimum and maximum pressure Max


differentials to be measured (Figure 16). Level LP

PMin = (SGp x a) - (SGf x d)


= LRV when HP at bottom of tank
= –URV when LP at bottom of tank b
PMax = (SGp x b) - (SGf x d)
= URV when HP at bottom of tank Min
Level HP
= –LRV when LP at bottom of tank a
Where:
Transmitter above datum
minimum level at 4mA
maximum level at 20 mA

a = distance between bottom tap and


minimum level Max LP
Level
b = distance between bottom tap and
maximum level

d = distance between taps b

SGf = Specific Gravity of capillary Min


Level HP
fill fluid (See Page 6 “Material a
Specifications” for values.)
Transmitter at datum
SGp = Specific Gravity of process fluid

Max LP
Level

b
Min
Level a HP

Transmitter below datum

24253
Figure 16—Closed tank liquid level measurement distance
22 STR700 Smart Pressure Transmitter

Application Data (Cont’d)


Density or Interface*
Calculate the minimum and maximum pressure
differentials to be measured (Figure 19).

Pmin = (SGmin – SGf) x (d);


minimum density, 4mA output LP

Pmax = (SGmax – SGf) x (d);


maximum density, 20mA output

Where:

d = distance between the taps


HP
SGmax = maximum Specific Gravity
24257
SGmin = minimum Specific Gravity

SGf = Specific Gravity of capillary fill fluid (See


Figure 19- Density, direct acting transmitter
Page 6 “Material Specifications” for values.) configuration

Seal Configurations

Figure 20—Flush Flange Seals


Flush Flange Seals can be used with differential, gauge Figure 22—Pancake Seals
and absolute pressure transmitters and are available with Pancake Seals can be used with differential, gauge and
3” ANSI Class 150, ANSI Class 300 and DIN DN80-PN40 absolute pressure transmitters and are available with 3”
process connections. Flush flange seals can also be ANSI Class 150, 300 and 600 process connections.
provided with Lowers. Lowers are essentially calibration
rings, which allow flushing connections if needed.

Figure 21 — Flange Seal with Extended Diaphragm


Figure 23— Chemical Tee “Taylor” Wedge
Flange Seal with Extended Diaphragm can be used with Chemical Tee “Taylor” Wedge can be used with
differential, gauge and absolute pressure transmitters and differential pressure transmitters and are available with
are available with 3” and 4” ANSI Class 150, ANSI Class Taylor Wedge 5” O.D. process connection.
300, DIN DN80-PN40 and DIN DN100-PN40 process
connections. 2”, 4” and 6” extension lengths are available
STR700 Smart Pressure Transmitter 23

Seal Configurations (cont’d)

Figure 24— Seals with Threaded Process Figure 28 — Stainless Steel Armor and PVC Coated
Connections Stainless Steel Armor Capillaries
Seals with Threaded Process Connections can be used Stainless Steel Armor and PVC Coated Stainless Steel
with differential, gauge and absolute pressure Armor Capillaries are available with Honeywell Remote
transmitters and are available with ½”, ¾” and 1” NPT Seal Solutions.
Female process connections.

Figure 29 — 2” Stainless Steel Nipples


Figure 25 — Sanitary Seals
2” Stainless Steel Nipples are available for Close-
Sanitary Seals can be used with differential, gauge and Coupled remote seal solutions
absolute pressure transmitters and are available with 3”
and 4” Tri-Clover-Tri-Clamp process connections.

Figure 26— Saddle Seals


Figure 30 — Welded Meter Body for All-Welded
Saddle Seals can be used with differential, gauge and Remote Seal Solution
absolute pressure transmitters and are available with 3” Welded Meter Body for All-Welded Remote Seal Solution.
and 4” (6 bolt or 8 bolt designs) process connections. The welded ST 700 meter body is an important part of an
All-Welded Remote Seal Solution, which is commonly
used in Vacuum applications.

Figure 27 — Calibration Rings


Calibration Rings are available with Flush Flange Seals
and Pancake Seals. Flushing ports (1/4” or ½”) are
available with calibration rings.
24 STR700 Smart Pressure Transmitter

Model Selection Guide


Model Selection Guides are subject to change and are inserted into the specifications as guidance only.
Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published at:
www.honeywellprocess.com/en-US/pages/default.aspx

Model STR700
(DP, GP) Remote Seals
Model Selection Guide
34-ST-16-104 Issue 15

Instructions
● Select the desired Key Number. The arrow to the right marks the selection available.
● Make selections from each Table (I, II and IX) using the column below the proper arrow .
● A ( ●) denotes unrestricted availability. A letter denotes restricted availability.
● Restrictions follow Table IX.

