Performance Data For HWP - 36-275Y - ECO
Performance Data For HWP - 36-275Y - ECO
Note: Capacities are gross and do not include allowance for fan motor heat loss. For fan motor heat loss refer to Air Handling Performance.
Water flow and cooling capacity based on 5 °C water temp. difference.
17 23 3.6 2.8 0.22 4.4 3.4 2.6 0.22 4.3 3.3 2.5 0.22 4.2 3.1 2.4 0.22 4.1 3.1 2.3 0.22 4.1 3.0 2.1 0.22 4.1
HWP 36Y 190 19 27 3.8 2.8 0.22 4.7 3.8 2.8 0.22 4.7 3.5 2.8 0.22 4.4 3.4 2.6 0.22 4.4 3.1 2.6 0.22 4.1 3.1 2.5 0.22 4.1
21 31 4.1 3.3 0.22 5.0 4.1 3.3 0.22 5.0 4.0 3.3 0.22 5.1 3.7 3.2 0.22 4.7 3.5 3.2 0.22 4.6 3.3 3.2 0.22 4.4
17 23 4.6 3.6 0.28 5.6 4.4 3.4 0.28 5.4 4.2 3.2 0.28 5.3 4.0 3.1 0.28 5.2 3.9 3.0 0.28 5.2 3.9 2.7 0.28 5.2
HWP 48Y 230 19 27 4.9 3.6 0.28 6.0 4.8 3.6 0.28 6.0 4.4 3.6 0.28 5.6 4.3 3.4 0.28 5.6 4.0 3.3 0.28 5.2 3.9 3.3 0.28 5.2
21 31 5.2 4.2 0.28 6.3 5.2 4.2 0.28 6.3 5.1 4.2 0.28 6.4 4.7 4.1 0.28 6.0 4.5 4.1 0.28 5.8 4.2 4.0 0.28 5.6
17 23 6.1 5.1 0.34 7.6 5.8 4.7 0.34 7.4 5.6 4.5 0.34 7.2 5.3 4.4 0.34 7.0 5.2 4.2 0.34 7.0 5.2 3.8 0.34 7.0
HWP 59Y 320 19 27 6.5 5.1 0.34 8.1 6.5 5.0 0.34 8.1 5.9 5.0 0.34 7.6 5.8 4.7 0.34 7.5 5.3 4.6 0.34 7.0 5.2 4.6 0.34 7.0
21 31 7.0 5.9 0.34 8.6 6.9 5.9 0.34 8.5 6.9 5.8 0.34 8.7 6.3 5.8 0.34 8.1 6.0 5.7 0.34 7.8 5.7 5.6 0.34 7.5
17 23 8.4 6.7 0.50 9.9 7.7 6.2 0.50 9.7 7.7 5.9 0.50 9.8 7.3 5.8 0.50 9.5 7.2 5.5 0.50 9.5 7.1 5.0 0.50 9.4
HWP 79Y 500 19 27 6.7 6.7 0.50 10.6 8.6 6.6 0.50 10.6 8.1 6.6 0.50 10.2 7.9 6.2 0.50 10.2 7.3 6.2 0.50 9.5 7.2 6.0 0.50 9.5
21 31 0.5 7.8 0.50 11.3 9.2 7.8 0.50 11.2 9.5 7.7 0.50 11.7 8.6 7.6 0.50 10.9 8.3 7.5 0.50 10.6 7.8 7.5 0.50 10.2
17 23 10.2 8.3 0.61 12.5 9.7 7.7 0.61 12.2 9.3 7.3 0.61 11.9 8.9 7.1 0.61 11.6 8.7 6.8 0.61 11.5 8.6 6.2 0.61 11.5
HWP 98Y 560 19 27 11.0 8.3 0.61 13.3 10.8 8.1 0.61 13.3 9.9 8.1 0.61 12.5 9.6 7.7 0.61 12.4 8.9 7.6 0.61 11.6 8.7 7.4 0.61 11.6
21 31 11.7 9.6 0.61 14.2 11.6 9.6 0.61 14.1 11.5 9.5 0.61 14.3 10.5 9.4 0.61 13.3 10.0 9.3 0.61 12.9 9.5 9.2 0.61 12.4
Page 10 of 28
Water Cooled air conditioners
ECO Performance Data
Note: Capacities are gross and do not include allowance for fan motor heat loss. For fan motor heat loss refer to Air Handling Performance.
