Professional Documents
Culture Documents
Project:__________________________________________ Project No:_________
Associated Equipment:
____ prime mover, ___ generator, ___ fuel system, ____ cooling system, ____ battery
system, ___ exhaust system, ____ ATS, ___ UPS, ____Other______________
1. Participants
Party filling out this form & witnessing _____________________ Date of test
_________
___________________________________ __________
2. Prerequisite Checklist
a. The prefunctional checklist for this emergency power system is complete and
approved:
Yes / No
b. Functional testing is complete and approved for the generator room exhaust
system:
Yes / No
c. All A/E punchlist items for this and related equipment are corrected: Yes / No
d. Sequence of operation is attached: Yes / No
e. These functional test procedures reviewed and approved by installing contractor
and applicable subcontractors: Yes / No
Pass
Step Mode Test Procedure Expected Response
(Y/N)
1 Incremen- Functional Test No. 1: Verify that:
tal
a. Open main switchgear breakers. a. Power has been lost from each
b. Perform test and record data. load served by the emergency
c. At end of test restore normal power power system.
and shut generator down through b. i) Frequency regulation from
normal shutdown procedure. no load to full/rated load is less
than or equal to 3 Hz;
a. Open main switchgear breakers. a. Power has been lost from each
b. Perform test and record data. load served by the emergency
c. At end of test restore normal power power system.
and shut generator down through b. i) Frequency regulation from
normal shutdown procedure. no load to full/rated load is less
than or equal to 3 Hz;
3a Building During 3 hour Cold Start and ATS test, All function properly.
Integrated verify that proper power is delivered to each
Test device listed in the emergency panel
schedule(s) and that they function properly.
Record information on Functional Test
Record 3a.
Comments:
-- END OF SECTION --
03/02 16998-01- OF 3 D:\DOCS\DIV1\03-02\16998-01.DOC