Key Number I II III IV V VI VII VIII IX


STR7 _ _ - _______ - _________ - _ - ___ - ___ - _ - ____ - __,__ + 0000

KEY NUMBER URL LRL Max Span Min Span Units Selection Availability

Measurem ent 100 (7) -100 (-7) 100 (7) 0.9 (0.062) psi (bar) STR73D
Range Std Accuracy 500 (35) 500 (35) 5 (0.35) STR74G
-14.7 (-1.0) psi (bar)
Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.

TABLE I Description Selection


1 Remote Seal (High Side) 1______ ● ●
a. Number of
2 Remote Seals 2______ ●
Seals
1 Remote Seal (Low Side) 3______ ●
Silicone Oil 200 _1_____ ● ●
b. Primary Fill
Fluorinated Oil CTFE _2_____ 2 2
Fluid
Silicone Oil 704 _3_____ ● ●
(Meter body)
NEOBEE® M-20 11 _4_____ ● ●
c. Construction Non-Wetted Adapter Head Materials
316 SS Bonnet _ _ A_ _ _ _ ●
In-Line Gauge
316 SS Bonnet for Close-Couple __B____ 3
316 SS (bolt-on heads) __C____ ●
Dual Head DP 316 SS for Close-Couple __D____ 3
316 SS with all-welded meter body __E____ 4
None ___0___ 22 ●
d. Bolts and
Carbon Steel Bolts and Nuts ___C___ ●
Nuts
316 SS Bolts and Nuts ___S___ ●
forTransmitter
Heads
A286 SS (NACE) Bolts and 304 SS (NACE) Nuts ___N___ ●
B7M (NACE) Bolts and 7M (NACE) Nuts ___B___ ●
No Fill Fluid ____0__ 5 5
Meter Body & e. Secondary Silicone Oil 200 ____1__ ● ●
Capillaries Fill Fluid Fluorinated Oil CTFE ____2__ ● ●
(capillary & Silicone Oil 704 ____3__ ● ●
seal) Neobee® M20 11 ____4__ ● ●
Syltherm ® 800 12 ____5__ ● ●
No Capillary, No Nipple (Specify for VAM Unit Only) _____0_ 5 5
5 feet 1.5 m _ _ _ _ _ A_ ● ●
10 feet 3.0 m _____B_ ● ●
15 feet 4.5 m _____C_ ● ●
SS Armor
20 feet 6.1 m _____D_ ● ●
f. Connection 25 feet 7.5 m _____E_ ● ●
of Remote Capillary 35 feet 10.7 m _____F_ ● ●
Seal to Meter Length 5 feet 1.5 m _____G_ ● ●
Body 10 feet 3.0 m _____H_ ● ●
15 feet 4.5 m PVC Coated SS _____J_ ● ●
20 feet 6.1 m Armor _____K_ ● ●
25 feet 7.5 m _____L_ ● ●
35 feet 10.7 m _ _ _ _ _ M_ ● ●
2 inch long SS nipple close-coupled _____2_ 6 6
None ______0 ● ●
g. Seal Option Std Gold Plated Seal Diaph. = 50 µin ______1 7 7
Teflon Coated Seal Diaphragm - only for anti-sticking ______4 7 7

11
Limited vacuum availability.
12
Minimum static pressure requirement. No vacuum allow ed. See Specifications 34-ST-03-88 Figure 15
STR700 Smart Pressure Transmitter 25

In-Line Gauge Dual Head DP All welded

STR74G
STR73D

Note: When selecting required seal, you must specify


Selection
only the 9 selections within the required seal type.