Water flow and cooling capacity based on 5 °C water temp. difference.
17 23 12.7 9.6 0.75 15.5 12.1 8.9 0.75 15.0 11.5 8.5 0.75 14.7 11.0 8.3 0.75 14.3 10.8 7.9 0.75 14.2 10.7 7.2 0.75 14.2
HWP 118Y 620 19 27 13.6 9.7 0.75 16.4 13.4 9.5 0.75 16.4 12.2 9.5 0.75 15.4 11.9 8.9 0.75 15.4 11.0 8.8 0.75 14.3 10.8 8.7 0.75 14.3
21 31 14.5 11.2 0.75 17.5 14.3 11.1 0.75 17.3 14.2 11.1 0.75 17.7 13.0 11.0 0.75 16.4 12.4 10.8 0.75 16.0 11.7 10.7 0.75 15.3
17 23 15.2 11.5 0.88 18.4 14.5 10.7 0.88 17.9 13.8 10.2 0.88 17.6 13.2 10.0 0.88 17.0 13.0 9.5 0.88 17.0 12.9 8.7 0.88 16.9
HWP 142Y 775 19 27 16.3 11.6 0.88 19.5 16.1 11.4 0.88 19.6 14.7 11.3 0.88 18.4 14.3 10.7 0.88 18.3 13.2 10.6 0.88 17.1 13.0 10.4 0.88 17.1
21 31 17.4 13.4 0.88 20.8 17.2 13.4 0.88 20.7 17.1 13.3 0.88 21.0 15.6 13.2 0.88 19.6 14.9 13.0 0.88 19.0 14.1 12.9 0.88 18.3
17 23 19.1 15.4 1.06 23.1 18.2 14.3 1.06 22.4 17.4 13.6 1.06 22.0 16.6 13.3 1.06 21.3 16.4 12.7 1.06 21.3 16.2 11.6 1.06 21.2
HWP 172Y 1015 19 27 20.5 15.4 1.06 24.5 20.2 15.2 1.06 24.5 18.5 15.1 1.06 23.0 18.0 14.3 1.06 22.9 16.6 14.1 1.06 21.4 16.4 13.8 1.06 21.4
21 31 21.9 17.9 1.06 26.1 21.7 17.8 1.06 25.9 21.5 17.7 1.06 26.4 19.6 17.5 1.06 24.5 18.8 17.3 1.06 23.8 17.7 17.1 1.06 22.9
17 23 21.9 17.4 1.26 26.6 20.9 16.2 1.26 25.8 19.9 15.4 1.26 25.4 19.0 15.0 1.26 24.6 18.7 14.4 1.26 24.5 18.5 13.1 1.26 24.4
HWP 192Y 1160 19 27 23.4 17.5 1.26 28.2 23.1 17.2 1.26 28.3 21.2 17.1 1.26 26.5 20.6 16.2 1.26 26.5 19.0 16.0 1.26 24.7 18.7 15.6 1.26 24.7
21 31 25.0 20.2 1.26 30.1 24.8 20.1 1.26 29.9 24.5 20.1 1.26 30.4 22.4 19.8 1.26 28.3 21.4 19.5 1.26 27.5 20.3 19.4 1.26 26.4
17 23 26.4 20.1 1.53 31.6 25.1 18.6 1.53 30.7 24.0 17.8 1.53 30.1 22.9 17.3 1.53 29.2 22.6 16.5 1.53 29.1 22.3 15.1 1.53 29.0
HWP 255Y 1220 19 27 28.3 20.1 1.53 33.5 27.9 19.8 1.53 33.6 25.5 19.7 1.53 31.5 24.9 18.6 1.53 31.4 22.9 18.4 1.53 29.3 22.6 18.0 1.53 29.3
21 31 30.1 23.3 1.53 35.7 29.9 23.2 1.53 35.5 29.6 23.1 1.53 36.1 27.0 22.9 1.53 33.6 25.9 22.5 1.53 32.6 24.4 22.3 1.53 31.3
17 23 28.8 22.0 1.63 34.4 27.1 20.4 1.63 33.4 25.9 19.5 1.63 32.8 24.7 19.0 1.63 31.8 24.3 18.1 1.63 31.7 24.1 16.5 1.63 31.6
HWP 275Y 1400 19 27 30.5 22.1 1.63 36.5 30.1 21.7 1.63 36.6 27.5 21.6 1.63 34.3 26.8 20.4 1.63 34.2 24.7 20.2 1.63 31.9 24.3 19.8 1.63 31.9
21 31 32.5 25.5 1.63 38.9 32.2 25.4 1.63 38.6 31.9 25.3 1.63 39.3 29.1 25.1 1.63 36.6 27.9 24.7 1.63 35.5 26.4 24.5 1.63 34.1
Page 11 of 28
Water Cooled air conditioners
Performance Data - Reverse Cycle Systems
Water Coil
Leaving water temperature (LWT) °C
Flow E.A.T.
