You are on page 1of 16

INSTALLATION MANUAL

WALL MOUNTED
SPLIT TYPE AIR CONDITIONER

WALL MOUNTED
Part No.: R08019028786
IM-WMG-0906-DAIKIN
14
OUTLINE AND DIMENSIONS

English
Indoor Unit
A

TOP VIEW

C
B

FRONT VIEW SIDE VIEW

G D F
H

O
E

N
I

J M I
K INSTALLATION
L PLATE
All dimensions are in mm/ (in)

Dimension A B C D E F G H I J K L M N O
FT20FV1M/FT25FV1M 799 260 198 379 246 185 124 8 56 50 319 379 50 128 132
(31.5) (10.2) (7.8) (15.0) (9.7) (7.3) (4.9) (0.3) (2.2) (2.0) (12.6) (15.0) (2.0) (5.1) (5.2)
FT28FV1M/FT35FV1M 899 260 198 590 246 185 124 8 56 50 419 495 50 128 132
(35.4) (10.2) (7.8) (23.2) (9.7) (7.3) (4.9) (0.3) (2.2) (2.0) (16.5) (19.5) (2.0) (5.1) (5.2)

A
Dimension A B C D E
FT50FV1M / FT60FV1M9 1060 310 220 912 294
(41.7) (12.2) (8.6) (35.9) (11.6)
C
TOP VIEW
Dimension F G H I J
FT50FV1M / FT60FV1M9 99 51 8 48 43
B

(3.9) (2.0) (0.3) (1.9) (1.7)

FRONT VIEW SIDE VIEW


A Dimension K L M N O
G D F FT50FV1M / FT60FV1M9 354 403 160 138 160
H

(13.9) (15.9) (6.3) (5.4) (6.3)


CENTER LINE
O
M
B

J M
I

INSTALLATION
K
PLATE
L
All dimensions are in mm/ (in)

1
Outdoor Unit

Dimension A B C
R20FV1M/R25FV1M 600 475 245
(23.6) (18.7) (9.6)
L K L R35FV1M 700 521 250
(27.5) (20.5) (9.8)

N
Dimension D E F

M
R20FV1M/R25FV1M 418 177 35
(16.4) (6.9) (1.3)

C
R35FV1M 485 175 36
(19.1) (6.8) (1.4)

N
(1.2)
30
A C Dimension G H I
O D G H R20FV1M/R25FV1M 93 81 83
(0.1)
3

F
(3.6) (3.1) (3.2)
R35FV1M 95 93 86
(3.7) (3.6) (3.3)

E Dimension J K L
B

R20FV1M/R25FV1M 55 398 101


(2.2) (15.6) (3.9)
(3.1) (2.6)
80 65

R35FV1M 68 441 130


(2.6) (17.3) (5.1)
(0.7)

I J Dimension M N O
19

R20FV1M/R25FV1M 97 17 22
(3.8) (0.6) (0.8)
R35FV1M 111 15 18
All dimensions are in mm/ (in)
(4.3) (0.5) (0.7)

L K L
N
M
C
N
P

C
A
O D G H
Q

F
E

FOR R71FV1M
B

ONLY
T
S

I J
R

Dimension A B C D E F G H I J K L M N O
R50FV1M 855 628 328 513 182 44 93 149 101 113 603 126 164 17 49
(33.7) (24.7) (12.9) (20.0) (7.1) (1.7) (3.7) (5.9) (4.0) (4.4) (23.7) (5.0) (6.4) (0.7) (1.9)
R60FV1M9 855 730 328 513 182 44 93 149 101 113 603 126 164 17 47
(33.7) (28.7) (12.9) (20.2) (7.2) (1.7) (3.7) (5.9) (4.0) (4.4) (23.7) (5.0) (6.4) (0.7) (1.9)

Dimension P Q R S T
R50FV1M 32 3 23 73 75
(1.3) (0.1) (0.9) (2.9) (3.0)
R60FV1M9 32 3 23 73 75
(1.3) (0.1) (0.9) (2.9) (3.0) All dimensions are in mm/ (in)

2
INSTALLATION MANUAL

English
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air condi-
tioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.

