SN Cases Description

1 Grid Islanding - Generator & Grid Response. Voltage Level


2 4.3 MW Generator Tripping - Rest generators response
3 10 MW Generator Tripping - Rest generators response
4 80 MW Generator Tripping - Rest generators response
5 5.4 MW Generator Tripping with grid - Rest generators response
6 5.4 MW Generator Tripping - Rest generators response
7 Inhouse generator (5No) Trip - Grid response
8 Highest motor starting - Generator & Grid Response
9 2 Highest motor starting - Generator & Grid Response
10 LLLG Fault on RRVPNL GRID - Generator & Grid Response 220
11 LLLG Fault on PLANT MAIN BUS - Generator & Grid Response 220
12 LLLG Fault on CELL HOUSE BUS 2 - Generator & Grid Response 33
13 LLLG Fault on RDMN 4 - Generator & Grid Response 11
14 LLLG Fault on CPP UNIT 1 BUS - Generator & Grid Response 11
15 LLLG Fault on STG BUS - Generator & Grid Response 11
16 LLLG Fault on MRBUS 2A - Generator & Grid Response 11
17 LLLG Fault on LPMain_B - Generator & Grid Response 11
18 LLLG Fault on CDSS_A - Generator & Grid Response 11
19 LLLG Fault on RSTRGEN - Generator & Grid Response 11
20 LLLG Fault on ROASTERA - Generator & Grid Response
21 LLLG Fault on ROASTERB - Generator & Grid Response
22 LLLG Fault on SKM62 - Generator & Grid Response
23 LLLG Fault on STATN_C2- Generator & Grid Response 6.6
24 LLLG Fault on UNITB1A - Generator & Grid Response 6.6
25 LLLG Fault on RSTR3A - Generator & Grid Response 3.3
26 LLLG Fault on PCC118B - Generator & Grid Response 0.415
27 LLLG Fault on RSTRPC2A - Generator & Grid Response
28 LLLG Fault on New 5.6MW Generator Bus - Generator & Grid Response 11
29 LLLG Fault on grid bus - Genrator response 220
30 LLLG Fault on PCC Lead Plant - Generator response 0.415

# Sensitivity: Internal (C3)


Documents required Critical Cases Priliminary cases Final Cases
Load shedding scheme yes yes
Load shedding scheme no yes
Load shedding scheme no yes
Load shedding scheme no yes
yes yes
Load shedding scheme no yes
yes yes
no yes
no yes
yes yes 80ms
yes yes 80ms
yes yes this is actually 33kV switchgear Bus at MRSS
no no
no yes
yes yes R4 STG Bus
yes yes this is actually 11kV switchgear Bus at MRSS
yes yes 80ms
no no
no yes R5 STG Bus
no no
no no
no no
yes yes 1s
no yes 2s
no yes
no yes
no no
yes yes 1.08
yes yes GRID FAR END
yes yes 1s

# Sensitivity: Internal (C3)


switchgear Bus at MRSS

switchgear Bus at MRSS 1s

# Sensitivity: Internal (C3)


S.no Description Voltage CCT
CPP-1 CPP-1
STG-1
(80MW) (80MW)
1 LLLG Fault on LPMain_B - Generator Response 11KV 70ms 700ms 700ms
2 LLLG Fault on MRBUS 2A - Generator Response 11KV >1s 690ms 690ms
LLLG Fault on New 5.4MW Generator Bus -
3 Generator Response 11KV 75ms 690ms 690ms
LLLG Fault on PCC Lead Plant - Generator
4 response 415 V >1s - -
LLLG Fault on PLANT MAIN BUS - Generator
5 Response 220 KV 80ms 300ms 300ms
LLLG Fault on RRVPNL GRID - Generator
6 Response 220 KV >1s 370ms 370ms
7 LLLG Fault on STATN_C2- Generator Response 6.6 KV >1s >1s >1s
8 LLLG Fault on UNITB1A - Generator 6.6 KV >1s >1s >1s
CCT
4.3MW STG 10MW STG

790ms 660ms
300ms 690ms

300ms 690ms

- -

300ms 350ms

370ms 370ms
>1s >1s
>1s >1s