Rate D.B. 12.5 15.5 18.5
Model l/s °C HC HAb. EWT INPT HC HAb. EWT INPT HC HAb. EWT INPT
18 3.5 2.6 15.4 0.9 3.7 2.8 18.6 0.9 4.0 3.0 21.8 0.9
HWP 36Y 0.22 21 3.4 2.5 15.3 0.9 3.7 2.7 18.5 1.0 4.0 3.0 21.8 1.0
25 3.4 2.4 15.2 1.0 3.7 2.7 18.4 1.0 3.9 2.9 21.7 1.1
18 4.4 3.3 15.3 1.1 4.7 3.6 18.6 1.1 5.0 3.8 21.8 1.2
HWP 48Y 0.28 21 4.3 3.2 15.3 1.1 4.6 3.5 18.5 1.2 5.0 3.8 21.7 1.2
25 4.3 3.1 15.2 1.2 4.6 3.4 18.4 1.3 5.0 3.6 21.6 1.3
18 5.2 3.7 15.1 1.5 5.5 4.0 18.3 1.6 5.9 4.3 21.5 1.6
HWP 59Y 0.34 21 5.1 3.6 15.0 1.6 5.4 3.8 18.2 1.7 5.9 4.2 21.5 1.7
25 5.1 3.4 14.9 1.7 5.4 3.7 18.1 1.8 5.9 4.0 21.3 1.9
18 8.4 6.5 15.6 1.9 9.0 7.1 18.9 2.0 9.7 7.6 22.1 2.1
HWP 79Y 0.50 21 8.4 6.4 15.5 2.0 8.9 6.9 18.8 2.1 9.7 7.5 22.1 2.2
25 8.4 6.2 15.5 2.2 8.9 6.7 18.7 2.3 9.6 7.2 22.0 2.4
18 10.6 8.2 15.7 2.4 11.3 8.9 18.9 2.4 12.2 9.6 22.2 2.6
HWP 98Y 0.61 21 10.5 8.0 15.6 2.5 11.3 8.7 18.8 2.6 12.1 9.4 22.1 2.7
25 10.5 7.8 15.5 2.7 11.3 8.5 18.8 2.8 12.1 9.1 22.0 2.9
Page 12 of 28
Water Cooled air conditioners
Performance Data - Reverse Cycle Systems
Water Coil
Leaving water temperature (LWT) °C
Flow E.A.T.