MODEL
Indoor Outdoor
FT20FV1M R20FV1M
FT25FV1M R25FV1M
FT35FV1M R35FV1M
FT50FV1M R50FY1M
FT60FV1M9 R60FV1M9

SAFETY PRECAUTIONS

! WARNING ! CAUTION
• Installation and maintenance should be performed by Please take note of the following important points when installing.
qualified persons who are familiar with local code and • Do not install the unit where leakage of flammable gas may occur.
regulation. and experienced with this type of If gas leaks and accumulates around the unit. it may cause fire
ignition.
appliance. • Ensure that the drainage piping is connected properly.
• All field wiring must be installed in accordance with If the drainage piping is not connected properly. it may cause
the national wiring regulation. water leakage which will dampen the furniture.
• Ensure that the rated voltage of the unit corresponds • Do not overcharge the unit.
to that of the name plate before commencing wiring This unit is factory pre-charged. Overcharge will cause over-
work according to the wiring diagram. current or damage to the compressor.
• Ensure that the units panel is closed after service or installation.
• The unit must be GROUNDED to prevent possible Unsecured panels will cause the unit to operate noisily.
hazard due to insulation failure.
• All electrical wiring must not touch the refrigerant • Sharp edges and coil surfaces are potential locations which may
piping or any moving parts of the fan motors. cause injury hazards. Avoid from being in contact with these
places.
• Confirm that the unit has been switched OFF before • Before turning off the power supply. set the remote controller’s
installing or servicing the unit. ON/OFF switch to the “OFF” position to prevent the nuisance
• Disconnect from the main power supply before tripping of the unit. If this is not done. the unit’s fans will start turning
servicing the air conditioner unit. automatically when power resumes. posing a hazard to service
• DO NOT pull out the power cord when the power is personnel or the user.
ON. This may cause serious electrical shocks which • Do not operate any heating apparatus too close to the air
conditioner unit. This may cause the plastic panel to melt or deform
may result in the fire hazards. as a result of the excessive heat.
• Ensure the color of wires of the outdoor unit and the terminal
markings are same to the indoors respectively.
• IMPORTANT : DO NOT INSTALL OR USE THE AIR
CONDITIONER UNIT IN A LAUNDRY ROOM.

INSTALLATION OF THE OUTDOOR UNIT


A B
The outdoor unit must be installed in such a way, so as to prevent short circuit of the hot
discharged air or obstruction to the smooth air flow. Please follow the installation clearances
Return Air

shown in the figure. Select the coolest possible place where intake air temperature is not
Discharge Air

greater than the outside air temperature (maximum 45°C).


Obstacle
Obstacle

Installation Clearances
Dimension A B C D
Minimum Distance, 300 1000 300 500 C D
mm (in) (11.8) (39.4) (11.8) (19.7)
Return Air

Note: If there is any obstacle higher than 2m, or if there is any obstruction at
Obstacle
Obstacle

the upper part of the unit, please allow more space than the figure indicated in
Service

the above table.


Access

3
INSTALLATION OF THE INDOOR UNIT

The indoor unit must be installed in such a way so as to prevent short circuit of 50.0 mm 50.0 mm
the cool discharged air with the hot return air. Please follow the installation
clearance shown in the figure. Do not place the indoor unit where there could be
direct sunlight shining on it. Also, this location must be suitable for piping and
drainage, and be away from doors or windows. Air Flow

Eye Level
Higher
Direction

Than
Maintenance &
Servicing Space

Routing Of Piping Mount The Unit Onto The Installation Plate


Remove the screw holding the front panel. Hook the indoor unit onto the upper portion of the
installation plate (Engage the two hooks at the rear top of the
Piping Routing indoor unit with the upper edge of the installation plate). Ensure
that the hooks are properly seated on the installation plate by
2 3
moving it to the left and right.
1
4