TABLE II Description
No Seal Attached to Core Transmitter (Specify for VAM Unit Only) 000000000 21 21
Dia phra g Flange Flange Pressure
Seal Type m Selection
Size Rating 1
Dia me te r
ANSI Class 150 AFA _ _ _ _ _ _ ● ●
3"
3.5" ANSI Class 300 AFC _ _ _ _ _ _ ● ●
80mm DIN DN80-PN40 AFM _ _ _ _ _ _ ● ●
Diaphragm Upper Insert Selection
316L SS 316L SS _ _ _ AA _ _ _ _ ● ●
Hastelloy ® C-276 316L SS _ _ _ AB _ _ _ _ ● ●
Wetted Material
Hastelloy ® C-276 Hastelloy ® C-276 _ _ _ AC _ _ _ _ ● ●
® ®
Monel 400 Monel 400 _ _ _ AE _ _ _ _ 8 8
5
Tantalum 316L SS _ _ _ AF _ _ _ _ 8 8
Non-Wetted Material CS (Nickel Plated) _____1___ ● ●
(upper) 316L SS _____2___ ● ●
Seals Seal-Capillary Center Seal ______1__ ● ●
Connection Side Seal ______2__ 9 9
Flush Flanged
Seal Calibration Rings None _ _ _ _ _ _ _ A_ ● ●
316L SS _______B_ 10 10
®
Hastelloy C-276 _______C_ 10 10
Monel 400 ® _______D_ 10 10
Flushing None ________0 ● ●
Connections One 1/4" with plastic plug ________H 11 11
4
and Plugs One 1/4" with metal plug ________J 11 11
(Metal plug material Two 1/4" with plastic plugs ________M 11 11
w ill be the same as Two 1/4" with metal plugs ________N 11 11
Cal. ring material if One 1/2" with plastic plug ________P 11 11
metal plug is chosen ) One 1/2" with metal plug ________Q 11 11
Two 1/2" with plastic plugs ________R 11 11
Two 1/2" with metal plugs ________S 11 11
Table II continued next page
1
Standard facing 125-250 AARH RF (raised face) serrated surface finish.
4
Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation
5
Tantalum Upper insert has Tantalum w etted parts and 316 SS or CS non-w etted parts

Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.
26 STR700 Smart Pressure Transmitter

STR74G
STR73D

TABLE II Descripton Selection


Dia phra g Flange Const. - See
Flange Construction - See Spec.
Seal Type m Pressure Spec. Figure 34-
Dia me te r Size Figure 34-ST-03-104
Rating 1 ST-03-104
ANSI 150 22 BCA _ _ _ _ _ _ ● ●
1"
ANSI 300 22 BCC _ _ _ _ _ _ ● ●
ANSI 150 22 BGA _ _ _ _ _ _ ● ●
1-1/2"
ANSI 300 22 BGC _ _ _ _ _ _ ● ●
2.4"
ANSI 150 22 BDA _ _ _ _ _ _ ● ●
2"
ANSI 300 22 BDC _ _ _ _ _ _ ● ●
ANSI 150 22 BFA _ _ _ _ _ _ ● ●
3"
ANSI 300 22 BFC _ _ _ _ _ _ ● ●
1/2" ANSI 150 23 CAA _ _ _ _ _ _ ● ●
ANSI 150 23 CCA _ _ _ _ _ _ ● ●
1"
ANSI 300 23 CCC _ _ _ _ _ _ ● ●
2.9" ANSI 150 22 CGA _ _ _ _ _ _ ● ●
1-1/2"
ANSI 300 22 CGC _ _ _ _ _ _ ● ●
ANSI 150 22 CDA _ _ _ _ _ _ ● ●
2"
ANSI 300 22 CDC _ _ _ _ _ _ ● ●
1/2" ANSI 150 22 DAA _ _ _ _ _ _ ● ●
ANSI 150 23 DCA _ _ _ _ _ _ ● ●
1"
ANSI 300 23 DCC _ _ _ _ _ _ ● ●
ANSI 150 22 DGA _ _ _ _ _ _ ● ●
1-1/2"
4.1" ANSI 300 22 DGC _ _ _ _ _ _ ● ●
ANSI 150 23 DDA _ _ _ _ _ _ ● ●
2"
ANSI 300 22 DDC _ _ _ _ _ _ ● ●
ANSI 150 22 DFA _ _ _ _ _ _ ● ●
Seals (continued) 3"
Flush Flanged ANSI 300 22 DFC _ _ _ _ _ _ ● ●
Seal Diaphragm Low er Selection
with Lower 316L SS 316L SS _ _ _ BA _ _ _ _ ● ●
Hastelloy ® C-276 316L SS _ _ _ BB _ _ _ _ ● ●
Hastelloy ® C-276 Hastelloy ® C-276 _ _ _ BC _ _ _ _ ● ●
Wetted Material ® ®
Monel 400 Monel 400 _ _ _ BE _ _ _ _ 8 8
Tantalum 316L SS _ _ _ BF _ _ _ _ 8 8
Tantalum Hastelloy ® C-276 _ _ _ BG _ _ _ _ 8 8
Tantalum Tantalum Clad _ _ _ BH _ _ _ _ 13 13
Upper Upper Insert Selection
Non-Wetted Material
316L SS 316L SS _____4___ ● ●
(upper, upper insert)
Carbon Steel 316L SS _____5___ ● ●
Bolts 6 No Selection ______0__ ● ●
Flushing None _______0 _ ● ●
Connections One 1/4" with plastic plug _______H_ ● ●
and Plugs 4 One 1/4" with metal plug _______J _ ● ●
(Metal plug material Two 1/4" with plastic plugs _ _ _ _ _ _ _ M_ ● ●
w ill be the same as Two 1/4" with metal plugs _______N_ ● ●
Low er material, if One 1/2" with plastic plug _______P_ ● ●
metal plug is chosen - One 1/2" with metal plug _______Q_ ● ●
(SS Plug for CS Low er Two 1/2" with plastic plugs _______R_ ● ●
and Tantalum Clad) Two 1/2" with metal plugs _______S_ ● ●
®
Klinger C-4401
________K ● ●
(non-asbestos)
Gasket Grafoil ® ________G ● ●
Teflon ® ________T ● ●
Gylon ® 3510 ________L 15 15
Table II continued next page