Rate D.B. 12.5 15.5 18.5
Model l/s °C H HAb. EWT INPT H HAb. EWT INPT H HAb. EWT INPT
18 10.9 8.0 15.1 2.9 11.7 8.7 18.3 3.0 12.5 9.4 21.5 3.2
HWP 118Y 0.75 21 10.8 7.8 15.0 3.1 11.6 8.4 18.2 3.2 12.5 9.1 21.4 3.4
25 10.8 7.5 14.9 3.3 11.6 8.2 18.1 3.5 12.4 8.8 21.3 3.6
18 14.1 10.8 15.4 3.3 15.1 11.7 18.0 3.4 18.0 13.6 21.5 4.4
HWP 142Y 0.88 21 14.0 10.6 15.4 3.5 14.5 11.4 18.0 3.7 16.2 12.4 21.9 3.8
25 14.0 10.2 15.3 3.8 14.5 11.1 18.5 3.9 16.1 12.0 21.8 4.1
18 15.7 11.6 15.0 4.1 16.8 12.6 18.2 4.2 18.0 13.3 21.5 4.4
HWP 172Y 1.06 21 15.6 11.3 15.0 4.3 16.7 12.2 18.1 4.2 18.0 13.6 21.4 4.7
25 15.5 10.9 14.9 4.6 16.7 11.8 18.1 4.5 17.9 13.3 21.3 5.1
18 17.4 12.6 14.9 4.9 18.7 13.6 18.1 4.9 20.0 12.8 21.3 5.3
HWP 192Y 1.26 21 17.3 12.2 14.8 5.1 18.6 13.2 18.0 5.4 20.0 14.3 21.2 5.6
25 17.3 11.7 14.7 5.6 18.6 12.7 17.9 5.8 19.8 13.8 21.1 6.1
18 21.5 16.5 15.1 4.9 23.0 17.9 18.3 5.1 24.7 19.3 21.5 5.4
HWP 255Y 1.53 21 21.3 16.1 15.0 5.2 23.0 17.4 18.2 5.4 24.6 18.9 21.5 5.7
25 21.2 15.6 14.9 5.6 22.8 17.0 18.2 5.9 24.4 18.3 21.4 6.1
18 23.0 17.2 15.0 5.9 24.7 18.6 18.2 6.1 26.5 20.1 21.4 6.4
HWP 275Y 1.63 21 22.9 16.7 14.9 6.2 24.5 18.0 18.1 6.5 26.4 19.6 21.4 6.8
25 22.8 16.1 14.9 6.7 24.5 17.5 18.1 7.0 26.2 18.9 21.3 7.3
Page 13 of 28
Water Cooled air conditioners
ECO Performance Data
AIR HANDLING
Airflows are for a dry coil. Reduce airflow by 10% in high moisture removal conditions. In a free blow application, beware of exceeding fan
motor’s full load amp limit. Refer page 13 for filter losses. Air flows given are for HWP units without filter installed.
INPUT (W)
INPUT (W)
150 150
8V 8V
100 100
6V 6V
50 50
4V 4V
0 0
100 150 200 250 300 350 100 150 200 250 300 350
NOMINAL NOMINAL
AIR FLOW (l/s) 2.5 m/s Face Velocity AIR FLOW (l/s) 2.5 m/s Face Velocity
INPUT (W)
INPUT (W)
10V
250 400
8V
200 250 8V 300
150 200
6V
6V
200 100 200 100
4V 10V
50
150 150
EXTERNAL PRESSURE (Pa)
EXTERNAL PRESSURE (Pa)
10V
8V 8V
100 100
6V
6V
50 50
4V
0 0
200 250 300 350 400 450 200 300 400 500 600 700
NOMINAL
AIR FLOW (l/s) 2.0 m/s Face Velocity AIR FLOW (l/s) NOMINAL 2.5 m/s Face Velocity
10V 10V
INPUT (W)
400 700
200 500
6V 8V
200 100 400 400
10V 6V 300
10V
8V 200
100
8V
6V 100
50
6V
0 0
200 300 400 500 600 700 400 450 500 550 600 650
NOMINAL
AIR FLOW (l/s) NOMINAL 2.5 m/s Face Velocity AIR FLOW (l/s) 2.3 m/s Face Velocity
Page 14 of 28
Water Cooled air conditioners
ECO Performance Data
INPUT (kW)
INPUT (W)
10V 10V
700 1.2
8V
600 1.0
8V
500 0.8
6.5V
6.5V
400 400 400 0.6
300 0.4
10V 10V
300
8V 8V
200 200
6.5V 6.5V
100 100
0 0
400 500 600 700 800 900 400 600 800 1000 1200 1400
NOMINAL
AIR FLOW (l/s) 2.5 m/s Face Velocity AIR FLOW (l/s) NOMINAL 2.5 m/s Face Velocity