The refrigerant piping can be routed to the unit in a number of


ways (left or right from the back of the unit), by using the 1. Hook the unit onto the installation plate.
cut-out holes on the casing of the unit (see figure). Bend the
pipes carefully to the required position in order to align it with Water Drainage Piping
the holes. For the right hand and rear side out, hold the bottom
The indoor drain pipe must be in a downward gradient for smooth
of the piping and then position it to the required direction (see drainage. Avoid situations that are likely to cause water to leak.
figure). The condensation drain hose can be taped to the pipes.
Water Drainage
Right & Rear Side Routing

Water
Retention End
Dipped
Water Water Water Into
Leaking Leaking Leaking Water
Unit Piping
Drain Hose Drain
Fix With Vinyl Tape
Correct Wrong Wrong Wrong

Mounting Installation Plate


Ensure that the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce the wall with
plates, beams or pillars.
Use the level gauge for horizontal mounting, and fix it with 4 suitable screws.
In case the rear piping draws out, drill a hole 65mm in diameter with a cone drill, slightly lower on the outside wall (see figure).
Screw Position In The Wall Hole With Cone Drill

Centre Line
Indoor Side Outdoor Side
72.0

Ø 65.0 mm Hole In The Wall

Screw Position In The Wall

Inside Outside

1/50 Inclination
Ø 65.0 mm Hole In The Wall

4
REFRIGERANT PIPING WORK

English
Piping Length & Elevation Indoor Unit
If the pipe is too long, both the capacity and reliability of the unit will
drop. As the number of bends increases, resistance to the flow of
refrigerant system increases, thus lowering cooling capacity. As a
result, the compressor may become defective. Always choose the
shortest path and follow the recommendations as tabulated below:

Outdoor Unit

Model FT20FV1M FT25FV1M FT28FV1M FT35FV1M FT50FV1M FT60FV1M9


Maximum length, m (ft), L 12 (39) 12 (39) 12 (39) 12 (39) 15 (49) 15 (49)
Max. elevation, m (ft), H 5 (16.4) 5 (16.4) 5 (16.4) 5 (16.4) 8 (26.2) 8 (26.2)
Max. number of (90˚) bends 10 10 10 10 10 10
Liquid pipe size 1/4” 1/4” 1/4” 1/4” 1/4” 3/8”
Gas pipe size 3/8” 3/8” 3/8” 1/2” 5/8” 5/8”

Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.62 m/ 25 ft.

Piping Works
• Do not use contaminated or damaged copper tubing. Do not
remove plastic, rubber plugs and brass nuts from the valves, Cutting Copper Tube
fittings, tubings and coils until you are ready to connect suction
or liquid line into valves or fittings. 1/4t
• If any brazing work is required, ensure that the nitrogen gas is
passed through coil and joints while the brazing work is being
done. This will eliminate soot formation on the inside walls of
the copper tubings.
• Cut the connection pipe with a pipe cutter.
• Remove burrs from cut edges of the pipes with remover.
Hold the end of the pipe downwards to prevent metal chips from
entering the pipe.
• Insert the flare nuts, mounted on the connection parts of both the
indoor unit and outdoor unit onto the copper pipes.
• Flare the pipe with extra length above the flaring tool as shown
in the table. Remove Burr
• The flared edge must be even and not cracked or scratched.

Ø Tube, D A (mm)
Inch mm Imperial Rigid
1/4" 6.35 1.3 0.7
Copper Tube
3/8" 9.52 1.6 1.0 Swaging
1/2" 12.70 1.9 1.3 Block
5/8" 15.88 2.2 1.7
3/4" 19.05 2.5 2.0

5
Piping Connection To The Units Flare Joint Flared Tube
• Align the center of the piping and tighten the flare nut suffi-
ciently with fingers.
• Finally, tighten the flare nut with the torque wrench until the
wrench clicks.
Pipe Size mm / (in) Torque Nm / (ft - lb) Indoor Piping Flare Nut

6.35 (1/4) 18 (13.3)


9.53 (3/8) 42 (31.0)
12.7 (1/2) 55 (40.6)
15.88 (5/8) 65 (48.0)
19.05 (3/4) 78 (57.6)

Torque Wrench
Spanar

ELECTRICAL WIRING CONNECTION

Cooling Unit
IMPORTANT: * The figures shown in the table are for information purpose only. They should be checked and selected to
comply with the local/national codes of regulations. This is also subject to the type of installation and
conductors used.

