You are on page 1of 5

Produced on 7/30/2015 with Xpress Selection V7.0.1 - database DIL 11.1.

Project name KHO BAC VINH LONG


Reference 28/7/2015
Client name THE VINH
Revision R4

Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description
RXQ40TSY1 1 Cooling only VRV IV SPACE SAVING
RXQ60TNY1 2 Cooling only VRV IV STANDARD
FXFQ100LUV1 12 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ125LUV1 11 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ63LUV1 7 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ80LUV1 11 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXMQ140PVE 4 VRV M - Ceiling Mounted Duct
FXZQ25MVE 1 VRV Z - Ceiling Mounted Cassette(Compact Multi Flow)
FXZQ32MVE 2 VRV Z - Ceiling Mounted Cassette(Compact Multi Flow)
FXZQ50MVE 1 VRV Z - Ceiling Mounted Cassette(Compact Multi Flow)
KHRP26A22T 7 Refnet branch piping kit
KHRP26A33T 18 Refnet branch piping kit
KHRP26A72T 9 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 12 Refnet branch piping kit
BRC1E62 49 Wired Remote Controller (Navigation Remote Controller)
BYCP125K-W1 41 Decoration panel
BYFQ60B3W1 4 Decoration panel
BHFP22P100 1 Outdoor unit multi connection piping kit
BHFP22P151 2 Outdoor unit multi connection piping kit

2. ITM: 01 BO+KHUYE CH DAI: 01 BỘ


3. CASSETLE R410A, INVERTER: 03 BO

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

4.1. Piping Out 1


Out 1
RXQ60TNY1
RXQ20TY1 RXQ20TY1 RXQ20TY1

15.9×28.6 15.9×28.6 15.9×28.6


19.1x41.3
BHFP22P151

19.1×41.3 9.5×22.2 9.5×22.2


KHRP26A73T + KHRP26A33T KHRP26A33T
KHRP26M73TP

6.4×12.7 9.5×15.9 9.5×15.9

Ind 16 Ind 17 Ind 20


FXZQ32MVE FXFQ125LUV1 FXFQ125LUV1
19.1×41.3 9.5×15.9
KHRP26A73T + KHRP26A22T
KHRP26M73TP

6.4×12.7 6.4×12.7

Ind 18 Ind 19
FXZQ25MVE FXZQ32MVE
19.1×41.3 12.7×28.6 9.5×22.2
KHRP26A73T + KHRP26A72T KHRP26A33T
KHRP26M73TP

9.5×15.9 9.5×15.9

Ind 14 Ind 15
FXFQ100LUV1 FXFQ100LUV1
9.5×15.9
KHRP26A22T

9.5×15.9 9.5×15.9

Ind 12 Ind 13
FXFQ63LUV1 FXFQ80LUV1
19.1×41.3 9.5×19.1
KHRP26A73T + KHRP26A22T
KHRP26M73TP

9.5×15.9 9.5×15.9

Ind 10 Ind 11
FXFQ100LUV1 FXFQ80LUV1
19.1×34.9 9.5×22.2 9.5×22.2
KHRP26A73T + KHRP26A33T KHRP26A33T
KHRP26M73TP

9.5×15.9 9.5×15.9 9.5×15.9

Ind 7 Ind 8 Ind 9


FXFQ63LUV1 FXFQ80LUV1 FXFQ125LUV1
15.9×28.6 12.7×28.6 9.5×22.2 9.5×19.1
KHRP26A72T KHRP26A72T KHRP26A33T KHRP26A22T

9.5×15.9 9.5×15.9 9.5×15.9 9.5×15.9

Ind 3 Ind 4 Ind 5 Ind 6


FXFQ80LUV1 FXFQ100LUV1 FXFQ63LUV1 FXFQ100LUV1
9.5×22.2
KHRP26A33T

9.5×15.9 9.5×15.9

Ind 1 Ind 2
FXMQ140PVE FXMQ140PVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

4.2.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3
4.3. Piping Out 2
Out 2
RXQ60TNY1
RXQ20TY1 RXQ20TY1 RXQ20TY1

15.9×28.6 15.9×28.6 15.9×28.6


19.1x41.3
BHFP22P151

19.1×41.3 15.9×28.6 9.5×22.2 9.5×22.2 9.5×15.9


KHRP26A73T + KHRP26A72T KHRP26A33T KHRP26A33T KHRP26A22T
KHRP26M73TP

9.5×15.9 9.5×15.9 9.5×15.9 9.5×15.9

Ind 39 Ind 40 Ind 41 Ind 42


FXFQ63LUV1 FXFQ80LUV1 FXFQ63LUV1 FXFQ80LUV1
9.5×22.2
KHRP26A33T

9.5×15.9 9.5×15.9

Ind 37 Ind 38
FXFQ100LUV1 FXFQ100LUV1
19.1×41.3 19.1×34.9 15.9×28.6 12.7×28.6 12.7×28.6 9.5×22.2 9.5×22.2
KHRP26A73T + KHRP26A73T + KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A33T KHRP26A33T
KHRP26M73TP KHRP26M73TP

6.4×12.7 9.5×15.9 9.5×15.9 9.5×15.9 9.5×15.9 9.5×15.9

Ind 31 Ind 32 Ind 33 Ind 34 Ind 35 Ind 36


FXZQ50MVE FXFQ63LUV1 FXFQ80LUV1 FXFQ63LUV1 FXFQ80LUV1 FXFQ125LUV1
9.5×19.1
KHRP26A22T

9.5×15.9 9.5×15.9

Ind 29 Ind 30
FXFQ100LUV1 FXFQ80LUV1
19.1×34.9 9.5×22.2
KHRP26A73T + KHRP26A33T
KHRP26M73TP

9.5×15.9 9.5×15.9

Ind 27 Ind 28
FXFQ100LUV1 FXFQ100LUV1
15.9×28.6 9.5×22.2
KHRP26A72T KHRP26A33T

9.5×15.9 9.5×15.9

Ind 24 Ind 25
FXFQ100LUV1 FXFQ100LUV1
9.5×22.2
KHRP26A33T

9.5×15.9 9.5×15.9

Ind 22 Ind 23
FXMQ140PVE FXMQ140PVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

4.4.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4
4.5. Piping Out 3
Out 3
RXQ40TSY1
RXQ20TY1 RXQ20TY1

15.9×28.6 15.9×28.6

BHFP22P100

19.1×41.3 19.1×34.9 19.1×34.9 12.7×28.6 9.5×22.2 9.5×19.1


KHRP26A73T + KHRP26A73T + KHRP26A73T + KHRP26A72T KHRP26A33T KHRP26A22T
KHRP26M73TP KHRP26M73TP KHRP26M73TP

9.5×15.9 9.5×15.9 9.5×15.9 9.5×15.9

Ind 48 Ind 49 Ind 50 Ind 51


FXFQ125LUV1 FXFQ125LUV1 FXFQ80LUV1 FXFQ80LUV1
9.5×22.2
KHRP26A33T

9.5×15.9 9.5×15.9

Ind 46 Ind 47
FXFQ125LUV1 FXFQ125LUV1
9.5×22.2
KHRP26A33T

9.5×15.9 9.5×15.9 9.5×15.9

Ind 43 Ind 44 Ind 45


FXFQ125LUV1 FXFQ125LUV1 FXFQ125LUV1

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a