Pipes marked with a short red stripe in the diagrams must be connected to the device with a reducing joint.
15.9×28.6 15.9×28.6
BHFP22P100
38.0m 3.5m
22.2×41.3 6.4×12.7
KHRP26A73T +
KHRP26M73TP
IU:1-1
FXAQ32AVM4
2.0m 2.0m
22.2×38.1 9.5×15.9
KHRP26A73T +
KHRP26M73TP
IU:1-9
FXFQ63AV4
1.0m 1.5m
22.2×38.1 6.4×12.7
KHRP26A73T +
KHRP26M73TP
IU:1-2
FXAQ40AVM4
1.5m 1.5m
22.2×38.1 6.4×12.7
KHRP26A73T +
KHRP26M73TP
IU:1-3
FXAQ40AVM4
4.0m 3.0m
22.2×38.1 9.5×15.9
KHRP26A73T +
KHRP26M73TP
IU:1-10
FXFQ63AV4
3.0m 1.5m
19.1×31.8 6.4×12.7
KHRP26A72T
IU:1-4
FXAQ40AVM4
1.5m 1.5m
19.1×31.8 6.4×12.7
KHRP26A72T
IU:1-5
FXAQ40AVM4
2.0m 3.0m
19.1×31.8 9.5×15.9
KHRP26A72T
IU:1-11
FXFQ63AV4
5.0m 1.5m
19.1×31.8 6.4×12.7
KHRP26A72T
IU:1-6
FXAQ40AVM4
1.5m 1.5m
15.9×31.8 6.4×12.7
KHRP26A72T
IU:1-7
FXAQ40AVM4
2.0m 3.0m 2.5m
15.9×31.8 9.5×15.9 9.5×15.9
KHRP26A72T KHRP26A22T
IU:1-12
FXFQ63AV4
5.0m
9.5×15.9
IU:1-8
FXFQ80AV4
1.5m 2.0m
12.7×25.4 6.4×12.7
KHRP26A33T
IU:1-14
FXAQ25AVM4
1.5m 2.0m
12.7×25.4 6.4×12.7
KHRP26A33T
IU:1-15
FXMQ50PAV4
7.0m 5.0m
12.7×22.2 6.4×12.7
KHRP26A22T
IU:1-16
FXAQ40AVM4
1.5m 5.0m
12.7×19.1 9.5×15.9
KHRP26A22T
IU:1-13
FXFQ63AV4
4.0m 3.0m
12.7×19.1 6.4×12.7
KHRP26A22T
IU:1-17
FXAQ25AVM4
4.0m
6.4×12.7
IU:1-18
FXAQ25AVM4
The actual length (43.0m) from the first branch to IU:1-18 exceeds 40.0m. The intermediate pipes are sized up
The actual length (42.0m) from the first branch to IU:1-17 exceeds 40.0m. The intermediate pipes are sized up
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 22
4.2. Piping OU-2
OU-2
RXQ22AMY14
RXQ12AY14 RXQ10AY14
12.7×28.6 9.5×22.2
BHFP22P100
39.0m 2.5m
15.9×28.6 6.4×12.7
KHRP26A72T
IU:2-2
FXAQ50AVM4
2.0m 5.5m
15.9×28.6 6.4×12.7
KHRP26A72T
IU:2-1
FXAQ20AVM4
1.0m 10.5m
15.9×28.6 9.5×15.9
KHRP26A72T
IU:2-11
FXAQ63AVM4
3.5m 2.5m
12.7×28.6 6.4×12.7
KHRP26A72T
IU:2-3
FXAQ50AVM4
6.5m 2.5m
12.7×28.6 6.4×12.7
KHRP26A72T
IU:2-4
FXAQ50AVM4
1.5m 8.5m 6.5m
12.7×28.6 9.5×15.9 9.5×15.9
KHRP26A72T KHRP26A22T
IU:2-7
FXAQ63AVM4
3.5m
9.5×15.9
IU:2-8
FXAQ63AVM4
4.5m 2.5m
9.5×19.1 6.4×12.7
KHRP26A22T
IU:2-5
FXAQ50AVM4
8.0m 3.0m
9.5×15.9 6.4×12.7
KHRP26A22T
IU:2-6
FXAQ50AVM4
1.5m 3.0m
9.5×15.9 6.4×12.7
KHRP26A22T
IU:2-9
FXAQ40AVM4
5.0m
6.4×12.7
IU:2-10
FXAQ50AVM4
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 23
4.3. Piping OU-3
OU-3
RXQ26AMY14
RXQ14AY14 RXQ12AY14
12.7×28.6 12.7×28.6
BHFP22P100
32.0m 3.0m
19.1×34.9 9.5×15.9
KHRP26A73T +
KHRP26M73TP
IU:3-1
FXAQ63AVM4
1.5m 2.5m
19.1×31.8 6.4×12.7
KHRP26A72T
IU:3-2
FXAQ32AVM4
1.5m 3.0m
19.1×31.8 6.4×12.7
KHRP26A72T
IU:3-3
FXAQ32AVM4
7.5m 2.5m
19.1×31.8 6.4×12.7
KHRP26A72T
IU:3-5
FXAQ50AVM4
2.5m 10.5m
19.1×31.8 9.5×15.9
KHRP26A72T
IU:3-14
FXAQ63AVM4
2.5m 5.0m
19.1×31.8 6.4×12.7
KHRP26A72T
IU:3-4
FXAQ20AVM4
1.0m 2.0m
15.9×31.8 6.4×12.7
KHRP26A72T
IU:3-6
FXAQ50AVM4
6.0m 2.5m
15.9×31.8 6.4×12.7
KHRP26A72T
IU:3-7
FXAQ50AVM4
1.5m 8.5m 6.5m
15.9×31.8 9.5×15.9 9.5×15.9