Cooling Unit (Power From Indoor) FT20/25/28/35FV1M


Indoor Unit Outdoor Unit
Terminal Block Terminal Block
COMP COMP

N2 N

N1

Power Supply Cable

!
There must be a double pole switch
with a minimum 3mm contact gap and
FT20FV1M FT50FV1M
fuse/circuit breaker as recommended
FT25FV1M FT60FV1M9
in the fixed installation circuit. Model FT28FV1M
FT35FV1M
Cooling Unit (Power From Outdoor) FT50FV1M/ Voltage range 220V-240V / 1Ph / 50Hz + !
FT60FV1M9 Power supply cable size* mm2 1.5 2.5
Outdoor coil sensor Outdoor Unit
Number of wire 3 3
Indoor Unit
Terminal Block connection wire (8m long) Terminal Block Interconnection cable size* mm2 2.0 2.0
attached in the indoor unit Number of wire 3 3
COMP COMP Recommended fuse A 15 20
N2 L1

N1

N1 L

L N

Power Supply Cable


There must be a double pole switch

! with a minimum 3mm contact gap and


fuse/circuit breaker as recommended in
the fixed installation circuit.

• All wires must be firmly connected.


• All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor.
• The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps.
• The power supply cord must be equivalent to H05RN-F (245IEC57) which is the minimum requirement.

6
VACUUMING AND CHARGING

English
Purging The Piping And The Indoor Unit Refrigerant Piping
Allen Key Flare Nut
Except for the outdoor unit which is pre-charged with refrigerant, the indoor
unit and the refrigerant connection pipes must be air-purged because the air
containing moisture that remains in the refrigerant cycle may cause malfunc-
tion of the compressor.
• Remove the caps from the valve and the service port.
• Connect the center of the charging gauge to the vacuum pump. Service Port Outdoor Unit 3 Ways Valve
• Connect the charging gauge to the service port of the 3-way valve.
• Start the vacuum pump. Evacuate for approximately 30 minutes. The Liquid Side
Indoor Unit
Indoor Unit Liquid side Outdoor
Outdoor Unit
evacuation time varies with different vacuum pump capacity. Confirm that Discharge Unit
Valve
the charging gauge needle has moved towards -760mmHg. Close
Caution:
• If the gauge needle does not move to -760mmHg, be sure to check for gas Gas Side
Gas side
leaks (using the refrigerant detector) at flare type connection of the indoor
and outdoor unit and repair the leak before proceeding to the next step. Suction
valve
• Close the valve of the charging gauge and stop the vacuum pump. Open
Open
Vacuum
Vacuum Close
• On the outdoor unit, open the suction valve (3 way) and liquid valve (2 way) Pump
pump Hi
Hi
Low
(in anti- clockwise direction) with 4mm key for hexagon sacked screw. Close
Close

Additional Charge
The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 7.62m (25ft), then additional charge after vacuuming is
not necessary. If the piping length is more than 7.62m (25ft), then use the additional charge valve as indicated in the table.
Additional charge in gram (For R22 models)
Model 10m/32.8ft 12m/39.4ft 15m/49.2ft
FT20FV1M / FT25FV1M 35 65 -
FT28FV1M/FT35FV1M
FT50FV1M 35 65 -
FT60FV1M9 90 165 280