1
Standard facing 125-250 AARH RF (raised face) serrated surface finish.
6
Bolt material w ill be same as Upper Material. How ever, if Table I bolts/nuts material is NACE or B7M, seal bolt material w ill be 304 SS NACE.
4
Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation
Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.
STR700 Smart Pressure Transmitter 27

STR74G
STR73D
TABLE II Descripton
D ia phra gm Flange 1
Seal Type D ia m e t e r
Flange Pressure Rating Selection
Size
3" ANSI Class 150 EFA _ _ _ _ _ _ ● ●
2.8" (2.8" OD ANSI Class 300 EFC _ _ _ _ _ _ ● ●
extension) DIN DN80-PN40 EFM _ _ _ _ _ _ ● ●
4" ANSI Class 150 FGA _ _ _ _ _ _ ● ●
3.5" (3.70" OD ANSI Class 300 FGC _ _ _ _ _ _ ● ●
extension DIN DN100-PN40 FGP _ _ _ _ _ _ ● ●
Diaphragm Ext. Tube Selection
Flange Seal
Seals (continued) 316L SS 316L SS _ _ _ EA _ _ _ _ ● ●
with Extended Wetted Material
Hastelloy ® C-276 316L SS _ _ _ EB _ _ _ _ ● ●
Diaphragm
Hastelloy ® C-276 Hastelloy ® C-276 _ _ _ EC _ _ _ _ ● ●
Non-Wetted CS (Nickel Plated) _____7___ ● ●
Material (flange) 316L SS _____8___ ● ●
Bolts No Selection ______0__ ● ●
2" _______2 _ ● ●
Extension Length 4" _______4_ ● ●
6" _______6_ ● ●
No Selection No Selection No Selection ________0 ● ●
Table II continued below

STR74G
STR73D
TABLE II Descripton
Dia phra g Flange Pressure Rating
Flange
Seal Type m Dependent on Custom er Flange Selection
Size 1
Dia me te r

3.5" 3" ANSI Class 150/300/600 GFA _ _ _ _ _ _ ● ●


Diaphragm Body
316L SS 316L SS _ _ _ GA _ _ _ _ ● ●
Hastelloy ® C-276 316L SS _ _ _ GB _ _ _ _ ● ●
Wetted Material
Hastelloy ® C-276 Hastelloy ® C-276 _ _ _ GC _ _ _ _ ● ●
Monel 400 ® Monel 400 ® _ _ _ GE _ _ _ _ 8 8
7
Tantalum Tantalum _ _ _ GG _ _ _ _ 8 8
Non-Wetted Material No Selection _____0___ ● ●
Bolts No Selection ______0__ ● ●
Seals (continued) Calibration Rings None _ _ _ _ _ _ _ A_ ● ●
316L SS _______B_ 10 10
®
Pancake Seal Hastelloy C-276 _______C_ 10 10
Monel 400 ® _______D_ 10 10
Flushing None ________0 ● ●
Connections One 1/4" with plastic plug ________H 11 11
and Plugs 4 One 1/4" with metal plug ________J 11 11
(Metal plug material Two 1/4" with plastic plugs ________M 11 11
w ill be the same as Two 1/4" with metal plugs ________N 11 11
Cal. Ring material, if One 1/2" with plastic plug ________P 11 11
metal plug is chosen ) One 1/2" with metal plug ________Q 11 11
Two 1/2" with plastic plugs ________R 11 11
Two 1/2" with metal plugs ________S 11 11
Table II continued next page

