Packaged Pump Sets

FOR DIESEL FUEL OIL APPLICATION


®
Packaged Pump Sets for Diesel/Fuel Oil Application

Description
Simplex SPS Series Packaged Pump
Sets are pre-engineered, integrated
systems of pumps, pump drivers, con-
trols and accessories, pre-plumbed and
pre-wired, totally contained within an
enclosure equipped with a leak detec-
tion basin. External ports are provided
for connection of field plumbing. Four
models are available spanning from 2
GPM through 36 GPM, simplex, duplex,
triplex or quadplex pumps; 0.33 through
7.5 HP and are suitable for wall or pad
mounting. Isolated compartments are
provided for mechanical and electri-
cal devices. Full system integration of
pumps, starters, controls, tank moni-
tors, tank level controls, external alarm
panels is provided.
SPS-10-SS Packaged Pump Set
If requirements exceed the capacity of
an SPS enclosure, pump sets can be specified
• Pump disconnect circuit upon leak detection
skid-mounted. Simplex SKS Series Skid Pump
Sets offer the customer a greater variety and • Inlet, outlet and pressure relief manifolds
quantity of options but because of the open (SPS Series only)
catch basin design they are suitable for indoor
installation only. • Fuel connections made to fittings in sidewalls
(SPS Series only)
Simplex Packaged Pump Sets are intended for
use with fuel oil or lube oil. • High performance hydraulic gear pumps

• Pump shutoffs available

Features • Industrial motors

• System engineered, integrated function • Motor starter with overload relay and discon-
packages nect available

• TYPE 1 indoor enclosure, primed and • Disconnect switch interlocked with hinged
painted door

• TYPE 3R weatherproof enclosure, primed • Simplex, duplex, triplex, quadplex pumps


and painted, available available

• Wall or pad mountable • Automatic duplex pump controllers available

• Segregated electrical/mechanical compart- • “Tank Commander” tank monitors, PLC


ments within enclosure Control, level controllers, annunciators, fill
panels, overfill panels are available as op-
• Enclosure drip pan and leak detector tions
• Pressure relief valve, external port for relief to • Packaged Pump Sets can be engineered
tank available with Simplex Main Storage Tanks, Day Tanks
and Fuel Supply Systems

Simplex Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 (24 Hr.) • Fax 217-483-1616 • www.simplexdirect.com
© 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA • 1101-01.00 • Design subject to change without notice. • Page 2
®
Packaged Pump Sets for Diesel/Fuel Oil Application

MODEL SINGLE DUPLEX TRIPLEX QUADPLEX Application


SPS-10 10GPM-¾HP N/A N/A N/A Guide
SPS-25 25GPM-1½HP 17GPM-1HP 2GPM-½HP N/A

SPS-55 35GPM-5HP 25GPM-2HP 7GPM-1HP 2GPM-½HP

CHOOSING A PUMP CHOOSING A MODEL


Super-XL Pump SPS-10
for applications where the pump starts and simple single pump applications
stops on demand, such as for automatic
tank refilling. Use for viscosity to 1000 SSU.
Use also for high pressure applications up SPS-25
to 2500 PSI. Do not use for noise sensitive complex single pump applications involv-
applications. ing starters and level controllers
– or –
Series 420 & 500 Pumps simple duplex and triplex pump applica-
(cast iron gear) for continuous duty ap- tions involving starters and duplex con-
plications where the pump runs nonstop troller
for extended periods of time. Use for boiler
feed loop applications. Use also for noise
sensitive applications. Viscosity from 32 to SPS-55
5000 SSU or higher with slow speed motor. complex and large, single pump applica-
tions involving starters and level controls
– or –
complex duplex, triplex, quadplex pump
applications involving starters and con-
trollers

SKS
size and complexity is dependent on avail-
able site space, rated TYPE 1 indoor

WARNING: These Pump Sets are not


intended for use with gasoline or other flam-
mable liquids having a flash point less than
100°F. Use with gasoline or use with any
flammable liquids at a temperature exceed-
ing the flash point of that liquid, presents
an immediate explosion and fire hazard.
Do not use the Pump Set at a temperature
exceeding the flash point of its contents.