Charge Operation
This operation must be done by using a gas cylinder and a precise weigh-
Indoor Unit Liquid
Liquid Side
side Outdoor
OutdoorUnit
Unit
ing machine. The additional charge is topped-up into the outdoor unit Discharge Valve
using the suction valve via the service port. Open
• Remove the service port cap.
• Connect the low pressure side of the charging gauge to the suction
Gas side
Gas Side
service port center of the cylinder tank and close the high pressure
side of the gauge. Purge the air from the service hose. Suction
Check
Check
• Start the air conditioner unit. Valve
Valve
Valve
Open
• Open the gas cylinder and low pressure charging valve. Hi
Hi
• When the required refrigerant quantity is pumped into the unit, close Low
Low
Close
Close
the low pressure side and the gas cylinder valve.
• Disconnect the service hose from service port. Put back the service
port cap.

7
INDICATOR LIGHTS

IR Signal Receiver
When an infrared remote control operating signal has been
transmitted, the signal receiver on the indoor unit will make a
<beep> sound to confirm acceptance of the signal transmis-
sion.
IR Receiver

Cooling Unit LED Indicator Lights

The table shows the LED indicator lights for the air conditioner
unit under normal operation and fault conditions. LED Indicator Lights for Cooling Unit / Heat Pump Unit
The LED indicator lights are located at the middle of the air
conditioner unit.

Sleep mode Cool Timer Ionizer

LED Indicator Lights : Normal Operation And Fault Conditions For Cooling

Normal Operation / Fault Indication Action


COOL/HEAT
(GREEN/RED)

Cool mode –
Green

Timer on –

Sleep mode on –

Ionizer on –

Fan mode on –

Dry mode on –

Room air sensor contact


Call your dealer
1 time Loose / Short

Indoor coil sensor open Call your dealer

Compressor overload /
1 time
Indoor coil sensor short / Call your dealer
Outdoor coil sensor short

3 times
Gas leak Call your dealer

6 times
Hardware error (tact switch pin short) Call your dealer

ON ON or OFF Blinking

8
AIR CONDITIONER UNIT OPERATION

English
Dry Mode Frost Prevention
• When the air humidity is high, the unit can operate in dry • When the air filter is dirty, the evaporating temperature will
mode. Press <MODE> button and choose <DRY>. decrease and eventually cause frosting.
• If the room temperature is 2°C/3.6°F higher than the set • The LED light will blink to indicate that the filter is dirty. If
temperature, the air conditioner will operate under cooling the evaporating temperature reaches -1°C/33.8°F, the unit
mode until it reaches within the 2°C/3.6°F range of will trip and defrost.
difference compared to the set temperature before it converts
Fan Speed And Rated Cooling Capacity
to dry mode.
• If the room temperature is within the 2°C/3.6°F range of • The rated cooling capacity is provided at the maximum fan
difference compared to the set temperature, it will speed.
directly operate under dry mode. • The cooling capacity is lower when the unit is operating at
• The unit will operate at LOW speed under dry mode. MEDIUM and LOW fan speed.

Horizontal Air Flow Control


• For more effective air circulation, you can manually adjust
the air discharge grille to the left or right. Horizontal

Cooling
• During cool mode operation and dry mode operation, do

Dry
not direct the air discharge louver downwards for too long.
25°C/77°F
If operating continues in this way, condensation may occur
on the louver, thus resulting in drippings.

STANDARD OPERATING CONDITIONS

Cooling Unit
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature 19.4 / 66.9 13.9 / 57.0
Maximum indoor
temperature 26.7 / 80.1 19.4 / 66.9
Minimum outdoor
temperature 19.4 / 66.9 13.9 / 57.0
Maximum outdoor
temperature 46 / 114.8 24 / 75.2
Ts: Dry bulb temperature. Th: Wet bulb temperature.

! CAUTION
1. The electrostatic air purifying and deodorizing filter should be replaced once every 6 months or when the
filter changes color to brownish, whichever is sooner.
2. Used dusty filters should be disposed and shouldn't be reused, even if it has been cleaned and washed.
3. The filter is a consumable part which you can purchase from your air conditioner dealer.
4. Use the new filter immediately once it has been taken out from its sealed packing. Do not unpack the new filter too early before
it is actually used as this may decrease its deodorizing effect.

