LOAD CALCULATIONS :
Inaccessible Live Load = 0.75 kN/m2 (for slope upto 10˚and below)
(except for maintenance)
For Slope of α (12) = 0.710 kN/m2
Say, = 0.750 kN/m2
WIND LOAD : As per IS 875 Part - III 2015,
( 21 m )
FRAME SECTION :
10.731
α = 12
( 12.915 m )
( 10.7 m )
( 21 m outer to outer )
Permeability of Building : Considering three sides closed & one side open,
2
Pz = 0.6 × Vz
Pd = Pz × Kd × Ka
Variation in design Wind speed & Pressure with height :
HEIGHT VZ PZ Pd ( kN/m2 )
K2 Kd
(m) ( m/s ) ( kN/m2 ) Column Rafter Purlin
upto 10 m 0.91 30.030 0.90 0.541 0.392 - 0.483
15 m 0.97 32.010 0.90 0.615 0.445 0.443 0.550
Wind load details, from cl. 7.3.1 - IS 875 Part - III 2015
F = C p × A × Pd
Cp = ( Cpe - Cpi )
External Pressure Coefficient for roof, from Table - 6, - IS 875 Part - III 2015
h = 10.70 = 0.5095 ≤½
w 21.00
Roof angle, α = 12 C
E G
D
Θ = 90°
Cp = ( Cpe - Cpi )
Cpi Θ EF GH EG FH
0.70 0° -1.740 -1.10 - -
0.70 90° - - -1.48 -1.30
-0.70 0° -0.34 0.30 - -
-0.70 90° - - -0.08 0.10
External Pressure Coefficient for wall, from Table - 5, - IS 875 Part - III 2015
h = 10.70 = 0.5095 ≤½
w 21.00
Θ A B C D
0° 0.70 -0.25 -0.60 -0.60
90° -0.50 -0.50 0.70 -0.10
Building with one open side or opening exceeding 20% of wall area may be assumed to be
subjected to internal positive pressure or suction similar to those of buildings with large
openings.
Internal pressure coefficients with respect to direction of wind (C pi values) is as per IS875
Part 3 Clause 7.3.2.2 fig.2
R2
Cp = ( Cpe - Cpi )
Cpi Θ A B C D
0.80 0° -0.10 -1.05 -1.40 -1.40
-0.50 90° 0.00 0.00 1.20 0.40
-0.40 180˚ 1.10 0.15 -0.20 -0.20
-0.50 270˚ 0.00 0.00 1.20 0.40
Case (ii). WL : 0° - C pi