1 Grid Islanding - Generator & Grid Response. Voltage Level
2 4.3 MW Generator Tripping - Rest generators response 3 10 MW Generator Tripping - Rest generators response 4 80 MW Generator Tripping - Rest generators response 5 5.4 MW Generator Tripping with grid - Rest generators response 6 5.4 MW Generator Tripping - Rest generators response 7 Inhouse generator (5No) Trip - Grid response 8 Highest motor starting - Generator & Grid Response 9 2 Highest motor starting - Generator & Grid Response 10 LLLG Fault on RRVPNL GRID - Generator & Grid Response 220 11 LLLG Fault on PLANT MAIN BUS - Generator & Grid Response 220 12 LLLG Fault on CELL HOUSE BUS 2 - Generator & Grid Response 33 13 LLLG Fault on RDMN 4 - Generator & Grid Response 11 14 LLLG Fault on CPP UNIT 1 BUS - Generator & Grid Response 11 15 LLLG Fault on STG BUS - Generator & Grid Response 11 16 LLLG Fault on MRBUS 2A - Generator & Grid Response 11 17 LLLG Fault on LPMain_B - Generator & Grid Response 11 18 LLLG Fault on CDSS_A - Generator & Grid Response 11 19 LLLG Fault on RSTRGEN - Generator & Grid Response 11 20 LLLG Fault on ROASTERA - Generator & Grid Response 21 LLLG Fault on ROASTERB - Generator & Grid Response 22 LLLG Fault on SKM62 - Generator & Grid Response 23 LLLG Fault on STATN_C2- Generator & Grid Response 6.6 24 LLLG Fault on UNITB1A - Generator & Grid Response 6.6 25 LLLG Fault on RSTR3A - Generator & Grid Response 3.3 26 LLLG Fault on PCC118B - Generator & Grid Response 0.415 27 LLLG Fault on RSTRPC2A - Generator & Grid Response 28 LLLG Fault on New 5.6MW Generator Bus - Generator & Grid Response 11 29 LLLG Fault on grid bus - Genrator response 220 30 LLLG Fault on PCC Lead Plant - Generator response 0.415
# Sensitivity: Internal (C3)
Documents required Critical Cases Priliminary cases Final Cases Load shedding scheme yes yes Load shedding scheme no yes Load shedding scheme no yes Load shedding scheme no yes yes yes Load shedding scheme no yes yes yes no yes no yes yes yes 80ms yes yes 80ms yes yes this is actually 33kV switchgear Bus at MRSS no no no yes yes yes R4 STG Bus yes yes this is actually 11kV switchgear Bus at MRSS yes yes 80ms no no no yes R5 STG Bus no no no no no no yes yes 1s no yes 2s no yes no yes no no yes yes 1.08 yes yes GRID FAR END yes yes 1s
# Sensitivity: Internal (C3)
switchgear Bus at MRSS
switchgear Bus at MRSS 1s
# Sensitivity: Internal (C3)
S.no Description Voltage CCT CPP-1 CPP-1 STG-1 (80MW) (80MW) 1 LLLG Fault on LPMain_B - Generator Response 11KV 70ms 700ms 700ms 2 LLLG Fault on MRBUS 2A - Generator Response 11KV >1s 690ms 690ms LLLG Fault on New 5.4MW Generator Bus - 3 Generator Response 11KV 75ms 690ms 690ms LLLG Fault on PCC Lead Plant - Generator 4 response 415 V >1s - - LLLG Fault on PLANT MAIN BUS - Generator 5 Response 220 KV 80ms 300ms 300ms LLLG Fault on RRVPNL GRID - Generator 6 Response 220 KV >1s 370ms 370ms 7 LLLG Fault on STATN_C2- Generator Response 6.6 KV >1s >1s >1s 8 LLLG Fault on UNITB1A - Generator 6.6 KV >1s >1s >1s CCT 4.3MW STG 10MW STG