SPS-25-SD Mechanical Compartment

Simplex Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 (24 Hr.) • Fax 217-483-1616 • www.simplexdirect.com
© 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA • 1101-01.00 • Design subject to change without notice. • Page 3
®
Packaged Pump Sets for Diesel/Fuel Oil Application

Standard SPS-10 SPS-25 SPS-55

Equipment SINGLE Basic (-BS) X X X

List Super (-SS) X X X

DUPLEX Basic (-BD) X X

NOTE: All Standard Super (-SD) X X


Pump Sets include
Engineer Specifications (-ED) X
Super-XL 2GPM, 1/3HP,
115V AC pumps and
containment sump with SINGLE PUMP DUPLEX PUMP
leak sensor. Optional
pumps and motors are
available. Consult Sim-
Basic (-BS) Basic (-BD)
plex for cabinet size • Super-XL 2GPM, 1/3HP, 115V AC pump • Super-XL 2GPM, 1/3HP, 115V AC pump
when multiple options • Opt. 191, containment sump leak sensor • Opt. 345, automatic duplex pump controller
are required. • Opt. 070, check valve
Super (-SS) • Opt. 087, shut-off valves on inlet and outlet
• Super-XL 2GPM, 1/3HP, 115V AC pump • Opt. 191, containment sump leak sensor
• Opt. 260, door mounted disconnect switch Super (-SD)
with interlock
• Super-XL 2GPM, 1/3HP, 115V AC pump
• Opt. 768, single-phase starter with coil wired
• Opt. 345, automatic duplex pump controller
to terminal block
• Opt. 070, check valve
• Opt. 087, shut-off valves on inlet and outlet
• Opt. 260, door mounted disconnect switch
• Opt. 095, pressure relief valve with interlock
• Opt. 070, check valve • Opt. 768, single-phase starter
• Opt. 191, containment sump leak sensor • Opt. 087, shut-off valves on inlet and outlet
• Opt. 095, pressure relief valve
• Opt. 191, containment sump leak sensor

Engineer Specifications (-ED)


• Super-XL 2GPM, 1/3HP, 115V AC pump
• Opt. 345, automatic duplex pump controller
• Opt. 070, check valve
• Opt. 260, door mounted disconnect switch
with interlock
• Opt. 768, single-phase starter
• Opt. 087, shut-off valves on inlet and outlet
• Opt. 095, pressure relief valve
• Opt. 060, fuel strainer
• Opt. 100, pressure gauge with isolation hand
valve, each pump outlet
• Opt. 101, vacuum gauge with isolation hand
valve, each pump inlet
• Opt. 285, loss of flow alarm/lag pump acti-
vate
• Opt. 191, containment sump leak sensor

Simplex Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 (24 Hr.) • Fax 217-483-1616 • www.simplexdirect.com
© 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA • 1101-01.00 • Design subject to change without notice. • Page 4
®
Packaged Pump Sets for Diesel/Fuel Oil Application

Description Features
• Pressure loaded design
SUPER-XL
The Simplex SUPER-XL is a high-technology
hydraulic pump featuring pressure-loaded, self- • Efficient, simple design with few moving parts Pumps
compensating gears and a mechanical shaft seal. • Exceptionally compact and lightweight for their
The SUPER-XL is the capacity
standard pump used
• Efficient at high pressure operation
in Simplex Packaged
Pump Sets and • Resistant to cavitation effects
is available in • High tolerance to system contamination
2-25 GPM ca-
• Reliable under cold weather operation
pacity range.
• Sleeve bearing construction
• Multi-Fluid compatibility

Flow, GPM (LPM)

PUMP DISPLACEMENT RPM 100 PSI 1000 PSI 1500 PSI 2000 PSI 2500 PSI
MODEL IN3 (CC/REV.) (6.9 Bar) (69 Bar) (103 Bar) (138 Bar) (172 Bar)

SUPER .262 1800 1.99 1.86 1.79 1.73 1.66


XL-11 (4.29) (7.54) (7.05) (6.78) (6.56) (6.29)

SUPER .942 1800 7.08 6.87 6.77 6.66 6.56


XL-39 (15.44) (26.83) (26.04) (25.66) (25.24) (24.86)

