CAPACITY TR
CAPACITY AFTER DIVERSITY
1 WC Chiller capacity/each TR
Quantity Nos.
Chiller Power/each KW/TR
KW/TR WC CHILLER KW/TR
AC Chiller capacity/each TR
Quantity Nos.
Chiller Power/each KW/TR
KW/TR AC CHILLER KW/TR
Total chiller power KW
Total chiller TR TR
WC chiller cost each Rs.
AC chiller cost each Rs.
Total chiller cost Rs.
Operation cost per month Rs.
1 of 4
Chiller Plant Comparison
2 of 4
Chiller Plant Comparison
Assumptions:
No standby pump considered in the power calculations
AHU, piping and riser piping cost being common are not included
Electricity Rs. Per unit 6.50
Water Rs./ 10 KL 1200
Loading factor common for all seasons 0.5
No. of hours of operation/day 12 hours
No. of days of operation/month 26 days
Running Cost of Power = Kw x 0.5 x 12hrs/day x 26 days/month x rate/unit (Rs.6.50 per unit)
Kw x 0.5 Diversity x 12 hours/day x 26 day/s month x Rs. 6.50 Electrical cost per KWH = 1014
Constant 1014 Rs. Per KW/day
Cost of water = No. of litres/day x 0.5 x 26 days/month x rate/lit (Rs. 1200/10 KL)
No of litres/day x 0.5 diversity x 26 days a month x cost of water (Rs. 1200/10 KL) = 1.56
Constant 1.56 Rs. Per lit/day
ADVANTAGES
3 of 4
Chiller Plant Comparison
DISADVANTAGES
4 of 4