Installation

Compact and Modular Bases Mounting Positions

Introduction
This section shows the correct and incorrect mounting positions for all bases.
NOTE: Keep adequate spacing for proper ventilation and to maintain an ambient
temperature between 0° C (32° F) and 55° C (131° F).

CAUTION
EQUIPMENT OVERHEATING
Do not place heat generating devices such as transformers and power supplies
underneath the controllers or expansion I/O modules.
Failure to follow these instructions can result in injury or equipment damage.

Correct Mounting Position for all Bases


Compact and Modular bases must be mounted horizontally on a vertical plane as
shown in the figures below.

Additional Permitted Mounting Positions for Compact Bases


Where the ambient temperature will not exceed 40° C (104° F), the compact bases
may be mounted sideways on a vertical place as shown below:

40 35011387 06/2011