Fuel flow
Fuel flow at rated load, L/hr (US gph) 548.8 (145.0)
Maximum inlet restriction, mm Hg (in Hg) 101.6 (4.0)
Maximum return restriction, mm Hg (in Hg) 508.0 (20.0)
©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation.
D-3415 (7/08)
Standby Prime Continuous
Air rating rating rating
3
Combustion air, m /min (scfm) 60.3 (2130.0) 56.7 (2005.0)
Maximum air cleaner restriction, kPa (in H2O) 6.2 (25.0)
3
Alternator cooling air, m /min (scfm) 158.5 (5600.0)
Exhaust
3
Exhaust flow at rated load, m /min (cfm) 178.6 (6310.0) 164.7 (5820.0)
Exhaust temperature, °C (°F) 576.7 (1070.0) 565.6 (1050.0)
Maximum back pressure, kPa (in H2O) 6.7 (27.0)
Weights2
Unit dry weight kgs (lbs) 7676 (16922)
Unit wet weight kgs (lbs) 7973 (17578)
Notes:
1
For non-standard remote installations contact your local Cummins Power Generation representative.
2
Weights represent a set with standard features. See outline drawing for weights of other configurations.
Derating factors
Engine power available up to 980 m (3214 ft) at temperatures up to 40 °C (104 °F) and up to 355 m
(1164 ft) at 50 °C (122 °F). Above these elevations, derate at 3.5% per 305 m (1000 ft) up to 3000 m
Standby
(9843 ft). Above 50 °C (122 °F) and 3000 m (9843 ft), derate an additional 9.0% per 500 m (1640 ft) and
15% per 10 °C (18 °F).
Prime
Continuous
Ratings definitions
Emergency standby power Limited-time running power Prime power (PRP): Base load (continuous)
(ESP): (LTP): power (COP):
Applicable for supplying power to Applicable for supplying power Applicable for supplying power Applicable for supplying power
varying electrical load for the to a constant electrical load for to varying electrical load for continuously to a constant
duration of power interruption of a limited hours. Limited Time unlimited hours. Prime Power electrical load for unlimited
reliable utility source. Emergency Running Power (LTP) is in (PRP) is in accordance with ISO hours. Continuous Power (COP)
Standby Power (ESP) is in accordance with ISO 8528. 8528. Ten percent overload is in accordance with ISO 8528,
accordance with ISO 8528. Fuel capability is available in ISO 3046, AS 2789, DIN 6271
Stop power in accordance with accordance with ISO 3046, and BS 5514.
ISO 3046, AS 2789, DIN 6271 and AS 2789, DIN 6271 and BS 5514.
BS 5514.
Full load current amps at 110/190 115/200 120/208 110/220 127/220 115/230 120/240 220/380 230/400 240/415 255/440
standby rating 3343 3175 3053 2887 2887 2761 2646 1673 1590 1532 1445
1.
Single phase power can be taken from a three phase generator set at up to 40% of the generator set nameplate kW rating at unity power factor.