1
Standard facing 125-250 AARH RF (raised face) serrated surface finish.
4
Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation
7
Tantalum Body has Tantalum w etted parts and 316 SS non-w etted parts

Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.
28 STR700 Smart Pressure Transmitter

STR74G
STR73D
TABLE II Descripton
Dia phra g Flange 1
Seal Type m Flange Pressure Rating Selection
Size
Dia me te r
Taylor
3.5" Wedge 750 psi HM0 _ _ _ _ _ _ 16
5" O.D.
Diaphragm Body Selection
Seals (continued) 316L SS 316L SS _ _ _ HA _ _ _ _ ●
Wetted Material
Hastelloy ® C-276 316L SS _ _ _ HB _ _ _ _ ●
Chemical Tee
Hastelloy ® C-276 Hastelloy ® C-276 _ _ _ HC _ _ _ _ ●
"Taylor" Wedge
Non-Wetted Material No Selection _____0___ ●
Bolts No Selection _____0__ ●
Styles No Selection _______0 _ ●
No Selection No Selection ________0 ●
Table II continued below

STR74G
TABLE II Descripton STR73D

Dia phra g Threaded Process Pressure Rating


Seal Type m Connection Size 304 SS
Dia me te r CS Bolts Selection
(NPT Fem ale) Bolts
1/2 NPT JJG _ _ _ _ _ _ ● ●
2,500 1,250
2.4" 3/4 NPT JKG _ _ _ _ _ _ ● ●
psi psi
1 NPT JLG _ _ _ _ _ _ ● ●
1/2 NPT KJG _ _ _ _ _ _ ● ●
2,500 1,250
2.9" 3/4 NPT KKG _ _ _ _ _ _ ● ●
psi psi
1 NPT KLG _ _ _ _ _ _ ● ●
1/2 NPT LJG _ _ _ _ _ _ ● ●
1,500 750
4.1" 3/4 NPT LKG _ _ _ _ _ _ ● ●
psi psi
1 NPT LLG _ _ _ _ _ _ ● ●
Diaphragm Low er Selection
316L SS Carbon Steel _ _ _ JA _ _ _ _ ● ●
316L SS 316L SS _ _ _ JB _ _ _ _ ● ●
Hastelloy ® C-276 316L SS _ _ _ JC _ _ _ _ ● ●
Wetted Material
Hastelloy ® C-276 Hastelloy ® C-276 _ _ _ JD _ _ _ _ ● ●
® ®
Monel 400 Monel 400 _ _ _ JE _ _ _ _ 8 8
Tantalum 316L SS _ _ _ JF _ _ _ _ 8 8
Seals (continued) Seal with Tantalum Hastelloy ® C-276 _ _ _ JG _ _ _ _ 8 8
Threaded
Non-Wetted Material CS (Nickel Plated) _ _ _ _ _ A_ _ _ ● ●
Process
(upper) 316 Stainless Steel _____C___ 17 17
Connection
8
Carbon Steel ______C__ ● ●
Bolts
304 SS ______D__ ● ●
Flushing None _______0 _ ● ●
Connections One 1/4" with plastic plug _______H_ ● ●
and Plugs 4 One 1/4" with metal plug _______J _ ● ●
(Metal plug material Two 1/4" with plastic plugs _ _ _ _ _ _ _ M_ ● ●
w ill be the same as Two 1/4" with metal plugs _______N_ ● ●
Low er material, if One 1/2" with plastic plug _______P_ 18 18
metal plug is chosen - One 1/2" with metal plug _______Q_ 18 18
(SS Plug for CS Low er Two 1/2" with plastic plugs _______R_ 18 18
and Tantalum Clad) Two 1/2" with metal plugs _______S_ 18 18
Klinger® C-4401
________K ● ●
(non-asbestos)
Gasket Grafoil ® ________G ● ●
Teflon ® ________T ● ●
Gylon ® 3510 ________L 15 15
Table II continued next page
1
Standard facing 125-250 AARH RF (raised face) serrated surface finish.
4
Plastic Plugs are TEMPORARY ONLY to protect threads and MUST be REMOVED before installation
8
If Table I Bolts and Nuts material option is NACE, Bolts and Nuts w ill ship w ith Alloy Steel NACE and MAWP may change.
Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.
STR700 Smart Pressure Transmitter 29