KHRP26A72T KHRP26A22T
IU:3-10
FXAQ63AVM4
3.5m
9.5×15.9
IU:3-11
FXAQ63AVM4
4.5m 2.5m
12.7×22.2 6.4×12.7
KHRP26A22T
IU:3-8
FXAQ50AVM4
8.0m 3.0m
12.7×19.1 6.4×12.7
KHRP26A22T
IU:3-9
FXAQ50AVM4
1.5m 3.5m
12.7×19.1 6.4×12.7
KHRP26A22T
IU:3-12
FXAQ40AVM4
5.0m
6.4×12.7
IU:3-13
FXAQ50AVM4
The actual length (43.0m) from the first branch to IU:3-13 exceeds 40.0m. The intermediate pipes are sized up
The actual length (41.5m) from the first branch to IU:3-12 exceeds 40.0m. The intermediate pipes are sized up
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 24
4.4. Piping OU-4
OU-4
RXQ32AMY14
RXQ18AY14 RXQ14AY14
15.9×28.6 12.7×28.6
BHFP22P100
IU:4-4
FXMQ32PAV4
1.0m 4.5m
9.5×15.9 6.4×12.7
KHRP26A22T
IU:4-2
FXAQ20AVM4
4.0m
6.4×12.7
IU:4-3
FXAQ20AVM4
6.5m 2.0m
19.1×31.8 9.5×15.9
KHRP26A72T
IU:4-7
FXMQ80PAV4
21.5m 5.5m
19.1×31.8 6.4×12.7
KHRP26A72T
IU:4-12
FXAQ20AVM4
1.0m 5.0m
19.1×31.8 9.5×15.9
KHRP26A72T
IU:4-5
FXMQ125PAV4
2.5m 3.5m
15.9×31.8 9.5×15.9
KHRP26A72T
IU:4-6
FXMQ100PAV4
1.5m 2.5m
12.7×25.4 9.5×15.9
KHRP26A33T
IU:4-11
FXFQ80AV4
3.5m 2.0m
12.7×25.4 9.5×15.9
KHRP26A33T
IU:4-13
FXMQ80PAV4
1.5m 2.0m
12.7×19.1 6.4×12.7
KHRP26A22T
IU:4-10
FXMQ40PAV4
7.0m
9.5×15.9
IU:4-14
FXMQ80PAV4
The actual length (45.0m) from the first branch to IU:4-14 exceeds 40.0m. The intermediate pipes are sized up
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 25
4.5. Piping OU-OK1
OU-OK1
RXQ10AY14
32.0m
9.5×22.2
IU:4-8
FXMQ250PVM
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 26
4.6. Piping OU-OK2
OU-OK2
RXQ10AY14
65.0m
9.5×22.2
IU:4-9
FXMQ250PVM
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 27
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded
cable can be used if local regulation prescribes it)
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 28
5.2. Wiring OU-2
P1,P2
OU-2 BRC1E63
IU:2-2
RXQ22AMY14
FXAQ50AVM4
IN F1,F2 F1,F2
RXQ12AY14 L,N 0.7A 1ph
Q1,Q2 L1,L2,L3,N P1,P2
22.5A 3ph IU:2-1 BRC1E63
FXAQ20AVM4
RXQ10AY14 F1,F2
Q1,Q2 L1,L2,L3,N L,N 0.6A 1ph
21.2A 3ph P1,P2
IU:2-11 BRC1E63
FXAQ63AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:2-3 BRC1E63
FXAQ50AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:2-4 BRC1E63
FXAQ50AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:2-7 BRC1E63
FXAQ63AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:2-8 BRC1E63
FXAQ63AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:2-5 BRC1E63
FXAQ50AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:2-6 BRC1E63
FXAQ50AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:2-9 BRC1E63
FXAQ40AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:2-10 BRC1E63
FXAQ50AVM4
F1,F2
L,N 0.7A 1ph
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded
cable can be used if local regulation prescribes it)
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 29
5.3. Wiring OU-3
P1,P2
OU-3 BRC1E63
IU:3-1
RXQ26AMY14