SUPER 1.47 1800 11.10 10.81 10.70 10.60 10.40


XL-62 (24.14) (42.07) (40.97) (40.55) (40.17) (39.42)

SUPER 2.23 1800 16.70 16.50 16.30


XL-90 (36.5) (63.29) (62.54) (61.78)

SUPER 3.35 1800 25.30 24.90 24.60 24.40


XL-114 (54.9) (95.89) (94.37) (93.23) (92.48)

Simplex Series 420 & 500 internal gear rotary


pumps are used for lubricating, low pressure
equipped with a mechanical seal. With optional
seals available in a number of different materials, Series
hydraulic, transfer, circulating, burner oil and
many other industrial pump applications.
these pumps can meet almost any temperature
or fluid compatibility requirement. 420 & 500
Precisely machined and assembled with only
two moving parts, they achieve and retain their
A wide range of configurations with capabilities
from 1.8GPM to 35GPM is available.
Pumps
reliability over a wider range of viscosities than There are only two moving parts. Pumping ac-
alternative pump designs. And they’re substan- tion is based on a rotor, idler gear and crescent-
tially quieter than other pump designs. shaped partition cast integral with the cover.
All rotors are precision milled and ground. All Optional automatic reversing is available.
models have bushing support provided for Models 420, 422, and 424 are UL Listed.
the rotor shaft for added reliability. Pumps are

MATERIALS OF CONSTRUCTION

IDLER
HOUSING COVER ROTOR IDLER PIN SEAL

MECHANICAL
CAST CAST STEEL IRON HARDENED CARBON RING
IRON IRON STEEL NI-RESIST OR
CERAMIC SEAL

Simplex Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 (24 Hr.) • Fax 217-483-1616 • www.simplexdirect.com
© 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA • 1101-01.00 • Design subject to change without notice. • Page 5
®
Packaged Pump Sets for Diesel/Fuel Oil Application

Dimensions and Key Features


SPS-10 23.1” 1.187”

1. Pressure Relief Outlet, 6


¾" NPT Male 4.5”

2. Pump Inlet, ¾" NPT Male 13.875” 11”


4.5”
3. Pump Outlet, ¾" NPT Male
4. Customer Conduit Entry,
0.5”
½" NPT 21.35”
5. Vent Louvers TOP VIEW
6. Mounting Holes (6),
20”
.437" x .875" Dia. 4
7. Ground Stud 7 11
8. Motor 5

9. Pump 8
10. Fuel Line Leak Sensor
11. Mounting Holes (12),
6 2
8 4

0 1

12
.437" x .875" Dia. 9
23” 32.575”
12. Lockable Latch
13. Sump Drain Plug
10

4” 1.5”TYP.
2”
1 2 3 21.60” 13
SIDE VIEW FRONT VIEW LESS DOOR FRONT VIEW

SPS-25 12 13 14 2.4”

1. Main Disconnect Switch 11


5.5”
2. Ball Valve (4), Opt. 087 15.658”
5.5”
3. Check Valve (2), Opt. 070
4. Fuel Line Leak Sensor 33.375”
5. Sump Drain Plug 34.85”
6. Pump (2) TOP VIEW WITHOUT CONTROL PANEL
7. Motor (2)
8. Drip Pan
9. Fuel Strainer (2), Opt. 060
10. Junction Box 1
ON

11. Mounting Holes (6),


.437" x .875" Dia. 15 17
12. Pump Outlet, 1" NPT Male 10 18
16
13. Pressure Relief Outlet,
1" NPT Male 2 9
70.692”
14. Pump Inlet, 1" NPT Male 2 2 9
15. Wall Mounting Holes (14), 48”
.437" x .875" Dia.
3 16
16. Lockable Latch (2) 8 18
17. Customer Conduit Entry, 6 7
1½" and 1" NPT, both sides 7.5” TYP.
18. Vent Louvers, both sides
4.5” 3”
4 5 33.375”
34.85” 14” .675”

FRONT VIEW WITHOUT DOORS FRONT VIEW SIDE VIEW

Simplex Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 (24 Hr.) • Fax 217-483-1616 • www.simplexdirect.com
© 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA • 1101-01.00 • Design subject to change without notice. • Page 6
®
Packaged Pump Sets for Diesel/Fuel Oil Application