STR74G
STR73D
TABLE II Descripton
Dia phra g Flange
Seal Type m Pressure Rating Selection
Size
Dia me te r
1.9" 2" MD0 _ _ _ _ _ _ 20 19
2.4" 2-1/2" Customer clamp rating or NE0 _ _ _ _ _ _ 19 19
2.9" 3" 600 psi, whichever is less PF0 _ _ _ _ _ _ 19 19
4.1" 4" QG0 _ _ _ _ _ _ 19 19
Seals (continued) Diaphragm Body Selection
Wetted Material
316L SS 316L SS _ _ _ N A_ _ _ _ ● ●
Sanitary Seal 9
Non-Wetted Material No Selection _____0___ ● ●

Bolts No Selection ______0__ ● ●


Styles Tri-Clover Tri-Clamp
®
_______8 _ ● ●
Gasket No Selection ________0 ● ●
Table II continued below

STR74G
TABLE II Descripton STR73D
Dia phra g Size and Seal Pressure Rating
Seal Type m Bolt
Dia me te r C.S. Bolts 304 SS Bolts Selection
Pattern
2.4" RFK _ _ _ _ _ _ ● ●
for 3" Pipe
8-Bolt 2,500 psi 1,250 psi
≥ 4" pipe RGK _ _ _ _ _ _ ● ●
Design
2.4" RPK _ _ _ _ _ _ ● ●
for 3" Pipe
6-Bolt 2,000 psi 1,000 psi
≥ 4" pipe RQK _ _ _ _ _ _ ● ●
Design
Diaphragm Low er Housing Selection
316L SS Carbon Steel _ _ _ RA _ _ _ _ ● ●
316L SS 316L SS _ _ _ RB _ _ _ _ ● ●
Wetted Material Hastelloy ® C-276 316L SS _ _ _ RC _ _ _ _ ● ●
Seals (continued) Hastelloy ® C-276 Hastelloy ® C-276 _ _ _ RD _ _ _ _ ● ●
10
Saddle Seal 316L SS N/A-Body Only _ _ _ SB _ _ _ _ ● ●
Hastelloy ® C-276 N/A-Body Only 10
_ _ _ SC _ _ _ _ ● ●
Body Bolts 10,11 Selection
Non-Wetted Material Carbon Steel Carbon Steel _____B___ 8 8
316L SS 316 SS _____C___ ● ●
Bolts No Selection ______0__ ● ●
Styles No Selection _______0_ ● ●
®
Klinger C-4401
________K ● ●
(non-asbestos)
Gasket Grafoil®
________G ● ●
Teflon
®
________T ● ●
®
Gylon 3510 ________L ● ●
9
All sanitary seals have dairy grade 3A approval.
10
Bolts are not included w ith "body only" selection.
11
If Table I Bolts and Nuts material option is NACE, seal bolt material w ill be 304 SS NACE.
Note: Remote seal system pressure rating is body rating or seal rating, w hichever is less.
30 STR700 Smart Pressure Transmitter

STR74G
STR73D

TABLE III Agency Approvals (see data sheet for Approval Code Details)
No Approvals Required 0 ● ●
FM Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof A ● ●
CSA Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof B ● ●
ATEX Explosion proof, Intrinsically Safe & Non-incendive C ● ●
Approvals
IECEx Explosion proof, Intrinsically Safe & Non-incendive D ● ●
SAEx/CCoE Explosion proof, Intrinsically Safe & Non-incendive E ● ●
INMETRO Explosion proof, Intrinsically Safe & Non-incendive F ● ●
NEPSI Explosion proof, Intrinsically Safe & Non-incendive G ● ●