FXAQ63AVM4
IN F1,F2 F1,F2
RXQ14AY14 L,N 0.7A 1ph
Q1,Q2 L1,L2,L3,N P1,P2
26.9A 3ph IU:3-2 BRC1E63
FXAQ32AVM4
RXQ12AY14 F1,F2
Q1,Q2 L1,L2,L3,N L,N 0.6A 1ph
22.5A 3ph P1,P2
IU:3-3 BRC1E63
FXAQ32AVM4
F1,F2
L,N 0.6A 1ph
P1,P2
IU:3-5 BRC1E63
FXAQ50AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:3-14 BRC1E63
FXAQ63AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:3-4 BRC1E63
FXAQ20AVM4
F1,F2
L,N 0.6A 1ph
P1,P2
IU:3-6 BRC1E63
FXAQ50AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:3-7 BRC1E63
FXAQ50AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:3-10 BRC1E63
FXAQ63AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:3-11 BRC1E63
FXAQ63AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:3-8 BRC1E63
FXAQ50AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:3-9 BRC1E63
FXAQ50AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:3-12 BRC1E63
FXAQ40AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
IU:3-13 BRC1E63
FXAQ50AVM4
F1,F2
L,N 0.7A 1ph
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded
cable can be used if local regulation prescribes it)
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 30
5.4. Wiring OU-4
P1,P2
OU-4 BRC1E63
IU:4-1
RXQ32AMY14
FXAQ20AVM4
IN F1,F2 F1,F2
RXQ18AY14 L,N 0.6A 1ph
Q1,Q2 L1,L2,L3,N P1,P2
30.2A 3ph IU:4-4 BRC1E63
FXMQ32PAV4
RXQ14AY14 F1,F2
Q1,Q2 L1,L2,L3,N L,N 0.6A 1ph
26.9A 3ph P1,P2
IU:4-2 BRC1E63
FXAQ20AVM4
F1,F2
L,N 0.6A 1ph
P1,P2
IU:4-3 BRC1E63
FXAQ20AVM4
F1,F2
L,N 0.6A 1ph
P1,P2
IU:4-7 BRC1E63
FXMQ80PAV4
F1,F2
L,N 2.3A 1ph
P1,P2
IU:4-12 BRC1E63
FXAQ20AVM4
F1,F2
L,N 0.6A 1ph
P1,P2
IU:4-5 BRC1E63
FXMQ125PAV4
F1,F2
L,N 3.4A 1ph
P1,P2
IU:4-6 BRC1E63
FXMQ100PAV4
F1,F2
L,N 2.9A 1ph
P1,P2
IU:4-11 BRC1E63
FXFQ80AV4
F1,F2
L,N 1A 1ph
P1,P2
IU:4-13 BRC1E63
FXMQ80PAV4
F1,F2
L,N 2.3A 1ph
P1,P2
IU:4-10 BRC1E63
FXMQ40PAV4
F1,F2
L,N 1.4A 1ph
P1,P2
IU:4-14 BRC1E63
FXMQ80PAV4
F1,F2
L,N 2.3A 1ph
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded
cable can be used if local regulation prescribes it)
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 31
5.5. Wiring OU-OK1
P1,P2
OU-OK1 IU:4-8 BRC1E63
RXQ10AY14 FXMQ250PVM
IN F1,F2 F1,F2
L1,L2,L3,N 21.2A 3ph L,N 9A 1ph
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded
cable can be used if local regulation prescribes it)
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 32
5.6. Wiring OU-OK2
P1,P2
OU-OK2 IU:4-9 BRC1E63
RXQ10AY14 FXMQ250PVM
IN F1,F2 F1,F2
L1,L2,L3,N 21.2A 3ph L,N 9A 1ph
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded
cable can be used if local regulation prescribes it)
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 33
6. Device Options
6.1. Outdoor Unit Options
Model Description Used by
BHFP22P100 Outdoor unit multi connection piping kit OU-4 [RXQ32AMY14] OU-3 [RXQ26AMY14] OU-2 [RXQ22AMY14]
OU-1 [RXQ36AMY14]
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 34