INPUT (kW)
INPUT (kW)
10V 10V
1.0 1.0
8V
8V
0.8 0.8
0.6 6V 0.6
9V
8V 8V
200 200
6V 6V
100 100
4V
0 0
400 600 800 1000 1200 1400 400 600 800 1000 1200 1400
NOMINAL NOMINAL
AIR FLOW (l/s) 2.5 m/s Face Velocity AIR FLOW (l/s) 2.5 m/s Face Velocity
HWP 275Y
HWP 275Y
l/s - Pa ---- l/s - W Note
1.2
INPUT (kW)
Page 15 of 28
Water Cooled air conditioners
Performance Data
Model: HWP 118 HWP 142 HWP 172 HWP 192 HWP 255 HWP 275
THR 15.4 18.4 23.0 26.5 31.5 34.3
Water Temp Water Press Water Press Water Press Water Press Water Press Water Press
Difference Flow Drop Flow Drop Flow Drop Flow Drop Flow Drop Flow Drop
K l/s kPa l/s kPa l/s kPa l/s kPa l/s kPa l/s kPa
5.0 0.75 55.0 0.88 69.0 1.06 83.0 1.26 34.0 1.53 48.00 1.63 55.00
5.5 0.67 43.9 0.80 57.1 1.00 74.0 1.16 28.5 1.40 40.48 1.49 46.25
6.0 0.61 36.9 0.73 48.0 0.92 62.1 1.06 24.1 1.28 34.01 1.37 38.86
6.5 0.57 31.4 0.68 40.9 0.85 53.0 0.98 20.5 1.19 28.98 1.26 33.11
7.0 0.53 27.1 0.63 35.2 0.79 45.6 0.91 17.7 1.10 24.99 1.17 28.55
7.5 0.49 23.6 0.59 30.7 0.73 39.8 0.85 15.4 1.03 21.77 1.09 24.87
Min. water flow 0.21 4.3 0.24 5.1 0.30 6.7 0.35 2.6 0.43 3.82 0.46 4.40
Page 16 of 28
Water Cooled air conditioners
Performance Data
SOUND LEVELS
Test Conditions:
Sound Power Levels (SWL) SPL measured to JIS 8616 (1m from source in an anechoic chamber)
10 V 51 62 61 63 57 58 54 49
8V 51 62 61 64 57 58 54 49
HWP 59Y
6V 44 55 56 56 50 50 47 41
4V 34 45 51 48 40 39 35 30
10 V 60 71 67 68 66 67 64 60
8V 55 66 63 62 61 62 59 54
HWP 79Y
6V 47 58 56 55 54 54 50 45
4V 36 47 50 46 44 43 38 32
10 V 60 71 68 69 66 67 64 60
8V 54 65 63 62 60 61 57 53
HWP 98Y
6V 35 46 55 53 53 53 49 43
4V 35 46 48 45 42 42 38 29
10 V 63 74 71 70 68 70 68 66
8V 60 71 68 66 66 66 64 62
HWP 118Y
6V 52 63 61 59 59 58 55 53
4V 29 40 53 49 48 47 43 39
10 V 61 72 69 69 68 68 65 63
8V 61 72 69 69 68 68 65 63
HWP 142Y 6.5 V 59 70 67 66 66 65 63 60
6V 57 68 66 64 65 63 60 58
4V 44 55 56 53 54 50 47 42
Page 17 of 28
Water Cooled air conditioners
Performance Data
SOUND LEVELS
Test Conditions:
Sound Power Levels (SWL) SPL measured to JIS 8616 (1m from source in an anechoic chamber)
Page 18 of 28
Water Cooled air conditioners
Performance Data
8V 39 50 51 49 45 45 44 40
HWP 36Y
6V 35 46 47 44 41 42 39 34
4V 29 40 45 42 36 35 31 24
10 V 40 51 50 50 46 47 45 41
8V 39 50 51 49 45 45 44 40
HWP 48Y
6V 35 46 47 44 41 42 39 34
4V 29 40 45 42 36 35 31 24
10 V 41 52 51 54 47 48 44 39
8V 41 52 51 54 47 48 44 39
HWP 59Y
6V 37 48 49 49 43 43 40 34
4V 30 41 47 43 36 35 31 25
10 V 48 59 55 56 54 55 52 48
8V 45 56 53 52 51 52 49 44
HWP 79 Y
6V 40 51 49 48 47 47 43 38
4V 32 43 46 42 40 39 39 28
10 V 48 59 56 57 54 55 52 48
8V 44 55 53 52 50 51 47 43