TABLE IV TRANSMITTER ELECTRONIC SELECTIONS


Material Connection Lightning Protection
Polyester Powder Coated Aluminum 1/2 NPT None A__ ● ●
a. Electronic Polyester Powder Coated Aluminum M20 None B__ ● ●
Housing Polyester Powder Coated Aluminum 1/2 NPT Yes C__ ● ●
Material & Polyester Powder Coated Aluminum M20 Yes D__ ● ●
Connection 316 Stainless Steel (Grade CF8M) 1/2 NPT None E__ ● ●
Type 316 Stainless Steel (Grade CF8M) M20 None F__ ● ●
316 Stainless Steel (Grade CF8M) 1/2 NPT Yes G__ ● ●
316 Stainless Steel (Grade CF8M) M20 Yes H__ ● ●
Analog Output Digital Protocol
b. Output/ 4-20mA dc HART Protocol _H_ ● ●
Protocol 4-20mA dc DE Protocol _D_ ● ●
none Foundation Fieldbus _F_ ● ●
Indicator Ext Zero, Span & Config Buttons Languages
None None None __0 ● ●
None Yes (Zero/Span Only) None __A f f
c. Customer
Basic None English __B ● ●
Interface
Selections
Basic Yes English __C ● ●
Simple (w/internal
Zero, Span & Conf None English __D u u
Buttons)

TABLE V CONFIGURATION SELECTIONS


a. Application Diagnostics
Softw are Standard Diagnostics 1__ ● ●
Write Protect Fail Mode High & Low Output Lim its 3
Disabled High> 21.0mAdc Honeywell Std (3.8 - 20.8 mAdc) _1_ f f
b. Output Limit,
Disabled Low< 3.6mAdc Honeywell Std (3.8 - 20.8 mAdc) _2_ f f
Failsafe &
Enabled High> 21.0mAdc Honeywell Std (3.8 - 20.8 mAdc) _3_ f f
Write Protect
Settings Enabled Low< 3.6mAdc Honeywell Std (3.8 - 20.8 mAdc) _4_ f f
Enabled N/A N/A Fieldbus _5_ g g
Disabled N/A N/A Fieldbus _6_ g g
c. General Factory Standard __S ● ●
Configuration Custom Configuration (Unit Data Required from customer) __C ● ●

TABLE VI CALIBRATION & ACCURACY SELECTIONS


Accuracy Calibrated Range Calibration Qty
Accuracy and
NA None None 0 21 21
Calibration
Standard Factory Std Single Calibration A 23 23
Standard Custom (Unit Data Required) Single Calibration B 23 23

3
NAMUR Output Limits 3.8 - 20.5mAdc can be configured by the customer or select custom configuration Table Vc
STR700 Smart Pressure Transmitter 31

STR74G
STR73D

TABLE VII ACCESSORY SELECTIONS


Bracket Type Material
None None 0___ ● ●
Angle Bracket Carbon Steel 1___ ● ●
Angle Bracket 304 SS 2___ ● ●
Angle Bracket 316 SS 3___ ● ●
a. Mounting Marine Approved Bracket Carbon Steel 8___ y
Bracket Marine Approved Bracket (In - Line) Carbon Steel 9___ ●
Marine Approved Bracket 304 SS 4___ y
Marine Approved Bracket (In - Line) 304 SS A_ _ _ ●
Flat Bracket Carbon Steel 5___ ● ●
Flat Bracket 304 SS 6___ ● ●
Flat Bracket 316 SS 7___ ● ●
Custom er Tag Type
b. Customer No customer tag _0__ ● ●
Tag One Wired Stainless Steel Tag (Up to 4 lines 26 char/line) _1__ ● ●
Two Wired Stainless Steel Tag (Up to 4 lines 26 char/line) _2__ ● ●
Unassem bled Conduit Plugs & Adapters
c. No Conduit Plugs or Adapters Required _ _ A0 ● ●
Unassembled 1/2 NPT Male to 3/4 NPT Female 316 SS Certified Conduit Adapter _ _ A2 n n
Conduit 1/2 NPT 316 SS Certified Conduit Plug _ _ A6 n n
Plugs & M20 316 SS Certified Conduit Plug _ _ A7 m m
Adapters Minifast® 4 pin (1/2 NPT) _ _ A8 n n
Minifast® 4 pin (M20) _ _ A9 m m