9
INSTALLATION OF UNIT WITH O2 THERAPY FEATURE

3. Insert the end hose to the connector (indoor)

O2 Hose

Refrigerant Piping

2. Insert the end hose to the connector (outdoor)

1. Open valve cover to connecting the


O2 hose

AUTO RANDOM RE-START FUNCTION

If there is a power cut when the unit is operating, it will automatically resume the same operating mode when the power is
restored.

! CAUTION
Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” position to prevent the nuisance
tripping of the unit.
If this is not done, the unit’s fans will start turning automatically when power resumes, posing a hazard to service personnel or the
user.

SERVICE AND MAINTENANCE

! WARNING
• Disconnect from the main power supply before servicing the air conditioner unit.
• DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result
in fire hazards.

Service Parts Maintenance Procedures Period


1. Remove any dust adhering to the filter by using a vacuum cleaner or wash in At least once
lukewarm water (below 40°C/104°F) with a neutral cleaning detergent. every 2 weeks.
Indoor air filter 2. Rinse the filter well and dry before placing it back onto the unit. More frequently if
3. Do not use gasoline, volatile substances or chemicals to clean the filter. necessary.
1. Clean any dirt or dust on the grille or panel by wiping it with a soft cloth At least once
soaked in lukewarm water (below 40°C/104°F) and a neutral detergent every 2 weeks.
Indoor unit solution. More frequently if
2. Do not use gasoline, volatile substances or chemicals to clean the necessary.
indoor unit.

10
English
1 Off the unit.
2 Unscrew the air discharge housing.
3 Flip open the air discharge housing.
4 Clean the blower.
5 Close the air discharge housing and tighten it with screw.

! CAUTION
Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt or deform as
a result of the excessive heat.

When The Unit Is Not To Be Used For An Extended Long Period Of Time

Operate the unit for 2 hours Remove the power plug.


with the following setting. If you are using an independent
electric circuit for your unit,
Operating mode : cool cut off the circuit.
Temperature : 30°C/86°F Remove the batteries in the
remote control.

11
TROUBLESHOOTING

If any malfunction of the air conditioner unit is noted, immediately switch off the power supply to the unit. Check the
following fault conditions and causes for some simple troubleshooting tips.

Fault Causes / Action


1. The compressor does not operate 3 minutes after the air - Protection against frequent starting. Wait for 3 to 4 minutes for the
conditioner unit is started. compressor to start operating.

2. The air conditioner unit does not operate. - Power failure, or the fuse needs to be replaced.
- The power plug is disconnected.
- It is possible that your delay timer has been set incorrectly.
- If the fault persist after all these verifications, please
contact the air conditioner unit installer.

3. The air flow is too low. - The air filter is dirty.


- The doors or windows are open.
- The air suction and discharge are clogged.
- The regulated temperature is not high enough.

4. Discharge air flow has bad odour. - Odours may be caused by cigarettes, smoke particles, perfume etc.
which might have adhered onto the coil.

5. Condensation on the front air grille of the indoor unit. - This is caused by air humidity after an extended long period of
operation.
- The set temperature is too low, increase the temperature setting and
operate the unit at high fan speed.
6. Water flowing out from the air conditioner unit. - Switch off unit and call dealer.
7. Hissing air flow sound from the air conditioner unit during - Refrigerant fluid flowing into the evaporator coil.
operation.

If the fault persists, please call your local dealer / serviceman.

12
English

• In the event that there is any conflict in the interpretation of this manual and any translation of the same in any languages, the
ENGLISH version of this manual shall prevail.
• The manufacturer reserves right to revise any of the specification and design contain herein at any time without prior notification.

OYL MANUFACTURING COMPANY SDN. BHD.


JALAN PENGAPIT 15/19, P.O. BOX 7072, 40702 SHAH ALAM, SELANGOR DARUL EHSAN, MALAYSIA.
13

You might also like