HWP 98Y
6V 39 50 48 46 46 46 42 36
4V 31 42 44 41 38 38 34 25
10 V 51 62 59 58 56 58 55 54
8V 50 61 58 56 56 56 54 52
HWP 118Y
6V 45 56 54 52 52 51 48 46
4V 36 47 49 45 44 43 39 34
10 V 51 62 59 58 56 58 55 53
8V 51 62 59 58 58 58 55 53
6V 50 61 59 57 58 56 53 51
4V 40 51 52 49 50 46 43 38
Page 19 of 28
Water Cooled air conditioners
Performance Data
8V 54 65 56 60 61 61 57 55
6V 49 60 55 56 58 56 52 50
4V 41 52 51 49 51 47 43 39
10 V 52 63 62 59 58 59 56 54
8V 53 64 63 61 60 60 57 55
HWP 192Y
6V 48 59 60 57 56 54 52 49
4V 40 51 54 49 48 46 43 38
10 V 55 66 67 64 61 61 57 56
8V 55 66 67 64 61 61 57 56
HWP 255Y 7V 52 63 65 62 59 59 55 53
6V 51 62 64 65 59 56 53 50
4V 41 52 57 51 51 47 44 39
8V 56 67 66 64 62 62 59 58
7V 54 65 65 62 60 60 57 56
5V 48 59 61 56 57 53 51 49
4V 43 54 58 52 52 48 47 43
Page 20 of 28
Water Cooled air conditioners
Performance Data
8V 50 61 66 63 56 53 54 50
HWP 36Y
6V 44 55 61 56 50 48 47 43
4V 40 51 58 52 46 44 43 43
10 V 52 63 68 66 59 56 56 53
8V 50 61 66 63 56 53 54 50
HWP 48Y
6V 44 55 61 56 50 48 47 43
4V 40 51 58 52 46 44 43 43
10 V 53 64 71 66 60 58 54 50
8V 43 64 70 65 60 58 54 50
HWP 59Y
6V 48 59 68 60 56 51 47 41
4V 44 55 66 58 54 44 38 33
10 V 56 67 68 68 63 62 60 55
8V 51 62 65 62 58 58 55 49
HWP 79Y
6V 45 56 62 56 53 51 48 42
4V 41 52 61 50 50 43 42 39
10 V 56 67 69 68 62 62 60 55
8V 51 62 64 62 57 57 55 48
HWP 98 Y
6V 45 56 61 55 52 51 48 42
4V 41 52 58 50 50 44 43 41
10 V 58 69 70 69 65 64 61 58
8V 55 66 68 66 62 61 58 55
HWP 118Y
6V 48 59 63 59 56 54 51 47
4V 42 53 59 55 50 45 42 42
10 V 57 68 68 67 6 63 60 56
8V 56 67 69 67 64 63 59 55
6V 53 64 65 64 61 59 56 51
4V 46 57 59 56 54 52 48 42
Page 21 of 28
Water Cooled air conditioners
Performance Data
8V 60 71 74 70 68 67 63 60
6V 53 64 67 64 61 58 55 51
4V 44 55 61 55 53 50 47 43
10 V 60 71 76 73 66 66 64 60
8V 60 71 75 72 66 65 63 60
HWP 192Y
6V 53 64 69 65 60 58 56 53
4V 47 58 61 56 56 51 49 48
10 V 59 70 77 71 67 64 62 59
8V 59 70 77 71 67 64 62 59
HWP 255Y 7V 55 66 71 67 63 60 57 54
6V 53 64 71 65 61 58 55 52
4V 44 55 62 55 53 49 46 41
8V 62 73 78 72 69 68 65 61
7V 60 71 78 70 68 66 63 61
5V 53 64 71 62 62 57 56 53
4V 49 60 65 57 58 54 53 49
Page 22 of 28
Water Cooled air conditioners
Performance Data
4. If generous duct size is not possible, use turning vanes on bends to reduce
air turbulence (regenerated noise). TURNING
VANES
5. Use 90° bends in ducting to significantly assist in noise reduction. MINIMUM OF 1 m
25 mm INSULATED DUCT
FLEXIBLE CONNECTION
SUSPENDED CEILING
SUPPLY AIR RETURN AIR GRILLE LOCATED ALTERNATIVE FILTER LOCATION
GRILLE AWAY FROM UNIT TO MINIMISE WITH SWING OPENING GRILLE
NOISE TRANSMISSION FOR EASY SERVICING
Page 23 of 28