SPS-55 2 3 4 2.479”

1
1. Mounting Holes (12), .437" x .875" Dia. 7.5”
2. Pump Outlet, 1" NPT 19.843”
3. Pressure Relief Outlet, 1" NPT 7.5”

4. Pump Inlet, 1.5" NPT


5. Weatherproof Outer Door, Opt. 181 56.25”
57.7”
6. Wall Mounting Holes (14) - .437" x .875" Dia. TOP VIEW WITHOUT CONTROL PANEL
7. Ball Valve (3), Opt. 087
8. Check Valve - Opt. 070 56.474”
55”
9. Fuel Strainer, Opt. 060
10. Junction Box
5
11. Pressure Relief Valve, Opt. 095
12. Pump (2)
13. Motor (2) 6
10
18
7 16
14. Sump Drain Plug 19
15. Fuel Line Leak Sensor 7 16
16. Fuel Strainer (2), Opt. 060 11 17
72.025”

17. Drip Pan 7


50”
18. Vent Louvers, both sides 12
8
19. Lockable Latch 9
13

20. Latch (3)


20
12
7.5” TYP.
13 3.036”
3” 3”
14 15 18” .904”

FRONT VIEW WITHOUT DOORS SIDE VIEW

SKS-10 54”
48”
1. Mounting Holes (4), ¾" 1

2. Motor
3. Pump
4. Pump Outlet, Ball Valve, ¾" NPT 20”
5. Pump Inlet, Ball Valve, ¾" NPT
6. Sump Drain, Both Sides (2), ½" NPT
7. Fuel Line Leak Sensor 2”
1.5” 51”

TOP VIEW WITHOUT CONTROLLER

46.5”±1”

2 3 4 5
29”

FLOW

3”
2”
3”

24” 6 7

SIDE VIEW FRONT VIEW

Simplex Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 (24 Hr.) • Fax 217-483-1616 • www.simplexdirect.com
© 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA • 1101-01.00 • Design subject to change without notice. • Page 7
®
Packaged Pump Sets for Diesel/Fuel Oil Application

SKS-30 1 3”
59”
53”
1. Mounting Holes (4), ¾" 3 3
2. Pressure Relief Outlet, ¾" NPT Male 2 2
3. Motor (2)
4. Pump (2) 5 6 7
28”
5. Ball Valve (4), Opt. 087
6. Fuel Strainer (2), Opt. 060 4 4
5 6

7. Auxiliary Inlet, 1" NPT


8. Pump Unit Outlet, 1" NPTM 2”
9. Check Valve (2), Opt. 070 1.5” 56”

10. Flowswitch (2), Opt. 285 TOP VIEW WITHOUT CONTROL PANEL

11. Sump Drain, Both Sides (2), ½" NPT


12. Fuel Line Leak Sensor
13. Pump Unit Inlet, 1" NPT
8

5 5

9 9
54.672”
10 10

13

0.625” 2”
3”
4 4 11 12
8” 10” 8” 3”
32”

SIDE VIEW FRONT VIEW

SKS-50 1 3”
84”
78”
1. Mounting Holes (4), ¾" 3 3
2. Pressure Relief Outlet, ¾" NPT Male 7

3. Motor (2)
2 2
4. Pump (2)
5. Ball Valve (4), Opt. 087 44”
5 6

6. Fuel Strainer (2), Opt. 060


7. Pump Inlet, 3" NPT
8. Pump Unit Outlet, 2" NPT 4 4

9. Flowswitch (2), Opt. 285


10. Check Valve (2), Opt. 070 2”
81”
5 6

11. Sump Drain, Both Sides (2), ½" NPT 1.5”


TOP VIEW WITHOUT CONTROL PANEL
12. Fuel Line Leak Sensor
13. Main Disconnect Switch, Opt. 260
8

5 5

13
9 9

54”±2” 10 10

8” 20” 8” 6” 11 12
48”

SIDE VIEW FRONT VIEW

Simplex Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 (24 Hr.) • Fax 217-483-1616 • www.simplexdirect.com