TABLE VIII OTHER Certifications & Options : (String in sequence comma delimited (XX, XX, XX,….)
None - No other options 00 * *
NACE MR0175; MR0103; ISO15156 (FC33338) Process wetted parts only FG ● ● b
NACE MR0175; MR0103; ISO15156 (FC33339) wetted and non-wetted parts F7 c c
Marine (DNV,ABS,BV,KR,LR) MT d d
EN10204 Type 3.1 Material Traceability (FC33341) FX ● ●
Certifications &
Certificate of Conformance (F3391) F3 ● ●
Warranty b
Calibration Test Report & Certificate of Conformance (F3399) F1 ● ●
Certificate of Origin (F0195) F5 ● ●
FMEDA (SIL 2/3) Certification (FC33337) FE j j
Over-Pressure Leak Test Certificate (1.5X MAWP) (F3392) TP ● ●
Cert Clean for O2 or CL 2 service per ASTM G93 OX e e

TABLE IX Manufacturing Specials


Factory Factory Identification 0000 ● ●
32 STR700 Smart Pressure Transmitter

MODEL RESTRICTIONS
Restriction Available Only With Not Available With
Letter Table Selection(s) Table Selection(s)
b Select only one option from this group
d VIIa 1,2,3,5,6,7 _ _ _

c Id _ _ _ 0, N, B _ _ _

e Ib _2__2__
f IVb _F_
g IVb _ H, D _
j IVb _H_ Vb _ 1,2,6 _
m IVa B, D, F, H _ _
n IVa A, C, E, G _ _
u IVb _H_
y Ic __E____
____0__
2 Ie ____2__
____4__

3 If _____2_ Ia 2______

4 I 2__0___

5 II 000000000 VIII FG, F7, FX, OX,TP,MT,F1

6 I _ _ B,D _ _ _ _ Ia 2______
_ _ _ AF _ _ _ _
_ _ _ BF _ _ _ _
_ _ _ BG _ _ _ _
7 II _ _ _ BH _ _ _ _
_ _ _ GG _ _ _ _
_ _ _ JF _ _ _ _
_ _ _ JG _ _ _ _
8 VIII FG, F7
_ _ _ AA2_ _ _
9 II
_ _ _ AB2_ _ _
10 II ________0
11 II _ _ _ _ _ _ _ A_
II ________T
13 II _______0_
VIII FG, F7
_ _ _ BF _ _ _ _
_ _ _ BG _ _ _ _
15 II _ _ _ BH _ _ _ _
_ _ _ JF _ _ _ _
_ _ _ JG _ _ _ _
16 I 2______
17 II _ _ _ JA _ _ _ _
JJG _ _ _ _ _ _
18 II JKG _ _ _ _ _ _
JLG _ _ _ _ _ _
19 If _____2_

20 If _ _ _ _ _ A, G _

21 I _ _ _ _ 000
22 Ic __E____
23 II 000000000
STR700 Smart Pressure Transmitter 33

Sales and Service


For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one
of the offices below.

ASIA PACIFIC EMEA AMERICA’S


Honeywell Process Solutions, Honeywell Process Solutions, Honeywell Process Solutions,
(TAC) hfs-tac- Phone: + 80012026455 or Phone: (TAC) 1-800-423-9883 or
support@honeywell.com +44 (0)1344 656000 215/641-3610
(Sales) 1-800-343-0228
Australia Email: (Sales)
Honeywell Limited FP-Sales-Apps@Honeywell.com Email: (Sales)
Phone: +(61) 7-3846 1255
FAX: +(61) 7-3840 6481 or FP-Sales-Apps@Honeywell.com
Toll Free 1300-36-39-36 (TAC) or
Toll Free Fax: hfs-tac-support@honeywell.com (TAC)
1300-36-04-70 hfs-tac-support@honeywell.com
China – PRC - Shanghai
Honeywell China Inc.
Phone: (86-21) 5257-4568
Fax: (86-21) 6237-2826

Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033

South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015

Specifications are subject to change without notice.


34 STR700 Smart Pressure Transmitter

For more information


To learn more about SmartLine Transmitters,
visit www.honeywellprocess.com
Or contact your Honeywell Account Manager

Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042

Honeywell Control Systems Ltd


Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB

Shanghai City Centre, 100 Jungi Road


Shanghai, China 20061
34-ST-03-104
March 2016
www.honeywellprocess.com 2016 Honeywell International Inc.